SNTP OPC Server User`s Manual
Contents
1. Attributes TimeSync Timesync client Timesync status Server Status Attributes TimeSync Timesync server In use 23 Grid Automation Controller COM600 4 0 1MRS757277 SNTP OPC Server User s Manual 4 1 4 2 4 3 24 Operation About this section This section describes the basic operation procedures you can carry out after the been configured After this you can for example monitor and control the condition of connections in network This is done by using the Online diagnostics function in SAB600 Activating COM600 with new configurations For information about activating COM600 with new configuration see COM600 User s Manual SNTP OPC Server diagnostics To view the SNTP OPC Server diagnostics right click the SNTP OPC Server object and select Diagnostic AE Client see Figure 4 3 1 SNTP OPC Server Online diagnostics 1qbX Online attributes Version information Product version File version 1933 Protocol stack version lt n a gt Time synchronization Server Inuse Status Not OK Client Inuse Status Not OK Current Time Synchronization Source Reset Clear log fie M Tool connection SNTP_OPC_Server_Online_Diagnostics png Figure 4 3 1 SNTP OPC Server diagnostics You have the following alternatives e to view version information 1MRS757277 Grid Automation Controller COM600 4 0 SNTP OPC Server User s Manual 4 4
2. Enable Time Syn True Controls if time synchronization client chronization Cli ent False is initially in use or not Default False Enable Time Syn True Controls if time synchronization server chronization is initially in use or not Server False Default False Port Number For 1 65535 Port number for time synchronization Time Synchroniza server tion Server Default 123 3 5 3 Configuring data objects for Internal OPC Data 3 5 3 1 General about configuring data objects for Internal OPC Data Internal data objects describe internal status information of an OPC server for example whether the connection between the and the device IED is working or not When internal 21 Grid Automation Controller COM600 4 0 1MRS757277 SNTP OPC Server User s Manual 3 5 3 2 3 5 3 3 22 information of an OPC server needs to be transferred that is information that does not originate from a device to an OPC Client virtual data objects must be created The SNTP OPC Server supports three internal data object types that provide status information e 3 5 3 2 Integer status INS for OPC internal data e 3 5 3 3 Controllable single point SPC for SNTP OPC internal data e 3 5 3 4 Single point status SPS for OPC internal data Integer status INS for OPC internal data Table 3 5 3 2 1 Configurable INS for OPC internal data properties for OPC Servers Property Para Value or Value range
3. toreset the SNTP OPC Server e to view the event log file toclear the log file B PCS conn 3 Eventlog t t Notepad File Edit Format View Help warning 2010 08 03 05 13 09 544 Configuration BlueBay Simulator 1 AddItem failed storage numeric reg21 Error 2010 08 03 05 13 09 554 configuration Could not connect server Default completely Ext Event log file png Figure 4 3 2 Event log file Diagnostic AE Client Diagnostic events can be monitored and controlled using the Diagnostic AE Client function Click Refresh to update the status information To be able to receive events from a certain device diagnostic events must be enabled for this respective device To enable diagnostic events 1 Right click the device 2 Select Diagnostic AE Client Data object diagnostics For information on data object diagnostics refer to COM600 User s Manual 25 26 1MRS757277 Grid Automation Controller COM600 4 0 SNTP OPC Server User s Manual Index A adding Data obJect u n eer Eq i I EE D WE I HR s A 19 Gateway Objet iis sciet teet ebat ertet estare ei 17 Logical AVISA d pete REDDERET aes 18 logical NOG gir cise sc aie ota chats Reg e ada 18 OPC Server Oelse Eva teens 17 configuration object properties 0 cc cc cececeeeee eee ce cece ce eeee ce eeeeaeeeaeeeecaaeesaeeeeaaeeeseeeeseeeseeeesaes 19 Controllable single point SPC POPC eS ta re atadas 22 D Data object AGGING eem 19 data object diagnostics dr
4. Default Description meter Basic Common Data Common data class according to IEC Class 61850 Addresses Item Tag Path Default None Item tag path for the internal status information The internal server tags that can be used are located in the Attributes nodes that are located under the root line and IED nodes When an attribute tag is referred to in the internal item definitions below it is possible to use either the whole tag path or just the path relative to the IED the internal tags are configured per IED for example Attributes Diagnostic coun ters Transmitted data messages When the whole path is used it must be pre ceded by a slash character for example Channel Name Attributes Dia gnostic counters Transmitted data mes sages Controllable single point SPC for SNTP OPC internal data Table 3 5 3 3 1 Configurable SPC for OPC internal data properties for OPC Servers Property Para Value or Value range Default Description meter Basic Common Data Class Common data class according to IEC 61850 Addresses 1MRS757277 Grid Automation Controller COM600 4 0 SNTP OPC Server User s Manual 3 5 3 4 Property Para Value or Value range Default Description meter Item Tag Path Default None Item tag path for the internal status information The internal server tags that can be used are located in the Attributes nodes that are located under the root l
5. ob ero Ro tete om tub een 25 diagnostics Hil 24 G Gateway object A O EA Ei 17 l Integer status INS DIOPEMMleS O 22 L Logical device adding c te UE REN Ret e A 18 Logical node A m 18 27 Grid Automation Controller COM600 4 0 1MRS757277 SNTP OPC Server User s Manual 28 O object properties configuration E object tree building asier A l E E A AEE EA A AEA OPC Server propertles see e oe oec E a ee ve eee cese e aa 15 OPC Server object adding vic eese e a eb o We Lo edu P properties Controllable single point SPC ssssse eme Integer status INS ciet o e quede lur relie oe cod age ibd e eH eye tod ue cde OBPG SOLVOlt costi ad toute tabs Poke tati 15 Single point status SPS sssssssssssseee eee eene nnne S server dIagrnostiGS d doen eget PEOR OR REB RENE ee Single point status SPS Properties M DE SNTP SUBMETWOMK de T da SNTP Virtual IED OBIECT xcii noo oie nib pete fet as subnetwork Contact us ABB Oy Distribution Automation P O Box 699 FI 65101 VAASA FINLAND Tel 358 10 22 11 Fax 358 10 224 1094 ABB Inc Distribution Automation 655 Century Point Lake Mary FL 32746 USA Tel 1 407 732 2000 Fax 1 407 732 2335 www abb com substationautomation Power and productivity for a better world 1MRS757277 B 31 5 2012 O Copyright 2012 ABB All rights reserved AA ED ED FADED
6. 7 Grid Automation Controller COM600 4 0 SNTP OPC Server User s Manual 3 4 2 3 4 3 3 4 4 H Virtual Subnetwork and objects below it are only needed for diagnostic purpose Adding Gateway object To start building the object tree add a Gateway object in the Communication structure by selecting the project name right click it and select New Communication Gate way Adding SNTP OPC Server object After the Gateway object has successfully been added you can continue building the object tree by adding an SNTP OPC Server object To add an SNTP OPC Server object 1 Select the Gateway object in the communication structure and right click it 2 Select New Time Synchronization SNTP OPC Server By using the SCL Import function it is possible to import an entire server s or individual device s configurations without having to insert them manually To open the SCL Import function right click the desired object and select SCL Import For more information about the SCL Import function see COM600 User s Manual Adding SNTP Virtual Subnetwork objects optional H Virtual Subnetwork and the objects below it are only used to provide diagnostic status information about the SNTP server or client for the COM600 HMI or other applications After the server object has been successfully added you can continue building the object tree by adding subnetwork objects To add SNTP Virtual subnetwork object 1 Select SNTP
7. Abbreviation Description URCB Unbuffered Report Control Block XML eXtended Markup Language Related documents Name of the manual MRS number COM600 User s manual 1MRS756125 Document revisions Document version date Product revision History A 30 6 2011 Document created B 31 5 2012 Document revised 1MRS757277 Grid Automation Controller COM600 4 0 SNTP OPC Server User s Manual 2 1 2 2 Introduction Functional overview The SNTP OPC Server includes an SNTP server and a client The SNTP server enables SNTP clients for example IEDs to synchronize their time with the time of COM600 The SNTP client of the SNTP OPC Server enables the synchronization of COM600 from an external SNTP server for example GPS Clock device The SNTP server and client functionality can be configured and activated separately The SNTP OPC Server provides diagnostic information about the synchronization status that can be used for example in the COM600 HMI or forwarded to a remote system via a slave protocol IEC 61850 OPC Server also includes the SNTP server and H client functionality The SNTP server and client should be configured either in the IEC 61850 OPC Server or in the SNTP OPC Server but not in both lg SNTP_overview png Figure 2 1 1 System overview 1 Network time source 2 COM600 with SNTP OPC Server 3 Station Automation Builder 600 SAB600 4 Protection and contro
8. OPC Server object 2 Right click the SNTP OPC Server object 3 Select New New or New Virtual SNTP Virtual Subnetwork Grid Automation Controller COM600 4 0 1MRS757277 SNTP OPC Server User s Manual 3 4 5 3 4 6 3 4 7 Adding Virtual IED objects optional After adding a subnetwork you can add virtual device objects To add a Virtual Device object 1 Select a Subnetwork object 2 Right click on the Subnetwork object and select New gt New or New gt Virtual gt SNTP Virtual IED With SCL import function you can import new objects with configurations from an existing file Right click the device and select SCL Import from the shortcut menu To import a new configuration file Click Select File 2 Browse to a new configuration file from the appearing dialog 3 Select the file and click Open 4 Select the device to import from the drop down list You can preview the configur ation on the right 5 Click Import The new preconfigured objects appear in the object tree If the configuration file is large the import may take time To import a configuration file for a different device right click the device select SCL Import again and repeat the steps above For more information about the SCL Import function see COM600 User s Manual Adding Logical Device objects optional Virtual subnetwork and the objects below it are only used for diagnostic purpose Once a Virtual IED object is added
9. OPC Server object and its child objects like subnetworks devices and data objects Indentation is used to indicate the parent child relationship between the objects After you have added the necessary objects to the object tree in the communication structure you need to configure them see 3 5 1 Configuring object properties Table 3 2 1 SNTP OPC Server related objects Description SNTP OPC Server SNTP Virtual Subnetwork SNTP Virtual IED SNTP Virtual Logical Device LD An object representing the SNTP OPC Server Object representing a physical subnetwork The IED object presents a virtual device An object representing a group of functions Each function is defined as a Logical Node A device consists of one or several LDs 1MRS757277 Grid Automation Controller COM600 4 0 SNTP OPC Server User s Manual 3 3 Object Description Logical Node LN An object defined by its data and methods LN is the smallest part of a function that exchanges data Data Object DO Data object is an instance of one of the IEC 61850 Data Object Classes such as Single point status and Measured Value Depending on the class each data object has a set of attributes for monitoring and controlling the object e g value quality and control Configuring SNTP OPC Server properties Table 3 3 1 lists the configurable SNTP OPC Server properties and value ranges for them The actual configura
10. SNTP OPC Server User s Manual Power and productivity for a better world 1MRS757277 Issued 30 6 2011 Version B 31 5 2012 Grid Automation Controller COM600 4 0 SNTP OPC Server User s Manual Contents 1 About this manual s s sssrds ac 5 Toh Copyrights dei nn aaan M Oti eb ettet ease a anaia is 5 Wi2s E e O E E 5 13 Generale e HR dr FE S era ids 5 1 4 Document conventions sssssssssseeeeneene 6 1 5 CUSCO symbols tenen ate Pul bc d mte toe oa re enit 7 E ise CP EE 7 1 Abbreviations d EH ae 8 1 8 Related doc urrients usd repre li 10 1 9 Document revisions ssssssssssssssseeee emen 10 2 Introduction ci iran 11 2 1 Functional overview sess 11 2 2 SNTP OPC Server features eese 11 3 Configurdtilon ui air rne tek vi aia ave rua ni vh nog edu d c Ewa 13 3 1 About this section ooooooooocooocooocconcnccnoncnnncnoncnnnonnncnnncnnnnnnnnnnonononnns 13 3 2 Overview of configuration ccccesscecseeeeteeeeseseceeeceneeenenscees 13 3 3 Configuring SNTP OPC Server properties ssssss 20 3 4 Building object Wee sic core is aes 16 3 4 1 General about building object tree 16 3 4 2 Adding Gateway Object oooooocccccccnoonccoccccccccnnnnanancccnnnnn 17 3 4 3 Adding SNTP OPC Server object ssss 17 3 4 4 Adding SNTP Virtual Subnetwork obj
11. bed in 3 5 1 Configuring object properties Table 3 5 2 1 SNTP OPC Server properties Name Value Value range SNTP Client 1 Address for SNTP Server 1 Port Number 1 65535 Default 123 1 Synchroniza 0 3600 tion Interval Default 15 Description IP address or node name for SNTP Server Primary TCP IP port number Time syncronization interval in seconds If value is 0 no time syn cronization will be done 1MRS757277 Grid Automation Controller COM600 4 0 SNTP OPC Server User s Manual Name Value Value range Description 2 Address for Default None IP address or node name for SNTP SNTP Server Server 2 Port Number 1 65535 TCP IP port number Default 123 2 Synchroniza 0 3600 Time synchronization interval in tion Interval seconds If value is 0 no time syn Default 15 cronization will be done IP address or node name for SNTP Server 3 Address for SNTP Server 3 Port Number 1 65535 TCP IP port number Default 123 3 Synchroniza 0 3600 Time syncronization interval in tion Interval seconds If value is 0 no time syn Default 15 cronization will be done 4 Address for Default None IP address or node name for SNTP SNTP Server Server 4 Port Number 1 65535 TCP IP port number Default 123 4 Synchroniza 0 3600 Time syncronization interval in tion Interval seconds If value is 0 no time syn Default 15 cronization will be done
12. ects optional 17 3 4 5 X Adding Virtual IED objects optional 18 3 4 6 Adding Logical Device objects optional 18 3 4 7 Adding Logical Node objects optional 18 3 4 8 Adding data objects optional 19 3 5 Configuring Objects oe cote mtt tas 19 3 5 1 Configuring object properties sssssssssss 19 3 5 2 Configuring SNTP OPC Server properties 20 3 5 3 Configuring data objects for Internal OPC Data 21 3 5 3 1 General about configuring data objects for Internal OPC Data ococcccccccncccncncnnncnnnnnnnnnns 21 3 5 3 2 Integer status INS for OPC internal data T 22 3 5 3 3 Controllable single point SPC for SNTP OPC internal data eee 22 3 5 3 4 Single point status SPS for OPC internal dadas 23 LMMEOIICdbIPee ias 24 4 1 About this Sectionin a a a E nennen 24 Grid Automation Controller COM600 4 0 1MRS757277 SNTP OPC Server User s Manual 4 2 Activating COM600 with new configurations 24 4 3 SNTP OPC Server diagnostics eeeeeee mmn 24 44 Data object diagnostics cocino e 25 1MRS757277 Grid Automation Controller COM600 4 0 SNTP OPC Server User s Manual 1 1 1 2 1 3 About this manual Copyrights The information in this document is subject to change w
13. g an object tree in the commu nication structure on the left and Object Properties window displaying the object properties on the right H When configuring OPC servers the following characters cannot be used in object names V Grid Automation Controller COM600 4 0 1MRS757277 SNTP OPC Server User s Manual 14 Communication Substation Structure EX E a 8 SNTP 010 Basic El dj Gateway 3 4 x In Use In Use m Process E vent Definitions El 020 Addresses ha Communication Diagnostic E vent Definitions IP Address 127 0 0 1 h Common Event Settings El 060 Control Authorization E Scale Definitions Station Remote Switch OPC Pal Ei am SNTP OPC Server El 070 OPC Alarm and Event B GG SNTP Virtual Subnetwork Device Connection Status Class Device Connection Status E 8 SNTP Virtual IED E Misc El LD SNTP Virtual LD Caption SNTP Virtual IED E LN LLNO Description Virtual IED ms Internal INS SC sior Caption SNTP_example2 Figure 3 2 1 Example view of SAB600 The configuration work can basically be divided into two separate tasks 1 building an object tree and 2 configuring object properties First you need to build an object tree This is done by adding objects to the object tree see 3 4 1 General about building object tree Figure 3 2 1 shows an example of how the object tree may look like after it has been built In the example tree you can see the SNTP
14. ine and IED nodes When an attribute tag is referred to in the internal item definitions below it is possible to use either the whole tag path or just the path relative to the IED the internal tags are configured per IED e g Attributes Diagnostic counters YTrans mitted data messages When the whole path is used it must be preceded by a slash character e g Channel Name Attributes Diagnostic counters Trans mitted data messages Single point status SPS for OPC internal data Table 3 5 3 4 1 Configurable SPS for OPC internal data properties for OPC servers Property Para Value or Value range Default Description meter Common Data Common data class according to IEC Class 61850 Addresses Item Tag Path Client Status Item tag path for the internal status information The internal server tags that Attributes TimeSync Timesync can be used are located in the Attributes client In use nodes that are located under the root line and IED nodes When an attribute tag is referred to in the internal item definitions below it is possible to use either the whole tag path or just the path relative to the IED the internal tags are configured per IED e g Attributes Diagnostic counters Trans mitted data messages When the whole path is used it must be preceded by a Attributes TimeSync Timesync Slash character e g Channel server Timesync status Name Attributes Diagnostic counters Trans mitted data messages
15. ithout notice and should not be construed as a commitment by ABB Oy ABB Oy assumes no responsibility for any errors that may appear in this document In no event shall ABB Oy be liable for direct indirect special incidental or consequential damages of any nature or kind arising from the use of this document nor shall ABB Oy be liable for incidental or consequential damages arising from use of any software or hardware described in this document This document and parts thereof must not be reproduced or copied without written per mission from ABB Oy and the contents thereof must not be imparted to a third party nor used for any unauthorized purpose The software or hardware described in this document is furnished under a license and may be used copied or disclosed only in accordance with the terms of such license Copyright 2012 ABB All rights reserved Trademarks ABB is a registered trademark of ABB Group All other brand or product names men tioned in this document may be trademarks or registered trademarks of their respective holders General This manual provides thorough information on the SNTP OPC Server and the central concepts related to it You find instructions on how to configure SNTP OPC Server related objects The basic operation procedures are also discussed Information in this user s manual is intended for application engineers who configure the SNTP OPC Server This user s manual is divided into follo
16. l devices with SNTP client SNTP OPC Server features The SNTP OPC Server supports the following features e OPC Data Access Server v 1 0 2 0 Grid Automation Controller COM600 4 0 SNTP OPC Server User s Manual 1MRS757277 e OPC Alarms and Events server v 1 10 e SNTP client and server for time synchronization 1MRS757277 Grid Automation Controller COM600 4 0 SNTP OPC Server User s Manual 3 1 3 2 Configuration About this section This section guides you in the configuration tasks required before you can start using the SNTP OPC Server For information on the IEC 61850 data modeling refer to COM 0600 User s Manual Start SAB600 to open a project You can also open and name a new project 1 Select File gt Open Manage Project In the Open Manage Project dialog select the required location for the project Projects on my computer Projects on network 3 Select New Project on the left Enter a Project Name The Description is optional 4 Click Create 5 Click Open Project Overview of configuration Before you can start using the SNTP OPC Server you need to build and configure an object tree in SAB600 to define the Communication structure within the Gateway object The possible objects are e Gateway SNTP OPC Server e SNTP Virtual Subnetwork SNTP Virtual IED e Logical Device objects Logical Node objects e Data objects Figure 3 2 1 shows an example view of SAB600 includin
17. oftware or damage to equipment or property The information icon alerts the reader to relevant facts and conditions QA The tip icon indicates advice on for example how to design your project or how to use a certain function Terminology Term Description Alarm An abnormal state of a condition Alarms and Events AE An OPC service for providing information about alarms and events to OPC clients Data Access DA An OPC service for providing information about process data to OPC clients Data Object DO Part of a logical node object representing specific information for example status or measurement From an object oriented point of view a data object is an instance of a class data object DOs are normally used as transaction objects that is they are data structures Grid Automation Controller COM600 4 0 1MRS757277 SNTP OPC Server User s Manual 1 7 Term Data Set Device Event Intelligent Electronic Device Logical Device LD Logical Node LN LON LON Application Guideline for substation automation LAG OPC OPC item Property Report Control Block SPA SPA device Substation Configuration Lan guage SCL Description The data set is the content basis for reporting and logging The data set contains references to the data and data attribute val ues A physical device that behaves as its own communication node in the network for example protection relay Change of
18. onds If value is 0 no time syn Default 15 cronization will be done Controls if time synchronization client is initially in use or not Enable Time Syn True chronization Cli ent False Default False SNTP Server Controls if time synchronization server is initially in use or not Enable Time Syn True chronization Server False Default False Port Number For 1 65535 Port number for time synchronization Time Synchroniza server tion Server Default 123 Building object tree General about building object tree The object tree is built in the Communication structure of SAB600 see Figure 3 2 1 It is built by adding objects in a logical order starting from the Gateway You have several possible ways to add objects to the object tree in the Communication structure e You can right click the object to which you want to add a child object Then select New Object type group Object name for example New Time Synchroniz ation SNTP OPC Server e Youcan right click the object type and select New gt New A New Object window appears Select the object type you want to add and click OK or double click it e Youcan copy the object Add the objects in the following order Gateway SNTP OPC Server SNTP Virtual Subnetwork optional SNTP Virtual IED optional Logical Device objects optional Logical Node objects optional Data objects optional DISQY A m oS pr 1MRS75727
19. process data or an OPC internal value Normally an event consists of value quality and timestamp A physical IEC 61850 device that behaves as its own commu nication node in the IEC 61850 protocol Representation of a group of functions Each function is defined as a logical node A physical device consists of one or several LDs The smallest part of a function that exchanges data An LN is an object defined by its data and methods A communication protocol developed by Echelon A proprietary method of ABB on top of the standard LON pro tocol Series of standards specifications aiming at open connectivity in industrial automation and the enterprise systems that support industry Representation of a connection to the data source within the OPC server An OPC item is identified by a string object path gt lt property name gt Associated with each OPC item are Value Quality and Time Stamp Named data item The report control block controls the reporting processes for event data as they occur The reporting process continues as long as the communication is available ABB proprietary communication protocol used in substation automation Protection and or Control Product supporting the SPA protocol version 2 5 or earlier XML based description language for configurations of electrical substation IEDs Defined in IEC 61850 standard Abbreviations Abbreviation Description AE Alarms and Events ASDU Applica
20. properties on the right 3 Select the property you want to configure Depending on the property value type configuring is always done either by selecting a predefined value from a drop down combo box or entering a text string or a numerical value in a text field Grid Automation Controller COM600 4 0 SNTP OPC Server User s Manual 1MRS757277 3 5 2 20 Object Properties 5 41 E3 E 010 Basic AE Prog ID ABB SNTP OPC AE Server Instance 1 DA Prog ID ABB SNTP OPC D Server Instance 1 E 020 SNTP Client 1 Address for SNTP Server 10 58 125 143 1 Port Number 123 1 Synchronization Interval 15 2 Address for SNTP Server 2 Port Number 123 2 Synchronization Interval 15 3 Address for SNTP Server 3 Port Number 123 3 Synchronization Interval 15 4 Address for SNTP Server 4 Port Number 123 4 Synchronization Interval 15 Enable Time Synchronization Client False E 025 SNTP Server Enable Time Synchronization Server True Port Number For Time Synchronization Server 123 E Misc SNTP OPC Server Description SNTP OPC Server Caption Figure 3 5 1 1 Example of object properties SNTP_OPC_Server_Object_Properties PNG The available properties for different objects are listed in the following subsections Configuring SNTP OPC Server properties Table 3 3 1 lists the configurable SNTP OPC Server properties and value ranges for them The actual configuration by using SAB600 is performed as descri
21. tion Service Data Unit 1MRS757277 Grid Automation Controller COM600 4 0 SNTP OPC Server User s Manual Abbreviation BRCB DA DMCD DO GW HMI IEC IED LAG LAN LD LMK LN LSG NCC NUC NV OLE OPC P amp C PLC POU RTS SA SCD SCL SFC SLD SNMP SNTP SOAP RCB Description Buffered Report Control Block Data Access Data Message Code Definition Data Object Gateway component connecting two communication networks together Human Machine Interface International Electrotechnical Commission Intelligent Electronic Device LON Application Guideline for substation automation Local Area Network Logical Device LonMark interoperable device communicating in LonWorks network In this document the term is used for devices that do not support the ABB LON LAG communication Logical Node LON SPA Gateway Network Control Center Norwegian User Convention Network Variable Object Linking and Embedding OLE for Process Control Protection amp Control Programmable Logic Controller Program Organization Unit Request To Send Substation Automation Substation Configuration Description Substation Configuration Language Sequential Function Chart Single Line Diagram Simple Network Management Protocol Simple Network Time Protocol Simple Object Access Protocol Report Control Block Grid Automation Controller COM600 4 0 1MRS757277 SNTP OPC Server User s Manual 1 8 1 9
22. tion by using SAB600 is performed as described in 3 5 1 Configuring object properties Table 3 3 1 SNTP OPC Server properties Name SNTP Client 1 Address for SNTP Server 1 Port Number 1 Synchroniza tion Interval 2 Address for SNTP Server 2 Port Number 2 Synchroniza tion Interval 3 Address for SNTP Server Value Value range Description IP address or node name for SNTP Server Primary 1 65535 TCP IP port number Default 123 0 3600 Time syncronization interval in seconds If value is 0 no time syn Default 15 cronization will be done Default None IP address or node name for SNTP Server 1 65535 TCP IP port number Default 123 0 3600 Time synchronization interval in seconds If value is 0 no time syn Default 15 cronization will be done IP address or node name for SNTP Server 3 Port Number 1 65535 TCP IP port number Default 123 3 Synchroniza 0 3600 Time syncronization interval in tion Interval seconds If value is 0 no time syn Default 15 cronization will be done 4 Address for Default None IP address or node name for SNTP SNTP Server Server 15 Grid Automation Controller COM600 4 0 1MRS757277 SNTP OPC Server User s Manual 3 4 3 4 1 Name Value Value range Description 4 Port Number 1 65535 TCP IP port number Default 123 4 Synchroniza 0 3600 Time syncronization interval in tion Interval sec
23. two data objects representing Server Status and Client Status are pre populated and included in the object tree To add a Logical Device object 1 Select an SNTP Virtual IED object and right click it 2 Select New New or New Communication SNTP Virtual LD H Each SNTP IED must have at least one Logical Device object as a child object Adding Logical Node objects optional To add a Logical Node 1 Select a Logical Device object and right click it 2 Adda Logical Node object 3 Rename the new object The names of the Logical Node objects have to be unique 1MRS757277 Grid Automation Controller COM600 4 0 SNTP OPC Server User s Manual 3 4 8 3 5 3 5 1 H You should have only one Logical Node 0 LLNO as a child object to a Logical Device object Adding data objects optional To add a data object 1 Selecta Logical Node object and right click it 2 Adda data object 3 Rename the new object The names of the data objects have to be unique However you can have a data object with same name under a different Logical Node Configuring objects Configuring object properties After the objects have been added you must configure the object properties To configure an object 1 Select an object in the object tree of the Communication structure 2 The object properties appear now in the Object Properties window see Figure 3 5 1 1 You can see the selected object on the left and the available
24. us and menu items are boldfaced For example the File menu The following convention is used for menu operations MenuName gt Menu Item CascadedMenultem For example select File New Type The Start menu name always refers to the Start menu on the Windows taskbar System prompts messages and user responses input are shown in the Courier font For example if you enter a value out of range the following message is displayed Entered value is not valid The value must be 0 30 Youcan be asked to enter the string MIF349 in a field The string is shown as follows in the procedure MIF349 Variables are shown using lowercase letters sequence name 1MRS757277 Grid Automation Controller COM600 4 0 SNTP OPC Server User s Manual 1 5 1 6 Use of symbols This publication includes warning caution and information icons that point out safety related conditions or other important information It also includes tip icons to point out useful information to the reader The corresponding icons should be interpreted as follows A A The electrical warning icon indicates the presence of a hazard which could result in electrical shock The warning icon indicates the presence of a hazard which could result in personal injury The caution icon indicates important information or warning related to the concept discussed in the text It may indicate the presence of a hazard which could result in corruption of s
25. wing sections Introduction This section gives an overview of the SNTP OPC Server and its features Grid Automation Controller COM600 4 0 1MRS757277 SNTP OPC Server User s Manual 1 4 Configuration In this section you will find an overview of configuration You are given instructions on how to configure SNTP OPC Server related objects and the model of a substation or system Operation This section covers the basic operation procedures you can carry out when transferring or activating Grid Automation Controller COM600 later referred to as COM600 with new configurations Document conventions The following conventions are used for the presentation of material The words in names of screen elements for example the title in the title bar of a window the label for a field of a dialog box are initially capitalized e Capital letters are used for the name of a keyboard key if it is labeled on the keyboard For example press the ENTER key e Lowercase letters are used for the name of a keyboard key that is not labeled on the keyboard For example the space bar comma key and so on e Press CTRL C indicates that you must hold down the CTRL key while pressing the C key to copy a selected object in this case e Press ESC E C indicates that you press and release each key in sequence to copy a selected object in this case The names of push and toggle buttons are boldfaced For example click OK The names of men