1. Display panel The control includes a digital display panel that may be either locally or remotely mounted The operator screens are made up of internationally accepted symbols or English test so translations are not required The display is composed of a backlit LCD display with a series of 6 generator status LED lamps The display is accompanied by six tactile feel membrane switches that are used by the operator to navigate through control menus and to make control adjustments There are no rotary potentiometers in the control All adjustments are made via the display panel or InPower It is configurable for units of measurement It is adjustable for screen contrast and brightness Our energy working for you www cumminspower com 2010 Cummins Power Generation Inc All rights reserved Cummins Power Generation and Cummins are registered trademarks of Cummins Inc InPower and Our energy working for you are trademarks of Cummins Power Generation Other company product or service names may be trademarks or service marks of others Specifications are subject to change without notice S 1506d 6 10 Page 2 of 7 The run oft auto switch function is integrated into the display panel therefore an external switch is not required All data on the control can be viewed by scrolling through screens with the navigation keys The control displays current active faults and a time ordered history of previous faults LED ind
2. 2010 Cummins Power Generation Inc All rights reserved Cummins Power Generation and Cummins are registered trademarks of Cummins Inc InPower and Our energy working for you are trademarks of Cummins Power Generation Other company product or service names may be trademarks or service marks of others Specifications are subject to change without notice S 1506d 6 10 Page 4 of 7 The display panel is designed for proper operation in ambient temperatures from 20 C to 70 C 4 F to 158 F and for storage from 30 C to 80 C 22 F to 176 F The control board is fully encapsulated to provide superior resistance to dust and moisture The display panel has a single membrane surface which is impervious to effects of dust moisture oil and exhaust fumes This panel uses a sealed membrane to provide long reliable service life in harsh environments The control system is specifically designed and tested for resistance to RFI EMI and to resist effects of vibration to provide a long reliable life when mounted on a generator set The control includes transient voltage surge suppression to provide compliance to referenced standards Control interface Input signals to the base control include Generator set status lamp Remote start signal Remote emergency stop Configurable inputs Control includes 2 input signals from customer discrete devices that are configurable for warning shutdown or status indication
3. Voltage regulation adjustments Power Generation Cycle cranking Configurable fault set up Configurable output set up Meter calibration Display language and units of measurement Other information Control not communicating Pop up timers to indicate time remaining on time delays in the system Internal control functions Engine control 12 VDC 24 VDC battery operations The 1301 control will operate either on 12 VDC or 24 VDC batteries Isochronous governing Capable of controlling engine speed within 0 25 for any steady state load from no load to full load Frequency drift will not exceed 0 5 for a 33 C 60 F change in ambient temperature over an 8 hour period The maximum actuator drive current of the electronic governing power stage option is 6 0 amps continuous and 10 amps peak for 1 second This feature can be disabled to allow the use of an external governor Temperature dependent governing dynamics Modifies the engine governing control parameters as a function of engine temperature Allows engine to be more responsive when warm and more stable when operating at lower temperature levels Remote start mode The 1301 control accepts a ground signal from remote devices to automatically start the generator set and immediately accelerate to rated speed and voltage The control can incorporate a time delay start Remote emergency stop he control accepts a ground signal from an exter
4. as well as message displayed Output signals from the 1301 control include Configurable relay outputs Control includes 2 relay outputs rated at 2 amps These outputs can be configured to activate on any control warning or shutdown fault as well as ready to load not in auto common alarm common warning and common shutdown Ready to load generator set running signal Operates when the generator set has reached 90 of rated speed and voltage and latches until generator set is switched to off or idle mode B signal output Communications connections include Modbus interface This RS 485 port allows the control to communicate with external devices like PLC on Modbus protocol PC tool interface This RS 485 communication port is shard with the Modbus interface mentioned above It allows the control to communicate with a personal computer running InPower Note An RS 232 to RS 485 converter is required for Communication between PC to control Networking This RS 485 communication port allows connection from the control to the other Cummins Power Generation products Power Generation Software InPower beyond 4 5 version is a PC based software service tool that is designed to directly communicate to the 1301 generator set control components to facilitate service and monitoring of these products Certifications The 1301 control meets or exceeds the requirements of the following codes and standards N
5. company product or service names may be trademarks or service marks of others Specifications are subject to change without notice S 1506d 6 10 Page 1 of 7 Control system The 1301 Control system includes all functions necessary to locally or remotely start and stop regulate voltage and protect the generator set Run off auto In the off mode the generator set is immediately shut down if running and cannot be started In the zun mode the generator set will execute its start sequence and operate at rated speed and voltage In the auto mode the generator set can be started with a start signal from a remote device such as an automatic transfer switch Operation of the switch to the off position also resets faults in the control Status indications The control includes a lamp driver for an external fault status indication When this feature is used it provides the operator with basic status information on the generator set Functions displayed include e The lamp flashes during preheat when used and while the generator set is starting e The lamp indicates ready to load by flashing until the generator set is at rated voltage and frequency then glowing continuously e Fault conditions are displayed by flashing a two digit fault code number Engine speed governing The control is available with an optional governor power stage This power stage amplifies control signals to directly drive an engine fuel control valve
6. FPA110 For Level 1 or 2 systems ISO 8528 4 1993 compliance Controls and Switchgear CE marking The control system is suitable for use on generator sets to be CE Marked EN 50081 1 2 Residential Light Industrial Emissions or Industrial Emissions EN 50082 1 2 Residential Light Industrial or Industrial Susceptibility ISO 7637 2 level 2 DC Supply Surge Voltage Test Mil Std 202C Method 101 and ASTM B117 Salt Fog Test IS09001 PowerCommand control systems and generator sets are designed and manufactured in ISO9001 certified facilities UL 508 Recognized or Listed and suitable for use on UL 2200 Listed generator sets Warranty All components and subsystems are covered by an express limited 90 day warranty Other optional and extended factory warranties and local distributor maintenance agreements are available 1301 Control 1301 genset control kit Includes a 1301 control module operator interface oil pressure sender coolant temperature sender and all required harnesses Part number 0541 1230 Current transformers Kits include 3 CTs for alternator current metering protection Part number 0541 1263 01 through 09 depending on ratio The 1301 is compatible with standard 5 amp secondary CTs The primary CT rating is sized to produce rated CT secondary current of 2 5 amps at rated genset load at 0 8 pf To select the proper CT ratio you must first calculate the lower and upper bound of the primary rat
7. PowerCommand 1301 digital generator set control kit and optional upgrade kits gt Specification sheet Our energy working for you Generation Description The 1301 control is a microprocessor based generator set monitoring metering and control system The control provides a simple operator interface to the generator set digital voltage regulation digital engine speed governing start stop control 12 V 24 V battery operation and generator set protective functions The integration of all functions into a single control system provides enhanced reliability and performance compared to conventional generator set control systems The 1301 generator set control is designed for mounting directly on the generator set and is suitable for use ona wide range of generator sets in non paralleling applications It is compatible with reconnectable alternators up to 600 VAC line to line and can be configured for any frequency voltage and power connection configuration from 120 600 VAC line to line It functions over a voltage range from 8 VDC to 30 VDC The control offers a wide range of standard and optional features so custom control configurations are not needed to meet application specifications Power for the control is derived from the generator set starting batteries Features 12 and 24 VDC battery operation Digital voltage regulation Full wave rectified single phase line to line sensing Digital engine speed go
8. __P 111 4 38 OQO00 OU Dimensions mm inches Power a Generation Electrical interconnections Gov Power STATUS LAMP O Jos 9N1d MOND 44OLNHS aN 1X3 ldo HALYVIS 1X4 Ld g 1100 AVY OSIA HALHVLS HOLVNHAL Tv 90 pet HAGNAS dna aoe A HAGNAS HO MS SSJHd 110 4 TIT i anya ow Se HMI211 OPERATOR PANEL JJJ P AAA 1301 Control TANVd YOLVYAdO OL VO1 OL AQVSY SLAdLNO ATEVYENSIANOO LYVLS SALOWSAY dO1S 4 ALOWSY c NI LINVA LANI LINVA _9 WEG BBEGREE __ MODBUS SERVICE TOOL PORT See your distributor for more information Cummins Power Generation Americas Europe CIS Middle East and Africa 1400 73 Avenue N E Minneapolis MN 55432 USA Manston Ramsgate Phone 763 574 5000 Kent CT 12 5BF United Kingdom Fax 763 574 5298 Phone 44 1843 255000 Fax 44 1843 255902 Manston Park Columbus Ave ALTERNATOR TO CUSTOMER LOADS Asia Pacific 10 Toh Guan Road 07 01 TT International Tradepark Singapore 608838 Phone 65 6417 2388 Fax 65 6417 2399 Warning Back feed to a utility system can cause electrocution and or property damage Do not connect to any building electrical except through an approved device or after building main breaker is open Our energy working for you www cumminspower com 2010 Cummins Power Generation Inc All rights reserved Cummins Power Generation and Cummins are reg
9. ation at 240 V producing rated output current of 602 amps phase This would yield a Min_CT_Ratio of 1204 5 and a Max_CT_Ratio of 3010 5 Any CT with a ratio between these would be sufficient for this application Example of CT sizing reconnectable A reconnectable generator capable of 208 240 416 480 V outputs with a 125 kVA 3 phase only rating We first need to find the current in each phase for each output voltage This is done using the following formula eq 3 1 3 Power Generation Using this equation above the current in each phase is computed and shown below Voltage V 208 240 416 480 Output current A The next step is to use equations 3 1 1 and 3 1 2 to find the lower and upper bound for the CT ratios for each voltage configuration For the 208 240 voltage configuration Max _CT _ Ratio 5 300 192 1500 96 Min _ CT _ Ratio 2 346 376 692 752 For the 416 480 voltage configuration Max _CT _ Ratio 5 150 096 754 8 Min _CT _ Ratio 2 173 188 346 376 For three tap CTs it would be advisable to choose a CT with a 1500 5 ratio For the 208 240 voltage configuration connect the CT leads to the 1st and 3rd CT connections leaving the center tap un connected For the 416 480 voltage configuration it would be advisable to use the same 1500 5 ratio CT but this time connect the CT leads to the 1st and 2nd center tap connections on the CT With this configuration one CT could be used for a
10. e that might be damaging Time delay start and stop cooldown Configurable for time delay of 0 300 seconds prior to starting after receiving a remote start signal and for time delay of 0 600 seconds prior to ramp to idle or shut down after signal to stop in normal operation modes Default for both time delay periods is O Sec Alternator control The 1301 control includes an integrated line to line sensing voltage regulation system that is compatible with shunt excitation systems The voltage regulation system is full wave rectified and has an SCR output for good motor starting capability Major system features include Digital output voltage regulation The 1301 control will regulate output voltage to within 1 0 for any loads between no load and full load Voltage drift will not exceed 1 5 for a 40 C 104 F change in temperature in an 8 hour period On engine starting or sudden load acceptance voltage is controlled to a maximum of 5 overshoot over nominal level The maximum regulator filed drive current is 4 0 amps RMS continuous and 6 0 amps peak for 10 seconds This feature can be disabled to allow the use of an external voltage regulator Torque matched V Hz overload control The voltage roll off set point and rate of decay i e the slope of the V Hz curve is adjustable in the control za ma SST CEH l i 7 p 5 a s Fi Protective functions On operation of a protective function the con
11. icating lamps The display panel includes LED indicating lamps for the following functions Not in auto Shutdown Warning Remote start Auto Run Operator adjustments The display panel includes provisions for many set up and adjustment functions via raise lower switches Functions that can be adjusted by the operator include Time delay start 0 300 seconds Time delay stop 0 600 seconds Alternator voltage plus or minus 5 Generator set hardware data Access to the control and software part number generator set rating in kVar and generator set model number is provided from the display panel or InPower Data logs Engine run time controller on time number of runs and number of start attempts are available from the display panel or through InPower Fault history Provides a record of the most recent fault conditions with control hours time stamp Up to 5 events are stored in the control non volatile memory Alternator data Voltage single or three phase line to line and line to neutral Current 8 phase KVA Frequency Engine data Starting battery voltage Engine speed Engine temperature Engine oil pressure Service adjustments The operator panel includes provisions for adjustment and calibration of generator set control functions Adjustments are protected by a password Functions include Engine speed governor adjustments 12 VDC 24 VDC battery operations
12. ing Once this is done you select a CT turns ratio within these bounds Our energy working for you www cumminspower com 2010 Cummins Power Generation Inc All rights reserved Cummins Power Generation and Cummins are registered trademarks of Cummins Inc InPower and Our energy working for you are trademarks of Cummins Power Generation Other company product or service names may be trademarks or service marks of others Specifications are subject to change without notice S 1506d 6 10 Page 5 of 7 Turns ratio primary secondary Part number Tap1 2 tapira 0541 1263 01 100 5 0541 1263 02 150 5 0541 1263 03 200 5 0541 1263 04 300 5 0541 1263 05 400 5 0541 1263 06 500 5 0541 1263 07 750 5 0541 1263 08 800 5 0541 1263 09 1000 5 The lower bound of the primary ratio is calculated by multiplying the maximum rated current by two per phase Min _CT _ Ratio 2 Max _ Rated _ Current 5 eq 3 1 1 The upper bound of the primary ratio is calculated by multiplying the maximum rated current by five per phase Max _ CT _ Ratio 5 Min _ Rated _Current 5 eq 3 1 2 Current is calculated by Current Power VA a3 Voltage or Current mw J3 Power _ Factor Voltage In non reconnectable genset applications the Max_Rated_Current and Min_Rated_Current will be the same In reconnectable genset applications they will be different Example of CT sizing non reconnectable A 250 kVA rated genset applic
13. istered trademarks of Cummins Inc InPower and Our energy working for you are trademarks of Cummins Power Generation Other company product or service names may be trademarks or service marks of others Specifications are subject to change without notice S 1506d 6 10 Page 7 of 7 Power Generation
14. ll voltage configurations Mechanical drawings 224 8 82 a 14 5 56 _ BASIC CONTROL BOARD OPERATOR PANEL Loo ee 149 5 88 lt 100 3 94 gt GOVERNOR POWER STAGE Our energy working for you www cumminspower com 2010 Cummins Power Generation Inc All rights reserved Cummins Power Generation and Cummins are registered trademarks of Cummins Inc InPower and Our energy working for you are trademarks of Cummins Power Generation Other company product or service names may be trademarks or service marks of others Specifications are subject to change without notice S 1506d 6 10 Page 6 of 7 Optional upgrades Electronic governing power stage Includes an actuator driver power stage compatible with the 1301 control system Part number 0541 1231 This kit is required for electronic governing Care should be taken to ensure compatibility with fuel actuator RS 232 to RS 485 converter kit Includes converter and harness Part number 0541 1199 Remote annunciator kit Includes remote annunciator see specification sheet S 1472 Part number 0300 5929 02 Sales simulator Allows operation of the control system on a table top for sales demonstrations Part number 0541 1234 Includes 1301 control specific for use with simulator display panel mounting stand and harness Part number 0300 6597 includes universal simulator 33 5 1 32 lt
15. nal emergency stop switch to cause the generator set to immediately shut down The generator set is prevented from running or cranking with the switch engaged Sleep mode The control is configured to include a sleep mode When the mode select switch is in the off position the control will revert to a low power consumption mode until any button on the display panel is pressed Engine starting The control system supports automatic engine starting including a relay driver for a starter and fuel shutoff pilot relay Primary and backup start disconnects are achieved by one of three methods magnetic pickup battery charging alternator feedback or main alternator output frequency The control also supports programmable glow plug control This feature can be disabled when not required Our energy working for you www cumminspower com 2010 Cummins Power Generation Inc All rights reserved Cummins Power Generation and Cummins are registered trademarks of Cummins Inc InPower and Our energy working for you are trademarks of Cummins Power Generation Other company product or service names may be trademarks or service marks of others Specifications are subject to change without notice S 1506d 6 10 Page 3 of 7 Cycle cranking Configurable for number of starting cycles 1 to 7 and duration of crank and rest periods Control includes starter protection algorithms to prevent the operator from specifying a starting sequenc
16. ning Indicates status of battery charging system failure by continuously monitoring battery voltage Weak battery warning he control system will test the battery each time the generator set is signaled to start and indicate a warning if the battery indicates impending failure Fail to start overcrank shutdown Fail to crank shutdown Control has signaled starter to crank engine but engine does not rotate Cranking lockout The control will not allow the starter to attempt to engage or to crank the engine when the engine is rotating Sensor failure indication Logic is provided on the base control to detect analog sensor or interconnecting wiring failures Alternator protection High low AC voltage shutdown High default to 110 for 10 seconds instantaneous 130 Low default to 85 for 10 seconds Over current warning shutdown Warning default to 110 for 60 seconds Shutdown default to 150 for 10 seconds Requires CT option Under over frequency Under default to 6 Hz for 10 seconds Over default 6 Hz for 10 seconds Loss of sensing voltage shutdown Field Overload Shutdown Environment The control is designed for proper operation without recalibration in ambient temperatures from 40 C to 70 C 40 F to 158 F and for storage from 55 C to 80 C 67 F to 176 F Control will operate with humidity up to 95 non condensing Our energy working for you www cumminspower com
17. trol will indicate warning or shutdown by lighting the appropriate LED The associated fault symbol text and fault code will also be displayed on the digital display The nature of the fault and time of occurrence are logged in the control The service manual and InPower service tool provide service keys and procedures based on the service codes provided System protective functions Configurable alarm and status inputs The 1301 control will accept up to two alarm or status inputs configurable contact closed to ground or open to indicate customer specified conditions The control is programmable for warning shutdown or status indication and for labeling the input Power Generation Emergency stop Annunciated whenever the emergency stop signal is received from external switch Engine protection Over speed shutdown Default setting is 115 of nominal Low lube oil pressure warning shutdown Level is preset configurable with InPower to match the capabilities of the engine used Control includes time delays to prevent nuisance shutdown signals High engine temperature warning shutdown Level is preset configurable with InPower to match the capabilities of the engine used Control includes time delays to prevent nuisance shutdown signals Low coolant temperature warning Indicates that engine temperature may not be high enough for a 10 second start or proper load acceptance Low and high battery voltage war
18. verning optional Provides isochronous frequency regulation Generator set monitoring Monitors status of all critical engine and alternator functions Configurable for single or three phase AC metering Engine starting Includes relay drivers for start fuel shut off FSO and glow plug spark ignition power Start disconnect is achieved by monitoring the battery charging alternator Generator set protection Engine and alternator Operator display panel Provides easy to use symbolic English text operator display of critical generator set parameters and operating history Advanced serviceability Utilizing InPower a PC based software service tool Environmental protection The control system is designed for reliable operation in harsh environments The core control board is an encapsulated module that is fully protected from the elements Configurable inputs and outputs Two discrete inputs and two dry contact relay outputs Certifications Suitable for use on generator sets that are designed manufactured tested and certified to relevant UL NFPA ISO IEC Mil Std and CE standards Warranty and service Backed by a comprehensive warranty and worldwide distributor service network 2010 Cummins Power Generation Inc All rights reserved Cummins Power Generation and Cummins are registered trademarks of Cummins Inc InPower and Our energy working for you are trademarks of Cummins Power Generation Other