MANUALE DI INSTALLAZIONE, USO E MANUTENZIONE Unità di

image

Contents

1. E PULIZIA FILTRI e SCAMBIATORE DI CALORE MAINTENANCE AND CLEANING OF FILTERS and HEAT EXCHANGER 2 3 4 Oo Vedere il video di manutenzione all indirizzo www utek eu View the video in our website www utek eu VA PRECAUZIONI NELLA MOVIMENTAZIONE DELLO SCAMBIATORE DI CALORE SI PRECAUTIONS IN HANDLING THE HEAT EXCHANGER f Manutenzione periodica consigliata per i filtri Recommended periodical maintenance Sostituzione filtri Filter replacement variabile in funzione dell inquinamento dell aria ambiente polveri fumi variable depending on environment air pollution dust fume Manutenzione periodica consigliata per lo scambiatore Recommended periodical maintenance Pulizia scambiatore Exchanger cleaning 1 anno di funzionamento circa 1 operation season approximately OTEK Anomalia Avviamento difficoltoso Anomalie di funzionamento Cause a Tensione d alimentazione ridotta b Coppia di spunto del motore insuffi ciente Rimedi a Verificare i dati di targa del motore b Chiudere le serrande fino al raggiungimento della piena velocit Nel caso provvedere alla sostituzione del motore Calo di prestazioni dopo un periodo di funzionamento accettabile Portata d aria e pressione insufficienti Temperatura aria di rinnovo troppo fredda Rendimento scambiatore di calore insufficiente a Perdita nel circuito a monte e o a valle del ventilatore b Girante danneggiata a Tubazioni int
2. must be suitable to the weight of the unit and don t cause vibrations a position that does not block passageways or entrances the unit must be canalized measures to protect the fan vents with special protection to prevent contact with moving mechanical parts The protection degree is IP20 In case of outdoor installation place the unit in a place sheltered from the weather REMAINING RISKS The risks of the products have been analyzed according to the Machine Directi ve all of Directive 2006 42 CE The present handbook contains information for all persons in charge and has the purpose to avoid possible damages to persons and or things attributable to remaining risks MACHINE SIGNALS The machine can be provided with several signalling pictograms which may not be removed Said signals can be subdivided into PROHIBITION SIGNALS Do not repair or adjust during motion DANGER SIGNALS QA AL They signal the presence of parts under voltage in the container on which the plate is provided IDENTIFICATION SIGNALS Serial number plate it states the product data and the manufacturer address REMARK other signals can be added to the product according to the analysis carried out on the remaining risk GOODS RECEPTION Each product is carefully checked before shipping On goods reception it is necessary to make sure that products have not suffered any damages during transport In this case send a complaint t
3. original spare part Other troubleshooting for unit with CTR08 EVO P H EVO D PH microprocessor control Fault Fans alert sue baucuseusseuessevigsecnveceusecersuesresnscestenesiencissnecuustvaccesieorensscensboassenionsbhucsennbecndsvesaehavecsseeasucnsenssvccsautesnes esrescescdsvessseuscuabhucesanieesesuesdenverersvesaucussresicorsaviossesvesssiuersdsiesarbuesucsdsoadebessenuesdsnvecsutieearbaesucsussesaviousouuccecssesuacressesnecrenuneeravisisenucrdonecuseciesdusussusuvnsesanisvabnier crvousesusedesnessanceyerneesonsbeerenrvousssvesdenucsedsvesantvecrsouserdertedssousbacstcodsnverssticonsseee CBR CCA CI OI OOO O CO OO IIC COSIO IU IO T cetaesiiedenssneeddsuasaenensdaderessccsdesrenasineeasiddesoucacaseccesees stueediardeiseatesdubcognaedsbsceneiiecsuecseresnebaa Gi ccaaueravieviceretaesbesseness sents CTRO8 EVO PH EVO D PH display LED OFF www utek eu marketing utek it Causes Failure or objects blocking the fan Machine not powered Via provinciale 30 23030 Mazzo di Valtellina So Tel 39 0342 862031 Tel 39 02 26417298 Fax 39 0342 862029 Remedies Verify that anything blocks the functioning of the fans in the case proceed with removal Check the correct connection between the control panel and electronic card
4. osservare i vigenti dispositivi di legge in materia di prevenzione deve rispettare le istruzioni qui di seguito riportate Deve indossare adeguato abbigliamento antinfortunistico E obbligatorio l uso di cuffie afoniche quando il rumore supera il limite ammissi bili Deve verificare l esistenza di un interblocco che impedisca l avviamento della macchina da parte di altre persone CONDIZIONI DI INSTALLAZIONE Installazione all interno di edifici residenziali con temperatura ambiente compresa tra 0 e 45 C Da evitare aree in prossimit di fonti di calore vapore gas infiammabili e o esplosivi aree particolarmente polverose Da fare considerare un area dove la mandata d aria ed il rumore dell unit non rechino disturbo ai vicini considerare una posizione che rispetti gli spazi minimi come indicato nel presen te manuale la consistenza del pavimento o della parete deve essere adeguata al peso dell unit e non provocare vibrazioni considerare una posizione che non ostruisca passaggi o ingressi provvedere alla canalizzazione dell unit provvedere alla protezione delle bocche del ventilatore con apposite protezioni per evitare il contatto con organi meccanici in movimento Il grado di protezione dell unit IP20 In caso di installazione all esterno collocare l unit in luogo riparato da agenti atmosferici RISCHI RESIDUI E stata effettuata l analisi dei rischi dei p
5. ITION OTEK COLLEGAMENTI ELETTRICI ELECTRICAL CONNECTIONS Prima di effettuare qualsiasi operazione su parti elettriche assicurar si che non vi sia tensione Verificare che la tensione di alimentazione corrisponda ai dati no minali dell unit tensione numero di fasi frequenza riportati sulla targhetta a bordo macchina L allacciamento di potenza avviene tramite cavo bipolare e condutto re di protezione La sezione del cavo deve essere adeguata alla massima corrente assorbita e dovr essere protetto da un adeguato interruttore ma gnetotermico differenziale IAn 0 03 A La tensione di alimentazione non deve subire variazioni superiori a 5 Il funzionamento deve avvenire entro i valori sopra citati in caso contrario la garanzia viene a decadere immediatamente collegamenti elettrici ai quadri di comando devono essere effettuati da personale specializzato Assicurarsi che la tensione e la frequenza riportate sulla targhetta corrispondano a quelle della linea elettrica di allacciamento collegamenti elettrici devono essere realizzati a regola d arte in accordo con le informazioni riportate sullo schema elettrico allegato all unit e dovranno tenere conto delle rispettive norme vigenti Tutte le linee devono essere protette all origine a cura dell installa tore ATTENZIONE NON ALIMENTARE EVENTUALI RESISTENZE CON VENTILATO RE SPENTO Before starting any work on electrical parts make sure that the power
6. N aria ripresa exhaust air aria rinnovo fresh air aria mandata Supply air aria esplusione expulsion air lato ispezione Side inspection OTEK INSTALLAZIONE DI BATTERIA AD ACQUA BA AFC HB E RISCALDATORE ELETTRICO REL M INSTALLATION OF WATER COIL BA AFC HB AND ELECTRIC HEATERS REL M It s possible to install the optional PRE or POST heating devices such as water coils or electric heaters These accessories are equipped with male female spigots for the ducting connection and can be installed on delivery and or suction mouths of the units direct installation or in the circuit of ducts remote installation E possibile installare come opzione dei dispositivi di PRE o POST riscalda mento quali batterie ad acqua o riscaldatore elettrico nell unica posizione consentita mostrata in figura Questi accessori sono dotati di nippli maschio femmina per il collegamento a canale spiroidale e possono essere installati sulle bocche prementi e o aspiranti delle unit installazione diretta oppure all interno del circuito delle canalizzazioni installazione remota batteria ad acqua BA AFC water coil riscaldatore elettrico di post riscaldamento REL M riscaldatore elettrico di sbrinamento RCF SCTTC post heating electric resistance deicing electric resistance REL M REL M CORRETTA INSTALLAZIONE RIGHT INSTALLATION SCORRETTA INSTALLAZIONE WRONG INSTALLATION UNICA POSIZIONE CONSENTITA ONLY POSSIBLE POS
7. Unit di ventilazione meccanica controllata con recupero di calore per edifici residenziali Heat recovery ventilator for energy efficient residential buildings n min 75 max gt 90 MANUALE DI INSTALLAZIONE USO E MANUTENZIONE GUIDE FOR INSTALLATION USE AND MAINTENANCE DI cs Istruzioni originali Original instructions Validit dal Validity from 01 2011 Rel 02 2011 OTEK NORME DI SICUREZZA E MARCHIATURA CE nostri tecnici sono impegnati quotidianamente nella ricerca e nello sviluppo studiando prodotti sempre pi efficienti nel rispetto delle norme di sicurezza in vigore Le norme e le raccomandazioni riportate qui di seguito riflettono prevalentemente quanto vigente in materia di sicurezza e quindi si basano principalmente sull os servanza di tali norme di carattere generale Pertanto raccomandiamo vivamente a tutte le persone esposte di attenersi scru polosamente alle norme di prevenzione degli infortuni in atto nel proprio paese UTEK s r l si esime da ogni responsabilit per eventuali danni causati a persone e cose derivanti dalla mancata osservanza delle norme di sicurezza nonch dalle eventuali modifiche apportate al prodotto Il contrassegno CE e la relativa dichiarazione di conformit attestano la conformit alle norme comunitarie applicabili prodotti che non riportano sulla targhetta la marchiatura CE devono essere completati dall acquirente che dovr poi certificare tutto l impia
8. all be performed by a qualified installer in accordance with relevant local and national regulations in force UTEK INSTALLAZIONE DELL UNITA INSTALLATION OF THE UNIT INSTALLAZIONE ORIZZONTALE A SOFFITTO L unit provvista di staffe di sollevamento nei quattro angoli superiori dove possibile agganciarsi con barre filettate o catene per agevolare il fissaggio al soffitto ed il suo livellamento Assicurata l unit nella giusta posizione effettuare il collegamento con la canalizzazione l allacciamento alla rete elettrica ed il fissaggio del tubo scarico condensa sul lato inferiore HORIZONTAL CEILING INSTALLATION The unit is equipped with lifting rods in the four bottom unit angles where hooking is possible through threaded bars or chains in order to facilitate ceiling fastening and levelling After fastening the unit in the right position carry out the connection to the ducting the connection to the supply mains and the conden sate discharge pipe fastening on the air exhaust side I nante e ee eee een N INSTALLAZIONE ORIZZONTALE A PAVIMENTO L unit provvista di staffe nei quattro angoli inferiori alle quali possibile agganciarsi con barre filettate per agevolare il fissaggio al pavimento ed il suo livellamento Assicurata l unit nella giusta posizione effettuare il collegamento con la canalizzazione l allacciamento alla rete elettrica e il fissaggio del tubo scarico condensa sul lato d espu
9. asate e o punti aspirazione occlusi b Girante intasata c Filtro sovraccaricato d Velocit di rotazione insufficiente e Pacco di scambio occluso Ventilatore che lavora in prossimit di condizioni di portata nulla Instabilita del flusso ostruzione o cattiva connessione a Verifica del circuito e ripristino delle condizioni originali b Verificare la girante e nel caso sostituire con ricambio originale a Pulizia tubazioni e aspirazioni b Pulizia girante c Pulire o sostituire il filtro d Verifica della tensione di alimentazione nel caso correggere e Pulizia pacco di scambio Modifica del circuito e o sostituzione del ventilatore Pulizia e o ripristino canalizzazione in aspirazione Intervenire nel regolatore elettronico aumentando la velocit minima voltaggio insufficiente Vibrazioni eccessive Squilibri delle parti rotanti Verificare l equilibratura della girante nel caso ripristinarla o sostituirla Anomalie aggiuntive per unit con controllo a microprocessore CTR08 EVO P H EVO D PH Anomalia Allarme ventilatori Cause Guasto oppure presenza di oggetti che ostruiscono il ventilatore Rimedi Verificare che non ci sia qualcosa che blocchi il funzionamento dei ventilatori nel caso procedere alla rimozione CRI AC CI OO I OOO ORO CO COCO III OO RO UO LOI OI COLI A RI AI III IIC II SCO OI SII II OOO ETT Display o LED spenti CTR08 EVO PH EVO D PH Macchina non ali
10. is off Check that the power supply voltage is the same as the nominal data for the unit voltage number of phases frequency shown on the nameplate on the machine The power connection must be formed using a 1p n earth cable Pass the electric cables into the machine and electrical panel via the cable glands Cables must have a cross section that is able to handle the maximum power absorbed and must be protected by residual current operated circuit breakers with integral overcurrent protection RCBOS IAn 0 03 A The power supply voltage must not fluctuate by more than 5 The unit must work within the values indicated above If this is not the case the guarantee shall become null and void immediately The electrical connections to the control panel must be carried out by qualified personnel Make sure that the voltages and frequency shown on the data plate correspond to those of the power line Carry out the connections in accordance with the local technical stan dards All the connections must be protected at the source by the installer WARNING DO NOT WORK THE ELECTRICAL RESISTANCE WHEN THE FAN IS OFF GLI SCHEMI ELETTRICI SONO DISPONIBILI SUL SITO WWW UTEK EU ELECTRICAL CONNECTIONS ARE AVAILABLE ON THE WEBSITE WWW UTEK EU CONFIGURAZIONE ORIZZONTALE HORIZONTAL CONFIGURATION aria mandata supply air aria ripresa exhaust air OTEK aria esplusione expulsion air aria rinnovo fresh air MANUTENZIONE
11. ive moisture and not subject to sudden changes of temperature in order to avoid the formation of condensation inside the unit EXTENDED DOWNTIME In the event of extended downtime with the unit connected to the system of venti lation close the suction injection and periodically check the absence of humidity inside the machine In case of condensation wipe it dry it immediately START Before starting it is opportune to carry out some checks follow the safety instruc tions in section DISASSEMBLY AND ASSEMBLY Make sure there is no condensation inside the unit and if necessary wiipe it dry before attempting to operate the unit Check thefilters status Make sure that the product does not contain any foreign matters and that all components are fastened in their seats Try manually that the impeller does not rub on the walls Make sure that the inspection door is closed CAUTION If the fan mouths are not ducted use a suitable protection net Check the earth connection The electrical connection must be carried out by qualified personnel DISASSEMBLY AND ASSEMBLY Before starting any operation make sure that the product is excluded from any electrical connection and that the impeller is switched off Disassembly and assembly are extraordinary maintenance operations and must be carried out by qualified personnel DISPOSAL Do not dismantle the system themselves disassembly of the product and X any other party sh
12. lsione aria HORIZONTAL FLOOR INSTALLATION The unit is equipped with lifting rods in the four bottom unit angles where hooking is possible through threaded bars or chains in order to facilitate floor fastening and levelling After fastening the unit in the right position carry out the connection to the ducting the connection to the supply mains and the condensate discharge pipe fastening on the air exhaust side SPAZI MINIMI DI MANUTENZIONE ORDINARIA in mm MINIMUN SPACES REQUIRED FOR THE ORDINARY MAINTENANCE in mm OTEK INSTALLAZIONE SCARICO CONDENSA SIPH CONDENSATE DRAINAGE INSTALLATION L unit provvista di scarico per il drenaggio dell acqua che si forma durante il normale funzionamento Dovr essere sempre prevista una tubazione di scarico con sifone e pendenza minima del 3 al fine di evitare stazionamenti dell acqua di condensa La presenza del sifone fondamentale per il buon funzionamento della macchina al fine di evitare risucchi d aria e permettere il naturale deflusso dell acqua di condensa The unit is equipped with condensate drainage to evacuate the water during normal operation Should always be provided with a drain pipe siphon and minimum slope of 3 in order to avoid stationing of condensate The siphon is essential for the proper functioning of the machine in order to avoid sucking air and allow the natural flow of condensate CONFIGURAZIONE ORIZZONTALE HORIZONTAL CONFIGURATIO
13. mentata Verificare la corretta connessione tra pannello di controllo e scheda elettronica UTEK LUTEK NY AN Fault Difficult start Performance drop after a period of acceptable operation Insufficient air capacity and insufficient pressure Exchange air temperature too cold Insufficient heat exchanger performance Excessive vibrations Troubleshooting Causes a Reduced supply voltage b Insufficient motor static torque a Circuit leak before and or after the fan b Damaged impeller a Clogged pipelines and or suction points b Clogged impeller c Overloaded filter d Insufficient rotation speed e Clogged heat exchanger The fan capacity conditions are near zero flow instability clogging or wrong connection Rotating parts unbalance Remedies a Check motor plate data b Close the air locks to reach full speed if necessary replace the motor a Circuit check and restoration of original conditions b Check the impeller if necessary replace through an original spare part a Pipelines and suction point cleaning b Impeller cleaning c Filter cleaning or replacement d Supply voltage check if necessary correct e Heat exchanger cleaning Increase the min speed on the electronic speed regulator insufficient voltage Modify the circuit and or replace the fan Clean and or restore the suction duct Check the impeller balance in case restore or replace it Through an
14. ns for the temporary removal cease All ordinary and extraordinary maintenance interventions shall be carried out with disconnected machine and electrical and pneumatic supply In order to avoid the risk of possible accidental starts provide the electric panels the central units and the switchboards with warning signals with the following reading caution control disconnected for maintenance works Before connecting the electrical supply cable to the terminal board make sure that the line voltage is in compliance with the voltage stated on the machine plate Replace the product labels if with the passing of time they should become illegible MAINTENANCE REGULATIONS The personnel in charge with maintenance must keep to the accident prevention regulations in force and to the following instructions wear suitable accident prevention clothes when the noise exceeds the admissible levels use protection headsets make sure that an interlock is provided so that the machine may not be started from non authorized persons INSTALLATION CONDITIONS Installation allowed inside the buildings or outdoor with temperature between 0 to 45 C To avoid areas near sources of heat source steam flammable and or explosives gases dusty areas To consider consider an area where the air flow and noise of the unit don t disturb the neighbors minimum space required for the maintenance as defined below the floor or wall
15. nto fornendo cos la certificazione di conformit Le macchine sono conformi a quanto prescritto da Direttiva macchine 2006 42 CE Direttiva bassa tensione 2006 95 CE Direttiva compatibilit elettromagnetica 2004 108 CE Riferimento norme armonizzate EN 12100 1 2003 EN 12100 2 2003 EN 60204 1 2006 NORME GENERALI Le protezioni di sicurezza non devono essere rimosse se non per assoluta neces sit di lavoro nel qual caso dovranno essere immediatamente adottate idonee misure atte a mettere in evidenza il possibile pericolo Il ripristino sul prodotto di dette protezioni deve avvenire non appena vengono a cessare le ragioni della temporanea rimozione Tutti gli interventi di manutenzione ordinaria e straordinaria devono essere effet tuati a macchina ferma ed alimentazione elettrica pneumatica ecc disinserite Per scongiurare il pericolo di possibili inserimenti accidentali apporre sui quadri elettrici sulle centrali e sui pulpiti di comando cartelli di avvertimento con la dicitu ra Attenzione comando escluso per manutenzione in corso Prima di collegare il cavo di alimentazione elettrica alla morsettiera verificare che la tensione di linea sia idonea a quella riportata sulla targhetta posta sulla macchina Prestare attenzione alle etichette poste sul prodotto se col passare del tempo dovessero diventare illeggibili sostituirle NORME PER LA MANUTENZIONE Il personale addetto alla manutenzione oltre a dover
16. o the forwarding agent The forwarding agent is responsible for any transport damages Products are loaded on pallets and fastened to them by means of straps and pro tection film or in self supporting cardboard boxes which are fastened to pallets MOVIMENTAZIONE Prima di spostare il prodotto accertarsi che il mezzo utilizzato sia di portata adeguata Per il sollevamento servirsi di sollevatore a forche sollevando il pallet Il sollevamento a mano massimo specificato nella norma 89 391 CEE e successive Generalmente accettabile un peso di Kg 20 al di sotto della spalla ma al di sopra del livello del suolo IMMAGAZZINAMENTO Conservare l unit in un luogo riparato senza eccessiva umidit e non sogget to a forti sbalzi termici al fine di evitare la formazione di condensa all interno dell unit FERMO PROLUNGATO In caso di fermo prolungato con l unit allacciata all impianto di ventilazione chiudere i condotti di aspirazione immissione e controllare periodicamente l assenza di umidit all interno della macchina In caso di formazione di umidit provvedere ad asciugarla immediatamente AVVIAMENTO Prima dell avviamento opportuno effettuare alcuni controlli seguire le indica zioni di sicurezza riportate nel paragrafo SMONTAGGIO E MONTAGGIO Accertarsi che all interno dell unit non sia presente condensa ed eventual mente asciugarla prima di mettere in funzione l unit Controllare lo sta
17. rodotti come previsto dalla Direttiva Mac chine allegato della Direttiva 2006 42 CE Questo manuale riporta le informazioni destinate a tutto il personale esposto al fine di prevenire possibili danneggiamenti a persone e o cose a causa di rischi residui CARTELLI A BORDO MACCHINA Sulla macchina possono essere presenti diversi pittogrammi di segnalazione che non devono essere rimossi segnali sono divisi in SEGNALI DI DIVIETO amp Non riparare o registrare durante il moto SEGNALI DI AVVERTIMENTO INFORMAZIONE OAAL Segnala la presenza di parti in tensione all interno del contenitore su cui la targhet ta applicata SEGNALI DI IDENTIFICAZIONE Targhetta matricola riporta i dati del prodotto e l indirizzo del fabbricante o del suo mandatario N B altri segnali possono essere aggiunti al prodotto in relazione all analisi fatta del rischio residuo RICEVIMENTO DELLA MERCE Ogni prodotto viene controllato accuratamente prima di essere spedito All atto del ricevimento occorre controllare che il prodotto non abbia subito danni durante il trasporto in caso contrario esporre reclamo al trasportatore Il vettore responsabile di eventuali danni derivanti dal trasporto prodotti vengono imballati su pallet e fissati allo stesso tramite reggie e film pro tettivo oppure in scatole di cartone autoportanti adeguatamente fissate al pallet SAFETY STANDARDS AND CE MARKING Our technicians are steadil
18. to dei filtri Accertarsi che all interno del prodotto non ci siano corpi estranei e che tutti i componenti siano fissati nelle loro sedi Provare manualmente che la girante non sfreghi sulle pareti Verificare che la portina d ispezione sia chiusa ATTENZIONE Se le bocche di un ventilatore non sono canalizzate si deve provvedere un adeguata rete di protezione Controllare il collegamento elettrico di messa a terra Il collegamento elettrico deve essere effettuato da personale qualificato SMONTAGGIO E MONTAGGIO Prima di intraprendere qualsiasi operazione accertarsi che il prodotto non sia e non possa casualmente o accidentalmente essere alimentato elettricamente e la girante sia ferma Lo smontaggio e il relativo montaggio sono operazioni di manutenzione straor dinaria devono essere eseguite da personale qualificato SMALTIMENTO Non cercare di smontare il sistema da soli lo smontaggio del prodotto e Ka qualsiasi altra parte devono essere eseguiti da un installatore qualifi cato in conformit con le relative norme locali e nazionali in vigore HANDLING Before displacing products make sure that the means of transport employed has a suitable carrying capacity For pallet lifting use forklifts According to the standard 89 391 CEE and following standards manual lifting is admissible up to a max weight of 20 Kg under shoulders level but over floor level STORAGE Store the unit in a sheltered spot without excess
19. y engaged in research and development of more and more efficient products in compliance with the safety standards in force The standards and suggestions contained herein reflect the safety standards in force and therefore are mainly based on the compliance of said general regulations Consequently we would suggest all people exposed to risks to comply the acci dent prevention regulations in force in their respective countries Messrs UTEK s r l are exempted from any responsibility attributable to damage caused to persons and things resulting from the non compliance with the safety standards and any product modifications The CE marking and the relevant declaration of conformity prove the conformity to the applicable community regulations The products which are not provided with the CE marking must be certified by the purchaser who shall have to certify the conformity of the whole plant Units are as prescribed by Machinery directive 2006 42 EC Low voltage directive EEC 2006 95 Electromagnetic compatibility directive 2004 108 EC And in accordance with the following harmonized standards EN 12100 1 2003 EN 12100 2 2003 EN 60204 1 2006 GENERAL The safety protection devices may not be removed if this is not absolutely necessary In this case suitable measures to point out the possible danger shall be imme diately taken The restoration of said protection devices on the product shall take place as soon as the reaso

Download Pdf Manuals

image

Related Search

Related Contents

DCS800 Firmware Manual - Galco Industrial Electronics  M-575V/570V/475/470 Microcassette™-Corder  F3Dn Service Manual Parts Replacement / Section 2.2 2.2 Freezer    Manual de Usuario  Technical/Manual 1  KS 1100 B HD KS 1100 B  Informations produit - Philips StorageUpdates  Manual do Usuário v1.0 Software Rota Certa v1.0  1 Información importante Información básica 2  