Home

Duct Type

image

Contents

1. Unit mm Model re ee Lee KUE 140 HTN6 938 633 5 404 448 370 392 1369 KUE 176 HTN6 Outdoor Units 41 Service Space 2 Service Space Wall or obstacle Air ma More than 30cm More than 30cm 5 Y i Air inlet gt J Maintain channel _More than soom s More than 200cm 42 More than 60cm Outdoor Units Piping Diagrams 3 Piping Diagrams KUE 140 HTN6 KUE 176 HTN6 INDOOR OUTDOOR CHECK VALVE Heating Model only wn 2 WAY VALVE T3 Condenser temp sensor CAPILIARY TUBE LIQUID SIDE q HEAT EXCHANGE EVAPORATOR n T1 Room temp T4 Ambient EXCHANGE Sensor temp sensor CONDENSER T2 Evaporator temp sensor 4 _ A GAS SIDE lt ae K gt 4 WAY VALVE lt
2. Cooling 45 43 40 35 STD 30 Heating 25 25 24 20 20 18 I e 15 A i5 A O o 10 1 m With Low 5 ux STD Ambient 5 Cooling ux 9 System YA 0 8 0 o G 6 5 5 7 7 10 10 10 1517 20 25 3032 35 0 5 10 15 20 25 30 Indoor temperature C WB Indoor temperature C WB Outdoor Units 7 Sound Levels Outdoor Units Outdoor Unit DA Di Microphone P lt _ H lt gt 1 0m Note H 0 5 x height of outdoor unit Sound Levels 47 Installation 48 Part 4 Installation 1 Installation ciao iia 49 EOCATION SCICCHON a 50 3 Indoor unit installation 51 3 Outdoor unit installation Side Discharge Unit 61 5 Refrigerant pipe installation 62 6 Drainage pipe installation 63 7 Vacuum Drying and Leakage Checking 67 8 Additional refrigerant charge 68 9 Engineering OF IASUIAHONM iria 69 10 Engineering of e
3. 73 2 IPOUDIOSHOQUD8 82 S Tg go U uzun a su 97 72 Electrical Control 1 Electrical Control Function 1 1 Definition T1 T2 T4 T5 Indoor room temperature Coil temperature of evaporator Coil temperature of condenser Outdoor ambient temperature Compressor discharge temperature 1 2 Main Protection 1 2 1 Time delay at restart for compressor 1 2 2 Sensor protection at open circuit and breaking disconnection 1 2 3 Phase check function Electrical Control Function If the phase sequence is detected wrong or lack of 1 or 2 phase the unit won t start and there is error code displayed on outdoor PCB 1 2 4 Over current protection When compressor is running if the current is over twice of the rated for 3 seconds the compressor will stop and an error code will be displayed on the outdoor PCB If the current becomes normal the indoor sends signal to the outdoor the outdoor will display normally 1 2 5 Fan Speed is out of control When Indoor fan speed keeps too low less than 300RPM for 50s the unit will stop and the LED will display the failure Electrical Control 73 Electrical Control Function 1 3 Operation Modes and Functions 1 3 1 Fan mode 1 Outdoor fan and compressor stop 2 Temperature setting function is disabled and no setting temperature is di
4. Ventilated Panel 1 4 Reserved remote on off and central control ports gt Reserved remote on off ports and central control ports can connect the cable of an on off controller or a central controller to realize remote on off control function or group control function Remote on off ports Central control ports 1 5 Built in drain pump Optional gt Built in drain pump can lift the water to 750mm upmost It s convenient to install drainage piping under most space condition f r r E 4 i g ALL 750mm upmost Duct Type Features 1 6 Built in display board gt standard indoor unit can be controlled by wired controller gt There 15 a display board with a receiver in the E box Move out the display and fix it in other place even in the distance of 10m The unit will realized remoter control gt The wired controller and the display board can display the error code or production code when the chips detect some failure Wired Controller Standard Remote Controller Optional Duct Type 9 Dimensions 2 Dimensions Outline dimension and air outlet opening size Unit mm Electric control cabinet Electric control cabinet Air outlet O Air return Size of outline dimension mounted plug J K L 1094 288 45 1240 10 Duct Type 3 Service Space Ensure enough space required for installation and maintenance 200mm or more 300mm or more
5. A b 4 gt 600mmX600mm checking orifice ESEDA AE Service Space There is enough space for installation and maintenance The ceiling is horizontal and its structure can endure the weight of the indoor unit The outlet and the inlet are not impeded and the influence of external air is the least The air flow can reach throughout the room The connecting pipe and drainpipe could be extracted out easily There is no direct radiation from heater Duct Type Wiring Diagrams 4 Wiring Diagrams KPD 140 6 KPD 176 HN6 12 WIRING DIAGRAM INDOOR UNIT 202070790548 FOR DIFFERENT OUTDOOR UNIT WITH DOUBLE FAN SINGLE FAN FOR SETTING AUTO RESTART SW5 SW3 1 DC MOTOR DRIVER MODLE FAN FAN L SET ACCORDING TO THE QUANTITIES OF OUTDOOR FAN 51 80 81 120 121 150 gt 150 MIDDLE STATIC 0 25 26 37 38 50 51 100 ee AA FOR SETTING POWER ENC1 Trower 53 7 90 195 140 130 1601150 SETTING ACCORDING TO RELATED MODEL PE FOR SETTING NETADDRESS 51 52 9 CODE o INDOOR UNIT MAINBOARD E Y X Q m a DEES FT E Comm Bus RED s reo E Cui Reactor TO WIRE CONTROLLER OUTER PIPE TEMP VAN 69 T2 BLACK MIDDLE PIPE TEMP r1 ROOM TEMP om v t Tooutdoor POWER SULLY Duct Type Static Pressure 5 S
6. When the evaporator coil temp T2 keeps lower than 5 for 30 minutes compressor and outdoor fan will shut off When T2 is higher than TE6 the compressor and outdoor fan will restart up Electrical Control 75 Electrical Control Function Condition 2 T2 TE6 TE5 2 Off When the evaporator coil temp T2 keeps lower than TE5 2 for 20 minutes the compressor and outdoor fan will shut off When T2 is higher than TE6 the compressor and outdoor fan will restart up Condition 3 T2 TE6 TE5 4 Off When the evaporator coil temp T2 keeps lower than TE5 4 for 8 minutes the compressor and outdoor fan will shut off When T2 is higher than TE6 the compressor and outdoor fan will restart up 1 3 2 5 Condenser high temperature T3 protection For Duct amp super slim cassette type Off 6 12 13 When T32TE12 for Time1 the compressor will shut off When T3 lt TE13 the compressor will restart 76 Electrical Control Electrical Control Function For Ceiling amp Floor Off i9 TE10 TE11 J On When T32TE10 the compressor will shut off When T3 lt TE11 the compressor will restart 1 3 3 Heating Mode 1 3 3 1 Compressor running rules For Duct amp super slim cassette type Once the compressor starts up it keeps running 7 minutes For Ceiling amp Floor Once the compressor starts up it keeps running HEATFTIM
7. Replace indoor or outdoor No Y Replace the sensor 86 Electrical Control Troubleshooting c Outdoor unit malfunction E6 Outdoor unit malfunction Whether the outdoor main board has error display No Y Whether the outdoor Yes p Refer to corresponding solving steps No gt unit is power on Yes Check whether the communication wire outdoor unit is between the indoor and connected correctly v Replace outdoor main board Check if the errors Check whether the power is on Connect the wiring well or replace the communication wire happen again Yes Y Replace the indoor PCB Electrical Control No Y Trouble is solved 87 Troubleshooting d Indoor EEPROM malfunction E7 Shut off the power supply and turn it on 5 seconds later Is it still displaying the error code Yes If the EEPROM chip is welded on PCB replace the PCB directly Otherwise No Insert the EEPROM well check whether the EEPROM chip plugged in PCB well Yes y Replace the indoor PCB e Full water malfunction E8 If the water level switch No is inserted well Yes Y If the water level switch is broken No y If the water pum
8. Service Manual 2014 Frigicoll Contents Contents Content Part 1 General Information 1 1 Part 2 maoor UNIS u uuu u uu u 5 Part 3 Outdoor UNS cuina 40 Part 4 INSTA ATION i uu s 48 Part 5 Electrical Control System J 72 X The specifications designs and information in this book are subject to change without notice for product improvement Contents General Information Part 1 General Information 1 Model Lists 2 2 External me eec m 3 o SS 3 222 Outdo r UNAS aid 3 4 FC AUS io 4 General Information Model Lists 1 Model Lists 1 1 Indoor Units R410A Capacity multiplied by 1000Btu h Duct Cooling and heating je Super slim 4 way cassette Cooling and heating pe e Ceiling amp Floor Cooling and heating Pe je 1 2 Outdoor Units Universal Outdoor unit Model Compressor type Compressor Brand Matched indoor units Heat Pump KPD 140 HN6 KUE 140 HTN6 SCROLL SANYO KCIS 140 HN6 KPC 140 HN6 KPD 140 HN6 KUE 176 HTN6 SCROLL SANYO KCIS 176 HN6 KPC 176 HN6 2 General Information External Appearance 2 External Appearance 2 1 Indoor Units o o 5 O gt T st E WI o 2 42 Ceiling amp floor type 2 2 Outdoor U
9. 6 2 3 Individual design of drainage pipe system gt drainage pipe of air conditioner shall be installed separately with other sewage pipe rainwater pipe and drainage pipe in building gt drainage pipe of the indoor unit with water pump should be apart from the one without water pump 6 2 4 Supporter gap of drainage pipe gt In general the supporter gap of the drainage pipe horizontal pipe and vertical pipe is respectively 1m 1 5m and 1 5m 2 0m gt Each vertical pipe shall be equipped with not less than two hangers gt Overlarge hanger for horizontal pipe shall create bending thus leading to air block Too long distance l Gas bag 64 Installation Insulation Work 6 2 5 The horizontal pipe layout should avoid converse flow or bad flow Drainage pipe Drainage pipe Drainage pipe Drain tee SSS AAA Water flow Water flow gt Water flow Water flow Water flow Drain tee Water flow Water flow Water flow Gas Water flow Branch pipe x gt correct installation will not cause converse water flow and the slope of the branch pipes can be adjusted freely gt The false installation will cause converse water flow and the slope of the branch pipe can not be adjusted 6 2 6 Water storage pipe setting gt Ifthe indoor unit has high extra static pressure and without water pump t
10. Field Wiring 9 Field Wiring 140 6 KPC 176 HN6 Air Condition Link Circuit OUTDOOR UNIT with 3 Phase outdoor unit Ceiling amp Floor Type INDOOR UNIT NM peti M ONJ uss Use 3 core cable 3x1 0mm for the others 3 core shielded cable 3X0 2mm 24AWG Power supply 3 Phase 380 420V 30K 60K 5 core cable 5x2 5mm 3 Phase 220V 30K 60K 5 core cable 5x4 0mm For 30K 60K Btu h auxiliary electric heater PTC OUTDOOR UNIT 202070890525 INDOOR UNIT ANT Power supply WX 1 Phase 208 240V IN WX re mosse wh auxiliary electric heater PTC Use 3 core cable 3x1 0mm for the others 3 core shielded cable 3 0 2 24AWG Power supply 1 Phase 208 240V 18K 24K 3 core cable 3 2 5 2 30K 36K 3 core cable 3x4 0mm 42 48K 3 core cable 3x6 0mm 60K 3 core cable 3x10 0mm2 For 18K 60K Btu h with 1 Phase outdoor unit 39 Outdoor Units 40 Part 3 Outdoor Units MICH SIONS RE 41 SOI NICO An 42 S PIDIN DIAG ANIS cuna kennende nitens 43 Tt 44 TET 45 Operation LIMITS accio 46 Sound Levels aaan aanne nn U UU UU U U U RES 47 Outdoor Units Dimensions 1 Dimensions
11. The Specification of Power 38 s 172 ILL 39 Ceiling amp Floor Type Features 1 Features 1 1 New design more modern and elegant appearance 1 2 Convenient installation The ceiling type can be easily installed into a corner of the ceiling even if the ceiling is very narrow lt is especially useful when installation of an air conditioner in the center of the ceiling is impossible due to a structure such as one lighting 1 3 Two direction auto swing vertical amp horizontal and wide angle air flow Air flow directional control minimizes the air resistance and produces wilder air flow to vertical direction The range of horizontal air discharge is widened which secures wider air flow distribution to provide more comfortable air circulation no matter where the unit is set up 1 3 Three level fan speed more humanism design meets different air supply requirement 1 5 New foam drain pan with plastic spraying inner surface Foam case Plastic spraying surface 1 6 Easy operation 1 7 Remote control and optional wired control method Ceiling amp Floor Type 33 Dimensions 2 Dimensions Capacity Btu h 34 D Connecting point of refrigerant pipe D gas side Drain point E Connecting point of refrigerant pipe E Liquid side A D KPC 140 6 1285 675 235 1200 220 KPC 176 6 1650 675 235 1565 220
12. The special vacuum drying method shall be adopted when 1 Finding moisture during flushing refrigerant pipe 2 Conducting construction on rainy day because rain water might penetrated into pipeline 3 Construction period is long and rain water might penetrated into pipeline 3 Rain water might penetrate into pipeline during construction Procedures of special vacuum drying are as follows 1 Vacuum drying for 1 hour 2 Vacuum damage filling nitrogen to reach 0 5Kgf cm2 Because nitrogen is dry gas vacuum damage could achieve the effect of vacuum drying but this method could not achieve drying thoroughly when there is too much moisture Therefore special attention shall be drawn to prevent the entering of water and the formation of condensate water 3 Vacuum drying again for half an hour If the pressure reached 55mmHg start to pressure leakage test If it cannot reached the value repeat vacuum damage and vacuum drying again for 1 hour 4 Leakage test After the vacuum degree reaches 755mmHg stop vacuum drying and keep the pressure for 1 hour If the indicator of vacuum gauge does not go up it is qualified If going up it indicates that there is moisture or leak source Additional refrigerant charge gt After the vacuum drying process is carried out the additional refrigerant charge process need to be performed gt outdoor unit is factory charged with refrigerant The additional refrigerant charge volume is deci
13. 027078 12 187177 52 3419183 92 080132 132 02648 __ 13 17805 53 307075 9 077709 133 02557 14 169341 54 29586 94 07573 134 025125 15 16115 55 284421 95 07319 15 0 24512 16 153418 56 27323 96 0704 136 023910 __ 17 136181 5 263682 97 0684 137 023388 18 139180 58 25393 98 066818 18 02276 19 132631 59 244677 99 064862 139 022281 1 1 NO NO oO O DO PB N O I II N NTN O gt O gt O gt O gt O gt NI I O N Po G O O CO O O BR O NTN ITN IN BR O O O O O KOE OI KOA O O O I O gt 5 GO COO OO O OI I T IC CO O O WIN O O cO Y 5 CO N N 5 N co 96 Electrical Control 3 Controller Controller 3 1 01 Wireless Remote Controller Optional Mode setting CD Adjust Y ON OFF L Swing Wind Harz swing Reset gt ct cb Lock Cnoolheat Electrical Control 3 5 D d KaSS Fan speed setting 2 D Adjust 6 A
14. Defrosting Alarm Display digital lamp lamp lamp lamp tube Communication malfunction between indoor sensor sensor RA 22171727 w tr mareos x X Xx x A u on X off flash at 5Hz 28 For Super slim 4 way Cassette NO Menci n Running Timer Defrosting Alarm Display digital lamp lamp lamp lamp tube 1 Communication malfunction between indoor X X Ej and outdoor units Open or short circuit of T1 temperature sensor Open or short circuit of T2 temperature sensor m N m m ep Communication malfunction between main PCB and up down panel PCB Up down panel malfunction Up down panel is not closed on X off flash at 5Hz Open or short circuit of T3 temperature sensor O m en 1 1 x X x X X X 1 12 EE N Electrical Control 83 Troubleshooting For Ceiling amp Floor Malfunction Running Timer Defrosting lamp lamp lamp Communication malfunction between indoor and outdoor units LEDs for the indication of outdoor trouble ES ee Red O light X off flash at 1Hz Note 1 T3 Outdoor condenser temperature sensor 2 4 Outdoor ambient temperature sensor BI Electrical Control Troubleshooting 2 3 Solving steps for typical malfunction 1 For indoor unit a Communication malfunction
15. OFF has been set 108 Electrical Control
16. Specification of Power KPD 176 HN6 Frequency and Voltage 220 240V 50Hz INDOOR UNIT POWER 5 POWER WIRING mm 3 Circuit Breaker Fuse A 20 16 Frequency and Voltage 380 415V 50Hz OUTDOOR UNIT POWER T POWER WIRING mm Circuit Breaker Fuse A 25 20 Indoor Outdoor Connecting Wiring Weak Electric Signal mm Indoor Outdoor Connecting Wiring Strong Electric Signal mm Duct Type 17 Field Wiring 10 Field Wiring KPD 140 6 176 6 Air Condition Link Circuit INDOOR UNIT INA mW 4 hi Power supply VAM 1 Phase 208 240V y Use 3 core cable 3x2 5mm 2 M for the models which with auxiliary electric heater PTC Use 3 core cable 3x1 0mm for the others 3 core shielded cable 3x 0 2mm 24AWG Power supply 3 Phase 380 420V 30K 60K 5 core cable 5x2 5mm OUTDOOR UNIT 3 Phase 220V 30K 60K 5 core cable 5x4 0mm For 30K 60K Btu h with 3 Phase outdoor unit 18 OUTDOOR UNIT NY NM WA Use 3 core cable 3x2 5mm 2 LJ 202070890525 INDOOR UNIT n Power supply 1 Phase 208 240V for the models which with auxiliary electric heater PTC Use 3 core cable 3x1 0mm for the others 3 core shielded cable 3 0 2 24AWG Power supply 1 Phase 208 240V 18K 24K 3 core cable 3x2 5mm 30K 36K 3 core cable 3x4 0mm 42 48K 3 core cable 3x6 0mm 60K 3 core cable 3x10 0mm 2 For 18K 60K Btu h with 1 Phase outdoor
17. X A LIE A Ceiling Panel Outlet Inlet Outlet 880mm Ceiling hole Ground gt 2500mm Model A H KCIS 176 HN6 Art Flux Super slim Cassette Type 24 3 Service Space gt 1000mm A EM vs zi 5 gt 1000mm S A Art Flux Super slim Cassette Type Service Space 25 Wiring Diagrams 4 Wiring Diagrams KCIS 140 6 KCIS 176 HN6 FUNCTION OF SWITCH 3 TO WIRE WIRING DIAGRAM POWER ells ar INDOOR UNIT ee TT 202042890254 iS 5812 12 0 15 32 47 ua A ate CN15 _ ED ON uh SW1 l l 141 160 ALARM ON 89 QUT D D 1654 heces SW6 1 RED BROWN Water T1 Level BUILT IN ACCORDING MODE PARAMETERS TO EEPROM JEDE donada 111 41 0 WIRE T CONTROLLER TO CCM TO OUTDOOR COMM BUS COMM BUS NOTE PLEASE USE SHIELDED WIRE Factory Setting N INDOOR UNIT POWER 220 240vAc 1220 24000 MAK 26 Art Flux Super slim Cassette Type jError No hay texto con el estilo especificado e
18. and the indicator light on display board will shine Art Flux Super slim Cassette Type 21 Features 1 4 External air duct design gt Reserve external air duct more flexible for the air supply _ 15 Built in draining pump gt Due to the improvement of structure more convenient to repair or replace the draining pump gt Pe E gt Built in draining pump to make sure condensed water drain out reliably Ceiling 22 Art Flux Super slim Cassette Type Features 1 6 Terminals for alarm lamp and long distance on off controller connection are standard gt Reserve terminals for the connection of alarm lamp and long distance on off controller more human control a ye L GA 2 ALARM CN33 ON OFF CN23 Long distance on off controller 1 7 Optional touch screen wired controller gt Touch screen wired controller is optional with error code indication function Better man machine conversation interface gt Undated structure design 4 way wire layout design no raised part at backside more convenient to place the wires and install the device Art Flux Super slim Cassette Type 23 Dimensions 2 Dimensions Tubing side Drain side 680 Hook location 950 Panel Unit mm Connecting point of refrigerant pipe Connecting point of drain pipe Liquid side Connecting point of refrigerant pipe Hi Ne L f N
19. electric cabinet by the accessory slotted head screws Confirm the bottom cover is parallel to wall surface And then reinstall the bottom cover to centralized controller See fig 3 5 2 Please connect the other side of signal received panel with the wall pre bedded 5 core cable reliability 3 Connect the wire control leads from wire controller with the wall pre bedded 5 core cable reliability See Fig 3 3 4 Take off the screws in the bottom cover of centralized controller by slotted head screw driver See Fig 3 4 NOTE Over tighten the screw would cause rear cover deformed and LCD damage When installation please maintain the screws and wire controller at the same height level without deformed When installation please reserve a certain length of wire controller connective cable for future maintenance to take off the wire controller Electrical Control 103 Controller 3 2 4 Wiring diagram for wiring wire controller with air conditioner 1 Wiring diagram of wire controller connects with four way cassettes indoor unit Indoor unit electric cabinet Insert of the electric control m Electric control panel of indoor unit Indoor unit panel 1 O cor ed connective wires Signal received s i sgnal received Panel lon The rear side wire controller Fig 4 1 y Indoor unit electric cabinet Indoor unit panel Insert of the electric co
20. gt 3 WAY VALVE Accumulator High pressure switch Compressor Low pressure switch 4 COOLING 4 HEATING Outdoor Units 43 Wiring Diagrams 4 Wiring Diagrams KUE 140 HTNG KUE 176 6 202075790595 WIRING DIAGRAM OUTDOOR UNIT m CODE PART NAME 3 PIPE TEMPERATURE SENSOR OUTDOOR TEMPERATURE SENSOR P3 XP8 CONNECTORS 53 158 CONNECTORS CURRENT INDUCTOR DISCHARGE TEMPERATURE SENSOR PIPELINE HIGH PRESSURE SWITCH OR SOUR LN D PIPELINE LOW PRESSURE SWITCH OR SHORTING STUB 3 TEMPERATURE PROTECT SWITCH OR SHORTING STUB VALVE REVERSING VALVE NN gt RRR HEAT ELECTRIC HEATING STRING RRR RN TRANS TRANSFORMER TO INDOOR COMM BUS POWER SUPPLY NANI NOTE PLEASE USE 3 CORE SHIELDED WIRE gt lt gt lt ER AN 44 Outdoor Units Electric Characteristics 5 Electric Characteristics Model Voltage Min Max KUE 140 HTN6 380 415V 342V 435V KUE 176 6 380 415V 342V 435V Outdoor Units AB Operation Limits 6 Operation Limits 46 Cooling operation Heating operation Room temperature 17 C 32 O C 30 Outdoor temperature Outdoor temperature C DB 18 C 43 7 C 43 C For the ZC 24 C models with low temperature cooling system
21. on or timer off has been set it cancel this setting then send instruction to stop the machine 3 Adjust Button Press this key to increase the indoor temperature settings 1 degree to be increased for every once press 4 Adjust Button Press this key to decrease the indoor temperature settings 1 degree to be decreased for every once press Electrical Control 105 Controller 5 Time Button Normally LCD displays the current time of the setting clock however LCD would display 12 00 when the first time power to the wire controller or reset the wire controller Press this key lasting for 4 seconds the clock will flashing at the frequency of 0 5 Sec by using and to adjust the time 1 minute to be increased decreased for every once press the A V Long pressing the A it will increase decrease 4 times sec 10 mins time Release the key when finish the clock setting the time will stop flashing automatically 6 FAN SPEED Button Press this button consecutively the fan speed will circle as follow This button is unavailable when in the mode of AUTO or DRY SPEED TIMER Button Press this button the Timing will turn on Set Timing ON time by Aand Y The clock will Increase and decrease once every 10 minutes long pressing the keys it will increase decrease once 10 minutes 0 2 seconds SWING Button In the unit ON status press this key at the first time the Swing type air supply mode to be activated Pres
22. unit via ON OFF 4 On DRY mode ECO and FAN SPEED are unavailable Timer operation TIMER ON and TIMER OFF are used to turn on and turn off the unit at the set time respectively TIME ON operation 1 Press TIMER ON icon SET HOUR and ON are lightened 2 Press TIMER ON again and adjust the time 3 Keep pressing this button the time will increase by 0 5 hour When the set time exceeds 10 hours pressing the button will increase the time by 1 hour 4 0 5s after setting remote controller will send TIME ON command to the unit TIME OFF operation 1 Press TIME OFF icon SET HOUR and OFF are lightened 2 Press TIME OFF again and adjust the time 3 Keep pressing this button the time will increase by 0 5 hour When the set time exceeds 10 hours pressing the button will increase the time by 1 hour 4 0 5s after setting remote controller will send TIME OFF command to the unit Set TIME ON and TIME OFF simultaneously 1 Set TIME ON according to procedures 1 and 2 specified in TIME ON operation 2 Set TIME OFF as the procedures 1 and 2 specified in TIME OFF operation 3 If both the set time of TIME ON and TIME OFF not exceed 10 hours time OFF operation will activated 0 5 hour later than time ON operation If both the set time of TIME ON and TIME OFF exceed 10 hours time OFF operation will be activated 1 hour later than time ON operation 4 0 5s after setting remote controller will send TIME ON command to the unit Modification
23. will be lightened or off when pressing ECO button NOTE All the above icons will be displayed only when the remote controller is electrified for the first time or reset HEAT X SET Electrical Control 99 Controller 3 1 4 OPERATION INSTRUCTIONS Install and replace batteries Install 2 pieces of 7 alkaline batteries Slide the cover to install batteries and make sure to place them in right pole AUTO operation Switch on the power and running indicator light on indoor unit flashes 1 Press MODE to select AUTO 2 Adjust temp and Generally the range is 17 C 30 C 3 Press ON OFF and running indicator light on indoor unit is lightened Air conditioner will work on AUTO mode and fan speed is AUTO which is nonadjustable 4 ECO 15 effective on AUTO operation COOL HEAT FAN operation 1 Press MODE to select COOL HEAT or FAN 2 Adjust temp and Generally the range is 17 C 30 C 3 Press FAN SPEED to select AUTO LOW MED or HIGH 4 Press ON OFF and running indicator light on indoor unit is lightened Air conditioner will work on the set mode Stop operation via ON OFF NOTE On FAN mode temp 15 nonadjustable and ECO is ineffective Procedure 2 is omitted DRY operation 1 Press MODE to select DRY 2 Adjust temp Aand Generally the range is 17 30 C 3 Press ON OFF and running indicator light on indoor unit is lightened Air conditioner will work on DRY mode Turn off the
24. with drain pump Remove the side board and the grille Hanging arm Hanging screw bolt a Grille Installation 59 Indoor unit installation Locate the hanging arm on the hanging screw bolt Prepare the mounting bolts on the unit Screw nut Washer 20 25mm Hanging screw bolt Put the side panels and grilles back D Connecting point of refrigerant pipe D gas side E Connecting point of refrigerant pipe E Liquid side UMMM J Drain point Downward declicity lower between 1 2 100 Wall mounted installation Hang the indoor unit by insert the tapping screws into the hanging arms on the main unit The bottom of body can touch with floor or suspended but the body must install vertically NIHHHHHHHHHHTHHHHHHHHHHHHX 60 Installation Insulation Work 4 Outdoor unit installation Side Discharge Unit 4 1 Service space for outdoor unit Wall or obstacle 55 Air inlet y 5 gt 30cm E Maintain channel N 260cm 74 P Air inlet 5 M y Air outlet Al Fig 6 5 Fix with bolt 4 2 Bolt pitch Model a D Installation Refrigerant pipe installation 4 3 Install the Unit Since the gravity center of the unit is not at its physical center so please be careful when lifting it with a sl
25. 3 5 1 The indoor fan will keep running at low speed 1 3 5 2 All protections are active and the same as that in cooling mode 1 3 5 3 The louver operates the same as in cooling mode 1 3 6 Timer function 1 3 6 1 Timing range is 24 hours 1 3 6 2 Timer on The machine will turn on automatically when reaching the setting time 1 3 6 3 Timer off The machine will turn off automatically when reaching the setting time 1 3 6 4 Timer on off The machine will turn on automatically when reaching the setting on time and then turn off automatically when reaching the setting off time 1 3 6 5 Timer off on The machine will turn off automatically when reaching the setting off time and then turn on automatically when reaching the setting on time 1 3 6 6 The timer function will not change the AC current operation mode Suppose AC is off now it will not start up firstly after setting the timer off function And when reaching the setting time the timer LED will be off and the AC running mode has not been changed 1 3 6 7 The setting time is relative time 1 3 7 Economy function 1 3 7 1 It is valid in cooling heating and auto mode 80 Electrical Control Electrical Control Function 1 3 7 2 Turning off changing mode or setting fan speed will cancel economy function 1 3 7 3 Operation process in sleep mode is as follow After pressing ECONOMIC or SLEEP button on the controller the machine will go into economy mode
26. 5 0 54448 14 793110 26 955074 66 189697 106 052902 ta 735360 27 912445 67 14903 107 05146 __ 12 70468 28 871983 68 176647 108 049989 660898 29 833566 69 17047 048600 10 622756 30 7908 70 16469 047256 _ 9 587079 31 76241 71 159068 111 045957 8 563604 32 729464 72 153668 112 044699 __ 52248 33 698142 73 14848 043482 4931601 34 66835 74 143498 114 042304 __ 5 46575 35 640021 75 13870 115 041164 430000 36 613059 76 1 34105 040060 41578 37 587359 77 1208 117 0389931 398239 38 562961 78 125423 037956 371988 39 539689 79 121330 119 0394 352024 40 517519 80 117388 120 0 35982 33 3269 41 396392 81 1 13600 121 035042 __2 81565 42 376253 82 109958 122 0343 3 29908 43 357050 83 1 0644 123 033246 4 2849 44 338736 84 103069 144 0 32300 _ 5 26878 45 321263 85 0998155 125 031559 6 25494 46 30459 86 096681 126 0 30754 28492 47 388673 87 093660 127 029974 22562 48 373476 88 090753 128 029216 21894 49 35862 89 087950 129 0 28482 10 207184 50 345097 90 085248 130 0270 __ 1 196891 51 331847 91 082643 131
27. Ceiling amp Floor Type Service Space 3 Service Space 21000mm gt 35mm Ceiling amp Floor Type 35 Wiring Diagrams 4 Wiring Diagrams KPC 140 HN6 KPC 176 HN6 4 Outer Driver DC Motor INDOOR UNIT MAINBOARD DC MOTOR DRIVER MODLE DC MOTOR DRIVER MODLE 1 1 CN40 CN23 CN33 BBI Outer Driver CN29 CN28 DC Motor ON OFF ALARMI YATIONLNOD 38HIM OL Control Output 36 69 C P 106 To CCM To outdoor Comm Bus Comm Bus CN10 CN10A CN26 CN3 DISPLAY BOARD TO WIRE CONTROLLER For Setting POWER N F075 ENC1 55 o bsg 12 Code 4 POWER 53 Seine According to related model For Setting NETaddress amp gt Q S1 52 sD 81 Code 0 F NETaddress 0 15 Factory Setting NT For Setting Speed Parameter of DC Motor For Setting Auto Restart ON ON sw2 1 1 ON SW3 i BLACK MIDDLE PIPE TEMP WN KT LOS n WHITE ROOM TEMP C To Earth E WIRING DIAGRAM 202044690350 Mode Built in parameters According to EEPROM Mode ON F
28. When cooling the setting temperature rises 1 C be lower than 30 every hour 2 hours later the setting temperature stops rising For heat pump models when they are in heating the setting temperature reduces 1 higher than 17 every hour 2 hours later the setting temperature stops reducing 1 3 7 4 In this mode the fan speed is forced into AUTO mode 1 3 8 Auto Restart function The indoor unit is equipped with auto restart function which is carried out through an auto restart module In case of a sudden power failure the module memorizes the setting conditions before the power failure The unit will resume the previous operation setting not including Swing function automatically after 3 minutes when power returns 1 3 9 Drain pump control For duct amp cassete 1 3 9 1 Water level check The water lever will be checked every 5 seconds if the feedback signal is abnormal it will be considered as drain water full by the control system 1 3 9 2 Drain pump control lf there is no water full error the drain pump will be on when the unit is in cooling mode including auto cooling and forced cooling and dry mode It will be off when the unit is in heating mode fan only mode or off state if the pump is on before the unit is off it will delay 3 minutes to be off If there is a water full error the drain pump will be on when the error occurs Afterwards lf the error disappears in 3 minutes the drain pump will work as normal
29. actory Setting Factory Setting For Setting Fan Quantity optional For Setting temperature compensation SW4 ON r 1 ON ON 1 Mode Single Fan Double Fan Mode Factory Setting s Factory Setting Ceiling amp Floor Type Electric Characteristics 5 Electric Characteristics RUN Indoor Units Power Supply ode KPC 140 HN6 220 240V 198V 254V KPC 176 HN6 220 240V 198V 254V Remark MFA Max Fuse Amps A 6 Sound Levels SS Microphone m Im 1 5m Air outlet side 1m I Y Microphone 7 Ceiling Floor Noise level dB A Ceiling amp Floor Type 37 Accessories 7 Accessories m 1 Remote controller Remote controller amp Its 2 Remote controller holder holder 3 Mounting screw ST2 9x10 C H 8 The Specification of Power sd 1 EE _ INDOOR UNIT POWER Frequency and Voltage 380 415V 50Hz OUTDOOR UNIT POWER 7 POWER WIRING mm Circuit Breaker Fuse A 25 20 Indoor Outdoor Connecting Wiring Weak Electric Signal Indoor Outdoor Connecting Wiring Strong Electric Signal 3x0 2 38 Ceiling amp Floor Type
30. at the joint pipe shall be banded to the gap pipe and liquid pipe tightly The linking part should be use glue to paste together Be sure not bind the insulation material over tight it may extrude out the air in the material to cause bad insulation and cause easy aging of the material NN Y 9 2 Insulation of drainage pipe 9 2 1 Operational procedure of refrigerant pipe insulation Select the suitable pipe insulation except joint section piping layout and connection drainage test insulate the joint parts Installation 69 Engineering of electrical wiring 9 2 2 Purpose of drainage pipe insulation The temperature of condensate drainage water is very low If insulation is not enough it shall form dew and cause leakage to damage the house decoration 9 2 3 Insulation material selection for drainage pipe gt insulation material should be flame retardant material the flame retardancy of the material should be selected according to the local law gt Thickness of insulation layer is usually above 10mm gt Use specific glue to paste the seam of insulation material and then bind with adhesive tape The width of tape shall not be less than 5cm Make sure it is firm and avoid dew 9 2 4 Installation and highlights of insulation construction gt single pipe should be insulated before connecting to another pipe the joint part should be insulated after the drainage test gt There should be no insulation
31. between indoor and outdoor units E1 Power off then turn on the unit 5 seconds later reconnect the power wire Is the error still displaying after several minutes Yes v Check if there s any interference Remove interference Such as too many lamps power gt Increase the capacity of anti transformers Or the signal wire is i Interference too long No Y Check whether the signal wire is shield cable whether the shield No ACOP ene e ha cable earthing cable is earthing Yes Y Check whether the wire is correct polarity P to P Q to Q E to E Yes v Check whether the signal wire is broken No Correct the connection Y Y Yes Replace the signal wire No Y Check whether the signal wires insert on PCB well Yes Y Replace indoor PCB is the error distinguished No Pull out and insert back Y No Y Replace the outdoor PCB Electrical Control 85 Troubleshooting b Open or short circuit of temperature sensor E2 E3 E4 Check the connections between temperature sensor and PCB Are the connections good No Correct the connections Y Yes Y Check the resistance value of the sensor via Appendix 1 Yes
32. controller is used with corresponding unit 98 Electrical Control Controller 3 1 3 INDICATORS AND FUNCTIONS dii 5 san B C pa 76 Time ON OFF FAN Cran SPEED into Gan Temp Display the set temperature Adjust temperature Y No display this area if the unit is mode Transmitting display The icon will flash once when the signal is sent by remote controller ON FF Icon is displayed when the remote controller is turned on or vice versa Running mode Press MODE to display current running mode AUTO COOL DRY HEAT and FAN can be selected Time Display the current set time Press CLOCK for 5s icon indicating hour will flash Press this button again icon indicating minute will flash AAnd Ware used to adjust the figure Setting or modification is effective only by pressing OK button to make confirmation Lock The icon will be lightened or off when pressing LOCK In locked state all the buttons are ineffective except button LOCK Time ON OFF In the state of time ON icon ON will be lightened which is the same to the state of time OFF Setting timer ON and OFF simultaneously both icons ON and OFF are displayed Fan speed Press FAN SPEED to display the current wind speed AUTO LOW MED and HIGH can be selected The default state is high fan speed for the unit without medium fan speed Economic operation This icon
33. ctromagnetic wave near the unit There should not be inflammable materials or gas near the unit There should not be strong voltage vibration 2 2 Outdoor unit location selection Y V V YV V V V YV Y YV V 50 The place shall easily support the outdoor unit s weight Locate the outdoor unit as close to indoor unit as possible The piping length and height drop can not exceed the allowable value The place where the noise vibration and outlet air do not disturb the neighbors There is enough room for installation and maintenance The air outlet and the air inlet are not impeded and not face the strong wind 15 easy to install the connecting pipes and cables There is no danger of fire due to leakage of inflammable gas should be a dry and well ventilation place The support should be flat and horizontal Do not install the outdoor unit in a dirty or severely polluted place so as to avoid blockage of the heat exchanger in the outdoor unit is built over the unit to prevent direct sunlight rain exposure direct strong wend snow and other scraps accumulation make sure that heat radiation from the condenser is not restricted More than 30cm More than 60cm Service space More than 30cm eq d 4 More than 60cm ed More than 200cm Installation Insulation Work 3 Indoor unit in
34. ded by the diameter and length of the liquid pipe between indoor and outdoor unit Refer the following formula to calculate the charge volume Diameter of liquid pipe mm 06 35 69 52 012 7 V 11g mx L 5 V 30g mx L 5 V 60g mx L 5 V Additional refrigerant charge volume L The length of the liquid pipe m Note gt Refrigerant may only be charged after performed the vacuum drying process Always use gloves and glasses to protect your hands and eyes during the charge work gt Use electronic scale or fluid infusion apparatus to weight refrigerant to be recharged Be sure to avoid extra refrigerant charged it may cause liquid hammer of the compressor or protections gt Use supplementing flexible pipe to connect refrigerant cylinder pressure gauge and outdoor unit And The refrigerant should be charged in liquid state Before recharging The air in the flexible pipe and manifold gauge should be exhausted After finished refrigerant recharge process check whether there is refrigerant leakage at the connection joint part Using gas leakage detector or soap water to detect 68 Installation Insulation Work 9 Engineering of insulation 9 1 Insulation of refrigerant pipe 9 1 1 Operational procedure of refrigerant pipe insulation Cut the suitable pipe insulation except joint section flare the pipe piping layout and connection vacuum drying insulate the joint parts 9 1 2 Purpose of refrigera
35. default state is high fan speed for the unit without medium fan speed 3 2 9 Operation instructions 1 AUTO operation Switch on the power and running indicator light on indoor unit flashes 1 Press MODE to select AUTO 2 Adjust temp Aand Generally the range is 17 C 30 3 Press ON OFF and running indicator light on indoor unit is lightened Air conditioner will work on AUTO mode and fan speed is AUTO which is non adjustable Press the ON OFF button again to stop the unit operation NOTE In the AUTO mode the air conditioner can logically choose the mode of COOL FAN by sensing the difference between the actual ambient room temperature and the set temperature on the remote controller If the AUTO mode is not comfortable for you the desired mode can be selected manually 2 COOL HEAT FAN operation 1 Press MODE to select COOL HEAT or FAN 2 Adjust temp Aand Y Generally the range is 17 30 3 Press FAN SPEED to select AUTO LOW MED or HIGH 4 Press ON OFF and running indicator light on indoor unit is lightened Air conditioner will work on the set mode Stop operation via ON OFF NOTE The FAN mode cannot be used to control the temperature While in this mode only steps 1 4 be performed 3 DRY operation 1 Push the MODE button to select DRY 2 Push the TEMP button to set the desired temperature from 17 to 30 Electrical Control 107 Controller 3 Push the ON OFF button The opera
36. ectrie CharacteriStlCS 14 QUA EEVEIS cundo gene 15 O ACCOCSSOMES TR 16 9 The Specification of Power dnd 17 An 18 6 Duct Type Features 1 Features 1 1 Installation accessories Optional gt Front Board Canvas Air Passage Filter Panel for easy installation Canvas Air Passage Filter Panel 1 2 Easy Installation Two air inlet styles Bottom side or Rear side gt Air inlet from rear is standard for all capacity air inlet from bottom is optional gt The size of air inlet frame from rear and bottom is same it s very easy to move the cover from bottom to rear side or from rear to the bottom in order to matching the installation condition gn Air intake from rear Standard Air intake from bottom ai 1 3 Easy maintenance gt Clean the filter Optional standard product without filter 15 easy to draw out the filter from the indoor unit for cleaning even the filter is installed in rear side or bottom side gt Replace the motor or centrifugal fan Remove the ventilated panel firstly Remove a half of blower housing and take out the motor with centrifugal fan Directly remove two bolts and then replace the motor or centrifugal fan easily Duct Type 7 Features UV CCS Blower Housing p
37. g Blowhole Indoor unit Indoor unit PEN Y N 2 6 2 9 end of drainage pipe shall not contact with ground directly 6 3 Drainage test 6 3 1 Water leakage test After finishing the construction of drainage pipe system fill the pipe with water and keep it for 24 hours to check whether there is leakage at joint section 6 3 2 Water discharge test 1 Natural drainage mode the indoor unit with outdoor drainage pump Infuse above 600ml water through water test hole slowly into the water collector observe whether the water can discharge through the transparent hard pipe at drainage outlet 2 Pump drainage mode 2 1 Disconnect the plug of water level switch remove the cover of water test hole and slowly infuse about 2000ml water through the water test hole be sure that the water will not touch the motor of drainage pump 66 Installation Insulation Work Cover of test hole Test hole 4 4 4 CES Drain plug 2 2 Power on and let the air conditioner operate for cooling Check operation status of drainage pump and then connect the plug of water level switch check the operation sound of water pump and observe whether the water can discharge through the transparent hard pi
38. g 3x0 2 Weak Electric Signal mm dd Indoor Outdoor Connecting Wiring Strong Electric Signal mm 30 Art Flux Super slim Cassette Type jError No hay texto con el estilo especificado en el documento 9 Field Wiring KCIS 140 6 KCIS 176 HN6 Air Condition Link Circuit INDOOR UNIT Power supply 1 Phase 208 240V Use 3 core cable 3x2 5mm for the models which with auxiliary electric heater PTC Use 3 core cable 3x1 0mm for the others 3 core shielded cable 3x0 2mm 24AWG Power supply 3 Phase 380 420V 30K 60K 5 core cable 5x2 5mm OUTDOOR UNIT 3 Phase 220V 30K 60K 5 core cable 5x4 0mm For 30K 60K Btu h with 3 Phase outdoor unit Art Flux Super slim Cassette Type OUTDOOR UNIT 2020 0890525 INDOOR UNIT use 3 core cable 3x2 5mm y for the models which with auxiliary electric heater PTC Use 3 core cable 3x1 0mm for the others 3 core shielded cable 3Xx0 2mm 24AWG Power supply 1 Phase 208 240V 18K 24K 3 core cable 3 2 5 30K 36K 3 core cable 3x4 0mm 42 48K 3 core cable 3x6 0mm 60K 3 core cable 3x10 0mm 2 For 18K 60K Btu h with 1 Phase outdoor unit 31 Ceiling amp Floor Type 32 Ceiling amp Floor Type AA 33 DIMENSIONS EIL aa 34 HOOT VICE SPACE is 35 une a 36 Electric Characteristics siii dan 37 SOUNA LEVES I 37 WAC COS SOM lerne 38
39. g and wiring are correctly completed The refrigerant pipe system is leakage checked The drainage is unimpeded The ground wiring is connected correctly The length of the tubing and the added stow capacity of the refrigerant have been recorded The power voltage fits the rated voltage of the air conditioner There is no obstacle at the outlet and inlet of the outdoor and indoor units The gas side and liquid side stop values are both opened The air conditioner is pre heated by turning on the power Y V V V V V YV V V V 70 Installation Insulation Work 11 3 Test operation Set the air conditioner under the mode of COOLING by remote controller and check the following points Indoor unit Whether the switch on the remote controller works well Whether the buttons on the remote controller works well Whether the air flow louver moves normally Whether the room temperature is adjusted well Whether the indicator lights normally Whether the temporary buttons works well Whether the drainage is normal Whether there is vibration or abnormal noise during operation VV VV VV V WV Outdoor unit gt Whether there is vibration or abnormal noise during operation gt Whether the generated wind noise or condensed of by the air conditioner have influenced your neighborhood gt Whether any of the refrigerant is leaked Installation 71 Electrical Control Part 5 Electrical Control System 1 Electrical Control
40. gap between the insulation material 10 Engineering of electrical wiring 10 1 Highlights of electrical wiring installation gt field wiring construction should be finished by qualified electrician gt Air conditioning equipment should be grounded according to the local electrical regulations gt Current leakage protection switch should be installed Donot connect the power wire to the terminal of signal wire When power wire is parallel with signal wire put wires to their own wire tube and remain at least 300mm gap gt According to table in indoor part named the specification of the power to choose the wiring make sure the selected wiring not small than the date showing in the table Select different colors for different wire according to relevant regulations Donotuse metal wire tube at the place with acid or alkali corrosion adopt plastic wire tube to replace it here must be not wire connect joint in the wire tube If joint is a must set a connection box at the place gt The wiring with different voltage should not be in one wire tube Ensure that the color of the wires of outdoor and the terminal No are same as those of indoor unit respectively 11 Test operation 11 1 The test operation must be carried out after the entire installation has been completed 11 2 Please confirm the following points before the test operation The indoor unit and outdoor unit are installed properly Tubin
41. ing Never hold the inlet of the outdoor unit to prevent it from deforming Do not touch the fan with hands or other objects Do not lean it more than 45 and do not lay it sidelong Make concrete foundation according to the specifications of the outdoor units Fasten the feet of this unit with bolts firmly to prevent it from collapsing in case of earthquake or strong wind Fix with bolt 5 Refrigerant pipe installation 5 1 Maximum pipe length and height drop Considering the allowable pipe length and height drop to decide the installation position Make sure the distance and height drop between indoor and outdoor unit not exceeded the date in the following table 45 000Btu h 60 000Btu h 50m 25m 5 2 The procedure of connecting pipes 5 2 1 Choose the pipe size according to the specification table 5 2 2 Confirm the cross way of the pipes 5 2 3 Measure the necessary pipe length 5 2 4 Cut the selected pipe with pipe cutter gt the section flat and smooth X X X a Lean Crude Burr 5 2 5 Insulate copper pipe gt Before test operation the joint parts should not be heat insulated 5 2 6 Flare the pipe gt Insert a flare nut into the pipe before flaring the pipe gt According to the following table to flare the pipe 62 Installation Insulation Work Flare dimension A mm Pipe diameter Flare
42. lectrical wiring 70 NI IIEecubee puasa 70 Installation Insulation Work 1 Installation Procedure Indoor unit installation Outdoor unit installation location selection location selection Indoor unit installation Outdoor unit installation Refrigerant pipe Refrigerant pipe installation and insulation installation and insulation Drainage pipe installation Drainage pipe installation and insulation and insulation Vacuum drying and leakage checking Additional refrigerant charge Insulation the joint part of refrigerant pipe Wiring connection and electric safety checking Test operation Installation 49 Location selection 2 Location selection 2 1 Indoor unit location selection VV VV VV VV VV VY V V The place shall easily support the indoor unit s weight The place can ensure the indoor unit installation and inspection The place can ensure the indoor unit horizontally installed The place shall allow easy water drainage The place shall easily connect with the outdoor unit The place where air circulation in the room should be good There should not be any heat source or steam near the unit There should not be any oil gas near the unit There should not be any corrosive gas near the unit There should not be any salty air neat the unit There should not be strong ele
43. ller Please refer to the wiring diagram of this installation manual to wire the wire controller with indoor unit 3 The Shielded wire of the wire controller must be grounded reliable 4 After finishing the wire controller connection do not employ a tramegger to detect the insulation 2 The wire controller working in low voltage loop circuit Avoid to directly contact the cable of 220Vcommercial electricity or of 380V high voltage and don t wire this kind of wire in the said loop wiring clearance between configured tubes should at the range of 300 500 or above 3 2 3 Installation method oimplified schematic of wire controller the here the length should be set base field installation 15 rm Connectwe wires for the signal received panel accessory A in ET The shielded 5 core wire signal pre embedded into wall panel 102 Electrical Control Controller The shielded cor e wire pre embed ded into wall Fig 3 5 A 1 Connect the male joint of 5 core wires group of the signal received panel with the female 5 core terminal of signal received panel See Fig 3 2 5 Adjust the length of two plastic bolts base on the length of throughout from standard electric cabinet to the wall Confirm the two bolts fixing in the cabinet are in the same length and vertical to the wall surface 6 Fix the bottom cover to the
44. minutes then it will follow the below rules When indoor room temp T1 is higher than the compressor and outdoor fan will shut off When T1 is lower than Tgap0 1 the compressor and outdoor fan will start up T1 TS Off TgapO TgapO 1 On For Ceiling Floor TgapO setting temperature compensation 1 3 3 2 Outdoor fan running rules Fan below The outdoor fan runs all the time Fan above T4 18 Off 1 3 3 3 Indoor fan running rules When the compressor is on the indoor fan can be set to high med low auto And the anti cold wind function has the priority Electrical Control 77 Electrical Control Function Auto fan action For Duct amp super slim cassette type For Ceiling amp Floor setting temperature compensation 4 C T1 Ts Low 3 Medium 1 High For Ceiling amp Floor setting temperature compensation 1 C T1 Ts Low 0 Medium 2 High 1 3 3 4 Defrosting mode e Condition of defrosting AC will enter defrosting mode if any of the following items is satisfied A T3 TE19 and the compressor keeps running over 45 minutes Meanwhile T3 TE17 for 3minutes B After the last defrosting the time that the outdoor fan is off but the compressor is on in high T2 protection cumulates up to 90 minutes e Condition of ending defrosting If any one of the following items is satisfied the defro
45. mp Yes Is it K1 or K2 open Is temp protective switch close ls pressure protective switch K2 close Yes Yes Possible reason 1 The wires is loose to K2 2 Air or other gas in the refrigerant 3 Heat exchanger is dirty 4 Possible reason 1 wires is loose to 1 2 Air or other gas in the refrigerant 3 Heat exchanger is dirty 4 Outdoor motor or fan blade is defective Outdoor unit is in bad ventilation Refrigerant is too much Outdoor fan or fan blade is defective Outdoor unit is in bad ventilation Refrigerant is leakage 94 Electrical Control Troubleshooting e High temperature protection of condenser High temperature protection of condenser Check the resistance of the temp sensor according to Appendix 1 is it normal Possible reason Replace the sensor Air or other gas in the refrigerant Heat exchanger is dirty Outdoor fan or fan blade is defective Outdoor unit is bad ventilation Refrigerant is leakage Electrical Control 95 Troubleshooting Appendix 1 Temperature Sensor Resistance Value Table Kom kom C kom _ o 115266 126431 6o 235774 100 06293 19 108146 120561 61 227249 101 061148 18 101517 22 11500 62 219073 05996 __ 47 963423 109731 21124 103 05763 16 895865 24 104736 64 203732 104 0 56038 15 882190 25 1000 65 196532 10
46. n el documento 5 Electric Characteristics UN Indoor Unit Power Supply ode KCIS 140 HN6 220 240V 198V 254V KCIS 176 HN6 220 240V 198V 254V Note MFA Max Fuse Amps A Art Flux Super slim Cassette Type 27 Sound Levels 6 Sound Levels 1 4m Microphone Noise level dB A Model 28 Art Flux Super slim Cassette Type jError No hay texto con el estilo especificado en el documento 7 Accessories Name Quantity INSTALLATION FITTINGS Installation paper board 1 Bolt M5 4 Tubing amp Fittings Soundproof insulation sheath 2 Out let pipe 1 Drainpipe Fittings Out let pipe sheath 1 Out let pipe clasp 1 Remote controller amp Frame 1 Remote controller amp Its Remote controller holder 1 Frame Mounting screw ST2 9x10 C H 2 Remote controller manual 1 Alkaline dry batteries AM4 2 Owner s manual 1 Others Installation manual 1 Network wires 1 Installation accessory Expansible hook 4 The product you have following accessories Orifice Art Flux Super slim Cassette Type 29 The Specification of Power 8 The Specification of Power KCIS 140 HN6 Frequency and Voltage 220 240V 50Hz INDOOR UNIT POWER 5 POWER WIRING mm 3 Circuit Breaker Fuse A 20 16 Frequency and Voltage 380 415V 50H OUTDOOR UNIT POWER 3 d 2 2 f POWER WIRING mm Circuit Breaker Fuse A 25 20 Indoor Outdoor Connecting Wirin
47. nits nmm mi O O 2 O c 43 2 O C General Information Features 3 Features 3 1 High quality coils The coil is constructed of advanced inner grooved copper tube and aluminum fins 3 2 Anti rust 500 hours salt spray test 3 3 Low operation sound level Well known stable and quiet running fan motor 3 4 Well known compressor 3 5 Compact design Smaller dimension and larger stuffing capacity 3 6 Universal outdoor unit design 3 7 Optional air outlet grille plastic type and wire type 7 22222 A 24 HH Z 2 2 7 SOK gt 22 SS 27 222 29 a gt 2 4 ES Mm 2 d SSS SS Ed SEE WSS NS SS SS 5 SS 1 NN NN Wire type Plastic type Plastic type 3 8 Optional low temperature cooling module 3 9 R410A environment friendly refrigerant 4 General Information Indoor Units Part 2 Indoor Units 6 Super slim Cassette Type 19 Ceiling Floor VD 32 Indoor Units Duct Type Duct Type T PeQ0Ir6S ana ori 7 2 DIMENSIONS 10 3 11 Wiring Diagrams riada 12 5 Slate PresSU Buin 13 El
48. nt pipe insulation gt During operation temperature of gas pipe and liquid pipe shall be over heating or over cooling extremely Therefore it is necessary to carry out insulation otherwise it shall debase the performance of unit and burn compressor gt Gas pipe temperature is very low during cooling If insulation is not enough it shall form dew and cause leakage gt Temperature of gas pipe is very high generally 50 100 during heating Insulation work must be carried out to prevent hurt by carelessness touching 9 1 3 Insulation material selection for refrigerant pipe gt The burning performance should over 120 gt According to the local law to choose insulation materials gt thickness of insulation layer shall be above 10mm lf in hot or wet environment place the layer of insulation should be thicker accordingly 9 1 4 Installation highlights of insulation construction gt Gas pipe and liquid pipe shall be insulated separately if the gas pipe and liquid pipe were insulated together it will decrease the performance of air conditioner Liquid pipe Insulation meterial Gas pipe The insulation material at the joint pipe shall be 5 10cm longer than the gap of the insulation material The insulation material at the joint pipe shall be inserted into the gap of the insulation material The insulation material
49. ntrol panel 10 Electric control panel of indoor unit 10 cored aona recelved connective w ires Connective wies group af signal received parel y shielded 5 cable See Installation preparation sheet 1 tor the specification The rear side of wire controller Fig 42 3 2 5 Specification Input voltage LIC a Ambient humidity RH40 3 2 6 General function Main functions of this wire controller as follows Connect with indoor unit via the five ports of A B C D E Set operation mode via buttons control Provided with LCD display function Provided with timing function 104 Electrical Control Controller 3 2 Name and operation of the button on the wire controller 2 9 E 8 4 Mode select button ON OFF button Adjust button Adjust button Time button FAN speed button Timer button Swing button Cancel button Infrared remote receiver OO JO OO N mb D MODE Select Button Each time you push the button a mode is selected in a sequence that goes from AUTO COOL DRY HEAT and FAN as the following figure indicates AUTO COOL DRY HEAT FAN 2 ON OFF Button When in off state press this button the indicator is on the wire controller enter into on state and send setting information to indoor PCB When in on state press this button the indicator is offhand send instruction If timer
50. o elevate the condensate water such as high extra static pressure duct unit the water storage pipe should be set to avoid converse flow or blow water phenomena Main pipe More than 50mm Plug Cs More than 25mm A 7 6 2 7 Lifting pipe setting of indoor unit with water pump Water storage pipe gt length of lifting pipe should not exceed the pump head of indoor unit water pump Pump head of big four way cassette 750mm Pump head of compact four way cassette 500mm gt drainage pipe should be set down inclined after the lifting pipe immediately to avoid wrong operation of water level switch Heferthe following picture for installation reference Indoor unit Installation 65 Drainage pipe installation Down incline pipe A Length of horizontal pipe 150mm B Lift height the pump head of water pump Flexible 300mm 6 2 8 Blowhole setting gt For the concentrated drainage pipe system there should design a blowhole at the highest point of main pipe to ensure the condensate water discharge smoothly gt The air outlet shall face down to prevent dirt entering pipe gt Each indoor unit of the system should be installed it gt installation should be considering the convenience for future cleanin
51. of timer operation Press corresponding button and readjust the time of time ON and time OFF Adjust the time figure to 0 00 to cancel the timer operation NOTE The time set in timer operation is the relative figure based on the clock on remote controller Adjusting clock is unavailable when TIME ON or TIME OFF is activated 100 Electrical Control Controller 3 2 KC 01 2 R Wired IR Remote Controller Optional 3 2 1 Safety precautions Read the safety precautions carefully before installing the unit Stated below are important safety issues that must be obeyed WARNING Means improper handling may lead to personal severe injury CAUTION Means improper handling may lead to personal injury or property loss WARNING Please entrust the distributor or professionals to install the unit Installation by other persons may lead to imperfect installation electric shock or fire Adhere to this installation manual Improper installation may lead to electric shock or fire Reinstallation must be performed by professionals Improper installation may lead to electric shock or fire Do not uninstall the unit randomly Random uninstalling may lead to abnormal operation heating or fire of the air condition NOTE Do not install the unit in a place vulnerable to leakage of flammable gases Once flammable gases are leaked and left around the wire controller fire may occur The wiring should adapt to the wire controller current Other
52. opper oxide shall damage compressor gt Eliminating the non condensable gas air in system to prevent the components oxidizing pressure fluctuation and bad heat exchange during the operation of system 7 2 Selection of vacuum pump gt The ultimate vacuum degree of vacuum pump shall be 756mmHg or above gt Precision of vacuum pump shall reach 0 02mmHg or above 7 3 Operation procedure for vacuum drying Due to different construction environment two kinds of vacuum drying ways could be chosen namely ordinary vacuum drying and special vacuum drying 7 3 1 Ordinary vacuum drying Installation 67 Additional refrigerant charge 1 When conduct first vacuum drying connect pressure gauge to the infusing mouth of gas pipe and liquid pipe and keep vacuum pump running for 1hour vacuum degree of vacuum pump shall be reached 755 2 vacuum degree of vacuum pump could not reach 55mmHg after 1 hour of drying it indicates that there is moisture or leakage in pipeline system and need to go on with drying for half an hour 3 If the vacuum degree of vacuum pump still could not reach 55mmHg after 1 5 hours of drying check whether there is leakage source 4 Leakage test After the vacuum degree reaches 755mmHg stop vacuum drying and keep the pressure for 1 hour If the indicator of vacuum gauge does not go up it is qualified If going up it indicates that there is moisture or leak source 7 3 2 Special vacuum drying
53. p is Yes gt No Insert the water level switch well Replace the water level switch normal Yes Y Check PCB board or replace the indoor main PCB 88 Y Replace the water pump Electrical Control Troubleshooting f Indoor fan speed has been out of control Eb Find out the cause and have it solved For example check whether the fan is blocked or the bearing is broken Correct the connections Shut off the power supply and turn it on 5 seconds later Is it still displaying No gt The unit operates normally the error code ve Shut off power supply rotate the fan by hand No Does it rotate properly Yes Check i wires of fan motor Are all the No gt good Check mm the fan Replace the fan motor is normal through No t index 1 Yes Y Replace the Check whether the main PCB is POB No The normal through index 2 E malfunction is solved Yes Electrical Control If the malfunction is still existing replace the main PCB 89 Troubleshooting Index 1 1 Indoor DC fan motor control chip is inside fan motor Measure the resistance value of each winding by using the tester If any resistance value is zero the fan motor must ha
54. pe gt Adopt suitable pipe diameter gt Adopt nearby condensate water discharge 6 2 Key points of drainage water pipe installation 6 2 1 Considering the pipeline route and elevation gt Before installing condensate water pipeline determine its route and elevation to avoid intersection with Installation 63 Drainage pipe installation other pipelines and ensure slope is straight 6 2 2 Drainage pipe selection gt drainage pipe diameter shall not small than the drain hose of indoor unit gt According to the water flow rate and drainage pipe slope to choose the suitable pipe the water flow rate is decided by the capacity of indoor unit Relationship between water flow rate and capacity of indoor unit 2 OSS os i According to the above table to calculate the total water flow rate for the confluence pipe selection For horizontal drainage pipe The following table is for reference Reference value of inner Allowable maximum water flow rate l h PVC pipe di Remark lameter of pipe mm store 1 50 Sope 1 1 100 For branch pipe PVC32 PVC40 2 Attention Adopt or bigger pipe to be the main pipe For Vertical drainage pipe The following table is for reference Reference value n m Allowable water flow rate E EN PVC25 For branch pipe 40 waf PVC63 2760 Could be used for confluence pipe Attention Adopt PVC40 or bigger pipe to be the main pipe
55. pe at drainage outlet In light of the length of drainage pipe water shall be discharged about 1 minute delayed 2 3 Stop the operation of air conditioner power off the power supply and put the cover of water test hole back to the original place a After stopped the air conditioner 3 minutes check whether there is anything abnormal If drainage pipes have not been distributed properly over back flow water shall cause the flashing of alarm indicator at remote controlled receiving board and even water shall run over the water collector b Continuously infusing water until water level alarmed check whether the drainage pump could discharge water at once If water level does not decline under warning water level 3 minutes later it shall cause shutdown of unit When this situation happens the normal startup only can be recovered by turning down power supply and eliminating accumulated water Note Drain plug at the main water containing plate is used for eliminating accumulated water in water containing plate when maintaining air conditioner fault During normal operation the plug shall be filled in to prevent leakage 6 4 Insulation work of drainage pipe Refer the introduction to the insulation engineering parts 7 Vacuum Drying and Leakage Checking 7 1 Purpose of vacuum drying gt Eliminating moisture in system to prevent the phenomena of ice blockage and copper oxidation Ice blockage shall cause abnormal operation of system while c
56. ponding unit CLOCK Display the current time 12 00 is displayed when resetting or electrifying for the first time Press CLOCK for 5s icon indicating hour will flash with 0 5s Press it again icon indicating minute will flash with 0 5sW and Aare used to V J adjust the figure Setting or modification is effective only by pressing OK button to make confirmation TIME ON For time ON setting Once pressing this button the time will increase by 0 5 hour When the set time exceeds 10 hours pressing the button will increase the time by 1 hour Adjusting the figure to 0 00 will cancel time ON setting TIME OFF For time OFF setting Once pressing this button the time will increase by 0 5 hour When the set time exceeds 10 hours pressing the button will increase the time by 1 hour Adjust the figure to 0 00 will cancel time ON setting RESET inner located Press this button with a needle of 1mm to cancel the current setting and reset remote controller LOCK inner located Press this button with a needle of 1mm to lock or unlock the current setting OK Used to confirm the time setting and modification COOL HEAT inner located Press this button with a needle of 1mm to shift mode between COOL only and COOL amp HEAT During setting back light will be lightened Factory default mode is COOL amp HEAT ECO Activate or turn off economic operation mode It is suggested to turn on this function when sleeping Only available when remote
57. r PCB is Ne defective Change it Yes Y The up down panel is defective Change it Problem is solved Electrical Control 91 Troubleshooting c Up down panel is not closed F2 Displayed The up down panel is not closed Check if the filter panel of up down panel is closed Yes Y The up down panel is defective Change it 92 Problem is solved Lift the filter panel to close it Electrical Control Troubleshooting 2 For the outdoor unit a Phase sequence error Phase sequence error Change the order of two of the wires to power supply Switch on the unit again If the problem cannot be solved the outdoor PCB is defective b Lack of phase Electrical Control Lack of phase Check the power supply is it 3 phase 380 415V Yes Check the connection between power supply and terminal is the voltage in outdoor terminal is 3 phase 380 415 Yes Outdoor PCB is defective 93 Troubleshooting c Overload of current Overload of current Check the current normally Is the current in rated range No Yes Possible reason The outdoor PCB is defective The compressor is defective 2 3 Refrigerant is over charged 4 Air enter the refrigerant system d Protection of pressure or temp Protection of pressure or te
58. rail Air return flange Dentilation panel Stick the attached seal sponge as per the indicating place in the following fig and then change the mounting positions of air return panel and air return flange 4 The installation has finish upon filter mesh which fixing blocks have been insert to the flange positional holes Installation 53 Indoor unit installation 3 3 Super slim cassette indoor unit installation 3 3 1 Service space for indoor unit Connecting point of Connecting point of drain pipe refrigerant pipe Liquid side gt 1000mm gt 1000mm ff Connecting point of T d TT EF refrigerant pipe Gas side Ceiling 0 AS E outlet Inlet Outlet N Panel 880mm ceiling hole A Y Ground HWH Remark ______ ENEN R410A and R22 Cooling Cooling amp Heating pred R410A and R22 Cooling Cooling amp Heating 3 3 2 Bolt pitch Tubing side Drain side 680 Hook location Unit mm 3 3 3 Install the pendant bolt Select the position of installation hooks according to the hook holes positions showed in upper picture Drill four holes of 12mm 45 50mm deep at the selected positions on the ceiling Then embed the expansible hooks fittings 54 Installation Insulation Work 3 3 4 Install the main body Make the 4 suspender through the 4 hanger of the main body to suspend it Adjust
59. responding channel when installing the cover Note The panel shall be installed after the wiring connected Installation 57 Indoor unit installation 3 4 Ceiling amp floor indoor unit installation 3 4 1 Service space for indoor unit gt 1000 gt 35mm NNNNNNNNNNNNNNNNN 3 4 2 Bolt pitch O Ceiling installation Capacity Btu h KPC 140 HN6 KPC 176 HN6 Wall mounted installation LI T I I I T I LL TJ LL LJ an ILLI ILL LT LI TJ LAU I mu immi LL L1 I IL Y BB Installation Insulation Work 3 4 3 Install the pendant bolt Ceiling installation Select the position of installation hooks according to the hook holes positions showed in upper picture Drill four holes of 12mm 45 50mm deep at the selected positions on the ceiling Then embed the expansible hooks fittings Wall mounted installation Install the tapping screws onto the wall Refer to picture below LI 1 aS IL LI LI L LL LU IL ILI imm LI immi LI IL IL LII LL IL L 1 m i L 3 4 4 Install the main body Ceiling installation The only installation method for the unit
60. rt to the receiver on air conditioner 3 1 2 BUTTONS AND THEIR FUNCTIONS MODE Once pressing running mode will be selected in the following sequence AUTO COOL DRY HEAT FAN FAN SPEED Fan speed will be selected in following sequence once pressing this button Q Fan speed setting AUTO LOW MED HIGH Adjust Alncrease the set temp Keeping pressing will Adjust increase the temp with 1 C per 0 5s Adjust V Decrease the set temp Keeping pressing will decrease the temp with 1 C per 0 5s ON OFF For turning on or turning off the air conditioner Air direction setting AIR DIRECTION Activate swing function of air deflector Once pressing air deflector will turn 6 For normal operation Time setting and better cooling and heating effect deflector will not turn to the degree which is the state of deflector when the unit is Mode setting Adjust Y G ON OFF 9 Wind Vert Swing O TRF TIMER ON Wind Horiz Swing turned off Only available when remote controller is used with O TIMER OFF OFF corresponding unit Reset Rea Wind Vert Swing Activate turn off wind vertical swing tek 0 Confirm button function Only available when remote controller is used with corresponding unit O Wind Horiz Swing Activate or turn off wind horizontal swing function Only available when remote controller is used with corres
61. s this key again the function will cancel This function could available only equip with the coordinated entire units system 9 CANCEL Button Push this button to cancel the TIMER settings 3 2 8 Indicators and functions 106 o 9 1 Operation mode indication 2 Temperature display zone 3 Time ON indication 4 Time indication 5 Time indication 6 Fan speed indication 1 Operation mode indication Press MODE to display current running mode AUTO COOL DRY HEAT and FAN can be selected HEAT function is invalid for cool only type unit 2 Temperature display zone Electrical Control Controller Display the set temperature Adjust temperature and Y No display in this area if the unit is on FAN mode 3 Time ON indication During setting the Timing ON or after set the Timing ON the LCD would display TIME ON 4 Time indication Normally LCD displays the current time of the setting clock When press this Button last for 4 sec the clock will flash at the frequency of 0 5 sec By usingA and Y to set the minute Release the button when finish the clock setting the time will stop flashing automatically which means time setting successfully Time OFF indication During setting the Timing OFF or after set the Timing OFF the LCD would display TIME OFF 6 Fan speed indication Press SPEED to display the current wind speed AUTO LOW MED and HIGH can be elected The
62. shape 90 4 12 4 gt After flared the pipe the opening part must be seal by end cover or adhesive tape to avoid duct or exogenous impurity come into the pipe 5 2 Drill holes if the pipes need to pass the wall 5 2 8 According to the field condition to bend the pipes so that it can pass the wall smoothly 5 2 9 Bind and wrap the wire together with the insulated pipe if necessary 5 2 10 Set the wall conduit 5 2 11 Set the supporter for the pipe 5 2 12 Locate the pipe and fix it by supporter gt For horizontal refrigerant pipe the distance between supporters should not be exceed 1m gt For vertical refrigerant pipe the distance between supporters should not be exceed 1 5m 5 2 13 Connect the pipe to indoor unit and outdoor unit by using two spanners gt sure to use two spanners and proper torque to fasten the nut too large torque will damage the bell mouthing and too small torque may cause leakage Refer the following table for different pipe connection Pipe Diameter 1 4 6 35 144 176 1420 1720 3 8 9 52 333 407 3270 3990 1 2 12 7 504 616 4950 6030 5 8 15 9 630 770 6180 7540 3 4 19 990 1210 9270 11860 6 Drainage pipe installation Install the drainage pipe as shown below and take measures against condensation Improperly installation could lead to leakage and eventually wet furniture and belongings 6 1 Installation principle gt Ensure at least 1 100 slope of the drainage pi
63. splayed 2 3 Indoor fan can be set to high med low auto 4 5 High Medium 4 The louver operates same as in cooling mode 5 Auto fan 1 27 26 24 1 3 2 Cooling Mode 1 3 2 1 Compressor running rules Once the compressor starts up it will follow the below rules Low When indoor room temp T1 is lower than Ts the compressor and outdoor fan will shut off When T1 is higher than Ts 1 the compressor and outdoor fan will start up T1 Ts 1 Ts 1 3 2 2 Outdoor fan running rules For double fan outdoor units Fan above The outdoor fan runs all the time Fan below T3 33 30 74 Electrical Control Electrical Control Function 1 3 2 3 Indoor fan running rules In cooling mode indoor fan runs all the time and the speed can be selected as high medium low and auto The auto fan T1 Ts High Medium 1 Low 1 3 2 4 Low evaporator coil temperature T2 protection For Duct T2 TE6 TE5 When the evaporator coil temp T2 keeps lower than TE5 for the compressor and outdoor fan will shut off When T2 is higher than TE6 the compressor and outdoor fan will restart up For Ceiling amp Floor super slim cassette type AC will enter T2 protection if any of the following conditions is satisfied Condition 1 2 6 TE5
64. stallation 3 1 Duct indoor unit installation 3 1 1 Service space for indoor unit 200mm or more 300mm or more gt N i 600mmA600mm checking orifice gt 3 1 2 Bolt pitch Electric control box Size of outline dimension mounted plug oe 3 1 3 Install the pendant bolt Select the position of installation hooks according to the hook holes positions showed in upper picture Drill four holes of 12mm 45 50mm deep at the selected positions on the ceiling Then embed the expansible hooks fittings Installation 51 Indoor unit installation 3 1 4 Install the main body Make the 4 suspender through the 4 hanger of the main body to suspend it Adjust the hexangular nuts on the four installation hooks evenly to ensure the balance of the body Use a leveling instrument to make sure the levelness of the main body is within 1 Screw nut Shockproof cushion Overhang part Washer Hanging screw bolt 3 1 5 Install the air filter Insert the air filter through the filter slot and fix it with 2 screws 3 1 6 Install the air duct Please design the air duct as below recommended picture Canvas tie in Canvas tie in Zi nu TAL Z Isolation booth Z Air inlet Isolation booth Air dust filter checking orifi Air outlet 52 Installation Insulation Work 3 1 7 Change the air inlet direction Take off ventilation panel and flange cut off the staples at side
65. state if it is necessary to turn off the pump it will be off in 1 minute delay If the error is still there in 3 minutes the drain pump will be off as well as the AC unit The error can be cleared only when the power of the unit is cut off Electrical Control 81 Troubleshooting 2 Troubleshooting 2 1 Display board 2 1 1 Icon explanation on indoor display board A5 Duct amp High Static Pressure Duct PRE DEF indicator cooling and heating type or fan only indicator cooling only type Timer indicator Alarm indicator Operation lamp Infrared signal receiver Temporary button Display digital tube O O O O O MANUAL OPERATION TIMER DEF FAN ALARM 2 1 2 Icon explanation on indoor display board Super slim 4 way cassette Temporary button Digital LED Infrared signal receiver Operation lamp Timer indicator Alarm indicator PRE DEF indicator cooling and heating type or fan only indicator cooling only type 2 1 4 Display board of auto lifting panel of 4 way cassette Digital 88 Display Pd Check Button Running LED Timer LED Defrost LED Alarm LED 2 1 5 leon explanation on indoor display board Ceiling amp Floor MANUAL OPERATION TIMER fa Infrared signal receiver 82 Electrical Control Troubleshootin 2 2 Self diagnosis Indoor unit s LED indication 1 For Duct NO Malun ioh Running Timer
66. sting will terminate and the machine will turn to normal heating mode A T3 rises to be higher than TE18 B The machine has run for 10 minutes in defrosting C Turn to other modes or off 78 Electrical Control Electrical Control Function Defrosting action Setting defrosting time 458 458 4 1 3 3 5 High evaporator coil temp T2 protection For Duct and Super slim Cassette Compressor off Outdoor fan off Compressor on Outdoox fan on TE9 TE8 TE10 For Ceiling amp Floor Compressor off P Compressor and Outdoor fan off TES Outdoor fan off Compressor and TE9 Outdoor fan on Compressor and Outdoor fan on 1 3 4 Auto mode This mode can be chosen with remote controller and the setting temperature can be changed between 17 30 In auto mode the machine will choose cooling heating or fan only mode according to AT AT 11 15 Electrical Control 79 Electrical Control Function For Duct and Super slim Cassette E For Ceiling amp Floor AT T1 Ts Running mode Indoor fan will run at auto fan of the relevant mode The louver operates same as in relevant mode If the machine switches mode between heating and cooling the compressor will keep stopping for 15 minutes and then choose mode according to T1 Ts If the setting temperature is modified the machine will choose running function again 1 3 5 Drying mode 1
67. t direction setting O Time setting TIMER ON 5 O TIMER OFF 3 Confirm button 8 7 Economie operation MODEL AND SPECIFICATION ROS BGE RMOS BGE T RMOS BG T E A Rated voltage 3 0V 2 pieces of LRO3 7 batteries Min voltage for sending signal of CPU Effective receiving distance Operation condition 5 60 C 97 Controller 3 1 1 PRECAUTIONS Curtain door or the like objects will prevent the remote signal from being received by air conditioner Do not get the interior of remote controller wet It is forbidden to expose it to direct sunlight or locate it in the place with high temp Malfunction may occur if infrared signal receiver on air conditioner is exposed to sunlight Please shelter the signal receiver from sunlight with curtain Please remove the nearby electronic device for they may affect the performance of remote controller Do not put the used or different batteries into the remote controller otherwise remote controller will fail to send signal Please remove the batteries before long period unused otherwise the remote controller may be damaged If pressing the button reset the remote controller which indicates low battery please replace the batteries If no receiving sound is heard from indoor unit or on remote controller does not flash please replace the batteries Effective transmitting distance of remote controller is 8m please aim the signal sending pa
68. tatic Pressure 45 000 48 000Btu h 51 000 60 000Btu h Pa Pa 120 120 110 110 100 100 90 90 80 2 Super high speed Super high speed 82 70 1 70 High speed High speed 2 m D 60 PU e Low speed 5 50 Mid speed ao 4 C 40 5 ow speed Z gt 30 30 2 20 20 i 1000 1300 1600 1900 2200 2500 2800 3100 1000 1300 1600 1900 2200 2500 2800 3100 3400 Air volume m h Air volume m h Duct Type 13 Electric Characteristics 6 Electric Characteristics Model Indoor Unit Power Supply KPD 140 HN6 220 240 198V 254V KPD 176 6 220 240V 198V 254V Note MFA Max Fuse Amps A Duct Type Sound Levels 7 Sound Levels Concealed Duct Type Discharge Suction Duct Duct A 1 4m Vv Microphone Noise level dB A Model Duct Type 15 Accessories 8 Accessories Quantity Soundproof insulation sheath C Dle Tubing amp Fittings Binding tape Drainpipe Fittings Seal ring Wire controller Wire controller others Installation manual 16 Duct Type The Specification of Power 9 The
69. the hexangular nuts on the four installation hooks evenly to ensure the balance of the body Use a leveling instrument to make sure the levelness of the main body is within 1 Adjust the position to ensure the gaps between the body and the four sides of ceiling are even The body s lower part should sink into the ceiling for 10 12 mm In general L is half of the screw length of the installation hook Ceiling Locate the air conditioner firmly by wrenching the nuts after having adjusted the body s position well Installation 55 Indoor unit installation 3 3 5 Install the panel Remove the grille Remove the 4 corner covers Hang the panel to the hooks on the mainbody If the panel is with auto lift grille please watch the ropes lifing the grille DO NOT make the ropes enwinded or blocked Y IS j SEK Hook bolt X 4 Cross screwdriver 56 Installation Insulation Work Tighten the screws under the panel hooks till the panel closely stick on the ceiling to avoid condensate water 7 Loosen upper nut 1l Lo ER Gap not allowed Leakage Ceiling YSewww Pollution p o Water condensation 0 Hang the air in grill to the panel then connect the lead terminator of the swing motor and that of the control box with corresponding terminators on the body respectively Install the 4 corner covers back Installation cover s rope Tap Screw Slide the four sliders in the cor
70. tion lamp lights and the air conditioner starts to operate in the DRY mode Push the ON OFF button again to stop this unit operation NOTE Due to the difference of the set temperature of the unit and the actual indoor temperature the Air Conditioner when in DRY mode will automatically operate many times without running the COOL and FAN mode 4 Timing set 4 TIMER button is for set TIME ON TIME OFF these two types of timing Timing ON time and CLOCK are display at the same displayed zone When the Timing ON has been set the CLOCK displayed zone would show the Timing ON information Press the CLOCK key to query the current time which would last for 3 seconds and then recover to Timing ON information During the setting the timing press the CANCEL button to exit the timing set For the first time press the TIMER button the icon of TIME will display and the timing time will flashing at the 1Hz while the TIMER OFF icon will not show and the timing off time would not flash in the case of without timing off setting the information will not show Press the TIMING key again the TIME OFF icon will show and the timing time will flashing at 1Hz while the TIME ON icon will not show and the timing on time would not flash in the case of without timing on setting the information will not show Button pressing base on this circulating logic Set the Timing ON time only 1 Press the TIMER button the LCD in the
71. unit Duct Type Art Flux Super slim Cassette Type Art Flux Super slim Cassette Type le 20 Euer 24 8 SEVICE SPACE 25 3 26 5 Electric Characteristics 27 D Sound ESVOlS curas ds 28 T ACCESSORIES or 29 8 The Specification of Power 30 9 Field INO uuu 31 Art Flux Super slim Cassette Type 19 Features 1 Features 1 1 Overview gt Compact design super slim body size less space requiring in installation gt Each louver can be separately controlled more comfort air blowing is possible gt Auto lifting panel design more convenient to clean and maintain the filter optional Leis cese New Sim Cassone 30K 60K 4 1 2 Fresh air intake function gt Fresh air fulfills air quality more healthy and comfortable gt Ventilation motor is optional to increase the effect of fresh air 20 Art Flux Super slim Cassette Type Features CA New air intake 1 3 Optional ionizer generator gt lonizer generator is optional to get refreshing air to your room lonizer generator Ventilation motor connector connector gt lonizer can be switched on or by remote controller When pressing the Clean Air button on the remote controller lonizer will work
72. ve problems and need to be replaced c NS 123456 Index2 1 DC fan motor control chip is inside fan motor Power on and when the unit is in standby measure the voltage of pin1 pin3 pin4 pin3 in fan motor connector If the value of the voltage is not in the range showing in below table the PCB must have problems and need to be replaced DC motor voltage input and output NO Color Sigma Voltage _ i Red i439 2 4 Ww 4 Ve 135265 s Be 6 90 Electrical Control Troubleshooting For the super slim cassette with up down panel a Communication error between indoor unit and up down panel b Up down panel is defective or F1 Displayed Communication failure between indoor unit and up down panel Or up down panel is defective the wire connection between up down panel and indoor unit is it right Correct the No connection Yes emove the up down panel ano repower the indoor unit Connect a display board and turn on it can it start The indoo
73. wire controller will show TIME ON at the same time the time zone will display the last setting time which flash at the frequency of 1Hz the wire control enters to Timing ON status 2 By using Yto set the desired Timing ON time In case originally provide with timing set in the system please press the CANCEL button to cancel the current settings 3 After 0 5 seconds of done the setting the wire controller will deliver the Timing ON information 2 seconds later the Timing ON information will stop flashing Timing ON has been set 4 2 Set Timing ON and OFF 1 Press the TIMER button the LCD in the wire controller will show TIME ON at the same time the time zone will display the last setting time which flash at the frequency of 1Hz the wire control enters to Timing ON status 2 By using and Y to set the desired Timing ON time 3 Press the TIMER button again the LCD in the wire controller will show TIME OFF at the same time the time zone will display the last setting time which flash at the frequency of 1Hz the wire control enters to Timing OFF status In case originally provide with timing set in the system please press the CANCEL button to cancel the current settings 4 By using Vto set the desired Timing OFF time 5 After 0 5 seconds of done the setting the wire controller will deliver the Timing OFF information 2 seconds later the Timing OFF information will stop flashing Timing
74. wise electric leakage or heating may occur and result in fire The specified cables shall be applied in the wiring No external force may be applied to the terminal Otherwise wire cut and heating may occur and result in fire Electrical Control 101 Controller 3 2 2 Installation accessory Select the installation location Don t install at the place where contents with heavy oil vapor or sulphurous gas otherwise this product would be deformed that would lead to system malfunction Preparation before installation 1 Please confirm that all the following parts you have been supply Wire controller a C ruciform sot screw 25 Thi accessory Weed when iretall the wire Plastic 2 contra ireide the cabina Installation and owners manual 1 The connective uires of receed panel Forconnect between the signal wire on some model and shielded Sore cable 2 Please filed install the following accessory 1 Electric cabinet iei pecto specification Shielded Score cable 1 Pre embed FsP 0 S5mm2x5 into wall con tube related 1 Preembed incl lorges no exceeding an l n JEN Philips serewdriver Ferinstall Crudform sbt sere Slotted head screwdtiver 1 Forunscrew the bottom cover of wire controller Precaution of install the wire control 1 This manual provides the installation method of wire contro

Download Pdf Manuals

image

Related Search

Related Contents

第7号(平成21年1月)【PDF:7.43MB】  電波時計 (掛時計) 取扱説明書  Téléchargez le manuel de directives    Biographie langagière  Voir - MADD Technologies Sàrl  PDF file - Primare  Turtle Beach PX51  車日本車両 - 日本車輌製造    

Copyright © All rights reserved.
Failed to retrieve file