ERITECH® INTERCEPTOR SI Instruction Manual
Contents
1. Material Mast height 2m 3m 4m 5m 6m 7m 8m INTCPTADM116UN ER1 1000 SS ER1 2000 SS ER2 2000 SS ER2 3000 SS ER3 2000 SS ER3 3000 SS ER2 BASE SS ER3 BASE SS GUYKIT 4 GUYKIT 7 CABTIE SS 6 9 9 18 18 Notes For masts of 2 to 3 meters above the roof plane 1m lower cantilever section with 2 mounting brackets are required For masts of 4 to 6 meters above the roof plane 2m lower cantilever section with 3 mounting brackets are required The downconductor should connect at the bottom of the upper mast section e CABTIE SS are installed 3 per meter to strap the downconductor to the remaining length of lower mast Other items required per standards Downconductor s fixing s protective sleeve s earth test clamp s Lightning Event Counter and grounding system ER1 1000 SS ER1 2000 SS AL Y ER2 2000 SS ER2 3000 SS ER3 2000 55 ER3 3000 55 ou OR mes co ER2 BASE ER3 BASE Standard Mounting Method 2 8 m D INTCPTADM116UN v ER2 2000 5S ER2 3000 5S ER3 2000 SS ER3 3000 SS y ER2 BASE ER3 BASE Alternative Mounting Method 2 6 m Requires INTCPTADM116UN gt www erico com ERITECH INTERCEPTOR SI INSTRUCTION MANUAL Support Options Option 1 ERITECH INTERCEPTOR
2. from your ERICO customer service representative 2 ERICO products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings 3 All instructions must be completely followed to ensure proper and safe installation and performance 4 Improper installation misuse misapplication or other failure to completely follow ERICO s instructions and warnings may cause product malfunction property damage serious bodily injury and death SAFETY INSTRUCTIONS All governing codes and regulations and those required by the job site must be observed Always use appropriate safety equipment such as eye protection hard hat and gloves as appropriate to the application www erico com ERICO ERITECH INTERCEPTOR SI INSTRUCTION MANUAL b For Cantilevered Mast 51 25 51 40 51 60 51 25 51 40 51 60 Adapter refer to tj page 6 RS d 1 55 55 LPC580 4 For masts 4 6 m above roof plane 2 m lower cantilever section with 3 mounting brackets For masts 2 3 m above roof plane 1 m lower cantilever section with 2 mounting brackets p NS DOWNCONDUCTOR 5 Refer to your local standard for downconductor number and routing requirements y 4 www erico com ERITECH INTERCEPTOR SI INSTRUCTION MANUAL P For Guyed Mast Adapter refer t
3. D lt lt INTCPTADM116UN Y Y ER2 2000 SS ER2 3000 SS ER3 2000 SS ER3 3000 SS y Y ER2 BASE ER3 BASE M todo de montaje alternativo 2 6 m Requiere INTCPTADM116UN SR www erico com ERITECH INTERCEPTOR SI MANUAL DE INSTRUCCIONES Opciones de apoyo Opci n 1 ERITECH INTERCEPTOR SI conectado a ER2 2000 SS 6 ER2 3000 SS lt ERITECH INTERCEPTOR SI I INTCPT ADM116UN I ER2 2000 55 ER2 3000 SS N pieza INTCPT ADM116UN 702301 Opci n 2 Conexi n de ERITECH INTERCEPTOR SI a un m stil tubular eL ERITECH INTERCEPTOR SI 4 Ve Zm WY lt lt INTCPT ADM3 4UNC Am Nota INTCPT ADM3 AUNC D con roscado 3 4 UNC N pieza INTCPT ADM3 4UNC 702299 Se incluye con ER1 1000 SS y ER1 2000 SS www erico com 15 ERICO i ERITECH INTERCEPTOR SI MANUAL DE INSTRUCCIONES Opcion 3 Nota Si se utiliza un conductor de bajada de cobre aseg rese de que no est en contacto con el m stil de aluminio Se recomienda un conductor de bajada de cobre con aislamiento de PVC Opci n 4 ERITECH INTERCEPTOR SI con m stil de aluminio y conductor de bajada est ndar a ERITECH INTERCEPTOR SI INTCPT ADBUTT ADAPTADOR DE g ELECTRODO DE GE MASTIL A uE TORNILLO DE D 7 SUJECI N lt lt TERMLUGCOUP M STIL TUBULAR DE ALUMINIO ERICO N pieza TERM
4. ERITECH INTERCEPTOR SI fonctionne uniquement lors d activit orageuse Le syst me ne requiert pas d alimentation externe ou de pi ces de remplacement Une contr le r guli r du syst me de protection contre la foudre ERITECH NTERCEPTOR SI est essentiel La v rification doit avoir lieu Apr s chaque foudroiement connu de INTERCEPTOR SI ou suivant la p riodicit d finie par la norme Si la structure a connu un quelconque changement extension ou modification ajout d antenne etc 18 www erico com ERITECH INTERCEPTOR SI MANUEL D INSTALLATION Proc dure de v rification Aucune verification ou maintenance lors de p riodes d orage 1 V rifier que la structure physique du b timent n a pas chang et qu aucune structure suppl mentaire telle qu une antenne panneaux publicitaires antennes paraboliques groupes de maintenance de b timent ou autre n a t install e moins de 2 m sous la pointe de l ERITECH INTERCEPTOR SI 2 Contr ler visuellement l ERITECH INTERCEPTOR SI pour s assurer qu il n est pas endommag physiquement 3 Contr ler la pointe sup rieure au dessus de l ERITECH INTERCEPTOR SI pour s assurer qu il n est pas br l d form ou manquant 4 V rifier que le m t est fermement fix la structure V rifier que les haubans sont bien fix s et ne sont pas endommag s Les remplacer le cas ch ant V rifier que la fixation des d
5. must be less than 10 ohms This should be measured without downconductor s connected and with out interconnection to other grounding systems For full details on installing your ERITECH INTERCEPTOR SI please refer to ERICO s technical notes and the French or Spanish national standards NFC17 102 UNE 21186 It is also recommended to adhere to local standards for relevant local downconductor and grounding requirements Operation and Maintenance The ERITECH INTERCEPTOR SI lightning protection system requires no user operation it is completely automatic in operation The ERITECH INTERCEPTOR SI becomes active only during storm activity The system does not require any external power requirements or replacement components for normal operation e t is essential that the ERITECH INTERCEPTOR SI Lightning Protection System be regularly maintained Maintenance should be undertaken 1 After each known strike to the ERITECH INTERCEPTOR SI or at least once per year 2 If any changes have been made to the structure whether they be structural antennae or building maintenance unit additions etc www erico com ERITECH INTERCEPTOR SI INSTRUCTION MANUAL Maintenance should be undertaken as follows Do not attempt maintenance during potential lightning periods 1 Check that the building is the same physical shape and that no additional structures such as antennae advertising signs satellite
6. AISON HAUTE DU CABLE ERITECH ERICORE ISOLANT FRP R f INTCPT ADBUTT n 702296 24 www erico com ERITECH INTERCEPTOR SI MANUEL D INSTALLATION Option 5 Raccordement de l ERITECH INTERCEPTOR SI un tube de 2 lt E ERITECH INTERCEPTOR SI ota Filetage de tube H standard H britannique INTCPT ADF2NSP NTCPT ADF2BSPF lt OU 2 INTCPT ADF2BSPF Filetage de tube DE 2 standard USA NTCPT ADF2NSP R f INTCPT ADF2BSPF n 702297 2 R f INTCPT ADF2NSP n 702298 WWNW erico com 25 ERICO AUSTRALIA 6 Chilvers Road P O Box 148 Thornleigh Sydney NSW 2120 Australia Phone 61 2 9479 8500 Fax 61 2 9484 9188 BELGIUM Postbus 33 3110 Rotselaar Belgium Phone 32 14 69 96 88 Fax 32 14 69 96 90 BRAZIL R Dom Pedro Henrique de Orleans E Braganca 276 Vila Jaguara S o Paulo CEP 05117 000 Brazil Phone 55 11 3621 4111 Fax 55 11 3621 4066 CANADA P O Box 170 Mississauga Ontario Canada L5M 2B8 Phone 1 800 677 9089 Fax 1 800 677 8131 CHILE Alcantara 200 piso 6 Of 17 Las Condes Santiago Chile Phone 56 2 370 2908 Fax 56 2 370 2914 CHINA Room 1204 Tomson Commercial Building No 710 Dongfang Road Pudong Shanghai P R China 200122 Phone 86 21 5081 3900 Fax 86 21 5831 8177 DENMARK Box 211 201 22 Malm Sweden Phone 46 40 611 13 60 Fax 46 40 611 94 15 FRANCE rue Charles Dalli re BP 31 42161 Andr
7. ECH INTERCEPTOR SI connection to 2 water pipe ERITECH INTERCEPTOR SI INTCPT ADF2NSP OR INTCPT ADF2BSPF P No INTCPT ADF2BSPF P No INTCPT ADF2NSP 702297 702298 www erico com ERICO ERITECH INTERCEPTOR SI MANUAL DE INSTRUCCIONES Este manual es una gu a para la instalaci n funcionamiento y mantenimiento del sistema de protecci n contra descargas atmosf ricas ERITECH INTERCEPTOR SI Se parte del supuesto de que la instalaci n del sistema deber ser realizada por un representante autorizado de ERICO El dise o del sistema incluye Dise o del sistema de puesta a tierra debe dise arse una configuraci n en funci n del an lisis de resistividad del suelo Tendido de conductores de bajada se seleccionar con el objeto de evitar otros servicios mantener un radio de curvatura m nimo y minimizar la longitud del tendido atmosf ricas debe ser inferior a 10 ohmios La medici n debe realizarse sin conectar el o los conductores de bajada y sin interconexi n con otros sistemas de puesta a tierra Consulte informaci n detallada sobre la instalaci n del sistema ERITECH INTERCEPTOR SI en las Notas t cnicas de ERICO y en las normas nacionales francesa y o espa ola NFC17 102 UNE 21186 Asimismo se recomienda cumplir las normas locales sobre requisitos de conductores de bajada y de puesta a tierra del conductor de bajada Requisitos de inmovilizaci n
8. LUGCOUP 701840 ERITECH INTERCEPTOR SI con conductor de bajada ERITECH ERICORE ERITECH INTERCEPTOR SI INTCPT ADBUTT ADAPTADOR DE ELECTRODO DE H La M STIL TORNILLO DE q amp SUJECI N TERMINACI N SUPERIOR DEL CONDUCTOR DE BAJADA ERITECH ERICORE E FRP MAST N pieza INTCPT ADBUTT 702296 16 www erico com ERITECH INTERCEPTOR SI MANUAL DE INSTRUCCIONES Opci n 5 A E ERITECH INTERCEPTOR SI Nota INTCPT ADF2BSPF con roscado de INTCPT ADF2NSP tubo de 2 BS 3 INTCPT ADF2BSPF in TUBO DE 2 INTCPT ADF2BSPF con roscado de tubo de 2 NS EE UU Conexi n del sistema ERITECH INTERCEPTOR SI a tubo de agua de 2 N pieza INTCPT ADF2BSPF 702297 N pieza INTCPT ADF2NSP 702298 www erico com 17 ERICO ERITECH INTERCEPTOR SI MANUEL D INSTALLATION Le pr sent manuel est un guide d installation et d entretien du Syst me de Protection contre la Foudre ERITECH INTERCEPTOR SI Il suppose que le syst me installer a t concu par un repr sentant ERICO agr Le projet du syst me comprendra Une conception de syst mes de mise la terre une configuration devrait tre concue en tenant compte de l analyse Trac du ou des conducteurs de descente choisis pour viter la proximit d autres r seaux pour respecter les rayons de courbure et pour minimiser la longueur du conducteur de descente e Fix
9. RES Instruction Manual ERITECH INTERCEPTOR SI Manual de instrucciones Manuel d installation ERITECH INTERCEPTOR SI Instruction Manual English p 2 9 Espanol p 10 17 Francais p 18 25 mui www erico com ERICO ERITECH INTERCEPTOR SI INSTRUCTION MANUAL This manual is a guide to the Installation Operation and Maintenance of the ERITECH INTERCEPTOR SI Lightning Protection System It assumes that the system to be installed has been designed by an authorized ERICO representative The system design will include e Grounding systems design a configuration should be designed as a result of soil resistivity analysis e Downconductor routes chosen to avoid other services maintain minimum bending radii and minimize down conductor run length Downconductor securing requirements e LPSD CAD analysis design software which determines terminal placement mast amp height requirements as well as protection level calculation All of the above are recommended for a successful installation If there is any doubt about any of the points mentioned please contact ERICO or its nearest representative for clarification Warning Only attempt to install the ERITECH INTERCEPTOR SI during storm free periods The ERITECH INTERCEPTOR SI must be at least two meters higher than any other point on the structure it is intended to protect The resistance of the lightning protection grounding system
10. SI connected to ER2 2000 SS or ER2 3000 SS lt ERITECH INTERCEPTOR SI I INTCPT ADM116UN I ER2 2000 55 ER2 3000 SS P No INTCP ADM116UN 4702301 Option 2 ERITECH INTERCEPTOR SI connection to tubular mast aL ERITECH INTERCEPTOR SI d Ve Zm WY INTCPT ADM3 4UNC gt 5 m lt m lt Note INTCPT ADM3 4UNC EME 3 4 UNC thread P No INTCPT ADM3 AUNC 702299 Supplied with ER1 1000 SS amp ER1 2000 SS www erico com 7 ERICO ERITECH INTERCEPTOR SI Option 3 Note If using copper downconductor ensure this is not in contact with aluminum mast PVC insulated copper is suggested Option 4 INSTRUCTION MANUAL ERITECH INTERCEPTOR SI with aluminum mast and standard downconductor ERITECH INTERCEPTOR SI INTCPT ADBUTT MAST BUTT ADAPTOR LOCKSCREW TERMLUGCOUP ERICO ALUMINUM TUBULAR MAST P No TERMLUGCOUP 701840 ERITECH INTERCEPTOR SI with ERITECH ERICORE s ERITECH INTERCEPTOR SI INTCPT ADBUTT MAST BUTT ADAPTOR 7 w LOCKSCREW ERITECH ERICORE UPPER TERMINATION lt MAST P No INTCPT ADBUTT 702296 8 www erico com ERITECH INTERCEPTOR SI INSTRUCTION MANUAL Option 5 Note INTCPT ADF2BSPF 2 British Standard Pi thread pe INTCPT ADF2NSP 2 USA National Standard Pi thread pe ERIT
11. ations adapt es du conducteur de descente et respect des distances de s curit Logiciel de conception LPSD CAD qui d termine l emplacement du paratonnerre les hauteurs de m t en fonction du niveau de protection est conseill de suivre les points pr cedents pour une installation r ussie En cas de doute concernant ce qui pr c de veuillez contacter ERICO ou son repr sentant le plus proche pour tout claircissement Attention Toute installation de l ERITECH INTERCEPTOR SI doit uniquement se faire lors de p riodes non orageuses L ERITECH INTERCEPTOR SI doit se trouver au moins deux m tres au dessus de tout autre point sur la structure qu il doit prot ger La r sistance de la prise de terre du syst me de protection contre la foudre doit tre inf rieure 10 ohms Cette mesure doit s effectuer en d connectant tous les conducteurs de descente et toute interconnexion avec d autres r seaux de terre Pour de plus amples informations concernant installation de votre ERITECH INTERCEPTOR SI veuillez vous reporter aux notes techniques et aux normes nationales fran aises ou espagnoles NFC17 102 UNE 21186 Il est galement conseill de respecter les normes locales pour les conducteurs de descente appropri s et les exigences de mise la terre Fonctionnement et maintenance Le syst me de protection contre la foudre ERITECH INTERCEPTOR SI fonctonne de mani re enti rement autonome L
12. blage des m ts 2 6 m N cessite l adaptateur INTCPTADM116UN www erico com ERITECH INTERCEPTOR SI MANUEL D INSTALLATION Adaptateurs de m t Option 1 ERITECH INTERCEPTOR SI reli ER2 2000 SS ou ER2 3000 SS lt ERITECH INTERCEPTOR SI I INTCPT ADM116UN I ER2 2000 55 ER2 3000 SS R f INTCP ADM116UN n 702301 Option 2 Raccordement de l ERITECH INTERCEPTOR SI un m t filet 3 4 UNC eL ERITECH INTERCEPTOR SI d Ve Zm WY INTCPT ADM3 4UNC gt 5 m lt m lt Nota INTCPT ADM3 4UNC E CONDUCTEUR 3 4 filetage UNC R f INTCPT ADM3 4UNC n 702299 Fourni avec ER1 1000 SS amp ER1 2000 SS www erico com 23 ERICO i ERITECH INTERCEPTOR SI MANUEL D INSTALLATION Option 3 UERITECH INTERCEPTOR SI avec mat en aluminium et conducteur de descente standard ERITECH INTERCEPTOR SI Nota Y INTCPT ADBUTT En cas d utilisation ee ADAPTATEUR d un conducteur de D EXTR MIT DE M T descente en cuivre VIS DE BLOCAGE s assurer qu il n est pas en contact avec lt Velo eraot le m t en aluminium ll est conseill d utiliser du cuivre NT UE EU ay ALUMINIUM ERICO isol en PVC R f TERMLUGCOUP n 701840 Option 4 ERITECH INTERCEPTOR SI avec cable ERITECH ERICORE ERITECH INTERCEPTOR SI INTCPT ADBUTT ADAPTATEUR a D EXTR MIT DE MAT 7 w VIS DE BLOCAGE 44 TERMIN
13. del conductor de bajada e LPSD software de an lisis de dise o CAD que determina la ubicaci n de terminales los requisitos del m stil y su altura y los c lculos de nivel de protecci n Todo lo mencionado es parte de nuestra recomendaci n para una instalaci n correcta En caso de duda acerca de alguno de los puntos mencionados consulte a ERICO o al representante m s pr ximo Advertencia el sistema ERITECH INTERCEPTOR SI no debe instalarse durante per odos de tormentas El sistema ERITECH INTERCEPTOR SI debe ser como m nimo dos metros m s alto que cualquier otro punto de la estructura que est previsto proteger La resistencia del sistema de puesta a tierra para la protecci n contra descargas Funcionamiento y mantenimiento El sistema de protecci n contra descargas atmosf ricas ERITECH INTERCEPTOR SI no requiere ninguna operaci n por parte del usuario ya que su funcionamiento es totalmente autom tico e El sistema ERITECH INTERCEPTOR SI se activa solamente en caso de tormenta e Para su funcionamiento normal el sistema no requiere alimentaci n externa ni el empleo de componentes de recambio Es esencial someter al sistema de protecci n contra descargas atmosf ricas ERITECH INTERCEPTOR SI a un programa de mantenimiento peri dico El mantenimiento debe realizarse 1 Cada vez que tenga conocimiento de que el sistema ERITECH INTERCEPTOR SI recibi una descarga o al menos una vez a
14. dishes building maintenance units or similar have been installed within 2 m 80 in height of the ERITECH INTERCEPTOR SI 2 Inspect the ERITECH INTERCEPTOR SI to ensure that it is not dented or physically damaged in any way 3 Inspect the finial tip on top of the ERITECH INTERCEPTOR SI to ensure that it is not excessively burnt deformed or missing 4 Check that the mast is securely attached to the structure Check that the guys are secure and undamaged Replace if necessary Check that all fastenings are secure and tight 5 Look for signs of damage to the downconductor whether by lightning careless handling vandalism or other causes 6 Check that the Lightning Event Counter is secure if the display is registering a reading then record the reading and date 7 Ensure the grounding resistance is less than 100 8 Check the continuity of all bonding conductors Installation Instructions The recommended order of installation is as follows 1 Full installation of the grounding system 2 Full installation of the downconductor 3 Termination of the downconductor to the grounding system 4 Terminate the top of the downconductor to the ERITECH INTERCEPTOR SI mast 5 Raise the mast into position and secure WARNING 1 ERICO products shall be installed and used only as indicated in ERICO product instruction sheets and training materials Instruction sheets are available at www erico com and
15. e 46 40 611 13 60 Fax 46 40 611 94 15 SWITZERLAND Postfach 54 3280 Murten Switzerland Phone 00 800 5000 1090 Fax 00 800 6000 1090 THAILAND 163 Ocean Insurance Bldg 16th Fl Unit B Surawongse Road Bangrak Bangkok 10500 Thailand Phone 66 2 634 1692 Fax 66 2 634 1694 UNITED KINGDOM 52 Milford Road Reading Berkshire RG 81 United Kingdom Phone 44 118 955 0900 Fax 44 118 955 0925 UNITED STATES 34600 Solon Road Solon Ohio 44139 US A Phone 1 440 248 0100 Fax 1 440 248 0723 Copyright 62007 ERICO International Corporation All rights reserved CADDY CADWELD CRITEC ERICO ERIFLEX ERITECH and LENTON are registered trademarks of ERICO International Corporation IP79130 A E668IS03EN 0091 7
16. ement suivies pour assurer une installation conforme s curis e et performante 4 Une installation ou une application non conforme un mauvais usage ou tout autre manquement au respect des instructions et avertissements ERICO peut provoquer un mauvais fonctionnement des dommages aux quipements des blessures s rieuses et m me la mort INSTRUCTIONS DE SECURITE Toutes les r glements et normes en vigueur l endroit du chantier doivent tre respect s Toujours utiliser un quipement adapt comme des lunettes de protection un casque de chantier des gants suivant l application www erico com 19 ERICO ERITECH INTERCEPTOR SI MANUEL D INSTALLATION b Pour montage en d port mural 5 25 51 40 SI 60 51 25 51 40 51 60 5e reporter la page 22 I nd TMC SS TMC SS Adaptateur LPC580 Pour les m ts de 4 6 m au dessus du toit pr voir 2 m pour la fixation en d port l aide de 3 supports de fixation o CONDUCTEUR DE DESCENTE gt Se reporter aux normes concernant le nombre et le cheminement du ou des conducteurs de descente Pour les m ts de 2 3 m au dessus du toit pr voir 1 m pour la fixation en d port l aide de 2 supports de fixation 20 www erico com ERITECH INTERCEPTOR SI MANUEL D INSTALLATION Pour m t hauban Adaptateur se report
17. er la page 22 A 3 ATL TMC SS TMC SS LPC330 Angle recommand 45 60 CONDUCTEUR DE DESCENTE Se reporter aux normes concernant le nombre et le cheminement du ou des conducteurs de descente lt Mat I 74 ER3 BASE SS Embase support ER2 BASE SS ou D 5 25 SI 40 51 60 Ne pas mettre en tension les c bles de hauban l g rement d tendus Kit de haubanage Les points d encrage ne sont pas fournis avec le KIT de haubanage 4 trous www erico com 21 ERICO ERITECH INTERCEPTOR SI M ts en d port mural Hauteur au dessus du toit 2m 3m 4m 5m 6m Longueur de mat totale 3m 4m 6m 7m 8m INTCPTADM116UN ER1 1000 SS ER1 2000 SS ER2 2000 SS ER2 3000 SS ER3 2000 SS ER3 3000 SS ALOF1 GS 2 2 3 3 3 CABTIE SS 6 9 18 18 Nota Pour des m ts de 2 3 m tres au dessus du toit pr voir 1 m pour la fixation en d port l aide de 2 supports de fixation Pour les m ts de 4 6 m tres au dessus du toit pr voir 2 m pour la fixation en d port l aide de 3 supports de fixation Le conducteur de descente doit se brancher la partie inf rieure de la section du m t sup rieur Les colliers CABTIE SS sont install s raison de 3 par m tre pour attacher le conducteur de descente la lo
18. eras de comprobaci n de puesta a tierra un contador de eventos de descargas el ctricas y el sistema de puesta a tierra M stiles con vientos Material Altura del mastil 2m 3m 4m 5m 6m 7m 8m INTCPTADM116UN H ER1 1000 SS ER1 2000 SS ER2 2000 SS ER2 3000 SS ER3 2000 SS ER3 3000 SS ER2 BASE SS ER3 BASE SS GUYKIT 4 GUYKIT 7 CABTIE SS 6 9 9 18 18 Notas Para m stiles de 2 a 3 metros por encima del plano del techo se requiere una secci n inferior en voladizo de 1 m con dos abrazaderas de montaje Para m stiles de 4 a 6 metros por encima del plano del techo se requiere una secci n inferior en voladizo de 2 m con tres abrazaderas de montaje El conductor de bajada debe conectarse a la parte inferior de la secci n superior del m stil Deben instalarse sujeciones CABTIE SS 3 por metro para fijar el conductor de bajada al resto de la longitud del m stil inferior Otros componentes que requieren las normas son conductores de bajada accesorios manguitos de protecci n abrazaderas de comprobaci n de puesta a tierra un contador de eventos de descargas el ctricas y el sistema de puesta a tierra ER1 1000 SS ER1 2000 SS n Y ER2 2000 SS ER2 3000 55 ER3 2000 SS ER3 3000 SS O BIEN jee co ER2 BASE ER3 BASE M todo de montaje estandar 2 8 m
19. ezieux Bouth on Cedex France Phone 33 4 77 36 54 32 Fax 33 4 77 55 20 10 4 www erico com ji GERMANY 66851 Schwanenm hle Germany Phone 49 6307 918 10 Fax 49 6307 918 150 HONG KONG Unit 1 2nd Floor Block A Po Yip Building 62 70 Texaco Road Tsuen Wan New Territories Hong Kong Phone 852 2764 8808 Fax 852 2764 4486 HUNGARY P f 184 1476 Budapest Hungary Phone 31 13 58 34 547 Fax 31 13 58 35 499 INDONESIA Sampoerna Strategic Square Tower B 19th Fl Jalan Jend Sudirman Kav 45 46 Jakarta 12930 Indonesia Phone 62 21 575 0941 Fax 62 21 575 0942 ITALY A amp B Business Center Via Valla 16 nr 17 20141 Milano Italy Phone 39 02 8474 2250 Fax 39 02 8474 2251 MEXICO Melchor Ocampo 193 Torre A piso 13 Col Veronica Anzures 11300 Mexico D F Mexico Phone 52 55 5260 5991 Fax 52 55 5260 3310 NETHERLANDS Jules Verneweg 75 5015 BG Tilburg Netherlands Phone 31 13 58 35 400 Fax 31 13 58 35 499 NORWAY Postboks 148 1366 Lysaker Norway Phone 47 67 53 12 00 Fax 47 67 12 42 68 IM ds uwullil gt POLAND ul Krzemieniecka 17 54 613 Wroclaw Poland Phone 48 71 374 40 22 Fax 48 71 374 40 43 SINGAPORE Jurong Industrial Estate 16 Wan Lee Road Singapore 627 946 Phone 65 6 268 3433 Fax 656 268 1389 SPAIN C Provenza 288 Pral 08008 Barcelona Spain Phone 34 93 467 7726 Fax 34 93 467 7725 SWEDEN Box 211 201 22 Malm Sweden Phon
20. iff rents composants et les protections m caniques sont en bon tat 5 Rechercher tout signe d endommagement sur le conducteur de descente caus par le foudroiement la n gligence le vandalisme ou autres 6 V rifier que le Compteur de coups de foudre est bien fix v rifier l indication de l cran l enregistrer ainsi que la date 7 S assurer que la r sistance de la prise de terre est inf rieure 10 O 8 V rifier la continuit de tous les conducteurs et liaisons quipotentielles ainsi que les distances de s curit Instructions d installation L ordre d installation conseill est le suivant 1 Installation compl te du syst me de mise la terre 2 Installation compl te du conducteur de descente 3 Raccordement du conducteur de descente au syst me de mise la terre 4 Dresser le m t sur son emplacement et le fixer 5 Raccorder la partie sup rieure du conducteur de descente au m t ERITECH INTERCEPTOR SI AVERTISSEMENT 1 Les produits ERICO seront install s et utilis s conform ment aux notices techniques et documents de formation Des fiches techniques sont disponibles sur www erico com et aupr s de nos repr sentants commerciaux 2 Les produits ERICO ne doivent jamais tre utilise pour un autre usage que celui pr vu par leur conception ou d une mani re exc dant les valeurs limites de charge et de r sistance 3 Toutes les instructions doivent tre scrupuleus
21. l a o 2 En caso de haberse realizado cualquier modificaci n en la estructura o en las antenas o bien si se han a adido unidades al edificio 10 www erico com ERITECH INTERCEPTOR SI MANUAL DE INSTRUCCIONES El mantenimiento debe realizarse del siguiente modo No intente realizar ninguna tarea de mantenimiento durante periodos en los que exista la posibilidad de descargas atmosf ricas 1 Compruebe que el edificio mantenga la misma forma fisica y que no se hayan agregado estructuras adicionales como antenas vallas publicitarias antenas de sat lite unidades de mantenimiento adicionales o similares a una altura de 2 metros 80 pulgadas por encima del sistema ERITECH INTERCEPTOR SI 2 Inspeccione el sistema ERITECH INTERCEPTOR SI para asegurarse de que no haya sufrido ningun da o 3 Inspeccione el extremo del sistema ERITECH INTERCEPTOR SI para verificar que no est excesivamente quemado o deformado o que falte alg n componente 4 Compruebe que el m stil est firmemente fijado a la estructura Verifique que los vientos est n firmes y no presenten da os Sustituyalos si fuese necesario Compruebe que todas las sujeciones est n seguras y apretadas 5 Observe indicios de da os en el conductor de bajada sea por descargas manipulaci n indebida vandalismo u otras causas 6 Compruebe que el contador de eventos de descargas atmosf ricas est firmemente instalado Si la pantal
22. la registra alguna lectura apunte su valor y la fecha 7 Aseg rese de que la resistencia de la puesta a tierra sea inferior a los 10 Q 8 Verifique la continuidad de todos los conductores de empalme Instrucciones de instalaci n El orden recomendado de la instalaci n es el siguiente D 1 Instalaci n comp a tierra a del sistema de puesta 2 Instalaci n completa del o de los conductores de bajada 3 Conexi n terminal del conductor de bajada al sistema de puesta a tierra 4 Conexi n terminal del extremo del conductor de bajada al m stil del sistema ERITECH INTERCEPTOR SI 5 Instale el m stil en su posici n e inmovil celo ADVERTENCIA 1 Los productos de ERICO deben ser instalados y utilizados seg n se indica en sus instrucciones y en el material de formaci n de ERICO Tiene las instrucciones a su disposici n en www erico com y tambi n se las puede solicitar a su representante del servicio de atenci n al cliente 2 Los materiales ERICO nunca han de utilizarse de otro modo que aquel previsto en su dise o o sobrepasando los valores limite de carga y de resistencia 3 Todas las instrucciones se han de seguir perfectamente para asegurar una instalaci n conforme segura y eficiente 4 Instalar inadecuadamente los productos hacer mal uso de ellos aplicarlos de manera incorrecta en general no seguir al detalle las instrucciones y advertencias de ERICO podr a derivar e
23. n un funcionamiento incorrecto del producto da os a la propiedad graves lesiones corporales e incluso la propia muerte INSTRUCCIONES DE SEGURIDAD Todos los reglamentos as como todas las normativas vigentes en el lugar de la obra han de ser respetados Siempre se ha de utilizar un equipo adaptado como gafas de protecci n casco guantes seg n la aplicaci n www erico com 11 ERICO ERITECH INTERCEPTOR SI MANUAL DE INSTRUCCIONES b Mastil en voladizo 5 25 51 40 SI 60 51 25 51 40 51 60 Adaptador consulte la y p gina 14 Ya I nd TMC SS TMC SS LPC580 Para m stiles de 4 6 m por encima del plano del techo una secci n inferior en voladizo de 2 m con tres abrazaderas de montaje Para m stiles de 2 3 m por encima del plano del techo una secci n inferior en voladizo de 1 m con dos abrazaderas de montaje CONDUCTOR DE Ts y Consulte en las normas locales los requisitos de n mero de conductores de bajada y tendido de los mismos y 12 www erico com ERITECH INTERCEPTOR SI MANUAL DE INSTRUCCIONES b Para m stil sujetado con vientos Adaptador consulte la p gina 14 YA Le Es TMC SS TMC SS LPC330 ngulo preferente de 45 a 60 CONDUCTOR DE BAJADA Consulte en las normas locales los req
24. ngueur restante du m t inf rieur Autres articles n cessaires selon les normes Conducteur s de descente fixation s fourreau x de protection joint s de contr le de la prise de terre compteur de coups de foudre et prise de terre M ts hauban s Mat riel Hauteur du m t 2m 3m 4m 5m 6m 7m 8m INTCPTADM116UN e ER1 1000 SS ER1 2000 SS ER2 2000 SS ER2 3000 SS ER3 2000 SS ER3 3000 SS ER2 BASE SS ER3 BASE SS GUYKIT 4 GUYKIT 7 CABTIE SS 6 9 9 18 18 Nota Le conducteur de descente doit se brancher la partie inf rieure de la section du m t sup rieur Les colliers CABTIE SS sont install s raison de 3 par m tre pour attacher le conducteur de descente la longueur restante du m t inf rieur Autres articles n cessaires selon les normes conducteur s de descente fixation s fourreau x de protection joint s de contr le de la prise terre compteur de coups de foudre et prise de terre MANUEL D INSTALLATION ER1 1000 SS ER1 2000 SS Y AL ER2 2000 SS ER2 3000 SS ER3 2000 SS ER3 3000 SS ou OU a ER2 BASE ER3 BASE Assemblage des m ts 2 8 m D lt INTCPTADM116UN Y Y ER2 2000 SS ER2 3000 SS ER3 2000 SS ER3 3000 SS y Y ER2 BASE ER3 BASE Assem
25. o page 6 TMC SS TMC SS LPC330 Preferred Angle 45 60 DOWNCONDUCTOR 9 Refer to your local standard for downconductor number and routing requirements D 5 25 51 40 51 60 MAST Do not over tension Guy Wires slightly sagging Anchor Points not supplied with GUYKIT Support Base ER2 BASE SS or A ER3 BASE SS www erico com ERICO ERITECH INTERCEPTOR SI INSTRUCTION MANUAL Cantilevered Masts Height above roof plane 2m 3m 4m 5m 6m Total mast length 3m 4m 6m 7m 8m INTCPTADM116UN ER1 1000 SS ER1 2000 SS ER2 2000 SS ER2 3000 SS ER3 2000 SS ER3 3000 SS ALOF1 GS 2 2 3 3 3 CABTIE SS 6 9 18 18 Notes For masts of 2 to 3 meters above the roof plane 1 m lower cantilever section with 2 mounting brackets are required For masts of 4 to 6 meters above the roof plane 2 m lower cantilever section with 3 mounting brackets are required The downconductor should connect at the bottom of the upper mast section CABTIE SS are installed 3 per meter to strap the downconductor to the remaining length of lower mast Other items required per standards Downconductor s fixing s protective sleeve s earth test clamp s Lightning Event Counter and grounding system Guyed Masts
26. uisitos de n mero de conductores de bajada y tendido de los mismos D 5 25 51 40 51 60 lt M STIL NO tense en exceso los vientos deben quedar ligeramente flojos Kit de vientos El kit de vientos no incluye puntos de anclaje Base de apoyo ER2 BASE SS o bien A ER3 BASE SS 4 orificios de www erico com 13 ERICO ERITECH INTERCEPTOR SI MANUAL DE INSTRUCCIONES Mastiles en voladizo Altura sobre el plano del techo 2m 3m 4m 5m 6m Longitud total del mastil 3m 4m 7m 8m INTCPTADM116UN ER1 1000 SS ER1 2000 SS ER2 2000 SS ER2 3000 SS ER3 2000 SS ER3 3000 SS ALOF1 GS 2 2 3 3 3 CABTIE SS 6 9 18 18 Notas Para m stiles de 2 a 3 metros por encima del plano del techo se requiere una secci n inferior en voladizo de 1 m con dos abrazaderas de montaje Para m stiles de 4 a 6 metros por encima del plano del techo se requiere una secci n inferior en voladizo de 2 m con tres abrazaderas de montaje El conductor de bajada debe conectarse a la parte inferior de la secci n superior del m stil Deben instalarse sujeciones CABTIE SS 3 por metro para fijar el conductor de bajada al resto de la longitud del m stil inferior Otros componentes que requieren las normas son conductores de bajada accesorios manguitos de protecci n abrazad
Download Pdf Manuals
Related Search
Related Contents
Service Manual / Manuel de Service 36” Slip Roll Rouleaux 36” Navigocorpus Manuel d`utilisation Cables Direct CDEX-222 ADJ - Mystic LED user manual - Premier Lighting and Production Westinghouse 7214100 Installation Guide Dominion Stores Ltd. se désiste en Cour Suprême AT100E 取扱説明書 Rheem Classic Series: Package Dual Fuel Specification Sheet CLC Genomics Workbench Prime-Line D 1548 Instructions / Assembly Copyright © All rights reserved.