Home
1732 Operators Manual
Contents
1. 05 Damping Factor 5x Samples Setup Menu The oxygen measurement can be damped by averaging successive readings from the probe This can be used to smooth out fluctuations in the process gas level and should improve stability of the readings of the system The larger the number selected here the more successive readings are averaged and the smoother the measurement will be The damping factor is not applied to the Probe EMF and Probe Temperature values used to calculate oxygen but to the oxygen value itself The pre damped oxygen value is not displayed or retransmitted via digital or analog outputs when damping is enabled the damped oxygen value is shown on the local display as well as being retransmitted via digital or analog outputs 5 3 5 Process Alarms POWER ALTES Options Enabled Disabled 06 Process Alarms Default Disabled Disabled Setup Menu This function allows the operator to Disable process alarms Configuration of the process alarms is not covered in this manual please refer to the 1732 Technical Manual for details 1732 Oxygen Transmitter A CONTROLS mws 17 This page has been intentionally left blank Operators Manual 18 NEW tech CONTROLS m 119 February 2015 1732 Oxygen Transmitter 6 ALARMS The 1732 Oxygen Transmitter has 4 alarm relays a built in alarm annunciator and an alarm log When an alarm occurs the Alarm Light will flash To find out what the alarm is
2. 6 1 Checking and Accepting an Alarm Alarm Description Time title Time Activated P POWER OXYGEN TRANSMITTE Probe 2 TC Open Ct Time Activated Time Accepted Time Cleared 08 Mar 2006 03 45 29 Status Active Time of the event Alarm Status Active Accepted Self Cleared When a new alarm occurs either a process alarm or an alarm that will appear in the common alarm list the Alarm Light will flash quickly The more new alarms there are the faster the light will flash To check the cause of the alarm 1 wm 5 6 Press the ALARM A button This will put the transmitter into the current alarm mode The Setup Light will flash The alarm screen will appear displaying the cause of the alarm on the top line Press the ALARM ACCEPT button to accept the alarm Press the OPTION A button to see the next active alarm or the OPTION V button to see the previous active alarm When all the new alarms have been ACCEPTED the Alarm Light will stop flashing Accept each alarm and then press the SETUP RUN button to return to the Run Mode 6 1 1 Current Alarms To view the alarms that are still current press the ALARM A button from the Run Mode and then use the ALARM A and ALARM V buttons to view all alarms Use the DISPLAY A and DISPLAY V buttons to view the Time Activated and the Time Accepted of each alarm Operators Manual Etech February 2015 20 CONTROLS miia 1732 Oxygen Transmitter 6 1 2 Alarm Log
3. 6 4 Selectable Process Alarms There are three user configurable alarm relays Any or all of the following functions can be selected for each relay The description of how the trip levels and the delay times are set is in the 1732 Technical Manual NOTE The process alarms will only be activated if they are enabled in SETUP menu function 06 20 Oxygen 1 Very Low 21 Oxygen 2 Very Low The measured oxygen level on the indicated probe has been below the trip level shown in setup function 07 for longer than the delay time shown in setup function 08 22 Oxygen 1 Low 23 Oxygen 2 Low The measured oxygen level on the indicated probe has been below the trip level shown in setup function 09 for longer than the delay time shown in setup function 10 24 Oxygen 1 High 25 Oxygen 2 High The measured oxygen level on the indicated probe has been above the trip level shown in setup function 11 for longer than the delay time shown in setup function 12 26 Oxygen Deviation The difference between the oxygen level measured on probe 1 and the oxygen level measured on probe 2 is greater than the trip level shown in setup function 13 and the time delay shown in setup function 14 has expired 6 5 Warning Messages 27 Probe 1 Temperature Low 28 Probe 2 Temperature Low The probe temperature is under 650 C 1200 F The oxygen reading is therefore invalid If the probe heate
4. Altitude Degree of Protection Case Size Case Weight 100 to 240VAC 50 60 Hz Reinforced insulation Category II IEC60364 4 443 5 Watts for controller plus probe power 530W max 25 duty cycle each probe on 240VAC 110W max 100 duty cycle each probe on 110VAC 576W 2 4A max Operating Temperature 25 C to 55 C Relative Humidity 5 to 95 non condensing 2000m Maximum IP65 IP54 with internal reference air pump 315mm 12 4 wide 190mm 7 5 high 110mm 4 3 deep 3 Kg 6 6 lbs WARNING All signal level connections onto the transmitter must be treated as safety extra low voltage SELV as defined in the standard IEC61140 Double insulation must be used when connecting these terminals to systems that might carry high voltage February 2015 1732 Oxygen Transmitter NP tech Operators Manual SN CONTROLS mis 7 3 2 Operational Specifications 3 2 1 Scaling of Analog Outputs Channel 1 and Channel 2 Function Min Range Max Range Linear oxygen 1 0 to 100 Average oxygen A CA Logarithmic oxygen 0 1 20 Fixed Oxygen deficiency 10 to 0 10 to 20 E Combustibles 05 0t020 E Burner efficiency 20 00 0to100 0 No Output For Logarithmic Oxygen scaling see the appendices in the 1732 Technical Manual Output Channel 2 is independently isolated and separately scaled with the same options as analog Output Channel 1 For configurations in which one oxygen probe is used both chan
5. When the transmitter is in the Setup Menu the SETUP light will be lit The following table shows the Setup Menu menu functions Menu Function Description Range Default Value k E A ON O rc 02 Probe 2 Offset 6 0mV 0 0mV No Damping to 10 05 Damping Factor Samples Averaged 5 2 Setup Menu Display TOT robe se Selected Option Activity Indicator A Autocal active Verification that the selected option has been saved Menu name Z Probe impedance check active The purpose of having an interactive Setup Menu is to allow for configuration of the transmitter using the graphical display and keypad Once an option is changed and entered using the ENTER button that value immediately becomes active The device configuration and calibration is stored into the non volatile memory and will be retained permanently even if the device does not have power To change an option in the Setup Menu system 1 Enter the Setup Menu by pressing the SETUP RUN button once The Setup Light will come on and the display will have the format shown below The operations of the buttons are now the operations written in WHITE on the keypad The menu name is written at the bottom of the display 2 While in the Setup Menu the required function can be selected by using the FUNCTION A and FUNCTION V buttons The options available for that function can be seen by using the OPTION A and OPTION V buttons 3 When the required option
6. press the ALARM A button When the ALARM A button has been pressed the transmitter goes into the Alarm Display Mode In this mode some of the buttons take on a different function Button text Run Mode Alarm Mode SETUP RUN j Return to Run Mode DISPLAY FUNCTION V Last alarm Gas 2 PURGE 2 AUTO CAL z z This button is not used in the Alarm Display Mode When the Alarm Mode has been entered the Setup Light flashes once a second The transmitter will return to Run Mode if the SETUP RUN button is pressed a second time or after 60 seconds of keypad inactivity All relays have fail safe alarm contacts That is When the transmitter is powered off the contacts are open circuit When the transmitter is powered on but there are no alarms the contacts will be closed When there is a current unaccepted alarm event the contacts will be open circuit When there is a current accepted alarm event the state of the contacts will depend on the selection in the Commissioning Menu 53 Refer to the 1732 Technical Manual for details All alarms drive the alarm light on the front door The light will be off if there are no alarms current The light will flash if there is a current alarm that has not been acknowledged The light will be on steady if there are current alarm s that have not been cleared The light will flash faster as more alarms occur February 2015 Etech Operators Manual 1732 Oxygen Transmitter CONTROLS miia 19
7. The alarm log keeps a record of the alarm events after the cause of the alarm has been cleared It will hold a record of up to 4000 alarm events and will be retained even with the transmitter power off To view all the alarms that have occurred in the alarm log press the ALARM V button from the Run Mode The display will look like this Alarm Description Time title Time Activated P Power OXYGEN TRANSMITTER Probe 2 TC Open Ct Time Activated Time Accepted Time Cleared 08 Mar 2006 03 45 29 Alarm Log 0002 0057 Number of the alarm being viewed Total number of alarms logged Use the OPTION A and OPTION V to scroll through the alarm events that have been saved in the alarm log The alarm event will be transferred to the alarm log when the alarm has been cleared The alarms are stored in the alarm log in chronological order However it may be seen that the current alarm number will skip some numbers These numbers have been reserved for alarm events that are still current When the alarm cause has been removed these alarm events will be transferred to the alarm log The alarms are stored in the alarm log in chronological order However it may be seen that the current alarm number will skip some numbers These numbers have been reserved for alarm events that are still current When the alarm cause has been removed these alarm events will be transferred to the alarm log 6 2 Alarm Relays The common alarm relay is use
8. and regulations 1 1 Cautions Please read the safety information below before connecting power to the transmitter CAUTION 1 The probe heater is supplied with MAINS VOLTAGE This supply has electrical shock danger to maintenance personnel Always isolate the transmitter before working with the probe The EARTH wire green from a heated probe must ALWAYS be connected to earth CAUTION 2 Combustion or atmosphere control systems can be dangerous Burners must be mechanically set up so that in the worst case of equipment failure the system cannot generate explosive atmospheres This danger is normally avoided with flue gas trim systems by adjustment so that in the case of failure the appliance will not generate CO in excess of 400 ppm in the flue The CO level in the flue should be measured with a separate CO instrument normally an infrared or fuel cell type CAUTION 3 The oxygen probe is heated to over 700 C 1290 F and is a source of ignition Since raw fuel leaks can occur during burner shutdown the transmitter has an interlocking relay that removes power from the probe heater when the main fuel shut off valve power is off If this configuration does not suit or if it is possible for raw fuel to come into contact with a hot oxygen probe then the Model 1732 transmitter with a heated probe will not be safe in your application An unheated probe can be utilised in such applications however the oxygen readings are val
9. is on the display press the ENTER button to save that value When finished press the SETUP RUN button to return to the Run Mode February 2015 Etech Operators Manual 1732 Oxygen Transmitter CONTROLS miia 15 5 3 Setup Menu Functions 5 3 1 Probe 1 amp Probe 2 Offset Options 6 0mV in 0 1mV increments DO POWER OXYGEN TRANSMITTER ZEE Default 0 0mV 01 Probe 1 Offset 0 0 mV Setup Menu Each Novatech oxygen probe has an offset calibration value printed on a tag that is attached to the probe when it is dispatched To achieve the most accurate measurement of oxygen the offset value must be entered into this setup function with the same polarity as it is printed on the label For a healthy probe the offset value should be within 1 0mV NOTE An offset of 1 0mV will change the oxygen reading by approximately 1 oxygen when the probe is in ambient air However as the process oxygen measurement drops this offset will have a diminishing effect At a process gas oxygen concentration of 2 the 1 0mV offset error will only change the reading by 0 1 oxygen If in any doubt about the correct offset value set it to 0 OmV The function Probe 2 Offset will only appear if the transmitter has been configured for 2 oxygen probes 5 3 2 Lower Line Items DO POWER OXYGEN TRANSMITTER 03 Lower Line Items Probe 1 EMF Enabled Setup Menu This function allows the operator to change the items that are available to b
10. screen In order to configure the transmitter the operator must access Setup Menu This is achieved by pressing the SETUP button The transmitter will return back to the Run Mode when the SETUP button is pressed again or after a period of 60 seconds of inactivity The front panel of the 1732 Oxygen Transmitter 4 1 Run Mode Display In Run Mode the 1732 shows the first oxygen probe measurement in large characters at the top of the display and a user selectable lower line in smaller characters below Other items on the display include the activity heartbeat indicator in the top right corner a row of single letter action indicators in the bottom left corner and the current time in the bottom right corner Power Indicator gt Ss OXYGEN TRANSMITTER Probe 1 Oxygen 1 2 2 Bo Yo Heartbeat Indicator Lowerline secondary Probe 1 Temp 720 3 C process variable B x Activity Information Indicators B Burner input enabled terminals 11812 The transmitter is performing an automatic ADC calibration below operating temperature 650 C 1200F The transmitter is performing a probe impedance check A T flashing One or more oxygen probes is Z February 2015 Etech Operators Manual 1732 Oxygen Transmitter ii 9 4 2 Oxygen Display The oxygen measurement is displayed on the top line of the transmitter It can be scaled in either or ppm see chapter 5 3 3 Oxygen Display Units If Oxygen is selected in Setup Menu 04
11. the transmitter will maintain the best resolution available The display will show oxygen in the following format Range Display format 30 0 to 100 0 H 1 digit after the decimal on o mena OO m oo lt lt AAA i aia oo If Oxygen ppm is selected in Setup Menu 04 the transmitter will show the oxygen in ppm format between 10 and 9 999ppm Outside this range the oxygen will be shown in format The show oxygen in the following format Range Display format gt 10 000ppm format see above ua i lt lt ae a n Operators Manual Etech February 2015 10 CONTROLS miia 1732 Oxygen Transmitter 4 3 Keypad There are 8 buttons built into the label on front panel of the 1732 Oxygen Transmitter The button functions are written in BLACK and WHITE to identify the function of the button in either Run Mode or the Setup Menu system Setup Light J FUNCTION o Button Text oe Alarm Light A Q OPTION ALARM G OPTION Run Mode white text Cal Purge Lights N SENS Y AUTO 268 Setup Menu black blue text 1 SETUP RUN Enter Setup Menu Return to Run Mode ALARM OPTION A Next alarm Next increment option 7 GAS 1 PURGE 1 SENS IMP 8 GAS 2 PURGE 2 AUTO CAL Gas 1 Purge 1 manual activate _ o Gas 2 Purge 2 manual activate Check Probe impedance gt calibration 4 3 1 Keypad in Run Mode After the transmitter i
12. 04 Degree of Protection Provided By Enclosures IP Code This product is manufactured in Australia under ISO9001 2008 quality systems and ISO14001 2004 environmental certification Manufacturer s name Novatech Controls Pty Ltd Manufacturer s address 309 Reserve Road Cheltenham VIC 3192 AUSTRALIA Type of equipment Oxygen Transmitter Model Number 1730 Series Transmitter 1231 Oxygen Probe 1232 Oxygen Probe 1234 Oxygen Sensor hereby declare that the equipment specified herein conforms to the above directive s and standards s in 2014 Full Name Douglas Rice Position R amp D Manager
13. 1 button will turn on solenoid 1 to purge probe 1 for as long as the button is pressed Pressing the GAS 2 PURGE 2 button will turn on solenoid 2 to purge probe 2 for as long as the button is pressed Pressing the GAS 1 PURGE 1 button will turn on solenoid 1 to pass calibration gas to probe 1 for as long as the button is pressed Pressing the GAS 2 PURGE 2 button will turn on solenoid 2 to pass calibration gas to probe 2 for as long as the button is pressed Refer to the person responsible for the commissioning to find out how the transmitter has been configured Operators Manual 26 Etech February 2015 CONTROLS ms 1732 Oxygen Transmitter 8 INDEX AMS tronco drid atra ataron 21 Alarms y Ghecking Hersenen Si qheec cca caddies a sete sccdectast aside nats cueh aaushaydeatuatesso3 susendsaneaisvaces sateen eE EE AEE 22 AlarMs COMMON cra BR rr eee ee 24 Alarms Process Enabling c ccccceccseeeeeeseeeeeeeeceaeeeeeeeseaeeseaeeseaeeeaeeeeaeeeeeaeesaaeesaaeseseeesaaeeeaaeeseaeeeaeeeseaeeeeeeseaeesneeeseaeeenaees 19 Alarms Selecta iii sazdvudsubataualnnedvwedebavergs AE S tees 25 Alarms Warning Messages cscccccseeseeeseeeeeseeecaeeeeeessaeessaeesseessaeeseaeeeaaeseaeeeeaneseseeesaaesesaeesaaesesaeesaaesesaeesaeseaeeseaeeeates 25 Galibration Gas Gneck E EE ETEA EE AE E TEE da 14 27 COMPUTE ean eose eae ENE EE E N e cies iinet ee he aie 7 Display R n Mode iii aaa a a paa a aa a E a O EE O E e 11 Displa
14. 732 has a timer and solenoid driving system that can be configured to admit a certified calibration gas into the probe or an air supply to purge the probe filters through the gas connection Both the calibration gas and the filter purge gas must be piped to the port on the probe labelled CAL PURGE There are two solenoids drivers in the 1732 transmitter They can be used for a variety of combinations of gas checking and probe purging functions The available options depend on the way that the transmitter has been configured Single Probe Configuration Gas 1 amp Purge 2 Solenoid 1 should be connected to calibration gas and Solenoid 2 should be connected to the purge gas Gas 1 amp Gas 2 Solenoid 1 should be connected to calibration gas 1 and Solenoid 2 should be connected to calibration gas 2 Dual Probe Configuration Purge 1 amp Purge 2 Solenoid 1 should be connected to the purge gas on probe 1 and Solenoid 2 should be connected to the purge gas on probe 2 Gas 1 amp Gas 2 Solenoid 1 should be connected to calibration gas 1 and Solenoid 2 should be connected to calibration gas 2 The transmitter can also be configured to be in a MANUAL or AUTOMATIC purge and gas check mode The information on configuring the transmitter is contained in the 1732 Technical Manual February 2015 NEW tech Operators Manual 1732 Oxygen Transmitter CONTROLS miia 25 7 1 Actions that Occur when the Gas Sole
15. 85 2844 Victoria 3192 Email info novatech com au Australia Web site http www novatech com au Novatech Controls or their authorised dealers should carry out all maintenance and service on the product Novatech Controls can accept no liability whatsoever for any loss or damage caused by service or maintenance by unauthorised personnel This manual is intended only to assist the reader in the use of the product and therefore Novatech Controls shall not be liable for any loss or damage whatsoever arising from the use of any information or particulars in or any error or omission in this manual or any incorrect use of the product Operators Manual Etech February 2015 2 ii 1732 Oxygen Transmitter 1 USING THIS MANUAL This manual is a shortened version of the 1732 Oxygen Transmitter product manual to be used by the operator lt does not cover the commissioning calibration or servicing of the 1732 Oxygen Transmitter If more detailed information is required than what is provided in this manual please refer to the more detailed 1732 Oxygen Transmitter Technical Manual Both manuals are supplied with each transmitter and are also available to download at the Novatech Controls website http www novatech com au 1732 It is assumed in this manual that the transmitter has been installed by qualified personal and that the wiring to the main power supply the oxygen probe and all the associated signal devices complies with the local safety codes
16. ANE tech CONTROLS PTY LTD Oxygen Transmitter Model 1732 Operators Manual February 2015 TABLE OF CONTENTS 1 USING THIS MANUAL ion ida 3 APG AUTIONS a o o el das Codo Ost codo 3 1 2 WARNINE SMBOLS ita a 4 2 INTRODUCTION ccccsssscccessccccnssnsssesecuseccnnsaenseeeeusennsnsesesenuaeaeansaseeeeeauaennanseseseguauonansaseseeeauaeonaaseseseenaeasanaees 5 3 DEVICE SPECIFICAT O N S 0000 le aa a aa da Aa aaa aaa ada AN aaa 7 3 1 HARDWARE SPECIFICATIONS cccccconooncccccncononononanonnconononnnnnnnnnnnn nono nena nn AENA nono nn nana nn nn canon nena nan anna EEEREN EEEE EEEn EnEn 7 3 2 OPERATIONAL SPECIFICATIONS cooocccccccccccnnonncccnancnnnnnnnnnnannnonnn nono nana nn arcano none nan nn nnnn nn nn AEREAS EAEE canon nana na nanancnnnnns 8 3 2 1 SCALING OF ANALOG OUTPUTS CHANNEL 1 AND CHANNEL 2 wiceccccccccessseececccccsccenentececceessaseeeteceeessenans 8 3 2 2 LOCAL DISPLAY OF PROCESS VARIABLES wisiseccccccccceecececccecsccunsescecececessaueuesecseessseaueseeeceaesessneeteceeesesnane 8 4 DISPLAY AND KEY PAD siii diia 9 ARUN MODE DIS PLA das 9 CAS MAT o PES OE CO III II O tenance baat 10 A S KEYPAD aeaea E brea recast A E EE E E A E E A aut 11 43 7 KEYPADIN RUN MODE aa 11 4 3 2 KEYPAD IN THE SETUP MENU ii dd 12 4 353 INFORMATION SCREEN a A A a edd 13 5 SETUP MENU 5 aiii da sedeueantusuveduccdesvccussasvcudcdduaus cieussaeceustauuduavecceuedadansdeivecsceweadensdsidacueeuuss 15 5 1 SETUP MENU FUNCTION SUMMARY ccco
17. The 1732 Oxygen Transmitter is based on the well known model 1632 transmitter It includes a number of hardware and software improvements such as a graphic display larger characters faster microprocessor simplified set up menu alarm logging faster probe heater control and more calculated values such as burner efficiency The 1732 Oxygen Transmitter has a variety of user selectable functions They are simple to use because each selection is menu driven For options you are not sure about read the manual on that particular item in chapter 5 Setup Menu Features include Inputs Two zirconia oxygen probe heated or unheated Oxygen range from 1 x 10 to 100 Furnace kiln or flue thermocouple field selectable as type K J RorS Main flame established safety interlock for heated probes only Purge flow switch Outputs Two linearised 4 20mA or 0 20mA DC isolated outputs max load 1000Q The output function and the range are field selectable Common alarm relay programmable Three other alarm relays with selectable functions Computer RS 232 or RS 485 for connection of a computer terminal or printer for diagnostics of the transmitter probe or combustion process This connection is suitable for network connection to a computer DCS or PLC using MODBUS protocol Display Multi font graphical display Large characters for the oxygen on the top line Multiple lower line items for the secondary functions ie Probe temperature Ox
18. able is 1 Model and version of the current firmware The date time that the firmware was compiled The maximum temperature that the transmitter has measured inside the cabinet Current date and time The time of all the next timed events Impedance test cal purge 1 cal purge 2 ADC calibration data analogue input calibration DAC calibration data analogue output calibration Probe temperature record probe 1 and 2 oNN The information screen is accessed from the Run Mode by pressing and holding the ALARM ACCEPT button and then pressing the SETUP RUN button The first data appears at the top of the screen and there is a scroll bar down the left hand side The data can be scrolled through by using the DISPLAY A and DISPLAY V buttons The data is for reference only and cannot be changed February 2015 Etech Operators Manual 1732 Oxygen Transmitter CONTROLS miia 13 This page has been intentionally left blank Operators Manual 14 NEW tech CONTROLS m 119 February 2015 1732 Oxygen Transmitter 5 SETUP MENU This chapter describes the functions available in the Setup Menu on the 1732 Oxygen Transmitter The Setup Menu is mode is accessed from Run Mode by pressing the SETUP button momentarily so the words Setup Menu appear at the bottom of the display The transmitter will return to the Run Mode when the SETUP button is pressed again or after 60 seconds of keypad inactivity 5 1 Setup Menu Function Summary
19. d to monitor faults within the transmitter and the probe The list of events that will cause the common alarm relay to be activated is shown in chapter 6 3 Common Alarms The relay contacts will be open circuit if there is a current alarm condition The contacts will close again when the alarm has been acknowledged The other three alarm relays are user defined and are used to monitor the process The function of the process alarm relays is user selectable See chapter 6 4 Selectable Process Alarms and the 1732 Technical Manual for further information February 2015 Etech Operators Manual 1732 Oxygen Transmitter CONTROLS miia 21 6 3 Common Alarms The events that drive the common alarm relay are 1 Probe 1 High Impedance 2 Probe 2 High Impedance Oxygen probe or electrode failure high impedance This alarm is inhibited when the probe temperature is under 650 C 1200 F 3 Probe 1 Heater Fail 4 Probe 2 Heater Fail In the first 20 minutes of power being applied to the heater after being switched on this alarm will not occur but a T display will be shown on the bottom of the display If an ADC alarm occurs the heaters will automatically be turned off If the probe has not reached 650 C 1200 F in 20 minutes the Probe 1 2 Heater Fail alarm will be raised 5 Probe 1 TC Open Circuit 6 Probe 2 TC Open Circuit Probe thermocouple is open circuit The heater in heated probes will swi
20. e retrieved on device start up If this button is not pressed before changing to a new function then the previous option will be retained SENS IMP When this button is pressed the transmitter will measure the impedance of oxygen probe s attached to the transmitter If the burner is not enabled terminals 10 amp 11 or the probe temperature is below 700 C 1292 F impedance checking will not be performed During impedance checking a Z will be seen in the bottom left hand corner of the display AUTO CAL When this button is pressed the transmitter will calibrate the analog output channels that are set to auto calibration This is performed by directing the output current away from the output terminals terminals 12 amp 13 and 14 amp 15 and back the current back into the transmitter input The transmitter will then calculate a zero and a span calibration factor for each of the output channels The output calibration will only happen if the channel is not set to manual output calibration see 1732 Technical Manual for more details During this process normal output to the analog channels will be interrupted sending the outputs open circuit Operators Manual Etech February 2015 12 ii 1732 Oxygen Transmitter 4 3 3 Information Screen The 1732 Oxygen Transmitter has an information screen available to the user to allow more detailed information about the running of the transmitter to be easily read by the user The information avail
21. e alarm and the date time that the alarm was acknowledged ALARM ACCEPT Press this button to acknowledge the currently displayed alarm see Chapter 6 Alarms Gas 1 PURGE1 GAS 2 PURGE 2 These two buttons are used to turn on the gas purge solenoids When the transmitter is in the manual cal purge mode Commissioning Menu function 23 32 the solenoid will be activated for as long as the button is pressed When the transmitter is in the auto cal purge mode the automatic cal purge cycle is started The cycle can be stopped by pressing the same button again see Chapter 7 Gas Calibrate and Purge 4 3 2 Keypad in the Setup Menu From Run Mode if the SETUP RUN button is pressed once the transmitter will display the Setup Menu For information about accessing the Commissioning Menu or Calibration Menu see the 1732 Technical Manual The following functions are then available in the Setup Menu SETUP RUN Pressing this button while in the Setup Menu will return the transmitter to the Run Mode FUNCTION A FUNCTION V These two buttons allow the selection of the Setup Menu function A function summary table is found at the start of Chapter 5 1 Setup Menu OPTION A OPTION V These two buttons allow for modifying the option for the selected function A list range of options for each function is found in Chapter 5 3 ENTER This button applies updates the currently displayed option and stores the value in non volatile memory to b
22. e displayed on the lower line of the transmitter in Run Mode If the word Enabled appears on the display for a selected lower line option the measurement will be available to be shown on the display in the Run Mode by scrolling through the list using the DISPLAY A and DISPLAY V buttons Each individual lower line measurement can be enabled or disabled by pressing the ENTER button OPTIONS Temperature Probe 1 Temperature Probe 2 Sensor EMF Probe 1 Sensor EMF Probe 2 Sensor Impedance Probe 1 Sensor Impedance Probe 2 Oxygen Probe 2 Boiler Efficiency Oxygen Average Probe 1 and Probe 2 Flue Pressure Auxiliary TC Temperature Burner Run Time Ambient Temperature Service Date Oxygen Deficiency Probe 1 Oxygen Deficiency Probe 2 Combustibles Probe 1 Combustibles Probe 2 Carbon Dioxide Maximum Dry Probe 1 Carbon Dioxide Maximum Dry Probe 2 1 Requires Single Probe and Aux TC Type to be set Operators Manual NET tech February 2015 16 ii 1732 Oxygen Transmitter 5 3 3 Oxygen Display Units DO power OXYGEN _TRANSM IER Options Oxygen Oxygen ppm 04 oxygen Display Units Default Oxygen Oxygen Saved Setup Menu The top line of the display that shows the oxygen measurement can be displayed in either or parts per million ppm 5 3 4 Damping Factor Options No Damping 1 to 10 Samples Averaged Default 5 Samples P POWER OXYGEN TRANSMITTER
23. id only above 650 C 1200 F CAUTION 4 The reducing oxygen signal from the transmitter and the associated alarm relay can be used as an explosive warning or trip This measurement assumes complete combustion If incomplete combustion is possible then this signal will read less reducing and should not be used as an alarm or trip A true excess combustibles analyser normally incorporating a catalyst or thermal conductivity bridge would be more appropriate where incomplete combustion is possible Also read the probe electrical shock caution in the probe heater interlock caution in chapter 4 7 of the Model 1732 Technical Manual CAUTION 5 FIL 3 filter If the optional FIL 3 has been fitted to the 1231 probe in this installation please read the Important Notice in the Technical Manual February 2015 Etech Operators Manual 1732 Oxygen Transmitter CONTROLS miis 3 1 2 Warning Symbols Operators Manual 4 Danger high voltage Risk of electrical shock Caution hot surface Caution risk of danger See additional information in the manual Atech February 2015 1732 Oxygen Transmitter 2 INTRODUCTION The Novatech 1732 Dual Probe Oxygen Transmitter is designed to measure the oxygen gas concentration in combustion applications such as power stations and industrial boilers The measurement is used to control the air fuel ration in the burner to maintain efficiency and safe operation conditions
24. nccnnnanananannna concannnnn nana cano ncanan nana nan ananananan ca naanaas 25 7 1 ACTIONS THAT OCCUR WHEN THE GAS SOLENOID BUTTONS ARE PRESSED coooccccccccnonononanncnancnnnononanacininnnns 26 Be INDE CPE Ce Ue Pee devetesuceaceucuddecdedweccdeueuccccedewetecedeudauctudvccccedeus 27 February 2015 Etech Operators Manual 1732 Oxygen Transmitter 1 Copyright NOVATECH CONTROLS PTY LTD 2015 This manual describes the transmitter firmware version 1 29 February 2015 Neither the whole nor any part of the information contained in or the product described in this manual may be adapted or reproduced in any material form except with the prior written approval of Novatech Controls Pty Ltd Novatech The product described in this manual and products for use with it are subject to continuous developments and improvement All information of a technical nature and particulars of the product and its use including the information in this manual are given by Novatech in good faith However it is acknowledged that there may be errors or omissions in this manual A list of details of any amendments or revisions to this manual can be obtained upon request from Novatech Controls Technical Enquiries Novatech Controls welcome comments and suggestions relating to the product and this manual All correspondence should be addressed to Technical Enquiries Novatech Controls Pty Ltd 309 Reserve Road Tel 61 3 9585 2833 Cheltenham Fax 61 3 95
25. nels transmit Oxygen process variables based on that probe For configurations with two oxygen probes Channel 1 outputs process variables related to oxygen probe 1 and Channel 2 outputs process variables related to probe 2 3 2 2 Local Display of Process Variables Process Variable Range Notes Probe 1 2 Oxygen 1x10 to 100 Probe 1 is displayed always probe 2 is displaued if the transmitter is configured for dual Probe 1 2 EMF 40 to 1350mV probe cee ae TZ E O A A O l aS Max Theoretical Dry CO 0 to 40 0 Burner Efficiency 0 to 100 0 Oxygen display units automatically default to range above 10 000ppm 1 The oxygen deficiency output can be used in the same way as a combustibles analyser to signal the extent of reducing conditions of combustion processes Operators Manual Etech February 2015 8 CONTROLS miia 1732 Oxygen Transmitter 4 DISPLAY AND KEYPAD The 1732 Oxygen Transmitter has a graphic display 8 buttons and 5 LED indicators to show the stats of the transmitter All of the buttons have multiple functions depending on what is currently on the display As a general starting point the larger white text on the button is the function while the transmitter is in the Run Mode and the smaller black text on the button is the function in the Setup Menu When the transmitter is sitting idle it will revert to Run Mode in which standard information relating to the process appears on the
26. noid Buttons are Pressed Purge and Gas check Number of mode probes E O D O D Gas option Pressing the GAS 1 PURGE 1 button will start the timed gas check cycle on solenoid 1 to button 1 Pressing the GAS 2 PURGE 2 button will start the timed filter purge cycle on solenoid 2 to probe 1 Pressing the GAS 1 PURGE 1 button will start the timed gas check cycle on solenoid 1 to probe 1 Pressing the GAS 2 PURGE 2 button will start the timed gas check cycle on solenoid 2 to probe 1 Pressing the GAS 1 PURGE 1 button will start the timed filter purge cycle on solenoid 1 to probe 1 Pressing the GAS 2 PURGE 2 button will start the timed filter urge cycle on solenoid 2 to probe 2 Pressing the GAS 1 PURGE 1 button will start the timed gas check cycle on solenoid 1 to probe 1 Pressing the GAS 2 PURGE 2 button will start the timed gas check cycle on solenoid 2 to probe 2 Pressing the GAS 1 PURGE 1 button will turn on solenoid 1 to purge probe 1 for as long as the button is pressed Pressing the GAS 2 PURGE 2 button will turn on solenoid 2 to purge probe 1 for as long as the button is pressed Pressing the GAS 1 PURGE 1 button will turn on solenoid 1 to pass calibration gas to probe 1 for as long as the button is pressed Pressing the GAS 2 PURGE 2 button will turn on solenoid 2 to pass calibration gas to probe 1 for as long as the button is pressed Pressing the GAS 1 PURGE
27. occccccccconononononcncconononnnncnnnnnnnnnnnnnanncnnnnnnnnnn nana nnnnnnnnnnnnnncnnnnnnnnnnnnnacacannns 15 5 2 SETUP MENU DISPLAY da 15 5 3 SETUP MENU FONCTIONS eiii Aiii ei aa Pead a Revie BY ale dda ded adie va coded Pe 16 5 3 1 PROBE 1 amp PROBE 2 OFFSET accesarii ania rara a aE a aaa raaa ae Ana a ira aaa a ari aaia 16 5 3 2 LOWER LINE ITEMS morate a aa a aari aea aa 16 5 3 3 OXYGEN DISPLAY UNITS uucccccccseeecececcccccesencececececeeeanensesececeeeaeeaersesseeeaeseauensrsesseeeuseauenesecesessssanerseseeeees 17 AD NERO c1cccccccccccceeecececcccececeunenseceeceueeaeeneeseseceseseauenseseceeessauenedsesseceussauenseseceeseussanenseseeeees 17 5 3 5 PROCESS ALARM a ab dass 17 6 ALARMS cui ataca 19 6 1 CHECKING AND ACCEPTING AN ALARM occcccccncnonoccnncnnonononanoncnnnonononennnnnnnnnnnnnonnnncnnnnannnnnnnnnnnnn anna nn nnnnnnacacannns 20 6 1 1 CURRENT ALARMS I 20 6 1 2 ALARM LOG wiwwissvecccccccsenssnescssatecctsntasessassenscevssesesssnssactensiesseseatiancunstenesenstbentssasssessacnenssevscesacaanbaavsesssacs 21 6 2 ALARM PEAY Siac ats ccectceee E E E sauatac Desaaibtd 21 6 3 COMMON ALARMS coi aan 22 6 4 SELECTABLE PROCESS ALARMS cccononoccccnnconononenannnnannnonononnnnnnnnnnnnnnnnnnannn anna nono nena aA aid anna nn aia iaaa 23 6 5 WARNING MESSAGES ccccocooccccccnnonononanoncnnnonononnnnnnnnnnnnnnnnn nena anar E a EAE n nana anar anna none nana anna E EEA 23 7 GAS CALIBRATE AND PURGE oooccocccconononanananonanononanananannn
28. r has been on for more than 20 minutes and the temperature is less than 650 C 1200 F a Probe 1 2 Heater Fail alarm will occur There will be a flashing T symbol on the bottom left hand corner of the display until the temperature of the probe s is over 650 C 1200F NOTE The Probe 1 2 Temperature Low function is also used with unheated probes to show that the probe temperature is below 650 C 1200 F when the process temperature falls below this level 29 Cal 1 in Progress 30 Cal 2 in Progress A calibration check is occurring either manual or automatic mode 31 Purge 1 in Progress 32 Purge 2 in Progress A probe purge is occurring either manual or automatic mode February 2015 Etech Operators Manual 1732 Oxygen Transmitter CONTROLS miis 23 This page has been intentionally left blank Operators Manual 24 NEW tech CONTROLS m 119 February 2015 1732 Oxygen Transmitter 7 GAS CALIBRATE AND PURGE The Novatech oxygen sensor that is used in the Novatech oxygen probe is extremely predictable stable and reliable For this reason the calibration of a Novatech oxygen system does not require the use of calibration gases However all Novatech oxygen probes have a built in gas connection that does allow the accuracy of the probe to be checked This chapter describes the operation of this gas checking system For further details see the 1732 Technical Manual The 1
29. r the operation of the heater current As a result the transmitter will give an alarm within 1 second of a heater power control switch Solid State Relay failure If either of the SSR s are found to be faulty both heaters will be turned off immediately and the alarm will be raised The SSR must be replaced The SSR Leakage alarm will occur if one of the heater SSR s are partly shorted If probe 1 SSR has failed and only one probe is being used the 1732 Technical Manual describes how the SSR for probe 2 can be selected instead If 2 probes are being used but neither of the solenoid outputs are being used consult the Technical Manual Operators Manual Etech February 2015 22 ii 1732 Oxygen Transmitter 16 Probe 1 Filter Blocked 17 Probe 2 Filter Blocked Blocked probe filter This test is only performed when automatic purging of the probe is selected Refer to the 1732 Technical Manual for further details This alarm will not reset until the next purge cycle that can be initiated manually or automatically or the power to the transmitter is turned off and back on 18 Gas 1 Calibration Error 19 Gas 2 Calibration Error This alarm will only be raised if the oxygen measurement during an automatic gas calibration check falls outside the set gas limits This alarm will not reset until the next purge cycle that can be initiated manually or automatically or the power to the transmitter is turned off and back on
30. s powered on and has completed the initial startup procedure it will enter the Run Mode In this mode the top line of the display will show the oxygen measurement from probe 1 The other button functions are SETUP RUN By pressing this button once from Run Mode the transmitter will enter the Setup Menu system In the Setup Menu the function of each of the buttons is reassigned Pressing the SETUP RUN button a second time while in the Setup Menu will return the transmitter to the Run Mode If the transmitter is left idle in the Setup Menu for more than 60 seconds it will automatically return to Run Mode DISPLAY A DISPLAY V The display buttons are used to scroll the lower line up and down through the variety of measurements that are available on the lower line For a complete list of options see chapter 5 3 2 Lower Line ltems ALARMA If there is either a new alarm or an active alarm the ALARM A button can be pressed to examine the alarm status The Alarm Light will be flashing if there is a new alarm or steady if there is an existing alarm see Chapter 6 Alarms The Setup Light will flash slowly to show that the transmitter is now in the alarm display mode February 2015 1732 Oxygen Transmitter NET tech Operators Manual 11 ALARM V When the transmitter is displaying active alarms the ALARM A button has been pressed the ALARM A button and ALARM V button allow the operator to examine the date time of th
31. tch off 7 Auxiliary TC Open Circuit Stack thermocouple is open circuit If the thermocouple is not needed select NO T C for Aux TC Type or place a short circuit between terminals 7 amp 8 8A Reference Air Pump Fail The reference air pump in the transmitter is either disconnected or is drawing lt 20mA 8B Reference Air Pump Overload The reference air pump in the transmitter has drawn gt 300mA The power will be turned off to the pump to avoid damage to the pump driving circuit The 1732 will attempt to restart the pump every minute To force a restart disconnect the pump and reconnect it 9 ADC Calibration Fail The analog to digital converter has been found to fall outside the normal calibration specifications In this case the probe heater will automatically be turned off 10 Output 1 Failure 11 Output 2 Failure The digital to analog and voltage isolator circuit has been found to fall outside the normal calibration specifications This check is only performed when the AUTO CAL button is pressed 12 BBRAM Fail All of the setup options are held in the battery backed memory BBRAM This is the battery shaped device at the bottom centre of the 1730 1 PCB labeled MEM1 This alarm will occur when this device fails and will need to be replaced 13 Heater 1 SSR Failure 14 Heater 2 SSR Failure 15 Heater SSR Leakage The 1732 has the ability to monito
32. y Setup Menu eecceeeceeceeeeeeeeeeeeeeeeeecaeeeeeeseaeeseaeesaaeeeeaeessaeesaeeeeseeeeaeeecseeeeaeeseaeeseaeeseaeeseaeeseeesseeeeeeseneeeeieeeeieeeeaes 17 PP chet sessactrnaidellebesde eussaacaesh sees caveats Meserecsec assaeasel eras Sattancuuase E E EE 7 IK GY ici a ca do cies 13 Lower Line Changes iii di 18 OUTPUT RANG SS tarro ercer Ian Sheds eeatei gies E de raro sa 10 A tec a EE cad eee hcg weet EREE batec eased E E E E E A tien EiS 7 a100 KEI EEE od 18 Setup Men s scarann aee oe e N ola o AE E a pi dt 17 Specifications HardWarS iocii id a bl necia diesen 9 Specifications Operational oooooinnccnnininncnnnnocnncnnocnnnccn narran nnnananns 10 Units Oxygen DISplay sess ise ceteedeanicecceeetsnd cnsacnideeteaceedaapatacceusheedeut eats euvecsaspteessepedncesuchasscgaasleasdaeedyendeupheaiee aaa 19 Voltage mains SUpDIV uscar dina 9 WTS ii e A 5 February 2015 NEW tech Operators Manual 1732 Oxygen Transmitter id ii 27 DECLARATION OF CONFORMITY Application of Council Directives 2004 108 EC 2006 95 EC Standards to which conformity is declared EN61010 1 2010 Safety Requirements for Electrical Equipment for Measurement Control and Laboratory Use EN50270 1999 Electromagnetic Compatibility Electrical Apparatus for the Detection and Measurement of Combustible Gases Toxic Gases or Oxygen CFR47 FCC Part 15 Subpart B Class A Electromagnetic Compatibility Radiated and Conducted Emissions AS60529 20
33. ygen for the second probe Alarm display mode that shows the time the alarm occurred and the acceptance time Alarm log mode that keeps the time the alarm occurred the acceptance time and the time the alarm was cleared for the last 4 000 alarms Power Universal mains supply voltage 100 to 240VAC Automatically detects the mains voltage and frequency and set the power control accordingly February 2015 Etech Operators Manual 1732 Oxygen Transmitter CONTROLS miis 5 This page has been intentionally left blank Operators Manual 6 NEW tech CONTROLS m 119 February 2015 1732 Oxygen Transmitter 3 DEVICE SPECIFICATIONS 3 1 Hardware Specifications Number of Oxygen Probes Oxygen Range Oxygen Accuracy Thermocouple Types Temperature Accuracy Analog Outputs 1or2 1 x 10 30 to 100 11 of actual measured oxygen value with a repeatability of 0 5 of the measured value Type K and J 2 C 0 20mA or 4 20mA field selectable Active Outputs WARNING DO NOT LOOP POWER OUTPUTS Use only passive receivers for commissioning and testing The use of loop powered receivers will damage the output Output Load Alarm Relays Alarm Relay Contacts 1000 ohm max 4 2A 240VAC 2A 30VDC Reinforced insulation when used with mains voltage WARNING Do not use both mains voltage and low voltage connections to adjacent alarm contacts Mains Voltage Supply Overvoltage Power Environmental Rating
Download Pdf Manuals
Related Search
Related Contents
HYGIESOLV - Hygiena Boutique Bosch GAS 25 L SFC Guida dell`utente monitor tattile Manual del usuario Manuale d`uso TG-1 PocketBook SurfPad Instruction Guide Placas de cocción, encimeras, cocina, vitroceramica Owner`s Manual - Gander Mountain SUNNY TRIPOWER 15000TL Economic Excellence / 20000TL GOLDEN SCAN 3 Copyright © All rights reserved.
Failed to retrieve file