Home
Operator-manual_ICH_ICHL
Contents
1. 4 2 Fill up and connect the water tank Water specifications For steam creation use only demineralised water aqua dem in accordance with VDE 0510 DIN EN 50272 regulations must be strictly adhered to production conductivity gt 5 lt 10 uS cm Battery water in accordance with VDE 0510 is available in larger chemist s shops super markets hardware stores and in the wholesale trade The standard VDE 0510 DIN EN 50272 has to be explicitly specified on the label Otherwise possible calcification in the steam generators steam piping and peristaltic pumps could affect the operability of the device The water used must have a pH value between 5 and 7 and be chlorine free D30381 Date 10 2014 21 Putting into operation Fill the supplied water tank with water and connect it with the enclosed tube to the H O connection on the rear of the chamber Fig 11 For appliances of size 750 the tank can be attached to the appliance with the included tank holder Fig 12 To do so hook the tank holder into the slots on the rear of the appliance For wall mounting the tank holder also has two drill holes fastening material not included in the delivery Fig 11 Water connection Fig 712 Tank holder 4 3 Switching on Switch on the appliance by pressing the On Off switch on the front of the appliance Fig 13 The starting process is shown by three an mated white dots LIG If the dots have another colour an
2. 6 Set the calibration value to 0 0 K and ac cept the setting by pressing the confirma Temperature Cat 10 0 rh tion key Cal2 60 0 rh Cal3 80 0 rh 7 Position the sensor of the calibrated refer ence instrument centrally in the appli ance s working chamber 8 Close the door and in manual mode i 2 9 5 rh adjust the set humidity to 60 rh Set Aven HUMIDITY 9 Wait until the appliance reaches the set humidity and displays 60 rh The refer HUMIDITY ence instrument should display 58 5 rh le 0 0 rh cas rh Set 60 0 rh 10 In the SETUP adjust the calibration value Cal2 to 1 5 actual value measured Temperature Cal1 10 0 rh 0 5 minus setpoint humidity and save the 6 cal 60 0 n E setting by pressing the confirmation key Cal3 80 0 rh 1 0 11 After the calibration procedure the hu midity measured by the reference instru HUMIDITY ment should now also be 60 rh 6 0 O rh Set 60 0 rh 52 D30381 Date 10 2014 memmen Menu mode 7 6 Program In the PROG display programmes created using the AtmoCONTROL software can be trans ferred to the appliance and saved on a USB storage medium Here programme to be used in manual mode can also be selected see page 31 and programmes can be deleted To load a programme from a USB stor age medium Connect the USB storage medium with the saved programme s to the interface on the right side of the control panel 1 A
3. If the appliance is first to be stored after delivery Read the storage conditions from page 61 18 D30381 Date 10 2014 MEMMeEr Delivery transport and setting up 3 6 Setting up A 3 6 1 Preconditions The installation site must be flat and horizontal and must be able to reliably bear the weight of the appliance see Technical data on page 14 Do not place the appliance on a flamma ble surface Depending on the model see nameplate a 230 V or 115 V power connection must be avail able at the installation site The distance between the wall and the rear of the appliance must be at least 15 cm The clear ance from the ceiling must not be less than 20 cm and the side clearance from walls or nearby appliances must not be less than 5 cm Fig 9 Sufficient air circulation in the vicinity of the appliance must be guaranteed at all times Do not put anything in front of the fan opening of the cooling unit at the appliance front For appliances with castors these need to be positioned in forward direction at all times Warning Due to its centre of gravity the appliance can fall over to the front and injure you or other people Always attach the appliance to a wall with the tilt protection see page 20 In case there is not enough space do not put the appliance into operation and do not open the door Contact the Memmert service see page 2 The appliance may only be installed on the floor Fig 9 Minimum clearance
4. End Bu Test 012 30 D30381 Date 10 2014 memmert Operation and control You can now gt restart the programme as described select another programme for processing in menu mode see page 53 and run it as described return to manual mode To do so reactivate it by pressing the activation key next to the status display then turn the turn a aie RNC control until the hand symbol W is highlighted in colour and Manual Mode press the confirmation key 5 5 Monitoring function 5 5 1 Temperature monitoring The appliance is equipped with a multiple overtemperature protection in accordance with DIN 12 880 This serves to avoid damage to the chamber load and or appliance in case of a malfunction electronic temperature monitoring TWW gt automatic temperature monitor ASF gt mechanical temperature limiter TB The monitoring temperature of the electronic temperature monitoring is measured via a separate Pt100 tem ear pets bet perature sensor in the interior Temperature monitoring settings 36 5 C 38 5 C are made via the ALARM display The settings made apply to all En operating modes OMOR t 2 0K If temperature monitoring has been trig gered this is indicated by the temperature display the actual temperature is high lighted in red and a warning symbol is shown Fig 17 The type of temperature monitoring triggered TWW in this exam ple is shown beneath the temperature If the acoustic
5. firmed by pressing the confirmation key before cancelling the setting procedure are accepted 2 With the turn control select the desired new setting e g Espanol Spanish a vV FRANCAIS Hie 3 Save the setting by pressing the confir mation key ENGLISH DEUTSCH FRANCAIS 4 To return to the menu overview press the activation key again You can now gt activate another menu function by press ing the corresponding activation key or gt return to manual mode by pressing the MENU key D30381 Date 10 2014 43 Menu mode memmert All other settings can be made accordingly The settings possible are described in the follow ing sections If no new values are entered or confirmed for approx 30 seconds the appliance automati 1 cally returns to the main menu and restores the former values 7 3 Setup 7 3 1 Overview In the SETUP display you can set the following parameters the IP address and Subnet mask of the appliance s Ethernet interface for connection to a network the Unit of the temperature display C or F see page 45 how the digital backwards counter with target time setting works Timer mode see page 46 the type of the slide in unit grid or shelf see page 46 the defrosting system Defrost see page 46 Remote control see page 40 Gateway see page 40 If the Setup menu contains more entries than can be i displayed this is indicated by the display 1 2
6. memmert For your Safety 1 8 Behaviour in case of malfunctions and irregularities The appliance may only be used in a flawless condition If you as the operator notice irregu larities malfunctions or damage immediately take the appliance out of service and inform your superior J You can find information on eliminating malfunctions from page 38 1 9 Switching off the appliance in an Emergency Press the main switch at the ControlCOCKPIT Fig 2 and disconnect the power plug This disconnects the appliance from the power sup ply at all poles Fig 2 Switch off the appliance by pressing the main switch D30381 Date 10 2014 9 Construction and description 2 Construction and description 2 1 Construction Fig 3 Construction 1 ControlCOCKPIT with capacitive function 7 Nameplate see page 13 keys and LCD displays see page 25 8 Inner glass door 2 On Off switch see page 22 9 Illumination box with fluorescent tubes 3 Door handle only for model ICH L see page 59 4 Chamber fan 10 Turn control with confirmation key 5 Castors 6 Cooling unit see page 58 10 D30381 Date 10 2014 MEMMEr Construction and description 2 2 Construction and function The appliance can heat up the interior to up to 60 C and cool it down to 10 C without humidity and without light or 10 C with humidity A compressor is used for cooling Humidification of the interior is achieved by evaporating water from a tank at a
7. 3 Date and time display 4 Date and time setting activation key 5 Exit menu mode a return to operating mode 6 Setup activation key basic appliance set tings 7 Setup display basic appliance settings 8 Adjustment display 9 E activation key 10 Turn control for adjustment 42 PROTOCOL A USER ID 11 Confirmation key accepts setting made with the turn control 12 Programme setup activation key 13 Programme setup display 14 Protocol display 15 Protocol activation key 16 Acoustic signal ea activation key 17 Acoustic signal adjustment display 18 User ID display 19 User ID activation key D30381 Date 10 2014 memmen Menu mode 7 2 Basic operation in menu mode using the example of language selection In general all settings in menu mode are done just like in manual mode Activate the re spective display use the turn control for setting and press the confirmation key to accept the change A more detailed description is provided in the following using the example of language selection 1 Activate the desired parameter in this example the language To do so press the corresponding activation key on the er left or right of the respective display The FRANCAIS activated display is enlarged SEPANG If you want to exit or cancel your settings again press the activation key which you have used to activate the display The appliance returns to the menu overview Only the settings that you have con
8. Date 12 05 2012 on v Save the setting by pressing the 6 Time 12 00 confirmation key Time zone GMT 0 Daylight saving time and standard time are not changed automatically For this reason J please keep in mind to adjust them at the beginning of each period Time zone GMT 0 8 Now set date day month year and time hours minutes in the same way Accept the selection by pressing the confirma tion key Daylight savingsD X OR 48 D30381 Date 10 2014 memmert Menu mode 7 5 Calibration To guarantee perfect control we recommend to calibrate the appliance once a year 7 5 1 Temperature adjustment The appliances are temperature calibrated and adjusted at the factory In case readjustment should be necessary later on for example due to influence of the chamber load the ap pliance can be calibrated customer specifically using three calibration temperatures of your choice gt Call Temperature calibration at low temperature Cal2 Temperature calibration at medium temperature Cal3 Temperature calibration at high temperature 1 For temperature adjustment you will need a calibrated reference measuring device Fig 26 Schematic example of temperature adjustment Example Temperature deviation at 30 C should be corrected 1 Press the activation key to the right of the CALIB display The display is enlarged and the temperature adjustment option ae oe an is automatically highlighted cata 37 00 02
9. This means that there is a second page of entries 1 2 To display the hidden entries use the turn control to scroll beyond the lowest entry The page display changes to 2 2 evvvvy vv Subnet mask 255 255 0 0 7 3 2 IP address and subnet mask Unit OKRO If you want to operate one ore more appliances in a net work each appliance must have its own unique IP address for identification By default each appliance is delivered with the IP address 192 168 100 100 m 192 168 1 216 LAN 1 192 168 1 233 LAN 2 192 168 1 215 LAN 3 192 168 1 241 Fig 24 Operation of several appliances in a network schematic example 44 D30381 Date 10 2014 memmen Menu mode 1 Activate the SETUP display The entry IP address is automatically highlighted Subnet mask 255 255 0 0 Unit O C F Timer mode Or Slide in unit Grid Shelf 2 Accept the selection by pressing the con firmation key The first three digits of the IP address are automatically selected Subnet mask 255 255 0 0 Unit Orc F Timer mode or Or 3 With the turn control set the new num ber e g 255 Subnet mask 255 255 0 0 Unit O c Ola Timer mode or Or 4 Accept the selection by pressing the confirmation key The next three digits of the IP address are automatically selected Setting these is done according to the description above Subnet mask 255 255 0 0 Unit O C Ola Timer mode or 5 After setting the las
10. alarm has been activated in the menu mode Sound see page 54 indicated by the speaker symbol sf inthe Fig 17 o alarm display the alarm is additionally Temperature monitoring triggered signalled by an intermittent acoustic signal which can be turned off by pressing the confirmation key Information on what to do in this case is provided in the chapter Malfunctions warning and error messages from page 38 Before reading how to adjust temperature monitoring from page 33 please read the description of the individual monitoring functions here D30381 Date 10 2014 31 Operation and control memmerf Electronic temperature monitoring TWW The manually set monitoring temperature min and max of the overtemperature control is monitored by an adjustable over undertemperature controller TWW protection class 3 3 acc to DIN 12 880 If the manually set monitoring temperature Max is exceeded the TWW takes over temperature control and begins to regulate the monitoring temperature Fig 18 A Emergency operation Setting MAX Set temperature Controller error Fig 18 Schematic diagram of how TWW temperature monitoring works 32 D30381 Date 10 2014 memmert Operation and control Automatic temperature monitor ASF ASF is a monitoring device that automatically follows the set temperature setpoint within an adjustable tolerance band Fig 19 The ASF if switched on is automatically activated as soon as the actual
11. error has occurred see page 41 After the first start up the appliance display is set to J English by default You can change the language as X described from page 43 However to get a basic ca overview of operating the appliance you should read the following chapter first Fig 13 Switching on the ap pliance 22 D30381 Date 10 2014 memmert Operation and control 5 Operation and control A Caution When in operation small amounts of condensed water may leak from the appliance Always wear shoes with slip proof soles and wipe up the condensed water immediately Warning UV light is a danger to your eyes Your eyes could be injured by UV light if you do not wear protection Always wear UV safety goggles when opening the door of the ICH L climate chamber This is indicated by the warning signs on the door see page 7 Caution The surfaces in the appliance s interior and the chamber load may be very cold Always wear gloves when you touch the interior of the appliance 5 1 Operating personnel The appliance may only be operated by persons who are of legal age and have been instruct ed accordingly Personnel who are to be trained instructed or who are undergoing general training may only work with the appliance under the continuous supervision of an experi enced person 5 2 Opening the door To open the door pull the door handle to the side to the left or to the right depending on the door
12. from walls and ceiling D30381 Date 10 2014 19 Delivery transport and setting up MEMMErT F 3 6 2 Tilt protection Attach the appliance to a wall with the tilt protection The tilt protection is included in the delivery 1 20 Screw the tilt protection as shown onto the back of the appliance Bend the tilt protec tion upwards by 90 in the desired distance to the wall consider the minimum distance to the wall see Fig 9 Drill a hole insert a plug and screw the tilt protec tion to a suitable wall D30381 Date 10 2014 memmerf Putting into operation 4 Putting into operation Caution J The first time the appliance is operated it must not be left unattended until it has reached the steady state 4 1 Connecting the appliance Caution J Observe the country specific regulations when mak ing connections e g in Germany DIN VDE 0100 with residual current circuit breaker Observe the connec tion and power ratings see nameplate and Technical Data on page 14 Make sure to establish a safe PE conductor connection Zu Plug the provided power cable into the rear of the appli i he 5 a sg p n iee ance and connect it to the power supply Fig 10 PP Lay the power cable so that it is always accessible and within reach so it can be disconnected quickly in the event of failure or emergencies gt no one can trip over it it does not come into contact with any hot parts
13. of the appliance with caustic or solvent based cleaning agents 8 1 3 Glass surfaces Glass surfaces can be cleaned with a commercially available glass cleaner D30381 Date 10 2014 5 Maintenance and Servicing memmerf 8 1 4 Cooling unit In order to guarantee perfect function and a long lifetime of the refrigeration unit it is abso lutely essential to remove dust deposits from the condenser with a vacuum cleaner paint brush or bottle brush depending on the amount of dust To do so open the screws at the lower front cover number varies depending on the appliance size and remove the front cover Fig 29 Fig 29 Unscrew and remove the front cover 8 1 5 Peltier dehumidification modules In order to guarantee perfect function and a long lifetime of the Peltier dehumidification modules it is abso lutely essential to remove dust deposits from the heat sink on the rear side of the appliance with a vacuum cleaner paintbrush or bottle brush depending on the amount of dust Fig 30 Fig 30 Peltier cooling modules at the rear side of the appliance 58 D30381 Date 10 2014 memmerf Maintenance and Servicing 8 2 Repairs and Service gt Warning OD After removing covers live parts may be exposed You may receive an electric shock if you touch these parts Disconnect the mains plug before removing any covers Any work inside the appliance may only be performed by qualified electri cians Repairs and se
14. operates as follows In manual mode After power supply has been restored operation is continued with the parameters set The time and duration of the power failure are documented in the log memory In timer or programme mode In case of an interruption of the power supply of less than 60 minutes the current pro gramme is continued from the point at which it was interrupted For longer interruptions of the power supply all appliance functions heating fan etc are switched off In remote control mode The previous values are restored If a programme has been initiated via remote control it is continued D30381 Date 10 2014 41 Menu mode 7 Menu mode memmert In menu mode you can make basic settings load programmes and export protocols as well as adjust appliance parameters Caution J Before changing menu settings read the description of the respective functions on the fol lowing pages to avoid possible damage to the appliance and or chamber load To enter menu mode press the MENU key To exit the menu mode at any time press the MENU key again The appliance then returns to manual mode Only changes accepted by pressing the confirmation key are saved 7 1 Overview Press the MENU key to change between the displays in menu mode 1 2 3 LANGUAGE N TIME f As i SETUP ControICOCKPIT in menu mode Fig 23 1 Language selection activation key 2 Language selection display
15. to normal and the 3 appliance begins adjusting to the defined 2 C set value Set 37 0 C Additional parameters can be set accordingly If no new values are entered or confirmed for approx 30 seconds the appliance automati J cally restores the former values If you want to cancel the setting procedure press the activation key on the left or right of the display that you want to exit The appliance restores the former values Only the settings that you have confirmed by pressing the confirmation key before cancelling the setting procedure are accepted 5 4 3 Operating modes The appliance can be operated in different modes gt Manual mode The appliance runs in permanent operation at the values set on the Con trolCOCKPIT Operation in this mode is described in chapter 5 4 4 gt Operation with digital backwards counter with target time setting adjustable from 1 minute to 99 days Timer The appliance runs at the values set until the timer has elapsed Operation in this mode is described in chapter gt Programme mode The appliance automatically runs programme sequences which have been defined using AtmoCONTROL software at a computer laptop and then transferred to the appliance from a USB stick or via Ethernet Operation in this mode is described in chapter 5 5 gt via remote control The status display shows you which operating mode or operating state the appliance is currently in The current operating s
16. 014 memmert 5 6 2 Humidity profile 1 Activate graphic representa tion as described above and then press the activation key next to the parameter selec tion 2 Select humidity with the turn control 3 Press the confirmation key to confirm The humidity profile is displayed You can change the display range as described above as well as extend or reduce it 5 7 Ending operation 1 Switch off active appliance functions turn back the set values 2 Remove the chamber load 3 Check the freshwater tank and fill up if necessary see page 21 4 Switch off appliance Fig 22 D30381 Date 10 2014 Operation and control 12 09 2012 12 09 2012 12 09 2012 RER Fig 22 Switching off the appliance 37 Malfunctions warning and error messages mMEMMEr 6 Malfunctions warning and error messages Warning After removing covers live parts may be exposed You may receive an electric shock if you touch these parts Malfunctions requiring work inside the appliance may only be rectified by electricians Ob serve the separate service manual for this Do not try to rectify appliance errors yourself but contact the MEMMERT customer service department see page 2 or an authorised service point In case of enquiries please always specify the model and appliance number on the nameplate see page 13 6 1 Warning messages of the monitoring function Ifthe acoustic alarm has been activated in
17. 26 A2 2003 Directive 2006 42 EC Directive of the European Parliament and Council dated May 17 2006 on machinery and amending directive 95 16 EC revised Standards complied with DIN EN ISO 12100 1 2003 DIN EN ISO 12100 2 2003 EN ISO 14121 1 2007 EN ISO 14121 2 2007 2 9 Declaration of conformity You can download the EC declaration of conformity of the appliance online English http Awww memmert com en service downloads ce statement German http www memmert com de service downloads eg konformitaetserklaerung D30381 Date 10 2014 15 Construction and description memmert 2 10 Ambient conditions The appliance may only be used in enclosed areas and under the following ambient condi tions 15 C to 28 C to 34 C with limited temperature Ambient temperature and humidity range Humidity rh max 70 non condensing Overvoltage category II Pollution degree 2 Altitude of installation max 2 000 m above sea level The appliance may not be used in areas where there is a risk of explosion The ambient air must not contain any explosive dusts gases vapours or gas air mixtures The appliance is not explosion proof gt Heavy dust production or aggressive vapours in the vicinity of the appliance could lead to sedimentation in the interior and as a consequence could result in short circuits or dam age to electrical parts For this reason sufficient measures to prevent large clouds of dust or aggressive vapours fr
18. 381 Date 10 2014 memmen Menu mode If humidity room temperature are particularly high it is possible that the factory setting for defrosting 12 hours is not sufficient If this is the case you should set a more frequent de frosting interval e g every 6 hours Automatic defrosting is disabled with the setting Off When operating at low temperatures this over time causes the cooling unit to ice over Regular defrosting needs to be carried out in order to prevent damage to the cooling system 7 3 7 Remote control In the setup entry Remote control you can set whether the appliance should be controlled via remote control and if so in which mode These settings are available ae Off Gateway 192 168 5 1 gt Read Only Write Write Alarm When the appliance is in remote control mode the symbol appears in the temperature display In the settings Write and Write Alarm the appliance cannot be controlled at the ControlCOCKPIT until the remote control has been switched off setting Off or set to Read Only A In order to use the remote control function program 2 3 AAG ming skills and special libraries are required Set 180 0 C TEMP 33 7 3 8 Gateway The setup entry Gateway is used to connect two networks with different protocols The gateway is set the same way as the IP address see page 44 7 4 Date and Time In the Time display you can set date and time time zone and daylight saving
19. CONTROL soft ware to the appliance and read out protocols The Ethernet interface is located on the rear of the appliance Fig 5 For identification purposes each appliance con nected must have its own unique IP address Setting the IP address is described on page 44 Fig 5 Ethernet interface You will find a description of how to transfer programmes via Ethernet in the en BA closed AtmoCONTROL manual With an optional USB to Ethernet converter the appliance can be directly connected to a com puter laptop see Optional accessories on page 16 12 D30381 Date 10 2014 MEMMERr Construction and description 2 6 Designation nameplate The nameplate Fig 6 provides information about the appliance model manufacturer and technical data It is attached to the front of the appliance on the right behind the door see page 10 E Typ ICH 260 F Nr 230 V 5 9 A 50 60 Hz 1350 W 4 g DIN12880 K1 3 3 Nenntemp 10 60 C qJ Schutzart DIN EN 60529 IP 20 P GmbH Co KG D 91126 Schwabach FRG Tel 49 0 91 22 92 50 Made in Germany S 5 Fig 6 Nameplate example 1 Type designation 6 Address of manufacturer 2 Operating voltage 7 Disposal note 3 Applicable standard 8 Temperature range 4 Protection type 9 Connection power ratings 5 CE conformity 10 Appliance number D30381 Date 10 2014 13 Construction and description 2 7 Technical data Appliance width D mm Appliance h
20. E TORA 24 5 4 Operating the appliance ccccsssccceesssssseeeeecsssnseeecesssseeeeeeeesseeaeeeeeesssaeeeeesessenseeeeesssenaes 24 5 3 Monitoring TAn UON esse nenn 31 20 AD ee re ee 36 57 Ending operate een ee 37 4 D30381 Date 10 2014 memmert 6 Malfunctions warning and error messages 6 1 Warning messages of the monitoring FUNCTION c ccceesseeesssteeeessseeeeseeees 6 2 Malfunctions operating problems and appliance errors cccceeeeesseeeeees 6 3 Power failure een 7 Menu mode EL OVEMIEW nn ee re ee 7 2 Basic operation in menu mode using the example of language selection Ds UD tas EEE E IE EEREECERCRSERER 14 Dateand N eee ner ee ne ee 75 211 0 Eeen nee ee 7 0 PROC AN 7 S N 7 3 PV ONOGON ee A A 19 NIS DD e E ee ee eee 8 Maintenance and Servicing 3 1 CCNA NINO erento 8 2 Repairs And SONNCG nannte 9 Storage and disposal I DIOTIGE east ep inneren eier ee rien 92 DPO rer ee ee Index D30381 Date 10 2014 Contents For your Safety memmerf 1 For your Safety 1 1 Terms and signs used In this manual and on the appliance itself certain common terms and signs are used to warn you of possible dangers or to give you hints that are important in avoiding injury or damage Observe and follow these hints and regulations to avoid accidents and damage These terms and signs are explained below 1 1 1 Terms used Warning is used whenever you or somebody else could be inj
21. ID 7 9 1 Description With the User ID function you can lock the settings of individual e g temperature or all parameters so that they cannot be changed at the appliance by accident or unauthorised persons You can also lock setting options in menu mode e g adjustment or date and time settings this way If adjustment options are locked this is indicated by the lock symbol in the respective display Fig 28 User ID data are entered in the AtmoCONTROL soft ware and saved on the USB storage medium The USB storage medium is thus acting as a key Parameters can only be locked or unlocked if it is connected Fig 28 Temperature adjustment li lock AtmoCONTROL is provided in the separate at appliance locked example ah A description of how to create a user ID in AtmoCONTROL manual 7 9 2 User ID activation and deactivation 1 Connect the USB storage medium with the user ID data to the interface on the right side of the control panel 2 Activate the user ID To do so press the USERID activation key on the right side of the User ID display The display is enlarged and the entry Activate automatically highlighted Deactivate 3 Confirm the activation by pressing the confirmation key The new user ID data are transferred from the USB storage medium and activated As soon as activa tion is complete a check mark appears in front of the corresponding entry 4 Remove the USB storage medium Locked parameter
22. ace any of the chamber load on the floor touching the side walls or right below the ceiling of the chamber Fig 15 see also the correct loading sticker on the appli ance In case of improper loading chamber loaded too tightly the set temperature may Fig 15 Correct placement of the chamber load be exceeded or it may take longer until it is reached To achieve the correct heating capacity the type of drawer used Grid or Shelf must be J setin the menu under SETUP see page 54 5 4 Operating the appliance 5 4 1 ControlCOCKPIT In manual operation the desired parameters are entered at the ControlCOCKPIT on the front of the appliance Fig 16 You can also make basic settings here menu mode Additionally warning messages are displayed e g if the temperature is exceeded In programme mode the parameters defined the programme description the programme segment currently active and programme duration remaining are displayed for a more detailed description see page 31 24 D30381 Date 10 2014 memmert Operation and control n 13 30 B 11 Set 30 rh 0 04 30 30m Fig 16 depending on appliance size 1 Activation key for temperature setpoint adjustment Setpoint and actual temperature display Fan speed display Activation key for fan speed setting Switch to menu mode see page 42 Interior lighting activation key only for mode
23. adjust the desired tolerance band e g 2 0 K 1 We recommend a tolerance band of 1 to 3 K 34 D30381 Date 10 2014 memmert Operation and control 10 Press the confirmation key to confirm Temperature monitoring is now active ALARM min max 36 5 C 38 5 c auto OOL t 2 0K 5 5 2 Humidity monitoring If humidity monitoring has been triggered this is indicated by the humidity display the actual humidity is highlighted in red and a warning symbol A is shown Fig 21 If the acoustic alarm has been activated in the Sound menu see page 54 which is indicated by the speaker symbol s the alarm is additionally signalled by an intermittent acoustic signal Information on what to do in this caseare Fig 21 provided in the chapter Malfunctions Humidity monitoring triggered warning and error messages on page 38 Adjusting humidity monitoring 1 Press the activation key to the left of the ALARM display The temperature moni toring setting is automatically activated HUMIDITY A rh Set 70 0 rh 2 Turn the turn control until the humidity monitoring entry is highlighted OEN Tai 40 0 rh min 20 0 rh 3 Accept the selection by pressing the con firmation key The lower humidity alarm a Rn limit is automatically highlighted L0 0 rh 4 By turning the turn control adjust the desired lower alarm limit in the example ei ae on the right 50 rh 40 0 rh D30381 Date 10 2014 35 Oper
24. alibration values are set to 0 0 K the factory calibration settings are restored 50 D30381 Date 10 2014 memmen Menu mode 7 5 2 Humidity calibration Humidity control can be adjusted according to customer requirements by means of three freely selectable balance points For each selected calibration point a positive or negative compensation correction value between 10 and 10 can be set Fig 27 1 For humidity adjustment you will need a calibrated reference measuring device rh 50 Fig 27 Humidity adjustment example Example Humidity deviation at 60 should be corrected 1 Press the activation key to the right of the CALIB display The display is enlarged and the temperature adjustment option a ese ae ca is automatically highlighted cat 37 00 0 2x Calibration Last updated 12 10 2012 12 00 00 2 Turn the turn control until Humidity is highlighted Temperature Cal1 10 0 rn 0 Cal2 50 0 rh Cal3 80 0 rh 3 Press the confirmation key repeatedly until the calibration point Cal2 is selected Temperature cat 10 0 mh 0 Cal2 Cal3 4 With the turn control set the calibration point Cal2 to 60 rh Temperature cal 10 0 rh 0 07 1 74 rh Cal3 80 0 rh D30381 Date 10 2014 51 Menu mode memmert 5 Save the setting by pressing the confir mation key The corresponding calibra Temperature cal 10 0 rh tion value is automatically highlighted Cal2 60 0 rh Cal3 80 0 rh
25. and seriously injure you Never tilt the appliance and transport it in upright position and without load only except for standard accessories such as steel grids or shelves Appliances with castors always have to be moved by two people DO D30381 Date 10 2014 17 Delivery transport and setting up mMEMMEr 3 2 Delivery The appliance is packed in cardboard and is delivered on a wooden palette 3 3 Transport The appliance can be transported in three ways With a forklift truck move the forks of the truck entirely under the pallet Ona manual pallet jack gt On its own castors in case of the corresponding configuration for which the catch on the front castors must be released 3 4 Unpacking u To avoid damage do not unpack the appliance until you reach the installation site 1 Remove the cardboard packaging by pulling it upwards or carefully cutting along an edge 3 4 1 Checking for completeness and transport damage Check the delivery note to ensure that the delivery is complete Check the appliance for damage If you notice deviations from the delivery note damage or irregularities do not put the appli ance into operation but inform the haulage company and the manufacturer 3 4 2 Disposing of packaging material Dispose of the packaging material cardboard wood foil in accordance with the applicable disposal regulations for the respective material in your country 3 5 Storage after delivery
26. asurement function Temperature monitoring sensor defective The oper ating sensor takes over the measurement function Operating and monitoring sensor defective Check the power supply page 21 Contact customer service page 2 Unlock with USER ID page 56 Wait until the end of the programme or timer mode or switch off the remote control Change to operating or menu mode by pressing the MENU key gt The appliance can be temporarily operated gt Contact customer service aS SOON as possible page 2 The appliance can temporarily be kept in service gt Contact customer service as SOON as possible page 2 Switch off appli ance gt Remove the cham ber load Contact customer service page 2 D30381 Date 10 2014 MEMMeEr Malfunctions warning and error messages Error message E 6 in Humidity sensor defective No humidity con the humidity display trol possible gt Contact customer page 2 HUMIDITY asui A rh Set 50 0 rh When switching on gt Cyan GS Contact customer page 2 the appliance the start Not enough storage service animation is displayed space on the SD card in another colour than gt Red GG Contact customer page 2 white CO The system files could service not be loaded gt Orange EGE The Download the firm fonts and images could Ware update at mem not be loaded mert com and install it 6 3 Power failure In case of a power failure the appliance
27. ation 49 Temperature limiter 33 Temperature monitor 31 33 Temperature monitoring 31 Temperature profile 36 Temperature sensor 31 Tilt protection 20 Time 46 Timer 28 Timer mode 46 Transport 17 18 Transport damage 18 Turn control 25 27 28 D30381 Date 10 2014 Index TWW 32 TWW temperature monitor Ing 32 U Unit 45 Unpacking 18 USB interface 12 55 User ID 56 UV light 7 23 28 59 UV safety goggles 7 23 59 Ww Warning messages 12 38 Water specifications 21 Water tank 21 Weight 14 What to do in case of ac cidents 9 63 memmert Experts in Thermostatics Climate chamber ICH D30381 Date 10 2014 englisch Memmert GmbH Co KG Willi Memmert Stra e 90 96 D 91186 B chenbach Tel 49 9122 925 0 Fax 49 9122 14585 E Mail sales memmert com facebook com memmert family Die Experten Plattform www atmosafe net
28. ation and control 5 Accept the selection by pressing the con firmation key The upper humidity alarm limit is automatically highlighted By turning the turn control adjust the desired upper alarm limit in the example on the right 70 rh Accept the selection by pressing the confirmation key and leave the Alarm display by pressing the activation key on the side Humidity monitoring is now active 5 6 Graph The GRAPH display provides an overview of the chronological sequence of the set values and the actual values as a curve 5 6 1 Temperature profile 1 Press the activation key to the right of the GRAPH display The display is enlarged and the temperature profile shown To change the time frame to be displayed Press the activa tion key next to the lt ID ar row symbols The time frame to be displayed can now be changed by turning the turn control To extend or reduce the time frame to be displayed Press the activation key next to the magnifying glass symbol With the turn control select if you want to zoom in or out and confirm your selec tion by pressing the confirma tion key 12 09 2012 16 00 12 09 2012 memmert ALARM d max rh min 150 0 rh ALARM a D max rh min 50 0 rh ALARM d max 70 0 rh min S0 0 rh To close the graphical representation again press the activation key which you have used to activate It 36 D30381 Date 10 2
29. by the L symbol in the timer display When the timer has elapsed the display shows 00h 00m All func tions heating etc are switched off In addition an acoustic alarm ee sounds which can be turned off by pressing the confirmation key 0 0 70 0 h a m End 13 30 23 11 To deactivate the timer open the timer display by pressing the activation key again and then turning the turn control to reduce LZ the timer setting until is displayed Confirm with the confirma tion key End 9 00 23 11 5 4 6 Programme mode In this operating mode programmes saved in the appliance can be started with different combinations of individual parameters temperature humidity interior lighting at staggered intervals which the appliance then automatically processes in sequence These programmes are not created directly at the appliance but externally at a computer laptop and using AtmoCONTROL software Transfer to the appliance is possible using the provided USB storage medium or via Ethernet A description of how to create and save programmes can be found in the separate AtmoCONTROL software manual Starting a programme 1 Press the activation key to the right of the status display The current operating BEE mode is highlighted automatically in this L Activate example manual mode W D30381 Date 10 2014 29 Operation and control memmerf 2 Turn the turn control until the gt start symbol is highlighte
30. cools down 2 Reset the TB To do so press the red button on the right of the appliance rear side until a clicking sound can be heard If the alarm continues Contact page 2 customer service Fill the water tank with dem ineralised distilled water and press the confirmation key page 21 Open the door for 30 sec and wait to see if the appliance reliably adjusts to the setpoint If the error occurs again con tact customer service page 2 Check if the door is closed Check the water supply and the filling level of the water tank If required refill the water tank If the error occurs again con tact customer service page 21 page 2 39 Malfunctions warning and error messages memmert 6 2 Malfunctions operating problems and appliance errors Displays are dark Displays cannot be activated Displays suddenly look different Display T E 3 in the temperature display Set 37 0 c Error message Al E 3 in the temperature display AN Error message E 3 in the temperature display C Set 37 0 c C Set 45 0 c AN 40 External power supply was interrupted Miniature fuse appliance fuse or power module faulty Appliance locked by USER ID The appliance is in pro gramme timer or remote control mode mode Write or Write Alarm Appliance is in wrong mode Temperature operating sen sor defective The monitor ing sensor takes over the me
31. ctivate the programme display To do so press the activation key on the left side of the PROG display The display is enlarged Program and the entry Select automatically Zee highlighted The programmes available Test 015 for activation are shown on the right The 77 Test 016 programme currently available for use u in this example Test 012 is highlighted IN orange 2 Call the Select function by pressing the confirmation key All programmes available are displayed including the ones saved on the USB storage medium identified by the USB symbol The programme currently available for use is highlighted in orange 3 With the turn control select the pro gramme you want to make available for use Delete Test 022 Test 013 Test 014 Delete Test 022 Test 013 Test 014 lt Test 022 4 Accept the selection by pressing the confirmation key The programme is now loaded which is indicated by the transfer mines le s mbol Test 013 y Test 014 5 As soon as the programme is ready the T 012 selection returns to Select To start the Dane Se 022 programme As described on page 31 Test 013 return to manual mode by pressing the Test 014 MENU key Test 015 You can now remove the USB storage medium To delete a programme select Delete with the turn control and select the programme to be deleted the same way you can select a programme for activation D30381 Date 10 2014 53 Menu mode memmer
32. d The current programme is displayed in this example Test 012 gt ready 12 Sept 2012 10 44 Ma Test 012 Only the programme currently selected in the menu and shown in the display can be used If you want to process another programme you need to activate it in the menu first description from page 53 Hie 3 To start the programme press the confir 12 Sept 2012 10 44 mation key The programme starts The display shows the programme description in this exam ple Test 012 gt the programme segment description in gt _ Test 012 L gt Ramp 1 this example Ramp 1 the current run in case of loops You cannot change any parameters e g the temperature at the appliance while a J programme is running However the displays ALARM and GRAPH can still be used Cancelling a programme You can cancel an active programme at any time 12 Sept 2012 10 44 Mu Test 012 1 Press the activation key to the right of gt Ramp 3 the status display The status display is automatically highlighted 2 Turn the turn control until the W stop 12 Sept 2012 10 48 symbol is highlighted Cancel program Bu Test 012 3 Press the confirmation key to confirm The programme is cancelled 12 Sept 2012 10 49 End A cancelled programme cannot be Ma Test 012 resumed at the point it was cancelled It must be restarted from the beginning End of programme The display shows End when the programme PAOA is finished
33. eating Resetting the mechanical temperature limiter permanently Adjusting temperature monitoring 1 Press the activation key to the left of the ALARM display The temperature moni L TT Aan 4 toring setting is automatically activated i i AO vOx 0 0K D30381 Date 10 2014 33 Operation and control memmerf 2 Save the selection by pressing the con firmation key The min setting under s EEE dj Rn temperature protection is automatically ec FAW tre activated ako n OMON 0 0K 3 By turning the turn control adjust the desired lower alarm limit value in the example on the right 35 5 C The lower alarm limit value cannot be set J higher than the top one If no undertem perature protection limit is required set the lowest temperature 4 Press the confirmation key to confirm The max display overtemperature protec tion is activated 5 By turning the turn control adjust the desired upper alarm limit value in the example on the right 38 5 C The monitoring temperature must be set sufficiently high above the maximum set temperature We recommend 1 to 3 K e 6 Accept the upper alarm limit value by pressing the confirmation key The setting of the automatic temperature monitor ASF is automatically activated auto 7 With the turn control select ON v or OFF X 8 Press the confirmation key to confirm The ASF tolerance band setting is acti vated 9 With the turn control
34. ed with a miniature fuse 100 mA 160 mA at 115 V 2 5 Connections and interfaces 2 5 1 Electrical connection This appliance is intended for operation on an electrical power system with a system imped ance Zna of a maximum of 0 292 ohm at the point of transfer service line The operator must ensure that the appliance is operated only on an electrical power system that meets these requirements If necessary you can ask your local energy supply company what the system impedance is Observe the country specific regulations when connecting e g in Germany DIN VDE 0100 with residual current circuit breaker D30381 Date 10 2014 11 Construction and description MEMMEr 2 5 2 Communication interfaces The communication interfaces are intended for appliances which meet the requirements of IEC 60950 1 USB interface The appliance is fitted by default with a USB interface in accordance with the USB specifica tion This way you can gt transfer software stored on a USB storage medium to the appliance see page 53 gt export protocol logs from the appliance to a USB storage medium see page 55 gt transfer user ID data stored on a USB stor 2 medium to the appliance see page Fig 4 Berka The USB port is located on the right side of the ControlCOCKPIT Fig 4 Ethernet interface Via Ethernet interface the appliance can be connected to a network so that you can transfer pro grammes created with the Atmo
35. eight E mm Appliance depth F without door handle mm Depth of door lock mm Chamber width A mm Chamber height B mm Chamber depth C mm Chamber volume litres Weight including packaging kg ICH ICHL 230 V 50 60 Hz 230 V 50 60 Hz with light 115 V 50 60 Hz 115 V 50 60 Hz with light max number of sliding shelves max load per sliding shelf kg Power W Current consumption A max load per appliance kg with humidity without humidity with light Setting temperature range C Working temperature range C Adjustment precision C Adjustment range humidity rh Adjustment precision humidity rh Light intensity Lux Illumination only ICH L Standard illuminant Spectral range 14 memmert 745 824 1224 1233 1552 1950 634 134 834 56 560 640 1040 480 800 1200 400 500 600 108 256 749 127 209 324 1350 1450 1530 5 9 6 3 6 7 11 8 12 6 13 3 5 9 14 30 150 200 10 to 60 C 10 to 60 C 0 to 60 C 10 to 60 C 0 1 10 to 80 1 approximately 6000 D65 6 500 K 315 to 400 nm 5 W m2 D30381 Date 10 2014 MEMMERT Construction and description Fig 7 Dimensions 2 8 Applied directives and standards Directive 2004 108 EC amended Directive of the council for harmonisation of the laws of the member states on electromagnetic compatibility Standards complied with DIN EN 61326 2004 05 EN 61326 1997 EN 61326 A1 1998 EN 61326 A2 2001 EN 613
36. el and carefully push out the glass plate Fig 34 Fig 34 Remove the side panel and push out the glass plate 6 Undo the screw connections on the sockets of the fluorescent tubes to be exchanged Fig 35 7 Carefully pull the fluorescent tubes out of the sockets and remove them 8 Insert the new fluorescent tubes and screw them tight Push the glass plate back on and screw the side panel tight 9 Put the illumination box back into the appliance Put in the plug and lock the bayonet catch by turning it right Fig 31 10 Check the function of the lighting Fig 35 Undo the screw connections 60 D30381 Date 10 2014 memmerf Storage and disposal 9 Storage and disposal 9 1 Storage The appliance may only be stored under the following conditions in adry and enclosed dust free room frost free disconnected from the power supply Before storage remove water tube and empty the water tank see page 22 9 2 Disposal This product is subject to the Directive 2002 96 EC on Waste Electrical and Electronic Equipment WEEE of the European Parliament and of the Council This appliance has been brought to market after August 13th 2005 in countries which have already integrated this directive into their national laws It may not be disposed of in normal household waste For disposal please contact your dealer or the manufacturer Any appliances that are infected infectious or contami nated with materia
37. ho are of legal age and have been instructed accordingly Personnel who are to be trained instructed or who are un dergoing general training may only work with the appliance under the continuous supervision of an experienced person Repairs may only be performed by qualified electricians The regulations in the separate service manual must be observed 1 5 Responsibility of the owner The owner of the appliance is responsible for the flawless condition of the appliance and for it being operated in ac cordance with its intended use see chapter 1 6 is responsible for ensuring that persons who are to operate or service the appliance are qualified to do this have been instructed accordingly and are familiar with the operating instructions at hand must know about the applicable guidelines requirements and operational safety regula tions and train staff accordingly is responsible for ensuring that unauthorised persons have no access to the appliance is responsible for ensuring that the maintenance plan is adhered to and that maintenance work is carried out properly see page 57 has to ensure that the appliance and its surroundings are kept clean and tidy for example through corresponding instructions and inspections is responsible for ensuring that personal protective clothing is worn by operating person nel e g work clothes safety shoes and UV safety goggles Y vV VY 7Y 1 6 Intended use Climate chambers ICH a
38. id 46 H Hazards 7 Hot air generator 11 Humidity 27 Humidity adjustment 51 Humidity monitoring 35 36 40 Humidity profile 36 Illumination box 11 59 60 Installation site 19 Intended use 8 Interfaces 11 Interior lighting 27 IP address 44 L Language selection 43 Light 27 Light display 27 Lighting 27 Loading the appliance 24 Log memory 41 55 Maintenance 57 Malfunctions 9 38 40 Manufacturer 2 memmert Material 11 Mechanical temperature monitoring 33 Menu 47 Minimum clearances 19 Monitoring function 31 Monitoring temperature 31 Nameplate 13 Network 12 44 O Operating 23 Operating modes 26 Operating personnel 8 23 Operating problems 40 Operation 23 P Packaging material 18 Parameter adjustment 25 Power failure 41 Power supply 55 Press of a key 54 Product safety 7 Programme 53 Programme mode 26 29 31 Protocol 55 Pt100 temperature sensor 31 Putting into operation 21 Rectifying errors 40 Replacing fluorescent tubes 59 S Safety goggles 7 23 59 Safety labels 7 Safety regulations 6 10 Service 59 Servicing 59 Setting parameters 43 Setting up 17 19 Setup 44 Shelf 46 Slide in unit 46 D30381 Date 10 2014 memmert Speaker symbol 31 35 38 Standards 15 Storage after delivery 18 Switching off 37 Switching on 22 T Tank holder 22 TB 33 Technical data 14 Temperature 27 Temperature adjustment 49 Temperature comparison 49 Temperature devi
39. k Calibration Last updated 12 10 2012 12 00 00 2 Press the confirmation key repeatedly until the calibration temperature Cal2 is i Cal 5 0c selected Cal2 C Cal3 37 0c D30381 Date 10 2014 49 Menu mode memmert 3 With the turn control set the calibration temperature Cal2 to 30 C 4 Save the setting by pressing the confir mation key The corresponding calibra tion value is automatically highlighted 5 Set the calibration value to 0 0 K and ac cept the setting by pressing the confirma tion key 6 Position the sensor of a calibrated refer ence instrument centrally in the appli ance s working chamber 7 Close the door and in manual mode adjust the set temperature to 30 C 8 Wait until the appliance reaches the set temperature and displays 30 C The ref TEMP erence instrument should display 31 6 C 3 0 0 C Set 30 0 C 9 In the SETUP adjust the calibration value xx Cal2 to 1 6 K actual value measured AS x 5 0c 0 2 minus setpoint temperature and save the 6 setting by pressing the confirmation key I 30 0c j 37 0c 0 2k 10 After the calibration procedure the temperature measured by the reference TEMP instrument should now also be 30 C 9 0 0 C Set 30 0 C With Cal1 a calibration temperature below Cal2 can be programmed accordingly and with Cal3 a temperature above The minimum difference between the Cal values is 10 K 1 If all c
40. l ICH L Display interior lighting only for model ICH L Appliance state and programme display Activation key for the appliance state 0 Activation key digital backwards counter with target time setting adjustable from 1 minute to 99 days N D UW AR GW NO 5 4 2 Basic operation ControICOCKPIT for ICH ICH L appliances in operating mode width may differ 11 On Off switch 12 Display digital backwards counter with target time setting adjustable from 1 min ute to 99 days 13 Humidity control display 14 Humidity control activation key 15 Turn control for setpoint adjustment 16 Confirmation key accepts setting made with the turn control 17 Activation key setting the temperature and humidity monitorin 18 Display temperature and humidity moni toring 19 Graphic representation 20 Activation key for graphic representation In general all settings are made according to the following pattern 1 Activate the desired parameter e g tem perature To do so press the correspond ing activation key on the left or right of the respective display The activated dis play is lined in colour the other displays are dimmed The set value is highlighted in colour 2 By turning the turn control to the left or right adjust the set value e g to 37 0 C D30381 Date 10 2014 25 Operation and control memmerf 3 Save the set value by pressing the confir mation key PERL 35 The display returns
41. ls hazardous to health are excluded from return Please also observe all other regulations applicable in this context Before disposing of the appliance please render the door locking mechanism unusable for example to prevent playing children from being locked inside the appliance Note for Germany The appliance may not be left at public or communal recycling or collection points D30381 Date 10 2014 61 Index Index A Accessories 16 Activation key 25 27 Alarm 31 33 35 38 Ambient conditions 16 Ambient temperature 16 Appliance error 40 ASF 31 33 AtmoCONTROL 3 12 16 26 29 53 55 56 Balance 46 Basic device settings 42 Basic settings 42 C Carrying 17 Cause of errors 40 Chamber load 24 Changes 8 Cleaning 57 Clock time 47 Communication interfaces 12 Compensation correction values 50 Connections 11 ControlCOCKPIT 24 25 Cooling unit 46 58 Customer service 2 D Daylight 27 Declaration of conformity 15 Defrost 46 Delete programme 53 Delivery 17 18 21 Digital backwards counter 28 Dimensions 15 Directives 15 Disposal 61 Door 23 Electrical connection 11 Electrical equipment 11 62 Electronic temperature moni toring 32 Emergency 9 Ending operation 37 End of programme 30 Error description 40 Error messages 38 Ethernet 12 Explosion protection 8 F Fanspeed 27 Fluorescent tubes 59 60 Forklift truck 18 Fresh water container 21 G Graph 36 Gr
42. ly perform work that is described in this manual If there is something you do not understand or certain information is missing ask your man ager or contact the manufacturer Do not do anything without authorisation Versions The appliances are available in different configurations and sizes If specific equipment fea tures or functions are available only for certain configurations this is indicated at the relevant points in this manual The functions described in this manual refer to the latest firmware version Due to individual configurations and sizes illustrations in this manual may be slightly different from the actual appearance Function and operation are identical Other documents that have to be observed gt For operation of the appliance with MEMMERT AtmoCONTROL observe the separate software manual For service and repair work see page 57 observe the separate service manual Storage and resale This instruction manual belongs with the appliance and should always be stored where persons working on the appliance have access to it It is the responsibility of the owner to ensure that persons who are working or will work on the appliance are informed as to the whereabouts of this instruction manual We recommend that it is always stored in a protected location close to the appliance Make sure that the instruction manual is not damaged by heat or humidity If the appliance is resold or transported and then set up again a
43. memmert Experts in Thermostatics d I bik PTET ET j F CLIMATE CHAMBER ICH ICH L 100 ATMOSAFE MADE IN GERMANY www memmert com www atmosafe net Manufacturer and customer service Memmert GmbH Co KG Willi Memmert Stra e 90 96 D 91186 B chenbach Deutschland Phone 49 0 9122 925 0 Fax 49 0 9122 14585 E mail sales memmert com Internet www memmert com Customer service Service hotline 49 0 9171 9792 911 Service fax 49 0 9171 9792 979 E mail service memmert com When contacting customer service always quote the product serial number on the nameplate see page 13 Shipping address for repairs Memmert GmbH Co KG Kundenservice Willi Memmert Str 90 96 DE 91186 BUchenbach Germany Please contact our customer service before sending appliances for repair or before returning equipment otherwise we have to refuse acceptance of the shipment 2014 MEMMERT GmbH Co KG Date 10 2014 We reserve the right to make changes memmen About this manual About this manual Purpose and target audience This manual describes the setup function transport operation and maintenance of climate chambers ICH and ICH L It is intended for use by trained personnel of the owner who have the task of operating and or maintaining the respective appliance If you are asked to work on the appliance read this manual carefully before starting Familiar ise yourself with the safety regulations On
44. nd ICH L are suitable for stability testing of pharmaceuticals cosmet ics food etc under long term stable ambient conditions Any other use could be dangerous In case of any doubts please contact the Memmert customer service The appliance is not explosion proof does not comply with the German workplace health amp safety regulation VBG 24 The appliance may only be loaded with materials and substances which cannot form any toxic or explosive vapours at the set temperature and which cannot explode burst or ignite The appliance may not be used for drying vaporising and branding paints or similar materi als the solvents of which could form an explosive mixture when combined with air If there is any doubt as to the composition of materials they must not be loaded into the appliance Potentially explosive gas air mixtures must not form neither in the working chamber nor in the direct vicinity of the appliance 1 7 Changes and conversions No unauthorised changes or alterations may be made to the appliance No parts may be added or inserted which have not been approved by the manufacturer Unauthorised changes or alterations result in the CE declaration of conformity losing its valid ity and the appliance may no longer be operated The manufacturer is not liable for any damage danger or injuries that result from unauthor ised changes or alterations or from non observance of the regulations in this manual 8 D30381 Date 10 2014
45. om developing should be taken 2 11 Scope of delivery gt Power cable Sliding grid load capacity 30 kg each gt Water tank with connection hose USB storage medium with software and AtmoCONTROL manual The operating instructions at hand Calibration certificate gt Separately packaged fastening material for wall mounting see page 20 Tank holder only for appliances of size 750 see page 22 2 12 Optional accessories gt USB to Ethernet converter Fig 8 Makes it possible to connect the Ethernet connection interface see page 12 to the USB port of a computer laptop gt Reinforced sliding steel grids with a load capacity of 60 kg each for appliance size 110 and larger Fig 8 Converter USB to Ethernet 16 D30381 Date 10 2014 mMEMME rt Delivery transport and setting up 3 Delivery transport and setting up 3 1 For your Safety Warning Because of the heavy weight of the appliance you could injure your self if you try to lift it For carrying appliances of size 110 at least 4 people are needed Appliances larger than that may not be carried but must be transported with a manual pallet jack or forklift truck 80 750 Warning You may get your hands or feet squashed when transport ing and installing the appliance Wear protective gloves and safety boots When grasping the bottom of the appliance grasp it only on the sides Warning The appliance could fall over
46. ot be switched off and is always active The measured data are stored in the appliance safe from manipulation If the power supply is interrupted the time of the power failure and voltage recovery are stored in the appliance You can export the protocol data for different periods to a USB storage medium via the USB interface or via Ethernet import them to the AtmoCONTROL software for graphical represen tation print out or storage 1 The log memory of the appliance is not modified or deleted by reading it out near Sr eee ay 1 Connect the USB storage medium to the interface on the right side of the control panel 2 Activate the protocol To do so press the activation key on the right side of Protocol L the PROTOCOL display The display is 3 enlarged and the period This Month au Kesum tomatically highlighted To select another logging period use the turn control 12 10 2012 12 00 3 Save your selection by pressing the confir mation key The transfer starts and a status symbol indicates the progress This Year Complete control range 4 As soon as the transfer is complete a check mark appears in front of the period selected The USB storage medium can This Year now be removed Complete control range For a description of how to import and process protocol data in AtmoCONTROL or BA read them out via Ethernet please observe the separate AtmoCONTROL manual D30381 Date 10 2014 55 Menu mode memmert 7 9 User
47. perating mode for this 1 Press the activation key to the left of the timer display The timer display is 4 activated Ende 9 00 23 11 2 Turn the turn control until the desired wi duration is displayed in this example 4 Je l hours 30 minutes The approximate end time is shown beneath in a smaller font End 13 30 23 11 Up to a duration of 23 hours 59 minutes the time is displayed in hh mm hours minutes J format For 24 hours and more the format dd hh days hours is used The maximum duration adjustable is 99 days 00 hours 28 D30381 Date 10 2014 memmert Operation and control 3 Press the confirmation key to confirm The display now shows the remaining time TIMER D 12 Sept 2012 13 44 in a large font and the approximate end time Ties achive in a smaller font beneath The status display 0 4 3 0 wi shows Timer active i Ende 13 30 23 11 4 Now as described under 5 4 4 set the individual values for temperature air flap position etc which you want the appliance to operate at The set values can be changed at any time during the timer The changes are effective immediately In Setup you can choose if the timer should run setpoint dependent or not This deter J mines whether the timer should not start until a tolerance band around the set tempera ture is reached or if it should start right after activation see page 46 If the timer runs setpoint dependent this is indicated
48. rior lighting only ICH L Adjustment range Daylight DL on 100 or off 0 UV light UV on 100 or off 0 Setting interior lighting 1 Activate light display To do so press the activation key on the left side of the light display The daylight entry DL is selected automatically 2 By turning the turn control to the left or right set the desired daylight value 0 off 100 on D30381 Date 10 2014 27 Operation and control memmerf 3 Save the setting by pressing the confir LICHT mation key The UV entry UV light is 100 gt DL UV automatically activated 4 By turning the turn control to the left or right set the desired UV light value 0 off 100 on LIGHT 100 DL UV 5 Save the setting by pressing the confir mation key LIGHT 100 DL A 100 UV As soon as the illumination boxes are active the refrigeration unit has to compensate the residual heat produced by the illumination boxes This means operation is only possible at limited temperature and humidity range We recommend a temperature of 25 C and a humidity of 50 RH at most Depending on the ambient conditions there may be some condensation in the chamber 5 4 5 Operation with digital backwards counter with target time setting adjustable from 1 minute to 99 days Timer In timer operation you can adjust the time the appliance runs at the set value The appliance has to be in manual o
49. rvice work are described in a separate service manual 8 2 1 Replacing fluorescent tubes only for model ICH L A gt Replace the fluorescent tubes only with fluorescent tubes of the same power and type e g UV light tubes only with UV light tubes not daylight tubes For information on the specifications please refer to chapter Technical data from page 14 Do not replace single tubes but always the entire tube set e g all UV light tubes instead of just one Replacing single tubes can influence the light output Warning UV light is a danger to your eyes Your eyes could be injured by UV light if you do not wear protection Please always wear UV safety goggles when testing the function of fluores cent tubes 1 Switch off the appliance and remove the mains plug 2 Loosen the connection of the illumination box in the interior To do so turn the bayonet catch to the left and pull off the plug Fig 31 3 Pull the illumination box out of the appliance on both handles Fig 32 Fig 31 Open the bayonet Fig 32 Pull out the illumination box catch and pull off the plug D30381 Date 10 2014 59 Maintenance and Servicing memmert 4 Turn the illumination box around and place it carefully on a smooth surface so that the fluorescent tubes are on top Fig 33 Undo the four screws on the side Fig 33 Put the illumination box on its rear side and undo the screws of the side panel 5 Remove the side pan
50. s are indicated by the lock symbol in the respective display Fig 28 To unlock the appliance connect the USB storage medium activate the User ID entry and select Deactivate Deactivate 56 D30381 Date 10 2014 ana Maintenance and Servicing Maintenance and Servicing Warning ore Danger rie to electric shock Before doing any maintenance work pull out the mains plug Warning NY In case of appliances of a certain size you can get accidentally ae locked in which is life threatening Do not climb into the appliance Caution Danger of cuts due to sharp edges Always wear gloves when work ing in the chamber interior To guarantee perfect control we recommend to calibrate the appliance once a year see page 49 8 1 Cleaning 8 1 1 Interior and metal surfaces Regular cleaning of the easy to clean interior prevents build up of material remains that could impair the appearance and functionality of the stainless steel chamber over time The metal surfaces of the appliance can be cleaned with normal stainless steel cleaning agents Make sure that no rusty objects come into contact with the interior or with the stain less steel housing Rust deposits can lead to an infection of the stainless steel If rust spots should appear on the surface of the interior due to impurities the affected area must be im mediately cleaned and polished 8 1 2 Plastic parts Do not clean the ControlCOCKPIT and other plastic parts
51. sccceccssssseeeeecesessseeeecesesaeeeeeesseeaeeeeeeeseeaeeeeeessssaeeeseesees 13 27 Technical Odessa 14 2 8 Applied directives and standards ccccccsscccccessseseeeccsseseeeeeessesseeeeeeseeseeeeessesssaeeeeeseas 15 29 Declaration of Chlor 15 2 10 Ambient conditions au er uc eeenee 16 2 11 Scope ol SUING ernennen 16 2 12 Optional accessories eeueensnnnnnnnnnnnnnnnnnennnnnnnnnnnnnnnnnnnnnnnnnnennnnennnnnennnnnennnnennnnnnnnnneennnnannnneennn 16 3 Delivery transport and setting up 17 321 TOP OU SAR ee ea ee ee 17 39 2 DEINE ee 18 i Yate AO enema ee Deere re 18 34 UNPa KNO peeeeee etree teeter een ee 18 3 5 Storage after delivery reunnnennensennnnnennnnnnnnnnennnnnnnnnnennnnennnnnnnnnnennnnnennnnennnnnnnnnneennnnannnneenann 18 3 6 SEEUNG UP zu er ee eer ee eee ee eee 19 4 Putting into operation 21 4 1 Connecting the appliance ccccceeesssssceceeeseeeeeeeeeeseneeeeeeecseeeseeeeseesneseeeesecseeeeeeeeesseenseeees 21 4 2 Fill up and connect the water tank ccccesesscccecceeeeeeeeessenaeeeeeeeesessseeeseeseeeeeeesesssseenaees 21 23 7SWILENING ONE ee ne ee EE AEEA ETE 22 5 Operation and control 23 5 1 Operating personnel uusssessessnnennnneennnnennnnnennnnnnnnnnennnnnnnnnnnennnnnnnnenennnnnnnnnensnnsnennnnnnnn nenn 23 5 2 Opening the COOL cccccccccccceccssssseseececeeeeeecsseecenaeeeeeeeeeeeesseeceaeeseeeeeessssseeseesesenenessaseeas 23 5 3 Loading the appliance un a snncen sa AARAA R
52. set rate by means of a hot air generator on the rear side of the appliance The sterile hot air is introduced into the interior above the fan and mixed with the air current Humidity is reduced through condensation using Peltier cooling modules on the rear side of the appliance Ice that might build up due to dehumidification is automatically defrosted in cycles The model ICH L is equipped with an illumination box in the upper interior which contains fluorescent tubes The chamber load can be illuminated with UV light and or daylight 2 3 Material For the outer housing MEMMERT uses stainless steel Mat No 1 4016 ASTM 430 and for the interior stainless steel Mat No 1 4301 ASTM 304 is used which stands out through its high stability optimal hygienic properties and corrosion resistance to many but not all chemical compounds caution for example with chlorine compounds The chamber load for the appliance must be carefully checked for chemical compatibility with the materials mentioned A material resistance table can be requested from the manufacturer 2 4 Electrical equipment Operating voltage and current consumption See nameplate Protection class I i e operating insulation with PE conductor in accordance with EN 61010 Protection type IP 20 acc to EN 60 529 gt Interference suppression acc to EN 55011 class B gt Appliance fuse Safety fuse 250 V 15 A quick blow gt The temperature controller is protect
53. stem Defrost The integrated automatic defrosting system for the cooling unit ensures perfect operation of the appliance at low temperatures and in permanent operation The defrosting interval can be set in steps of 6 hours between 6 and 48 hours The setting Off deactivates automatic defrosting Due to long term operation with a working temperature below 15 C or due to a damp chamber load and or the door opening frequently ice can form in the interior over time Heavy icing may impair the function of the appliance and could dam age the cooling system In this case the working chamber should be defrosted This can be achieved by short heating of the appliance to 30 40 C or by switching it off for a longer period of time e g over night The resulting melting water can best be collected with a cloth at the front edge of the working chamber Afterwards the smooth surface of the interior can easily be cleaned Due to this automatic defrosting there is a minor brief increase in the chamber temperature at regular intervals If you would like to further reduce this impairment in performance you can shorten the defrosting frequency e g to every 24 hours In this case please observe if there is a permanent drop in the cooling performance or a strong fluctuation of the actual value which may be an indication that the cooling unit is icing over If this is the case please set the automatic defrosting system one level higher 46 D30
54. suitable load poisonous or explosive vapours or gases may be produced This could cause the appliance to explode and people could be severely injured or poi soned The appliance may only be loaded with materials test objects which do not form any toxic or explosive vapours when heated up see also chapter Intended use on page 8 Warning w In case of appliances of a certain size you can get accidentally lt y locked in which is life threatening Do not climb into the appliance 1 2 1 Additional safety regulation for the model ICH L Warning A UV light i is a danger to your eyes Your eyes could be injured by UV light if you do not wear protection Always wear UV safety goggles when opening the door of the ICH L This is indicated by the warn 1 3 Safety labels ing signs on the door see Fig 1 The model ICH L has warning labels attached to its door warning against dangerous UV radiation in the interior Fig 1 They indicate that either the lighting has to be switched off or UVsafety goggles are required when the door is opened These stickers must not be removed and must always be well visible If they become unrecognisable or if they Fig 1 Warning sign on the door peel off they must be replaced They can be ordered from Memmert customer service D30381 Date 10 2014 7 For your Safety memmerf 1 4 Requirements of the operating personnel The appliance may only be operated and maintained by persons w
55. t 7 7 Sound In the Sound display it can be define whether or not the appliance should emit acoustic signals and if yes on which events gt gt gt gt ie io 54 Activate the acoustic signal adjustment on the press of a key at the end of a programme on alarm if the door is open To do so press the activation key on the left side of the SOUND display The display is enlarged The first category in this case Key sound is automatically highlighted On the right the current set tings are shown on At the end On alarm If door open If you want to edit another list entry Turn the turn control until the respective entry Arouna At the end e g If door open Special accessories Din ser is highlighted in colour Save the selection by pressing the confir mation key The adjustment options are i Keysound automatically highlighted At the end On alarm With the turn control select the desired setting in this example OFF x Keysound Atthe end On alarm Save the setting by pressing the confir mation key Keysound Atthe end If an acoustic alarm sounds it can be On alarm turned off by pressing the confirmation key D30381 Date 10 2014 memmerr Menu mode 7 8 Protocol The appliance continually logs all relevant measured values settings and error messages at 1 minute intervals The internal log memory is of the continuous memory type The logging function cann
56. t a different loca tion the operating instructions must go with it For the current version of this operating manual in pdf format please go to www memmert com de service downloads bedienungsanleitung D30381 Date 10 2014 3 Contents memmert Contents 1 For your Safety 6 1 1 Termsandsionsused eae en 6 1 2 Product safety and dangers ccccccsssssseceecsessseeeeecessnseeeeeesssaueeeeessesaseeeesesesseeeesesesnsaeeness 7 Po MOC NMS ese ccs atest nel ccc E E E E E 7 1 4 Requirements of the operating personnel cccccccccecssseceessseeeessseeeessseeessesseeeeesseeeeeess 8 1 5 Responsibility of the OWNED cccccssssssccesssssseceeecsssseeeeeessseaseeeeessesaseeeesssssseeeeesssssaeeeess 8 TO Ended USE ee are ee 8 1 7 Changes ANd CONVESSIONG cccccccssesseceecessesseceeecsssnueeeeecssseaseeeesesensaeeeessssssaseeeessssnsaeeeess 8 1 8 Behaviour in case of malfunctions and irregularities cccsccccceeesssseeceeeessseeeeeseesseeeeees 9 1 9 Switching off the appliance in an emergency uuuuensennnnsennnennnnnnnnnnennnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnen 9 2 Construction and description 10 2 CORSON ee ee ee ee een Een 10 22 Construction and TUNIC OI nee 11 23 Material 2002 sea ee aE ee ee 11 24 Electrical equipment anna 11 2 5 Connections and interfaces 222200444444nBBRnnnnnnnnnnennnnnennnennnnnennnnnennnnennnnnnnnnneennnnnnnnneenann 11 2 6 Designation namMeplate cccccccc
57. t three digits accept the new IP address by pressing the con firmation key The selection returns to the overview The subnet mask is set accordingly Subnet mask 255 255 0 0 Unit O C O le Timer mode or Or 7 3 3 Unit Here you can choose whether the temperature is displayed in C or F IP address 255 145 136 225 Subnet mask 255 255 0 0 Orc Timer mode or Or D30381 Date 10 2014 45 Menu mode memmert 7 3 4 Timer mode Here you can choose whether the digital backwards counter with target time setting see page 28 should run setpoint depend IP address 255 145 136 225 ent or not This determines whether the timer should not start Subnet mask 255 255 0 0 until a tolerance band of 3 K around the set temperature is Unit 0 reached Fig 25 B or if it should start right after activation A Fig 25 Timer Mode A Timer independent of setpoint Timer starts right after activation B Timer setpoint dependent Timer does not start until tolerance band is reached 7 3 5 Type of the slide in unit Grid or Shelf Here you have to set the type of the slide in unit grid or shelf Bares 255 145 136 225 used The selection Shelf enables you to adjust the control Subnet mask 255 255 0 0 function to the different air flow characteristics in the interior Unit c OF when using optional sliding shelves instead of the grids that are part of the standard delivery Timermode LE Or 7 3 6 Automatic defrosting sy
58. tate is highlighted in colour and indicated by the text display gt Appliance is in programme mode PP es ithe 12 Sept 2012 13 44 Programme is stopped 9 Appliance is in manual mode Manual Mode The example on the right shows the appliance in manual mode identified by the coloured hand symbol gt When the appliance is in timer mode Timer active is displayed 12 Sept 2012 13 44 Timer active 26 D30381 Date 10 2014 memmert Operation and control gt When the appliance is in remote control mode the symbol appears in the temperature display 5 4 4 Manual mode TEMP 4 In this operating mode the appliance runs in permanent operation at the values set on the ControlCOCKPIT 2 C Adjustment options Set 180 0 C As described in chapter 5 4 2 you can set the following parameters after pressing the corresponding activation key in any sequence Temperature Adjustment range dependent on model and operating mode see Ja 535 nameplate and technical data on page 14 2 2 A Heating operation is indicated by the symbol A4 C 1 Cooling is indicated by the symbol Set 37 0 C You can select C or F as the temperature unit displayed see page 45 Fan speed Adjustment option 10 to 100 in steps of 10 Humidity Adjustment range 10 to 80 rh Humidification is indicated by the 63 symbol J Dehumidification is indicated by the 6 symbol HUMIDITY N cy rh Set rh Inte
59. temperature value reaches 50 of the set tolerance band of the setpoint in the example 50 C 1 K for the first time section A When the temperature violates the set tolerance band around the setpoint in the example in Fig 19 50 C 2 K e g if the door is opened during operation section B of illustration the alarm is set off The ASF alarm is automatically triggered as soon as 50 of the set tolerance band of the setpoint in the example 50 C 1 K are reached again section C If the temperature setpoint is altered the ASF is automatically disabled temporarily in this example The setpoint is changed from 50 C to 25 C section D until the tolerance range of the new temperature setpoint is reached again section E C 52 C 52 C 50 C p ZZGL DLILILLL DZ 7 p ITU UUU LILI J IC ZOLL ZZ ATI III MD 48 C 48 C 27 C 25 C KZZ LIT ILL ZB DJ MH III II 44 LL L 23C t Pae AUTO Nane AUTO Paea AUTO ASF alarm Fig 19 Schematic diagram of how the ASF temperature monitoring works Mechanical temperature monitoring Temperature limiter TB The appliance is equipped with a mechanical temperature limiter TB of protection class 1 in accordance with DIN 12 880 Fig 20 If the electronic monitoring unit should fail during operation and the factory set maxi mum temperature is exceeded by approx 20 C the temperature limiter as the final Fig 20 protective measure switches off the h
60. the menu mode J Sound see page 54 indicated by the speaker symbol the alarm is additionally signalled by an intermittent acoustic signal If the confirmation key is pressed the acoustic alarm can be tempo rarily switched off until the next alarm event occurs 6 1 1 Temperature monitoring Temperature alarm and Automatic tem Check if the door is closed ASF are displayed perature monitor Close the door ASF triggered Extend the ASF tolerance band page 55 If the alarm continues Contact customer service page 2 Temperature alarm and The adjustable Increase the difference page 56 TWW are displayed temperature between the monitoring and controller TWW setpoint temperature by has assumed either increasing the max value heating control of the temperature monitor ing or decreasing the setpoint temperature If the alarm continues Contact page 2 customer service 38 D30381 Date 10 2014 memmert The mechanical temperature lim iter TB perma nently switched off heating Appliance does not heat up any more 6 1 2 Humidity monitoring Error display symbol Water tank empty HUMIDITY A rh Set 55 0 rh Alarm display MaxAl Upper humidity limit exceeded HUMIDITY AN rh Set 70 0 rh Alarm display MinAl Humidity below lower limit HUMIDITY rh Set 60 0 rh D30381 Date 10 2014 Malfunctions warning and error messages 1 Wait until the appliance
61. time Remote Control Off Always set the time zone and summer time yes no before you set the date and time Avoid changing the set time after that since this can lead to gaps or overlapping when recording measured values If you still need to change the time you should not run a programme immediately before or after doing so 1 Activate the time setting To do so press the activation key on the right side of ns the Time display The display is enlarged A and the first adjustment option Date Time 12 00 automatically highlighted Time zone GMT 1 BET NEVU i OE D30381 Date 10 2014 47 Menu mode memmert 2 Turn the turn control until Time zone is highlighted Date 12 05 2012 Time 12 00 GMT Daylight savings X Ov 3 Accept the selection by pressing the confirmation key BEG 12 05 2012 Time 12 00 GMT Daylight savings X Ov 4 Set the time zone of the installation site with the turn control e g O for France S Date 12 05 2012 Spain or Great Britain 1 for Germany Time 12 00 Accept the selection by pressing the GMT confirmation key Daylight savings X Ov 5 With the turn control select the Daylight Savings entry NS Date 12 05 2012 Time 12 00 Time zone GMT 0 O 6 Accept the selection by pressing the confirmation key The adjustment options Date 12 05 2012 are highlighted Time 12 00 Time zone GMT 0 7 Set daylight savings to off X or on v with the turn control in this case
62. ured if you do not observe the accompanying safety regulation Caution is used for information that is important for avoiding damage 1 1 2 Signs used Warning signs warning of a danger Danger of Danger of Gases va Danger of UV light Hazard area electrocu explosion pours toppling Observe the tion over operating instructions Prohibition signs forbidding an action Do not lift Do not tilt Do not enter Regulation signs stipulating an action SOAGE an Disconnect Wear gloves Wear safety Wear UV Observe information in the mains boots safety gog separate manual plug gles 1 Important or useful additional information Oo D30381 Date 10 2014 memmert For your Safety 1 2 Product safety and dangers The appliances described in this manual are technically sophisticated manufactured using high quality materials and subject to many hours of testing in the factory They contain the latest technology and comply with recognised technical safety regulations However there are still risks involved even when the appliances are used as intended These are described below Warning After removing covers live parts may be exposed You may receive an electric shock if you touch these parts Disconnect the mains plug before removing any covers Only electrical technicians may work on z the electrical equipment of the appliances OES Warning When loading the appliance with an un
63. variation see Fig Fig 14 A The door opens slightly so that the heat can be vented with the door ajar in case of high temperature inside the chamber The door can then be opened completely B To close the appliance push the door closed and the door handle to the side C Fig 14 Opening and closing the door D30381 Date 10 2014 23 Operation and control memmerf Warning NY In case of appliances of a certain size you can get accidentally ER locked in which is life threatening Do not climb into the appliance 5 3 Loading the appliance explosive vapours or gases may be produced This could cause the appliance to explode and people could be severely injured or poi soned The appliance may only be loaded with materials which do not form any toxic or explosive vapours when heated up and cannot ignite see also Intended use on page 8 If there is any doubt as to the composition of materials they must not be loaded into the appliance Warning gt When loading the appliance with an unsuitable load poisonous or Caution Check the chamber load for chemical compatibility with the materials of the appliance see page 11 Insert the sliding steel grids or sliding shelves The maximum number or grids shelves and the load capacity are specified in the technical data overview from page 14 The chamber must not be loaded too tightly so that proper air circulation in the interior is guaranteed Do not pl
Download Pdf Manuals
Related Search
Operator manual_ICH_ICHL
Related Contents
PIVOT PRO SOFTWARE USER MANUAL GO-MATIC Serie 1 hasta ST80 ESPAÑOL ECO WHEELER 1600 E #95122 Instruktion ECL Comfort 210 / 310, Applikation A237 / A337 Microsoft Windows Embedded Industry Enterprise EP/EPi6.0 and EP/EPi9.0 Copyright © All rights reserved.
Failed to retrieve file