Rockwell Automation Library of Process Objects: Tank Strapping
Contents
1. Manual publication 1756 PM010 for more information 12 Rockwell Automation Publication SYSLIB RMO33C EN P August 2014 Programming Example Storage Tank Level Storage Tank Level Analog input Storage Tank Level Faut al ma s Tank Strapping Table P StrapTbl This example uses the P_StrapT bl instruction to calculate the volume of product in a storage tank based on the measured storage tank level and storage tank strapping table information In this example there is no floating roof so there is no compensation for displacement There are no adjustments based on temperature to account for thermal expansion of the tank Storage Tank Strapping Table Calculation QH013 P StrapThi i Storage Tank volume LY1013 PAn gy Tank1013StrapTbl Analog hput va TOv P Sts UnderMn P Strapping Table The measured storage tank level is connected into the P StrapI bl instruction by using the input Inp Level In this example the level is reported in units of feet The storage tank is a 4 ft tall tank and strapping table information has been provided by the tank vendor Strapping tables often list data in terms of major and minor units In this example data has been provided at 6 in increments The vendor provided strapping table has nine rows and looks like the following table Level ft in Volume barrels 0 00 3 1 0 06 136 6 1 00 264 2 1 06 402 7 2 00 541 4 2 06 692 7 3 00
2. Product Compatibility and Download Center at http www rockwellautomation com rockwellautomation support pcdc page There are no visualization files because the P StrapI bl object does not use display elements or faceplates This section describes the parameter references for this Add On Instruction Tank Strapping Table InOut Structure InOut parameters are used to link the Add On Instruction to external tags that contain necessary data for the instruction to operate These external tags must be of the data type shown Description Tank calibration table level to volume each entry containing the following members e Major Real Number of major units feet meters e Minor Real Number of minor units inches centimeters millimeters Volume Real Tank volume barrels gallons liters at a given level The array size N must be greater than or equal to the number of calibration points provided in the strapping table IMPORTANT Make this array long enough to hold all of the strapping table entries for your tank For example if your tank is 30 ft tall and the strapping table provides data every inch create a tag of type P_StrapTbIRow 361 361 entries empty row 30 x 12 data rows Tank Strapping Table Input Structure Input parameters include the following e Input data elements Inp_ are typically used to connect field inputs from I O modules or signals from other objects e Configuration data elements C
3. all of its products to help ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned follow these procedures United States Contact your distributor You must provide a Customer Support case number call the phone number above to obtain one to your distributor to complete the return process Outside United States Please contact your local Rockwell Automation representative for the return procedure Documentation Feedback Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA DU002 available at http www rockwellautomation com literature Rockwell Automation maintains current product environmental information on its website at http www rockwellautomation com rockwellautomation about us sustainability ethics product environmental compliance page Rockwell Otomasyon Ticaret A S Kar Plaza Is Merkezi E Blok Kat 6 34752 erenk y stanbul Tel 90 216 5698400 www rockwellautomation com Power Control and Information Solutions Headquarters Americas Rockwell Automation 1201 South Second Street Milwaukee WI 53204 2496 USA Tel 1 414 382 2000 Fax 1 414 382 4444 Europe Middle East Africa Rockwell Automation NV Pegasus Park De Kleetlaan 12a 1831 Diegem Belgium Tel 32 2 663 0600 Fax 32 2 663 0640 Asia
4. 844 1 3 06 990 8 4 00 1137 5 To store the strapping table information in the controller the tag Tank1013StrapT bl is created as type P_StrapI blRow 9 a nine element array of strapping table information Rockwell Automation Publication SYSLIB RMO33C EN P August 2014 13 Tank Strapping Table P StrapTbl 14 The parameter Cfg MinorPerMajor is left at its default of 12 so that the instruction can convert the input feet to major and minor units feet and inches This allows the strapping table to be configured by using the same major and minor units as provided by the vendor Table 5 Strapping Table Calculation Examples Major Minor Volume Tank1013StrapTbI 0 0 0 3 1 Tank1013StrapTbI 1 0 6 136 6 Tank1013StrapTbI 2 1 0 264 2 Tank1013StrapTbI 3 1 6 402 7 Tank1013StrapTbI 4 2 0 5414 Tank1013StrapTbI 5 2 6 692 7 Tank1013StrapTbI 6 3 0 844 1 Tank1013StrapTbI 7 3 6 990 8 Tank1013StrapTbI 8 4 0 1137 5 The InOut tag Cfg CalTbl ofthe P StrapI bl instruction is modified to point to the new array Tank1013StrapTbl to provide the instruction with the strapping table information The output of P_StrapT bl is then connected to another P AIn instruction The output is the calculated volume of the storage tank The local configuration tags Cfg_Desc Cfg_Label and Cfg_Tag are not required to be set The P StrapI bl instruction does not include visualization elements global objects or facepl
5. Pacific Rockwell Automation Level 14 Core F Cyberport 3 100 Cyberport Road Hong Kong Tel 852 2887 4788 Fax 852 2508 1846 Publication SYSLIB RM033C EN P August 2014 Supersedes Publication SYSLIB RM033B EN P September 2013 Copyright 2014 Rockwell Automation Inc All rights reserved Printed in the U S A
6. Part 1 The instruction calculates the following items e Total Observed Volume TOV e Free Water Volume FW e Correction for Temperature of Tank Shell CTSh e Floating Roof Adjustment FRA e Gross Observed Volume GOV the primary output of this instruction All calculations require the overall level input and the tank calibration table strapping table The FW calculation is a specific requirement when calculating petroleum storage to adjust for free water content This requires an additional level signal for the product water interface The CTSh calculation compensates for thermal expansion of the storage tank If used this calculation requires these measurements and configuration settings e Product temperature and the ambient temperature e Configuration of the tank shell coefficient of linear expansion fraction per degree e Calibration temperature for the tank calibration table e Configuration constant for weighting the two measured temperatures a reasonable default is provided The FRA calculation compensates the level measurement for displacement caused by a floating roof This calculation requires a measurement or input of the product actual density and additional configuration data about the floating roof The final GOV calculation is provided without correction for product density and temperature other than the shell temperature above or included sediment and water Those calculations depend on the product n
7. Reference Manual Process Automation System Rockwell Automation Library of Process Objects Tank Strapping Table P StrapTbl Version 3 1 T Y A Allen Bradley Rockwell Software Automation Important User Information Read this document and the documents listed in the additional resources section about installation configuration and operation of this equipment before you install configure operate or maintain this product Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes laws and standards Activities including installation adjustments putting into service use assembly disassembly and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice If this equipment is used in a manner not specified by the manufacturer the protection provided by the equipment may be impaired In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by R
8. ates However these string parameters are provided for use in custom visualization elements if desired Rockwell Automation Publication SYSLIB RMO33C EN P August 2014 Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products At http www rockwellautomation com support you can find technical and application notes sample code and links to software service packs You can also visit our Support Center at https rockwellautomation custhelp com for software updates support chats and forums technical information FAQs and to sign up for product notification updates In addition we offer multiple support programs for installation configuration and troubleshooting For more information contact your local distributor or Rockwell Automation representative or visit http www rockwellautomation com services online phone Installation Assistance If you experience a problem within the first 24 hours of installation review the information that is contained in this manual You can contact Customer Support for initial help in getting your product up and running United States or Canada 1 440 646 3434 Outside United States or Canada Use the Worldwide Locator at http www rockwellautomation com rockwellautomation support overview page or contact your local Rockwell Automation representative New Product Satisfaction Return Rockwell Automation tests
9. calibration table data for the tank This instruction interpolates level between strapping table calibration points linearly Do not use this instruction if you have a spherical tank a conical tank or other tank shape for which the volume does not vary more or less linearly with level To determine the mass of product in the tank take the volume result from the P StrapIbl instruction and compensate for product density with further calculations See the American Petroleum Institute API Manual of Petroleum Measurement Standards MPMS for the appropriate calculations The P_StrapT bl instruction is intended only as a calculation function between other blocks and so no HMI components are provided For a faceplate or alarm send the calculated corrected volume to a P AIn Analog Input instruction See the Rockwell Automation Library of Process Objects Basic Analog Input P AIn Reference Manual publication SYSLIB RMOOL for alarming and display information Tank Strapping Table P_StrapTbl Required File Controller Code InOut Parameter Data Type Cfg_CalTbl P_StrapTblRow N Table 2 P_StrapTbl Input Parameters Input Parameter Data Type Enableln BOOL The Add On Instruction import P StrapIbl 3 1 00 AOLLSX must be imported into the controller project to use the instruction in the project The service release number boldfaced can change as service revisions are created The import file can be downloaded from the
10. cation SYSLIB RMO33C EN P August 2014 3 Table of Contents Notes 4 Rockwell Automation Publication SYSLIB RMO33C EN P August 2014 Preface This document is updated throughout for version 3 1 of the Rockwell Automation Library of Process Objects Changes for this revision are marked by change bars shown in the right margin Software Compatibility and Table 1 Summary of Changes Content Revision Topic Page Changed title from PlantPAx Library of Process Objects to Rockwell Automation Library of Process Front Cover Objects Changed version of Rockwell Automation Library of Process Objects from 3 0 to 3 1 5 8 Changed references to Knowledgebase Answer ID 62682 to Product Compatibility and Download 5 Center Additional Resources table added Rockwell Automation Library of Process Objects Basic Analog 6 Input Reference Manual publication SYSLIB RM001 Input Output Parameters Tables Added Alias For column 8 9 Operations added Simulation section 12 For the latest compatible software information and to download the Rockwell Automation Library see the Product Compatibility and Download Center at http www rockwellautomation com rockwellautomation support pcdc page For general library considerations see Rockwell Automation Library of Process Objects publication PROCES RMO002 Rockwell Automation Publication SYSLIB RMO33C EN P August 2014 5 Additional Resources The
11. fg_ are used to set configurable capabilities and features of the instruction Default Description Ladder Diagram If the rung in condition is true the instruction s Logic routine executes If the rung in condition is false the instruction s EnablelnFalse routine executes Function Block Diagram If true or not connected the instruction s Logic routine executes If the parameter is exposed as a pin and wired and the pin is false the instruction s EnablelnFalse routine executes Structured Text No effect The instruction s Logic routine executes Inp_Level REAL Input Tank innage level feet or meters Rockwell Automation Publication SYSLIB RMO33C EN P August 2014 Table 2 P_StrapTbl Input Parameters Tank Strapping Table P StrapTbl Input Parameter Data Type Default Description Inp_FWLevel REAL 0 0 Input Tank innage free water interface level feet or meters Inp_ObsAPI REAL 30 5 Input Observed density degrees API at product temperature This is used for floating roof compensation to calculate displacement based on weight of roof Inp_AvgProdTemp REAL 60 0 Input Average product temperature degrees Fahrenheit or Celsius Inp_AmbTemp REAL 60 0 Input Ambient temperature degrees Fahrenheit or Celsius Cfg_MinorPerMajor REAL 12 0 Table Minor units inches centimeters millimeters per major unit feet or meters type 0 0 if minor units not
12. lude visualization elements global objects or faceplates However these local configuration tags for descriptive strings are provided for use in custom visualization elements if desired Tag Name Data Type Default Description Cfg_Desc STRING_40 eee Description for display on HMI This string is shown in the title bar of the faceplate able Cfg_Label STRING_20 Strapping Table Label for graphic symbol displayed on HMI This string appears on the graphic symbol Cfg_LevellEU STRING_8 Feet Level engineering units for display on HMI Cfg_Tag STRING_20 P StrapTbI Tagname for display on HMI This string is shown in the title bar of the faceplate Cfg_TempEU STRING_8 Deg F Temperature engineering units for display on HMI Cfg_VolumeEU STRING_8 Gallons Volume engineering units for display on HMI 10 Rockwell Automation Publication SYSLIB RMO33C EN P August 2014 Operations Tank Strapping Table P StrapTbl The P StrapI bl Add On Instruction uses tank calibration data and a tank level measurement to calculate tank volume Tank calibration data can be obtained from the tank manufacturer or design firm or determined through calibration Example calibration methods are provided by the American Petroleum Institute s API Manual of Petroleum Measurement Standards MPMS section 2 2A or 2 2B This instruction performs its calculations by using the same methods described in API MPMS Section 12 1
13. monitor one analog value typically from a channel of an analog input module and deal with alarms when the analog value exceeds user specified thresholds high and low http www rockwellautomation com literature To order paper copies of technical documentation contact your local Allen Bradley distributor or Rockwell Automation sales representative Rockwell Automation Publication SYSLIB RMO33C EN P August 2014 Function Block P StrapTbl Strapping Table Inp Level d Inp_FW Level Cfg_CalTbl Val TOV Val FW Val TSh Val CTSh Val FRA Val GOV Guidelines Functional Description Rockwell Automation Publication SYSLIB RMO33C EN P August 2014 Tank Strapping Table P StrapTbl The P StrapIbl Tank Strapping Table Add On Instruction calculates the volume of product in an upright cylindrical tank given the level of the product and the tank calibration table This instruction can optionally compensate for free water at the bottom of the tank given a product water interface level or for thermal expansion of the tank shell given the coefficient of linear expansion of the shell material and product and ambient temperatures This instruction also can optionally compensate for a floating tank roof if the product density is provided Use this instruction in these situations e You want to determine the volume of product in an upright cylindrical tank given its level e You have the Strapping Table tank
14. nstruction Its output state always reflects Enableln input state Val TOV REAL Raw total observed volume from Cal Table barrels gallons liters Val FW REAL Free Water Volume barrels gallons liters Val TSh REAL Calculated tank shell temperature degrees Fahrenheit or Celsius Val CTSh REAL Correction for temperature of tank shell multiplier Val FRA REAL Floating roof adjustment volume barrels gallons liters Val GOV REAL Primary value Gross observed volume see API MPMS 12 1 1 Sts UnderMin BOOL Inp Level is below lowest level in strapping table Sts_OverMax BOOL Inp_Level is above highest level in strapping table P_StrapTbl BOOL Unique parameter name for auto discovery Rockwell Automation Publication SYSLIB RMO33C EN P August 2014 9 Tank Strapping Table P StrapTbl Table 4 P_StrapTbl Local Configuration Tags Tank Strapping Table Local Configuration Tags Configuration parameters that are array string or structure data types cannot be configured as parameters for Add On Instructions Configuration parameters of these types appear as local tags to the Add On Instruction Local tags can be configured with RSLogix 5000 software by opening the Instruction Logic of the Add On Instruction instance and then opening the Data Monitor on a local tag These parameters cannot be modified by using controller logic or RSLogix 5000 software export import functionality The P_StrapT bl instruction does not inc
15. ockwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited Throughout this manual when necessary we use notes to make you aware of safety considerations WARNING Identifies information about practices or circumstances that can cause an explosion in a hazardous environment which may lead to personal injury or death property damage or economic loss ATTENTION Identifies information about practices or circumstances that can lead to personal injury or death property damage or economic loss Attentions help you identify a hazard avoid a hazard and recognize the consequence P IMPORTANT Identifies information that is critical for successful application and understanding of the product Labels may also be on or inside the equipment to provide specific precautions SHOCK HAZARD Labels may be on or inside the equipment for example a drive or motor to alert people that dangerous voltage may be present BURN HAZARD Labels may be on or inside the equipment for example a drive or motor to alert people that surfaces may reach dangerous temperatures ARCFLASH HAZARD Labels may be on or inside the equipment for example a motor control center to alert people to potential Arc Flash Arc Flash will cause severe inju
16. ot just the tank calibration table and are beyond the scope of this general purpose instruction Rockwell Automation Publication SYSLIB RMO33C EN P August 2014 11 Tank Strapping Table P_StrapTbl No Modes or Alarms The P StrapI bl Add On Instruction only performs calculations and does not have any modes or alarms The instruction does not contain any embedded P_Mode or P_ Alarm instructions To provide High High High Low and or Low Low threshold alarms for the input or output of P_StrapT bl use the P_AIn Analog Input instruction Refer to the Rockwell Automation Library of Process Objects Basic Analog Input P AIn Reference Manual publication SYSLIB RMOOI for more information Simulation The P StrapI bl Add On Instruction does not have simulation capability Use the simulation capability of associated analog input instructions to simulate level or temperature inputs or volume outputs Execution The following table explains the handling of instruction execution conditions Condition Description Enableln False false rung No EnablelnFalse logic is provided The instruction maintains its last state when Enableln is false Powerup prescan first scan No Pre scan or First Scan logic is provided The P StrapTbl instruction simply performs its calculation every scan when Enableln is true Postscan No SFC Postscan logic is provided Refer to the Logix5000 Controllers Add On Instructions Programming
17. ry or death Wear proper Personal Protective Equipment PPE Follow ALL Regulatory requirements for safe work practices and for Personal Protective Equipment PPE gt gt gt Allen Bradley Rockwell Software Rockwell Automation RSLogix Logix5000 FactoryTalk PlantPAx and ControlLogix are trademarks of Rockwell Automation Inc Trademarks not belonging to Rockwell Automation are property of their respective companies Preface Tank Strapping Table P StrapTbl Table of Contents Software Compatibility and Content Revision sseusueues 5 Additional Resourcevelva secen en eese oer Art URP a Uh 6 Guidelines oi dodo chet tele eon wee el cel e T ar Aunt CHI Uk 7 Functional Description ss seseversvisida enue ea bus cron eerie ee RES 7 Required Ellas oi asistas Set erate wed whe soe b peu ata Sala tk teta Drs 8 Controller Code iic duced oco tp E LR dee eR Ua eei inian 8 Tank Strapping Table InOut Structure c cieee se o vex eter terre 8 Tank Strapping Table Input StXuctufe sisse rene base 8 Tank Strapping Table Output Structure x eere rrr em emnt 9 Tank Strapping Table Local Configuration Tags 10 Operationsa eoe cesc ic a ua i dud Ete ot a MONA DUANE A 11 NoModes r Alarms seco ae od ca stile rn beue Aa aa 12 Simulation oce ee er epe p ee Re P E Dod ta 12 PXCCULON eos esL M COR DN OS Chae Vd D EU 12 Programming Example is isses qoa ue siet en ue peli RA ax bese n PE 13 Rockwell Automation Publi
18. se documents contain additional information concerning related products from Rockwell Automation Resource PlantPAx Process Automation System Selection Guide publication PROCES SG001 Description Provides information to assist with equipment procurement for your PlantPAx system PlantPAx Process Automation System Reference Manual publication PROCES RMOO1 Provides characterized recommendations for implementing your PlantPAx system Rockwell Automation Library of Process Objects publication PROCES RM002 Provides general considerations for the PlantPAx system library of process objects FactoryTalk View Machine Edition User Manual publication VIEWME UM004 Provides details on how to use this software package for creating an automation application FactoryTalk View Site Edition User Manual publication VIEWSE UM006 Provides details on how to use this software package for developing and running human machine interface HMI applications that can involve multiple users and servers distributed over a network Logix5000 Controllers Add On Instructions Programming Manual publication 1756 PM010 Provides information for designing configuring and programming Add On Instructions Rockwell Automation Library of Process Objects Basic Analog Input Reference Manual publication SYSLIB RM001 You can view or download publications at Provides information on how to use the Add On Instruction to
19. used Cfg_Has TSh BOOL 0 0 No correction for temperature of tank shell 1 Include correction for temperature of tank shell Cfg_HasFRA BOOL 0 0 Do not use floating roof adjustment 1 Include floating roof adjustment to account for displacement of fluid level Cfg_CalTemp REAL 60 0 Temperature of tank calibration typically 60 F or 15 C Cfg_ShellCoefOfExp REAL 6 2E 06 Tank shell linear coefficient of thermal expansion 1 per degree Fahrenheit or 1 per Celsius Cfg K REAL 7 0 Temperature weighting type 0 0 for insulated tank see API MPMS 2 2A app D Cfg_FloatRoofLevel REAL 0 0 Lowest level at which to add subtract floating roof compensation feet Cfg FloatRoofCalAPI REAL 30 5 Degrees API for which table includes floating roof data Cfg_FloatRoofVolPerAPI REAL 2 5 Adjustment to table values for API lt gt CalAPI volume degrees API typically a negative number Table3 P StrapTbl Output Parameters Tank Strapping Table Output Structure Output parameters include the following e Value data elements Val are numeric outputs of the instruction for use by the HMI Values also can be used by other application logic or software packages e Status data elements Sts_ are bit outputs of the instruction for use by the HMI Status bits also can be used by other application logic Output Parameter Data Type Description EnableOut BOOL eae output The EnableOut signal is not manipulated by this i
Download Pdf Manuals
Related Search
Related Contents
Livre - Cité scolaire Pierre Larousse IP-011 Parts and Service Manual FUCILE - Bignami BDP-CX7000ES diviseuse-bouleuse volumetrique notice d`utilisation et d`entretien LX400e Manual Italiano Instructions de Montage et d`Utilisation RS EN 1004-8-12 Transparente Exprés Productivo ChromaPremier® Pro 74700S™ Copyright © All rights reserved.