Home

1747-SDN DeviceNet Scanner Module Installation Instructions

image

Contents

1. 1747 SDN DeviceNet Scanner M odule 37 Numeric Description Take this action Code 85 Data size was incorrect for this device at e Slave device is transmitting incorrect runtime length data e Verify device is not configured for variable poll connection size e Try replacing the device 86 Device is producing zero length data idle state Check device configuration and slave node status while module is in Run M ode 87 The primary owner has not allocated the slave Put the primary owner on line 88 The connection choices polled strobed etc Reconfigure the shared input only connection s between the primary connection and the shared choice s to be the same as or a subset of the input only connection do not match primary connection s choice s 89 Slave device initialization using Auto Device e Putthe slave device into configurable Replacement parameters failed mode e Check the slave s EDS file if the slave is configured offline e Check to see if the slave device has been replaced with an incompatible device 90 User has disabled communication port Check M odule Command Register for DISABLE bit set 91 Bus off condition detected on comm port Check DeviceNet connections and physical media Module is detecting communication errors integrity Check system for failed slave devices or other possible sources of network interference 92 No netw
2. The COP instruction below copies six words of data from an M1 data file in a module positioned in slot four to an integer file N1 0 This technique is used to monitor the contents of an MO or M1 data file indirectly in a processor data file An update of these six words is made for each SLC program scan Publication 1747 INO58C EN P M ay 2002 COP COPY FILE Source M1 4 3 Dest N10 0 Length 6 1747 SDN DeviceNet Scanner M odule 19 Reduce Scan Time To reduce processor scan time use discretion when you use instructions addressing the MO or M1 files For example XIC instruction M1 2 1 1 is used in rungs 1 and 2 below adding approximately 2 ms to the scan time if you are using a 5 02 Series B processor M1 2 1 B3 1 1 10 B3 M1 2 1 B3 2 J o 2 1 14 XIC instructions in rungs 1 and 2 are addressed to the M1 data file Each of these instructions adds approximately 1ms to the scan time 5 02 Series B processor In the equivalent rungs below XIC instruction M1 2 1 1 is used only in rung 1 reducing the scan time by approximately 1 ms M1 2 1 B3 1 di ce 1 10 B3 B3 B3 2 jf 1 E 12 10 14 These rungs provide equivalent operation to those of the previous diagram by substituting XIC instruction B3 10 for XIC instruction M1 2 1 1 in rung 2 Scan time is reduced by approximately 1ms 5 02 Series B processor The first two ladder diagr
3. where the transaction is routed Publication 1747 IN058C EN P M ay 2002 1747 SDN DeviceNet Scanner M odule 31 e MAC ID node address the DeviceNet network address of the slave device where the transaction is sent This value can range from 0 to 63 The port and MAC ID attributes coupled together identify the target slave device The slave device must be listed in the scanner module s scan list and be online for the Explicit Message transaction to be completed successfully e service for each Explicit Message Request and Response the service attribute contains the service request and response codes that match the corresponding request for the TXID The following figure describes the format and mapping of transaction blocks for request and response messages in the scanner module Format of 32 word MO Transfer File Format of 32 word M1 Transfer File for Explicit Message Request for Explicit Message Response 1 0 15 0 Transaction TXID cmd status word 224 Transaction TXID cmd status word 224 Header port size word 225 Header port size word 225 3 words service MAC ID word 226 3 words service MACID word 226 Class Instance Attribute optional Transaction Transaction Service Response Data l Service Data word 255 word 255 How the Processor and Scanner Module Manage Messages File transfer operations between the processor and the scanner alway
4. M1 files are read write files MO and M1 files can be addressed in your ladder program and they can also be acted upon by the module independent of the processor scan IMPORTANT During the processor scan MO and M1 data can be changed by the processor according to ladder diagram instructions addressing the MO and M1 files During the same scan the module can change MO and M1 data independent of the rung logic applied during the scan Address the M 0 M 1 Files The addressing format for MO and M1 files is as follows Mf S w b Where M module f file 0 or 1 S slot 1 30 w word 0 maximum supplied by the module b bit 0 15 When You Cannot Use M0 M 1 Data File Addresses You can use MO and M1 data file addresses in all instructions except the OSR instruction and the instruction parameters below Instruction Parameter characterized by file indicator BSL File bit array BSR SQ0 File sequencer file SQC SQL LFL LIFO stack LFU FFL FIFO stack FFU Publication 1747 INO58C EN P May 2002 1747 SDN DeviceNet Scanner M odule 17 Monitor Bit Instructions with M 0 or M1 Addresses When you monitor a ladder program in the Run or Test mode the following bit instructions addressed to an MO or M1 file are indicated as false regardless of their actual true false logical state Mf S w Mf S w M S w Mf S w Mf S w yk 3 E L U b b b b b XIC XIO OTE OTL OTU To sho
5. Shock 0 60 C 32 140 F mn Storage Temperature EC 60068 2 1 Test Ab Un packaged Non operating Cold EC 60068 2 2 Test Bc Un packaged Non operating Dry Heat EC 60068 2 14 Test Na Un packaged Non operating Thermal Shock 40 to 85 C 40 to 185 F Relative Humidity EC 60068 2 30 Test Db Un packaged Non operating Damp Heat 5 95 non condensing Vibration EC60068 2 6 Test Fc Operating 2g 10 500Hz Shock EC60068 2 27 1987 Test Ea Unpackaged shock ES 002 Operating 30g Non operating 50g Emissions CISPR 11 Group 1 Class A with appropriate enclosure ESD Immunity EC 61000 4 2 4KkV contact discharges Radiated RF Immunity EC 61000 4 3 10V m with 1kHz sine wave 80 AM from 30M Hz to 1000M hz EFT B Immunity EC 61000 4 4 2KV at 5kHz on communications ports Surge Transient Immunity EC 61000 4 5 2KV line earth CM on signal ports Conducted RF Immunity EC 61000 4 6 10Vrms with 1kHz sine wave 80 AM from 150kHz 0 30M Hz Enclosure Type Rating None open style Wiring Type 1771 CD Category 2 10 pin Linear Plug Torque 5 7 pound inches Catalog Number 1787 PLUG10R Specifications continued on back page Publication 1747 INO58C EN P M ay 2002 Specifications Continued Certifications UL UL Listed Industrial Control Equipment when product is marked CSA CSA Certified Process Control Equipment CSA CSA Certifi
6. device on the network The bits are assigned in consecutive order to consecutive device addresses starting with node 0 at M1 S 220 0 If the bit is set the corresponding node has failed to verify Publication 1747 INO58C EN P May 2002 24 1747 SDN DeviceNet Scanner Module Explicit Message Program Control Words 224 through 255 are used for Explicit Message Program Control Use this feature to configure device parameters on your DeviceNet network via the MO and M1 files in the SLC processor that is controlling these devices This feature is described in detail on page 27 Download Output Data to the Module The SIC 500 processor writes output data to the module using two methods e output image table e MO file transfer Output Image Table The output image table is a 32 word table for the module slot that is updated from the processor with each program scan The first word word 0 of this table is reserved for the module command register The remaining 31 words can be used to transfer data from the SLC output table to the DeviceNet nodes Module Command Register The module command register is located at word 0 in the output image area for the slot To execute a command set the appropriate bits in the module command word using SLC ladder instructions Publication 1747 INO58C EN P M ay 2002 1747 SDN DeviceNet Scanner M odule 25 The following table describes the functionality of the command register bits Command
7. essage is now available to be Response available in M1 read interpreted by the ladder program file 0 Empty SLC M1 File The SLC M1 file is a 256 word file that can be used to transfer a large quantity of information to the module with a single SLC instruction IM PORTANT Transferring data using this file takes more time than using the input image table The first 150 words are used for data transfer from the module The remaining 106 words are reserved for e device active table e node status e scan counter e device idle table e device failure table e auto verify table e explicit message program control For a details on the mapping of input and output image tables refer to page 13 Device Active Table Words 206 through 209 in the M1 file are used for the Device Active Table The scanner assigns one bit in consecutive order to consecutive device addresses starting at node 0 at M1 S 206 0 If a bit is set it indicates that the node is in the scanner s scan list and has successfully communicated with the scanner module The bit is reset if the scanner tries to communicate to the node but the node has gone offline Publication 1747 IN058C EN P M ay 2002 1747 SDN DeviceNet Scanner M odule 23 Node Address Status Indicator Word 210 is used for node address and scanner diagnostic information displayed in numeric codes The high byte is the node address and the low byte is the status for that node These codes and
8. is a multicast transfer of data 64 bits in length sent by the scanner module that solicits a response from each strobed slave device There is one bit for each of the possible 64 node addresses The devices respond with their data which can be as much as 8 bytes Change of State Change of state enables the scanner module to perform a scan e whenever a network data change occurs or e at a user configurable heartbeat rate Because data is only sent on an as needed basis this feature increases system performance by reducing network traffic Publication 1747 INO58C EN P May 2002 6 1747 SDN DeviceNet Scanner Module Cyclic 1 0 Cyclic I O allows you to instruct the scanner module to perform a scan at a specific send rate Because data is only sent at a periodic rate this feature increases system performance by reducing network traffic Pass Through The SLC 500 pass through feature allows communication with the DeviceNet network from another network This feature can be used to adjust and fine tune the nodes on your network The pass through feature is not intended to replace a 1770 KFD PCD PCID or PCIDS connection to the network System Requirements for Pass Through To use the pass through feature you must meet the following hardware software and firmware requirements Component Requirement Requirement SLC 500 processor SLC 5 03 or higher SLC 5 03 or higher 1747 SDN firmware 4 015 5 001 6 00
9. the responses to the requests using the TXID field Processor Scanner Module DeviceNet Network MO file transfer Request Request Scanner Transaction Se Transaction Request Block Blocks Queue Le ne DeviceNet i are Process Request Explicit Message Meee Land Responses _ Requests and Device y nl ea Done or Error detached Response Response Scanner Transaction Transaction Response Block lt Blocks Queue M1 file transfer Explicit Message Program Control Limitations e The processor is always the DeviceNet client and the slave is always the DeviceNet server e A maximum of ten Explicit Message Request Transaction Blocks with the execute command can be queued to the scanner module at any time For example ten MO file transfers containing one transactions each can be queued at any time The scanner module receives and deletes any additional client server requests with the execute command over the maximum of ten As transactions are removed from the queue and response transaction blocks are returned to the processor additional transaction blocks can be issued in their place as long as the total does not exceed ten e The scanner module supports one transaction block per upload and download e Request Transaction Blocks can only be queued for slave devices of the scanner module and must appear in the scanner module s scan
10. 0 223 Auto Verify Failure Table 4 words 224 255 Explicit Message Program Control 32 224 255 Explicit M essage Program Control words 32 words 256 394 Pass Through 139 words 256 394 Pass Through 139 words Use RSLogix 500 Softw are to Configure M0 M1 Files To enable pass through capability of the scanner module you must configure the MO and M1 files associated with the 1747 SDN module to 395 words If you do not want to use pass through configure the files to the default length of 256 words ATTENTION The pass through feature is not intended to replace a 1770 KFD PCD PCID or PCIDS connection to the network e Pass through is intended only for fine tuning and adjustment of your network devices Do not attempt to configure your entire network using a pass through driver or a time out may occur e The pass through method is not suitable for real time monitoring of your network devices Publication 1747 INO58C EN P May 2002 14 1747 SDN DeviceNet Scanner Module Use the following procedure to configure the 1747 SDN s MO and M1 files using RSLogix 500 software 1 Run RSLogix 500 and go offline to the SLC 500 processor Project H Help Controller i Controller Properties Processor Status i Jul 10 Configuration BE Channel Configuration 2 Under the Controller folder in the Project window double click on IO Configuration The I O Configuration window will open 170
11. 1 or higher RSLinx software 2 10 or higher 2 31 or higher M 0 and M1 files Configured for 361 words Configured for 395 words Publication 1747 INO58C EN P M ay 2002 1747 SDN DeviceNet Scanner Module 7 External Module Features Use this illustration to identify the external features of the scanner module DeviceNet STATUS M odule Status Indicator MODULE NET Network Status Indicator indicates module status indicates status of DeviceNet channel communication link Node address and status displays numeric codes and indicates scanner ADDRESS ERROR node address or error lt Access door Wiring color codes O O O O 10 pin linear plug t o O inserted into DeviceN et O O port O O Front of module Publication 1747 INO58C EN P M ay 2002 8 1747 SDN DeviceNet Scanner Module Hardware and Softw are Requirements Before you install your module you need the following items e personal computer with Microsoft Windows 95 or later operating system e RSNetWorx for DeviceNet software version 2 22 or later e RSLogix 500 software e SLC 1746 chassis with SLC 5 02 5 03 5 04 or 5 05 processor For network communication you have two options e use the pass through feature
12. 47 6 5 5 Performing the ControlFlash Update oe Firmware Upgrade Kit User 1756 6 5 6 RSLogix 500 software Getting Results with RSLogix 500 9399 RL50GR RSLinx software Getting Results with RSLinx 9399 WAB32GR Connecting the DeviceNet network DeviceNet Cable Planning and Installation ny 7 2 Manual Publication 1747 INO58C EN P M ay 2002 1747 SDN DeviceNet Scanner Module 5 Module Features Slave Mode Slave mode allows processor to processor communication and enables the scanner to perform as a slave device to another master on the network When the scanner module is in slave mode it exchanges data with only one master You control what information is exchanged through scan list configuration and associated mapping functions of RSNetWorx for DeviceNet software This feature has the following variations When the scanner module is in the scanner Null mode Contains an empty or disabled scan list default Serves as a master to one or more slaves but is not M aster mode simultaneously serving as a slave to another master Slave mode Serves as a Slave to another master Dual mode Serves as both a master to one or more slaves and as a slave to another master simultaneously Poll A poll message is a point to point transfer of data 0 255 bytes sent by the scanner module that solicits a response from a single device The device responds with its input data 0 255 bytes Strobe A strobe message
13. AB Installation Instructions ur 1747 SDN DeviceNet Scanner Module Cat No 1747 SDN B Contents Use this document as a guide to install the 1747 SDN B scanner module For this information See page portant User Information 1 Prevent Electrostatic Discharge 3 Where to Find M ore Information 4 odule Features 5 External M odule Features 7 Hardware and Software Requirements 8 stall the Scanner M odule Into the Chassis 9 Connect the Scanner M odule to the DeviceNet Network 10 Apply Chassis Power 12 Understand the Data Organization of the Scanner M odule 12 Program the Scanner M odule Using the M 0 and M 1 Files 16 Upload Input Data from the Scanner M odule 20 Download Output Data from the Scanner M odule 24 Explicit M essage Program Control 27 Troubleshoot the M odule and Network 35 For this reference information See page Specifications 39 Publication 1747 INO58C EN P M ay 2002 2 1747 SDN DeviceNet Scanner Module Important User Information Because of the variety of uses for the products described in this publication those responsible for the application and use of these products must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements including any applicable laws regulations codes and standards In no event will Allen Bradley be responsible o
14. Configuration x m Current Cards Available 1 A Slot Rack Filter All 10 Ra 2 fizo Rack Not Installed gt RG Config 1 746 1 8 Any 8pt Discrete Input Module 3 I0 RackNotinstaled 7 1746116 Any 16pt Discrete Input Module 1746 132 Any 32pt Discrete Input Module Eoas 1746 08 Any 8pt Discrete Output Module 1 746 016 Any 16pt Discrete Output Module 1 746 0 32 Any 32pt Discrete Output Module AMCI 153x AMCI Series 1500 Resolver Module AMCI 1561 AMCI Series 1561 Resolver Module 1746 BAS 5 01 BASIC Module 500 5 01 1 746 BAS 5 02 BASIC Module M0 M1 capable 1 747 DCM 1 4 Node Adapter Module 1 4 Rack 1 747 DCM 1 2 Node Adapter Module 1 2 Rack 1 747 DCM 3 4 Node Adapter Module 3 4 Rack 1 747 DCM FULLNode Adapter Module Full Rack 1747 DSN 7 Distributed 1 0 Scanner 1 0 Block 1747 DSN 30 Distributed 1 0 Scanner 30 1 0 Block 1 746 FI0 41 Fast Analog 2 Ch In 2 Ch Current Out 1 746 F104Y Fast Analog 2 Ch In 2 Ch Volt Out 1746 HS Single Axis Motion Control 1 746 HSCE High Speed Counter Module Lycra Help Hide All Cards 1 746 HSRY Motion Control Module x 3 Click on the Read I O Config button to upload the I O configuration from the processor i Pott Dao 0 1747 L5424 5 04 CPU 24K Mem 05400 1 2 1747 SDN DeviceNet Scanner Module 3 4 Double click on the 1747 SDN module Publication 1747 INO58C EN P May 2002 1747 SDN DeviceNet Scanner M odule 15 The Advanced I O Con
15. DeviceNet channel is disabled for communication No communication may occur over this channel Outputs on the network are not under program control If scanner was in Run mode devices will go to their fault state 5 Reserved 6 1 halt scanner Halt Scanner All scanner operations stop when this command is issued No communications occur over either DeviceNet port No M file or discrete I O mapping occurs Outputs on the network are not under program control If scanner was in Run mode devices will go to their fault state 7 1 reboot Reboot This command causes the scanner to reset as though power had been cycled When this command is issued all scanner communication stops for the duration of the scanners initialization sequence Outputs on the network are no longer under program control If scanner was in Run mode devices will go to their fault state 8 15 Reserved 1 All reserve bits must be set to zero or improper operation may result Publication 1747 INO58C EN P May 2002 26 1747 SDN DeviceNet Scanner Module Restore Factory Default Settings Flush Memory To restore the scanner module s factory default settings follow these procedures 1 While the SLC processor in Program mode clear the module command word 0 and set bit 2 of word 0 for the scanner module to ON or 1 starting with bit 0 going from right to left this is the third bit IMPORTANT If other bits in the module command word are set then the s
16. Transaction completed successfully 2 Transaction in progress not ready 3 Error slave not in scan list 4 Error slave offline 5 Error DeviceNet port disabled offline 6 Error transaction TXID unknown 7 Error slave not responding to explicit request 8 Error Invalid command code 9 Error Scanner out of buffers 10 Error Other Client server transaction in progress 11 Error could not connect to slave device 12 Error response data too large for block 13 Error invalid port 14 Error invalid size specified 15 Error connection busy 16 255 Reserved e TXID transaction ID when you create and download a request to the scanner the processor s ladder logic program assigns a TXID to the transaction This is a one byte integer in the range of 1 to 255 The scanner uses this value to track the transaction to completion and retums the value with the response that matches the request downloaded by the processor The ladder logic program monitors rollover and usage of TXID values Transaction Header 3 words 15 0 TXID cmd status port size service MAC ID Transaction Body 29 words word 224 word 225 word 226 word 255 One word two bytes 16 bits e size the size of the transaction body in bytes The transaction body can be as many as 29 words 58 bytes in length If the size exceeds 29 words an error code will be returned e port the DeviceNet port zero
17. Word 0 5 0 Operating Mode Description Bit Operating Mode 0 1 Run mode 0 Idle Run mode The scanner module maps output data from its scanner output table M 0 and discrete outputs to each device on the network Inputs are received and mapped into the scanner input table M 1 and discrete inputs Outputs on the network are under SLC program control Idle The scanner does not map output data to the devices but keeps network connections to devices open so device failures can be detected Input data is returned from devices and mapped into the scanner input table M 1 and the discrete inputs Outputs on the network are not under program control and will be in their configured idle state The scanner is put into this mode to perform online configuration of the scanner database tables 1 1 fault network Fault Network rec The scanner stops communicating with devices on the network No outputs or inputs are mapped Outputs on the network are not under program control If scanner was in Run mode devices will go to their fault state 2 1 restore to factory Restore to Factory Defaults Flush Memory defaults flush memory The scanner may receive a scan list or configuration that causes inappropriate scanner behavior It may be necessary to restore to the scanner module s factory defaults to recover from this state This procedure is described below 3 Reserved 4 1 disable netw ork Disable Netw ork The
18. affic from other modules detected on the Check the network configuration Scanlist may be network empty 76 No direct network traffic for module detected None The module hears other network communication 77 Data size expected by the device does not match Reconfigure your module for the correct transmit scan list entry and receive data sizes 78 Slave device in scan list table does not exist Add the device to the network or delete the scan list entry for that device 79 odule has failed to transmit a message Make sure that your module is connected to a valid network Check for disconnected cables 80 odule is in Idle mode Put controller in Run mode Enable Run bit in module command register 81 odule is in FAULT mode Check M odule Command Register for fault bit set 82 Error detected in sequence of fragmented 1 0 Check scan list table entry for slave device to make essages from device sure that input and output data lengths are correct Check slave device configuration 83 Slave device is returning error responses when Check accuracy of scan list table entry Check odule attempts to communicate with it slave device configuration Slave device may be in another master s scan list Reboot slave device 84 odule is initializing the DeviceNet network None This code clears itself once module attempts to initialize all slave devices on the network Publication 1747 INO58C EN P M ay 2002
19. ailure is detected you can put the communication into the Idle mode so that all output devices go to a safe state The SLC program can monitor the bits in the module status register and set the appropriate bits of the module command register to automatically control the operating mode of the module should a device failure occur Status Word I s 0 Operating Mode Description Bit Operating Mode 0 1 Run mode 0 Idle mode Run echoed from the module The scanner module maps output data from its scanner output table M 0 and command register discrete outputs to each device on the network Inputs are received and mapped into the scanner input table M 1 and discrete inputs Outputs on the network are under SLC program control Idle The scanner does not map output data to the devices but keeps network connections to devices open so device failures can be detected Input data is returned from devices and mapped into the scanner input table M 1 and the discrete inputs Outputs on the network are not under program control and will be in their configured Idle state The scanner must be put into this mode to perform offline configuration of the scanner database tables I 1 fault netw ork echoed Fault Netw ork from the module command The scanner has stopped communicating with devices on the network No outputs register or inputs are mapped Outputs on the network are not under program control If scan
20. amage or economic loss Identifies information about practices or circumstances that can ATTENTION lead to personal injury or death property damage or economic loss Identifies information that is critical for successful application IMPORTANT and understanding of the product Publication 1747 IN058C EN P M ay 2002 1747 SDN DeviceNet Scanner M odule 3 ATTENTION Environment and Enclosure This equipment is intended for use in a Pollution Degree 2 industrial environment in overvoltage Category II applications as defined in IEC publication 60664 1 at altitudes up to 2000 meters without derating This equipment is considered Group 1 Class A industrial equipment according to IEC CISPR Publication 11 Without appropriate precautions there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance This equipment is supplied as open type equipment It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts The interior of the enclosure must be accessible only by the use of a tool Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifi
21. ams in the last section illustrate a technique you use to capture and use MO or M1 data as it exists at a specific time In the first diagram bit M1 2 1 1 could change state between rungs 1 and 2 This could interfere with the logic applied in rung 2 The second diagram avoids the problem If rung 1 is true bit B3 10 captures this information and places it in rung 2 The following diagram illustrates another economizing technique The COP instruction addresses an M1 file adding approximately 4 29 ms to the scan time if you are using a 5 02 Series B processor You can save scan time by making this rung true only periodically For example you can use a clock bit S 4 8 clock bits are discussed in the programming manual Publication 1747 INO58C EN P May 2002 20 1747 SDN DeviceNet Scanner Module A rung such as this might be used when you want to monitor the contents of the M1 file but monitoring need not be continuous S 4 Bll COP OSR COPY FILE S 4 8 causes the M1 4 3 file 8 0 Source M1 4 3 to update the N10 0 file rah ae every 2 56 seconds In this example a COP instruction can be used to monitor the contents of an M1 file When the instruction goes true the six words of data in file M1 4 3 is captured as it exists at that time and placed in file N10 0 All subsequent logic should address the data in N10 0 The data will be consistent and it shortens scan time by eliminating reads to the module each time an MO
22. ata Attribute data was not saved prior to this request 19H Store operation failure Attribute data was not successfully saved 1FH Vendor specific error Second byte may offer details refer to vendor documentation 20H Invalid parameter Parameter associated with request is invalid DOH Reserved and service specific Used only when none of the standard error codes CFFH errors supplemented by the second byte accurately describes the problem Publication 1747 INO58C EN P M ay 2002 1747 SDN DeviceNet Scanner M odule 35 Troubleshoot the Module and Network The bicolor green red module status indicator MODULE located on the front of your module displays module status It indicates whether the module has power and is functioning properly Module Status Troubleshooting If the MODULE Then Take this action indicator is Off There is no power applied to the module Verify power connections and apply power Green The module is operating normally No action required Flashing Green The module is not configured Configure the module Flashing Red There is an invalid configuration Check configuration setup Red The module has an unrecoverable fault Replace the module The DeviceNet channel has a bicolor green red network status indicator NET The following table provides troubleshooting information about the DeviceNet channel communication link DeviceNet Channel Com
23. canner module will generate an error 2 Set bit 0 of word 0 for the scanner module to OFF or 0 3 On the SLC processor cycle the keyswitch from Program mode to Run mode then back to Program mode IM PORTANT The ladder logic may set bit 0 of word 0 for the scanner module If this happens then you must disable or delete this rung from the ladder program 4 When the code F9 is displayed on the Address Error LED display the default settings have been restored 5 Set bit 2 of word 0 for the scanner module to OFF or 0 6 Cycle power to the 1746 chassis to restore normal operation to the scanner module The scanner module will now have its factory default settings node 63 125 K baud no scanlist Publication 1747 INO58C EN P M ay 2002 1747 SDN DeviceNet Scanner M odule 27 SLC MO File The SIC MO file is a 256 word file that can be used to transfer a large quantity of information to the module with a single SLC instruction Transferring data using this file can take several scans and more time than using the output image table The first 150 words are used for sending data to DeviceNet nodes The next 74 words are reserved for future use the next 32 words are used for explicit message program control and the final 139 words are used for pass through For a detailed description of the mapping of input and output image tables refer to page 13 Using Explicit Message Program Control Use the Ex
24. cations See NEMA Standards publication 250 and IEC publication 60529 as applicable for explanations of the degrees of protection provided by different types of enclosure Also see the appropriate sections in this publication as well as the Allen Bradley publication 1770 4 1 Industrial Automation Wiring and Grounding Guidelines for additional installation requirements pertaining to this equipment Prevent Electrostatic Discharge This equipment is sensitive to electrostatic discharge which can cause internal damage and affect normal operation Follow these guidelines when you handle this equipment e touch a grounded object to discharge potential static e wear an approved grounding wrist strap e do not touch connectors or pins on component boards e do not touch circuit components inside the equipment e if available use a static safe workstation e when not in use store the equipment in appropriate static safe packaging Publication 1747 INO58C EN P May 2002 4 1747 SDN DeviceNet Scanner Module Where to Find More Information The following table describes related documentation To order a copy or to view or download an online version visit The Automation Bookstore at www theautomationbookstore com For information about See this document Publication number Configuring the scanner module and SLC 500 DeviceNet Scanner M odule eatin hardware in an example User M anual 17
25. e can accommodate one request or response for each transaction block You must format each transaction block as shown in the following figure 15 0 TXID cmd status word 224 Transaction Header port size word 225 3 words service MAC ID word 226 Transaction Body 29 words word 255 One word two bytes 16 bits The transaction block is divided into two parts e transaction header contains information that identifies the transaction to the scanner and processor e transaction body in a request this contains the DeviceNet Class Instance Attribute and Service Data portion of the transaction In a response this contains only the response message Each of the data attributes in the transaction header are one byte in length e command status for each download you assign a command code to instruct the scanner how to administer the request Command Code Description 0 Ignore transaction block block empty 1 Execute this transaction block 2 Get status of transaction TXID 3 Reset all client server transactions 4 Delete transaction from response queue 5 255 Reserved Publication 1747 INO58C EN P May 2002 30 1747 SDN DeviceNet Scanner Module For each upload the status code provides the processor with status on the device and its response Status Code Description 0 Ignore transaction block block empty 1
26. ed Process Control Equipment for Class Division 2 Group A B C D Hazardous Locations ce European Union 89 336 EEC EM C Directive compliant with EN 50081 2 Industrial Emissions EN 50082 2 Industrial Immunity European Union 73 23 EEC LVD Directive compliant with EN 61131 2 Programmable Controllers C Tick3 Australian Radiocommunications Act compliant with AS NZS 2064 Industrial Emissions ODVA ODVA conformance tested to ODVA DeviceNet specifications User M anual 1747 6 5 5 To remain compliant with UL CSA certification the DeviceNet power supply must meet NEC Class 2 requirements 2Use this conductor category information for planning conductor routing as described in publication 1770 4 1 Industrial Automation Wiring and Grounding Guidelines 3See the Product Certification link at www ab com for Declarations of Conformity Certificates and other certification details DeviceNet is a trademark of the Open DeviceNet Vendors Association SLC SLC 500 SLC 5 02 SLC 5 03 SLC 5 04 SLC 5 05 RSLinx RSLogix 500 and RSNetW orx are trademarks of Rockwell Automation Inc Windows is a trademark of Microsoft Corporation www rockwellautomation com Corporate Headquarters Rockwell Automation 777 East Wisconsin Avenue Suite 1400 Milwaukee WI 53202 5302 USA Tel 1 414 212 5200 Fax 1 414 212 5201 Headquarters for Allen Bradley Products Rockwell Software Products and Global Manufacturing Solu
27. equest issued there is a response DeviceNet 5 drop line FE 200 am w 7 1203 GKS 1305 AC Slave s Explicit Communication Drive Request Adapter 1 Format an MO file transfer in the processor to send an Explicit Message Request to the scanner module download 2 The scanner module transmits the Explicit Message Request to the slave device over the DeviceNet network 3 The slave device transmits the Explicit Message Response back to the scanner and is queued into a file transfer buffer 4 The processor uses an M1 file transfer to retrieve the Explicit Message Response from the scanner s buffer upload 5 Format an MO file transfer with a Delete Response Command and the current transaction ID read in step 4 The transaction IDs are deleted and can be reused The scanner module requires a precisely formatted MO and M1 file transfer size of 32 words including words 224 255 The scanner module uses the file memory content as a client server request Publication 1747 INO58C EN P M ay 2002 1747 SDN DeviceNet Scanner M odule 29 How to Format the Explicit Message Transaction Block Up to ten 32 word transaction blocks may be queued within the scanner module for Explicit Message Program Control The transaction blocks accommodate both the download of Explicit Message Requests and the upload of Explicit Message Responses The scanner modul
28. figuration window will open ATE F 1727 500 Oayeihiei 5 carr Mods t Hassan Iras Aone SE Mipamumn Output sors Sema _ Seanad brp teach je Scanned Output Words a bem See Routes SALE ln MO Length 335 Wi Length Frs BE Fie Length lt Eda G Daia 5 Set the MO Length and the M1 Length to one of the following a 256 for 1747 SDN firmware prior to 4 015 for no pass through support b 361 for 1747 SDN firmware 4 015 5 001 for pass through support c 395 for 1747 SDN firmware 6 001 or higher for improved pass through support 6 Click on the OK button 7 Download the changes to the processor IM PORTANT The SLC 500 must be placed in Run mode at least one time after downloading the M0 Miconfiguration to enable 1747 SDN pass through transactions For more information on how to e configure your module for DeviceNet operation e map data from DeviceNet nodes to M1 MO input and output image files refer to the Getting Results with RSLogix 500 publication number 9939 RL50GR and the 1747 SDN Scanner User Manual publication number 1747 6 5 5 Publication 1747 INO58C EN P May 2002 16 1747 SDN DeviceNet Scanner Module Program the Module Using the SLC M0 and M1Files The M0 and M1 files are data files that reside in the module There is no image for these files in the processor memory The MO file is a module output file and the M1 file is a module input file Both MO and
29. list Publication 1747 INO58C EN P M ay 2002 1747 SDN DeviceNet Scanner M odule 33 e If a slave device is not communicating at the time the scanner module processes its Request Transaction Block the scanner module will return an error status for that transaction e Check documentation of destination device for specifics concerning services supported and Class Instance Attribute information At a minimum the scanner module supports the following DeviceNet services in Request Transaction Blocks Service Name Service Code Example Get_Attribute_Single OE hex Upload a single parameter value from a device Set_Attribute_Single 10 hex Download a single parameter value to a device Get_Attribute_All 01 hex Upload all parameter values from a device Set_Attribute_All 02 hex Download all parameter values to a device e All transaction blocks are processed therefore an unused transaction block must be left blank e Client Server commands and requests with transaction IDs that are in use are ignored by the scanner module e Ifa slave device retums a DeviceNet error in response to the request downloaded from the processor the scanner recognizes the error as a successful transaction status code 1 Publication 1747 INO58C EN P May 2002 34 1747 SDN DeviceNet Scanner Module A failure to respond to the request within the number of retries or timeout period specified for the Explicit Message Connecti
30. munications Troubleshooting Ifthe NET Then Which indicates Take this action indicator is Off The device has no power or the The channel is disabled Power up the module provide network power to channel is disabled for communication for DeviceNet the channel and be sure the channel is enabled due to bus off condition loss of communication in both the module configuration table and the network power or has been module command word intentionally disabled Green Normal operation All slave devices in the None scan list table are communicating normally with the module Flashing he two digit numeric display for the The channel is enabled Configure the scan list table for the channel to Green channel indicates an error code that but no communication add devices provides more information about the is occurring condition of the channel Flashing he two digit numeric display for the At least one of the Examine the failed device and the scan list table Red channel displays an error code that slave devices in the for accuracy provides more information about the modules scan list table condition of the channel has failed to communicate with the module Red he communications channel has The module may be Reset module If failures continue replace ailed The two digit numeric display defective module orthe channel displays an error code hat provides more information about he condition of
31. ner was in Run mode devices will go to their fault state 2 Reserved 3 Reserved 4 1 disable network echoed Disable Netw ork from the module command The DeviceNet channel is disabled for communication No communication may register occur over this channel Outputs on the network are not under program control If scanner was in Run mode devices will go to their fault state 5 Reserved 6 1 device failure at least Device Failure one device failed One or more of the devices in the scanners scan list has failed to communicate with the scanner 7 Reserved 8 1 autoverify failure at Autoverify Failure least one device has failed One or more of the devices in the scanner s scan list is returning an incorrect auto verify number of bytes of data in response to a connection establishment according to the information stored in the scanner s scan list 9 Reserved 10 1 communication failure Communications Failure There is no communication on the port Publication 1747 INO58C EN P May 2002 22 1747 SDN DeviceNet Scanner Module Status Word l s 0 Operating Mode Description Bit Operating Mode 11 Reserved 12 1 duplicate node address Duplicate Node Address Failure failure There is another node with the same address as the scanner on the network 13 Reserved 14 Reserved 15 1 Explicit Message Explicit Message Program Control Program Control A response to a previously sent Explicit M
32. ombinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation Informations sur l utilisation de cet quipement en environnements dangereux Les produits marqu s CLI DIV 2 GP A B C D ne conviennent qu une utilisation en environnements de Classe Division 2 Groupes A B C D dangereux et non dangereux Chaque produit est livr avec des marquages sur sa plaque d identification qui indiquent le code de temp rature pour les environnements dangereux Lorsque plusieurs produits sont combin s dans un syst me le code de temp rature le plus d favorable code de temp rature le plus faible peut tre utilis pour d terminer le code de temp rature global du syst me Les combinaisons d quipements dans le syst me sont sujettes inspection par les autorit s locales qualifi es au moment de l installation EXPLOSION HAZARD e Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous e Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous Secure y external connections that mate to this equipment by using screws sliding latches threaded connectors or other means provided with this product e Substitution of components may impair suitability for Class Division 2 e If this product contains batterie
33. on is recognized by the scanner module as an error The error code is returned in the status attribute of the transaction header Explicit Messaging Error Codes Error codes have two bytes of data The first byte is a General Error Code and the second is an optional Additional Code Field that may contain additional information about the error If this field is unused the value OFFH is shown The following table describes explicit messaging error codes Numeric Name Description Code 02H Resource unavailable A needed resource was not available 08H Service unsupported Service is not defined or implemented for this class instance 09H Invalid attribute value Data is invalid for the specified attribute OBH Already in requested state Object is in the requested state redundant request OCH Object state conflict Not allowed with object in present state OEH Attribute cannot be set Read only attribute OFH Privilege violation A permission privilege check failed 10H Device state conflict Not allowed with device in present state 11H Reply too big Reply larger than buffer allocated when connection was established 13H Too little data Request included insufficient data 14H Attribute not supported Attribute number is incorrect 15H Too much data Request included extra data 16H Object does not exist Class instance numbers are incorrect 18H No stored attribute d
34. or M1 address is encountered in the program Upload Input Data from the Module to the SLC Processor The SLC 500 processor reads input data from the module using two methods e input image table e M1 file transfer Input Image Table The input image table is a 32 word table for the module slot that is updated by the processor with each program scan The first word word 0 is reserved for the module status register The remaining 31 words can be used to transfer DeviceNet input data to the SLC input image table The addressing format is I S w b Where S slot w word 0 31 b bit 0 15 Module Status Register The module status register is located at word 0 in the input image area for the slot Bits 0 5 echo back to the processor the current state of bits 0 5 of the module command register The echoes verify that the commands were executed The module sets the remaining bits when it detects a problem The bits latch in the ON state until the problem clears Bits 6 and 8 indicate that you should read the device failure table for more specific information about which devices failed Publication 1747 INO58C EN P M ay 2002 1747 SDN DeviceNet Scanner M odule 21 You can use bit 6 to keep the communication port in the Idle mode until the bit clears When the bit clears this indicates that all devices in the scanner s scan list are up and available When the devices are available you can put the port in Run mode If a device f
35. ork power detected on communication Provide network power M ake sure that module port drop cable is providing netw ork power to module comm port 95 Application FLASH update in progress None Do not disconnect the module while application FLASH is in progress You will lose any existing data in the modules memory 97 odule operation halted by user command Check M odule Command Register for HALT bit set 98 Unrecoverable firmware failure Service or replace your module 99 Unrecoverable hardware failure Service or replace your module E2 RAM Test Failure Service or replace your module E4 Lost power during FLASH upgrade Service or replace your module E5 No boot or main code Service or replace your module E9 odule memory has been flushed for factory Cycle module power to recover default settings Publication 1747 INO58C EN P May 2002 38 1747 SDN DeviceNet Scanner Module The follow ing information applies when operating this equipment in hazardous locations Products marked CL I DIV 2 GP A B C D are suitable for use in Class Division 2 Groups A B C D Hazardous Locations and nonhazardous locations only Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code W hen combining products within a system the most adverse temperature code lowest T number may be used to help determine the overall temperature code of the system C
36. plicit Message Program Control feature to configure device parameters on your DeviceNet network via the MO and M1 files Use the Explicit Message Program Control feature to e transmit configuration data from your scanner module to its slave devices on your DeviceNet network e receive status and diagnostics from these devices on your DeviceNet network e make runtime adjustments to device parameters according to changing conditions detected by your processor Publication 1747 INO58C EN P May 2002 28 1747 SDN DeviceNet Scanner Module How the Explicit Message Program Control Feature Works MO file transfer including words 224 255 sent from processor to scanner module M1 file transfer including words 224 255 sent from scanner module to processor LA M1 file transfer is completed TXIDs A ps are deleted and can a Masters Explicit aa be reused Request 4 ON PO RE Le A DeviceNet trunk line Loreena Explicit Message A message used to transmit commands data requests for data or responses The message is sent from a client on the DeviceNet network to a server on that network Request An explicit message sent by a client to a server requesting the server to perform a function Response An explicit message sent by a server to a client in response to the client s request For every r
37. r liable for indirect or consequential damage resulting from the use or application of these products Any illustrations charts sample programs and layout examples shown in this publication are intended solely for purposes of example Since there are many variables and requirements associated with any particular installation Allen Bradley does not assume responsibility or liability to include intellectual property liability for actual use based upon the examples shown in this publication Allen Bradley publication SGI 1 1 Safety Guidelines for the Application Installation and Maintenance of Solid State Control available from your local Allen Bradley office describes some important differences between solid state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication Reproduction of the contents of this copyrighted publication in whole or part without written permission of Rockwell Automation is prohibited Throughout this publication notes may be used to make you aware of safety considerations The following annotations and their accompanying statements help you to identify a potential hazard avoid a potential hazard and recognize the consequences of a potential hazard Identifies information about practices or circumstances that can cause an explosion in a hazardous environment which may lead to personal injury or death property d
38. rolFLASH Firmware Upgrade Kit User Manual publication 1756 6 5 6 Make Sure That Your Processor and Adapter are Compatible You can use the 1747 SDN Scanner Module in an I O chassis any slot except for the left most which is reserved for the SLC 500 processor IM PORTANT You cannot use the scanner module in a remote I O chassis with a 1747 ASB adapter module The adapter module does not support M file transfer Install the M odule Into the Chassis To install your module into the chassis 1 Turn off the chassis power supply If you insert or remove the scanner module with power WARNING applied to this module or any device on the network an electrical arc can occur This could cause an explosion in hazardous location installations Be sure that power is removed or the area is nonhazardous before proceeding Publication 1747 INO58C EN P May 2002 10 1747 SDN DeviceNet Scanner Module 2 Select a slot for the module in the chassis You may use any slot except the leftmost slot which is reserved for the SLC 500 processor FA al SIN _ ESS HE Na ae BEL TE 3 Insert the module into the slot you have selected 4 Apply firm even pressure to seat the module in the I O chassis backplane connectors Connect the Module to the DeviceNet Netw ork To connect your module to the DeviceNet network 1 Turn off the network power supply If you connect the scanner module with power applied
39. s they must only be changed in an area known to be nonhazardous o Publication 1747 IN058C EN P M ay 2002 AVERTISSEMEN RISQUE D EXPLOSION e Couper le courant ou s assurer que environnement est class non dangereux avant de d brancher quipement e Couper le courant ou s assurer que environnement est class non dangereux avant de d brancher les connecteurs Fixer tous es connecteur externes reli s cet quipement l aide de vis loquets coulissants connecteurs filet s ou autres moyen avec ce produi s i e La substitution de composants peut rendre cet equipeme inadapte a une utilisation en environnement de Classe Division 2 e S assurer que l environnement est class non dangereux avant de changer les piles v fournis 1747 SDN DeviceNet Scanner M odule 39 Specifications M odule Location SLC 5 02 or later chassis Module Defaults Node Address 63 Baud Rate 125 Kbits s Power Consumption Backplane Current DeviceNet 5Vdc 500 mA 24Vdc 90mA Class 2 Isolation Voltage Optical Isolation between backplane and DeviceNet channel tested to withstand 500Vac for 60 seconds 1 Megohm resistor from DeviceNet channel to chassis Operating Temperature EC 60068 2 1 Test Ad Operating Cold EC 60068 2 2 Test Bd Operating Dry Heat EC 60068 2 14 Test Nb Operating Thermal
40. s originate in the processor The scanner module can only wait for the processor to download a transaction block to the module or request an upload of a transaction block from the module Once an Explicit Message Request transaction block is downloaded to the scanner module a ladder logic program in the processor polls the scanner module for the transaction block containing the Explicit Message Response for that request This is done by the processor with an M1 file transfer on the scanner module Depending on the network load the scanner could take a few seconds to complete the request When a response is loaded bit 15 of the module status register is set to 1 The program may have to poll the scanner module a number of times before the scanner returns a Response Transaction Block The scanner module recognizes I O data and control as higher priorities over explicit messaging on DeviceNet Publication 1747 INO58C EN P May 2002 32 1747 SDN DeviceNet Scanner Module Message lengths and slave device types impact transaction message completion times If the processor has queued multiple Explicit Message Transactions to the scanner module for multiple slave devices the transactions with the slaves may not complete in the order in which the requests were received The slave responses are queued to the 32 word M1 file transfer in the order in which they are received As response transaction blocks are uploaded the processor s program matches
41. t 88 2 Firmware major revision 01 through 7F hexadecimal 3 Firmware minor revision 01 through FF hexadecimal 4 Baud rate indicates 00 for the default of 125 01 for 250 or 02 for 500 Kbits s 5 Node address 00 to 63 with 63 as the default Use the RSNetWorx for DeviceNet software to change the baud rate and node address Refer to the Numeric Code Display Summary table on page 36 for a complete listing of numeric displays Understand the Data Organization of the Module The module has four data areas to transfer data status and command information between the module and the processor e SLC input image table e SLC output image table e SLC M1 file e SLC MO file Publication 1747 INO58C EN P M ay 2002 Input and Output Image Tables 1747 SDN DeviceNet Scanner M odule 13 The following table describes the mapping of the 1747 SDN input and output image tables and the M1 and MO files Words SLC Input Image Words SLC Output Image 0 Status 0 Command 1 31 DeviceNet Input Data 31 words 1 31 DeviceNet Output Data 31 words Words SLC M1 File Words SLC MO File 0 149 DeviceNet Input Data 150 words 0 149 DeviceNet Output Data 150 words 150 205 Reserved 56 words 150 223 Reserved 206 209 Device Active Table 4 words 74 words 210 Node Address Status Indicator 1 word 211 Scan Counter 1 word 212 215 Device Idle Table 4 words 216 219 Device Failure Table 4 words 22
42. the channel Publication 1747 INO58C EN P May 2002 36 1747 SDN DeviceNet Scanner Module Numeric Codes and Descriptions Your module uses numeric displays to indicate diagnostic information about the status of your module The display flashes at 1 second intervals The following table summarizes the meanings of the numeric codes Numeric Code Display Summary Numeric Description Take this action Code 0 63 Normal operation The numeric display indicates None the 1747 SDN node address on the DeviceNet network 70 odule failed Duplicate Node Address check Change the module channel address to another available one The node address you selected Is already in use on that channel 71 Illegal data in scan list table node number Reconfigure the scan list table and remove any alternately flashes illegal data 72 Slave device stopped communicating node Inspect the field devices and verify connections number alternately flashes 73 Device s identity information does not match Verify that the correct device is at this node electronic key in scan list table entry number M ake sure that the device at the scrolling node address matches the desired electronic key vendor product code product type etc 74 Data overrun on port detected Modify your configuration and check for invalid data Check network communication traffic 75 No tr
43. their descriptions are listed on page 36 Scan Counter Word 211 is used for the module scan counter The module increments this counter whenever a scan of the DeviceNet devices is completed The counter rolls over when it reaches a maximum value of 65535 It is located at M1 S 211 Device Idle Table Words 212 through 215 in the M1 file are used for the device idle table This table indicates that there are devices on the network in Idle mode The module tracks devices in Idle mode by assigning one of the 64 bits in the table to each device on the network The bits are assigned in consecutive order to consecutive device addresses starting at mode 0 at M1 S 212 0 Device Failure Table Words 216 through 219 in the M1 file are used for the device failure table This table indicates communication failures of devices on the network The module tracks device failures by assigning one of the 64 bits in the table to each device on the network The bits are assigned in consecutive order to consecutive device addresses starting at mode 0 at M1 S 216 0 Auto Verify Failure Table Words 220 through 223 in the M1 file are used for the auto verify failure table The auto verify failure table is used to verify that data size received from the device matches the setting in the scanners scanlist entry for that node This check occurs at connection establishment time The module tracks auto verify failures by assigning one of the 64 bits in the table to each
44. tions Americas Rockwell Automation 1201 South Second Street Milwaukee WI 53204 2496 USA Tel 1 414 382 2000 Fax 1 414 382 4444 Europe Rockwell Automation SA NV Vorstlaan Boulevard du Souverain 36 BP 3A B 1170 Brussels Belgium Tel 32 2 663 0600 Fax 32 2 663 0640 Asia Pacific Rockwell Automation 27 F Citicorp Centre 18 Whitfield Road Causeway Bay Hong Kong Tel 852 2887 4788 Fax 852 2508 1846 Headquarters for Dodge and Reliance Electric Products Americas Rockwell Automation 6040 Ponders Court Greenville SC 29615 4617 USA Tel 1 864 297 4800 Fax 1 864 281 2433 Europe Rockwell Automation Br hlstraRe 22 D 74834 Elztal Dallau Germany Tel 49 6261 9410 Fax 49 6261 17741 Asia Pacific Rockwell Automation 55 Newton Road 11 01 02 Revenue House Singapore 307987 Tel 65 351 6723 Fax 65 355 1733 Publication 1747 IN058C EN P M ay 2002 PN 957678 59 Supersedes Publication 1747 INO58B EN P August 2001 Copyright 2002 Rockwell Automation Inc All rights reserved Printed in the U S A
45. to communicate with the DeviceNet network from another network This method is intended for fine tuning and adjustment of network devices e use a 1770 KFD RS 232 DeviceNet adapter or 1784 PCD PCID or PCIDS DeviceNet PC Card This method is necessary for a complete network configuration and real time monitoring of your network devices Before you install your module you must know how to e program and operate an Allen Bradley SLC 500 programmable controller e install and configure the devices on your DeviceNet network Electronic Data Sheet Requirement This release of the scanner module requires the latest EDS file for RSNetWorx for DeviceNet software If the software displays the device as an unknown device the EDS file must be downloaded You can get the latest EDS file online at http www ab com networks eds Once you are at this location 1 Select DeviceNet 2 Enter the catalog number 1747 SDN 3 Enter major revision number 4 Enter minor revision number 5 Select Search For more information contact Rockwell Automation Technical Support at 440 646 5800 Publication 1747 INO58C EN P M ay 2002 1747 SDN DeviceNet Scanner Module 9 Perform the ControlFLASH Update If you have the previous release of firmware and you want to upgrade it to this release you must perform the ControlFLASH update To get the kit contact Rockwell Automation Technical Support at 440 646 5800 To install the kit refer to the Cont
46. to this WARNING module or any device on the network an electrical arc can occur This could cause an explosion in hazardous location installations Be sure that power is removed or the area is nonhazardous before proceeding Publication 1747 IN058C EN P M ay 2002 1747 SDN DeviceNet Scanner M odule 11 2 Connect the DeviceNet drop line to the ten pin linear plug by matching the wire insulation colors to the colors shown on the label 424V Red AF woe N KY Can_H White Ten pin Red Drain Shield linear plug Can_LBlue gt o 4 24V Return Black et En 3 Locate the DeviceNet port connector on the front of the module 4 Insert the ten pin linear plug into the DeviceNet port connector AER IO T SN Ten pin linear plug i DeviceN et port connector DeviceNet drop line You have installed and wired your module To operate the module you must apply power and then configure and program the SLC processor to communicate with it We describe how to do this in the next three sections Publication 1747 IN058C EN P M ay 2002 12 1747 SDN DeviceNet Scanner Module Apply Chassis Power When you apply chassis power the module numeric indicators cycle through the following displays DeviceNet Module STATUS numeric MODULE NET indicators ADDRESS ERROR 1 Seven segment lamp tes
47. w the state of the MO or M1 addressed bit transfer the state to an internal processor bit This is illustrated below where an internal processor bit is used to indicate the true false state of a rung B3 B3 EQU M0 3 0 E EQUAL 0 1 Source N7 12 1 Source B N7 3 This rung does not show its true rung state because the EQU instruction is always shown as true and the MO instruction is always shown as false B3 B3 rm EQU B3 1 E EQUAL 0 1 Source A N7 12 2 MO 3 0 Source B N7 3 C 1 OTE instruction B3 2 has been added to the rung This instruction shows the true or false state of the rung Transfer Data Between Processor Files and M0 or M1 Files The processor does not contain an image of the MO or M1 file so you must edit and monitor MO and M1 file data via instructions in your ladder program For example you can copy a block of data from a processor data file to an MO or M1 data file or vice versa using the COP copy instruction in your ladder program Publication 1747 INO58C EN P M ay 2002 18 1747 SDN DeviceNet Scanner Module The COP instructions below copy data from a processor bit file and integer file to an MO file S 1 COP ae COPY FILE 15 Source B3 0 7 Dest M0 1 0 First scan bit It makes this rung Length 16 true only for the first scan after entering Run mode COP COPY FILE Source N7 0 Dest M0 1 16 Length 27

Download Pdf Manuals

image

Related Search

Related Contents

Utilizzo dell`origine dati TWAIN  Phaser 3300MFP Brochure  ねじゲージ - レッキス工業  PPDE.13.Piano manutenzione opera  CANAL JET  Circular Reglamentaria Externa DODM    取扱説明書  The OTISS User Manual - Public Schools of North Carolina  Katun 38750  

Copyright © All rights reserved.
Failed to retrieve file