ALTIVAR® 18 Adjustable Speed Drive

image

Contents

1. The drive controller is sensitive to the amount of capacitance either phase to phase or phase to ground present on the output power conductors If excessive capacitance is present the drive controller may trip on overcurrent Follow the guidelines below when selecting output cable e Cable type the cable selected must have a low capacitance phase to phase and to ground Do not use mineral impregnated cable because it has a very high capacitance Immersion of cables in water increases capacitance e Cable length the longer the cable the greater the capacitance Cable lengths greater than 100 ft 30 5 m may cause problems e Proximity to other output cables because of the high frequency switching and increased capacitance the drive controller may fault under some conditions e Do not use lightning arrestors on the output of the drive controller Wiring needs minimum inductance to protect the drive controller output from short circuits Provide at least 19 7 in 50 cm of cable at the drive controller output U V W CAUTION DRIVE CONTROLLER SWITCH FAILURE For proper drive controller electronic short circuit protection certain values of inductance may be required in the output power wiring Inductance can be supplied by the power wiring or auxiliary inductors Failure to follow these instructions can result in equipment damage 1997 2000 Schneider Electric All Rights Reserved 13 ALTIVAR 18 Drive Contr
2. Table 13 shows the Level 1 parameters The maximum value is always obtained by pressing and holding the a key The minimum value is always obtained by pressing and holding the O key Table 13 Level 1 Parameters de Factory Max Min i Min Code Function Setting Value Value Ynis Increment Type rdY Drive ready Display FrH Frequency reference enois o r Hz 0 1 Display LCr Motor current ae layed FrH A 0 1 Display rFr Rotation frequency hile y Hz 0 1 Display ULn Maintains voltage running 1 Vv 1 Display bFr Base frequency Select the same 50 50 60 Hz Config frequency as the mains frequency If the value of bFr is changed the drive controller will display nm E as it automatically adjusts the nominal motor voltage UnS and nominal frequency FrS to the following values ATV18 M2 bFr 50 230 V 50 Hz bFr 60 230 V 60 Hz ATV18 M4 bFr 50 400 V 50 Hz bFr 60 460 V 60 Hz The settings of UnS and FrS can be modified in the level 2 parameters ACC Linear acceleration ramp 3 0 3600 0 1 s 0 1 from 0 1 Adjust dEC Linear deceleration ramp 3 0 3600 0 1 s to 999 9 or Adjust f 1 from 1000 These ramps are defined for the base frequency to 3600 For example for a 10 s ramp if bFr 50 Hz O to 25 Hz takes 5 s if bFr 60 Hz O to 30 Hz takes 5 s LSP Low speed 0 0 HSP 0 0 Hz 0 1 Adjust HSP High speed ensure that the 50 0 tFr 12 LSP Hz 0 1 Adjust
3. 30 5 cm e Whenever power and control wiring cross the metallic conduits and non metallic conduits or trays must cross at right angles Branch Circuit Connections All branch circuit components and equipment such as transformers feeder cables disconnect devices and protective devices must be rated for the maximum input current of the ALTIVAR 18 drive controller not the motor full load current The drive controller input current is stamped on the nameplate A WARNING OVERCURRENT PROTECTIVE DEVICES MUST BE PROPERLY COORDINATED To achieve published fault withstand current ratings install the specified fuses listed on the drive controller nameplate and in Table 10 and Table 11 on page 23 Do not connect the drive controller to the power feeder whose short circuit capacity exceeds the drive controller withstand fault rating listed on the drive controller nameplate Failure to follow these instructions can result in death serious injury or equipment damage 12 1997 2000 Schneider Electric All Rights Reserved 52012 008 01B ALTIVAR 18 Drive Controller November 2000 Wiring Output Wiring Precautions 44 WARNING DRIVE CONTROLLER DAMAGE The drive controller will be damaged if input line voltage is applied to output terminals U V W Check the power connections before energizing the drive controller Failure to follow these instructions can result in death serious injury or equipment damage
4. 17 2 7 8 ATV18U90N4 210 300 170 190 280 g 17 6 8 0 ATV18D12N4 17 6 8 0 ATV18D16N4 9 65 15 35 7 48 8 86 14 57 0 40 10 26 4 12 0 ATV18D23N4 245 390 190 225 370 j 26 4 12 0 Dimensions are in inches millimeters ATV18 FAN FLOW RATES Table 6 ATV18 Fan Flow Rates Drive Controller ATV18 U09M2 U18M2 U18N4 Weights are in pounds kilograms Fan Flow Rate Non ventilated ATV18 U29M2 U29N4 8 8 CFM 0 25 m3 minute ATV18 U41M2 U54M2 U72M2 U41N4 U54N4 U72N4 26 5 CFM 0 75 m3 minute ATV18 U90M2 D12M2 U90N4 D12N4 D16N4 D23N4 45 9 CFM 1 3 m3 minute O 1997 2000 Schneider Electric All Rights Reserved ALTIVAR 18 Drive Controller 52012 008 01B Installation Precautions November 2000 INSTALLATION PRECAUTIONS The ATV18 drive controller is a NEMA Open device and must be installed in a suitable environment The environment around the drive controller must not exceed pollution degree 2 requirements as defined in NEMA ICS 1 or IEC 664 When shipped the ATV18 has a protection rating of IP31 and can be operated in an ambient of up to 40 C When installing the drive controller in an enclosure with an ambient of up to 50 C remove the grey tape from the top of the drive controller With the grey tape removed the drive controller has a protection rating of IP20 Figure 2 shows the minimum clearances required around the drive controller for unobstructed ai
5. Do not disconnect link PO between PO and PA ed PA Connection for dynamic braking PB resistance pil models PC Not used D16N4U and D23N4 only U Vv Output connections to motor All models Ww a E or G E Shield or equipment ground connection All models Located on heatsink on ATV18U09M2 and E Equipment ground connection U18M2 Located on metal cable entry plate on other models L1 L2 E PO PA PB U V W E Le L ea LE L L1 L2 L3 eve po ra Ps U V w CE Cy Po L1 12 13 CE ulv G E Figure 7 L Location of Power Terminals O 1997 2000 Schneider Electric All Rights Reserved ATV18U09M2 to U41M2 ATV18U54M2 U72M2 and ATV18U18N4 to U72N4 ATV18U90M2 D12M2 U90N4 D12N4 ATV18D16N4 and D23N4 15 ALTIVAR 18 Drive Controller 52012 008 01B Wiring November 2000 Table 8 Power Terminal Wire Size and Torque 1 ATV18 Maximum Wire Size Torque AWG mm lb in Nem U09M2 U18M2 14 1 5 9 1 0 U29M2 U41M2 U54M2 U72M2 U18N4 U29N4 U41N4 U54N4 U72N4 10 4 tee U90M2 D12M2 U90N4 D12N4 8 6 21 2 4 D16N4 D23N4 6 10 35 4 11175 C copper Equipment Ground Terminal Equipment ground terminals are located on the power terminal strip as shown in Table 7 on page 15 In addition an M5 equipment ground screw terminal is located on the heatsink of the ATV18U09M2 and U18M2 and on the metal cable entry plate on all other units Max
6. Place a DO NOT TURN ON label on drive controller disconnect e Lock disconnect in open position Failure to follow these instructions will result in death or serious injury O 1997 2000 Schneider Electric All Rights Reserved Electrical equipment should be serviced only by qualified personnel No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material 52012 008 01B ALTIVAR 18 Drive Controller November 2000 Table of Contents TABLE OF CONTENTS RECEIVING AND PRELIMINARY INSPECTION 1 STORING AND SHIPPING 4 4 4 4 44 eee 1 TECHNICAL CHARACTERISTICS 2 SPEGIFIGATIONS oa ae Ps de dr nn bead at dette 4 DIMENSIONS votas rare hte heroes RA N bee ls 5 ATV18 FAN FLOW RATES 5 INSTALLATION PRECAUTIONS 6 MOUNTING IN TYPE 12 IP54 METAL ENCLOSURE 7 Calculating Enclosure Size 7 Ventilation i cee setae bbe a bnew dede e 8 ELECTROMAGNETIC COMPATIBILITY EMC 9 Installation precautions for meeting EN55011 Class A 9 ERA eects RR 9 Installation Plan ss bo i ee ea ea ie AA 9 WIRING games a a Ne 11 General Wiring Practices 12 Branch Circu
7. Reassignment of the LI2 logic input Note Before assigning make sure that there is no voltage to the logic input WARNING UNINTENDED EQUIPMENT ACTION Assigning a logic input when it is in state 1 high with voltage present can cause the motor to start Before assigning verify that there is no voltage to the logic input Failure to follow these instructions can result in death serious injury or equipment damage If the function is already assigned to another input it will appear as a choice but will not be saved upon pressing ENT If PS2 and PS4 are both assigned the input assigned to PS4 must be changed before the input assigned to PS2 can be changed IFAIC is assigned for summing with rrS OFF PS4 Config A SAI 2 and one of the logic inputs is assigned to PS2 l the choices for LI2 are OFF not assigned rrS reverse dCl continuous DC injection braking drive In for 5s then at 0 5 ItH A WARNING NO HOLDING TORQUE DC injection braking does not provide holding torque at zero speed DC injection braking does not function during loss of power or drive controller fault When required use separate brake for holding torque Failure to follow these instructions can result in death serious injury or equipment damage FSt Fast stop This function is active when the Ll is at state 0 off JOG Jog Bl PS2 2 preset speeds 3 however display will not flash when ENT is pressed be
8. PI regulator with the system in open loop configuration sensor not connected adjust High Speed setting HSP so that maximum flow or pressure is obtained Then connect the sensor The values of proportional gain r F L and integral gain r I L are factory set to give adequate performance for most applications Factory setting for both parameters is 1 00 meaning that the output is modified by 1 00 times the input error for the proportional component and 1 00 times the input error for one second for the integral component If improved dynamic performance is required these parameters can be adjusted over the range of 1 00 to 100 or if the system is unstable from 0 01 to 0 99 O 1997 2000 Schneider Electric All Rights Reserved 52012 008 01B ALTIVAR 18 Drive Controller November 2000 Function Compatibility Page 32 further explains the adjustment parameters F O Proportional Gain r L Integral Gain and F h 5 Feedback Scaling NOTE The PI Feedback function is not compatible with Preset Speeds or Jog FUNCTION COMPATIBILITY The number of inputs outputs required by a function the number of inputs outputs on the drive controller available for reassignment and the compatibility of the selected functions see Figure 12 limit the number of functions which can be assigned There are 3 assignable logic inputs on the drive controller The following functions require one input reverse DC injection braking fast stop jog
9. Three Phase Output Drive Controller Input Line Motor Power Rated Transient Total Short Catalog Number Current 1 Output Output Dissipated Circuit Three Phase Current Current P Power Rating 200 V 230V In Rated Load A A kw hp A A W A rms sym ATV18U54M2 16 2 14 9 12 3 18 5 104 5 000 ATV18U72M2 20 4 18 8 5 16 4 KI 24 6 141 5 000 ATV18U90M2 28 7 26 5 5 5 75 22 3 33 200 22 000 ATV18D12M2 38 4 35 3 75 10 28 BI 42 264 22 000 11 Values correspond to the amount absorbed by drive controllers supplied by mains with fault capacity equal to short circuit rating indicated in table and under nominal conditions of load and speed of the associated motor without additional inductance 21 For 60 seconds 8 Rated output currents shown are for switching frequencies of 2 2 to 4 kHz If switching frequency is gt 4 kHz and lt 8 kHz derate output current by 5 If switching frequency is gt 8 kHz derate output current by 10 See page 37 for adjustment of switching frequency O 1997 2000 Schneider Electric All Rights Reserved 52012 008 01B ALTIVAR 18 Drive Controller November 2000 Technical Characteristics Table 3 Technical Characteristics 380 220 V 1 15 to 460 270 V 11 10 50 60 Hz 5 Three Phase Input Three Phase Output Drive Controller InputLine MotorPower Rated Transient Total Short Catalog Number Current 2 Output Output Dissipated Circ
10. al z N 3 Transient overtorque j 1 ee 0 5 0 N Hz 50 Hz 13 25 50 60 Hz 1 3 30 60 Figure 14 Typical ALTIVAR 18 Drive Controller Torque Characteristics FACTORY SETTINGS The ALTIVAR 18 is preset for constant torque applications Table 12 lists factory settings Table 12 Factory Settings Function Setting Drive ready when stopped Display Reference frequency when running Base frequency 50 Hz Motor voltage 230 V or 400 V depending on the model Acceleration and deceleration ramps 3s Low speed 0 Hz High speed 50 Hz Frequency loop gain Standard 26 Motor thermal current Nominal drive controller current DC braking current at stop 0 7 times nominal drive controller current for 0 5 s Operation Constant torque with sensorless vector control Logic inputs 2 run directions LI1 LI2 4 preset speeds LI3 LI4 0 Hz 5 Hz 25 Hz 50 Hz Analog inputs Al1 0 to 10 V reference Al2 0 to 10V or AIC 0 to 20 mA summed with Al1 Logic output LO Speed reference attained Deceleration ramp adaptation Switching frequency Automatic in the case of overvoltage when braking 4 kHz To modify these adjustments use the keypad to change the parameter settings The following section explains the keypad and parameters For operation at 60 Hz the bFr and HSP parameters must be adjusted 1997 2000 Schneider Electric All Rights Reserved 52012 008 01B ALTIVAR 18 Drive
11. motor and motor insulation Procedure 3 on page 41 e Check the dynamic braking resistance With the drive disconnected verify the wiring the isolation of the resistance and its ohmic value Procedure 3 on page 41 e Verify the ohmic value of the resistance Ensure that the drive controller horsepower size meets the application e Verify that electromagnetic interference does not affect drive controller operation Replace the drive controller Use L or P law Replace the drive controller 1997 2000 Schneider Electric All Rights Reserved 43 ALTIVAR 18 Drive Controller 52012 008 01B Notes November 2000 NOTES 44 O 1997 2000 Schneider Electric All Rights Reserved 52012 008 01B November 2000 INDEX A ACC 18 30 AIC 17 20 35 36 analog input 20 26 36 automatic reset 24 automatic restart 22 27 37 42 auto tuning fault 43 base frequency 26 30 bFr 26 30 brA 34 braking dc injection 19 21 26 27 31 35 dynamic 15 34 42 43 braking torque 4 branch circuit connections 12 C cable output 13 cable shields 9 10 15 can 38 capacitance maximum 13 clearances minimum 6 COM 17 condensation 8 constant torque 33 control terminals 17 control command wiring 10 CPU 37 current dc injection 32 full load 12 input 12 motor 24 30 motor thermal 26 nominal 26 overcurrent 12 43 D dbF 43 dc injection 21 27 31 32 35 del 35 d
12. scale 3 Reapply power and check for the correct line voltage per the drive controller nameplate rating 4 Remove power and repeat the procedure for L2 amp L3 and L1 amp L3 if wired for three phase 5 When all phases have been measured remove power Remove leads and reinstall covers Procedure 3 Checking the Peripheral Equipment The following equipment may need to be checked Follow the manufacturers procedures when checking this equipment 1 A protective device such as fuses or a circuit breaker may have tripped 2 Aswitching device such as a contactor may not be closing at the correct time 3 Conductors may require repair or replacement 4 Connection cables to the motor or high resistance connections to ground may need to be checked Follow NEMA standard procedure WC 53 5 Motor insulation may need to be checked Follow NEMA standard procedure MG 1 Do not apply high voltage to U V or W Do not connect the high potential dielectric test equipment or insulation resistance tester to the drive controller since the test voltages used may damage the drive controller Always disconnect the drive controller from the conductors or motor while performing such tests CAUTION EQUIPMENT DAMAGE HAZARD Do not perform high potential dielectric tests on circuits while the circuits are connected to the drive controller Any circuit requiring high potential dielectric tests must be disconnected from the drive con
13. the drive controllers at rated load see Tables 1 and 2 on page 2 and Table 3 on page 3 Useful heat exchange surface area S in2 of a wall mounted enclosure generally consists of the sides top and front The minimum surface area required for a drive controller enclosure is calculated as follows Rth Thermal resistance of the enclosure calculated previously S K K Thermal resistance per square inch of the enclosure Rih K 186 with enclosure fan K 233 without enclosure fan Consider the following points when sizing the enclosure e Use only metallic enclosures since they have good thermal conduction e This procedure does not consider radiant or convected heat load from external sources Do not install enclosures where external heat sources such as direct sunlight can add to enclosure heat load e If additional devices are present inside the enclosure consider the heat load of the devices in the calculation e The actual useful area for convection cooling of the enclosure will vary depending upon the method of mounting The method of mounting must allow for free air movement over all surfaces considered for convection cooling The following sample illustrates calculation of the enclosure size for an ATV18U72N4 5 hp drive controller mounted in a Type 12 enclosure e Maximum external temperature T 25 C e Power dissipated inside enclosure P 94 W e Maximum internal temperature T 40 C e Thermal resista
14. treatment ground plane Painted sheet metal can be used on the condition that a good electrical contact is made between the support and fixation surfaces and 2 and 5 O 1997 2000 Schneider Electric All Rights Reserved 9 ALTIVAR 18 Drive Controller 52012 008 01B Electromagnetic Compatibility EMC November 2000 Description of parts in Figure 3 continued 2 3 The ATV18 is mounted directly to the metal plate Ensure that all four corner mounting points have good electrical contact with the metal plate Non shielded input wire or cable connected to the input inductors if used Maintain separation between input wiring and motor wiring as described in General Wiring Practices on page 12 Non shielded wire for the output of the fault relay contacts Maintain separation between fault relay wiring and motor wiring as described in General Wiring Practices on page 12 Fastening and grounding of the shields of cables 6 and 7 must be made as close to the drive controller as possible Strip the shields Use straps with appropriate dimensions on the stripped portions of the shield for fastening to the sheet metal Clamps should be stainless steel The shields must be well clamped to the sheet metal in order to have good contact Shielded cable for connection to motor with shield tied to ground at both ends At the drive controller the shield is connected to the E or G E terminal on the far right o
15. voltage present Many parts in this drive controller including printed wiring boards operate at line voltage DO NOT TOUCH Use only electrically insulated tools Failure to follow these instructions will cause shock or burn resulting in death or serious injury Drive Controllers ATV18 M2 and ATV18U18N4 to D12N4 The voltage is measured between the equipment ground and each terminal on the power terminal strip The equipment ground is located on the heatsink for drive controllers ATV18U09M2 and U18M2 and on the metal conduit entry plate for the other products The power terminal strip is located on the power board as shown in Figure 20 on page 40 A second measurement is made between the PA terminal located on the power terminal strip and the other terminals on the power terminal strip To measure the bus capacitor voltage 1 Disconnect all power from the drive controller 2 Wait 1 minute to allow the DC bus to discharge 3 Remove all covers 4 Set the voltmeter to the 1000 Vdc scale Measure the voltage between the equipment ground terminal and each terminal on the power terminal strip and verify the DC voltage is less than 45 V for each measurement 5 With the voltmeter at the 1000 Vdc scale measure between the PA terminal and all of the other terminals on the power terminal strip Verify the DC voltage is less than 45 V for each measurement 6 If the bus capacitors are not fully discharged contact your local Squa
16. 0 V 1 FrS Nominal motor frequency bFr 320 0 40 0 Hz 0 1 Config Set to the nameplate value if it is different from that set by bFr tFr Maximum output frequency 60 0 320 0 40 0 Hz 0 1 Config MACHINERY OVERSPEED Some motors and or loads may not be suited for operation above the nameplate motor speed and frequency Consult the motor manufacturer before operating the motor above the rated speed Failure to follow this instruction can result in injury or equipment damage brA Automatic deceleration ramp YES no YES Config adaptation to avoid an overbraking ObF fault YES function active no function not active This function may be incompatible with the use of dynamic braking SLP Slip compensation m 50 oo Hz 0 1 Adjust This parameter only appears if UFt is set for n tLS Low speed run time Time at which 0 0 25 5 0 0 s 0 1 Adjust the motor runs at LSP if reference goes to 0 and direction command FW or RV is still present If tLS 0 the drive controller will run at the LSP setting as long as FW or RV is present The drive controller restarts when the reference becomes greater than 0 or if the direction input FW or RV is cycled 111 The factory setting depends on the drive controller rating 34 O 1997 2000 Schneider Electric All Rights Reserved 52012 008 01B ALTIVAR 18 Drive Controller November 2000 Drive Controller Set Up Code LI2 Table 14 Level 2 Parameters Continued 5 Factory Max Min
17. 0 with removal of grey tape from the top of the drive controller Resistance to vibrations 0 6 g from 10 to 50 Hz 2 g from 50 to 150 Hz Pollution degree Pollution degree 2 according to NEMA ICS 1 and IEC 664 Protect the drive controller against dust corrosive gas and falling liquid Maximum relative humidity 93 maximum non condensing and without dripping provide heating system if there is condensation Maximum ambient temperature Altitude Storage Operation 13 to 149 F 25 to 65 C 14 to 104 F 10 to 40 C without grey tape removed 14 to 122 F 10 to 50 C with grey tape removed Up to 3 300 ft 1 000 m without derating derate by 3 for each additional 3 300 ft 1 000 m Electrical Characteristics Input voltage ATV18 M2 1 phase 200 V 15 to 240 V 10 ATV18 M2 3 phase 200 V 15 to 230 V 10 ATV18 N4 380 V 15 to 460 V 10 Input frequency 50 60 Hz 5 Input phases ATV18U09M2 to U41M2 1 ATV18U54M2 to D12M2 3 ATV18 N4 3 Output voltage Maximum voltage equal to input voltage Output frequency 0 5 to 320 Hz Output phases 3 Max transient current 150 of nominal drive controller current for 60 seconds Braking torque 30 of nominal motor torque without dynamic braking typical value Up to 150 with optional dynamic braking resistor Frequency resolution Display 0 1 Hz Analog inputs 0 1 Hz for 100 Hz maxim
18. 4 Vdc 100 mA maximum LO Supply for logic output to be connected to Maximum 30 Vdc 24 or to external 24 V supply LO Open collector PLC compatible logic output 24 Vdc maximum 20 mA with internal supply or 200 mA with external supply 1 Al2 or AIC can be summed with Al1 Both inputs are reassignable Do not use them at the same time Figure 8 Location of Control Terminals O 1997 2000 Schneider Electric All Rights Reserved 17 ALTIVAR 18 Drive Controller 52012 008 01B Using the Logic Inputs November 2000 USING THE LOGIC INPUTS The logic inputs may be operated from either the internal supply or an external supply The possible assignments of LI1 to LI4 are shown below LI1 Forward Cannot be reassigned JM When the contact is closed the reference frequency will be applied to the motor in the forward direction Li 24 LI2 LI3 and LI4 can be assigned to the following functions e Reverse F5E i When the contact is closed the reference frequency will be 6 a applied to the motor in the reverse direction If LI1 and LI2 T E 24 are closed at the same time forward direction has priority O Otherwise the direction selected first has priority e 2Preset Speeds F 5 2 HE When the contact is open the reference LSP analog T a A reference When the contact is closed the reference HSP LI4 e 4Preset Speeds F 5 4 If K1 and K2 are open the reference is LSP analog reference I
19. 52012 008 01B November 2000 Instruction Bulletin Raleigh NC USA ALTIVAR 18 Adjustable Speed Drive Controllers for Asynchronous Motors User s Manual Retain for future use ES telemecanique D square D ALTIVAR 18 Drive Controller 52012 008 01B User s Manual November 2000 A DANGER HAZARDOUS VOLTAGE Read and understand this bulletin in its entirety before installing or operating ALTIVAR 18 drive controllers Installation adjustment repair and maintenance of these drive controllers must be performed by qualified personnel Disconnect all power before servicing drive controller WAIT ONE MINUTE until DC bus capacitors discharge then measure DC bus capacitor voltage see pages 39 and 40 to verify DC voltage is less than 45 V The DC bus LED is not an accurate indication of the absence of DC bus voltage DO NOT short across DC bus capacitors or touch unshielded components or terminal strip screw connections with voltage present Install all covers before applying power or starting and stopping the drive controller User is responsible for conforming to all applicable code requirements with respect to grounding all equipment For drive controller grounding points refer to Figure 5 on page 11 Many parts in this drive controller including printed wiring boards operate at line voltage DO NOT TOUCH Use only electrically insulated tools Before servicing drive controller Disconnect all power
20. Controller November 2000 Using the Display Keypad USING THE DISPLAY KEYPAD Figure 15 shows the locations and functions of the display keypad keys Red LED DC Bus Four 7 segment LED display Go to the previous parameter s Save the parameter or increase the value displayed or the value displayed Go from parameter name to parameter value and vice versa Go to the next parameter or decrease the value displayed Figure 15 Functions of Keys and Display Normal display when there is no fault e In 1E lnitialization sequence e r d 4 Drive controller ready e 44 Display of the reference frequency e dc h Braking by DC injection in progress e r Er 4 Automatic restart in progress Figures 16 17 and 18 illustrate operation of the keypad push buttons bEr 1 flash as 3 0 EJE OREIRO gt 54 ACC O d E Etc Figure 16 Example 1 Adjustment of Ramp Time O 1997 2000 Schneider Electric All Rights Reserved 27 ALTIVAR 18 Drive Controller 52012 008 01B Parameter Summary November 2000 1 flash la e O O ES Figure 17 Example 2 Access to Level 2 Parameters 1 flash E E L a A CI Etc Figure 18 Example 3 Configuration of a Logic Output PARAMETER SUMMARY Figure 19 lists the parameters There are two levels of access e Level 1 adjustments basic configuration e Level 2 extensions in functionality There are three types of p
21. EC 18 30 dimensions 5 drive ready 30 drive overload 42 dynamic braking 15 34 42 43 E EEF 43 enclosures NEMA Type 12 IP54 8 sizing 6 8 ventilation 8 ALTIVAR 18 Drive Controller Index F fan flow rates 5 fast stop 19 21 35 fault auto tuning 43 codes 38 42 internal 43 overbreaking 34 storage 42 fault relay 17 22 fault relay wiring 10 fault reset 22 37 38 42 faults overcurrent 12 FbS 32 FCS 37 Fat 32 FL 32 FLG 30 frequency base 26 30 input 4 jump 31 maximum 25 33 nominal 25 30 output 4 reference 27 30 rotation 30 switching 4 26 FrH 30 FrS 33 FSt 35 FtA 36 full load current 12 fuses 23 1997 2000 Schneider Electric All Rights Reserved 45 ALTIVAR 18 Drive Controller Index G grounding 14 16 39 H heatsink 15 16 24 39 holding torque 32 35 HSP 18 26 30 32 Ide 32 In 32 InF 43 input analog 20 26 36 current 12 frequency 4 logic 17 18 26 33 35 36 phases 4 power 15 single phase 2 three phase 2 3 15 voltage 4 17 41 42 input wiring 10 inspection 1 internal fault 43 ItH 31 32 35 J jog 18 21 32 35 JPF 31 jump frequency 31 46 1997 2000 Schneider Electric All Rights Reserved L L2A 32 LCr 30 LI 17 18 LI2 17 18 35 36 LI3 17 18 36 Ll4 17 18 36 logic input 17 18 26 33 35 36 logic output 17 26 28 36 LSP 18 30 32 34 maximum capacitance 13 maximum f
22. Equipment operation must conform with national and local safety regulations Failure to follow these instructions can result in death serious injury or equipment damage 1997 2000 Schneider Electric All Rights Reserved 52012 008 01B ALTIVAR 18 Drive Controller November 2000 Drive Controller Set Up Code Function Table 14 Level 2 Parameters Continued Switching frequency adjustable in order to reduce audible motor noise Factory Max Min Setting Value Value 4 0 12 0 2 2 kHz 0 1 generated by the motor Above 4 kHz the drive controller output current must be derated as follows ATV18U09M2U U18M2U U29M2U U41M2U U54M2U no derating necessary All other models lt 8 kHz 5 derating gt 8 kHz 10 derating StP Controlled stop upon loss of input no YES no Config power no motor coasts to stop at loss of input power YES deceleration follows a self adjusting ramp which is a function of the regenerated energy Atr Automatic restart after a fault if the no YES no Config cause of the fault has disappeared and the other operating conditions allow it The drive controller will attempt to restart after 1s then 5s then 10s and then 1 minute for the remaining attempts If the fault is still present after 5 minutes the fault relay de energizes and the drive controller must be reset by cycling power Automatic restart can be attempted after the following fault
23. Level 1 parameters This parameter must be adjusted AIC Assignment of the analog input AIC Al2 If the logic inputs are not assigned to SAI SAI PIF Config PS2 PS4 or JOG the choices are SAI Reference summing with Al1 PIF PI feedback This configuration automatical 1 Ll4 OFF or FSt 2 LI3 OFF or dCI 3 LI2 OFF or rrS y assigns Al1 as PI setpoint input and causes rPG rlG and FbS to appear in the Level 1 parameters Note PIF is only possible if the logic inputs have previously been assigned as follows in this order If a logic input is assigned to PS2 PS4 or JOG the choice is SAI Reference summing with Al1 SAI SAI SAI Config CrL Configuration of the AIC Al2 input 0 0 0 0 4 0 mA Config current range 0 0 AIC 0 to 20 mA Al2 0 to 10 V 4 0 AIC 4 to 20 mA Al2 2 to 10 V SPr Automatic catch on the fly with speed no no YES Config 36 research After a brief input line undervoltage the motor restarts following a ramp without starting at zero The maximum time for speed research is 3 2 s The speed reference and the run direction input must be maintained when power is restored no Function not active YES Function active A WARNING UNINTENDED EQUIPMENT ACTION Automatic catch on the fly can only be used for machines or installations that present no danger in the event of automatic restarting either for personnel or equipment e
24. S 6 Feedback scaling factor for the PI 1 100 0 0 1 0 1 Adjust feedback function associated with the analog input AIC or Al2 FLt By pressing the DATA key when this Display parameter is displayed the last fault can be displayed When there has been no fault the display is nErr L2A Level 2 access no YES no Config no no gt next display will be rdY if down arrow pressed yes YES next display will be the first level 2 parameter if down arrow pressed 4 In drive controller rated output current See Table 1 and Table 2 on page 2 and Table 3 on page 3 8 Note that during braking configuration parameters cannot be modified Adjust tdc to 25 5 s if continuous DC injection is necessary 6 These parameters only appear if the associated functions have been selected 32 1997 2000 Schneider Electric All Rights Reserved 52012 008 01B ALTIVAR 18 Drive Controller November 2000 Drive Controller Set Up Level 2 Parameters Level 2 parameters are accessed by setting the L2A parameter to yes Table 14 lists the Level 2 parameters and their functions The maximum value is always obtained by pressing and holding the a key The minimum value is always obtained by pressing and holding the key A WARNING UNINTENDED EQUIPMENT ACTION Application of voltages to the logic inputs while a Level 2 parameter is being adjusted may result in power being applied to the motor While chang
25. U41N4 600 V 10 A 600 V 10 A U54N4 600 V 15 A 600 V 15A 5 U72N4 600 V 20 A 600 V 20 A 5 5 7 5 U9ON4 600 V 25 A 600 V 25 A 75 10 D12N4 600 V 40 A 11 15 D16N4 600 V 40 A 15 20 D23N4 600 V 60 A lil Fast acting or time delay Class J fuses are acceptable Equip all inductive circuits near the drive controller relays contactors solenoid valves with noise suppressors or connect them to a separate circuit When commanding the power by line contactor avoid frequently opening and closing the line contactor which could cause premature failure of the filtering capacitors and precharge resistor Use inputs LI1 to LI4 to command the drive controller Limit operations of the line contactor to less than once per minute 1997 2000 Schneider Electric All Rights Reserved 23 ALTIVAR 18 Drive Controller 52012 008 01B Thermal Overload Protection November 2000 THERMAL OVERLOAD PROTECTION e Thermal overload protection of the drive controller is accomplished by a thermal sensor on the heatsink of the drive controller and a calculation of the Pt e Inaddition the ALTIVAR 18 drive controller provides indirect motor thermal protection by continuously calculating the Lt of the motor based on the setting of the ItH parameter These methods allow thermal protection of the motor and drive controller for normal conditions of ambient temperature Typical trip values are e motor current 185 of nominal drive controller c
26. adjustment matches the motor and the application FLG Frequency loop gain 33 100 0 1 Adjust Dependent on the inertia and resistive torque of the driven mechanical equipment machines with high resistive torque or high inertia progressively reduce FLG from 33 to 0 machines with fast cycles low resistive torque and low inertia gradually increase the gain from 33 to 100 An excess of gain can cause unstable operation 1 LCr rFr and ULn cannot be saved by pressing ENT but can be displayed momentarily until the motor is stopped or the next parameter is displayed 2 tFr is a level 2 parameter adjustable from 40 to 320 Hz preset at 60 Hz For HSP gt 60 Hz first modify tFr by going to the level 2 parameters 30 1997 2000 Schneider Electric All Rights Reserved 52012 008 01B ALTIVAR 18 Drive Controller November 2000 Drive Controller Set Up Code IH Table 13 Level 1 Parameters Continued f Factory Max Min pis Setting it e nl nt li Motor thermal protection 3 In 41 1 15 In 0 5 In Adjust 4 4 Adjust ItH to the motor nameplate current The thermal state of the motor thermal protection is automatically reset when power is removed To suppress motor thermal protection increase the value of Ith to the maximum and provide external thermal protection CAUTION LOSS OF MOTOR OVERLOAD PROTECTION Setting the ItH parameter to maximum will disable the internal motor overload p
27. age 3 1997 2000 Schneider Electric All Rights Reserved 31 ALTIVAR 18 Drive Controller 52012 008 01B Drive Controller Set Up November 2000 Table 13 Level 1 Parameters Continued Factory Max Min Idec Automatic DC injection current level 0 7 nM In 4 0 25 A Adjust ItH tde Automatic DC injection current time 0 5 25 5 0 0 s 0 1 Adjust Adjustment to 0 suppresses automatic DC injection Adjustment to 25 5 causes permanent injection of DC upon stop 5 A WARNING NO HOLDING TORQUE e DC injection braking does not provide holding torque at zero speed DC injection braking does not function during loss of power or drive controller fault When required use separate brake for holding torque Failure to follow these instructions can result in death serious injury or equipment damage UFr Allows optimization of torque at low 20 100 0 1 Adjust speed SP3 61 3rd preset speed 5 0 HSP LSP Hz 0 1 Adjust SP4 6 4th preset speed 25 0 HSP LSP Hz 0 1 Adjust JOG 8 Jog speed 10 10 0 Hz 0 1 Adjust Fat 6 Frequency level associated with 0 HSP LSP Hz 0 1 Adjust frequency level attained when LO is assigned to this function This level allows a hysteresis of 0 2 Hz rPG 6 Proportional gain for the PI feedback 1 100 0 0 01 0 01 Adjust function rlG 61 Integral gain for the PI feedback 1 100 0 0 01 1 s 0 01 Adjust function Fb
28. and 2 preset speeds The use of 4 preset speeds requires two inputs Forward direction Automatic DC injection Summing input Reverse direction DC injection braking by logic input Fast stop Jog Automatic DC injection braking Summing input Pl feedback Forward direction CIE ANNE Reverse direction DC injection braking by logic input Fast stop Preset speeds A a A mad i gt gt gt ti 1 gt ft Tita i MU Function priority The function indicated by the arrow has priority over the other one The first operated has priority Non compatible functions Compatible functions No significance Figure 12 Function Compatibility Chart O 1997 2000 Schneider Electric All Rights Reserved 21 ALTIVAR 18 Drive Controller 52012 008 01B Wiring Diagram November 2000 WIRING DIAGRAM 1 Phase Power Supply 1 Po 3 Phase Power Supply Manual Speed Brake Pot 0to 10 V 4 Resistor if required 24 V External Supply 1 ATV18U09M2 to U41M2 only 2 Line inductor if required 1 phase or 3 phase 3 Fault relay contacts for remote signalling of the drive controller state Contact state shown with drive controller deenergized or faulted 4 Relay must draw lt 20 mA to be used on internal supply For relay up to 200 mA use external supply 5 This jumper is needed only if logic output is used When using a 24 V external su
29. arameters e Display values displayed by the drive controller e Adjustment can be modified when the motor is running or stopped e Configuration only modifiable when the motor is stopped Can be displayed when the motor is running 28 1997 2000 Schneider Electric All Rights Reserved 52012 008 01B ALTIVAR 18 Drive Controller November 2000 Parameter Summary Level 1 Parameters Level 2 Parameters F AS rd nnn motor UFE FrH E Un LEF Un5 rFr Pr amp Oy ON UL n la FE lb Fr lb r Al tjACL SLP DEC ELS LSF E la ot HSF 15F3 E 3 FLO G PY E re IEH J OG LQ IPF xF dE a E ld E xr PL Er il E dE xr IL SE ip LI F i F b 5 5 F r HERE a m LCA Access to Level2 Le al Pie no L2A Y4ES L g ie YES 4 Display Configuration can only be modified Adjustment can be modified while motor is stopped while motor is running or stopped Parameter displayed only if the corresponding function is configured Figure 19 Parameter Summary 1997 2000 Schneider Electric All Rights Reserved 29 ALTIVAR 18 Drive Controller 52012 008 01B Drive Controller Set Up November 2000 DRIVE CONTROLLER SET UP Level 1 Parameters
30. ble 25 braking 4 constant 26 33 holding 32 35 tightening 16 17 typical 25 variable 33 tUn 33 U UFr 32 UFt 33 ULn 30 undervoltage 36 42 UnS 33 USF 42 V variable torque 33 ventilation 8 38 ventilation flow 6 8 voltage bus capacitor 39 41 input 4 17 41 42 motor 26 30 33 output 4 ALTIVAR 18 Drive Controller Index W wiring control command 10 diagram 22 fault relay 10 general practices 12 input 10 motor 10 output 13 power 12 terminal 11 1997 2000 Schneider Electric All Rights Reserved 47 ALTIVAR 18 Drive Controller User s Manual Square D Company 8001 Highway 64 E Knightdale NC 27545 USA 888 Square D 888 778 2733 Bulletin No 52012 008 01B www squared com Replaces 52012 008 01A dated 5 2000
31. cause another input was already assigned to PS2 PS4 4 preset speeds If AIC is assigned for summing with rs OFF PS2 Config Al SAI and no other LI is assigned to PS2 the choices for LI2 are OFF not assigned rrS reverse dCl continuous DC injection braking at drive In for 5s then at 0 5 ItH FSt Fast stop This function is active when the Ll is at state 0 off JOG Jog Bl PS2 2 preset speeds 3 the choices for LI2 are OFF not assigned rrS reverse dCI continuous DC injection braking at drive controller In for 5s then at 0 5 ItH FSt Fast stop This function is active when the Ll is at state 0 off ad rrS OFF FSt ij 2 Factory setting 3 These functions cause parameters to appear in Level 1 JOG SP2 SP4 that must be adjusted O 1997 2000 Schneider Electric All Rights Reserved 35 ALTIVAR 18 Drive Controller 52012 008 01B Drive Controller Set Up November 2000 Table 14 Level 2 Parameters Continued z Factory Min Code Function Setting Units Increment Type LI3 Reassignment of the LI3 logic input PS2 Same as LI2 To reassign LI3 from PS2 if LI4 is set to PS4 LI4 must be reassigned first Ll4 Reassignment of the LI4 logic input PS4 Same as LI2 LO Assignment of logic output There are SrA Config 2 choices SrA Speed reference attained with a FtA Frequency level attained When FtA is selected hysteresis of 2 5 Hz Fdt appears in the
32. damage STORING AND SHIPPING If the drive controller is not being immediately installed store it in a clean dry area where the ambient temperature is between 25 and 65 C 13 to 149 F If the drive controller must be shipped to another location use the original shipping material and carton to protect the drive controller 1997 2000 Schneider Electric All Rights Reserved 1 ALTIVAR 18 Drive Controller Technical Characteristics 52012 008 01B November 2000 TECHNICAL CHARACTERISTICS Table 1 Technical Characteristics 200 V 15 to 240 V 10 50 60 Hz 5 Single Phase Input Three Phase Output Drive Controller Input Line Motor Power Rated Transient Total Short Catalog Number Current 1 Output Output Dissipated Circuit Single Phase Current Current 2 Power O Rating 200V 240V In Rated Load A A kw hp A A W A rms sym ATV18U09M2 4 4 3 9 0 37 0 5 2 1 3 2 23 1 000 ATV18U18M2 7 6 6 8 0 75 1 3 6 5 4 39 1 000 ATV18U29M2 13 9 12 4 1 5 2 6 8 10 2 60 1 000 ATV18U41M2 19 4 17 4 2 2 3 9 6 14 4 78 1 000 1 Values correspond to the amount absorbed by drive controllers supplied by mains with fault capacity equal to short circuit rating indicated in table and under nominal conditions of load and speed of the associated motor without additional inductance For 60 seconds 2 Table 2 Technical Characteristics 200 15 to 230 V 10 50 60 Hz 5 Three Phase Input
33. f K1 is closed and K2 is open the reference is SP3 Speed 3 ____ If K1 is open and K2 is closed the reference is SP4 Speed 4 Li2or Li2or 24 If K1 and K2 are closed the reference is HSP LI3 or LI3 or Ll4 Ll4 PS4 PS2 e Jog JOG If the contact is closed and then the direction contact is JE closed the ramp time is 0 1 s regardless of the settings of 0 ACC and dEC If the drive is already running and the aoe Ha contact assigned to JOG is closed the ramp times will Ll4 be equal to ACC and dEC The minimum time between two jog operations is 0 5 s 18 1997 2000 Schneider Electric All Rights Reserved 52012 008 01B ALTIVAR 18 Drive Controller November 2000 Using the Logic Inputs Jog command Run direction Speed reference Frequency Figure 9 Jog Timing Diagram NOTE Whenever the drive controller is running in Jog automatic DC injection braking upon stop is inhibited However DC injection braking by logic input has priority over Jog run e FastStop F 5E IR Fast stop is commanded when the contact between the logic Li2or 24 input assigned to this function and 24 is opened LI3 or LI4 The ramp time isthe odEE time divided by 4 but limited to the minimum acceptable time for braking without causing an overbraking fault The ramp is automatically adapted if the braking capacity is exceeded NOTE When in fast stop automatic DC injection braking and DC injection by l
34. f the power terminal strip This shield must not be interrupted If intermediate terminal blocks are used they must be in EMC shielded metallic boxes The cable shield must have an ampacity greater than or equal to that of the ground conductor Shielded cable for connection to control commana For applications requiring several conductors a small wire size must be used 20 AWG or 0 5 mm2 The shield must be tied to ground at both ends At the drive controller the shield is connected to the E or G E terminal on the far right of the power terminal strip This shield must not be interrupted If intermediate terminal blocks are used they must be in EMC shielded metallic boxes Maintain separation between control command wiring and motor wiring NOTE Connection at equal potential of the grounds between the drive controller motor and cable shields does not preclude the connection of equipment ground conductors as required by national and local codes 10 1997 2000 Schneider Electric All Rights Reserved 52012 008 01B ALTIVAR 18 Drive Controller November 2000 Wiring WIRING To access the terminal blocks remove the two screws and remove the cover When accessing the terminals first perform the Bus Voltage Measurement Procedure on page 39 Figure 4 shows the location of the cover screws QOO A Removable Cover Screws _ O es Figure 4 Accessing Terminal Strips Figure 5 shows the location of the drive controlle
35. fault codes for the faults that can be automatically reset the probable causes of the faults and associated corrective action Table 16 on page 43 lists the fault codes for the faults which are not automatically resettable thus requiring reset by cycling power along with the probable causes of the faults and associated corrective action When taking corrective action follow the procedures outlined on pages 39 41 A DANGER HAZARDOUS VOLTAGE Read and understand these procedures before servicing ALTIVAR 18 drive controllers Installation adjustment and maintenance of these drive controllers must be performed by qualified personnel Failure to follow these instructions will cause shock or burn resulting in death or serious injury The following procedures are intended for use by qualified personnel and should not be viewed as sufficient instruction for those who are not otherwise qualified to operate service or maintain the equipment discussed 38 1997 2000 Schneider Electric All Rights Reserved 52012 008 01B ALTIVAR 18 Drive Controller November 2000 Bus Voltage Measurement Procedure 1 Bus Voltage Measurement A DANGER HAZARDOUS VOLTAGE Read and understand the Bus Voltage Measurement Procedure before performing the procedure Measurement of bus capacitor voltage must be performed by qualified personnel DO NOT short across capacitors or touch unshielded components or terminal strip screw connections with
36. imum wire size for this screw terminal is 8 AWG 6 mm2 Tightening torque is 21 Ib in 2 4 Nem for drive controllers ATV18U09M2 and U18M2 Tightening torque is 31 Ib in 3 45 Nem for all other 16 units O 1997 2000 Schneider Electric All Rights Reserved 52012 008 01B November 2000 ALTIVAR 18 Drive Controller Wiring Control Terminals Maximum wire size for all control terminals is 16 AWG 1 5 mm Tightening torque is 4 4 Ib in 0 5 Nem The control terminals are galvanically isolated from the power section Table 9 Control Terminal Strip Characteristics Terminal Reference Function Characteristics ATV18 0 SA Fault relay Minimum 10 mA 24 Vdc SB N O N C contact Maximum inductive load of sc Closed when drive controller energized with 0 3 A 250 Vac no fault 1 5 A 30 Vdc 10 Internal supply for reference potentiometer 10 Vdc 15 0 10 mA maximum Manual speed potentiometer value 1 KQ to 10 kQ Alt les input 1 Speed reference voltage 0 to 10 Vdc Impedance 30 kQ inpu Al2 Analog input 2 Voltage reference 0 to 10 Vdc Impedance 30 55 kQ or or or AIC 11 Current analog input current reference 0 20 mA 4 20 mA Impedance 400 Q COM Common for logic inputs analog input and 0 V logic output Ll1 Logic input 1 24 Vdc State 0 V lt 5 V State 1 V gt 11 V LI2 Logic input 2 Vmax 30 V LI3 Logic input 3 Ll4 Logic input 4 24 Internal supply for logic inputs and outputs 2
37. ing a Level 2 parameter ensure that no voltage is applied to the logic inputs Failure to follow these instructions can result in death serious injury or equipment damage O 1997 2000 Schneider Electric All Rights Reserved 33 ALTIVAR 18 Drive Controller 52012 008 01B Drive Controller Set Up November 2000 Code Function Table 14 Level 2 Parameters Factory Max Min Setting Value Value Selection of the type of volts n L nLd frequency ratio L constant torque for special motors or motors connected in parallel P variable torque n sensorless flux vector control for constant torque applications nLd energy savings for variable torque applications tUn Auto tune Only active when UFt is no YES no Config set for n or nLd no no auto tune factory parameters for standard IEC motors donE auto tune has already been performed auto tune parameters already in use YES setting to YES and pressing ENT starts auto tune When auto tune is completed rdY is displayed Returning to tUn displays donE If tnF tuning fault appears the motor is not adapted to the drive controller Use L or P mode UnS Nominal motor voltage Set to the Config nameplate value Maximum minimum and factory preset values depend on the model and the setting of the bFr parameter level 1 ATV18 M2 230 240 200 Vv 1 ATV18 N4 with bFr 50 400 460 380 V 1 ATV18 N4 with bFr 60 460 460 38
38. it Connections 12 Output Wiring Precautions 13 Grounding isa a ER AU Lane heath nm ane anda 14 PowerTerminalS ccoo sarria pineal ie ois nae ae ga 15 Equipment Ground Terminal 16 Control Terminal Sice cee ck De eee VG a eee ee aes ee 17 USING THE LOGIC INPUTS 2 18 USING THE ANALOG INPUTS 20 FUNCTION COMPATIBILITY cocccccccccoc tenes 21 WIRING DIAGRAM i sus ue m donee tata Ad Rein ben 22 FAUET RELA Votando ee la a el oe 22 RECOMMENDED FUSES 23 THERMAL OVERLOAD PROTECTION 24 AVAILABLE TORQUE 4 4 44 44e eue eue 25 FACTORY SETTINGS renaalne AA ee a eed 26 USING THE DISPLAY KEYPAD 0ooccccocccccocc eee eee 27 PARAMETER SUMMARY 00 0 c eee eet tenet eens 28 1997 2000 Schneider Electric All Rights Reserved i ALTIVAR 18 Drive Controller 52012 008 01B Table of Contents November 2000 DRIVE CONTROLLER SET UP o oocccccccccccc 30 Level 1 Param ters 244 A e end ets 30 L vel 2Parameters s nu rss nn Se ne A A A ele ur 23 33 MAINTENANCE csi id dons een te ie entrave de dore 38 PRECAUTIONS 5 ose ig as ae De TR aie neat A ara 38 Procedure 1 Bus Voltage Measurement 39 Dri
39. nce per square inch of enclosure K 186 1997 2000 Schneider Electric All Rights Reserved 7 ALTIVAR 18 Drive Controller 52012 008 01B Mounting in Type 12 IP54 Metal Enclosure November 2000 e Calculate maximum allowable thermal resistance Rth 40 C 25 C A Rth Hr 0 16 C W e Calculate minimum useful heat exchange surface area S 4 0 1 O z 1162 5 in o Useful heat exchange surface area S of the proposed wall mounted enclosure e Height 24 in 610 mm e Width 20 in 508 mm e Depth 12 in 305 mm front area top area side area S 24x20 20 x 12 2 24x12 1296 in If the selected enclosure does not provide the required surface area or does not meet application needs consider the following e Usea larger enclosure e Add a passive heat exchanger to the enclosure e Add an air conditioning unit to the enclosure Ventilation When mounting the drive controller inside a Type 12 or IP54 enclosure follow these ventilation precautions e Observe minimum clearance distances shown in Figure 2 on page 6 e Follow the installation precautions on page 6 e Astirring fan with filter may be necessary to circulate the air inside the enclosure prevent hot spots in the drive controller and to distribute the heat uniformly to surfaces used for convection cooling e If there is a possibility of condensation keep the control supply switched on during periods when the motor is not r
40. ogic input are inhibited e DC Injection Braking dE ME DC injection braking is commanded when the contact between Li2or 24 the logic input assigned to this function and 24 is closed LI3 or LI4 The current injected is equal to the drive controller nominal current for 5 seconds After 5 seconds the current is limited to a maximum value of 0 5 times the motor thermal current IE H NOTE Automatic DC injection braking remains active even if a logic input is assigned to AE 1 Fast stop has priority over DC injection braking 1997 2000 Schneider Electric All Rights Reserved 19 ALTIVAR 18 Drive Controller 52012 008 01B Using the Analog Inputs November 2000 USING THE ANALOG INPUTS 20 ATI is a 0 to 10 V analog input which is used for speed reference In addition one of two other analog inputs may be used either e AI2 0 to 10 V or 2 to 10 V voltage input or e AIC 0 to 20 mA factory setting or 4 to 20 mA current input AR or AIC can be assigned to reference summing with AI1 or PI feedback e Reference summing with All 5A Alt 0 to 10V Al2 0 to 10V or 0 to 20 mA or 4 to 20 mA Figure 10 Reference Summing e PI Feedback F IF This assignment automatically configures AI1 as PI setpoint input AI2 or AIC is the PI feedback input Alt 0to 10 V 2 Al2 Oto 10 V or AIC O 0 to 20 mA or 4 to 20 mA r IE 0 01 to 100 x 1 s Figure 11 PI Feedback To set up the
41. oller 52012 008 01B Wiring November 2000 Grounding For safe dependable operation ground the drive controller according to National Electrical Code and all local codes To ground the drive controller e Connect a copper wire from the equipment ground terminal to the power system ground conductor Wire size is determined by the drive controller size and by national and local codes e Verify that resistance to ground is one ohm or less Improper grounding causes intermittent and unreliable operation A DANGER HAZARDOUS VOLTAGE Ground equipment using the connection provided as shown in Table 7 on page 15 The drive controller panel must be properly grounded before applying power Do not use metallic conduits as a ground conductor Failure to follow these instructions will result in death or serious injury Ground multiple drive controllers as shown in Figure 6 Do not loop or series the ground cables Drive Controller Drive Controller Drive Controller Drive Controller Drive Controller Figure 6 Grounding Multiple Drive Controllers 14 1997 2000 Schneider Electric All Rights Reserved 52012 008 01B November 2000 ALTIVAR 18 Drive Controller Wiring Power Terminals Table 7 Power Terminal Strip Characteristics Terminal Function ATV18 Li All models L2 Input power L3 Three phase units only L EorG E Equipment ground connection All models Not used
42. pply connect the 0 V to the COM terminal and connect LO to the external 24 V instead of the 24 V terminal on the drive controller Figure 13 ALTIVAR 18 Drive Controller Wiring Diagram FAULT RELAY The fault relay is energized whenever there is power to the drive controller and there is no fault It is a Normally Open Normally Closed contact After a fault the drive controller is reset either by cycling power allowing the red LED see Figure 15 on page 27 to go dark or automatically after certain faults if automatic restart is selected For further explanation of automatic restart refer to page 37 22 1997 2000 Schneider Electric All Rights Reserved 52012 008 01B ALTIVAR 18 Drive Controller November 2000 Recommended Fuses RECOMMENDED FUSES Table 10 Recommended Fuses for 230 V Drive Controllers Motor Drive Controller Fuses kw HP ATV18 000 Class CC Class Jl 0 37 0 5 U09M2 600V 6A 600V 6A 0 75 1 U18M2 600 V 10 A 600 V 10 A 1 5 2 U29M2 600 V 20 A 600 V 20 A 2 2 3 U41M2 600 V 25 A 600 V 25 A U54M2 600 V 25 A 600 V 25 A 5 U72M2 600 V 30 A 5 5 7 5 U90M2 600 V 40 A 7 5 10 D12M2 600 V 40 A NT Fast acting or time delay Class J fuses are acceptable Table 11 Recommended Fuses for 460 V Drive Controllers Motor Drive Controller Fuses kW HP ATV 1800000 Class CC Class J 1 0 75 1 U18N4 600 V 5 A 600 V 5 A 1 5 2 U29N4 600 V 10 A 600 V 10 A 2 2 3
43. protection at all speeds and loading conditions Consult the motor manufacturer for thermal capability of the motor when operated over the desired speed range Failure to follow this instruction can result in injury or equipment damage AVAILABLE TORQUE Continuous duty e For self ventilated motors motor cooling depends on the speed e Continuous duty results in derating for speeds less than 50 of the nameplate motor speed Operation in overspeed e Inoverspeed operation the voltage no longer increases with the frequency resulting in reduced induction in the motor which translates into loss of torque Consult the motor manufacturer to ensure that the motor can operate in overspeed e Fora special motor the nominal frequency and the maximum frequency can be adjusted between 40 and 320 Hz A CAUTION MACHINERY OVERSPEED Some motors and or loads may not be suited for operation above the nameplate motor speed and frequency Consult the motor manufacturer before operating the motor abovethe rated speed Failure to follow this instruction can result in injury or equipment damage Figure 14 on page 26 shows the typical torque characteristics of the ALTIVAR 18 drive controller 1997 2000 Schneider Electric All Rights Reserved 25 ALTIVAR 18 Drive Controller 52012 008 01B Available Torque November 2000 T Tn 15 3 1 Self ventilated motor 1 2 N 2 Force ventilated motor N N
44. r wiring terminals Control Terminals Equipment Ground Terminal Power Terminals il Figure 5 Wiring Terminals 1997 2000 Schneider Electric All Rights Reserved 11 ALTIVAR 18 Drive Controller 52012 008 01B Wiring November 2000 General Wiring Practices Good wiring practice requires the separation of control circuit wiring from all power line wiring Power wiring to the motor must have the maximum possible separation from all other power wiring whether from the same drive controller or other drive controllers do not run in the same conduit This separation reduces the possibility of coupling electrical transients from power circuits into control circuits or from motor power wiring into other power circuits A CAUTION EQUIPMENT DAMAGE HAZARD Follow wiring practices described in this document in addition to those already required by the National Electrical Code and local electrical codes Failure to follow these instructions can result in injury or equipment damage Follow the practices below when wiring ALTIVAR 18 drive controllers Use metallic conduit for all drive controller wiring Do not run control and power wiring in the same conduit e Separate metallic conduits carrying power wiring or low level control wiring by at least 3 in 7 62 cm e Separate non metallic conduits or cable trays used to carry power wiring from metallic conduit carrying low level control wiring by at least 12 in
45. re D representative do not operate the drive controller 7 Replace all covers O 1997 2000 Schneider Electric All Rights Reserved 39 ALTIVAR 18 Drive Controller 52012 008 01B Bus Voltage Measurement November 2000 ore Til For these drive controllers the voltage is measured between the PA and PC terminals located on the power board as shown in Figure 20 To measure the bus capacitor voltage Equipment ground terminal Power terminals Figure 20 Measuring Bus Capacitor Voltage Drive Controllers ATV18D16N4 and ATV18D23N4 1 Disconnect all power from the drive controller 2 Wait 1 minute to allow the DC bus to discharge 3 Remove all covers 4 Set the voltmeter to the 1000 Vdc scale Measure the bus capacitor voltage between the PA and PC terminals to verify that DC voltage is less than 45 V Do not short across capacitor terminals with voltage present 5 Ifthe bus capacitors are not fully discharged contact your local Square D representative do not operate the drive controller 6 Replace all covers 40 1997 2000 Schneider Electric All Rights Reserved 52012 008 01B ALTIVAR 18 Drive Controller November 2000 Checking Supply Voltage amp Peripheral Equipment Procedure 2 Checking Supply Voltage To measure the input line voltage 1 Perform the Bus Voltage Measurement procedure see page 39 2 Attach the meter leads to L1 amp L2 Set the voltmeter to the 600 Vac
46. requency 25 33 memory failure 43 motor current 24 30 motor overload 42 motor thermal current 26 motor voltage 30 33 motor wiring 10 mounting 10 NEMA Type 12 IP54 8 multiple drives 14 N nominal current 26 nominal frequency 25 30 O ObF 42 OCF 43 OFF 35 52012 008 01B November 2000 OHF 42 OLF 42 OSF 42 output cable 13 logic 17 26 28 36 three phase 2 3 wiring 13 output frequency 4 output phases 4 output voltage 4 overcurrent 6 12 43 overheating motor 25 31 overload drive 42 motor 42 overspeed 25 overvoltage 42 P parameter summary 29 phases input 4 output 4 Pl feedback 20 21 32 PI regulator 20 PIF 36 power input 15 terminals 15 16 39 power wiring 12 preset speeds 18 21 35 protection 1 4 6 12 38 thermal 24 31 42 PS2 35 36 PS4 35 36 52012 008 01B November 2000 R rdY 30 37 reference frequency 27 reset 31 automatic 24 fault 22 37 38 42 restart 34 36 automatic 22 27 37 42 rFr 30 rlG 32 rotation frequency 30 rPG 32 S SA 17 SAI 36 SB 17 SC 17 SFr 37 shipping 1 slip compensation 34 SLP 34 SP3 32 SP4 32 SrA 36 storing 1 StP 37 switching frequency 26 T tdc 32 temperature 4 6 7 24 terminal blocks 11 terminal wiring 11 terminals control 17 power 15 16 39 tFr 33 thermal protection 24 31 42 thermal resistance 7 8 tightening torque 16 17 tLS 34 tnF 43 torque availa
47. rflow above and below 2 4 in 100 mm sides gt 2 in 50 mm These clearances should not be used as minimum enclosure size for proper thermal dissipation Mount the drive controller vertically Avoid placing near any heat sources Verify that the voltage and frequency characteristics of the input line match the drive controller nameplate rating Installation of a disconnect switch between the input line and drive controller is recommended Follow national and local codes Overcurrent protection is required Install line power fuses recommended in Table 10 on page 23 and Table 11 on page 23 Turn off all power before installing the drive controller Place a DO NOT TURN ON label on the drive controller disconnect Before proceeding with installation lock the disconnect in the open position Dimensions are in inches millimeters Figure 2 Minimum Clearances and Ventilation Flow 1997 2000 Schneider Electric All Rights Reserved 52012 008 01B ALTIVAR 18 Drive Controller November 2000 Mounting in Type 12 IP54 Metal Enclosure MOUNTING IN TYPE 12 IP54 METAL ENCLOSURE Calculating Enclosure Size Below is the equation for calculating Ry C W the maximum allowable thermal resistance of the enclosure Max internal ambient temp C around drive controller T R i o To Max external ambient temp C around enclosure P Total power dissipated in enclosure W For the power dissipated by
48. rotection function In this case external motor overload protection must be provided When using external overload relays connected to the drive controller output the overload relay must be capable of operation over the expected range of drive controller output frequencies including direct current When DC injection braking is used The overload relay must be suitable for operation with direct current flowing in the motor Do not use overload relays equipped with current transformers for sensing the motor current Failure to follow these instructions can result in equipment damage A CAUTION MOTOR OVERHEATING This drive controller does not provide direct thermal protection for the motor Use of a thermal sensor in the motor may be required for protection at all speeds and loading conditions Consult the motor manufacturer for the thermal capability of the motor when operated over the desired speed range Failure to follow this instruction can result in injury or equipment damage JPF 2 Hz Suppression of a critical speed which causes mechanical resonance Factory setting of 0 indicates that the function is not used Jump frequency with a bandwidth of 0 0 HSP 0 0 Hz 0 1 ES 3 For motors in parallel fed by the same drive controller a separate thermal relay should be added for each motor 4 In drive controller rated output current See Table 1 and Table 2 on page 2 and Table 3 on p
49. s OHF OLF USF ObF OSF The drive controller fault relay remains energized if the function is active The speed reference and the rotation direction must be maintained no Function not active YES function active UNINTENDED EQUIPMENT ACTION e Automatic restart can only be used for machines or installations that present no danger in the event of automatic restarting either for personnel or equipment Equipment operation must conform with national and local safety regulations Failure to follow these instructions can result in death serious injury or equipment damage FCS Return to factory settings no no YES Config no do not return to factory settings YES Return to factory settings display will then be rdY CPU Firmware version Display 1997 2000 Schneider Electric All Rights Reserved 37 ALTIVAR 18 Drive Controller 52012 008 01B Maintenance November 2000 MAINTENANCE Read the following safety statements before proceeding with any maintenance or troubleshooting procedures The following steps should be done at regular intervals e Check the condition and tightness of the connections e Make sure ventilation is effective and temperature around the drive controller remains at an acceptable level The average lifetime of the fans is 3 to 5 years depending on the conditions of use e Remove dust and debris from the drive controller if necessary PRECAUTIONS Table 15 on page 42 lists the
50. s not greater than intended for the drive controller e Wait for the motor to cool down before restarting OSF Input voltage too high or Verify the input voltage Procedure 2 on page 41 Overvoltage in Noisy mains Consider the installation of line inductors steady state or acceleration USF Input voltage too low or e Verify the input voltage Procedure 2 on page 41 Undervoltage Failed precharge resistance and the voltage parameter UnS e Reset Replace the drive controller ObF e Overbraking due to e Increase the deceleration time Overvoltage in excessive braking or Activate the brA function if compatible with deceleration overhauling load application Add dynamic braking resistor if necessary 42 1997 2000 Schneider Electric All Rights Reserved 52012 008 01B November 2000 ALTIVAR 18 Drive Controller Fault Codes Table 16 Non Automatically Resettable Faults Fault OCF Overcurrent dbF Dynamic braking overload InF Internal fault tnF Auto tuning fault EEF Probable Causes Output of the drive short circuited or grounded or e Overcurrent in the braking resistance Overload of dynamic braking circuit Internal fault e Special motor Motor horsepower size different from drive controller Memory failure Corrective Actions e Switch drive off Disconnect drive controller from motor at U V W Check cables connected to
51. troller prior to performing the test Failure to follow these instructions can result in equipment damage O 1997 2000 Schneider Electric All Rights Reserved 41 ALTIVAR 18 Drive Controller 52012 008 01B Fault Codes November 2000 Fault Storage The first fault detected is saved and displayed on the keypad screen if power is maintained The drive trips and the fault relay opens To reset the fault e Remove power from the drive controller e Before switching power back on identify and correct the cause of the fault e Restore power This will reset the fault if it has been corrected In certain cases if automatic restart has been enabled the drive can be automatically restarted after the cause of the fault has disappeared Refer to the Level 2 parameters FAULT CODES Table 15 Resettable Faults with Automatic Restart Fault Probable Causes Corrective Actions OHF e Drive controller 12t too high Ensure the motor load is not greater than intended Drive Overload or for the drive controller Check settings of motor Drive controller temperature Voltage UnS and motor frequency FrS Verify too high drive controller ventilation is sufficient and the environment is controlled e Wait for the drive controller to cool down before restarting OLF Thermal trip due to e Check the motor thermal protection adjustment Motor Overload prolonged motor overload ItH e Motor 12t too high Ensure the motor load i
52. uit Three Phase Current Current 3 Power O Rating 380 V 460V In A Rated Load A A kW hp A A W A rms sym ATV18U18N4 2 9 2 7 0 75 1 2 1 3 2 24 5 000 ATV18U29N4 5 1 4 8 1 5 2 3 7 5 6 34 5 000 ATV18U41N4 6 8 6 3 2 2 3 5 3 8 49 5 000 ATV18U54N4 9 8 8 4 3 7 1 10 7 69 5 000 ATV18U72N4 12 5 10 9 4 5 9 2 13 8 94 5 000 ATV18U90N4 16 9 15 3 5 5 7 5 11 8 17 7 135 22 000 ATV18D12N4 21 5 19 4 7 5 10 16 24 175 22 000 ATV18D16N4 31 8 28 7 11 15 22 33 261 22 000 ATV18D23N4 42 9 38 6 15 20 29 3 44 342 22 000 1 2 3 4 Suitable for use on neutral grounded systems only Values correspond to the amount absorbed by drive controllers supplied by mains with fault capacity equal to short circuit rating indicated in table and under nominal conditions of load and speed of the associated motor without additional inductance For 60 seconds Rated output currents shown are for switching frequencies of 2 2 to 4 kHz If switching frequency is gt 4 kHz and lt 8 kHz derate output current by 5 If switching frequency is gt 8 kHz derate output current by 10 See page 37 for adjustment of switching frequency 1997 2000 Schneider Electric All Rights Reserved 3 ALTIVAR 18 Drive Controller Specifications 52012 008 01B November 2000 SPECIFICATIONS Environment Degree of Protection Table 4 Specifications NEMA Open ll IP31 without removal of grey tape from the top of the drive controller IP2
53. um Switching frequency Adjustable from 2 2 to 12 kHz Drive controller protection Galvanic isolation between power and control power supplies inputs outputs Protection against short circuits e in available internal sources e between output phases e between output phases and ground for 7 5 to 20 hp drive controllers Thermal protection against overheating and overcurrents Undervoltage and overvoltage faults Overbraking fault Motor protection Protection integrated in the drive controller by l t calculation 11 Drive controller electrical creepages are designed for use in a pollution Degree 2 environment per NEMA ICS 1 and IEC 664 O 1997 2000 Schneider Electric All Rights Reserved 52012 008 01B ALTIVAR 18 Drive Controller November 2000 Dimensions DIMENSIONS Il Y T o E pcia al Figure 1 Altivar 18 Dimensions Table 5 Dimensions Mounting T Catalog No a b c Weight G H ATV18U09M2 4 41 7 17 4 76 3 94 6 7 0 20 5 3 3 1 5 ATV18U18M2 112 182 121 100 170 3 3 1 5 ATV18U29M2 587 7 24 618 5 39 6 77 ei ATV18U18N4 149 184 157 137 172 0 20 5 4 4 2 0 ATV18U29N4 4 6 2 1 ATV18U41M2 6 2 2 8 ATV18U54M2 7 3 3 3 ATV18U72M2 7 28 8 46 6 22 6 73 7 95 0 24 6 7 3 3 3 ATV18U41N4 185 215 158 171 202 g 6 8 3 1 ATV18U54N4 7 3 3 3 ATV18U72N4 7 3 3 3 ATV18U90M2 17 2 7 8 ATV18D12M2 8 27 11 81 6 69 7 48 11 02 0 28 7
54. unning or install thermostatically controlled strip heaters 8 1997 2000 Schneider Electric All Rights Reserved 52012 008 01B ALTIVAR 18 Drive Controller November 2000 Electromagnetic Compatibility EMC ELECTROMAGNETIC COMPATIBILITY EMC NOTE This section focuses on applications requiring compliance to the European Community EMC directive The Altivar 18 is considered to be a component It is neither a machine nor a piece of equipment ready for use in accordance with the European Community directives machinery directive or electromagnetic compatibility directive It is the user s responsibility to ensure that the machine meets these standards Installation Precautions for Meeting EN55011 Class A General Rules Ensure that the grounds of the drive controller the motor and the cable shields are at equal potential Use shielded cables with the shields tied to ground at both ends of the motor cable and the control cables The ground connection to the shield must make contact with the complete circumference of the shield As long as there is no discontinuity this shielding can be achieved by using metallic conduit Bonding at conduit fittings is required Installation Plan O O 2 ATV 18 f Re 5 PE 5 SE E es 4 7 Figure 3 Installation Diagram Description of parts in Figure 3 1 A sheet metal plate which is not painted and has an anti corrosion conductive
55. urrent for 2 seconds e motor current 150 of nominal drive controller current for 60 seconds If the motor current lt 110 of the nominal drive controller current the drive controller will not trip Derating for switching frequencies gt 4 kHz are automatically taken into account and the allowable 12t is reduced The thermal state of the drive controller is automatically reset when power is removed CAUTION LOSS OF MOTOR OVERLOAD PROTECTION Setting the ItH parameter to maximum will disable the internal motor overload protection function e In this case external motor overload protection must be provided When using external overload relays connected to the drive controller output the overload relay must be capable of operation over the expected range of drive controller output frequencies including direct current When DC injection braking is used The overload relay must be suitable for operation with direct current flowing in the motor Do not use overload relays equipped with current transformers for sensing the motor current Failure to follow these instructions can result in equipment damage 24 1997 2000 Schneider Electric All Rights Reserved 52012 008 01B ALTIVAR 18 Drive Controller November 2000 Available Torque 44 CAUTION MOTOR OVERHEATING This drive controller does not provide direct thermal protection for the motor Use of a thermal sensor in the motor may be required for
56. ve Controllers ATV18 M2 and ATV18U18N4 to D12N4 39 Drive Controllers ATV18D16N4 and ATV18D23N4 40 Procedure 2 Checking Supply Voltage 41 Procedure 3 Checking the Peripheral Equipment 41 Fault Storage riera rr hdd ed 42 FAUET CODES SES ad ER e a a ane o a te 42 INDEX 200 M AR ne US get ee bh gtk or ett dees 45 ii 1997 2000 Schneider Electric All Rights Reserved 52012 008 01B ALTIVAR 18 Drive Controller November 2000 Receiving amp Preliminary Inspection RECEIVING AND PRELIMINARY INSPECTION Before installing the ALTIVAR 18 ATV18 drive controller read this manual and follow all precautions e Before removing the drive controller from its packing material verify it is not damaged from shipping Any damage to the packing carton usually indicates improper handling If any damage is found notify the carrier and your Square D representative e After removing the drive controller from its packaging visually inspect the exterior for shipping damage If any shipping damage is found notify the carrier and your sales representative e Verify that the drive controller nameplate and label conform to the packing slip and corresponding purchase order A CAUTION EQUIPMENT DAMAGE HAZARD Do not operate or install any drive controller that appears damaged Failure to follow this instruction can result in injury or equipment