Honeywell ST3000 Safety Manual, 34-ST-25-31

image

Contents

1. NE option as a diagnostic fault The logic solver configuration must consider the slew time of the current signal and ensure that filtering is used to prevent a false diagnostic failure annunciation Reliability data and lifetime limit A detailed Failure Mode Effects and Diagnostics Analysis FMEDA report is available from HONEYWELL This report details all failure rates and failure modes common cause factors for applications with redundant devices and the expected lifetime of the HONEYWELL ST 3000 The HONEYWELL ST 3000 is intended for low demand mode applications up to SIL 2 for use in a simplex 1001 configuration depending on the PFDaycg calculation of the entire Safety Instrumented Function The development process of the HONEYWELL ST 3000 is certified up to SIL3 allowing redundant use of the transmitter up to this Safety Integrity Level depending the PFDavc calculation of the entire Safety Instrumented Function When using the HONEYWELL ST 3000 in a redundant configuration a common cause factor should be included in reliability calculations For details see the FMEDA report The reliability data listed the FMEDA report is only valid for the useful life time of the HONEYWELL ST 3000 The failure rates of the HONEYWELL ST 3000 may increase sometime after this period Reliability calculations based on the data listed in the FMEDA report for mission times beyond the lifetime may yield results that are too optimistic i e the calcu
2. alarms or warnings are present in the transmitter Verify all safety critical configuration parameters Restore the loop to full operation Remove the bypass from the safety PLC or otherwise restore normal operation This test will detect approximately 56 of possible DU failures in the transmitter Proof Test Coverage An alternative proof test consisting of proof test 1 with actual three point pressure calibration plus verification of the temperature measurement will detect approximately 99 of possible DU failures The person s performing the proof test of the HONEYWELL ST 3000 should be trained in SIS operations including bypass procedures transmitter maintenance and company Management of Change procedures Tools required are handheld communicator ST 3000 Safety Manual 11 09 Repair and replacement Any failures that are detected and that compromise functional safety should be reported to the Global Technical Support Center GTS When replacing the HONEYWELL ST 3000 the procedures in the installation manual should be followed FIRMWARE UPDATE In case firmware updates are required they should be performed at the factory The replacement responsibilities are then in place The user will not be required to perform any firmware updates 11 09 ST 3000 Safety Manual Honeywell Process Solutions Honeywell 512 Virginia Drive Fort Washington PA 19034 www honeywell com ps 34 ST 25 31 November 2009 2009 Honeyw
3. in reliability calculations for the safety instrumented functions for which the HONEYWELL ST 3000 is applied The exida exSILentia tool is recommended for these calculations The proof tests must be performed more frequently than or as frequently as specified in the calculation in order to maintain the required safety integrity of the safety instrumented function The following proof test is recommended It consists of a simple HART driven min to max output test The results of the proof test need to be documented and this documentation should be part of a plant safety management system Any failures that are detected and that compromise functional safety should be reported to the Global Technical Support Center GTS Action Bypass the safety PLC or take other appropriate action to avoid a false trip following Management of Change procedures Send a HART command to the transmitter to go to the high alarm current output and verify that the analog current reaches that value This procedure tests for compliance voltage problems such as a low loop power supply voltage or increased wiring resistance This also tests for other possible failures Send a HART command to the transmitter to go to the low alarm current output and verify that the analog current reaches that value This test checks for possible quiescent current related failures Use the HART communicator to view detailed critical and non critical device status to ensure no
4. 1 09 ST 3000 Safety Manual Terms and Abbreviations lool One out of one Basic Safety The equipment must be designed and manufactured such that it protects against risk of damage to persons by electrical shock and other hazards and against resulting fire and explosion The protection must be effective under all conditions of the nominal operation and under single fault condition FMEDA Failure Modes Effects and Diagnostic Analysis Functional Safety The ability of a system to carry out the actions necessary to achieve or to maintain a defined safe state for the equipment machinery plant apparatus under control of the system GTS Global Technical Support Center H ART Highway Addressable Remote Transmitter HFT Hardware Fault Tolerance Low demand mode Mode where the frequency of demands for operation made on a safety related system is no greater than one per year and no greater than twice the proof test frequency PFD ave Average Probability of Failure on Demand Safety Freedom from unacceptable risk of harm Safety Assessment SFF The investigation to arrive at a judgment based on evidence of the safety achieved by safety related systems Further definitions of terms used for safety techniques and measures and the description of safety related systems are given in IEC 61508 4 Safe Failure Fraction the fraction of the overall failure rate of a device that results in either a safe fa
5. Honeywell ST 3000 Smart Transmitter Release 300 with HART Communications Options Safety Manual Doc No 34 ST 25 31 Revision Date November 2009 Notices and Trademarks Copyright 2009 by Honeywell Inc November 2009 While this information is presented in good faith and believed to be accurate Honeywell disclaims the implied warranties of merchantability and fitness for a particular purpose and makes no express warranties except as may be stated in its written agreement with and for its customers In no event is Honeywell liable to anyone for any indirect special or consequential damages The information and specifications in this document are subject to change without notice Honeywell is a U S registered trademarks of Honeywell Inc Other brand or product names are trademarks of their respective owners Honeywell Process Solutions Honeywell 512 Virginia Drive Fort Washington PA 19034 ST 3000 Safety Manual 11 09 About This Document Contact Info World Wide Web The following lists Honeywell s World Wide Web sites that will be of interest to our industrial automation and control customers Honeywell Organization WWW Address URL Corporate http www honeywell com Honeywell Process Solutions http www honeywell com ps Telephone Contact us by telephone at the numbers listed below Organization Phone Number United States and Canada Honeywell Inc 1 800 343 0228 Sales 1 800 525 7439 Service 1
6. eeeaes 1 3 Designing with the HONEYWELL ST 3000 oe eee eeeeeecee eee eeeeeeeeeeeeeeeeeeees 2 Diagnostic RESPONSE TIMenis icri iaiii ai iaidd ie eda Kioii daaa iiid ia aiaia aedade iaiia 2 kote oaeo h1 aia o1 ATE E A A A T 2 Reliability data and lifetime limit ce cceccceesscceeeeeeeeeeeceneeeeeceeeeeeeseseeeeeecseeeeeseneseeeseeeaeeeseesaeeseseeaeens 2 Environmental MMS resisaat T ea alta en hia Aa aba alec S 2 Application liMitS 2iscctvetecte er a hear iy ek eee A ee ee ee 2 4 Installation with the HONEYWELL ST 3000 ccccceeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeenenees 3 Parameter SONGS serogn r rS EE Er loci cg EE acthece scalars cd aubtad laden dg adbotaac tess salon ent 3 5 Operation and Maintenance with the HONEYWELL ST 3000 c0ee 4 AKOO E KE EEE E A EE E E T le hese elite E eleshcr elie ess hdl cae db eceunchadey rie treylelb ast 4 Reparand replacements cescteicgetavksrecadiveineceubsrtuedhbearced EER ERREEN EKTE beak devel ecut thivad NAER OEREN TEKUSA 5 11 09 ST 3000 Safety Manual vi ST 3000 Safety Manual 11 09 1 Requirements Requirements for use of the manual This section is intended for user s who have our ST 3000 Smart Transmitter with either the HART Communication option HC or HART Communication option H6 and the SL SIL option Anything other than these option combinations is not specifically covered by this manual 2 Safety Function Primary Safety Fu
7. ell International Inc Honeywell
8. lated Safety Integrity Level will not be achieved Environmental limits The environmental limits of the HONEYWELL ST 3000 are specified in the User Manual Application limits The application limits of the HONEYWELL ST 3000 are specified in the User Manual If the transmitter is used outside of the application limits the reliability data provided becomes invalid 2 ST 3000 Safety Manual 11 09 4 Installation with the HONEYWELL ST 3000 No special installation is required in addition to the standard installation practices outlined in the ST 3000 Smart Transmitter User Manual However please note that when the device is in safety operation the optional write protect jumper must be set so that the device is write protected and HART devices must be disconnected See ST 3000 Smart Transmitter User Manual for details concerning the write protect jumper Parameter settings The following parameters need to be set in order to maintain the designed safety integrity mA Fault action Upscale Downscale If the standard failsafe option is specified in the model selection number option NE is not specified the transmitter is shipped with a default failsafe direction of upscale 20 8 mA This is acceptable for all high trip applications For low trip applications the fail safe direction is downscale 3 8 mA A jumper on the transmitter may be changed to accomplish this action see the Users Manual If the NAMUR NE43 failsafe
9. nctions The HONEYWELL ST 3000 measures the pressure gauge differential absolute of a process and reports the measurement within a safety accuracy of 2 Secondary Safety Functions The HONEYWELL ST 3000 performs automatic diagnostics to detect internal failures and reports these failures via out of band signals on the 4 20 mA output Systematic Integrity SIL 3 Capable SIL 3 Capability The product has met manufacturer design process requirements of Safety Integrity Level SIL 3 These are intended to achieve sufficient integrity against systematic errors of design by the manufacturer A Safety Instrumented Function SIF designed with this product must not be used at a SIL level higher than the statement without prior use justification by end user or diverse technology redundancy in the design 11 09 ST 3000 Safety Manual 3 Designing with the HONEYWELL ST 3000 Diagnostic Response Time The HONEYWELL ST 3000 will report an internal failure within 15 minutes of fault occurrence worst case Logic Solver Inputs The logic solver must be configured so that the engineering range in the transmitter matches the expected range of the logic solver To take advantage of the internal diagnostics in the ST 3000 the logic solver must be configured to annunciate an out of band current reading greater than 20 8 mA or less than 3 8 mA in standard instrument or greater than 21 0 mA or less than 3 6 mA with Namur
10. option NE is specified in the model selection number the transmitter is shipped with a default failsafe direction of upscale 21 0 mA This is acceptable for all high trip applications For low trip applications the fail safe direction is downscale 3 6 mA A jumper on the transmitter may be changed to accomplish this action see the Users Manual Engineering Range All engineering range parameters must be entered to match the trip points in the safety logic solver These parameters must be verified during the installation and commissioning to ensure that the correct parameters are set in the transmitter Engineering range parameters can be verified by reading these parameters from the local display or by checking actual calibration of the transmitter PV Damping The process safety time must be considered when selecting the PV Damping Time Constant A damping time must be low enough to ensure that the safety instrumented function process safety time is achieved 11 09 ST 3000 Safety Manual 5 Operation and Maintenance with the HONEYWELL ST 3000 Proof test The objective of proof testing is to detect failures within the HONEYWELL ST 3000 that are not detected by the automatic diagnostics of the transmitter Of main concern are undetected failures that prevent the safety instrumented function from performing its intended function The frequency of proof testing or the proof test interval is to be determined
11. ult or a diagnosed unsafe fault SIF Safety Instrumented Function a set of equipment intended to reduce the risk due to a specific hazard a safety loop SIL Safety Integrity Level discrete level one out of a possible four for specifying the safety integrity requirements of the safety functions to be allocated to the E E PE safety related systems where Safety Integrity Level 4 has the highest level of safety integrity and Safety Integrity Level 1 has the lowest SIS Safety Instrumented System Implementation of one or more Safety Instrumented Functions A SIS is composed of any combination of sensor s logic solver s and final element s ST 3000 Safety Manual 11 09 Contents Terms and Abbreviations sinks an aa AAA AA iv 1 Requirements perme ee ane Be Ri eer en renner nrnrt Er reeer crneme er rere ninenrr errr 1 Requirements for use of the manual ecececeeeeeeeeeeeeeeeeeeeeeeeeaeeeeaaeedeeeecaeeeseaeseeeeeeseeeeesaeeseaeeseaeeee 1 2 Safety RUNCIO Ms cok on ek oct Acecote eeauate omen ta maueh ereante emmatameeta erent 1 Primary Safety FUNCIONS siise inian sanec ck acts a due casaeatashcdutued cated a eva taal ccnducded aa E A 1 Secondary Safety FUNCTIONS ccccccceeeeeceeeeceeeeeeeaeeeeeeeeceaeeecaaeeseaaeseeeesaeeesaaeseeaeeseeeeeesaeeseeeeeeeseaes 1 Systematic Integrity SIL 3 Capable 0 0 eecceccceeceeeeeeeeeeeeeee cae eesaaaeseeeeeseaeeesaaeeseaeeseeeeseaeeeesaeesnae