Home
TD 1000 PLUS
Contents
1. 91 The instrument contains three separate generators Main generator that generates either AC current AC voltage DC voltage Auxiliary AC convertible current and voltage generator that generates an independent phase shiftable AC voltage or current Auxiliary DC voltage generator that generates the DC voltage that powers the relay under test All outputs are adjustable and metered at the same time on the large graphic LCD display TD 1000 PLUS can operate without connection to a PC With the multi purpose knob and the LCD display it is possible to enter the MENU mode that allows to set many functions that make TD 1000 PLUS a very powerful testing device with manual and semi automatic testing capabilities and with the possibility to transfer test results to a PC via USB interface These results can be recorded displayed and analysed by the powerful TDMS software that operates with all WINDOWS versions starting from WINDOWS 98 included TD 1000 PLUS Specification Main generator The main generator has three outputs currents voltage AC voltage DC The following specifications apply to the separate usage of these outputs AC current outputs RANGE CURRENT MAXIMUM LOAD RECOVERY A OUTPUT POWER TIME TIME AC A VA S min 100 30 300 steady 100 800 60 15 250 1000 1 5 40 12 300 steady 40 800 60 15 80 1000 1 5 10 5 400 steady 10 800 60 15 20 1000 2 5 AC voltage outputs RANGE VOLTAGE V OUTPUT
2. MAXIMUM LOAD RECOVERY POWER TIME TIME AC V VA S min 250 250 500 steady 250 750 10 45 DC voltage outputs RANGE VOLTAGE MAXIMUM LOAD RECOVERY V OUTPUT POWER TIME TIME DC V W min min 300 300 300 steady 300 500 10 45 Other features of main outputs Zero crossing control Main AC outputs are generated and stopped as the output waveform crosses zero High resolution adjustment control Overload alarm message Thermal protection Possibility to reduce the output power to one fifth for low burdens Auxiliary AC convertible current and voltage generator The auxiliary AC convertible current and voltage generator is isolated from the main AC current and voltage Range selection software driven by the multi function knob and LCD display Auxiliary voltage power 40 VA continuous duty at full range 50 VA for 1 minute Push button to enable or disable the output Auxiliary AC voltage output RANGE V MAX POWER VA 65 50 130 50 260 50 Auxiliary AC current Power 50 VA continuous duty MAX CURRENT A MAX POWER VA 20 50 Phase angle shifting Possibility to phase shift the auxiliary AC voltage output with respect to the main current or voltage Phase angle adjustment via the multi function knob Phase angle range from 0 to 360 Adjustment resolution 1 degree Frequency generator amp frequency r 0 C Possibility to change the frequency of the auxiliary
3. 5 A Standard accessories The instrument comes complete with the following items Set of standard test cables Mains cable USB cable User s manual Spare fuses no 5 T5A Software TDMS with serial cable me 4004 me 00H veaux 000v of amor If vocAux 000y Dep 99090008 TDMS Relay Test Result Weight and dimension Dimensions 380 w x 300 d x 240 h mm Weight 19 kg Case Alluminium case with cover and handle TD 1000 PLus TD 1000 PLUS 15 HZ With two current outputs to test differential relay and with high power at 15 Hz TD 1000 Plus 15 Hz is identical to TD 1000 Plus except for the high power and full range at 15 Hz This allows testing old railway and generator protection relays TD 1000 Plus 15 Hz does NOT have the DC battery simulator Power at 15 Hz 25 VA on all ranges No Auxiliary DC voltage supply Weight 21 kg All other performances are the same as T 1000 PLUS The request of this model must be specified at order OPTIONS Heavy duty transport case Heavy duty black plastics transport case with handle and wheels Connection cables The kit includes cables for any kind of connection TD 1000 PLUS Standard cable kit TD 1000 PLUS Optional cable kit FT 1000 current filter This external module removes AC current distortions It is connected in series to the relay under test and guarantees a sinusoidal waveform also when
4. AC voltage output Frequency generation characteristics Frequency range 15 Hz to 550 Hz Frequency adjustment 1 mHz Rate of change 1 mHz s to 99 99 Hz s Auxiliary DC voltage output DC voltage range 10 130 V or 20 240 V DC voltage power 90 W at full range continuous duty with a current limit of 0 9 A 130 V and 0 45 A 240 V Push button to enable or disable the output Timer The electronic digital timer has a fully automatic start and stop both for make and break of the input that can be either a clean dry contact or a contact under voltage wet Metering range can also be performed in cycles Possibility to test automatic reclosers Maximum number of reclosing commands 99 RANGE RESOLUTION ACCURACY From 0 to 9 999 s ms 1 ms 0 005 From 10 0 to 99 99 s 10ms 10 ms 0 005 From 100 0 to 999 9 s 100ms 100 ms 0 005 From 1 000 to 9 999 s s 1s 0 005 2 auxiliary contacts are available Contacts range 5 A 250 V AC 120 V DC OUTPUT CURRENT AND VOLTAGE MEASUREMENTS The following outputs are displayed at the same time on the LCD Current measurement OUTPUT RANGE RESOLUTION ACCURACY 10A 1 999 A 1 mA 5 MA 19 99 A 10 mA 20 mA 40A 7 999 A 4 mA 20 mA 100A 19 99A 10 mA 50 mA 199 9 A 100 mA 200 mA z el 1 79 99 A 40 mA 1 80 mA 1 i 249 9 A 100 mA 1 200 mA Voltage measurement OUTPUT RANGE PRESOLUTION 2
5. 50 V AC 1 99V 1 mV 19 99 V 10 mV REESE 100 mV 299 9 V 300 mV 1999N 10 mV 199 9N 100 mV 399 9V 300 mV 65 130 VAC 19 99 V 10 mV 199 9 V 100 mV ACCURACY 1 50 mV 1 50 mV 1 200 mV 1 300 mV 300 V DC 0 5 50 mV 0 5 200 mV 0 5 300 mV 1 20 mV F r 7 0 200 mV 260VAC 19 99 V 10 mV 20 mV 199 9 V 100 mV 200 mV 299 9 V 300 mV 300 mV 20AAC 20 00A 10 mA 30 mA 130VDC 19 99 V 10 mV 5 20 mV 199 9 100 mV 0 5 200 mV 260 VDC 19 99 V 10 mV 0 5 20 mV 199 9 100 mV 299 90y 300 mV 0 5 200 mV 0 5 300 mV I it i I i I I I i I it i I I i I I l Angle and frequency measurement Via the multi function menu knob it is possible to select the measurement of angle or frequency Readings resolution and accuracy see table MEASUREMENT RANGE RESOLUTION ACCURACY Phase 0 360 12 1 1 Digit Frequency 15 000 499 999 1 mHz 0 1 1 mHz Other measurements MEASUREMENT UNIT Active Power P I V cos j W Reactive Power Q I V sin j VAr Apparent Power 5 I V VA Impedance Z V I Ohm Active Impedance Component R Z cos j Ohm Reactive Impedance Component X Z sin j Ohm External inputs measurement It is possible to meter current or voltage input External current measurement Two inputs 20 mA and 10 A Range resolution accurac
6. DMS 120V and standard testing cables 93093 TD 1000 PLUS 15 Hz complete with Software TDMS 230V and standard testing cables 95093 TD 1000 PLUS 15 Hz complete with Software TDMS 120V and standard testing cables 17093 18093 16093 43102 13093 11093 12093 T 1000 PLUS T 1000 E PLUS TD 1000 PLUS FAMILY FEATURES COMPARISON TABLE MAIN MAIN MAIN AC V AC V DC MAX A MAX V MAX V AUX VAC MAX V Heavy Duty Transport Case Set of additional test cables FT 1000 Mains Filter Unit SHA 1000 scanning head Outputs transducer with interface connector Connection cable and RJ 45 connector for ABB relays REF542PLUS and REF601 Connection cable for THYTRONIC relays Thysensor series AUX AUX INV AC AC POWER 15 Hz T 1000 Plus 160 250 300 120 V T 1000 Plus 250 250 300 230 V T 1000 E Plus 250 900 300 TD 1000 Plus 160 250 300 120 V TD 1000 Plus 250 250 300 230 V TD 1000 Plus 15 Hz 160 250 300 120 V TD 1000 Plus 15 Hz 250 250 300 230 V 250 250 500 250 250 250 250 10 240 10 240 10 240 20 10 240 20 10 240 20 25 20 25 Hain 050 A 151 AC Aue 2336 v ie oc Aux 10 6 VE EN TD1000 02 2014
7. Designed for testing relays and transducers Two current outputs to test differential relays Convertible current and voltage generator With phase angle shifter Frequency generator 15 550 Hz Test results and settings are saved into local memory High power outputs Oscilloscope function for current and voltage Large graphical display Compact and lightweight Possibility to synchronize several TD 1000 PLUS test sets USB interface 2 auxiliary contacts for the test of autoreclosers In comparison with T 1000 Plus model TD 1000 Plus has two current outputs to test the differential relay characteristic curve and not only the pick up current In addition the frequency of this current can be chan ged as with voltages this allows to test the second har monic restraint characteristic of the differential relay ii po Ain 7 mi p 0 e Main 205 6 A 15565 AC Aux 233 6 Y 30 003 ne rs DC Aux 110 6 V Ext 10 8 mA J O The relay test set TD 1000 PLUS is suited for the testing of the following types of relays Distance relay 3 sets Thermal Directional Power relay Negative sequence over currrent Incomplete sequence relay GMG UME at SL CIC Inverse time over current relay Voltage balance relay Directional over current relay ectional Il Automatic reclosing Load shed Motor protection Voltage directional relay a a T i 48 ng gt 7 86
8. sformer for the power of 220 V AC to supply the scanning head Two safety banana plugs for the connection to TD 1000 PLUS Outputs transducer for low level signal relays The outputs transducer is an option that allows converting the high current and voltage outputs into low voltage signals The option is made of three components The Outputs transducer complete with the interface connector The connection cable from the transducer to a two BNC connectors and one RJ 45 connector for the ABB relays REF542PLUS and REF601 The connection cable from the transducer to one RJ 45 connector for the THYSENSOR series of THYTRONIC relays The items can be ordered separately the Output transducer alone or also one cable or both APPLICABLE STANDARDS The test set conforms to the EEC directives regarding Electromagnetic Compatibility and Low Voltage instruments A Electromagnetic Compatibility Directive no 2004 108 EC B Low Voltage Directive Directive n 2006 95 EC Applicable standards for a class instrument pollution degree 2 Installation category Il CEI EN 61010 1 In particular Inputs outputs protection IP 2X CEI 70 1 Operating temperature O to 50 C storage 40 C to 70 C Relative humidity 5 95 without condensing ORDERING INFORMATION CODE MODULE MODULE 94093 TD 1000 PLUS complete with Software TDMS 230V and standard testing cables 96093 TD 1000 PLUS complete with Software T
9. testing current relays with reverse time characteristics or with heavily saturating bur dens that tend to distort the current waveform Current input ranges 0 5 2 10 50 100 200 A on terminal bushings Maximum power yield 800 VA Filter burden less than 200 VA at 200 A The burden is pro portional to the range 50 VA at 50 A Service 50 A continuous service 200 A for 30 s Selection of the mains frequency 50 or 60 Hz by switch Dimensions 220 x 250 x 310 mm Weight 15 kg SHA 1000 scanning head SHA 1000 is a scanning head that eases the test of energy meters It is an universal scanning head because it can be used both with LED impulse electronic meters and Ferraris rotating disk meters selection is performed via a switch located on the scanning head In addition to this a knob allows to adjust the sensitivity of the head With rotating disk the sensor uses a green light beam that optimizes the recognition of any type of mark With LED recognition the following specification applies Impulse duration more than 60 us With an LED signal having a space ratio 1 2 the frequency must be less than 500 Hz Light wavelength 500 to 960 nm red green and blue ARE NOT detected The option includes The support that allows to keep the scanning head in front of the energy meter maximum height 175 mm The cable 2 m long from the scanning head to TD 1000 PLUS The power supply tran
10. y see table below INPUT RANGE RESOLUTION ACCURACY 20mA O0 02ADC 01 mA 0 5 0 1 mA 10A 1999AAC 1 mA 1 2mA 10A 999AAC 10 mA 1 20mA 10A 1999ADC 1 mA 05 2mA 10A 999ADC 10mA 0 5 20 mA External voltage measurement Maximum input voltage 600 V AC or DC Range resolution and accuracy see table below RANGE RESOLUTION ACCURACY 9 999 V AC 2m 1 10 mV 99 99 V AC 10 mV 1 20 mV 599 9 V AC 100 mV 1 200 mV 9 999 V DC 2mV 0 5 10 mV 99 99 V DC 10 mV 0 5 20 mV 599 9 V DC 100 mM 0 5 200 mV OTHER CHARACTERISTICS TD 1000 PLUS local memory Test settings can be stored and recalled from the TD 1000 PLUS local memory up to 10 test settings Test results can be saved into a permanent local memory up to 500 test results saved When the PC is connected setting can also be created and transferred into TD 1000 PLUS using the software TDMS When the PC is connected test results can be transferred to the PC via USB port using the software TDMS for saving and printing Resistors A set of resistors is supplied for the test of low impedance relays Available values RESISTANCE OHM POWER W MAX CURRENT A 0 5 50 10 1 50 7 22 50 2 15 470 50 0 33 1000 50 0 22 2200 50 0 15 Interface Interfaces for connection to PC USB Power supply Mains supply to be clearly indicated in purchase order 230 V 15 50 60 Hz or 120 V 15 50 60 Hz Maximum supply current
Download Pdf Manuals
Related Search
Related Contents
Manual do Proprietário Samsung SMART CAMERA ST150F Manuel de l'utilisateur サポート&プレゼントBOOK RCA P56938 User's Manual - 1 - 桐生市マスコットキャラクター「キノピー」着ぐるみ貸出要綱 (平成 27 Avaya 1200 Series User Guide Cougar ARCHON computer case Cadillac 2009 Automobile User Manual Techniques de mesure pour l`agroalimentaire Troubleshooting Other Information CONVENTIONAL RAPTOR Copyright © All rights reserved.