LON System-M Pushbutton MTN881401
Contents
1. 5 Technical Data Power supply Power consumption including BCU max Conirols application module 2 8 Operation buttons Indicators application module LEDs next to the operation buttons Operation LED Site Conditions Operation temperature Protection class Connections Physical External Interface PEI Conformity EU Directive Version 10 07 09 1 LPUL 285 mW 6 2 mA 42V 25 mA 5V DC 42 8V supplied by the network To activate the application specific function Red ON state Green ready for operation and online 5 C 45 IP20 10 pole interface PEI 2004 108 EEC Subject to modifications Page 5 of 21 Schneider LON ARTEC pushbutton G Electric Application 880451SW12E 6 Application The application 880451 SW12E 880451SW12E_Schneider nxe has to be used for the pushbuttons with multi function is for System M pushbutton application units with LON Bus Coupling Unit to control LON devices via the LON network Thus light scenes can be enabled just as switch and dim commands for blinds and lamps can be transmitted The application contains the LonMark profiles Switch 3200 10x Scene Panel 3250 1x and Occupancy Sensor 1060 1x 6 1 System requirements For the configuration of the application a LNS compatible commissioning tool is needed All properties are used as User defined Configuration Property Types UCPT s by Direct Memory Access For use of the
2. controlled The network variable output value is switched on with every falling edge that follows a short pulse at the one input It is switched off with every falling edge at the other input The dimming level is raised with every long pulse at the one input It is lowered with every long pulse at the other input The fade starts as soon as the press time threshold has been exceeded Then the values defined in UCPTcmdHoldFirstEvent i resp UCPTcmdHoldSecondEvent i are transmitted consecutively until the input is opened again whereas the corresponding sett ing element contains the dim step value The SCPTminSendTime i parameter defines the minimum period of time between two consecutive dim commands The parameters have to be configured as follows UCPTcmdReleaseFirstEvent i SET_ON x x UCPTcmdReleaseSecondEvent i SET OFF x x UCPTcmdHoldFirstEvent i SET_UP 5 x UCPTcmdHoldSecondEvent i SET_DOWN 5 x All other UCP TcmdXXX i SET NO MESSAGE x x Sunblind Control by rocker switch For sunblind control the UCPTpressTimeThreshold i parameter defines a time that distinguishes between push and hold of the button The sunblind is raised completely with every rising edge at the one input It is lowered completely with every rising edge at the other input It can be stopped by a falling edge that follows a short pulse by releasing the button after a push For this purpos
3. is adjusted to UCPTcmdXXX i function as follows function SET ON SET UP SET DOWN SET STATE state 1 function SET OFF gt state 0 function SET NUL gt state 1 nvoSWswitch i value is adjusted to UCPTcmdXXX i function as follows function SET_ON value SCPTmaxOut i after restart resp nviSWswitchFb i value last value before switching off function SET OFF gt value 0 function SET UP SET DOWN value value H setting function SET NUL SET STATE gt value setting Version 10 07 09 Subject to modifications Page 6 of 21 Schneider LON ARTEC pushbutton G Electric Application 880451SW12E The Switch Object provides a memory function If it is switched on by a SET_ON command the nvoSWswitch i output adopts the last feedback value received One fold switch control One of the digital inputs initiates the first as well as the second switching event Therefore UCPTbuttonMapFirstEvent i as well as UCPTbuttonMapSecondEvent i have to be assigned to this input by setting the corresponding bit 1 Switching by push button If a push button is connected to the digital input ON and OFF commands shall be transmitted alternately with every rising edge e g a push at a push button For this purpose the parameters have to be configured as follows UCPTcmdPushFirstEvent i SET_ON x x UCPTcmdPushSecondEvent i SET_OFF x x All other UCPTcmdXXX
4. 00 rotation 359 98 360 00 Default Value function SET NO MESSAGE setting 0 rotation 0 Description This message is transmitted via nvoSWsetting i when a long pulse is detected when the UCPTpressTimeThreshold i is exceeded in the second event when the button is hold for the second time If SCPTminSendTime i gt O it defines a time by which the values configured here are transmitted consecutively via nvoSWsetting i for fades Then the setting element of this parameter is adapted by nvoSWswitch i where it is used as dim step value UCPTpressTimeThreshold i Press time threshold Type SNVT time sec Valid Range 0 0 64 0 s Default Value 1 0s Description Distinguishes between long and short pulse Is this time O the command of UCPTcmdReleaseLong i is always transmitted when the contacts have been opened SCPTminSendTime i Minimum send time Type SNVT time sec Valid Range 0 0 6553 5 s Default Value 0 2s Description Defines the minimum period of time between two consecutive transmissions of the current value Provides a way to tailor the transmission rate to reduce bus load during fades If the values defined in UCPTcmdHoldFirstEvent i resp UCPTcmdHoldSecondEvent i shall be transmitted consecutively via nvoSWsetting i resp nvoSWswitch i when UCPTpressTimeThreshold i has been exceeded this parameter has to be set at gt 0 Version 10 07 09 Subject to modification
5. E Configuration Properties UCPTbuttonFs1SceneCmd i Scene command assignment Type SNVT scene Valid Range function SC RECALL SC LEARN SC NUL scene number 0 255 Default Value function SC NUL scene number 0 Description Used to assign a scene command to every button UCPTsceneLearnDelay Scene learn delay Type SNYVT time sec Valid Range 0 0 6553 5 s Default Value 10 0s Description Defines a time threshold to distinguish between recalling RECALL and storing LEARN scenes The learn command nvoSPscene function SC LEARN is transmitted when this time threshold is exceeded by a long switch pulse Version 10 07 09 Subject to modifications Page 20 of 21 Schneider LON ARTEC pushbutton G Electric Application 880451SW12E 6 5 Occupancy Sensor LONMARK profile 1060 Occupancy Sensor 1060 nvoOSoccupancy i SNVT occupancy UCPTbuttonRslOccCmd i w sr Output Network Variables nvoOSoccupancy i Occupancy Output Type SNVT_occupancy Valid Range OC OCCUPIED OC_UNOCCUPIED OC BYPASS OC_STANDBY OC NUL Default Value OC NUL Description Output to propagate the occupancy state Configuration Properties UCPTbuttonRslOccCmd i Occupancy command assignment to a close contact Type UNVT_occupancy Valid Range OC_OCCUPIED OC_UNOCCUPIED OC_BYPASS OC_STANDBY OC_NO_MESSAGE OC_NUL Default Value OC NO MESSAGE Description Used to assign an oc
6. Schneider LON System M Pushbutton P Electric Article no MTN881401 MTN881451 MTN881501 MTN881601 MTN881651 User Manual LON System M Pushbutton Content a ass cht hesitate aii nhtn hates abd hadi nein edd een 1 1 DOSGNIPUON a mana Na BG ha AG 3 2 FUNCION u uuu E ati a umn E E 3 3 Mountain u E NAINA MANG BANA 3 4 RemaikS acarana ae aE a Ea A a a Sh tasqa 4 5 Technical Dalai manahan ALAN 5 6 Applicatiof uuu AGA nA NAA a baa 6 6 1 System TEQUIFEMEMIS si aNG NINANG NAN aai aia iaaa 6 6 2 Node Object LONMARK profile 0 nanas 11 6 3 Switch Object LONMARK profile 3200 aaa 13 6 4 Scene Panel Object LONMARK profile 3250 l aaa 19 6 5 Occupancy Sensor LONMARK profile 1060 c ccsccesesssessesesessesessensens 21 Version 10 07 09 Subject to modifications Page 1 of 21 LON System M Pushbutton Schneider Article no MTN881401 MTN881451 MTN881501 MTN881601 MTN881651 Pushbutton 1 gang Pushbutton 4 gang MF Pushbutton 2 gang Pushbutton 4 gang Pushbutton 4 gang MF IR LON System M Pushbutton 1 gang MTN881401 polar white glossy Pushbutton 2 gang MTN881451 polar white glossy Pushbutton 4 gang MTN881501 polar white glossy Pushbutton 4 gang MF MTN881601 polar white glossy multi function Pushbutton 4 gang MF IR MTN881651 polar white glossy multi function IR receiver Version 10 07 09 Subject to modifications S
7. chneider LON System M Pushbutton Electric Article no MTN881401 MTN881451 MTN881501 MTN881601 MTN881651 1 Description Application module for LON network in System M Design available as 1 2 4 gang pushbutton With 2 4 or 8 pushbuttons for individually assigned functions Pushbutton 1 2 4 gang each have one status LED per pair of buttons Pushbutton 4 gang MF and pushbutton 4 gang MF IR each have one status LED per buttons The application module possesses one operating LED Software application according to LonMark profile Switch 3200 Scene Panel 3250 and Occupancy Sensor 1060 for light sunblind or scene and occupancy control 2 Function Via the pushbuttons the application specific functions can be executed There are applications available for lighting blind and scene control N The operating LED can be switched off via a configuration parameter The buttons can be dedicated individually to ten function objects switch Via the Universal Plug in there is alternatively the possibility to assign the button functions freely to any object There is among other things the possibility to configure specific functions according to the push or loose of the button also in combination with the pressing time Furthermore it is possible to assign different functions to the Status LEDs 3 Mounting The application module is plugged onto the LON BCU and completed with a frame The LON BCU and the frame have t
8. cupancy command to every button Version 10 07 09 Subject to modifications Page 21 of 21
9. e the parameters have to be configured as follows UCPTcmdPushFirstEvent i SET_UP 100 x UCPTcmdPushSecondEvent i SET DOWN 100 x UCPTcmdReleaseFirstEvent i SET_STOP x x UCPTcmdReleaseSecondEvent i SET_STOP x x All other UCP TcmdXXX i SET NO MESSAGE x x The required drive commands may vary according to the used motor control unit Version 10 07 09 Subject to modifications Page 8 of 21 Schneider LON ARTEC pushbutton G Electric Application 880451SW12E Scene Panel Object The UCPTbuttonFsl1SceneCmd i parameter assigns a scene number to a pushbutton The messages transmitted by nvoSPscene can be configured individually for every input by use of these configuration properties Recalling scenes Caused by a short switch pulse generally initiated by a short push on a make contact element a recall command nvoSPscene function SC_RECALL and the scene number of the particular input nvoSPscene scene_number UCPTbuttonFs1SceneCmd i are transmitted via the nvoSPscene output Thus the scene controller operates the corresponding scene settings A scene number zero is not transmitted Storing scenes Caused by a long switch pulse which exceeds the time threshold defined in the UCPTsceneLearnDelay property alearn command nvoSPscene function SC_LEARN and the scene number of the particular input nvoSPscene scene_number UCPTbuttonSslSceneCmd i are transmitted Thus t
10. he current scene settings are stored in the controller memory under the given scene number Occupancy Sensor All digital inputs can also be used as presence input The telegrams to be send at the nvoOSoccupancy can be configured in the parameters UCPTbuttonRslOccCmd i individually for every input Button and LED assignments for different applications The assignments of buttons B and LEDs L if available to the several software objects are different depending on the manufacturer They could be configured for individual requirements with the parameters UCPTbuttonMapFirstEvent i UCPTbuttonMapSecondEvent i and UCPTledMap i The indices bitx of the parameters correspond to the indices of the following patterns We advise to configure the application with the available LNS Plug Ins Example The explanation shows how to configure a LON ARTEC Pushbutton 1 gang to set the buttons to control the first software object with the index 0 Default 1 gang B L B 6 lo n UCPTbuttonMapFirstEvent 0 bit0 1 all other bitx 0 UCPTbuttonMapSecondEvent 0 bit1 1 allother bitx 0 UCPTbuttonMapFirstEvent 6 bit6 1 all other bitx 0 UCPTbuttonMapSecondEvent 6 bit7 1 all other bitx 0 Version 10 07 09 Subject to modifications Page 9 of 21 Schneider LON ARTEC pushbutton G Electric Application 880451SW12E With the default setting hardware conditioned the first event on the left button is corresp
11. i SET NO MESSAGE x x If the output network variable value shall be lowered to a value different from zero this value has to be defined in UCPTcmdPushSecondEvent i setting in combination with function SET STATE If the output network variable value shall be switched with every falling edge e g a push at a break contact element values have to be defined in UCPTcmdReleaseFirstEvent i and UCPTcmdReleaseSecondEvent i all other UCPTcmdXXX i are set at SET NO MESSAGE x x Switching Dimming by digital input push button If a push button is used for switching and dimming the UCPTpressTimeThreshold i parameter defines a time that distinguishes between push and hold of the button ON and OFF commands are transmitted alternately with every falling edge that follows a short pulse when the button is released after a push With every long pulse hold of the button the dimming level is raised lowered alternately The fade starts as soon as the press time threshold has been exceeded The values defined in UCPTcmdHoldFirstEvent i resp UCPTcmdHoldSecondEvent i are transmitted consecutively until the input is opened again whereas the corresponding sett ing element contains the dim step value The parameters have to be configured as follows UCPTcmdReleaseFirstEvent i SET_ON x x UCPTcmdReleaseSecondEvent i SET OFF x x UCPTcmdHoldFirstEvent i SET UP 5 x UCPTcmdHoldSecondE
12. lication 880451SW12E 64 Scene Panel Object LONMARK profile 3250 Scene Panel 3250 nviSPsceneFb nvoSPscene SNVT_scene SNVT_scene UCPTbuttonFsiSceneCmd i UCPTSceneLearnDelay ry Input Network Variables nviSPsceneFb Scene feedback input Type SNVT_scene Valid Range function SC_RECALL SC_LEARN SC_NUL scene number 0 255 Default Value function SC NUL scene number 0 undefined Description Provides the feedback from other scene panels generally without any effect Output Network Variables nvoSPscene Scene output Type SNVT scene Valid Range function SC RECALL SC LEARN SC NUL scene number 0 255 Default Value function SC NUL scene number 255 Description Used to control a scene controller Caused by a short switch pulse generally initiated by a short push on a make contact element this output transmits the particular scene number nvoSPscene scene_number UCPTbuttonFslSceneCmd i and recalls all corresponding scene settings by nvoSPscene function SC RECALL When the time threshold defined in the UCPTsceneLearnDelay parameter is exceeded by a long pulse a learn command nvoSPscene function SC_LEARN is transmitted so that all current scene settings are stored in the controller memory under to the given scene number Version 10 07 09 Subject to modifications Page 19 of 21 Schneider LON ARTEC pushbutton G Electric Application 880451SW12
13. n module UCPTdefaultPowerLedState Type Valid Range Default Value Description Version 10 07 09 SNVT switch value 0 100 State 0 1 On state 1 and value gt 0 Off state 0 and value any or state 1 and value 0 value 100 state 1 Power LED state after Reset or Initialisation Subject to modifications Page 12 of 21 LON ARTEC pushbutton Application 880451SW12E 63 Switch Object LONMARK profile 3200 Switch 3200 nvoSWswitch i SNVT_switch nviSWswitchFb i nvoSWsetting i SNVT_switch SNVT_setting UCPTbuttonMapFirstEvent i UCPTcmdPushFirstEvent i UCPTcmdReleaseFirstEvent i UCPTcmdhHoldFirstEvent i UCPTcmdReleaseLong i UCPTbuttonMapSecondEvent i UCPTcmdPushSecondEvent i UCPTcmdReleaseSecondEvent i UCPTcmdHoldSecondEvent i UCPTpressTimeThreshold i SCPTminSendTime i SCPTmaxSendTimel i SCPTmaxOut i UCPTminOut i UCPTledMapli ww Input Network Variables nviSWswitchFb i Switch feedback input Type SNVT_switch Schneider Off state O and value x or state 1 and value 0 Valid Range value O 10096 state 0 1 On State 1 and value gt 0 Default Value value 0 state 0 Description Provides the feedback from other devices to realise two way circuits Also used to adapt the current dimming level value of the actuator for dimming Output Network Variables nvoSWswitch i Switch output T
14. o be ordered separately The LON BCU represents the mechanical electrical and data technical connection between a LON TP LP network and the application module To prevent the connector of the application module from spoiling the application module has to be stuck upright onto the BCU Version 10 07 09 Subject to modifications Page 3 of 21 Schneider LON System M Pushbutton P Electric Article no MTN881401 MTN881451 MTN881501 MTN881601 MTN881651 4 Remarks Installation and assembly of electrical devices may take place only by an electrical specialist When planning and installing an electrical system the relevant standards guidelines and regulations of the respective country are to be considered Beyond that the device specifications are to be kept For project engineering assembly and line up detailed expertise of the LON technology is presupposed The function of the device is software dependent Only application programs may be loaded which are approved for this device The system integrator has to carry ensuring that the loaded application program and the configured parameters in it correspond with the outside wiring of the device This applies in particular if for different use several application programs for a device are available Version 10 07 09 Subject to modifications Page 4 of 21 Schneider LON System M Pushbutton P Electric Article no MTN881401 MTN881451 MTN881501 MTN881601 MTN881651
15. onding to the seventh software object with index 6 the second event of the software object 0 is corresponding to the right button This means that a key press on the left button would generate a telegram at the software object 6 and a key press on the right button would generate a telegram at the software object 0 Configuration to use both buttons with the software object 0 1 gang B L B 6 lo n UCPTbuttonMapFirstEvent 0 bit6 1 all other bitx 0 UCPTbuttonMapSecondEvent 0 bit1 1 all other bitx 0 UCPTbuttonMapFirstEvent 6 all bitx 0 UCPTbuttonMapSecondEvent 6 all bitx 0 After this configuration is done both buttons are configured to correspond to the software object 0 and the software object 6 is deactivated Similarly depending on the used application a configuration is needed to bring the buttons into a continuous order The default configuration of all supported applications is listed on the following pages Assignment of the buttons bit wise LON System M 1 gang 2 gang 4 gang MF and MF IR B L B B L B B 16 tot 7 oy 2 0 5 O 6 Version 10 07 09 Subject to modifications Page 10 of 21 LON ARTEC pushbutton Schneider Application 880451SW12E 62 Node Object LONMARK profile 0 Node Object 0 nviRequest SNVT_obj_request nvoStatus SNVT_obj_status nviPowerLed SNVT_switch UCPTapplicationUnit UCPTdefaultPowerLedState nvoVersion SNVT_coun
16. s Page 17 of 21 Schneider LON ARTEC pushbutton G Electric Application 880451SW12E Configuration Properties SCPTmaxSendTime i Maximum send time Type Valid Range Default Value Description SNVT time sec 0 6 553 s 0 disabled Defines the maximum period of time between consecutive transmissions of the current value If this value gt O the current values of nvoSWswitch i and nvoSWsetting i are transmitted automatically consecutively when this time expires SCPTmaxOut i Type Valid Range Default Value Description Maximum output value SNVT_lev_cont 0 100 100 Determines the maximum value limit of nvoSWswitch i value for when it is switched on or the dimming level is raised via nvoSWswitch i and nvoSWsetting i UCPTminOut i Type Valid Range Default Value Minimum Output Value SNVT lev cont 0 100 Yo 5 Description Determines the minimum value limit of nvoSWswitch i value for when the dimming level is lowered via nvoSWswitch i and nvoSWsetting i When it is switched off 0 0 is always propagated independently of the value defined in this parameter UCPTledMap i LED map Type SNVT state Valid Range bit0 bit n with n lt 15 0 1 Default Value all bits 0 Description Version 10 07 09 This parameter assigns the LEDs to the software objects Subject to modifications Page 18 of 21 Schneider LON ARTEC pushbutton G Electric App
17. s to the input at 1 The bit0 to bit n of this parameter are dedicated to the digital inputs UCPTcmdPushSecondEvent i Command push second event Type UNVT_setting Valid Range function SET OFF SET ON SET DOWN SET UP SET STOP SET STATE SET NO MESSAGE SET NUL setting O 100 Yo rotation 359 98 360 00 Default Value function SET OFF 0 0 0 00 setting 0 rotation 0 Description This command is transmitted via nvoSWsetting i with every rising edge of the second switching event e g second push at a make contact element UCPTcmdReleaseSecondEvent i Command release second event Type UNVT_setting Valid Range function SET OFF SET ON SET DOWN SET UP SET STOP SET STATE SET NO MESSAGE SET NUL setting O 100 Y rotation 359 98 360 00 Default Value function SET NO MESSAGE setting 0 rotation 0 Description This message is transmitted via nvoSWsetting i with every falling edge that occurs in the second switching event before the UCPTpressTimeThreshold i has been exceeded when the button is released after the second push Version 10 07 09 Subject to modifications Page 16 of 21 Schneider LON ARTEC pushbutton G Electric Application 880451SW12E Configuration Properties UCPTcmdHoldSecondEvent i Command hold second event Type UNVT_setting Valid Range function SET OFF SET ON SET DOWN SET UP SET STOP SET STATE SET NO MESSAGE SET NUL setting 0 1
18. se is detected when the UCPTpressTimeThreshold i is exceeded in the first event when the button is hold for the first time If SCPTminSendTime i 5 0 it defines a time by which the values configured here are transmitted consecutively via nvoSWsetting i for fades Then the setting element of this parameter is adapted by nvoSWswitch i where it is used as dim step value UCPTcmdReleaseLong i Command release long Type Valid Range Default Value Description Version 10 07 09 UNVT_setting function SET OFF SET ON SET DOWN SET UP SET STOP SET STATE SET NO MESSAGE SET NUL setting O 100 Yo rotation 359 98 360 00 function SET NO MESSAGE setting 0 rotation 0 This message is transmitted via nvoSWsetting i with every falling edge that occurs when the UCPTpressTimeThreshold i has been exceeded when the button is released after hold The values defined here affect the first as well as the second switching event For interpretation at nvoSWswitch i see functional description Subject to modifications Page 15 of 21 Schneider LON ARTEC pushbutton G Electric Application 880451SW12E Configuration Properties UCPTbuttonMapSecondEvent i Button map second event Type SNVT_state Valid Range bit0 bit n with n lt 15 0 1 Default Value all bits 0 Description This parameter defines which hardware input initiates the second switching event by setting the bit which correspond
19. se properties the Device Resource Files have to be installed before a device template is created This application was generated especially for the use with an LNS Version 3 0 or higher Function Switch Object Configuration of the Switch Object Push Button Sensor The Switch Object can be configured in a very flexible way to provide the user the opportunity to meet all requirements of his project By use of the UCPTcmdXXX i parameters messages can be assigned arbitrarily to the outputs nvoSWswitch i and nvoSWsetting i for every switching event By default the Switch Object is configured for one fold switch control Therefore the names FirstEvent and SecondEvent signify the alternating switching events at the digital input Assigning the switching events to the digital inputs To assign the switching events to the digital inputs the parameters UCPTbuttonMapFirstEvent i and UCPTbuttonMapSecondEventfi are used During every switching event up to four messages can be generated The commands the messages contain can be defined individually If a message shall not be transmitted the function element of the corresponding UCPTcmdXXX i parameter has to be set at SET NO MESSAGE Interpretation of the function element of UCPTcmdXXX at nvoSWswitch i The parameters UCPTcmdXXX i specify the output value of nvoSWsetting i The nvoSWswitch i output is adjusted according to the following scheme nvoSWswitch i state
20. setting Valid Range function SET OFF SET ON SET DOWN SET UP SET STOP SET STATE SET NO MESSAGE SET NUL setting 0 100 rotation 359 98 360 00 Default Value function SET_ON setting 100 rotation 0 Description This command is transmitted via nvoSWsetting i with every rising edge of the first switching event e g first push at a make contact element Version 10 07 09 Subject to modifications Page 14 of 21 Schneider LON ARTEC pushbutton Application 880451SW12E Configuration Properties UCPTcmdReleaseFirstEvent i Command Release First Event Type Valid Range Default Value Description UNVT setting function SET OFF SET ON SET DOWN SET UP SET STOP SET STATE SET NO MESSAGE SET NUL setting 0 100 rotation 359 98 360 00 function SET NO MESSAGE setting 0 rotation 0 This message is transmitted via nvoSWsetting i with every falling edge that occurs in the first switching event before the UCPTpressTimeThreshold has been exceeded when the button is released after the first push UCPTcmdHoldFirstEvent i Command hold first event Type Valid Range Default Value Description UNVT_setting function SET OFF SET ON SET DOWN SET UP SET STOP SET STATE SET NO MESSAGE SET NUL setting 0 100 rotation 359 98 360 00 function SET NO MESSAGE setting 0 rotation 0 This message is transmitted via nvoSWsetting i when a long pul
21. t nvo00FileDir SNVT address vi v Input Network Variables nviRequest Type Valid Range Default Value SNVT_obj request Valid Object ID RQ_NORMAL RQ_UPDATE_STATUS RQ_REPORT_MASK RQ_NORMAL P Electric Description Input which is used to initiate status messages from the node nviPowerLed Type SNVT_switch Valid Range value 0O 100 State 0 1 Default Value Description On state 1 and value gt O Off state 0 and value any or state 1 and value 0 value 100 state 1 Input to control the Power LED of the device Output Network Variables nvoStatus Type Valid Range Default Value Description Version 10 07 09 SNVT_obj_status The supported Status Bits are report mask Invalid id Invalid request All bits 0 Is sent when an update occurs in nviRequest Subject to modifications Page 11 of 21 LON ARTEC pushbutton Schneider Application 880451SW12E Output Network Variables nvoVersion Type Valid Range Default Value SNVT_count 0 65 535 Schneider 10 P Electric Description Specifies the detected application module nvo00FileDir Type SNVT address Valid Range 16 384 64 767 Default Value Description Not defined For internal function only Configuration Properties UCPTapplicationUnit Type UNVT u8 Valid Range 0 255 Default Value Description 0 Specifies the used applicatio
22. vent i SET_DOWN 5 x All other UCP TcmdXXX i SET NO MESSAGE x x Two fold switch control One of the digital inputs initiates the first switching event The other input initiates the second Both inputs cause always the same command Therefore the UCPTbuttonMapFirstEvent i parameter has to be assigned to the one input UCPTbuttonMapSecondEvent i to the other by setting the bit corresponding to the chosen input 1 Version 10 07 09 Subject to modifications Page 7 of 21 Schneider LON ARTEC pushbutton G Electric Application 880451SW12E Switching by rocker switch If a rocker switch is connected to two digital inputs ON commands shall be transmitted with every rising edge at the one input and OFF commands shall be transmitted with every rising edge at the other input For this purpose the parameters have to be configured as follows UCPTcmdPushFirstEvent i SET_ON x x UCPTcmdPushSecondEvent i SET_OFF x x All other UCPTcmAXXX i SET NO MESSAGE x x If the network variable output value shall be switched with every falling edge e g push at a break contact element values have to be defined in UCPTcmdReleaseFirstEvent i and UCPTcmdReleaseSecondEvent i all other UCPTcmdXXX i are set at SET NO MESSAGE x x Switching Dimming by rocker switch The UCPTpressTimeThreshold i parameter defines a time that distinguishes between push and hold of the button when fades are
23. ype SNVT_switch Valid Range value O 10096 State 1 0 1 Off state O and value x or state 1 and value 0 On state 1 and value gt O Default Value value 0 state 0 Description This output variable is used to control switching and dimming actuators Its function is specified by the configuration properties UCPTbutt onMapXXX and UCPTcmdXxXx Version 10 07 09 Subject to modifications Page 13 of 21 Schneider LON ARTEC pushbutton G Electric Application 880451SW12E Output Network Variables nvoSWsetting i Setting Output Type SNVT_setting Valid Range function SET OFF SET ON SET DOWN SET UP SET STOP SET STATE SET NUL setting 0 100 rotation 359 98 360 00 Default Value function SET NUL setting 0 rotation 0 Description This output variable is used to control controllers sunblind and dimming actuators Its function is specified by the configuration properties UCPTbuttonMapxxx and UCPTcmdXXx Configuration Properties UCPTbuttonMapFirstEvent i Button Map First Event Type SNVT state Valid Range bit0 bit n with n lt 15 0 1 Default Value all bits 0 Description This parameter defines which hardware input initiates the first switching event by setting the bit which corresponds to the input at 1 The bit0 to bit n of this parameter are dedicated to the digital inputs UCPTcmdPushFirstEvent i Command Push First Event Type UNVT_