Home
Installation Manual
Contents
1. 9 Positive static pressure Negative static pressure Figure 4 11 A combustion blower is used to extract the combustion gases from the firebox This causes a negative pressure in the firebox and a positive pressure in the venting system as shown in Figure 4 11 The longer the vent pipe and more elbows used in the system the greater the flow resistance The recommended maximum flue lengths for the P Series Pellet Stove are as follows 4 Stainless Steel Flex 30 Lineal ft Vertical 4 PL Vent Pipe 4 PI Vent Pipe 30 Lineal ft Vertical 4 PI Vent Pipe 14 ft Vertical w 1 90 and 4 lineal ft horizontal If additional 4 PL Vent fittings are required the overall length must be reduced by Vertical 90 or T 2 5 Vertical 45 1 5 Horizontal 90 or T 5 0 Horizontal 45 2 5 3 PL Vent Pipe 20 Lineal ft vertical 8 Lineal ft vertical w 1 90 amp 4 lineal ft horizontal If additional 3 PL Vent fittings are required the overall length must be reduced by Vertical 90 or T 2 0 Vertical 45 1 0 Horizontal 90 or T 4 0 Horizontal 45 2 0 Long runs of flex or PL vent pipe installed directly vertical from the flue stub may require more frequent cleaning due to fly ash falling off inside and collecting directly above the combustion blower outlet Any use of horizontal venting will require more frequent cleaning It is the responsibility of the installer to make sure the ent
2. Figure 4 14 17 Harman P Series Installation Manual_R3 2014 ___ 09 14 Outside Air Hearth amp Home Technologies recommend attaching outside air in all installations especially lower level and main floor locations Per national building codes consideration must be given to combustion air supply to all combustion appliances Failure to supply adequate combustion air for all appliance demands may lead to back drafting of those and other appliances When the appliance is side wall vented The air intake is best located on the same exterior wall as the exhaust vent outlet and located lower on the wall than the exhaust vent outlet When the appliance is roof vented The air intake is best located on the exterior wall oriented towards the prevailing wind direction during the heating season The outside air connection will supply the demands of the pellet appliance but consideration must be given to the total house demand House demand may consume some air needed for the stove especially during a power failure It may be necessary to add additional ventilation to the space in which the pellet appliance is located Consult with your local HVAC professional to determine the ventilation demands for your house To install outside air use 3 non combustible flex pipe Figure 4 13 There is a break away hole on the rear panel of the P Series stove which must be removed before connecting the flex pipe Figure 4 12 The pipe s
3. 2014 09 14 3 90 436168i Figure 4 5 Figure 4 6 13 5 Installing into an existing fireplace chimney Figure 4 5 w Full Liner This method provides excellent venting for normal operation This method also provides natural draft in the event of a power failure In some places in the US and Canada it is required that the vent pipe extend all the way to the top of the chimney The pipe or liner inside the chimney should be 4 diameter In this method a cap should also be installed on the chimney to keep out rain Be sure to use approved pellet vent pipe fittings Seal pipe joints with silicone or aluminum tape in addition to the sealing system used by the manufacturer Pipe size should be increased to 4 using this method 6 Installing into an existing chimney Figure 4 6 w Full liner This method provides excellent venting for normal operation This method also provides natural draft in the event of a power failure In some places in the US and Canada it is required that the vent pipe extend all the way to the top of the chimney Seal pipe joints with silicone or aluminum tape in addition to the sealing system used by the manufacturer The pipe or liner inside the chimney should be 4 diameter In this method a cap should also be installed on the chimney to keep out rain Harman P Series Installation Manual_R3 2014 09 14 3 90 436168i C N collar
4. Harman P Series Installation Manual_R3 2014 24 25 Harman P Series Installation Manual_R3 2014 09 14 3 90 436168i 26 Harman a brand Hearth amp Home Technologies Inc 352 Mountain House Road Halifax PA 17032 www harmanstoves com Please contact your Harman dealer with any questions or concerns For the location of your nearest Harman dealer please visit www harmanstoves com Printed in U S A Copyright 2012 Harman P Series Installation Manual_R3 2014 _ 09 14 3 90 436168i
5. Materials that are reported as passing ASTM E 136 Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750 C and UL763 shall be considered non combustible materials F Combustible Materials Specification Materials made of or surfaced with wood compressed paper plant fibers plastics or other material that can ignite and burn whether flame proofed or not or plastered or un plastered shall be considered combustible materials G Electrical Codes 120 VAC 60 Hz Start 4 2 Amps Run 2 8 Amps NOTE Some generator or battery back up systems may not be compatible with the micro processor electronics on this appliance Please consult the power supply manufacturer for compatible systems WARNING Risk of Fire Hearth amp Home Technologies disclaims any responsibility for and the warranty and agency listing will be voided by the below actions DO NOT Install or operate damaged appliance Modify appliance Install other than as instructed by Hearth amp Home Technologies e Operate the appliance without fully assembling all components Overfire Install any component not approved by Hearth amp Home Technologies Install parts or components not Listed or approved e Disable safety switches Improper installation adjustment alteration service or maintenance can cause injury or property damage For assistance or additional information consult a qualified installer service ag
6. 09 14 gt UNPACKING u ot ic epi Pi our eens Ror els Removing Rear Cover Panels Firebriek u s s a buy cheba ge eee be ea cba adka Flame Guide ciin urus eee eee eee ROOM SENSOM 2 pon ta py ees haqa g Low Draft Voltage Adjustment MOOWD 6 Reference Materials A Safety Reminders B Wiring Diagram Contains updated information 3 90 436168i Installation Standard Work Checklist ATTENTION INSTALLER Follow this Standard Work Checklist This standard work checklist is to be used by the installer in conjunction with not instead of the instructions contained in this installation manual Customer Date Installed Lot Address Location of Stove Installer Model Dealer Distributer Serial Number WARNING Risk of Fire or Explosion Failure to install appliance to these instructions can lead to a fire or explosion Appliance Install YES IF NO WHY Required non combustible floor protection Pg 9 Verified clearances to combustible Pg 11 14 Unit is Leveled and secured Venting Chimney Section 4 Pg 11 19 Venting Configuration complies to vent diagrams Venting installed sealed and secured in place with proper clearances Exterior wall roof flashing installed and sealed Terminations installed and sealed Elec
7. Negative pressure in the house will resist this natural draft if not accounted for in the pellet appliance installation Heat rises in the house and leaks out at upper levels This air must be replaced with cold air from outdoors which flows into lower levels of the house Vents and chimneys into basements and lower levels of the house can become the conduit for air supply and reverse under these conditions Outside Air An outside air kit is recommended in all installations The Outside Air Kit must be ordered separately Per national building codes consideration must be given to combustion air supply to all combustion appliances Failure to supply adequate combustion air for all appliance demands may lead to back drafting of those and other appliances When the appliance is roof vented strongly recommended The air intake is best located on the exterior wall oriented towards the prevailing wind direction during the heating season When the appliance is side wall vented The air intake is best located on the same exterior wall as the exhaust vent outlet and located lower on the wall than the exhaust vent outlet The outside air supply kit can supply most of the demands of the pellet appliance but consideration must be given to the total house demand House demand may consume the air needed for the appliance It may be necessary to add additional ventilation to the space in which the pellet appliance is located Consult wi
8. 7 Mashing PL vent manufacturer s firestop spacer and support N Figure 4 7 7 Installing through the ceiling No insulation or other combustible materials are allowed within 3 of the PL vent pipe Through the ceiling vent follow PL vent manufacturers recommendations when using wall and ceiling pass through Seal pipe joints with silicone or aluminum tape in addition to the sealing system used by the manufacturer Note Do not place joints within wall pass through 14 Minimum flue vent configuration It is recommended that outside air be installed with this venting configuration 12 in above ground level Figure 4 8 Area within dotted circle represents the minimum clearance to combustible materials such as shrubbery mulch or tall grasses min wall to outlet Figure 4 9 Harman P Series Installation Manual_R3 2014 09 14 3 90 436168i B Chimney Diagram m Inside Corner Detail Fixed Closed Porch or Deck Openable or Fixed Vent Terminal Figure 4 10 Requirements for Terminating the Venting WARNING Venting terminals must
9. Tested and approved for wood pellets and shelled field flammable materials corn fuel only Burning of any other type of fuel voids your warranty Keep clothing furniture draperies and other flammable materials away To obtain a French translation of this manual please Check building codes prior t installatign contact your dealer or visit www harmanstoves com e Installation MUST comply with local regional state and national codes and regulations 1 Contact local building or fire officials about restrictions and Pour obtenir une traduction fran aise de ce manuel s il installation inspection requirements in your area vous plait contacter votre revendeur ou visitez www harmanstoves com 1 Harman P Series Installation Manual_R3 2014 ___ 09 14 3 90 436168i Safety Alert Key DANGER Indicates a hazardous situation which if not avoided will result in death or serious injury e WARNING Indicates a hazardous situation which if not avoided could result in death or serious injury e CAUTION Indicates a hazardous situation which if not avoided could result in minor or moderate injury NOTICE Indicates practices which may cause damage to the stove or to property TABLE OF CONTENTS Installation Standard Work Checklist 3 5 Appliance Setup 1 Product Specific and Important Safety Information Qom7moogOW D gt Appliance Certification 4 Glass Specifica
10. not be recessed into a wall or siding NOTE Only PL vent pipe wall pass through and fire stops should be used when venting through combustible materials NOTE Always take into consideration the effect the prevailing wind direction or other wind currents will cause with flyash and or smoke when placing the termination In addition the following must be observed A The clearance above grade must be a minimum of 12 B The clearance to a window or door that may be opened must be a minimum of 48 to the side and 48 below the window door and 12 above the window door with outside air installed 12 to side and below C A 12 clearance to a permanently closed window is recommended to prevent condensation on the window D The vertical clearance to a ventilated soffit located above the terminal within a horizontal distance of 2 feet 60 cm from the center line of the terminal must be a minimum of 18 E The clearance to an unventilated soffit must be a minimum of 12 F The clearance to an outside corner is 11 from center of pipe G The clearance to an inside corner is 12 H Avent must not be installed within 3 feet 90 cm above a gas meter regulator assembly when measured from the horizontal center line of the regulator 15 Harman P Series Installation Manual_R3 2014 09 14 Q Air Supply Inlet Area where termination is not permitted The clearance to service regulator vent outlet m
11. system to the stove The starting collar must be secured to the flue stub with at least three screws and sealed with high temp silicone caulking 4 stainless steel flex vent piping is only allowed for use in masonry fireplaces and chimneys or factory built wood burning fireplaces with class A metal chimneys Pellet venting pipe also known as Type L vent is constructed of two layers with air space between the layers This air space acts as an insulator and reduces the outside surface temperature to allow a clearance to combustibles of only 1 inch The sections of pipe lock together to form an air tight seal in most cases however in some cases a perfect seal is not achieved For this reason and the fact that the P Series operates with a positive vent pressure we specify that the joints also be sealed with silicone Where passing through an exterior wall or roof be sure to use the appropriate pass through device providing an adequate vapor barrier Venting manufacturers generally provide these pass through devices 19 Harman P Series Installation Manual_R3 2014 09 14 3 90 436168i l Fire Safety To provide reasonable fire safety the following should be given serious consideration e 20 Install at least one smoke detector and CO detector on each floor of your home Locate smoke detector away from the heating appliance and close to the sleeping areas Follow the smoke detector manufacturer s placement and installati
12. 6 10 254mm with side shields 16 406mm without side shields gt 10 254mm f 406mm WW9ZZ 6 9 228mm With or Without Side Shields Figure 3 2 9 Harman P Series Installation Manual_R3 2014 09 14 3 90 436168i C Floor Protection Place the stove on a noncombustible type floor or floor protector that extends a minimum of 6 inches 152mm to the front of the load door opening 6 inches 152mm to the sides ofthe door opening and 6 inches to the rear Floor protection must also extend 2 inches 51mm beyond each side of any horizontal flue pipe The minimum floor protector material is 20 gauge sheet metal Other floor protector materials are ceramic tile stone brick etc Figure 3 3 NOTE for Canadian installation only Per ULC S627 00 If installed on a combustible floor the need to provide a noncombustible floor protector covering the area beneath the space heater and extending at least 17 72 450mm on the firing side and at least 7 87 200mm on the other sides In Canada you may follow smaller U S floor protection requirements ONLY if the user agrees to completely shut down the appliance and allow it to cool to where all fire is extinguished and the combustion blower and its indicator light shuts off prior to opening the firebox door or ash door D Mobile Home Installa
13. 8 P61A P68 50 3 90 436168i Termination Location and Vent Information A Vent Termination Minimum Clearances Cofnbuptibies pa to Combustibles Figure 4 1 es enibucubine Y 3 Ft to Combustibles Figure 4 2 11 Harman P Series Installation Manual_R3 2014 09 14 1 Preferred method Figure 4 1 This method provides excellent venting for normal operation and allows the stove to be installed closest to the wall Two inches from the wall is safe however four inches allows better access to remove the rear panel The vertical portion of the vent should be three to five feet high This vertical section will help provide natural draft in the event of a power failure Seal pipe joints with silicone or aluminum tape in addition to the sealing system used by the manufacturer Note Do not place joints within wall pass through 2 Preferred method Figure 4 2 This method also provides excellent venting for normal operation but requires the stove to be installed farther from the wall The vertical portion of the vent should be three to five feet high and at least 1 from a combustible wall This vertical section will prov
14. ATION USE OF IMPROPER FUELS FIRE STARTERS OR ALTERING THE STOVE FOR HIGHER HEAT OUTPUT MAY CAUSE DAMAGE TO THE STOVE AND COULD RESULT IN A HOUSE FIRE USE ONLY APPROVED FUELS AND OPERATION GUIDELINES 3 90 436168i iagram D iring B W v0S90 68 ON LuVd Nid LL ALIHM 52418 qaq anid LOdNUNd JCISNI 13 3 13 Y4LIN I MOTISA ALda A ALIHM I V C E ZH09 0S DVAOTL OOL VBE SLIVM ASN GYVGNVLS Y ZH09 0S DVANTL OOL OLS SLIVM XVW YOLOW Y30444 ALIHM I ALIHM ALIHM 14 NMOud SNOLLDANNOD 31 22 3171 301811 301811 YIM G31SIA1 MOTIAA 3gO d dS3 SSV19 dWY 9 A 5 dS3 3DVv18 ALIHM SLOVLINOD O N HDLIMS MOT 18 NOILNAIYLSIA YOLOW NOLLSNEWOD SNOLLDANNOD 3 1VIW34 41VW qaq ALIHM N3349 quvog TOULNOD 4 HOSN3S 31014301 D N3349 4008 3AO1S OL GAGNO8 aNNOY SI 34ql AA N3349 ALIHM ay r OD amog NAOd8 23 2 31VW34 31VW 405 89 8 8 WVYDVIC ONIMIM 131144 89d VL9d EVd uaggnu 81 e 09 14 3 90 436168i
15. For Residential Use STANDARD s ASTM E 1509 04 ULC ORD C1482 M1990 ULC S627 00 MODEL P68 Pellet Stove LABORATORY OMNI Test Laboratories Inc REPORT NO 135 S 13 2 135 S 13b 2 135 S 13c 6 2 TYPE Pellet Fueled Supplementary For Residential Use STANDARD s ASTM E 1509 04 ULC ORD C1482 M1990 ULC S627 00 NOTE This installation must conform with local codes In the absence of local codes you must comply with the ASTM E1509 2004 ULC 628 93 ULC ORD C 1482 M1990 UM 84 HUD B Glass Specifications This appliance is equipped with 5mm mirrored ceramic glass Replace glass only with 5mm ceramic glass Please contact your dealer for replacement glass C Mobile Home Approved This appliance is approved for mobile home installations when not installed in a sleeping room and when an outside combustion air inlet is provided The structural integrity of the mobile home floor ceiling and walls must be maintained The appliance must be properly grounded to the frame of the mobile home and use only listed pellet vent Class PL connector pipe AHarman Outside Air Kit must be installed in a mobile home installation THE STRUCTURAL INTEGRITY OF THE MANUFACTURED HOME FLOOR WALL AND CEILING ROOF MUST BE MAINTAINED DO NOT INSTALL IN SLEEPING ROOM The P61A and P68 Freestanding Pellet Stove by Harman are exempt from Environmental Protection Agency certification under 40 CFR 60 531 by definition Woo
16. Installation Manual Installation and Appliance Setup INSTALLER Leave this manual with party responsible for use and operation OWNER Retain this manual for future reference NOTICE SAVE THESE INSTRUCTIONS Please read this entire manual before installation and use of this pellet fuel burning room heater BUILT TO A STANDARD NOT A PRICE Failure to follow these instructions could result in property damage bodily injury Model s or even death P43 P61A amp P68 Do not store or use gasoline or other flammable vapors Freestanding Pellet Stove and liquids in the vicinity of this or any other appliance Do not overfire If any external part starts to glow you are overfiring Reduce feed rate Overfiring will void your warranty Comply with all minimum clearances to combustibles as specified Failure to comply may cause house fire HOT SURFACES Glass and other surfaces are hot during operation AND cool down Hot glass will cause burns Do not touch glass until it is cooled NEVER allow children to touch glass Tested amp Portiand Keep children away Listed By Oregon USA Eb bl ne CAREFULLY SUPERVISE children in same room as stove Alert children and adults to hazards of high temperatures High temperatures may ignite clothing or other
17. ce any part of the control system which has been under water 7 Harman P Series Installation Manual_R3 2014 09 14 3 90 436168i Clearances A Appliance Dimension Diagram Dimensions are actual appliance dimensions Use for reference only P43 Freestanding Pellet Stove P61A Freestanding Pellet Stove Outside Air Intake 13 3 4 Figure 3 1 8 Harman P Series Installation Manual_R3 2014 09 14 3 90 436168i B Clearances to Combustibles When selecting a location for the appliance it is important to consider the required clearances to walls see Figure 3 2 RISK OF FIRE OR BURNS Provide adequate clearance around air openings and for service access Due to high temperatures the appliance should be located out of traffic and away from furniture and draperies NOTICE Illustrations reflect typical installations and are FOR DESIGN PURPOSES ONLY Actual installatio
18. d Heater A Air to Fuel Ratio gt The P43 is EPA certified to comply with July 1990 particulate emission standards 4 Harman P Series Installation Manual_R3 2014 09 14 3 90 436168i D BTU amp Efficiency Specifications P43 Freestanding Pellet Stove Particulate 2 Emissions Rating Average Emissions 1 4 g h BTU Output 12 631 32 163 hr 3 up to 2 400 sq ft depending on Heating Capacity aie ZOnE q p 9 Hopper Capacity 50 Wood Pellets or Shelled Corn Shipping Weight 212 Ibs P61A Freestanding Pellet Stove Particulate BTU Output 0 61 000 hr Heating Capacity up to 3 500 sq ft depending on climate zone Hopper Capacity 72 Fuel s Wood Pellets or Shelled Corn Shipping Weight 249 lbs P68 Freestanding Pellet Stove Particulate N Emissions Rating BTU Output 0 68 000 hr Heating Capacity up to 3 900 sq ft depending on climate zone Fuel Wood Pellets or Shelled Corn Shipping Weight 290 Ibs BTU output will vary depending on the brand of fuel you use in your appliance Consult your Harman dealer for best results Hopper Capacity 76 Ibs 5 Harman P Series Installation Manual_R3 2014 09 14 E Non Combustible Materials Specification Material which will not ignite and burn Such materials are those consisting entirely of steel iron brick tile concrete slate glass or plasters or any combination thereof
19. d be installed in the location where you want to control the temperature NOTE Distances of more than 25 feet from the unit or in another room are not recommended The room sensor is essential for the P Series excellent efficiency NOTE It is recommended that the room sensor be installed even if only installed on the rear of the unit as a return air sensor F Low Draft Voltage Adjustment These units are pre tested at the factory with exactly 120 VAC 60 Hz They are checked and adjusted for firebox tightness gasket leakage motor operation and igniter operation The P Series is then factory set at a mid point adjustment and in most cases will not need any adjustments NOTE The factory low draft setting may not be correct for the unit s permanent installation conditions The control board on the P Series is equipped with a low draft adjustment port located on the control face just to the right of the igniter light Figure 5 4 This voltage adjustment is provided to allow the unit to be adjusted for the household voltage where the unit is going to be in permanent operation NOTE The line voltage varies from area to area and often home to home The low draft voltage should be adjusted to achieve the most efficient burn on low burn or maintenance This voltage adjustment allows the installer to change the low voltage set point approximately 10 volts This adjustment should be done by the installer during set up because a draft mete
20. ency or your dealer NOTE Hearth amp Home Technologies manufacturer of this appliance reserves the right to alter its products their specifications and or price without notice Harman is a registered trademark of Hearth amp Home Tech nologies 3 90 436168i Getting Started A Design and Installation Considerations 1 Appliance Location NOTICE Check building codes prior to installation Installation MUST comply with local regional state and national codes and regulations e Consult insurance carrier local building inspector fire officials or authorities having jurisdiction over restrictions installation inspection and permits It is a good idea to plan your installation on paper using exact measurements for clearances and floor protection before actually beginning the installation Consideration must be given to Safety convenience traffic flow e Placement of the chimney and chimney connector If you are not using an existing chimney place the appliance where there will be a clear passage for a factory built listed chimney through the ceiling and roof Installing an optional outside air kit would affect the location of the vent termination Since pellet exhaust can contain ash soot or sparks you must consider the location of Windows Air Intakes Air Conditioner Overhang soffits porch roofs adjacent walls e Landscaping vegetation When locating vent and ven
21. hould be run outside and terminate to the side or below the vent pipe outlet so the flue outlet is more than 12 from the inlet cover The Termination Cap should be used to keep birds rodents etc out of the pipe Figure 4 13 You may choose to use the optional Direct Vent Wall Pass through Kit which incorporates the venting pass through and outside air inlet into one component Figure 4 14 3 90 436168i Locating Your Appliance amp Chimney Location ofthe appliance and chimney will affect performance Install through the warm airspace enclosed by the building envelope This helps to produce more draft especially during lighting and die down of the fire Penetrate the highest part of the roof This minimizes the effects of wind loading e Locate termination cap away from trees adjacent structures uneven roof lines and other obstructions Minimize the use of chimney offsets e Consider the appliance location relative to floor and ceiling and attic joists DO NOT CONNECT THIS UNIT TO ACHIMNEY FLUE SERVICING ANOTHER APPLIANCE e DO NOT CONNECT TO ANY AIR DISTRIBUTION DUCT OR SYSTEM May allow flue gases to enter the house F Draft Draft is the pressure difference needed to vent appliances successfully When an appliance is drafting successfully all combustion by products are exiting the home through the chimney Considerations for successful draft include Preventing negative pressure e Loca
22. ide natural draft in the event of a power failure Seal pipe joints with silicone or aluminum tape in addition to the sealing system used by the manufacturer If the stove is installed below grade be sure the vent termination is at least 12 above grade with outside air only The outlet must also be 1 foot from the house building Note Do not place joints within wall pass through Keep combustible materials such as grass leaves etc at least 3 feet away from the flue outlet on the outside of the building 3 90 436168i Figure 4 3 Figure 4 4 12 33 Installing into existing chimney Figure 4 3 This method provides excellent venting for normal operation This method also provides natural draft in the event of a power failure If the chimney condition is questionable you may want to install a liner as in method 7 In some places in the US and Canada it is required that the vent pipe extend all the way to the top of the chimney The chimney should be inspected and cleaned before installing your stove If you discover that the chimney does not have a clay tile liner or has cracks or flaking of the tile liner you will need to install a stainless steel liner within the chimney In most cases the inside diameter of this liner should be 4 Either flexible or rigid liner may be used for this purpose Refer to Method 6 amp 7 Seal pipe joints with silicone or aluminum tape in addition to the sea
23. insurance representative before you begin your installation to ensure compliance with local codes including the need for permits and follow up inspections This appliance must be vented to the outside Due to high temperatures this stove should be placed out of traffic and away from furniture and draperies Children and adults should be alerted to the hazards of high surface temperatures and should stay away to avoid burn to skin and or clothing Young children should be carefully supervised when they are in the same room as the stove Clothing and other flammable materials should not be placed on or near this stove Installation and repair of this stove should be done by a qualified service person The appliance should be inspected before use and at least annually by a qualified service person More frequent cleaning may be required It is imperative that control compartments burners and circulating air passageways of this stove be kept clean 23 Harman P Series Installation Manual_R3 2014 09 14 MOBILE MANUFACTURED HOME GUIDELINES DO NOT ALLOW INSTALLATION IN A SLEEPING ROOM THE STRUCTURAL INTEGRITY OF THE MOBILE HOME FLOOR WALL AND CEILING ROOF MUST BE MAINTAINED THE STOVE IS HOT WHILE IN OPERATION KEEP CHILDREN CLOTHING AND FURNITURE AWAY CONTACT MAY CAUSE SKIN BURNS KEEP COMBUSTIBLE MATERIALS SUCH AS GRASS LEAVES ETC AT LEAST 3 FEET AWAY FROM THE POINT DIRECTLY UNDER THE VENT TERMIN
24. iprocating Saw Gloves Hammer Safety Glasses Phillips Screwdriver Electric Drill amp Bits Tape Measure Level May also need Non Combustible Sealant Vent Support Straps Material Venting Paint C Inspect Appliance and Components e Carefully remove the appliance and components from the packaging e The vent system components and decorative doors and fronts may be shipped in separate packages e Report to your dealer any parts damaged in shipment particularly the condition of the glass e Read all of the instructions before starting the installation Follow these instructions carefully during the installation to ensure maximum safety and benefit WARNING Risk of Fire or Explosion Damaged parts could impair safe operation DO NOT install damaged incomplete or substitute components Keep appliance dry Hearth amp Home Technologies disclaims any responsibility for and the warranty will be voided by the following actions Installation and use of any damaged appliance or vent system component Modification of the appliance or vent system Installation other than as instructed by Hearth amp Home Technologies Installation and or use of any component part not approved by Hearth amp Home Technologies Any such action may cause a fire hazard Risk of Fire Explosion or Electric Shock DO NOT use this appliance if any part has been under water Call a qualified service technician to inspect the appliance and to repla
25. ire flue configuration is accessible for cleaning 4 stainless steel flex vent piping is only allowed for use in masonry fireplaces and chimneys or factory built wood burning fireplaces with class A metal chimneys All pellet vent pipe must be secured together either by means provided by pipe manufacturer or by 3 screws at each joint 16 Harman P Series Installation Manual_R3 2014 09 14 Use only the specified venting components Use of any other components will void the product warranty and may pose a hazard Do Not Install A Flue Damper In The Exhaust Venting System Of This Appliance DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE NOTE Simpson DuraVent PelletVent Pro Harman Adapter Part 3PVP ADHB and PelletVent Pro Harman Adapter Increaser Part 3PVP X4ADHB are highly recommended to be installed on the starter collar to insure a proper pipe connection to the unit INSTALL VENT AT CLEARANCES SPECIFIED BY THE VENT MANUFACTURER Use silicone to create an effective vapor barrier at the location where the chimney or outside air ducting passes through to the exterior of the structure 3 90 436168i Outside Air Outside air flex pipe goes here Figure 4 12 Termination Cap part 1 10 09542 Figure 4 13 Direct Vent Wall Pass through Kit Part 1 00 677177
26. ling system used by the manufacturer Be sure to design the venting so that it can be easily cleaned 4 Installing into an existing fireplace chimney Figure 4 4 This method provides excellent venting for normal operation This method also provides natural draft in the event of a power failure If the chimney condition is questionable you may want to install a liner as in method 6 In some places in the US and Canada it is required that the vent pipe extend all the way to the top of the chimney The chimney should be inspected and cleaned before installing your stove If you discover that the chimney does not have a clay tile liner or has cracks or flaking of the tile liner you will need to install a stainless steel liner within the chimney In most cases the inside diameter of this liner should be 4 Either flexible or rigid liner may be used for this purpose Refer to Method 5 amp 6 The chimney should be sealed at the damper using a steel plate Kaowool mineral wool or an equivalent non combustible insulation is recommended to be installed on top of the sealing plate to reduce the possibility of condensation The connector pipe should extend through the smoke chamber to the base or into the first flue tile Seal pipe joints with silicone or aluminum tape in addition to the sealing system used by the manufacturer Be sure to design the venting so that it can be easily cleaned Harman P Series Installation Manual_R3
27. n may vary due to individual design preference Place the stove away from combustible walls at least as far as shown in Figure 3 2 Please note the difference in side wall clearance with and without side shields Note that the clearances shown are minimum for safety but do not leave much room for access when cleaning or servicing Please take this into account when placing the stove THIS APPLIANCE MUST BE VENTED TO THE OUTSIDE Due to high temperatures the stove should be placed out of traffic and away from furniture and draperies Children and adults should be alerted to the hazards of high surface temperatures and should stay away to avoid burns to skin and or clothing Young children should be carefully supervised when they are in the same room as the stove Clothing and other flammable materials should not be placed on or near this unit Alternate floor protector dimension may be used as long as they satisfy the measurement requirements shown below Minimum size floor protection for a corner installation hearth pad is 36 x 36 P61A amp P68 Freestanding Pellet Stove P43 Freestanding Pellet Stove 2 51mm 14 355mm with side shields 20 508mm without side shields gt 14 355mm 20 508mm 9 228mm 13 330mm 9 228mm With Side Shields 13 330mm Without Side Shields 0 EL
28. nel Leveling Bolt Shipping Bolts Note These same holes are used for securing the stove in mobile home Figure 5 1 installation 1 Firebrick 43 Pellet Stove P61A amp P68 Pellet Stove Flame guide A Unpacking The P Series is bolted 1 4 x 1 hex head bolts to the skid to prevent movement during shipping To free the stove from the skid you must remove the hold down bolts in the rear of the pedestal base using a 7 16 socket or wrench Figure 5 1 B Removing Rear Cover Panels The rear cover panels are secured to the stove with three screws each Two of the screws need only be loosened not removed to remove the panels It is recommended that the rear covers are installed using a 5 16 socket wrench or nut driver after the unit is in place and the vent pipe is installed to prevent contact with hot or moving parts Ifneeded install the 2 5 16 18 X 3 4 leveling bolts located in the hardware kit Figure 5 1 C Firebrick The P43 Pellet Stove has a single 1 firebrick that gets installed horizontally on the angle bracket above the burnpot The P61A and P68 have three 3 firebrick that get installed vertically on the angle bracket Figure 5 2 D Flame Guide Install the cast iron flame guide on top of the burn pot Make sure that the flame guide is fully seated
29. nts for furnaces water heaters and other combustion appliances Clothes dryers e Location of return air vents to furnace or air conditioning Imbalances of the HVAC air handling system Upper level air leaks such as Recessed lighting Attic hatch Duct leaks To minimize the effects of negative air pressure Install the outside air kit with the intake facing prevailing winds during the heating season Ensure adequate outdoor air for all combustion appliances and exhaust equipment Ensure furnace and air conditioning return vents are not located in the immediate vicinity of the appliance e Avoid installing the appliance near doors walkways or small isolated spaces Recessed lighting should be a sealed can design Attic hatches weather stripped or sealed Attic mounted duct work and air handler joints and seams taped or sealed NOTICE Hearth amp Home Technologies assumes no responsibility for the improper performance of the chimney system caused by Inadequate draft due to environmental conditions Downdrafts Tight sealing construction of the structure e Mechanical exhausting devices 3 90 436168i H Avoiding Smoke and Odors Negative Pressure Shut down and Power Failure To reduce the probability of back drafting or burn back in the pellet burning appliance during power failure or shut down conditions the stove must be able to draft naturally without exhaust blower operation
30. on instructions and maintain regularly Conveniently locate a Class A fire extinguisher to contend with small fires In the event of a hopper fire e Evacuate the house immediately Notify fire department Fire Risk Hearth amp Home Technologies disclaims any responsibility for and the warranty will be voided by the following actions Installation and use of any damaged appliance Modification of the appliance Installation other than as instructed by Hearth amp Home Technologies Installation and or use of any component part not approved by Hearth amp Home Technologies Operating appliance without fully assembling all components Do NOT Overfire Or any such action that may cause a fire hazard Harman P Series Installation Manual_R3 2014 09 14 Inspect Appliance amp Components Remove appliance and components from packaging and inspect for damage Report to your dealer any parts damaged in shipment Read all the instructions before starting the installation Follow these instructions carefully during the installation to ensure maximum safety and benefit Inspect appliance and components for damage Damaged parts may impair safe operation Do NOT install damaged components Do NOT install incomplete components Do NOT install substitute components Report damaged parts to dealer 3 90 436168i Appliance Set Up Rear Cover Rear Cover Pa
31. on the vertical sides of the burn pot and that the back of the guide rests against the body of the stove Figure 5 3 INSTALL EXHAUST VENT AT CLEARANCES SPECIFIED BY THE MANUFACTURER Most pellet vent pipe requires a minimum of 1 of clearance to combustible materials although some can be installed at 1 clearance Follow these instructions along with all local codes regarding installation of this appliance Do NOT use makeshift compromises when installing this appliance serious consequences may result With any hearth appliance installation of smoke detectors is recommended on every level of the home Possible causes of smoke detector activation Paint curing process Open a window near the appliance for the first few hours of burning Exhaust being drawn back inside the dwelling Outside air connection to the appliance is necessary Vent leakage All interior seams and joints should be sealed with silicone where applicable Follow vent manufacturers instructions for proper sealing 21 Harman P Series Installation Manual_R3 2014 09 14 3 90 436168i Room Sensor Installation The room sensor is a small temperature sensor on the end of a 60 wire This sensor is installed much like a standard wall thermostat There is a remote room sensor port on the rear of the unit for easy external connection Use standard 18 2 thermostat wire to extend the sensor to the desired location 50 maximum The room sensor shoul
32. or to slow before checking the low draft 6 If the low draft is between 35 and 45 record the reading in W C If the reading is higher slowly turn the set screw counter clockwise until the draft lowers If the reading is lower very slowly turn the set screw clockwise until the draft increases NOTE In some cases the draft may not go as low as 35 to 45 even with the set screw completely counter clockwise Ideally you should just set it as low as possible NI Draft Meter bolt hole location On a P Series the draft test hole is under the left rear corner of the firebox on the pedestal base Figure 5 5 Connect the power cord to a 100 VAC 50 Hz grounded receptacle A surge protector is recommended to protect the circuit board Also be sure that the polarity of the outlet that the stove is plugged into is correct 3 90 436168i Reference Material A Safety Reminders When installing and operating your Harman P Series respect basic safety standards Read these instructions carefully before you attempt to install or operate the P Series Failure to do so may result in damage to property or personal injury and may void the product warranty Consult with your local building code agency and
33. r reading is required to insure proper set up Combustion Motor Speed Control Low draft only set point The small straight screwdriver slot is plastic therefore the unit can be adjusted while in operation HARMAN POWER O STATUS O STRIBUTION BLOWER COMBSTION BLOWER IGNITER AUTO IGNITER O O MANUAL WARNING HIGHVOLTAGE Disconnect power before removing panel Figure 5 4 22 Harman P Series Installation Manual_R3 2014 ___ 09 14 Ifthe unit is not adjusted properly it does not cause a safety concern If the unit is adjusted too high only efficiency is lost If the unit is adjusted too low the low draft pressure switch will not allow the feed motor or the igniter to operate A simple draft test should be performed after completing the flue pipe installation To record the results for future reference 1 Plug unit into a 120 VAC 60 HZ outlet 2 Close the hopper lid front view door and the ash pan door Neither pellets or a fire are required for this test 3 With the mode selector in the OFF position turn the feed adjuster to TEST 4 Record the high draft in W C Normal is 50 to 60 The control will be on the High Draft for a total of 2 minutes 5 After 1 minute the combustion motor will go down to low draft and the distribution blower will go on high Allow approximately 15 seconds to pass for the combustion mot
34. th your local HVAC professional to determine the ventilation demands for your house Vent Pipe Vent Configurations To reduce probability of reverse drafting during shut down conditions Hearth amp Home Technologies strongly recommends Installing the pellet vent with a minimum vertical run of five feet preferably terminating above the roof line Installing the outside air intake at least four feet below the vent termination To prevent soot damage to exterior walls of the house and to prevent re entry of soot or ash into the house e Maintain specified clearances to windows doors and air inlets including air conditioners Vents should not be placed below ventilated soffits Run the vent above the roof Avoid venting into alcove locations Vents should not terminate under overhangs decks or onto covered porches e Maintain minimum clearance of 12 inches from the vent termination to the exterior wall If you see deposits developing on the wall you may need to extend this distance to accommodate your installation conditions Hearth amp Home Technologies assumes no responsibility for nor does the warranty extend to smoke damage caused by reverse drafting of pellet appliances under shut down or power failure conditions Be sure to use approved pellet vent pipe wall and ceiling pass through fittings to go through combustible walls and ceilings Be sure to use a starting collar to attach the venting
35. ting termination vent above roof line when possible Warning Risk of Fire Damaged parts could impair safe operation Do NOT install damaged incomplete or substitute components CAUTION If burning shelled field corn you must use approved venting specifically designed for corn to prevent corrosion or degradation Follow the instructions from the venting manufacturer NOTICE Locating the appliance in a location of considerable air movement can cause intermittent smoke spillage from appliance Do not locate appliance near Frequently open doors Central heat outlets or returns Recommended Location Recommended Location Above peak Above peak Inside heated Marginal Location Below peak Location NOT recommended Not the highest point of the roof Wind loading possible e Insulated exterior chase in cooler climates Windward s S sz Recommended Outside Air Intake on windward side Multi level Roofs Figure 2 1 pace Marginal Location Wind loading possible Location NOT recommended Too close to tree Below adjacent structure Lower roof line Avoid outside wall Leeward NOT recommended Outside Air Intake on leeward side 6 Harman P Series Installation Manual_R3 2014 09 14 3 90 436168i B Tools And Supplies Needed Tools and building supplies normally required for installation unless installing into an existing masonry fireplace Rec
36. tion When installing this unit in a mobile home several requirements must be followed 1 The unit must be bolted to the floor This can be done with 1 4 lag screws through the 2 holes in the base plate 2 The unit must also be connected to outside air See section 4 D Outside Air 3 Floor protection and clearances must be followed as shown 4 Unit must be grounded to the metal frame of the mobile home P43 Minimum size rectangular floor protection USA is 3272 wide By 33 deep 825mm X 838mm P61A Minimum size rectangular floor protection USA is 28 Deep By 24 Wide 719mm X 629mm P68 Minimum size rectangular floor protection USA is 33 Deep By 25 Wide 838mm X 635mm Floor protection dimensions for the front and sides are measured from the appliance door opening in The United States In Canada the side dimension is measured from the widest part of the appliance Floor Protection US Canada Requirements J Sides 6 On K Front 6 450mm Rear 6 200mm NOTE Measurement L is measured from the pedestal base in the US ONLY NOTE Measurement K is measured from the glass in the US ONLY J CANADA FLOOR PROTECTOR Figure 3 3 10 Harman P Series Installation Manual_R3 2014 09 14 Corner to edge dimension for corner installation floor protection P43 42 5
37. tion of appliance and chimney To measure the draft or negative pressure on your appliance use a magnahelic or a digital pressure gauge capable of reading 0 1 inches of water column W C The appliance should be running on high for at least 15 minutes for the test With the stove running on high you should have a negative pressure equal to or greater than the number given in the chart below If you have a lower reading than you find on the chart your appliance does not have adequate draft to burn the fuel properly Minimum Vacuum Requirements 35 55 Prior to installing the flue pipe connect a draft meter The draft meter must have a minimum range of 0 5 Record the first reading Connect flue pipe to stove and be sure all doors and windows in the home are closed Record the second draft reading If the second reading is more than 05 lower than the first reading check for possible restrictions or the need for outside air For more information on the draft test procedure refer to Page 21 18 Harman P Series Installation Manual_R3 2014 09 14 G Negative Pressure Risk of Asphyxiation Negative pressure can cause spillage of combustion fumes and soot Negative pressure results from the imbalance of air available for the appliance to operate properly It can be strongest in lower levels of the house Causes include Exhaust fans kitchen bath etc e Range hoods e Combustion air requireme
38. tions 4 Mobile Home Approvals 4 BTU Specifications 5 Non Combustible Materials Specification 5 Combustible Materials Specification 5 Electrical Codes cuy gneve bet eer doe 5 2 Getting Started A B C Design and Installation Considerations 6 Tools and Supplies Needed 7 Inspect Appliance and Components 7 3 Framing and Clearances A B C D Appliance Dimension Diagram 8 Clearances to Combustibles 9 Floor Protection u l rataran kas sus eee 10 Mobile Home Installation 10 4 Termination Location and Vent Information 8 r mnmo omp gt Vent Termination Minimum Clearances 11 Chimney Diagram 15 Venting amp Use of Elbows 16 Outside Ar eat eee keer eke Reba eee 17 Locating Your Appliance and Chimney 18 Draft pe rasa isso ties Potala pened Sethe 4 18 Negative Pressure 18 Avoiding Smoke amp Odors 19 Fire Safety 20 Inspect Appliance amp Components 20 Harman P Series Installation Manual_R3 2014
39. trical Section 1 Pg 5 120VAC unswitched power provided to the appliance Appliance Setup Section 5 Pg 21 22 All packaging and protective materials are removed Accessories installed properly Manual bag and all it s contents are removed from inside the appliance and given to party responsible for use and operation Started appliance and verified that all motors and blowers operate as they should Hearth and Home Technologies recommends the following Photographing the installation and copying this checklist for your file This checklist remain visible at all times on the appliance until the installation is complete Comments Further description of the issues who is responsible Installer Builder Other Trades etc and corrective action needed Comments communicated to party responsible by on Builder Gen Contractor Installer Date 3 Harman P Series Installation Manual_R3 2014 ___ 09 14 3 90 436168i 1 Product Specific and Important Safety Information A Appliance Certification MODEL P43 Pellet Stove LABORATORY OMNI Test Laboratories Inc REPORT NO 135 S 23 4 135 S 23b 6 2 TYPE Pellet Fueled Supplementary For Residential Use STANDARD s ASTM E 1509 04 ULC ORD C1482 M1990 ULC S627 00 MODEL P61A Pellet Stove LABORATORY OMNI Test Laboratories Inc REPORT NO 135 S 22 4 135 S 22b 6 2 TYPE Pellet Fueled Supplementary
40. ust be a minimum of 6 feet J The clearance to a non mechanical air supply inlet to the building or the combustion air inlet to any other appliance must be a minimum of 48 K The clearance to a mechanical air supply inlet must be a minimum of 10 feet with outside air installed 6 feet L The clearance above a paved sidewalk or a paved driveway located on public property must be a minimum of 7 feet M The clearance under a veranda porch deck or balcony must be a minimum of 12 inches B also NOTE The clearance to vegetation and other exterior combustibles such as mulch is 36 as measured from the center of the outlet or cap This 36 radius continues to grade or a minimum of 7 feet below the outlet Certain Canadian and or Local codes or regulations may require different clearances A vent shall not terminate directly above a side walk or paved driveway which is located between two single family dwellings and serves both dwellings Only permitted if veranda porch deck or balcony is fully open on a minimum of 2 sides beneath the floor See NFPA 211 for more installation clearance reductions when using outside air NOTE Where passage through a wall or partition of combustible construction is desired the installation shall conform to CAN CSA B365 if in Canada 3 90 436168i C Venting amp Use Elbows ol
Download Pdf Manuals
Related Search
Related Contents
LG WM2050CW Specifications caution - Tekno Point Gefen EXT-HD-DSMP numéro 25 fini - SGEP-SNEC-CFTC GE 36 in. Profile JGP962SECSS Gas Cooktop Avaya P334T-ML Switch User Manual Manuel d`Installation INGECON SUN Lite Copyright © All rights reserved.
Failed to retrieve file