Series 90-70 Programmable Controller Data Sheet Manual, GFK

image

Contents

1. Fault Mode Selection This output module can be configured from the programmer so that output points assume one of two states in response to certain operating or default conditions These states are Maintain existing output state Turn outputs OFF For more detailed information on module configuration refer to the Programming Software User s Manual for IC641 software products Fusing Each output is fused with a replaceable 3 15 amp fuse Replace with the following type Metric 5 x 20 mm 3 15 amp 250V Slo blo Module Mechanical Keying This module includes a mechanical key that prevents inad vertent substitution of one module type for another in a given slot The key fits a uniquely shaped area on the board below the connector Each module has a key pack aged with it When the module is first installed the key latches onto the backplane center rail When the module is extracted the key remains in the center rail configuring the slot to ac cept only identical module types If it is necessary to change the module location in the rack after the key has been latched onto the center rail of the rack the key can be removed by pushing it upward to un hook the latch while pulling it off the rail It may then be reinserted onto the module and the module inserted into the rack in the desired location Note that on y a power supply can be placed in the left most rack position and slot 1 adjacent to the powe
2. To remove the terminal board grasp the top of the terminal board and swing it outward as shown in Figure 4 Caution Do not use the hinged door to remove the terminal board The hinged door could be damaged if this is done 3 The terminal board is designed to accept wire sizes from AWG 22 0 36 mm through AWG 14 2 10 mm It is important that when using AWG 14 2 10 mm wire for wiring all points that a maxi mum insulation diameter of 135 inch 3 43 not be exceeded To ensure proper connection two wires may be terminated on any one terminal only if both wires are the same size The terminal board is designed to accept a maxi mum of 40 AWG 14 2 10 mm2 wires If AWG 14 2 10 mm wires are to be used then wire markers should be placed at least 8 inches 203 mm from termination end to provide sufficient space for the hinged door to close 51 4 Series 90 70 Programmable Controller Data Sheet Manual GFK 0600F Discrete Output Modules 120 240 Volt AC 2 Amp Isolated 12 Point Output Module 5 GFK 0382 August 1997 a43747 DO NOT PULL ON DOOR WIRE BUNDLE CABLE TIE CLEAT Figure 4 Removal of I O Terminal Board 5 After completing connections to all modules in a rack the wire bundle must be secured To ensure that the wire bundle is secured properly it is rec ommended that a cable tie be wrapped around the wi
3. Ordering Information OutputModule 120 240VAC 2 Amp Isolated 12 Points IC697MDL341 Note For Conformal Coat option or Low Temperature Testing option please consult the factory for price and availability 51 6 Series 90 70 Programmable Controller Data Sheet Manual GFK 0600F
4. registered trademarks of Microsoft Corporation Series 90 70 Programmable Controller Data Sheet Manual 51 1 GFK 0600F 2 GFK 0382J August 1997 Discrete Output Modules 120 240 Volt AC 2 Amp Isolated 12 Point Output Module Operation 120 240 Volt AC 2 Amp Isolated Output Module a44140 OPTO OPEN FUSE H N lt ISOLATOR DETECTOR N O FUSE L SYSTEM 3 15A BACKPLANE lt EREECE oe 4 OPTO OUTPUT Oem ISOLATOR DRIVER O LOAD FIELD MODULE CONNECTIONS Figure 1 Block Diagram for IC697MDL341 Output Characteristics The 120 240 Volt AC 2 Amp Isolated Output Module is compatible with a wide variety of load devices such as Solenoids Motor starters e Indicators The rating of 2 amps per point applies to the long term current capacity of each point Because of overall heat dissipation within the module the maximum current for the module is limited to 16 amperes Each output on this module is capable of transiently con ducting a surge current which is much greater than its long term current rating The rate at which such surges can be repeated depends on the current rating of the device and the duty cycle percent of time the device is ON For typical incandescent devices operating at a 50 duty cycle the following repetition rates apply to this module Steady State Current mA Repitition Rate Hz 0 5 5 1 1 2 0 1
5. Discrete Output Modules IC697MDL341 GFK 0382 120 240 Volt AC 2 Amp Isolated 12 Point Output Module 1 August 1997 Features aa i oaaao 12 individually isolated points O O e 2 amp capacity per point FEF Sees Ss A3 B3 C3 D3 A3 B3 C3 D3 High inrush capacity 10x rated current A4 B4 C4 D4 A4 B4 C4 D4 A5 B5 C5 D5 A5 B5 CS D5 A6 B6 C6 D6 A6 B6 C6 D6 A7 B7 C7 D7 A7 B7 C7 D7 A8 B8 C8 D8 A8 B8 C8 D8 Functions FUSE FUSE 50 60 HZ The 120 240 Volt AC 2 Amp Isolated Output Module for use Sasovac f toa Maxmonute with a Programmable Logic Controller PLC provides 12 PILOT DUTY ou HON isolated output points This allows each point to be used on eg S QHA different phases of the AC supply Each output point is indi S Oo HAON vidually fused with a 3 15 amp replaceable fuse S C5 Az A2 The module provides a high degree of inrush current S which makes the outputs suitable for a wide range of in A3 S S 5 ducti
6. r sup ply must always contain a CPU in rack 0 the CPU rack or a Bus Receiver Module in an expansion rack 51 2 Series 90 70 Programmable Controller Data Sheet Manual GFK 0600F Discrete Output Modules 3 120 240 Volt AC 2 Amp Isolated 12 Point Output Module GFK 0382 J August 1997 i irl a43985 Field Wiring TERMINALS FIELD WIRING The module is wired as shown in Figure 2 Since each output is isolated from the other outputs a wire from the ERN power source to the power input terminal for each output C is required power input terminals for each output are not connected inside the module H N The detachable field wiring terminal board will accept A2 wire sizes from 22 0 36 mm through 14 2 10 DAN mm Two wires may be terminated on a given lug if both wires are the same size There is room for a es bundle of forty 14 2 10 mm wires to be routed out through the terminal board cavity H N The wire bundle can be secured to the terminal board 13 Bt by passing a cable tie through a cleat located at the PERN lower corner of the terminal board B2 H N 55 a OH H N c2 8 H N c3 2 1 33 D1 H N D2 O 1te Figu
7. re 2 Field Wiring Connections Series 90 70 Programmable Controller Data Sheet Manual 51 3 GFK 0600F 4 Discrete Output Modules GFK 0382 August 1997 120 240 Volt AC 2 Amp Isolated 12 Point Output Module module Module features referenced in the following proce dures which are common to all IC697 I O modules are illus trated in the following figure Recommended Field Wiring Procedures The following procedures are recommended when connect ing field wiring to the detachable terminal board on this input m a43855 JACKSCREW HINGED i JACKSCREW O _ DOOR TERMINAL BOARD 5 O o Q O NJS 5 CORD CORD 2 TIE TIE H a O LEAT o oS y QlS Q O ole L O ra H Se Q Q oS QlS Q H HO K ec Af CORD TIE CLEAT Figure 3 I O Module Features 1 Turn off power before removing or installing ter minal boards Open the hinged door on the mod ule to access a jackscrew which holds the terminal board securely in place The detachable field wir ing terminal board can now be removed from the module by turning the jackscrew counter clock wise until it is fully disengaged
8. re bundle and tightly secured through the cable tie cleat located at the lower right corner of the terminal board For extremely large wire bundles additional cable ties should be used Adoor label insert is included with each module to indicate circuit wiring information and provide space to record user circuit wiring identification A slot is provided on the hinged door to allow for insertion of this label If the label is difficult to in sert crease the scored edge before insertion The outside label has a color coded stripe to allow quick identification of the module voltage type blue low voltage red high voltage After field wiring is completed the terminal board should be securely fastened to the rack by insert ing the terminal board strap attached to each module into the small rectangular slots in the bot tom card guide grill on the rack This strap not only secures the terminal board to the rack it also provides a way of identifying the wired terminal board with its correct mating rack slot location For adequate module ventilation it is recom mended that at least a 6 inch 152mm clearance be allowed above and below the rack grill Wire bundles should not obstruct the rack grill work Removing an I O Module The instructions below should be followed when re moving an I O module from its slot in a rack Grasp the board firmly at the top and bottom of the board cover with your thumbs on the front of
9. the cover and your fingers on the plastic clips on the back of the cover Squeeze the rack clips on the back of the cover with your fingers to disengage the clip from the rack rail and pull the board firmly to remove it from the backplane connector Slide the board along the card guide and remove it from the rack Series 90 70 Programmable Controller Data Sheet Manual GFK 0600F 51 5 6 Discrete Output Modules GFK 0382J 120 240 Volt AC 2 Amp Isolated 12 Point Output Module August 1997 Table 1 Specifications for IC697MDL341 Rated Voltage 120 240 volts AC Outputs per Module 12 individually isolated Isolation 1500 volts any output to backplane 500 volts between points Output Voltage Range 85 to 264 volts AC 47 63 Hz Output Current 2 amps maximum per point 16 amps maximum per module Output Characteristics Inrush Current 20 amps maximum for one cycle 20 ms Output Voltage Drop 1 5 volts maximum Response Time On 1 ms maximum Response Time Off 1 2 cycle maximum Output Leakage 3 mA maximum at 120 volts AC 6 mA maximum at 240 volts AC Current Required from 5 V Bus 25 amp VME System designed to support the VME standard C 1 Refer to GFK 0867B or later for product standards and general specifications Forinstallations requiring compliance to more stringent requirements for example FCC or European Union Directives refer to Installation Requirements for Conformance to Standards Table 2
10. ve and incandescent loads The module will operate D HON most size 4 contactors B S o B1 9 LED indicators which give the ON OFF status of each S oa point on the logic PLC side of the circuit as well as an B2 S s LED to indicate the status of the fuses are located at the S top of the module If one or more of the fuses should B3 O S blow this LED will turn ON S ae HON The module is mechanically keyed to ensure correct re c1 O 9 eE H N placement with a similar module type in the field I O S P Oaa references are user configurable without the use of jump c2 S H N ers or DIP switches on the module OQ S Com Configuration is done using the configuration func 3 9 O O9 tion of the MS DOS or Windows programming 9 S 5 O software running on Windows 95 or Windows NT S ae over Ethernet TCP IP or through the SNP port The O S em Programming Software configuration function is ne O 9S pon installed on the programming device The program S ming device can be an IBM XT AT PS 2 or com D3 patible Personal Computer Sar li E MODULE OBSADIL Stt Although this module is configured as a 16 point out U aa put only outputs 1 through 12 are available to be refer enced in your program For example if the starting reference is Q0017 then valid references are Q0017 through Q0028 IBMand PS 2are registered trademarks of International Business Machines Corporation MS DOS Windows Windows 95 and Windows NT are

Download Pdf Manuals

image

Related Search

Related Contents

  NEC NP-PX800X-08ZL Brochure  SafeGuard Enterprise Tools  ECS G41T-M motherboard  Philips Salon Multi-Curler HP8697/00    STI Opt Systèmes Motorisés Synthèse: Contrôle Trains Roulants  Groupe opérationnel 2 du Predit 4 Qualité et sécurité des  LiPoRxII Operating instructions for software  L4448 - N4448  