Home
T 1000 PLUS
Contents
1. Designed for testing relays and transducers 9 ing y 5 The relay test set T 1000 PLUS is suited for the ELAY TYPE NO With phase angle shifter Distance relay 3 sets 14 Frequency generator Soe eee 3 Under over voltage relay 27 59 Test results and settings are saved into local memory irectional r relay 3 Field relay 40 High power outputs E T G Oscilloscope function for current and voltage Phase sequence voltage relay 47 Large graphical display Instantaneous over current relay 50 Compact and lightweight Power factor relay 55 Possibility to synchronize several T 1000 PLUS test sets JON EEES EEN 50 Ground detector relay 64 USB and RS232 interface irectional over current rela E i Phase angle out of step relay 78 2 auxiliary contacts for the test of autoreclosers nes aes Frequency relay 81 Lockout relay 86 Voltage directional relay 91 Tripping relay 94 000o 1 r a 0000 000 Mam 2056A 1556s ACAux233 6 V 50 003 He oc aux 110 6 v Ennemi A The instrument contains three separate generators Main generator that generates either AC current AC voltage DC voltage Auxiliary AC voltage generator that generates an independent phase shiftable AC voltage Auxiliary DC voltage generator that generates the DC voltage that powers the relay under test All outputs are adjustable and metered at the same time on the large graphic LCD display T 1000 PLUS can operate without connectio
2. 120V 30093 T 1000 E PLUS 500V Aux Voltage outputs 220 V complete with Software TDMS 71093 T1000 PLUS 15 Hz 17093 Heavy Duty Transport Case 18093 Set of test cables for models T 1000 PLUS 40093 D 1000 differential relay test module 41024 FT 1000 PLUS Mains Filter Unit The document is subject to change without notice GB T 1000 PLUS 10 08
3. Via the multi function menu knob it is possible to select the measurement of angle or frequency Readings resolution and accuracy see table MEASUREMENT RANGE RESOLUTION ACCURACY Phase 0 360 ili 1 1 Digit Frequency 40 000 499 999 1 mHz 0 1 1 mHz Other measurements MEASUREMENT UNIT Active Power P V cos j W Reactive Power Q I V sin j VAr Apparent Power S I V VA Impedance Z V I Ohm Active Impedance Component R Z cos j Ohm Reactive Impedance Component X Z sin j Ohm External inputs measurement It is possible to meter current or voltage input External current measurement Two inputs 20 mA and 10 A Range resolution accuracy see table below INPUT RANGE RESOLUTION ACCURACY 20 mA 0 02ADC 01 mA 0 5 0 1 mA 10A 1 999 AAC 1 mA 1 2 mA 10A 9 99 AAC 10 mA 1 20 mA 10A 1 999 A DC 1 mA 0 5 2mA 10A 9 99 A DC 10 mA 0 5 20 mA External voltage measurement Maximum input voltage 600 V AC or DC Range resolution and accuracy see table below RANGE RESOLUTION ACCURACY 9 999 V AC 2 mV 1 10mV 99 99 V AC 10 mV 1 20 mV 599 9 V AC 100 mV 1 200 mV 9 999 V DC 2 mV 0 5 10 mV 99 99 V DC 10 mV 0 5 20 mV 599 9 V DC 100 mV 0 5 200 mv OTHER CHARACTERISTICS T 1000 PLUS local memory Test settings can be stored and recalled from the T 1000 PLUS local memory up to 10 test
4. elay test module The differential relay test module D 1000 allows the test of the differential relay curve and also of the harmonic restraint characteristic The module performances are the followings Input from the test set auxiliary AC voltage output Output 0 to 5 A CA Output power 5 VA Dimension 325 x 290 x 290 mm Weight 7 kg FT 1000 current filter This external module removes AC current distortions T 1000 PLUS 15 Hz In this model the minimum auxiliary AC voltage frequency is 15 Hz ISA Srl Via Prati Bassi 22 21020 Taino VA Italia Tel 39 0331 956081 Fax 39 0331 957091 Web site www isatest com E Mail isa isatest com Maximum output power becomes 20 VA The auxiliaru DC voltage is removed Other characteristics are unchanged APPLICABLE STANDARDS The test set conforms to the EEC directives regarding Electromagnetic Compatibility and Low Voltage instruments A Electromagnetic Compatibility Directive no 2004 108 EC B Low Voltage Directive Directive n 2006 95 EC Applicable standards for a class instrument pollution degree 2 Installation category Il CEI EN 61010 1 In particular Inputs outputs protection IP 2X CEI 70 1 Operating temperature 0 to 50 C storage 40 C to 70 C Relative humidity 10 80 without condensing Ordering information T 1000 PLUS 91093 T 1000 PLUS complete with Software TDMS 220V 81093 T 1000 PLUS complete with Software TDMS
5. med in cycles RANGE RESOLUTION ACCURACY From 0 to 9 999 s ims 1ms 0 005 From 10 0 to 99 99 s 10ms 10 ms 0 005 From 100 0 to 999 9 s 100ms 100 ms 0 005 From 1 000 to 9 999 s 1s 1 s 0 005 Possibility to test automatic reclosers Maximum number of reclosing commands 99 2 auxiliary contacts are available Contacts range 5 A 250 V AC 120 V DC OUTPUT CURRENT AND VOLTAGE MEASUREMENTS The following outputs are displayed at the same time on the LCD Current measurement OUTPUT RANGE RESOLUTION ACCURACY 10A 1 999 A 1 mA 1 5 mA 19 99 A 10 mA 1 20 mA 40A 7 999 A 4 mA 1 20 mA 79 99 A 40 mA 1 80 mA 100A 19 99A 10 mA 1 50 mA 199 9A 100 mA 1 200 mA 249 9A 100 mA 1 200 mA Voltage measurement OUTPUT RANGE RESOLUTION ACCURACY 250VAC 19 99 10 mV 1 50 mV 199 9 V 100 mV 1 200 mV 299 9 V 300 mV 1 300 mV 300VDC 19 99 V 10 mV 0 5 50 mV 199 9 V 100 mV 0 5 200 mV 399 9 V 300 mV 0 5 300 mV 65 130VAC 19 99 V 10 mV 1 20 mV 199 9 V 100 mV 1 200 mV 260VAC 19 99V 10 mV 1 20 mV 199 9 V 100 mV 1 200 mV 299291 300 mV 1 300 mV 130VDC 19 99V 10 mV 0 5 20 mV 199 9 V 100 mV 0 5 200 mV 260VDC 19 99V 10 mV 0 5 20 mV 199 9 V 100 mV 0 5 200 mV 299 9 V 300 mV 0 5 300 mV Angle and frequency measurement
6. n to a PC With the multi purpose knob and the LCD display it is possible to enter the MENU mode that allows to set many functions that make T 1000 PLUS a very powerful testing device with manual and semi automatic testing capabilities and with the possibility to transfer test results to a PC via USB or RS232 interface These results can be recorded displayed and analysed by the power ful TDMS software that operates with all WINDOWS versions starting from WINDOWS 98 included T 1000 PLUS Specification Main generator The main generator has three outputs currents voltage AC voltage DC The following specifications apply to the separate usage of these outputs AC current outputs RANGE CURRENT MAXIMUM LOAD RECOVERY A OUTPUT POWER TIME TIME AC A VA S min 100 30 300 steady 100 800 60 15 250 1000 1 5 40 12 300 steady 40 800 60 15 10 5 400 steady 10 800 60 15 AC voltage outputs RANGE VOLTAGE V OUTPUT MAXIMUM POWER LOAD TIME RECOVERY TIME AC V VA S min 250 250 500 steady 250 750 10 45 DC voltage outputs RANGE VOLTAGE MAXIMUM LOAD RECOVERY V OUTPUT POWER TIME TIME DC V W S min 300 300 300 steady 300 500 10 45 Other features of main outputs Zero crossing control Main AC outputs are generated and stopped as the output waveform crosses zero High resolution adjustment control Overload alarm message Thermal protection Possibility to reduce
7. settings Test results can be saved into a permanent local memory up to 500 test results saved When the PC is connected setting can also be created and transferred into T 1000 PLUS using the software TDMS When the PC is connected test results can be transferred to the PC via USB or RS232 port using the software TDMS for saving and printing Resistors A set of resistors is supplied for the test of low impedance relays Available values RESISTANCE OHM POWER W MAX CURRENT A 0 5 50 10 1 50 7 22 50 2 15 470 50 0 33 1000 50 0 22 2200 50 0 15 interface Interfaces for connection to PC USB and serial RS232 Power supply Mains supply to be clearly indicated in purchase order 230 V 15 50 60 Hz or 120 V 15 50 60 Hz Maximum supply current 5 A Standard accessories The instrument comes complete with the following items Set of test cables Mains cable R amp 232 and USB cable User s manual Spare fuses no 5 T5A Software TDMS with serial cable TDMS Relay Test Result Weight and dimension Dimensions 380 w x 300 d x 240 h mm Weight 19 kg Case Alluminium case with cover and handle OPTIONS T 1000 E PLUS In this model maximum main and auxiliary AC voltages are 500 V instead of 250 V Heavy duty transport case Connection cables The kit includes 17 cables in all for any kind of connection D 1000 Differential r
8. the output power to one fifth for low burdens Auxiliary AC voltage output The auxiliary AC voltage output is isolated from the main AC current and voltage Range selection software driven by the multi function knob and LCD display Auxiliary voltage power 30 VA continuous duty at full range 40 VA for 1 minute Push button to enable or disable the output Auxiliary AC voltage output RANGE V MAX POWER VA 62 5 40 125 40 250 40 Phase angle shifting Possibility to phase shift the auxiliary AC voltage output with respect to the main current or voltage Phase angle adjustment via the multi function knob Phase angle range from 0 to 360 Adjustment resolution 1 degree Frequency generator amp frequency r o c Possibility to change the frequency of the auxiliary AC voltage output Frequency generation characteristics Frequency range 40 Hz to 500 Hz Frequency adjustment 1 mHz Rate of change 1 mHz s to 99 99 Hz s Auxiliary DC voltage output DC voltage range 10 130 V or 20 240 V DC voltage power 90 W at full range continuous duty with a current limit of 0 9 A 130 V and 0 45 A 240 V Push button to enable or disable the output Timer The electronic digital timer has a fully automatic start and stop both for make and break of the input that can be either a clean dry contact or a contact under voltage wet Metering range can also be perfor
Download Pdf Manuals
Related Search
Related Contents
Sistema de minicomponentes de alta fidelidad An LLVM Back-end for REPLICA: Code Generation for a Multi Supplies How to Olympus FE-230 Quick Start Guide CEREC AC - Sirona - Technical Documentation Southwestern Bell FM2572 Telephone User Manual PDFファイル - 医薬品医療機器総合機構 Leica FlexLine Plus Series User Manual PDF Manual do Proprietário Copyright © All rights reserved.