V3.30 Release 3 Modbus Gateway User Manual
Contents
1. Reference Exceptions Read Memory Type Register tt of Registers Data Type Units zj R W Configuration zl Scaling MV Offset z Register Address HYAC Iv Access LI Lighting m The Data View on the Setup tab lists all of the translated information from the Modbus device Clicking on one of the entries will display additional information below the Data View Name The Name of the BACnet object that is linked to the Modbus register for this entry elta CO NT ROLL S Modbus Gateway User Manual Edition 2 1 Page 21 of 38 Page 22 of 38 Reference The object reference of the associated BACnet object Only AV BV and MV object references are supported Exceptions A read only field that shows any exception codes returned from the Modbus device for that entry Exception codes are error codes returned from a Modbus slave device in response to a request from the Master device Refer to Exception Responses in Appendix C for more information Read When the associated checkbox is checked this indicates that the value is being read from the Modbus device into the associated BACnet object Unchecked indicates the value is being written to the Modbus device This field is read only in the dataview To change this value you must highlight the desired entry and use the R W Configuration drop down box located below the dataview Memory Type Memory Type determines where the data
2. However with this many entries it will take substantial time for the DSM RTR MOD30 to read all of the values from all the Modbus slaves This has been estimated to take 13 minutes So clearly control of these slave devices will be impossible since new command signals could only be sent once every 13 minutes However if these 30 slaves were power meters then this might be perfectly acceptable If however VFDs were to be controlled via Modbus start stop and speed then a cautious approach is advised 30 VFDs that each have 10 registers total of 300 registers would require about 75 seconds to update Pressure control either liquid or air will be nearly impossible at this update interval Even with a minimum of 3 registers per VFD start stop speed control speed status total of 90 registers it would take about 22 seconds to update all the VFDs This might be acceptable for air pressure control but not for liquid pressure control Unlike previous firmware versions it is now possible to write to however many Modbus registers is required There is no arbitrary limit as there had been in the past The GWT object is used to transfer values between Modbus registers and the associated BACnet objects Refer to documentation that came with the Modbus device s for information on the registers For each Modbus device a GWT object must be created with an instance number equal to the network address of the Modbus device Modbus Gateway
3. Cancel Apply 2 This field displays the total number of Modbus packets sent from the Delta Controller since the last controller reset The value of this number is not very important but it should be continuously incrementing If the Total Sent is not incrementing then it means that no packets are being sent ADelta CONTROL S Modbus Gateway User Manual Edition 2 1 Appendices Total Received This field displays the total number of packets received from the Modbus slave s since the last controller reset The value of this field should be incrementing along with the Total Sent field If the Total Received is not incrementing along with the Total Sent field then it means that the Delta Controller is sending requests but the Modbus slaves are not responding Send Failures This field displays the total number of sent packets that failed to receive a response since the last controller reset Invalid Received This field displays the total number of invalid packets received since the last controller reset Invalid packets are those that contain an incorrect cyclic redundancy code CRC A CRC is a number derived from and transmitted with a block of data in order to detect corruption By recalculating the CRC and comparing it to the value originally transmitted the receiver can detect some types of transmission errors Protocol Errors This field displays the total number of exception responses returned since the last co
4. function allows reading of multiple register values in a single query Delta only supports reading a single register per query message with this function The following example shows the packets generated when requesting to read Input Status register 10197 from a Modbus slave with an address of 25 Tx Packet Query Field Name Slave Address Function Starting Address Hi Byte Starting Address Lo Byte of Points Hi Byte of Points Lo Byte Error Check CRC The normal response if the queried Input Status register was in the off state would be Rx Packet Response Field Name Data Byte Count Data Error Check CRC In the Data byte the information on the Input Status state is in the least significant bit LSB A value of 1 On 0 Off and the remaining bits in the data byte are padded with zeros Modbus Gateway User Manual Edition 2 1 Page 31 of 38 Function 03 Read Holding Registers This function is used to read the contents of 1 or more 16 bit Holding Registers In a Read Holding Register Query message the starting register address and number of registers to be read are specified df Note While this function allows reading of multiple register values in a single query Delta only supports reading of up to 2 registers in a single query depending on the data type The following example shows the packets generated when requesting to read Holding registers 40108
5. particular application s For example a site may have separate operators for the HVAC and Access applications It is possible for each operator to only see the objects related to their application Refer to Chapter 7 Security in the ORCAview Technical Reference Manual for more information on how to set up and administer Object Application Restrictions When a checkbox is checked an indicator icon appears at the top of the dialog The three application domains are o o Application n HVAC Red Access Blue NNN Lighting Green Description The description tab may contain a string of characters of up to 2000 characters in length The character string is limited to any printable character Page 24 of 38 Modbus Gateway User Manual Edition 2 1 Appendices Appendix C Modbus Protocol Implementation The following sections give general information about the Modbus protocol and specifics on what portions of the protocol Delta has implemented in its Modbus Gateway controllers Protocol Modbus RTU The Modbus ASCII protocol is not supported by this Gateway Byte format 8N1 8 data bits no parity and 1 stop bit with CRC error checking Modbus devices that require a Byte format with even or odd parity and 2 stop bits are not supported Connection Speeds Connection speeds of 2400 4800 9600 19200 and 38400 baud are supported Functions The following Modbus functions are supported Refer to sectio
6. registers can be written to or read from Input Status Registers 1x References Each Input Status register is a 1 bit piece of data that typically represents the Boolean ON OFF status of an input or internal variable These registers are read only Input Registers 3x References Each Input register is a 16 bit piece of data one or more of which typically represent the analog status of an input or internal variable There are several different formats in which the data may be stored These different data formats and the number of registers each takes is covered in the Data Types section of this appendix These registers are read only Holding Registers 4x References Each Holding register is a 16 bit piece of data one or more of which typically represent the analog state of an output or internal variable There are several different formats in which the data may be stored These different data formats and the number of registers each takes is covered in the Data Types section of this appendix These registers can be written to or read from Page 26 of 38 Modbus Gateway User Manual Edition 2 1 Appendices Data Types The data values stored in Modbus registers can be in several formats You need to know in what format the information is stored in order to be able to correctly configure the GWT object to read and or write that value This section details the different data formats supported by the Delta Modbus Gateway B
7. that may appear in this document or any damages and or losses resulting from the use of the product Note that Delta software programs described in this manual are copyrighted material and when you purchase any of the software programs you are granted a limited license to use the software as described in this and other manuals BACspec BACstat Delta Controls ORCAview and Virtual Stat are trademarks of Delta Controls Inc Windows is a registered trademark of Microsoft Corporation Adobe and Acrobat are registered trademarks of Adobe Systems Incorporated BACnet is a registered tradmark of the American Society of Heating Refrigeration and Air Conditioning Engineers Inc ASHRAE BTL is a registered trademark of the BMA Modbus is a trademark of Schneider Automation All other trademarks are the property of their respective owners Page 2 of 38 Modbus Gateway User Manual Edition 2 1 Table Of Contents Table Of Contents ABLE OF CONTENTS 3 SING THIS MANUAL 4 ORGANIZATION OF THIS DOCUMENT OTHER RELEVANT DOCUMENTS NTRODUCTION IMPORTANT INFORMATION AVAILABLE MODBUS PRODUCTS ONNECTING TO THE MODBUS DEVICE 7 ONFIGURING THE MODBUS GATEWAY 9 DOCUMENT CONTROL 38 Alta Modbus Gateway User Manual Edition 2 1 Page 3 of 38 Using this Manual Page 4 of 38 This manual is designed to inform the user of the specific features unique to Delta s Modbus Gateway controllers Users should have previous training on
8. 40109 from a Modbus slave with an address of 5 Tx Packet Query Field Name Slave Address Function Starting Address Hi Byte Starting Address Lo Byte of Points Hi Byte of Points Lo Byte Error Check CRC The normal response if holding registers 108 and 109 contained a 32 bit unsigned integer value of 169 824 461 would be Rx Packet Response Field Name Example Hex Slave Address 05 Function 03 Data Byte Count 04 Data Byte Hi Register 40108 0A Data Byte Lo Register 40108 1F Data Byte Hi Register 40109 50 Data Byte Lo Register 40109 CD Error Check CRC Page 32 of 38 Modbus Gateway User Manual Edition 2 1 Appendices Function 04 Read Input Registers This function is used to read the contents of 1 or more 16 bit Input Registers In a Read Input Register Query message the starting register address and number of registers to be read are specified df Note While this function allows reading of multiple register values in a single query Delta only supports reading of up to 2 registers in a single query depending on the data type The following example shows the packets generated when requesting to read Input register 30108 from a Modbus slave with an address of 5 Tx Packet Query Field Name Slave Address Function Starting Address Hi Byte Starting Address Lo Byte o
9. Delta O N T R O L S Modbus Gateway User Manual 3 30 Release 3 Firmware Copyright Delta Controls Inc All rights reserved Document Title Modbus Gateway User Manual Document Number Not required released as PDF file Current Revision Edition 2 1 Date of current revision October 5 2005 No part of this manual may be reproduced transmitted transcribed stored in a retrieval system or translated into any language natural or computer in any form or by any means without the prior written permission of Delta Controls Inc Limited permission is granted to reproduce documents released in Adobe Portable Document Format PDF electronic format in paper format Documents released in PDF electronic format may be printed by end users for their own use using a printer such as an inkjet or laser device Authorized distributors of Delta Controls Inc products Delta Partners may print PDF documents for their own internal use or for use by their customers Authorized Delta Partners may produce copies of released PDF documents with the prior written permission of Delta Controls Inc Information in this document is subject to change without notice and does not represent a commitment to past versions of this document on the part of Delta Controls Inc Delta Controls Inc may make improvements and or changes to this manual the associated software or associated hardware at any time Delta Controls Inc assumes no responsibility for any errors
10. Delta Controls products Specifically the user will need to know how to use ORCAview to connect to a controller load and save databases open and create objects in navigator and enter data using object dialogs Organization of this Document This document explains how to configure a Modbus Gateway Special Interface controller to communicate with one or more Modbus slave devices using Delta s ORCAview Operator Workstation software package The document describes e Software Communications setup e Linking Modbus Registers to BACnet Objects e Appendices Troubleshooting GW amp GWT Object Reference Modbus Protocol Implementation Other Relevant Documents This document only contains part of the information required to correctly install and program a Modbus Gateway Special interface controller to communicate with one or more Modbus devices Refer to the documents listed below for supplementary information e Installation Guides For installation instructions refer to the install guide for the standard version of the associated Modbus Gateway controller For example installation instructions for a DSC 1212 MODS Modbus Gateway controller can be found in the DSC 1212 Installation Guide e Delta Controls Wiring Guidelines This document contains instructions on recommended practices when wiring power communications and IO to Delta controllers e ORCAview Technical Reference Manual For general database configuration and programmin
11. PTP port only a single Modbus slave device is supported To communicate with multiple devices requires an RS 485 NET connection to the Modbus slave devices The diagram on the following page shows how to wire a single Modbus slave device to a DSM TOB MODxx controller using the NET2 port For more detailed wiring information refer to the Delta Controls Wiring Guidelines Modbus Gateway User Manual Edition 2 1 Page 7 of 38 NOTE If 24VDC power Modbus device supply is used DC polarity MUST be SER observed 24VAC Class 2 or 24VDC power supply IN RS485 d N Communications 24VAC or GND 24VDC M N S port Shield E To previous To next controller controller Shield on MS TP on MS TP l network network Solidly ground the shield RX TX RX TX Power NE 41 Power NET2 TERM 2 NET1 NET2 TERM Bottom edge of the DSM AMP connectors ne Note Use a shielded twisted pair wire for communications Never directly ground more than one point on the shield Doing so can induce large currents and result in communication problems Page 8 of 38 Modbus Gateway User Manual Edition 2 1 Configuring the Modbus Gateway Configuring the Modbus Gateway Two objects are required in order to make the controller communicate with the Modbus device s They are the G
12. User Manual Edition 2 1 Page 13 of 38 Appendices Appendix A Troubleshooting There are several features in this version of the Delta Modbus Gateway that can be used to help when troubleshooting the data exchange between the Modbus Gateway and it s associated devices Gateway Object Statistics Tab The statistics tab of the Gateway object has information that is very useful when troubleshooting See the GW Object Reference Statistics Tab Section in Appendix B for a description of the information contained in these fields Fault Flag Linked to a Modbus Register When set the fault flag of a BACnet object which is linked to a Modbus register indicates a problem with reading from or writing to that register value There are three possible causes for this 1 There is no response from the associated Modbus device This typically means the device is offline Ensure the device is powered up and verify the communications wiring between the devices If connecting using one of the NET ports check that both the Tx and Rx lights are blinking Next verify that you have the correct port and speed settings in the GW object 2 There was an exception code returned from the Modbus device Check the Exceptions field in the dataview entry of the associated GWT object If it is non zero then an exception was returned from the slave device This means the slave device had a problem executing the requested query from the Gateway controller Ref
13. ateway GW and Gateway Translation GWT objects This section gives a brief explanation of these objects and shows how configure them for use It is assumed the user already has a basic familiarity with the Modbus protocol as well as the GW and GWT objects For detailed information on the Delta Controls implementation of the Modbus protocol as well as the GW and GWT objects refer to the associated sections in the appendices of this document Communications Settings The Gateway GW object is used to setup the interface between the Gateway controller and the Modbus device s You cannot create the GW object It is automatically created in the controller whenever the Modbus Gateway firmware is present To setup the GW object follow these steps 1 Open the GW object and go to the setup tab IT Modbus Gateway 50000 GW1 Gateway Modbus Devices Supported Setup Statistics Programming Description Gateway iv Version 2 00 Status Running Type Modbus Port Setting Port NET2 x Speed 3600 od Status Active Modbus Gateway Access E Lighting DK Cancel Apply w ON TROLS Modbus Gateway User Manual Edition 2 1 Page 9 of 38 2 Ensure the Enable checkbox is checked and select from the Port drop down menu which port the Modbus device s are physically connected to Using the Speed drop down menu select the communications baud rate of the Modbus device s Refer to documentation that came with the Modbu
14. bus specifies a 1 based register addressing convention some implementations use a 0 based register addressing convention in their documentation of the register mappings The Register Base Count field allows the GWT object to be compatible with either convention For example the first register in the Holding Registers memory block also refered to as 4x references may be documented any of the following ways Page 20 of 38 Modbus Gateway User Manual Edition 2 1 Appendices e Holding Register 1 1 Based Decimal Register Count e Holding Register 0 0 Based Decimal Register Count e Holding Register 0000H 0 Based Hexadecimal Register Count e Register 40001 ner Note The leading digit in the last example is used to represent the memory type in this case a Holding register while the remaining digits indicate the register count in a 1 based decimal format Refer to the Memory Types section of Appendix C and the documentation that came with the Modbus device s to determine which setting to use Create BACnet Objects Pushbutton This button is used to automatically create the objects that are listed in the Reference column of the dataview if they do not already exist This button has to be depressed and the Apply button pressed in order to create the objects Setup Dataview cwt 100 6wT1 Gateway translation m Lal Z Setup Description Name GwT Test Register Base Count fi z Create BACnet Objects
15. codes Refer to documentation for the specific Modbus slave device for an explanation of any custom error codes returned from a particular device Page 37 of 38 Exception responses are identified by the value of the second byte in the data packet In the normal response this byte echoes back the function code of the query packet In an exception response this byte also has it s most significant bit set This makes the byte value exactly 80 hexadecimal greater than in the normal response The following example shows an Illegal Data Address exception response to a read coil status function 01 query packet sent from a Modbus slave device with an address of 10 Rx Packet Exception Response Field Name Example Hex 0A 81 02 Error Check CRC Document Control Document Title V3 30 Release 3 Modbus Gateway User Manual Document Filename V3 30 Release 3 Modbus Gateway User Manual pdf Revision Changes 0 1 Preliminary Version Created for Version 3 30 Release 2 Modbus Gateway 1 0 First edition coinciding with Version 3 30 Release 2 Modbus Gateway 2 0 Second edition coinciding with Version 3 30 Release 3 Modbus Gateway Page 38 of 38 Modbus Gateway User Manual Edition 2 1
16. de Name Description 01 ILLEGAL The function code received in the query is FUNCTION not an allowable action for the slave 02 ILLEGAL DATA The data address received in the query is ADDRESS not an allowable address for the slave 03 ILLEGAL DATA A value contained in the query data field is VALUE not an allowable value for the slave 04 SLAVE DEVICE An Unrecoverable error occurred while the FAILURE slave was attempting to perform the requested action 05 ACKNOWLEDGE The slave has accepted the request and is processing it but a long duration of time will be required to do so This response is returned to prevent a timeout error from occurring in the master 06 SLAVE DEVICE The slave is engaged in processing a long BUSY duration program command The master should retransmit the message later when the slave is free 07 NEGATIVE The slave cannot perform the program ACKNOWLEDGE function received in the query This code is returned for an unsuccessful programming request using function code 13 or 14 decimal The master should request diagnostic or error information from the slave 08 MEMORY The slave attempted to read extended PARITY ERROR memory but detected a parity error in the memory The master can retry the request but service may be required on the slave device Modbus Gateway User Manual Edition 2 1 In addition to the pre defined error codes listed above the Modbus specification allows custom defined error
17. e variable speed drives as part of the same mechanical system However in contrast to the Gateway products these controllers cannot be ordered with Modbus preloaded on them Rather order whatever DAC or DSC product you will be using with the appropriate I O for the mechanical system and then load the Modbus interface in the field for the number of Modbus units or devices you will be connecting to up to a maximum of 5 Modbus units per controller Please note below the two criteria needed in order to load Modbus Flash Loading Modbus Units into a Device Flash Loader has been modified to use credits which are programmed onto a new Flash Loader hardware key in Delta production The number of credits is based on what is ordered and decrements when an upgrade is chargeable As a result the one same hardware key is now used for all upgrades starting with V3 30 Flash Loader Release 3 for the following product upgrades DCU firmware DAC DSC DSM DLC ASM firmware Modbus Gateway Interface and units BACstats FUTURE when a new flash loadable model is released Modbus can be loaded into any Delta product that meets the following criteria 1 The controller must currently be loaded with at least V3 30 Release 2 firmware or higher and 2 Particularly for DAC models the controller hardware must be one of the more recent revisions that have the larger memory shipped in a box with a green dot on it and includes a green P
18. e used to load the Modbus Gateway interface So besides obtaining the right controller you will need to order a Flash Loader key and perhaps additional credits especially if you intend on upgrading a large number of controllers Model Number Description DFF099 KEY FLASH LOADER FIRMWARE KEY c w 50 credits already loaded At 10 credits per Modbus unit 50 credits will allow you to load 5 Modbus units into the same or different controllers DFF099 CDT FLASH LOADER CREDITS Additional credits you wish to add to the original 50 on the same key Note that the quantity for this product represents blocks of 50 You must include this second part number in the same order if you want more than the default 50 credits on the key Connecting to the Modbus Device The Modbus Gateway controllers can connect to Modbus slave device s on either of their RS 485 ports NET1 or NET2 or RS 232 PTP port The table below shows the available configuration options for the NET and PTP ports on the Modbus Gateway controllers NETI NET2 PTP Ethernet DSC or LINKnet or BACnet MS TP OWS Direct DSM RTR Modbus Subnet Level Connect Modem or Modbus or Modbus Non Ethernet DSC BACnet MS TP LINKnet or OWS Direct or DSM TOB or System Level Modbus Connect Modem DSM PWR or Modbus DAC BACnet MS TP LINKnet or N A Subnet Level Modbus Note When connecting to a Modbus device using the RS 232
19. er to the Exception Responses section of Appendix C for more information 3 The associated entry in the GWT for this object contains an invalid combination of settings For example a data type of float cannot be mapped to a BV Refer to the tables in the GWT Configuration Examples section for details on the valid settings based on data type Page 14 of 38 Modbus Gateway User Manual Edition 2 1 Appendices Exception Code Responses Exception codes may be returned when there is a problem with the request that was received by a Modbus slave device The code returned in the exception response gives diagnostic information on the reason why the request failed to process normally For more information and a list of the exception codes defined by the Modbus specification see the Exception Responses section in Appendix C Tx amp Rx Packet Snooping Setting the units for the associated object to Currency 10 enables a special packet sniffing mode When this mode is enabled the description tab of the associated BACnet object for a given GWT entry will display the Tx transmit packet sent out to the Modbus device on the last scan for that entry It will also display any Rx receive packet response sent back from the Modbus device for that entry The following screen capture shows the Rx and Tx packets in the description tab for reading an integer value from Holding Register 40001 of a Modbus device with an address of 1 D1Rd Hold Re
20. f Points Hi Byte of Points Lo Byte Error Check CRC The normal response if Input register 108 contained a 16 bit unsigned integer value of 2591 would be Rx Packet Response Field Name Example Hex Slave Address 05 Function 04 Data Byte Count 02 Data Byte Hi Register 30108 0A Data Byte Lo Register 30108 1F Error Check CRC Modbus Gateway User Manual Edition 2 1 Page 33 of 38 Function 05 Force Single Coil This function is used to write the contents of a single coil register to either ON or OFF In a Force Single Coil Query message the starting register address and the value to write to the coil are specified FF 00 hex ON 00 00 hex OFF The following example shows the packets generated when writing ON to Coil register 00172 to a Modbus slave with an address of 17 Tx Packet Query Field Name Starting Address Hi Byte Starting Address Lo Byte Force Data Hi Byte Force Data Lo Byte Error Check CRC The normal response is an echo of the query returned after the register contents have been written to Rx Packet Response Field Name Starting Address Hi Byte Starting Address Lo Byte Force Data Hi Byte Force Data Lo Byte Error Check CRC Page 34 of 38 Modbus Gateway User Manual Edition 2 1 Appendices Function 06 Preset Single Register This function is used to write to the contents of a sin
21. g Integer 9001 AV101 Analog V E o 255 0 Currency10 53 Auto Auto Value 0 Control Source Modbus Device 1 Description Setup Tx 01 03 00 00 00 01 84 04 Rx 01 03 02 00 FF F8 04 DK Cancel Apply 9 See Appendix C Modbus Protocol Implementation for details on the packet structure for Modbus communications ne Note I Any text already in the description tab when packet sniffing mode is enabled will be overwritten 2 For AV object s you must change the units directly in the associated AV object to go to packet sniffing mode for that entry For BVs and MVs which do not have a units field change the units property for the associated entry in the GWT object ADelta CONTROL S Modbus Gateway User Manual Edition 2 1 Page 15 of 38 Appendix B GW and GWT Object Reference The following sections give detailed information on all the application specific fields in the Gateway GW and Gateway Translation GWT Objects as they appear when opened in a Modbus Gateway Controller Gateway Object GW Header Modbus Gateway 7000 GW1 Gateway Modbus Devices Supported This field displays the maximum number of Modbus slaves the controller is able to communicate with Setup Modbus Gateway 7000 GW1 Gateway Enable This checkbox enables or disables the gateway elta CON T R OL S Page 16 of 38 Modbus Gateway User Manual Edition 2 1 Appendices Versi
22. g instructions e 3 30 Release 3 Modbus Gateway Products Release Notes For a summary of new features and any known issues with this version of the Delta Modbus Gateway firmware e Modbus Slave Device Documentation In order to configure the Modbus Gateway controller to communicate with a Modbus slave device you need to know the devices required communications type RS 485 or RS 232 network address and speed As well as the Register mappings including data types Float Integer etc e Modicon Modbus Protocol Reference Guide This document provides a detailed description of the Modbus protocol specification Modbus Gateway User Manual Edition 2 1 Introduction Introduction Many of Delta s Controllers have an ordering option that allows them to function as a Modbus master device and communicate with one or more Modbus slave devices This allows the controller to act as a Gateway translating information to from the Modbus slave device s into BACnet objects resident in the Gateway controller which can then be accessed by the rest of the BACnet network The Delta Modbus Gateway controllers communicate to Modbus slave devices using the Modbus RTU protocol via its NET RS 485 or PTP RS 232 ports Important Information When entering data into the Gateway Translation object GWT dataview do not use the insert or delete keys to insert or delete an entry in the dataview There is currently a bug with this functionality in the GWT ob
23. gle holding 4x register In a Preset Single Register Query message the starting register address and the data value to write to the register are specified L Note Since this function can only write to a single register at a time it is therefore only used when writing to Holding registers with a data type of Integer The other data types which span more than one register write using function 16 The following example shows the packets generated when writing a value of 3 to holding register 40002 in a Modbus slave with an address of 17 Tx Packet Query Field Name Slave Address Function Starting Address Hi Byte Starting Address Lo Byte Force Data Hi Byte Force Data Lo Byte Error Check CRC The normal response is an echo of the query returned after the register contents have been written to Rx Packet Response Field Name Slave Address Function Starting Address Hi Byte Starting Address Lo Byte Force Data Hi Byte Force Data Lo Byte Error Check CRC Modbus Gateway User Manual Edition 2 1 Page 35 of 38 Function 16 10 Hex Preset Multiple Registers This function is used to write to a series of holding 4x registers In a Preset Multiple Registers Query message the starting register address number of registers to be written to the number of data bytes followed by the data value to write to the register are specified DL Note This function is used w
24. hen writing values with a data type that spans more than one register to a holding register The Double Integer Long and all the Float data types span two registers The following example shows the packets generated when writing a value of 3 in a Signed 32 bit data format to holding registers 40002 and 40003 in a Modbus slave with an address of 17 Tx Packet Query Field Name Example Hex Slave Address 11 Function 10 Starting Address Hi Byte 00 Starting Address Lo Byte 01 of Registers Hi Byte 00 of Registers Lo Byte 02 Byte Count 04 Data Hi 00 Data Lo 00 Data Hi 00 Data Lo 03 Error Check CRC The normal response returns the slave address function code starting address and quantity of registers written to Rx Packet Response Field Name Slave Address Function Starting Address Hi Byte Starting Address Lo Byte of Registers Hi Byte of Registers Lo Byte Error Check CRC Page 36 of 38 Modbus Gateway User Manual Edition 2 1 Exception Responses Appendices For a given entry in a GWT data view the Exceptions field lists any exception responses returned for a particular request to a Modbus slave device Exception codes may be returned when there is a problem with the request that was received by the Modbus device There are 8 pre defined exception response codes in the Modbus specification Co
25. ig Memory Type Register of Registers Data Type Bit BV1 Write Coil 1 1 Bit Value N A Reading Input Registers Input Registers are read only 16 bit registers that can hold analog values in several different data formats The data format will generally determine what type of object the value should be mapped to and the number of registers that should be read The table below shows the valid settings for the object type number of registers to be read and bit fields based on the data type selected Object of Registers Data Type Bit Type BV 1 Bit Value 0 16 AV 1 Integer N A 2 Long N A 1 Bit Value 0 16 2 Double Integer N A 2 Float N A 2 FloatSwapped N A 2 FloatReversed N A MV 1 Integer N A For a definition of the different Data Types see the Data Types section of Appendix C Examples Read a Floating Point Value from Input Register 30002 to AV1 Reference R W Config Memory Type Register of Registers Data Type Bit AV1 Read Input Register 2 2 Float N A Read Bit 2 from Input Register 30002 to BV1 Reference R W Config Memory Type Register of Registers Data Type Bit BV1 Read Input Register 2 1 Bit Value 2 Reading Writing Holding Registers Holding Registers are the same as Input Registers with two exceptions 1 Holding Registers can be written to as well as
26. iguring the Modbus Gateway 3 In the dataview of the GWT object create an entry for each value from the Modbus device to be linked to a BACnet object in the Gateway Start entering data by double clicking in the column you wish to edit 4 Below the dataview there are also several dropdown boxes that contain more configuration settings for the current selected entry After filling out the fields in the dataview for a single entry you must click on Apply before you can enter data in these remaining fields After you finish setting these additional fields press Apply again to save the changes before moving to the next entry 5 Press the Create BACnet Objects button and press Apply This will automatically create all the required BACnet objects based on the object references and names you entered in the steps above Note 1 f an object reference is already used in the database the name of the object will not be overwritten by the GWT object however a link will still be created to the Modbus register If this object was already created because it is being used for some other purpose in the database there will be a conflict since there would now be two competing control sources for the object 2 Changes to the name or units properties for a given entry in the GWT after the associated BACnet object AV BV or MV has been created have no effect Once the object has been created any changes to these properties should be done directly in the
27. is stored in the memory of the Modbus device Each Memory Type reads or writes to a certain range of memory in the Modbus device The different Memory Types and corresponding register reference are listed below e Coil Register 0x References e Input Status Register 1x References e Input Register 3x References e Holding Register 4x References Refer to the Memory Types in Appendix C for more information Register Specifies the starting register for the data value in the Modbus device to be referenced Registers are specified without the Memory Type reference i e Ox Ix 3x 4x For example for a Memory Type register reference of 40001 enter a value of 1 assuming a 1 based Register Count of Registers Specifies the number of registers that the data value in the Modbus device spans The value that is entered in this field 1s determined by the data format selected in the Data Type field Data Type Specifies the data format used to read write the data value stored in the Modbus device The different Data Types are Modbus Gateway User Manual Edition 2 1 Appendices e Bit Value 1 bit Boolean ON OFF occupies 1 register e nteger 16 bit signed Integer occupies register e Long 32 bit signed Integer occupies 2 register e Double Integer 32 bit Unsigned Integer occupies 2 registers e Float IEEE 32 bit floating point Big Endian occupies 2 registers e Float Reversed IEEE 32 b
28. it Value Bit values are stored in a single 1 bit register They are used to store simple binary values 1 ON 0 Off Integer This data type uses a 16 bit signed integer format to store a whole number value from 32768 to 32767 Integer values are stored in a single 16 bit register Double Integer The double integer data type spans two 16 bit registers and can store any positive whole number value from 0 to 4 294 967 295 Long Longs are 32 bit signed Integers In this data type the most significant bit MSB is used to indicate if the value is positive or negative The remaining 31 bits are the binary equivalent of the decimal value For example 3 and 3 expressed in Binary Long format would be Decimal Value Binary 32 bit signed Integer Format 3 0000000000000000000000000000001 1 3 1000000000000000000000000000001 1 A Long value spans two 16 bit registers and can store any whole number value from 2 147 483 648 to 2 147 483 647 ner Note Delta uses a 32 bit single precision floating point format to store BACnet AV values This limits the stored value to 6 significant figures plus an exponent value This means that when mapping Double Integer and Long values from a Modbus device to AV s you are actually limited to integer values between 340 282 and 340 282 before round off errors due to trailing significant figures being dropped occurs 32 Bit Single Precision Floating Point numbers Floating Point val
29. it floating point Little Endian occupies 2 registers e Float Swapped IEEE 32 bit floating point Little Endian with byte swapped occupies 2 registers Refer to the Data Types in Appendix C for more information Bit Specifies a particular bit to extract when reading from a 16 bit Holding or Input register This can be a value from 0 16 were is the least significant bit LSB and 16 is the most significant bit MSB in the selected register 0 is a special case in which the entire 16 bit register is evaluated as either zero or non zero This field is only used when mapping a value from a Holding or Input register to a BV with a data type of Bit Value Setup Dataview Fields The following four fields are not actually in the dataview window itself They are located directly below the dataview in the GWT dialog Units The Units drop down box is used to select the units that the associated BACnet object will be created with when the Create BACnet Objects pushbutton is used This field only applies when mapping to an AV object MV or BV objects do not have a units property R W Configuration This dropdown box is used to select whether you want to read from or write to the selected data value in the Modbus device ne Note If you wish to both read and write to a single value in a Modbus device you must create two seperate entries in the table one for reading the value and another for writing to the value In addition these two en
30. ives a value of 1 465 2 Nextcalculate the exponent by counting how many decimal places you shifted to normalize the mantissa If the decimal was shifted to the left the exponent is positive and if shifted to the right it is negative In this case the exponent is 2 3 Byusing the formula above the scientific notation equivalent of 146 5 is Mantissa x Number Base 1 465 x 10 Binary scientific notation is done exactly the same way only using binary base 2 numbering For example the decimal number 146 5 in binary is 10010010 1 Normalizing the Mantissa gives a value of 1 00100101 The decimal was shifted 7 places to the left giving an exponent value of 7 Therefore 146 5 in binary scientific notation is Mantissa x Number Base 1 00100101 x 2 IEEE 32 bit Floating Point notation is similar to binary scientific notation with a few exceptions 1 One bit is used to indicate the sign of the value Positive or Negative 2 The exponent value has a 127 bias added to it 3 Ina base 2 normalized mantissa the digit on the left of the decimal point will always be 1 In IEEE format only the fractional portion of the Mantissa is stored and it is understood there is always an implied 1 in front of it Modbus Gateway User Manual Edition 2 1 Appendices The following diagram shows how an IEEE floating point value is stored in a 32 bit binary number using our example value of 146 5 146 5 in IEEE 32 Bit Floating Point Data Fo
31. ject that will result in the object being corrupted This will be fixed in a future revision of the Modbus Gateway firmware Available Modbus Products Modbus Gateways Gateway products are intended to be used where a gateway to BACnet is required for a number of Modbus devices or units communicating on the same Modbus network such providing BACnet access to a bunch of Rooftop units connected together on a Modbus network These are the only products that come pre loaded with the Modbus interface The table below lists the currently available controllers that can be ordered with the Modbus Gateway firmware Modbus Product Model Description Units DSM RTR MOD30 BACnet Router w Modbus Gateway 30 DSM TOB MOD5 K1A 16 Button Room Controller w Modbus 5 DSM TOB MOD15 K1A 16 Button Room Controller w Modbus 15 DSM TOB MOD30 K1A 16 Button Room Controller w Modbus 30 DSM PWR Room Controller w Modbus Power Meter Interface 1 Notes 1 This column lists the current number of Modbus slave devices supported by the associated controller 2 Gateways not already maxed out to 30 can be flash loaded in the field to support additional Modbus units up to 30 Modbus Gateway User Manual Edition 2 1 Page 5 of 38 Page 6 of 38 Modbus Controllers Almost any Delta I O controller installed to control some mechanical equipment can be loaded with the Modbus interface to pick up a few Modbus devices or units i
32. ng used in documentation Function 01 Read Coil Status This function is used to read the ON OFF state of a coil register In a Read Coil Status Query message the starting register address and number of registers to be read are specified ner Note While this function allows reading of multiple register values in a single query Delta only supports reading a single register per query message with this function The following example shows the packets generated when requesting to read coil register 00011 from a Modbus slave with an address of 2 Tx Packet Query Field Name Slave Address Function Starting Address Hi Byte Starting Address Lo Byte of Points Hi Byte of Points Lo Byte Error Check CRC The normal response if the queried coil register was in the on state would be Rx Packet Response Field Name Slave Address Function Data Byte Count Data Error Check CRC In the Data byte the information on the coil state is stored in the least significant bit LSB A value of 1 On 0 Off and the remaining bits in the data byte are padded with zeros Page 30 of 38 Modbus Gateway User Manual Edition 2 1 Appendices Function 02 Read Input Status This function is used to read the ON OFF status of an Input Status Register In a Read Input Status Query message the starting register address and number of registers to be read are specified df Note While this
33. ns following this for more detailed information on Modbus functions memory types and packet structure Code Name Decimal 01 Read Coil Status 02 Read Input Status 03 Read Holding Registers 04 Read Input Registers 05 Force Single Coil 06 Preset Single Register 16 Preset Multiple Registers Modbus Gateway User Manual Edition 2 1 Page 25 of 38 Memory Types Modbus data values are broken into 4 different memory types each of which represent a block of memory in the Modbus device Each of these blocks of memory is broken up into registers Depending on the memory type and data format a single data value will span or more registers To access a particular register both the register number and memory type must be specified Together these represent the register address There are several different conventions in which register addresses are documented For example the first register in the Holding Registers memory block also referred to as 4x references may be documented any of the following ways e Holding Register 1 1 Based Register Count e Holding Register 0 0 Based Register Count e Holding Register 0000H 0 Based Hexadecimal Register Count e Register 40001 A brief description of each memory type is given below Coil Registers 0x References Each coil register is a 1 bit piece of data that typically represents the Boolean ON OFF state of an output or internal variable These
34. ntroller reset GWT Update Interval This is the time in seconds that it took on the last iteration to scan all the GWT objects and update the associated BACnet objects The update rate varies depending on the number of Modbus slave devices and how many values are mapped from each device Programming The Programming tab is not used for the Modbus Gateway but only with the Delta Wireless Gateway Description The description tab may contain a string of characters of up to 2000 characters in length The character string is limited to any printable character Modbus Gateway User Manual Edition 2 1 Page 19 of 38 Gateway Translation Object GWT Header Ti Gateway Translation 200 GWT1 Gateway translation zt x Setup Common Area iGwt1 100 GWT1 Gateway translation E 215 xl Setup Description Name GwT T est Register Base Count fi z Reference Exceptions Read Memory Type Register tt of Registers Data Type Create BACnet Objects Units z R W Configuration z Scaling MV Offset zl Register Address HVAC lv Access r Lighting mi The common area of the Setup tab has two fields and a button located above the dataview area Name The name of the Gateway Translation object is displayed in this field This name must be unique among all the descriptors located in the same controller Register Base Count While Mod
35. object itself GWT Configuration Examples This section provides several examples on how to configure the GWT to read from and or write to the different Memory Types using various methods Note 1 The following examples all assume a Register base count setting of 1 If the register base count is set to 0 subtract 1 from the value to be entered in the Register field for each example 2 If you wish to both read and write to a single value in a Modbus device you must create two separate entries in the table one for reading the value and another for writing to the value In addition these two entries must not be referencing the same BACnet object Reading Input Status Registers Input Status Registers are single bit read only registers that store a binary On or Off value The following table shows the GWT settings required to Read the value from Input status register 10001 into BV1 in the Gateway Controller Example Read Input Status Register 10001 to BV1 Reference R W Config Memory Type Register of Registers Data Type Bit BV1 Read Input Status 1 1 Bit Value N A Modbus Gateway User Manual Edition 2 1 Page 11 of 38 Reading Writing Coil Registers Coil Registers are similar to Input Status Registers except they are writeable The example below shows the GWT settings to write to Coil Register 00001 Example Write BV1 value to Coil Register 00001 Reference R W Conf
36. on This field displays the version number of the gateway firmware loaded into the Delta Controller which is different from the main firmware version number listed in the Device object Type This field displays the type of gateway that is loaded into the Delta Controller In V3 30A firmware there are only two gateways currently supported e Modbus e Delta Wireless Sensors Status This field displays the status of the gateway When the gateway is enabled this field displays Running When the gateway is disabled this field displays Stopped Port This field is used to select the physical port which is to be connected to the Modbus slave device s There are three port options available e NET RS 485 port 1 e NET2 RS 485 port 2 e PTP Serial PTP port ae Note 1 Only DSC and DSM controllers come with a serial port 2 When connecting via PTP only a single Modbus slave device is supported Speed This field is used to select the baud rate for communicating with the Modbus slave devices s The baud rate must be set to the same speed on both devices in order that they communicate properly The supported speeds are 2400 4800 9600 19200 and 38400 baud Status This field displays the current status of the selected port When the port is being used by the gateway this field displays Active When the gateway is disabled this field displays Inactive If the selected port is in use by something other than the ga
37. read from Page 12 of 38 Modbus Gateway User Manual Edition 2 1 Configuring the Modbus Gateway 2 Youcannotuse the Bit Value data type when writing to a Holding register If you want to write to a single bit in a holding register you should read out the register value as an integer into an AV then use GCL bit manipulation to set clear the required bit and write this adjusted value back into the Modbus device Examples Read an Integer Value from Holding Register 40001 to AV1 Reference R W Config Memory Type Register of Registers Data Type Bit AV1 Read Holding Register 1 1 Integer N A Write the Value from AV3 as a Long to Holding Register 40002 Reference R W Config Memory Type Register of Registers Data Type Bit AV3 Write Holding Register 2 2 Long N A Memory Limits amp Performance Issues Each entry register in a GWT object occupies approximately 100 bytes of Static RAM database space Given that a DSM RTR has 319 kB of Static Ram available this puts an ultimate cap of about 3 200 entries across all created GWT objects However this would not allow for any trending alarming programming etc because the memory would be totally full Since a DSM RTR MOD30 can communicate with up to 30 Slave Devices this would nominally allow each slave to have about 100 entries registers 100 entries 30 GWT objects 3000 total entries
38. rmat 31 24 16 8 byte 4 byte 3 byte 2 byte 1 01000011000100101000000000000000 sign 1 bit lExponent 8 bits IMantissa 23 bits leading bit omitted Sign bit 31 The sign is stored as a single bit Boolean value 0 Positive 1 Negative Exponent bits 23 30 The exponent is stored as an 8 bit unsigned integer value Mantissa bits 0 22 The fractional part of the Mantissa stored as a 23 bit binary fraction As stated earlier there are 4 variations on the above data format The difference between each of these variations is the order in which each byte of data as numbered in the table above is stuffed into a memory location and or data packet The table below gives the stuffing order for each of the 4 formats Data Format Byte Order Floating Point Big Endian 4 3 2 1 Floating Point Big Endian with byte swapped 3 4 1 2 Floating Point Little Endian 1 2 3 4 Floating Point Little Endian with byte swapped 2 1 4 3 Note Floating Point Big Endian with byte swapped format is not supported in the Delta Modbus Gateway 8 8 yt pP Modbus Gateway User Manual Edition 2 1 Page 29 of 38 Functions The Delta Modbus Gateway Controllers support functions 1 6 and 16 of the Modbus protocol This section provides detailed information on each of these functions id Note Register addresses in the data packets are always zero based regardless of the Register Base Count convention bei
39. roduct Notice where flash memory has been increased to to 1 MB and the SRAM has been doubled to 256K Note You can also determine whether a product has more memory when it is powered up and communicating by looking at its DEV object using ORCA view Any product that includes the underscore as part of its Model Name on the Product tab 1 e DAC 322 has the increased memory as required You can even create a custom report in ORCAview to list this information and one has already been provided on GEORGE for download The V3 30 Release 3 Flash Loader is rather smart and can figure out what it can and cannot do with the controller you ve connected to and whether the controller is one that Modbus can be loaded into and indicates how many Modbus units have already been loaded and and whether you can load any more Loading Modbus into a controller will use or decrement 10 credits off the Flash Loader key for each Modbus unit Other product upgrades require a different number of credits And once loaded into a Delta product the credits are unrecoverable you cannot reverse the process Modbus Gateway User Manual Edition 2 1 Connecting to the Modbus Device Refer to Flash Loader documentation or the Help file for further information including how many credits are used to upgrade all other devices Flash Loader Key amp Credits As described the same Flash Loader key can be used to upgrade V2 DCUs or DACS to V3 and can also b
40. s device s for information on the valid connection speeds for that device 3 Press Apply and reset the controller Linking Modbus Device Registers to BACnet Objects The GWT object is used to transfer values between Modbus registers and the associated BACnet objects Refer to documentation that came with the Modbus device s for information on the registers For each Modbus device a GWT object must be created with an instance number equal to the network address of the Modbus device 1 Create a GWT object with an instance number equal to the network address of the Modbus device to be associated with it IT Modbus Device 3 9001 GWT3 Gateway translation Setup Description Name Modbus Device 3 Register Base Count 1 Reference Exceptions Read Memory Type Register of Registers Data Type Bit Access r Lighting E OK Cancel Apply 2 2 From the documentation that came with the Modbus slave device determine if it uses a 0 or 1 based register addressing convention and set the Register Base Count Field to match While Modbus specifies a 1 based register addressing convention some implementations use a 0 based register addressing convention in their documentation of the register mappings The Register Base Count field is used to configure the GWT to be compatible with the convention used by that particular device ADelta CO NT ROLL S Page 10 of 38 Modbus Gateway User Manual Edition 2 1 ae Conf
41. teway i e NET object this field displays In Use By and lists the name of the object using the port HVAC Access and Lighting Checkboxes These checkboxes indicate which application s the object is part of Any combination of the HVAC Access Control and Lighting applications can be selected Leaving all checkboxes blank is the same as checking them all Modbus Gateway User Manual Edition 2 1 Page 17 of 38 Page 18 of 38 As a part of OWS security these checkboxes allow an operator to see only the objects for a particular application s For example a site may have separate operators for the HVAC and Access applications It is possible for each operator to only see the objects related to their application Refer to Chapter 7 Security in the ORCAview Technical Reference Manual for more information on how to set up and administer Object Application Restrictions When a checkbox is checked an indicator icon appears at the top of the dialog The three application domains are Application o o 5 HVAC Red Access Blue Lighting Green NNN Statistics Mi Modbus Gateway 7000 GW1 Gateway loj xl Modbus Devices Supported 30 Z Setup Statistics Programming Description Total Sent 0 Send Failures 0 Protocol Errors 0 Total Received 0 Invalid Received 0 GWT Update Interval 1 Seconds Total Sent DK
42. tries must not be referencing the same BACnet object Modbus Gateway User Manual Edition 2 1 Page 23 of 38 Scaling MV Offset This field is used when mapping a Modbus value to an AV or MV object When mapping to an AV object it can be used to rescale a value from a Modbus device by doing a left or right shift of up to 4 decimal places For example if the Modbus device returned a value of 600 which represents a value of 60 0Hz selecting Div10 from this dropdown would convert the value from 600 to 60 0 before placing it into the associated AV object MV objects take an integer value and convert it to a text value based on an enumeration list in an associated MIC object The MIC enumeration list is 1 based while some Modbus device enumerations are 0 based In order to map a 0 based enumeration value from a Modbus device to an MV object select Div10 or 1 MV Offset from the dropdown list Register Address This is a display only field that displays the full decimal and Hexadecimal Address for the starting register of the data in the Modbus device for the currently selected dataview entry HVAC Access and Lighting Checkboxes These checkboxes indicate which application s the object is part of Any combination of the HVAC Access Control and Lighting applications can be selected Leaving all checkboxes blank is the same as checking them all As a part of OWS security these checkboxes allow an operator to see only the objects for a
43. ues are used to represent real numbers numbers with a fractional component IEEE specifies a standard format for 32 bit floating point values There are 4 variations in which IEEE Floating Point values may be stored and or transmitted in a data packet The Delta Modbus Gateway supports 3 of these formats The table below lists the 3 formats that Delta supports and which data type should be selected in the GWT to reference a floating point value using this format Data Format Floating Point Big Endian Floating Point Little Endian Floating Point Little Endian with byte swapped Single Precision 32 bit floating point values span two 16 bit registers and can store a real number value from 3 403 x 10 to 3 403 x 10 Modbus Gateway User Manual Edition 2 1 Page 27 of 38 Page 28 of 38 IEEE Floating Point Data Format Details This section gives a detailed description of the IEEE 32 bit floating point data format The IEEE floating point data format 1s similar to binary scientific notation data format Scientific notation expresses real numbers in the following format Exponent Mantissa x Number Base For example lets convert 146 5 to scientific notation using a number base of 10 decimal 1 Start by calculating the Mantissa To do this take the number to be converted in this case 146 5 and shift the decimal point until there is only one digit to the left of it This is called Normalizing the Mantissa This g
Download Pdf Manuals
Related Search
Related Contents
Artículo completo (PDF — 162 Kb) MODULE "MV" - Made in Algeria 取付方法(Adobe PDF154KB) AXFシリーズ 電磁流量計 フィールドバス通信形 FORD Fusion 2013 - Sûreté du Québec Benutzerhandbuch GlucoCheck Comfort D:\Ufficio Tecnico\manuali Igie user`s manual manual de usuario manuel de l`usuaire Transcend 64MB SDRAM 144Pin SO-DIMM PC133 Unbuffer Non-ECC Memory www . ElectricalPartManuals . com Copyright © All rights reserved.