JY997D14001F USER`S MANUAL
Contents
1. 3 Termination of cable end Strip the coating of strand wire and twist the cable core before connecting it or strip the coating of single wire before connecting it An alternative connection is to use a ferrule with insulating sleeve Manufacturer Model Pressure bonding tool CRIMPFOX ZA 3 ALO 5 0WE or CRIMPFOX UD 6 Phoenix Contact Co Ltd Strand wire single wire Stick terminal with insulating sleeve Insulation sleeve Contact area Crimping area Manual Hardware Edition Another PLC equipment Seo Shared grounding Good condition Another PLC equipment I I Independent grounding Best condition Another PLC equipment oS Common grounding Not allowed The grounding wire size should be AWG 22 20 0 3 0 5 mm The grounding point should be close to the PLC and all grounding wire should be as short as possible 4 Specifications scale of 10 V when ambient temperature is 25 C 5 C e 1 0 100mV for full scale of 10 V when ambient temperature is 0 C to 55 C If the external load resistance Rs is less than 5kQ the value calculated from the following formula will be added Addition will be 100mV per e 0 5 80 1A for full scale of 16mA when ambient temperature is 25 C 5 C
2. JY 997D14001F A JAPANESE VA ate MITSUBISHI Side B ENGLISH 5 Connect the special adapter fig C to the Special adapter slide lock Used to connect additional special adapters onto the left side of this special adapter Applicable standards 3 FX3U 4DA ADP units made in June 2005 or later comply with the EC Directive EMC Changes for the Better Directive and UL standards UL cUL Further information can be found in the following manual 4 Special adapter connector cover main unit as PROGRAMMABLE CONTROLLERS Refer to the FX3G Series Hardware Manual Manual No JY997D33401 Remove this cover to connect additional special adapters to the left side shown on the MELSECF Refer to the FX3u Series Hardware Manual Manual No JY997D18801 5 Direct mounting hole 2 holes of 4 5 0 18 mounting screw M4 screw right Refer to the FX3uc D DSS Series Hardware Manual Manual No Not used when connecting to FX3UC Series PLC 6 Slide back the FX3U 4DA ADP JY997D28601 special adapter 6 POWER LED green Lit while 24V DC power is supplied properly to terminals 24 and 24 7 Terminal block European type Connect the analog output voltage current signal and 24V DC power supply 8 Special adapter connector Used to connect this special adapter to PLC main unit or special adapter 9 DIN rail mounting hook 10 Special adapter fixing hook 11 Special adapter connector Used to connect comm
3. 4 Use 2 core shielded twisted pair cable for the analog output lines and separate the analog output lines from other power lines or inductive lines 2 24V DC service power supply of the FX3G FX3U Series PLC can also be used 3 Ground the shielded wire at one point on the signal receiving side 4 2 General Specifications Fi or the general specifications refer to the manual of the PLC main unit The items other than the following are equivalent to those of the PLC main unit Item Specification This manual confers no industrial property rights or any rights of any other kind nor does it confer any patent licenses Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual Dielectric withstand voltage Conforming to JEM 1021 pew ne for ons minute Between all terminals and ground terminal of PLC Insulation resistance 5MQ or more by 500V DC megger main unit 4 3 Power Supply Specifications Item Specification D A conversion 24V DC 20 15 150mA for 24V DC circuit driving power Connect a 24V DC power supply to the terminal block Warranty Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi opportunity loss or lost profits caused by faults in the Mitsubishi products damage secondary damage ac
4. e 1 0 160uA for full scale of 16mA when ambient temperature is 0 C to 55 C Total accuracy indicated 5 Connect the 8 ee CAUTION AE 100 0 9 special adapter mn Rs 47 AA fig B to the Ley 0 31 PRECAUTIONS connector i P e FX3U FX3UC Series PLC 200 us 2 6mm 0 1 414mm 0 55 e Do not disassemble or modify the PLC DIA conversion se Sick tcfrcireal with i i M r Doing so may cause fire equipment failures or malfunctions earversion The data will be updated at every scan time of the PLC adapter as Bee eee eee SNA WEN ag wire eh a039 A WIE WEN propor cana For repair contact your local Mitsubishi Electric distributor time e FX3G Series PLC 250 ps i shown on the sheath referring to the above outside dimensions or otherwise the wire cannot be k i The data will be updated at every scan time of the PLC right inserted easily e Do not drop the product or exert strong impact to it 6 Slide back the The tightening torque must be 0 22 to 0 25N m Doing so may cause damage special adapter I slide lock fig A 3 2 Power Supply Wiring Hepes A CAUTION 10V 20mAe of the connector For the power supply wiring refer to the FX3G FX3u FX3UC Series A Output z I gt necie User s Manual Analog Control Edition e Please contact a certified electronic waste disposal company for the characteristics I 1 z li sae z ale 3 3 Wiring of Analog Output environmentall
5. Part Names and Terminal Layout Manual name Manual No lock fig B of FX3G FX3U FX3UC 5 10 2 1 Connection to the FX3U Series PLC the main unit i Describes specifications for Procedure to fix the Series JY997D16701 i trol and special User s Manual MODEL CODE Olina mathod for EX8G 6 1 Turn off the power ESSN f ipera Analog Control 09R619 programming method for FX3G Disconnect all the cables connected to the PLC main unit and special adapter and P g C Edition FX3U FX3UC Series PLC 7 demount the main unit and special adapter mounted on DIN rail or mounted directly using screws Sa SIE AAIEASUE Nv A 2 Install an expansion board to the main unit 2 3 Connection to the FX3UC 32MT LT 2 Series PLC alia ing M I MODECO Pe ig quinetdctone 8 S A A For the expansion board installation procedure refer to the following manual For details refer to the FX3uc Series User s Manual Hardware Edition sis aL ate i OT lca wjoj Refer to the FX3u Series User s Manual Hardware Edition r Basic amp Applied eee andidevices g g 3 Remove the special adapter connector cover on Jnstruction Edition joje the expansion board fig A FX3G Series JY997D31301 Explains FX3G Series PLC When connecting this product to another special User s Manual MODEL CODE specifications for I O wiring adapter please replace the expansion board in Hardware Edition 09R521 installation and maintenance
6. installation or wiring work 24V DC T 24 7 FX3G Series PLC Ver 1 00 or later from first production Failure to do so may cause electric shock or damage to the product 2 I It gt F pEr Mak to ob the followi ti der t t The version number can be checked by monitoring D8001 as the last three digits ake sure to observe the following precautions in order to prevent any Grounding indicate it damage to the machinery or accidents due to abnormal data written to the PLC under the influence of noise 1 Do not bundle the main circuit line together with or lay it close to the main circuit high voltage line or load line Otherwise noise disturbance and or surge induction are likely to take place As a guideline lay the control line at least 100mm 3 94 or more away from the main circuit or high voltage lines 2 Ground the shield wire or shield of the shielded cable at one point on the PLC However do not use common grounding with heavy electrical systems Make sure to properly wire to the European terminal board in accordance with the following precautions Failure to do so may cause electric shock a short circuit wire breakage or damage to the product The disposal size of the cable end should be 9mm 0 35 Tightening torque should be between 0 22 and 0 25N m Twist the end of strand wire and make sure that there are no loose wires Ground resistance 1002 or less VO I ch O Drepresents the channel number
7. o gt 4000 4080 eas TRANSPORT AND CAUTION Digital input 5 Digital input Using alee AERE 4DA ADP STORAGE PRECAUTIONS 7 i 3 Wiring 1 Shielded block e The product is a precision instrument During transportation avoid any impacts lt The alegre ey adopted to insulate the analog output vo lt Failure to do so may cause failures in the product After transportation verify the Insulation area omae i g WIRING pecs 10 lt cho operations of the product method e The DC DC converter is adopted to insulate the power PRECAUTIONS DANGER 3 COMO supply line from the analog output area Usi I e Channels are not insulated from each other sing curren E i pes ars Rawr ata the power supply externally before output 4 1 Applicable PLC Occupied 0 point This number is not related to the maximum number of ee eee vot o lt P 5 points input output points of the PLC Failure to do so may cause electric shock or damage to the product YOK Tor 1 cho Model name Applicability hr J Tw COMO FX3U Series PLC Ver 2 20 or later from first production 3 WIRING PRECAUTIONS Z CAUTION External power supply wiring e Make sure to cut off all phases of the power supply externally before attempting installation or wiring work 24V DC 24 Failure to do so may cause electric shock or damage to the product 2 Ver 1 20 or later from the production manufactured in May 2004 with SER No 45 FX3G Series PLC Ver 1 00 or later f
8. purpose part for general Do not solder plate the electric wire ends VOC 1smA industries and has not been designed or manufactured to be incorporated in Do not connect more than the specified number of wires or electric wires Interface driving 5V DC aer is supplied from the internal power supply of a device ba system used in purposes related to human life 7 of unspecified size power F e Before using the product for special purposes such as nuclear power electric p main unit power aerospace medicine or passenger movement vehicles consult with Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed Make sure to properly wire to the FX3G FX3U FX3UC Series PLC in accordance with the following precautions Failure to do so may cause electric shock a short circuit wire breakage or damage to the product The disposal size of the cable end should follow the dimensions KA MITSUBISHI ELECTRIC CORPORATION described in this manual i Ea enti HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 Tightening torque should follow the specifications in this manual JAPAN HIMEJI WORKS 840 CHIYODA CHO HIMEJI JAPAN Mitsubishi Electric e This product has been manufactured under strict quality control However when installing the product where major accidents or losses could occur if the product fails install appropriate backup or failsafe functions in the system
9. AINTENANCE CAUTION EO 0 90 special adapter p 0 34 Rs 47 AA fig B to the LIY 0 31 PRECAUTIONS e FX3U FX3UC Series PLC 200 us connector m m i i conversion ee tAmm 0 5 a ee or malfunctions eer Cine data will bs updated at every sean tine oftheir LC adapter as When using a stick terminal with insulating sleeve choose a wire with proper cable For repair contact your local Mitsubishi Electric distributor ime e FX3G Series PLC 250 us shown on the sheath referring to the above outside dimensions or otherwise the wire cannot be g a 5 The data will be updated at every scan time of the PLC right inserted easily e Do not drop the product or exert strong impact to it 6 Slide back the The tightening torque must be 0 22 to 0 25N m Doing so may cause damage special adapter i slide lock fig A 3 2 Power Supply Wiring Heian A CAUTION 10V T 20mA ne connector For the power supply wiring refer to the FX3G FX3u FX3UC Series A Output z i gt Sapa User s Manual Analog Control Edition e Please contact a certified electronic waste disposal company for the characteristics 5 1 I z i a 3 3 Wiring of Analog Output environmentally safe recycling and disposal of your device PA l i S4mA i p 7 5 i i i lt Sa fig B For the terminal configuration refer to Section 1 2 So 40004080 S
10. Failure to do so may cause fire equipment failures or malfunctions Do not touch the conductive parts of the product directly Doing so may cause device failures or malfunctions Connect special adapter securely to their designated connectors Loose connections may cause malfunctions 2 1 Connection to the FX3U Series PLC Procedure 1 Turn off the power Disconnect all the cables connected to the PLC main unit and special adapter and demount the main unit and special adapter mounted on DIN rail or mounted directly using screws 2 Install an expansion board to the main unit For the expansion board installation procedure refer to the following manual Refer to the FX3u Series User s Manual Hardware Edition 3 Remove the special adapter connector cover on the expansion board fig A When connecting this product to another special adapter please replace the expansion board in the above description with a special adapter and perform the procedure as indicated 4 Slide the special adapter slide lock fig B of the main unit When connecting this product to another special adapter please replace the main unit in the above description with a special adapter and perform the procedure as indicated 5 Connect the special adapter fig C to the main unit as shown on the right 6 Slide back the special adapter slide lock fig B of the main unit to fix the special adapter fig C Connection pr
11. J 997D14001F JAPANESE Fd a MITSUBISHI PROGRAMMABLE CONTROLLERS MELSECF Side B ENGLISH Changes for the Better FX3U 4DA ADP USER S MANUAL JY 997D14001 Manual Number Revision F U Date September 2008 This manual describes the part names dimensions mounting and specifications of the product Before use read this manual and the manuals of all relevant products fully to acquire proficiency in handling and operating the product Make sure to learn all the product information safety information and precautions Store this manual in a safe place so that it can be taken out and read whenever necessary Always forward it to the end user Registration The company and product names described in this manual are registered trademarks or the trademarks of their respective companies Effective September 2008 Specifications are subject to change without notice 2005 Mitsubishi Electric Corporation j J L Safety Precaution Read these precautions before use This manual classifies the safety precautions into two categories DANGER and NCAUTION Indicates that incorrect handling may cause hazardous conditions resulting in death or severe injury DANGER Indicates that incorrect handling may cause hazardous conditions resulting in medium or slight personal injury or physical damage Z CAUTION Depending on the circu
12. al block European type 1 Wire size Wiring to analog device should use 20 22 AWG wire Description Item Voltage output 0 to 10 V DC Current output Analog output 4 to 20mA DC 2 Install a connector conversion adapter to the main unit 2 Applicable cable following figure for the meee conversion adapter installation procedure refer to the Type Wire size gna gt For details refer to the FX3G Series User s External load 5kQ to a External load 5009 or less following manual R F Manual Hardware Edition igital input 12 bits binary Refer to the FX3G Series User s Manual Hardware Edition Single wire 0 3mm to 0 5mm AWG22 to 20 For details refer to the FX3u Series User s i iti Resolution 2 5mV 10V 4000 4uA 16mA 4000 3 Remove the special adapter connector 2 wire 2 pieces of 0 3mm AWG22 Manual Hardware Edition For details refer to the FX3uc Series User s e 0 5 50mV for full cover when connecting this product to another special adapter Removal of the special adapter connector cover is not required when connecting this product to the connector conversion adapter Slide the special adapter slide lock fig A of the connector conversion adapter When connecting this product to another special adapter please replace the connector conversion adapter in the above description with a special adapter and perform the procedure as
13. cident compensation caused by special factors unpredictable by Mitsubishi damages to products other than Mitsubishi products and to other duties e This product has been manufactured as a general purpose part for general industries and has not been designed or manufactured to be incorporated in Do not solder plate the electric wire ends 5V DC 15mA a F fi Do not connect more than the specified number of wires or electric wires Interface driving i i i a device of systemiused Iniputposes related to human Ife nnect t pi aes 5V DC power is supplied from the internal power supply of e Before using the product for special purposes such as nuclear power electric of unspecified size p main unit Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed Make sure to properly wire to the FX3G FX3U FX3UC Series PLC in accordance with the following precautions Failure to do so may cause electric shock a short circuit wire breakage or damage to the product The disposal size of the cable end should follow the dimensions described in this manual Tightening torque should follow the specifications in this manual power aerospace medicine or passenger movement vehicles consult with Mitsubishi Electric e This product has been manufactured under strict quality control However when installing the product where major accidents or losses could occur if the product fails install a
14. e FX3G FX3U Series PLC can also be used Dielectric withstand B00 AE faut Conforming to JEM 1021 fF P 2 Ground the shield wire or shield of the shielded cable at one point on the A i i i ivinad si for one minute i arranty PLC However do not use common grounding with heavy electrical 3 Ground the shielded wire atone point onthe signal receiving side voltage Se ea tee Mitsubishi will not be held liable for damage caused by factors found not to be systems Insulation resistance 5MO or more by 500V DC megger main unit the cause of Mitsubishi opportunity loss or lost profits caused by faults in the Mitsubishi products damage secondary damage accident compensation Make sure to properly wire to the European terminal board in accordance prapory P caused by special factors unpredictable by Mitsubishi damages to products other than Mitsubishi products and to other duties with the following precautions Failure to do so may cause electric shock a short circuit wire breakage or 4 3 Power Supply Specifications damage to the product The disposal size of the cable end should be 9mm 0 35 Item Specification A For safe use Tightening torque should be between 0 22 and 0 25N m D A conversion 24V DC 20 15 150mA for 24V DC Twist the end of strand wire and make sure that there are no loose wires circuit driving power Connect a 24V DC power supply to the terminal block This product has been manufactured as a general
15. e Sup Ish tie ne recommen fat shiciged CA PS OUA SRUB omer communication or analog special adapter product Make sure to learn all the product information safety information and EMC protection is provided then users may experience temporary loss or 2 Installation accuracy between 10 in very heavy industrial areas precautions However Mitsubishi Electric suggest that if adequate EMC precautions are fol Store this manual in a safe place so that it can be taken out and read whenever necessary Always forward it to the end user lowed for the users complete control system users should expect accuracy as Registration specified in this manual The company and product names described in this manual are registered e Sensitive analog cable should not be laid in the same trunking or cable trademarks or the trademarks of their respective companies For installation uninstallation details refer to the following manuals s Refer to the FX3G Series User s Manual Hardware Edition 2 2 Connection to the FX3uc D DSS Series PLC Refer to the FX3u Series User s Manual Hardware E n Procedure 1 Turn off the power Disconnect all the cables connected to the PLC and demount the PLC from Refer to the FX3uc Series User s Manual Hardware Edition conduit as high voltage cabling Where possible users should run analog INSTALLATION the DIN rail Effective September 2008 cables separately PRECAUTIONS DANGER i Specifica
16. ecautions Connect all the high speed I O special adapters before connecting other special adapters when they are used in combination Do not connect a high speed I O special adapter on the left side of a communication or analog special adapter 2 2 Connection to the FX3uc D DSS Series PLC Procedure 1 Turn off the power Disconnect all the cables connected to the PLC and demount the PLC from the DIN rail 2 Remove the special adapter connector cover fig A 3 Slide the special adapter slide lock fig B of the main unit When connecting this product to another Bo special adapter please replace the main unit in the above description with a special adapter and perform the procedure as A indicated 4 Connect the special adapter fig C to the main unit as shown on the right 5 Slide back the special adapter slide lock fig B of the main unit to fix the special adapter fig C 2 3 Connection to the FX3UC 32MT LT 2 Series PLC For details refer to the FX3uc Series User s Manual Hardware Edition 2 4 Connection to the FX3G Series PLC 3 1 Applicable cable and terminal tightening torque 3 4 Grounding 4 4 Performance Specifications Procedure 3 1 1 Terminal block European type Grounding should be performed as stated below Description 1 Turn off the power 1 Wire size e The grounding re
17. h voltage cabling Where possible users should run analog cables separately e Good cable shielding should be used When terminating the shield at Earth ensure that no earth loops are accidentally created e When reading analog values EMC accuracy can be improved out by averaging the readings This can be achieved either through functions on the analog special adapters or through a users program in the FX3U C Series PLC main unit 1 Outline The FX3U 4DA ADP adapter for analog output hereinafter called 4DA ADP is a special adapter to add four analog output points 1 1 Incorporated Items Verify that the following product and items are included in the package Product Manual This manual 1 2 External Dimensions Part Names and Terminal Layout 5 10 98 3 86 106 4 18 Special adapter connector cover is removed 1 DIN rail mounting groove DIN rail DIN46277 2 Name plate 3 Special adapter slide lock Used to connect additional special adapters onto the left side of this special adapter 4 Special adapter connector cover Remove this cover to connect additional special adapters to the left side 5 Direct mounting hole 2 holes of 4 5 0 18 mounting screw M4 screw Not used when connecting to FX3UC Series PLC 6 POWER LED green Lit while 24V DC power is supplied properly to terminals 24 and 24 7 Terminal block European type Connect the analog o
18. mstances procedures indicated by A CAUTION may also cause severe injury It is important to follow all precautions for personal safety Associated Manuals Manual name Manual No Description FX3G FX3U FX3UC r PRE Series JY997D16701 Bese es spoon ons for User s Manual MODEL CODE araegepnra ath d for FX3G Analog Control 09R619 aD memod aa na og FX3U FX3UC Series PLC Edition FX3G FX3U FX3UC Series JY997D16601 Describes PLC programming Programming Manual MODEL CODE for basic applied instructions Basic amp Applied 09R517 and devices Instruction Edition FX3G Series JY997D31301 Explains FX3G Series PLC User s Manual MODEL CODE specifications for I O wiring Hardware Edition 09R521 installation and maintenance FX3U Series JY997D16501 Explains FX3U Series PLC User s Manual MODEL CODE specifications for I O wiring Hardware Edition O9R516 installation and maintenance FX3UC Series JY997D28701 Explains FX3UC Series PLC User s Manual MODEL CODE specifications for I O wiring Hardware Edition 09R519 installation and maintenance How to obtain manuals For product manuals or documents consult with the Mitsubishi Electric dealer from who you purchased your product Applicable standards FX3U 4DA ADP units made in June 2005 or later comply with the EC Directive EMC Directive and UL standards UL cUL Further information can be found in the following manual Refer to the FX3G Se
19. ppropriate backup or failsafe functions in the system sa MITSUBISHI ELECTRIC CORPORATION HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN HIMEJI WORKS 840 CHIYODA CHO HIMEJI JAPAN
20. ries Hardware Manual Manual No JY997D33401 Refer to the FX3u Series Hardware Manual Manual No JY997D18801 Refer to the FX3uc D DSS Series Hardware Manual Manual No JY997D28601 Refer to the FX3uc 32MT LT 2 Hardware Manual Manual No JY997D31601 Regarding the standards that relate to the main unit please refer to either the FX series product catalog or consult with your nearest Mitsubishi product provider Caution for EC Directive The analog special adapters have been found to be compliant to the European standards in the aforesaid manual and directive However for the very best per formance from what are in fact delicate measuring and controlled output device Mitsubishi Electric would like to make the following points As analog devices are sensitive by nature their use should be considered care fully For users of proprietary cables integral with sensors or actuators these users should follow those manufacturers installation requirements Mitsubishi Electric recommend that shielded cables should be used If NO other EMC protection is provided then users may experience temporary loss or accuracy between 10 in very heavy industrial areas However Mitsubishi Electric suggest that if adequate EMC precautions are fol lowed for the users complete control system users should expect accuracy as specified in this manual e Sensitive analog cable should not be laid in the same trunking or cable conduit as hig
21. rom first production FX3UC Series PLC The version number can be checked by monitoring D8001 as the last three digits Make sure to observe the following precautions in order to prevent any damage to the machinery or accidents due to abnormal data written to the Ground Grounding indicates PLC under the influence of noise 1002 or less 4 2 General Specifications 1 Do not bundle the main circuit line together with or lay it close to the main V I ch O Drepresents the channel number For the general specifications refer to the manual of the PLC main unit This manual confers no industrial property rights or any rights of any other kind circuit high voltage line or load line The items other than the following are equivalent to those of the PLC main unit nor does it confer any patent licenses Mitsubishi Electric Corporation cannot be Otherwise noise disturbance and or surge induction are likely to take 1 Use 2 core shielded twisted pair cable for the analog output lines and separate held responsible for any problems involving industrial property rights which may place As a guideline lay the control line at least 100mm 3 94 or more the analog output lines from other power lines or inductive lines Item Specification occur as a result of using the contents noted in this manual away from the main circuit or high voltage lines 2 24V DC service power supply of th
22. sistance should be 1009 or less Item eens all the cables connected to the PLC and demount the PLC from Wiring to analog device should use 20 22 AWG wire e Independent grounding should be performed for best results Voltage output Current output e rail a i ing i ing i 2 Applicable cable When independent grounding is not performed perform shared grounding of the Analog output 0 to 10V DC 4 to 20mA DC 2 Install aiconnectpr conversion adapter tothe Malt unit following figure range _ Extemal load 5k21to 1Ma External load 5000 or less For the connector conversion adapter installation procedure refer to the Type Wire size _ For details refer to the FX3G Series User s g i g following manual Manual Hardware Edition Digital input 12 bits binary i j isi ingle wi 2 2 Refer to the FX3G Series User s Manual Hardware Edition Single wire 0 3mm to 0 5mm AWG22 to 20 For details refer to the FX3u Series User s Resolution 2 5mV 10V 4000 4nA 16mA 4000 3 Remove the special adapter connector 2 wire 2 pieces of 0 3mm2 AWG22 i yae see ha heal E cover when connecting this product to gt For details refer to the FX3uc Series User s e 0 5 50mV for full another special adapter 3 Termination of cable end Manual Hardware Edition scale of 10 V when Removal of the special adapter Strip the coating of strand wire and twist the cable core before connecting it or Another Another Another ambient temperature is connec
23. the above description with a special adapter and perform the procedure as indicated FX3U Series JY997D16501 Explains FX3U Series PLC 4 Slide the special adapter slide lock User s Manual MODEL CODE specifications for I O wiring fig B of the main unit Hardware Edition 09R516 installation and maintenance When connecting this product to another special FX3UC Series JY997D28701 Explains FX3UC Series PLC adapter please replace the main unit in the User s Manual MODEL CODE specifications for I O wiring f above description with a special adapter and Hardware Edition 09R519 installation and maintenance 0 7 perform the procedure as indicated Special adapter connector cover is removed How to obtain manuals For product manuals or documents consult with the Mitsubishi Electric dealer from who you purchased your product 1 DIN rail mounting groove DIN rail DIN46277 2 Name plate 3 4 Grounding 4 4 Performance Specifications Grounding should be performed as stated below e The grounding resistance should be 1002 or less e Independent grounding should be performed for best results When independent grounding is not performed perform shared grounding of the 2 4 Connection to the FX3G Series PLC Procedure 1 Turn off the power Disconnect all the cables connected to the PLC and demount the PLC from the DIN rail 3 1 Applicable cable and terminal tightening torque 3 1 1 Termin
24. tion or rain and wind If the product is used in such conditions electric shock fire malfunctions deterioration or damage may occur When drilling screw holes or wiring make sure cutting or wire debris does not 1 Outline The FX3U 4DA ADP adapter for analog output hereinafter called 4DA ADP is a special adapter to add four analog output points 1 1 Incorporated Items Verify that the following product and items are included in the package Product a Indicates that incorrect handling may cause hazardous conditions resulting in death or severe injury DANGER Indicates that incorrect handling may cause hazardous conditions resulting in medium or slight personal injury or physical damage Z CAUTION Manual 4 Connect the Eog ai 3 special Depending on the circumstances procedures indicated by CAUTION may enter the ventilation slits i adapter fig C also cause severe injury Failure to do so may cause fire equipment failures or malfunctions to the main It is important to follow all precautions for personal safety Do not touch the conductive parts of the product directly unit as shown Doing so may cause device failures or malfunctions on the right Connect special adapter securely to their designated connectors 5 Slide back the Associated Manuals Loose connections may cause malfunctions special adapter slide 1 2 External Dimensions
25. tions are subject to change without notice e Good cable shielding should be used When terminating the shield at Earth 2 Remove the special adapter connector ensure that no earth loops are accidentally created e Make sure to cut off all phases of the power supply externally before attempting cover fig A 2005 Mitsubishi Electric Corporation E 3 me installation or wiring work 3 Failure to do so may cause electric shock or damage to the product 3 Slide the special adapter slide lock fig B of the main unit When connecting this product to another B special adapter please replace the main unit in the above description with a special adapter and perform the procedure as A indicated e When reading analog values EMC accuracy can be improved out by averaging the readings This can be achieved either through functions on the analog special adapters or through a users program in the FX3U C Series PLC main unit Safety Precaution Read these precautions before use This manual classifies the safety precautions into two categories DANGER and A CAUTION INSTALLATION PRECAUTIONS Z CAUTION e Use the product within the generic environment specifications described in PLC main unit manual Hardware Edition Never use the product in areas with excessive dust oily smoke conductive dusts corrosive gas salt air Cl2 H2S SOz or NO2 flammable gas vibration or impacts or expose it to high temperature condensa
26. tor cover is not required when strip the coating of single wire before connecting it PLC equipment PLC equipment PLC equipment 25 C 5 C connecting this product to the An alternative connection is to use a ferrule with insulating sleeve _ e 1 0 100mV for full connector conversion adapter Manufact Model P Bondinateel 1 I a a scale of 10 V when e 0 5 80 1A for full scale 4 Slide the special adapter slide lock EWA CY ose HUT LAT sed Independent grounding Shared grounding Common grounding ambient temperature is of 16mA when ambient fig A of the connector conversion P C CRIMPFOX ZA 3 Best condition Good condition Not allowed 0 C to 55 C temperature is 25 C 5 C Phoenix Contact Co Ltd Al 0 5 8WH Pie connecting this product to or CRIMPFOX UD 6 e The grounding wire size should be AWG 22 20 0 3 0 5 mm Totalaccuracy If the external load eH ae oe is full A i i i i resistance Rs is less than Scale of Tonys when another special adapter please replace alphas poni should be close to the PLC and all grounding wire should be dete een ambient temperature is 0 C the connector conversion adapter in Strand wire single wire Stick terminal with insulating sleeve BR SNOESS POSSE from the following formula to 55 C the above description with a special Insulation sleeve Contact area sf il A iti il adapter and perform the procedure as Crimping area 4 Specifications a G cailon will indicated 8 100mV per i ied 8mm M
27. unication or analog special adapters to the left side of the Refer to the FX3uc 32MT LT 2 Hardware Manual Manual No JY997D31601 Regarding the standards that relate to the main unit please refer to either the FX series product catalog or consult with your nearest Mitsubishi product provider USER S MANUAL Seorus canse Jy997D14001 The analog special adapters have been found to be compliant to the European F standards in the aforesaid manual and directive However for the very best per formance from what are in fact delicate measuring and controlled output device Mitsubishi Electric would like to make the following points As analog devices are sensitive by nature their use should be considered care fully For users of proprietary cables integral with sensors or actuators these slide lock fig B of the main unit to fix the special adapter fig C Manual Number Revision 3U describes the part names Date September 2008 Connection precautions Connect all the high speed I O special adapters before connecting other special adapters when they are used in combination This manual dimensions mounting and specifications of the product Before use read this manual and the manuals of E oon those inh erat ror Hadar If NO oth 4DA ADP Do not connect a high speed I O special adapter on the left side of a all relevant products fully to acquire proficiency in handling and operating th
28. utput voltage current signal and 24V DC power supply 8 Special adapter connector Used to connect this special adapter to PLC main unit or special adapter 9 DIN rail mounting hook 10 Special adapter fixing hook 11 Special adapter connector Used to connect communication or analog special adapters to the left side of the 4DA ADP 2 Installation For installation uninstallation details refer to the following manuals Refer to the FX3G Series User s Manual Hardware Edition Refer to the FX3u Series User s Manual Hardware E n Refer to the FX3uc Series User s Manual Hardware Edition INSTALLATION PRECAUTIONS DANGER e Make sure to cut off all phases of the power supply externally before attempting installation or wiring work Failure to do so may cause electric shock or damage to the product INSTALLATION PRECAUTIONS Z CAUTION e Use the product within the generic environment specifications described in PLC main unit manual Hardware Edition Never use the product in areas with excessive dust oily smoke conductive dusts corrosive gas salt air Cl2 H2S SO2 or NO2 flammable gas vibration or impacts or expose it to high temperature condensation or rain and wind If the product is used in such conditions electric shock fire malfunctions deterioration or damage may occur When drilling screw holes or wiring make sure cutting or wire debris does not enter the ventilation slits
29. y safe recycling and disposal of your device 2 Lo S 4mA special adapter 2 o p r 7 r m i fig B For the terminal configuration refer to Section 1 2 TONOA 3 0 40004080 o 4000 4080 i igital i igital inpu Sana vorags TERE 4DA ADP STORAGE PRECAUTIONS ACAUTION Digital input ital inp 3 Wiring 1 Shielded block e The product is a precision instrument During transportation avoid any impacts e The biaa adopted to insulate the analog output LEO vo sy Failure to do so may cause failures in the product After transportation verify the Insulation area trorm te K WIRING lo cho operations of the product method e The DC DC converter is adopted to insulate the power PRECAUTIONS DANGER mr 7 3 COMO supply line from the analog output area Usi T e Channels are not insulated from each other sing curren F eles pine ented the power supply extamally betore output 4 1 Applicable PLC Occupied 0 point This number is not related to the maximum number of Failure to do so may cause electric shock or damage to the product peeee vat 4 E ET Applicability points input output points of the PLC WIRING 3 COMO FX3U Series PLC Ver 2 20 or later from first production PRECAUTIONS Z CAUTION F Ver 1 20 or later from the production manufactured in May External power FX3UC Series PLC R peas supply wiring 2004 with SER No 45 e Make sure to cut off all phases of the power supply externally before I 24 Le attempting