1. Hole Pattern for Custom Mounting In applications where custom mounting to a panel or box is desired the clearance and mounting holes should be drilled as indicated in the following diagram and Table 7 Table 7 Custom Mounting Dimensions mm Inches mm Inches NOTICE In order to maintain the IP protection provided by PN models in custom installations watertight seals should be used under the heads of the four mounting bolts and they must be retained by a lock washer and nut on the inside of the box or panel Alternatively four blind holes may be drilled and threaded to accommodate the mounting screws provided that the hole depth is sufficient to achieve adequate gasket compression IJ OPERATION To ensure safe and reliable operation Meltric A plugs and receptacles must be used in accordance with their assigned ratings Meltric plugs amp receptacles can only be used in conjunction with mating receptacles or plugs manufactured by Meltric or another licensed producer of products bearing the Marechal technology trademark Meltric plugs amp receptacles are designed with different keying arrangements so that only plugs and receptacles with compatible contact configurations and electrical ratings will mate with each other Connection To connect open the protective plug cap align the red dots on the plug and receptacle bodies insert plug into receptacle apply force and rotate the plug 20 c
2. as E E W a UM Y AY P 0 Y 5 INSPN 6 Meltric Corporation 4640 Ironwood Drive Franklin WI 53132 Tel 800 433 7642 Fax 414 817 6161 e mail mailfdmeltric com A manufacturer of products using Marechal technology anaa U RENEA E GENERAL PN Series Standard Duty plugs and receptacles are designed to offer superior safety durability and consistent electrical contact performance Please follow the instructions below to ensure the proper installation operation and maintenance of this product LAW AR N l N G There are inherent dangers associated with electrical products Failure to follow safety precautions can result in serious injury or death These instructions must be followed to ensure the safe and proper installation operation and maintenance of the Meltric devices Before installation disconnect all sources of power to the circuit to eliminate the risk of electrical shock I RATINGS Meltrics PN7 PN20 and PN30 plugs amp receptacles are listed in accordance with UL 1682 CSA 22 2 No 182 1 and IEC 60309 1 The PN12c is listed in accordance with IEC 60309 1 The amperage voltage and environmental ratings are indicated in Table 1 Table 1 General Ratings PM12 Prn7 PN20 PN30 Current Non Current Voltage 600VAC 600VAC 600VAC 600VAC Environmental IP66 67 IP66 67 IP66 IP67 IP66 IP67 IP54 IP55 IP54 IP55 PN20HT and PN30HT are current interrupting up to 480V only envir
3. teniendo en cuenta que la cubierta del cable deber penetrar en la manija para un agarre seguro Retire el aislante de los conductores de acuerdo a la Tabla 4 Cuando aplique afloje los tornillos de la terminal pero no totalmente solo para permitir la entrada del conductor Inserte el conductor hasta el fondo en su terminal correspondiente y apriete las terminales de acuerdo al torque indicado en la Tabla 5 Tomacorriente Clavija a Empaque Multicapa Para asegurar la operaci n segura y confiable A los tomacorrientes y clavijas Meltric se deberan de utilizar de acuerdo con rangos asignados Solo pueden utilizarse en conjunto con tomacorrientes y clavijas Meltric 6 de otro fabricante autorizado de los productos que ostenten la marca registrada Marechal Meltric dise a sus tomacorrientes y clavijas con posiciones de bloqueo diferentes de tal manera que solo las clavijas y tomacorrientes que tienen las mismas configuraciones de contactos y voltaje pueden acoplarse entre s Conexi n Para conectar abra la tapa protectora alinee los puntos rojos en el cuerpo de la clavija y el tomacorriente inserte la clavija en el tomacorriente aplique fuerza y gire la Los contactos del tomacorriente deber n ser revisados solo por personal calificado Esto solo podr hacerse con el equipo desenergizado Cualquier reparaci n servicio deber ser realizado solo con partes originales MELTRIC RESPONSABIL
4. Models 14 to 6 or 1 or 11 Hot conductors no specific lettered ter minal applies to any specific colored conductor Hot conductors no specific lettered ter minal applies to any specific colored conductor I ASSEMBLY A Verify that power has been disconnected prior to assembly For In Line Connections Insert the cable through the handle and gasket Strip the cable jacket to provide a workable wire length being mindful that the jacket must extend into the handle to achieve a secure grip Then strip the wires to the lengths indicated in Table 4 When applicable back out the terminal screws far enough but not completely to allow the conductors to pass Insert the conductors fully into their respective terminals and hand tighten to the torques indicated in Table 5 Receptacle or Inlet Bushing Compression Handle Color Coded Nut Gasket For Mounted Receptacles Inlets Insert the cable through the wall box and cut to allow adequate length Strip the cable jacket to allow a workable wire length Strip the individual cables to the lengths indicated on Table 4 When applicable back out the terminal screws far enough but not completely to allow the conductors to pass Insert the conductors fully into their respective terminals and hand tighten to the torques indicated in Table 5 Assemble the receptacle inlet and the color gasket to the box with the appropriate hardware
5. Notas y Precauciones Generales 1 Este producto deber ser instalado por personal calificado 2 AVISO No esta e los finales del cable que se insertan en las terminales 3 AVISO No aplique aerosol con repelente de humedad en los contactos 4 No afloje excesivamente los tornillos de las terminales 5 AVISO Se proporcionan tornillos autorroscantes para ser utilizados con algunos componentes polim ricos puede requerirse de un gran torque para insertarlos una vez hecho esto evite apretarlos demasiado contra el material pl stico 6 AVISO Todas las manijas de MELTRIC tienen rosca estilo c nico El uso de cinta selladora se recomienda para mantener la impermeabilidad de todos los accesorios y uniones NPT 7 Se pueden usar varias opciones de manijas y sujetadores de cables estas instrucciones est n basadas en manijas que utilizan un sujetador para el cable tipo empaque multicapa 8 Si el tomacorriente y clavija son de acero inoxidable accesorios del mismo material deber n ser usados P MEDIOAMBIENTE Optimas condiciones de operaci n se logran instalando tomacorrientes y clavijas IP66 IP67 con el gatillo en la parte superior AVISO Para evitar el ingreso de agua los tomacorrientes y clavijas que no son a prueba de agua deber n mantenerse viendo hacia abajo cuando est n desconectadas Largo del Cable sin Aislamiento El largo de los cables sin aislamiento se indica en la tabla 4 El largo del cable para
6. asentarse depender de la aplicaci n espec fica Cuando se utiliza con manijas el largo del cable sin aislamiento deber llegar al fondo de Cableando las conexiones de las terminales Antes de iniciar verifique que el circuito no est A energizado que el rango del producto es el apropiado para la aplicaci n y que el producto cumpla con la normatividad vigente local y nacional Siga la codificaci n de los conductores y las marcas de las terminales detalladas en la Tabla 6 ADVERTENCIA Este producto deber de ser el ctricamente conectado a tierra Una terminal para tierra se provee en todos los accesorios de metal con un tornillo pintado de verde y una rondana Para Terminales con Tornillo Inserte el cable a trav s de la manija y retire la cubierta del conductor en la proporci n adecuada La cubierta del cable deber quedar por lo menos Y dentro de la manija Afloje los tornillos solo para que el conductor pueda entrar Retire el aislamiento de los conductores de acuerdo a lo indicado en la Tabla 4 Tuerza los hilos de cada conductor e ins rtelos hasta el fondo en la terminal Apriete los tornillos de las terminales de acuerdo a lo indicado en la Tabla 5 PN12c con Zapatas Terminales de Compresi n Soldables 1 Retire el aislamiento de cada uno de los cables 25 64 10mm 2A Para Cables Calibres 18 16 AWG use una zapata tipo casquillo 2B Para Cable Calibre 14 Max la zapata tipo casquillo no es
7. for their entire length and are inserted with the contact tip first into the rear of the inlet plug 5 The female contacts consist of a flexible braid and spring and are inserted with the contact tip first into the rear of the lidded receptacle connector 6 Insert the Provided Hole Plugs into the unused holes in the front of each insulating block NOTICE If a new Receptacle or Inlet is to mate with a previously installed device pay particular attention to the number of contacts and numbered position in the Receptacle or Inlet Continuity will not be obtained unless the male and female contacts are evenly mated Disassembly of PN12c Contacts 1 To remove the contact from the insulating block the provided Multi Contact Removal Tool 9 LD12 37 must be used From the front side of the insulating block slide the contact removal tool over the contact 2 Push until the contact pops out the back side of the insulating block 3 NOTICE Each contact is designed to be removed from the insulating block a maximum of 3 times New contacts should be used if contacts are removed more than 3 times Table 6 Conductor Coding and Terminal Markings a Green equipment grounding conductor G E or GND only or green with yellow stripe N White or gray system ground neutral conductor only N PN20 PN30 PN20HT PN30HT Models 1 or R1 Black 2 or S2 Red 3 or T3 Blue PN7c PN12c
8. puede ser retirada del tomacorriente con seguridad Los contactos de la clavija permanecer n cubiertos hasta despu s de que el circuito se desconecta Cierre la tapa del tomacorriente para evitar entrada de suciedad polvo PROVISIONES PARA BLOQUEO La Clavija se puede cerrar con un bloqueo del garillo excepto PNHT y PN12cSS Tornillo Con la clavija insertada 6 la tapa cerrada gire el tornillo de 5 16 con una llave Allen hasta que alcance la parte inferior AVISO NO apriete demasiado MANTENIMIENTO A ADVERTENCIA Antes de inspeccionar reparar o mantener los productos Meltric desconecte la alimentaci n al tomacorriente para eliminar el riesgo del shock el ctrico Los productos Meltric requieren de muy poco mantenimiento de cualquier manera es muy recomendable que se realicen las siguientes pr cticas de inspecci n general e Revise el apriete de los tornillos de montaje e Verifique que el peso del cable este soportado en el relevador de esfuerzos y no en las terminales de conexi n e Revise el desgaste y ajuste del empaque IP En ambientes h medos o de lavado los empaques deber n de ser revisados por desgaste y dureza peri dicamente cada 6 meses Interc mbielo si se requiere e Verifique la continuidad el ctrica del circuito de tierra cada 6 meses e Revise la limpieza y desgaste de la superficie de los contactos Dep sitos de polvo o materiales ajenos pueden ser limpiados con un trapo li
9. IDAD DEL FABRICANTE La responsabilidad de Meltric esta limitada estrictamente a la reparacion 6 reemplazo de cualquier producto que no cumpla con la garantia especificada en el contrato de compra Meltric no puede ser responsabilizado por fallas dano a consecuencia de la perdida de produccion 6 cualquier perdida financiera en la que incurra el cliente Meltric Corporation no puede ser responsabilizado cuando sus productos son utilizados en conjunto con otra marca que no tenga la marca registrada Marechal H a A ee A A ES a ee lt a oe o i A las terminales que se mencionan en la Tabla 2 Las considerada la superficie plana con los orificios para los e a si Ma piece di pecs phe E ener gu as para los rangos NPT se detallan en la tabla 3 Tabla 5 Torques para los Tornillos de las Terminales 4 Tornillos de montaje marca registrada Marechal invalidara toda garant a un Tabla 2 Capacidad de Alambrado en las terminales en AWG Dispositivo Contacto Desarmador o llave Allen Pulg lbs requerido Relevador en el producto Modelo Calibre del conductor asi oe Meltric es tambi n un miembro de BECMA Butt contact PN20 30 amp es 3 mm or 1 8 punta tipo cabinet Tuerca de S Manija Empaque Electrical Conectors Manufacturers Association Por color PN 20HT 30 HT PN12c PN12cSS Capacity is based on THHN wire sizes Pure 8 _ 0 9 8 mm or 1 8 punta tipo cabinet PN12c PN12cSS Zapatas de
10. ROJO ninguna terminal rotulada se aplica 3 6 T3 AZUL aun conductor de color espec fico Modelos PN7c PN12c 1 a 6 Conductores de l nea energizada ninguna terminal rotulada se aplica a un conductor de color espec fico dla a 417 cable dejando una adecuada longitud de los conductores Remueva el aislamiento de los conductores de acuerdo a lo indicado en la Tabla 4 Cuando aplique afloje los tornillos de la terminal pero no totalmente solo para permitir la entrada del conductor Inserte el conductor hasta el fondo en su terminal correspondiente y apriete las terminales de acuerdo al torque indicado en la Tabla 5 Ensamble el tomacorriente clavija junto con el empaque de color en la caja con los tornillos apropiados Dimensiones de Barrenos para Montaje Especial En aplicaciones en donde se requiere montaje especial a un panel o caja los barrenos y la distancia entre ellos deber n de hacerse de acuerdo con el diagrama y la tabla siguiente Tabla 7 Dimensiones de Barrenos para Montaje Especial 1 65 22 2 22 E OPERACI N AVISO Para mantener la protecci n IP de los productos PN requerida en instalaciones especiales se deber de utilizar sellos a prueba de agua en las cabezas de los Desconexi n Para abrir el circuito y remover la clavija Presione el gatillo aplique fuerza hacia el tomacorriente y gire la clavija 20 en sentido de las manecillas del reloj La clavija
11. compresi n soldables Ensamble Desensamble Montaje de Tomacorriente Clavija en Caja Inserte el cable a trav s de la caja de pared y c rtelo dejando una adecuada longitud Retire la cubierta del Conexiones Punta a Punta Para m s informaci n visite www becma ch INSPN G
12. icado de acuerdo con las normas el ctricas aplicables locales y nacionales Antes de iniciar verifique que el circuito est desenergizado que el rango del producto es el apropiado para la aplicaci n que los conductores cumplan con la normatividad vigente y que se encuentren dentro de la capacidad de Dispositivo Contacto PN12c PN12cSS 10 Torques para los Tornillos de las Terminales Las terminales de conexi n est n asistidas por resorte arillo de seguridad para evitar que se aflojen los cables debido a vibraci n asentamiento o ciclo t rmico AVISO No se deber de dar un apriete excesivo a las mismas Herramientas apropiadas y torques espec ficos son indicados en la Tabla 5 contra el hombro del contacto NOTA El aislante debe de ser aplicado en el dispositivo para mantener el aislamiento Ver fotograf a Con una pistola de aire caliente con rango de 600 F a 950 F Aplique calor uniformemente alrededor de los 360 del aislamiento hasta que se encoja sobre la terminal y el cable a Ensamble de los Contactos PN12c Una vez cableados los contactos se deben insertar en la parte trasera en el orificio correspondiente de la base aislante La parte trasera del tomacorriente o la clavija es desconectada antes de ensamblar Para Aplicaci n Tipo EXTENSI N Inserte el cable a trav s de la manija y el empaque Remueva la cubierta del cable para proveer una longitud viable de los conductores
13. ing the conductors to the plug and receptacle Wiring must be made according to all applicable local and national electrical codes Check that the rating is correct for the installation Follow the conductor coding and terminal markings detailed in Table 6 WARNING This product must be electrically grounded A grounding terminal is provided on all metal accessories with a green screw and a washer For Screw Type Terminals Insert cable through handle and strip cable jacket to adequate length The cable jacket should extend at least 1 2 into handle Back out terminal screws only far enough for conductor to clear Strip each conductor per Table 4 Twist the strands of each conductor together and insert fully into the terminal Tighten terminal screws to torques indicated in Table 5 PN12c Crimped Soldered Terminal Wire Connections 1 Strip each conductor to 25 64 inches 10 mm 2A For 18 16 AWG wires insert Ferrule into contact 2B For 14 AWG Wires max the Ferrule is not required 3 Insert stripped wire end into Ferrule or contact Perform either step 4 or 5 4A 18 16 AWG Wires For Crimping the Contacts use either North American Contact Crimping Tool 4CN30 using crimping slot 12 10 or Crimp contact with European Contact Crimping Tool 61 CA500 using 4 MM slot 4B 14 AWG Wires For Crimping the Contacts use either North American Contact Crimping Tool 4CN30 using crimping slot 8 or Crimp contact with Eur
14. itting Deposits of dust or debris can be rubbed off the contacts with a clean cloth NOTICE Under no circumstances should the contact surfaces be filed since this will remove the silver nickel butt contact tip and degrade the contact consistency Sprays should not be used since they tend to collect dirt If any significant pitting of the contacts or other serious damage is observed the device should be replaced Receptacle contacts may be inspected by qualified personnel This should only be done with the power disconnected Any repair or service must be performed with genuine Meltric parts only MANUFACTURER S RESPONSIBILITY Meltric s responsibility is strictly limited to the repair or replacement of any product that does not conform to the warranty specified in the purchase contract Meltric shall not be liable for any penalties or consequential damages associated with the loss of production work profit or any financial loss incurred by the customer Meltric Corporation shall not be held liable when its products are used in conjunction with products not bearing the Marechal technology trademark The use of Meltric products in conjunction with mating devices that are not marked with the Marechal technology trademark shall void all warranties on the product Meltric Corporation is a member of the international association BECMA the Butt contact Electrical Connectors Manufacturers Association For more informati
15. la clavija 5 Los contactos hembra consisten de una trenza flexible y un resorte y son insertados con la punta del contacto en la parte posterior del tomacorriente con tapa 6 En cada perforaci n no usada inserte los tapones proporcionados por la parte frontal de la base aislante AVISO Si un nuevo tomacorriente clavija es conectado a un dispositivo existente ponga particular atenci n al n mero de contactos y su posici n numerada en el tomacorriente clavija La continuidad no se obtendr a menos que todos los contactos macho y hembra est n acoplados de manera uniforme Desmontaje de Contactos PN12c 1 Para remover los contactos de la base aislante debe de usar la Herramienta de Extracci n Multi Contact 9 LD 12 37 Desde la parte frontal de la base aislante deslice la herramienta de extracci n en el contacto 2 Presione hasta que el contacto salga por la parte posterior de la base aislante 3 AVISO Cada contacto est dise ado para ser removido un m ximo de 3 veces Se deber n de usar nuevos contactos si son removidos m s de 3 veces Tabla 6 C digo de Conductores y Marcas en Terminales Codigo en Terminal en Terminal Funci n G E GND Conductor Verde verde con raya amarilla solo para aterrizar el equipo Blanco gris sistema neutro aterrizado solo conductor del neutro N Modelos PN20 PN30 PN20HT PN30HT 1 R1 NEGRO Conductores l nea energizada 2 S2
16. mpio AVISO Bajo ninguna circunstancia la superficie de los contactos podr lijarse ya que se remover a la Plata N quel de los contactos punta a punta degradando la consistencia del contacto Aerosoles no deben ser utilizados por que atraen suciedad Si hay un desgaste severo en los contactos o cualquier otro da o serio el dispositivo deber de ser reemplazado cuatro tornillos de montaje y deben ser retenidos por una rondana de presi n y una tuerca en el interior de la caja de conexiones o el tablero Alternativamente 4 barrenos ciegos pueden ser taladrados y o roscados para insertar los 4 tornillos de montaje la Manija para asegurar una sujeci n firme del cable la perforaci n de la parte superior de la terminal y permita que penetre por acci n capilar D jelo enfriar sin aplicar ning n esfuerzo mec nico 6 Deslice la funda termo contr ctil hasta que tope Tabla 1 Clasificaciones Generales PN12 PN7 PN20 PN30 MN ENSAMBLE Verifique que la alimentaci n el ctrica ha sido Interrupci n y le e corriente Voltaje 600VAC 600VAC 600VAC 600VAC Frecuencia 50 400 Hz 50 400 Hz 50 400 Hz 50 400 Hz Clasificaci n IP66 67 IP66 67 IP66 IP67 IP66 IP67 medioambiental 1P54 1P55 1P54 1P55 PN20HT y PN30HT son para interrupci n de corriente hasta 480 V y su rango ambiental es IP44 INSTALACI N Los tomacorrientes y clavijas de la Serie PN deben ser instalados por un electricista calif
17. necesaria 3 Inserte el cable sin aislamiento dentro de la zapata tipo casquillo la terminal del contacto Efect e uno de los pasos 4 6 5 4A Cables Calibre 18 16 AWG Para comprimir las terminales de los contactos use una herramienta de compresi n para terminales Americanas 4CN30 Use la ranura 12 10 use una herramienta de compresi n para terminales europea 61 CA500 Use la ranura 4mm 4B Cable Calibre 14 AWG Para comprimir las terminales de los contactos use una herramienta de compresi n para terminales Americana 4CN30 Use la ranura 8 use una herramienta de compresi n para terminales europea 61 CA500 Use la ranura 4mm 5 AVISO Soldar el conductor en la terminal fuera de la base aislante interior del dispositivo para evitar da os Use soldadura de esta o y un caut n de 50 W caliente la terminal por aproximadamente 30 segundos Al calentarlo aplique la soldadura en 1 AVISO Antes de insertar un contacto en la base aislante favor de revisar el esquema de numeraci n de los contactos en la base aislante de tal forma que el contacto de tierra y todos los contactos se coloquen en el orificio correcto 2 Empuje el contacto cableado en la base aislante hasta su posici n correcta y se asiente en su lugar 3 Aseg rese que el contacto se monto correctamente tirando levemente de el 4 El contacto macho es s lido en toda su longitud y se inserta con la punta del contacto en la parte posterior de
18. on visit www becma ch INSPN G PNZ e o PN20 INSPN G Meltric Corporation 4640 Ironwood Drive Franklin WI 53132 Tel 800 433 7642 Fax 414 817 6161 e mail mailfdmeltric com Fabricante de productos bajo la tecnologia Marechal meltric com MELTRIC A GENERAL La serie PN de tomacorrientes y clavijas para servicio est ndar fueron dise adas para ofrecer incremento en la seguridad durabilidad y un desempe o estable en las conexiones el ctricas Favor de seguir las siguientes instrucciones para asegurar la correcta instalaci n y mantenimiento de este producto Hay peligros inherentes con los 42 ADVERTENCIA productos el ctricos El no siguir las precauciones de seguridad puede resultar en lesiones grandes o muerte Estas instrucciones deben ser seguidas para mantener una segura y apropiada instalaci n uso y mantenimiento de los productos Meltric Antes de instalar desconecte todas las fuentes al circuito para eliminar el riesgo al shock el ctrico M RANGos Los tomacorrientes y clavijas PN7 PN20 Y PN30 de MELTRIC est n clasificadas de acuerdo a las normas UL1682 CSA 22 2 N 182 1 e IEC 60309 1 La PN12c est clasificada de acuerdo a la norma IEC 60309 1 Los rangos de amperaje voltaje y rangos ambientales se indican en la tabla N 1 Tabla 3 Gu a para NPT en Pulgadas Rango de Cable 062 0 50 187 0 75 ATTO 890 1650 1125 2438 1750 2565 Solo para PN12cSS 750 1375
19. onmental rating is IP44 E INSTALLATION A PN Series plugs and receptacles should be installed by a qualified person in accordance with all applicable local and national electrical codes Before starting verify that the power has been disconnected all product ratings are appropriate for the application and the conductors meet code requirements and are within the capacities of the terminals noted in Table 2 NPT Guidelines are detailed in Table 3 Table 2 Wiring Terminal Capacity in AWG Model Wire Size Min Wire Size Max PN 20 30 Ca IEA PN 20HT 30 HT pt 8 Capacity is based on THHN wire sizes 187 0 75 890 1 650 1 125 2 438 PN12cSS only General Notes amp Precautions 1 This product must be installed by a certified personnel 2 NOTICE Do not tin terminal wire ends 3 NOTICE Do not use moisture repellent sprays on the contacts 4 Do not back terminal screws fully out 5 Self tapping screws are provided for use with some polymeric accessories High torque may be required to drive them in NOTICE Once they are seated care should be taken in order to avoid over tightening them against the plastic material 6 NOTICE Meltric threaded handles come with tapered style threads The use of fitting seal tape is recommended to maintain watertightness of all NPT fittings and joints 7 Various handles and cord grip options may be used These instructions are based on handles pro
20. opean Contact Crimping Tool 61 CA500 using 4 MM slot 5 NOTICE Soldering of the wire into the contact must be performed with the contact out of the Interior Insulator to prevent damage to the insulator Using tin solder and a 50W soldering iron heat the terminal for approximately 30 seconds While heating apply the soldering wire into the hole at the bottom of the terminal and let it penetrate by capillary action Let it cool down without any mechanical stress 6 Slide the Heat Shrink Insulation Sleeve over the contact until it butts up against the contact shoulder NOTE Sleeve must be applied see picture 7 With a Heat Gun that has a temperature range of 600 F to 950 F apply heat evenly 360 around the sleeve until it shrinks around the contact and wire a Assembly of PN12c Contacts Once wired the contacts must be inserted into the rear of their respective insulating block The rear side of the inlet plug or receptacle connector is considered as the flat surface of the 4 bolt hole mounting surface Assembly Disassembly 1 NOTICE Before insertion of a contact into an insulator please review the insulator s contact numbering scheme so the ground and each contact phase is placed into the proper hole 2 Push the wired contact into the insulating block until it stops and snaps into place 3 Ensure its correct mounting by slightly pulling on the contact 4 The male contacts are solid
21. ounterclockwise CCW The contacts will mate and the circuit will close Disconnection To open the circuit and remove the plug press the pawl apply inward force and rotate the plug 20 clockwise CW The plug can be safely withdrawn from the receptacle The plug contacts remain shrouded until after the circuit is disconnected Close protective plug cap to prevent contamination by dirt dust or other debris LOCKOUT PROVISIONS The plug cap can be locked with a locking pawl except PNHT or PN12cSS Screw Plug inserted or cap closed turn the 5 16 screw with an Allen key until it reaches the bottom NOTICE Do not over tighten MAINTENANCE Before inspecting repairing or A WARNING maintaining Meltric products disconnect electrical power to the receptacle to eliminate the risk of electrical shock Meltric products require little on going maintenance However it is a good practice to periodically perform the following general inspections e Check the mounting screws for tightness e Verify that the weight of the cable is supported by the strain relief mechanism and not by the terminal connections e Check the IP gaskets for wear and resiliency In wet wash down environments the gaskets should be inspected periodically 6 months for wear and hardness Replace gaskets as needed e Verify the electrical continuity of the ground circuit every 6 months e Check the contact surfaces for cleanliness and p
22. vided with integral multi layer bushing cord grips 8 If the plug and receptacle are stainless steel then stainless steel accessories must be used E ENVIRONMENTAL Optimum operating conditions are achieved by installing IP66 IP67 plugs and receptacles with the latch at the top NOTICE To prevent water ingress non watertight plugs and receptacles must always face downwards when not mated Wire Strip Length Wire strip lengths are indicated in Table 4 Strip lengths for cable sheathing will depend on the specific application When used with handles the cable sheathing should extend into the handle to ensure secure cord gripping n cable Table 4 Wire Strip Lengths Dimension A PN20HT 30HT PN7c ans 8 so 8 PN12c PN12cSS Terminal Screw Tightening Torques Device Contact PN20 30 The wiring terminals are spring assisted to prevent loosening due to wire strand settlement vibration and thermal cycling NOTICE Avoid over tightening Appropriate tools and tightening torques are indicated in Table 5 Table 5 Terminal Screw Tightening Torques Required Screwdriver Device Contact or Allen Wrench PN20 30 3 mm or 1 8 precision tip N7c PN12c PN12cSS Wiring the Terminal Connections 3 mm or 1 8 precision tip crimp solder type terminals lbs Nem ic e fos PN20HT 30HT 8 0 9 3 mm or 118 precision tp e Jos precisi ED Verify that power has been disconnected prior to A wir

Download Pdf Manuals

image

Related Search

Related Contents

Oricom TP9 User's Manual  Manuale d`uso  Guide d`instruction (17 ko, PDF)  Victory Refrigeration ACRS-ID-S-STS User's Manual  廃棄物処理基準等専門委員会 資料4-3 平成23年8月11日  Voluviz - FFI rapporter - Forsvarets forskningsinstitutt  Goodmans GD11FVRSD32 Digital Camera User Manual  GBC Laminating Carriers  Auszug aus dem Benutzerhandbuch Diamond Cut 8  SERVICE MANUAL  