Home
Operating instructions DALI EASY II
Contents
1. Daylight simulation is disabled Daylight simulation is enabled 4 ON ON F Learn mode for transferring the IR code to DALI EASY and resetting DALI EASY to the factory defaults RESET Disabling scene storage Storing of scenes can be disabled by means of DIP switch 2 The ensures that scenes cannot be changed by mistake The DIP switch positions are shown in the table Changing between sequencer mode and daylight simulation Sequencer mode and daylight simulation mode are activated using DIP switches 3 and 4 Both operating modes may also be deactivated DALI EASY then operates in lighting control mode The necessary DIP switch positions are shown in the table RESET or setting the IR code The two IR codes enable two separate DALI EASY lighting control systems to be operated in the same room each with its own remote control with no interference between them This is how you process a RESET and change the infra red codes 1 Set the infra red code you want on DIP switch 1 e DIP switch 1 to OFF IR code 1 e DIP switch 1 to ON IR code 2 2 Note the settings of DIP switches 3 and 4 Set DIP switches 3 and 4 to ON 4 Press any button on the remote control the remote control must be pointing at the IR sensor L 3 then appears on the remote control display The luminaires provide confirmation of the setting e For IR code 1 the luminaires fla
2. EASY PB COUPLER connection of conventional push buttons switches or motion detectors 4008321915597 OT EASY 60 60W 4 ch LED control unit 4008321187796 k Y CONNECTOR EASY IR Branch for build up of a master slave Infra red receiver installation with connection cable 4050300803135 4008321053138 gt gt a i E j EASY PC KIT EASY IR CI EASY USB Adapter incl Software for facile system configuration 4008321915559 Infra red receiver for ceiling installation 4008321915573 aN as Or at oe LMS CI BOX Sensor Mounting Kit Independent mounting of DALI EASY II on top mounting of 4008321083692 EASY IR Cl 4008321916662 i The CE symbol signifies compliance with the relevant EU Directives Page 16 OSRAM Operating Instructions DALI EASY II control unit
3. Hh controlled switch optional T of a Re o S33 32 SS 6 SS SS Se SS ee eS l external push button external push button optional optional e Master optional i E E mS GND GND i DALI EASY Il cH4 we l DALI EASY Il CH3 B e Te S o o Easy Signal CH2 G e Easy Signal e CHi R mal ais eD OTi DALI ADL Pe 8 on DALI ECG l l E coat e Ol Ol O TE Cramp ed e G l cc e OTIDALI D es Infra red receiver 1 em 0 optional e Oo aan DA LED moduls LINEARIight Colormix i dae 5 DALIECG l Y Contiector optional e Y Connector PF it I opa e OTI DALI i HE p g el E E 6 1E DA I 4 l l oe o tras DALIECG 858 eonpaniot Push button coupler i i optional l l e e DALI ECG l DA bd Tel E se a ee ae i max 100m overall cable EASY PC Kit DALI EASY II amp length optional l e E te F38 DALIECG l ol e DA up to 15 Slaves e e Note 7 19 DALIECG z S T J 08 e ican een Make sure that there is a line of sight between the IR receiver and the remote control Up to 4 IR receivers may be connected To ensure that the remote control function a gt operates properly the IR receiver must not be exposed to direct light Wherever Y Connector Push button coupler DALIECG possible mount the I
4. e There is no power Check the fuses for the power supply The lamps are faulty Replace them The DALI EASY lighting controller is not reacting to the remote control Possible causes e Switch DALI EASY on at the external switch light switch If the luminaires do not respond to the external switch light switch check the lamps and the power supply The batteries in the remote control are too weak Press a switch on the remote control There must be something showing on the display If this is not the case change the batteries Make sure the batteries are inserted correctly e The remote control is outside the range of the infra red receiver Hold the infra red transmitter on the remote control close to the infra red receiver Press a switch on the remote control The LED on the infra red receiver must flicker If this is not the case check the IR code e The IR receiver is blinded by direct light Shade the IR receiver and if possible choose a different mounting location The DALI EASY lighting controller is not reacting to the external switch Possible cause e Switch DALI EASY on using the remote control If the luminaires do not respond to the remote control check the lamps and the fuses for the power supply The luminaires are not doing what you want them to Possible causes e The switch is being pressed too long or not long enough DALI EASY distinguishes between a long and a short press Please check the information
5. changes are generated Daylight simulation Daylight simulation operates in much the same way as the sequencer mode The difference is in the use of lighting scenes that correspond to the lighting conditions as they change during the course of a day The duration of the entire cycle in other words a simulated day and the predefined lighting scenes can be changed DALI EASY is not intended for any applications other than the ones indicated here Other applications are considered to be inappropriate If DALI EASY is used inappropriately there is no guarantee that it will operate safely Behaviour after a power failure In the event of a power failure the luminaires behave as follows Lighting control mode e The last status before the power failure is automatically restored Sequencer mode e The sequence is restarted beginning with the first active scene Daylight simulation e The simulation is restarted beginning with the first active scene Page 4 OSRAM Operating Instructions DALI EASY II control unit General Components DALI EASY Il control unit Keu IKor Infra red Display transmitter Channel switches Scene 1 Ch1 Scene 2 Ch2 Scene 3 Ch3 Scene 4 Ch4 Start Time E _ oniort ON DIP Stop Time Dimming IE A A 123 4 DIP Switches OSRAM Operating Instructions DALI EASY II control unit Page 5 Installation Wiring diagrams Controlling
6. fluorescent and low voltage halogen lamps N L PE Line switch or clock i E controlled switch optional T e qT external push button optional Sa ae ee t l l GND DALI EASY I cH4 we i CH3 B as e e Easy Signal CH2 G e d l LF o pa DALI ECG e j l 3 DA b lamp red Ji O L E Lite Zz trae DALIEcG Ee S Infra red receiver er EH a Ps a TEET Y Connector optional lamp green i IA J 4 aen DALIECG H T DA amp blue I f Y Connector Push button coupler l Py optional _ tres DALIECG gt i Da e h lamp white l Ea e A ERRi l Adapter GE DALI transformer CJ aa See DA Halogen lamps 8Y Connector ee l i g P 6 I e max 100m overall cable EASY PC Kit j length optional Note Make sure that there is a line of sight between the IR receiver and the remote control Up to 4 IR receivers may be connected To ensure that the remote control function operates properly the IR receiver must not be exposed to direct light Wherever possible mount the IR receiver in a shaded spot Page 6 OSRAM Operating Instructions DALI EASY II control unit Installation Installation Wiring diagrams System extension Controlling LED modules Master slave circuit N L N L l Line switch and or clock l r O Line switch and or clock H caniroled switch
7. in these operating instructions e The power supply has been interrupted Read the section on what happens after a break in the power supply The sequence in master slave mode is not synchronous Possible cause e The slaves have already been programmed and have their own scenes Perform a RESET and create the sequence again If you cannot remedy the problem please contact the customer service department of your luminaire manufacturer OSRAM Operating Instructions DALI EASY II control unit Page 15 Appendix Technical data Designation Power supply Inputs Outputs Master slave connection Operating voltage Power input Operating temperature Protection type CE requirement Dimensions DALI EASY II L N IR Sensor input SELV equivalent basic insulation to IEC 664 potential free switch input basic insulation 4 DALI broadcast control signals basic insulation to IEC 664 max 32 DALI devices connectable 64 mA total over all channels max 100m DALI control wire total over all channels max 100m connection cable in total max 10 slaves connectable do not run master slave connections together with power cables or lamp wires 100 230V AC 50 60 Hz DC operation allowed approx 3 5 W 0 50 C IP 20 EMC to EN 61547 EN 61347 11 189 x 30 x 21 mm W x H x D hole spacing for mounting 180 mm Accessories Not included EASY RMC Infra red remote control 4008321053152
8. provided no other button has been pressed after the sequence was interrupted Ending a sequence and change to light control mode End the sequence by pressing any of the Ch1 to Ch4 Scene 1 to Scene 4 or On Off Dimming buttons The function of the button pressed will be performed Setting the fade time 1 Press the Start time or Stop time button for about three seconds until the current fade time is shown on the display 2 Set the fade time Start time button Holding down the button increases the time at a rapid pace Briefly pressing the button increases the time in individual steps Stop time button Holding down the button shortens the time at a rapid pace Briefly pressing the button reduces the time in individual steps The new fade time is activated when the sequence is started next time Example of a sequence Scene 1 Ch1 red max Ch2 Ch3 Ch4 min Scene 2 Ch2 green max Ch1 Ch3 Ch4 min Scene 3 Ch3 blue max Chi Ch2 Ch4 min Scene 4 Ch1 Ch4 off will be skipped 9 Scene 1 Scene 2 Scene 3 red 2 g fot peel 1 Y t 5 blue Soe re lt lt lt gt time fade time hold time The hold time is set automaticially to 25 of the fade time OSRAM Operating Instructions DALI EASY II control unit Page 13 Operation Daylight simulation Daylight simulation mode is enabled bringing DIP Swit
9. OSRAM a Operating instructions 2007 DALI EASY II PE aput ia sites GAD E mates at Etika GAA M maie HFa a CE 93 aD OSRAM Siae DALI EASY II Version 1 0 OSRAM GmbH www osram com Customer Service Center CSC www osram de Steinerne Furt 6286167 Augsburg Germany Tel 49 1803 677 200 charges apply Fax 49 1803 677 202 General Contents General Safety information 2 Definition of terms 3 Application and function 4 Components 5 Installation Wiring diagrams 6 Wiring diagrams 7 Operation System extension 8 Master slave mode 9 Remote control display 10 Remote control settings 11 Lighting control mode 12 Sequencer mode 13 Appendix Daylight simulation 14 Troubleshooting 15 Technical data 16 Safety information The following information is provided for your safety Please read these operating instructions carefully before installing and using the DALI EASY lighting controller This is the only way to ensure that you use the equipment safely and correctly Keep these operating instructions in a safe place for future reference You should make sure that everyone who uses DALI EASY has read these operating instructions DALI EASY is intended exclusively for operating control gear with a DALI interface No further control units may be operated on the control line The appropriate infra red receiver must be used see Technical data DALI EASY may only be installed by qualified pers
10. R receiver in a shaded spot optional H ena ae F e am e DALIECG SP is DA lamp white Y Connector ae 0 max 100m overall EASY PC Kit cable length optional Note In the master slave circuit there must be precisely one master all other control units must be configured as slaves by having a bridge placed over the switch input OSRAM Operating Instructions DALI EASY II control unit Page 7 Page 8 OSRAM Operating Instructions DALI EASY II control unit Installation Master slave mode In master slave mode up to 16 DALI EASY or OT EASY lighting controllers can be controlled simultaneously via a single remote control a single push button coupler or a single PC This means that lighting systems with more than 32 DALI units can easily be set up This is how to set up the master slave circuit see wiring diagrams 1 For one lighting controller you should proceed as follows If required connect an external switch or leave the switch input free This lighting controller will act as the master 2 For all the other lighting controllers bridge the input of the external switch These lighting controllers will be automatically recognised as slaves when mains voltage is applied 3 Connect the individual DALI EASY lighting controllers using the connecting cable provided Use Y Connector available as an accessory for branching 4 Connect the infra red receiver to one of
11. ch 4 in the remote control battery compartment into ON and DIP Switch 3 into OFF position Further DIP Switch positions are given in the table on page 11 Creating a daylight simulation sequence 1 Set the first lighting scene of the sequence using buttons Ch1 to Ch4 2 Press the Scene 1 button Hold down the button After about three seconds the luminaires will flash to indicate that the scene has been stored 3 Release the button 4 Repeat steps 1 to 3 to store the subsequent lighting scenes in the sequence with buttons Scene 2 to Scene 4 The sequence created in this way always starts with scene 1 runs through scenes 2 to 4 and starts again with scene 1 Lighting scenes for which all the channels are switched off are skipped and not used The fade time between the scenes depends on the selected cycle time as follows Fade time cycle time number of lighting scenes stored 1 Switching on and continuing a sequence 1 Briefly press the Start time button ga l l l 5 2 appears on the display The sequence is started or continued An interrupted simulation sequence is also continued after a short press onto the external switch Interrupting a sequence placing on hold 1 Press the external switch or briefly press the Stop time button un l l I appears on the display The sequence is stopped The sequence can be resumed with the external switch or with th
12. e Start time button provided no other button has been pressed after the sequence was interrupted Ending a sequence 1 End the sequence by pressing any of the Ch1 to Ch4 Scene 1 to Scene 4 or On Off Dimming buttons The function of the button pressed will be performed Setting the cycle time 1 Press the Start time or Stop time button for about three seconds until the current fade time is shown on the display 2 Set the fade time Start time button Holding down the button increases the time at a rapid pace Briefly pressing the button increases the time in individual steps Stop time button Holding down the button shortens the time at a rapid pace Briefly pressing the button reduces the time in individual steps The new cycle time is activated when the sequence is started next time by the remote control Example of a simulation sequence Cycle time 12h clock controlled switch on at 8a m Scene 3 Scene 2 Scene 4 brightness Scene 1 50 Cycle time 8a m 12a m 4p m 8p m Clock time If the groups are equipped with lamps of different colour temperature beside a change of brightness also a dynamique change of colour temperature dependent on the time of day can be achieved Page 14 OSRAM Operating Instructions DALI EASY II control unit Appendix Troubleshooting The luminaires cannot be switched on Possible causes
13. g control unit has four channels With the remote control 4 with the push button coupler 12 and via PC up to 16 lighting scenes can be stored and retrieved Most settings are made from an infra red remote control An external light switch can also be used to switch all the luminaires on and off and to fade them up and down With DALI EASY it is possible to set up a coloured light mixing system in which a different lamp colour red green blue and white is assigned to each group By setting the individual groups to different values any colours can be mixed These colours can be stored as lighting scenes and retrieved at any time A uniform distribution of the light colour can be achieved by arranging the coloured luminaires behind diffusors DALI EASY can be synchronised with other DALI EASY light controllers via a master slave connection This means that more than 32 DALI units can be provided per installation DALI EASY has three operating modes Lighting control mode The lighting levels and the lighting scenes are adjusted manually In lighting control mode with the remote control up to four with the push button coupler up to 12 static lighting scenes can be stored and retrieved Sequencer mode In sequencer mode the lighting scenes stored by the user are called up automatically one after the other The fade time between the individual lighting scenes can be adjusted If DALI EASY is used as a colour mixing system automatic colour
14. light switch Short press All the luminaires are switched on Long press All the luminaires are switched on and faded from minimum to maximum brightness Switching off all the luminaires Briefly press the On Off Dimming button or the external switch light switch All the luminaires are switched off Fading luminaires in a group Press the button for the luminaire group Ch1 to Ch4 that you want to fade up or down Hold down the external switch until the required brightness is reached The longer you hold it down the more the brightness will change Fading all the luminaires Press the On Off Dimming button or the external switch light switch Hold down the switch until the required brightness is reached The longer you hold it down the more the brightness will change Changing the fade direction 1 The fading operation will stop when you release the button or switch 2 Press the button or switch again The fade direction is reversed Storing lighting scenes 1 Set the lighting scene you want using buttons Ch1 to Chg 2 Press the button for the scene you want to store Hold down the button After about three seconds the luminaires will flash to indicate that the scene has been successfully stored 3 Release the button Briefly press the button for the scene Scene 1 to Scene 4 that you want to call up The selected scene ee appears on the display The sce
15. ne is called up Page 12 OSRAM Operating Instructions DALI EASY II control unit Operation Sequencer mode Sequencer mode is enabled bringing DIP Switch 3 in the remote control battery compartment into ON and DIP Switch 4 into OFF position Further DIP Switch positions are given in the table on page 11 Creating a sequence Set the first lighting scene of the sequence using buttons Ch1 to Ch4 Press the Scene 1 button Hold down the button After about three seconds the luminaires will flash to indicate that the scene has been successfully stored Release the button 4 Repeat steps 1 to 3 to store the subsequent lighting scenes in the sequence with buttons Scene 2 to Scene 4 The sequence created in this way always starts with scene 1 runs through scenes 2 to 4 and starts again with scene 1 Lighting scenes for which all the channels are switched off are skipped Switching on a sequence and continuing a sequence Briefly press the Start time button L lt i E appears on the display The sequence is started or continued An interrupted sequence is also continued after a short press onto the external switch Interrupting a sequence placing on hold Press the external switch or briefly press the Stop time button rm S appears on the display The sequence is stopped The sequence can be resumed with the external switch or with the Start time button
16. o OFF of ND Notes on master slave mode In the master slave circuit there must be precisely one master all other control units must be configured as slaves by having a bridge placed over the switch input Upto 4 IR receivers may be connected In expert mode to delete control units that have already been programmed and to return to normal master slave mode you need to perform a RESET as described on page 11 OSRAM Operating Instructions DALI EASY II control unit Page 9 Operation Remote control display Display in response to buttons Display Meaning Description S O H roa The sequence or daylight simulation isputonh daylight Scenes 1 to 4 of the daylight simulation are called up scene 1 4 d5 daylight Daylight simulation is started sequence learn IR A new IR coding is transferred sequence Ce A command via Ch1 4 or On Off Dimming is transferred The function is not available in the current operating mode Display for the fade time of a Sequence Description Display Time range Effect Light Hi 0 1 to 0 9 seconds 1 to 59 seconds 1 to 99 minutes Daylight simulation Gi 1 to 24 hours Page 10 OSRAM Operating Instructions DALI EASY II control unit Operation Remote control settings The following settings can be made using the DIP switches in the battery compartment of the remote control DIP switch Function S 1 1 2 2 3 3 4 4 3
17. onnel who have been appropriately trained and who have the relevant authority The installation personnel must be familiar with the operating instructions Power must be switched off before any work is undertaken on the unit The EASY control unit is especially designed for installation within luminaires an independent installation is only allowed in combination with the mounting kit LMS CI BOX The relevant safety and accident prevention regulations must be observed The external switch must be designed for mains voltages If the control cable or switch input is wired with external voltage particularly with a mains voltage of 230 V the unit may be destroyed Page 2 OSRAM Operating Instructions DALI EASY II control unit General Definition of terms Sequence A sequence is taken to be the automatic retrieval of stored lighting scenes and their cyclic playback Group luminaire group A group is a collection of luminaires connected to the same DALI output channel This means that all the luminaires in a group always have the same brightness IR receiver The infra red receiver receives the signals from the remote control and forwards them to the DALI EASY controller Short press A short press means pressing a pushbutton for less than one second A short press is used for example for switching luminaires on and off Long press A long press means pressing a pushbutton for more than one second A long press is used for example fo
18. r dimming the luminaires Light switch Light switches are used to switch luminaires on and off in a room and to fade them up and down They are connected to the external switch input on the DALI EASY controller Scene lighting scene A lighting scene defines the lighting situation in a room This presupposes that there are a number of luminaires or luminaire groups in a room and that their brightness can be adjusted independently of one another Example 1 Office lighting Offices often have rows of luminaires running in parallel to the window Lighting scene A The luminaires near the window are set to minimal brightness The in daylight luminaires furthest away from the window are set to maximum brightness Lighting scene B All the luminaires are set to the same brightness after dusk Example 2 Coloured effect lighting The luminaires or luminaire groups have different colours red green blue white They are set to different brightness levels according to the shade of colour required for the room lighting This mixing colour is a lighting scene Fade time The fade time is the time in which the lighting system changes from one lighting scene to the next in sequencer mode Cycle time The cycle time is the time in which the daylight simulation system runs through a complete daylight cycle OSRAM Operating Instructions DALI EASY II control unit Page 3 General Application and function The DALI EASY lightin
19. sh once e For IR code 2 the luminaires flash twice 5 Set DIP switches 3 and 4 to their original positions The functions of the DIP switches are given in the table above oO Notes on RESET and changing the IR code In the event of a RESET or change of IR code all the connected control units are reset or changed You should therefore disable the connection to the IR receiver for the control units that are not to be reset or changed or disconnect the power supply for these units If there is more than one system in the reception area their IR receivers must first be disconnected or adequately covered to avoid an unwanted RESET OSRAM Operating Instructions DALI EASY II control unit Page 11 Operation Lighting control mode If a sequence or a daylight simulation is terminated the system changes to lighting control mode automatically Switching on a luminaire group Press the button for the luminaire group Ch1 to Ch4 that you want to switch on Short press The luminaires in the selected group are switched on Long press The luminaires in the selected group are switched on and faded from minimum to maximum brightness Switching off a luminaire group Briefly press the button for the luminaire group Ch1 to Ch4 that you want to switch off The luminaires in the selected group are switched off Switching on all the luminaires Briefly press the On Off Dimming button or the external switch
20. the Y Connector units The special case of expert mode different sequences for master and slaves For each DALI EASY controller sequences with different lighting scenes can be set as described below The master determines the fade time and ensures that the individual sequences run in synchronism a Configuration via PC please see EASY Color Control Software manual b Configuration via remote control Remove the bridges from the external switch inputs on all the lighting controllers Connect the infra red receiver to the DALI EASY lighting controller to be set Set up the lighting scenes you require and store them Repeat steps 2 and 3 for all the other DALI EASY lighting controllers For one lighting controller you should proceed as follows If required connect an external switch or leave the switch input free This lighting controller will act as the master 6 For all the other lighting controllers bridge the input of the external switch These lighting controllers will be automatically recognised as slaves when mains voltage is applied 7 Connect the individual DALI EASY lighting controllers using the connecting cable provided Use Y Connector available as an accessory for branching 8 Connect the infra red receiver to one of the Y Connector units 9 Activate the scene lock so that the lighting scenes already set are not changed by mistake To do this set DIP switch 2 on the remote control t