FS720 Commissioning / Maintenance / Troubleshooting

image

Contents

1. 8 Click on OK in the Information window The FW update main and additional CP Us window is displayed Only close this window once the firmware update is complete 9 Follow the procedures on the display of the Station and wait until the following lines appear Switch off 38 2 now The panel will reboot automatically 80 Building Technologies A6V10210416_f_en_ Fire Safety 14 01 2013 Updating the firmware of the Station Updating the firmware of the main CPU and the additional CPUs 10 Click on Close in the FW update main and additional CP Us window The following window is opened gt y Information e FCM2004 J Set 538 2 on the FCM2004 to OFF OR FCM2027 Reboots automatically after a successful update Initialize the station and check the FW of additional CPUs 11 On the Station set the S 38 2 switch to OFF gt The Station is restarted many times This procedure takes up to ten minutes 12 Click on OK in the Information window After the restart the Station display shows the available BDVs It is not necessary to install a BDV at this point iJ Initializing the Station instead of installing the BDV saves time During initialization the BDV and the configuration data
2. Scope The information contained in this document is valid for introduction package IP 4 Target groups The information in this document is intended for the following target groups Target group Activity Qualification Installation personnel Assembles and installs the product Has received specialist training in the components at the place of installation area of building installation technology e Carries out a performance check or electrical installations following installation Commissioning personnel Configure the product at the place of Has obtained suitable specialist installation according to customer training for the function and for the specific requirements products Check the product operability and Has attended the training courses for release the product for use by the commissioning personnel operator Searches for and corrects malfunctions Maintenance personnel Carries out all maintenance work Has obtained suitable specialist Checks that the products are in perfect training for the function and for the working order products Searches for and corrects malfunctions Reference document and source language e The source language of this document is German de e The reference version of this document is the international version in English The international version is not localized The reference document has the following designation ID_x_en_ x modification index e
3. Error during firmware update If errors occur during the firmware update the error messages are shown after the update on the Station display The line P ress Silence buzzer button is displayed after the error messages 1 Press lt Silence buzzer gt on the Person Machine Interface The Station restarts gt gt After a few minutes the Buzzer sounds twice 2 Press lt Acknowledge gt on the Person Machine Interface to switch off the Buzzer Do not perform any more actions on the Station until the Buzzer has sounded for the second time See also Preparation and security gt 71 83 Building Technologies A6V 10210416 f_en_ Fire Safety 14 01 2013 Updating the firmware of the Station Update the firmware of the additional CPUs 20 8 Update the firmware of the additional CPUs NOTICE Updating the firmware of the degraded mode module FN2001 If the firmware of the degraded mode module FN2001 has to be updated it must be temporarily connected to the slot for the main module FN2001 from slot X12 to X13 gt Familiarize yourself with the information in the chapter P reparation and security 1 Select Update gt FW update additional CPUs from the menu bar 2 Ifthe Password check window is open enter the password 1234 and click on OK The following window is opened Connect Local connection Target station address 4 3 Select
4. Ensure that all points listed in the Testing the product operability section below are observed You may only set controls to normal function when the product operability has been completely tested and the system has been handed over to the customer Testing the product operability e Prevent the remote transmission from triggering erroneously e ftesting building installations or activating devices from third party companies you must collaborate with the people appointed e The activation of fire control installations for test purposes must not cause injury to anyone or damage to the building installations The following instructions must be observed Use the correct potential for activation this is generally the potential of the building installation Only check controls up to the interface relay with blocking option Make sure that only the controls to be tested are activated e Inform people before testing the alarm devices and allow for possible panic responses e Inform people about any noise or mist which may be produced e Before testing the remote transmission inform the corresponding alarm and fault signal receiving stations Modifications to the system design and the products Modifications to the system and to individual products may lead to faults malfunctioning and safety risks Written confirmation must be obtained from Siemens and the corresponding safety bodies for modifications or additions M
5. Switch the test mode on Link gt 32 Replace the C NET device Link gt 61 Switch normal operation on Link gt 32 Connect the PC to the Station Link gt 20 Load the configuration from the Station to the PC Link gt 24 Disconnect the PC from the Station Link gt 20 Sy oO ee Oe I a The work described in this chapter may be performed when the C NET detector line is switched on Building Technologies Fire Safety A6V 10210416 f en 14 01 2013 Removing or replacing non stationary devices Base with loop contact 18 1 2 1 18 1 3 18 1 3 1 Replacing a device 1 Remove the C NET device you want to replace from the base 2 Wait approx 20 seconds 3 Insert the new C NET device of the same type The internal alarm indicator flashes for 10 seconds following successful replacement Proceed as follows if the alarm indicator does not flash 1 Ensure that you wait long enough before inserting 2 Check whether other C NET devices are missing on the detector line 3 Check whether a device that is not of the same type has been inserted If this is the case insert a device of the same type 4 Restart the C NET line Replacing non stationary devices of different types You will find additional information about the individual steps on the specified pages 1 Remove the C NET device from its base The Station detects that the device is missing and reports
6. Updating the firmware of the MCL USB adapter FDUZ221 The firmware of the MCL USB adapter FDUZ221 must be updated if a new firmware version is issued Preparation gt The driver for the MCL USB adapter is installed on the PC You will find instructions for installing the driver in document 009854 See chapter Applicable documents Select File gt Import new FW package In the selection window open the corresponding file F F XS2007 XX_x_X_ Zip Connect the MCL USB adapter to the PC The orange LED on the MCL USB adapter flashes for a short while When the device is ready for operation the green LED lights up ee ene FDUZ221 Connection of the PC to the MCL USB adapter Updating the firmware 1 Select Update gt FW update FDUZ221 MCL USB adapter The connection to the device is established The FW update FDUZ221 MCL USB adapter window opens The latest firmware package and the latest firmware version are suggested The green LED goes out opg Building Technologies Fire Safety A6V10210416_f_en_ 14 01 2013 Updating the firmware of the peripheral devices Updating the firmware of the floor repeater terminal FT2010 21 2 2 Click on Start When the hardware version is unknown another FW update FDUZ221 MCL USB adapter window is opened and you are prompted to check the hardware version When the hardware version is known the status bar indicates th
7. O OOO O g o Oo o 2 en A Q OO Oo oO O OE ot i O Cio 19 L s 3 o O Fault messages on the Person Machine Interface The table below shows the causes and measures should a fault be displayed LED LED flashes Cause What must be done 1 FAULT The Site has a fault Check whether another fault LED is flashing if not Check the display Check whether the Fault control input is activated 5 System Fault Failure of the main CPU Visual check of the cable connections Check whether the red LED H37 on the operating unit FCM 72xx is on Exchange PMI amp mainboard Fault of a component Restart Station When the Fautt is still indicated exchange the module Communication fault of a Check the transmission line networked Station Check the faulty Station 8 Remote alarm Fault Transmission equipment has a Check remote transmission Off Fault 10 Alarm device F ault Acoustic control line Fault Check the Line for open line short circuit or end of line element EOL is missing or defective 12 Control function Fault Fire control line F ault Check the Line for open line short circuit Check the function of the external control devices Check the function any existing feedback switch 24 4 Fault indicators on components The components are equipped with LED indicating the st
8. 63 Building Technologies Fire Safety A6V 10210416 f_en_ 14 01 2013 Removing or replacing non stationary devices Temporarily removing multiple non stationary devices 64 18 3 Temporarily removing multiple non stationary devices The procedure in this chapter applies both for the base with loop contact and the base without loop contact For the purpose of painting work it may be necessary to temporarily remove the C NET devices in a room Each C NET device must then be re inserted in its original base The C NET devices may not be exchanged Mark the allocation of the devices to the respective base to avoid additional work steps You will find additional information about the individual steps on the specified pages Switch the Zone off Link gt 30 Remove the C NET devices from their bases Perform the tasks Re insert the C NET devices to the respective position Switch the Zone on Link gt 30 Forall the re inserted C NET devices a localization fault is displayed 6 Restart the C NET detector line Link gt 30 If detectors have been swapped over or are missing the following messages are shown on the display of the Person Machine Interface Zone Serial no ID Nr Dev location fault Oe w Ne The work described in this chapter may be performed when the C NET detector line is switched on Building Technologies Fire Safety A6V10210416
9. Applicable documents e The procedure for updating the firmware depends on the Station configuration A Station can be configured as follows Standalone Station SAFEDLINK Station Router Station Ethernet Station Modular Station with CPU card e Windows firewall setting Toconnect the PC to the Station the Windows firewall settings must be changed if possible You will find more information on this in chapter Setting Windows firewall gt 77 Communication with GAP via C WEB LAN A GAP with DHCP must be configured for a connection with the PC via C WEB LAN You will find more information in document A6V10210424 See chapter Applicable documents Once the firmware has been updated the Station configuration must be loaded to Cerberus Engineering Tool in order to update the LRC data to the current firmware status A WARNING Fire detection installation is deactivated during the firmware update Fire may spread unhindered Supervision by people is required Re activate the fire detection installation as soon as possible 71 Building Technologies Fire Safety A6V 10210416 f_en_ 14 01 2013 Updating the firmware of the Station Updating the firmware of the main CPU and the additional CPUs Overview NOTICE Data loss during the firmware update Configuration data and event memory are deleted in the Station e Load the configuration data and e
10. Command executed You will find detailed information on the result of the auto configuration in the List of compatibility See chapter Applicable documents See also Applicable documents gt 8 Loading automatically created configuration to the PC 1 Select the File gt New site menu item gt The Create new site window opens 2 Select the Upload from station s option field 3 Click on Next The Create site by uploading from station s and Connect windows are opened 4 Inthe window Connect select Local connection and then click on OK The configuration is loaded to Cerberus E ngineering T ool The advancement status is displayed in the Create site by uploading from station s window The Site properties window is opened after loading 5 Change the entries if required and click on OK The New site confirmation window opens 6 Click on Yes The Site is opened in Cerberus Engineering T ool Adapting configuration Adapt the configuration in the Site in Cerberus E ngineering Tool e g Changing customer texts Setting the properties and the parameter sets Changing allocation of Zones and Sections Configuring controls Configuring the operating and display units Configuring the network You will find information about configuring a Site in document A6V10210424 See chapter Applicable documents See also Applicable documents
11. C Commissioning networked Stations 10 C Commissioning networked Stations NOTICE Commissioning as standalone Station Commissioned as standalone S tation Stations cannot be combined to form a networked Site later on e initialize networked Stations using a network address right from the start Prerequisites e The detector lines and C NET devices are installed e The acceptance test has been carried out for the detector lines e The Station is installed but the batteries are not connected yet J The cables for the detector lines and the mains supply have been inserted in the Station but not yet connected Cerberus E ngineering T ool is installed on the PC e The current firmware and BDV are available on the PC iJ You will find additional information about the individual steps on the specified pages Commissioning 1 Create a Site and the Stations in Cerberus Engineering T ool and pre configure if required 2 Prepare each Station individually for commissioning without BDV installation Link gt 28 Connect the PC to each Station individually Link gt 20 Initialize each Station individually Link gt 21 Read in the C NET devices for all Stations Link gt 31 Load the configuration from the Station to the PC Link gt 24 Adapt the configuration in Cerberus Engineering T ool Link gt 29 Load the configuration from the
12. gt 23 Initializing Station gt 21 mg mg 5 4 Initializing Station e Each Station in a fire detection system with several networked Stations must have a unique address e Once a Station has been started for the first time or once the firmware on the main CPU has been updated a Station has the address 1 Networked S tations must therefore all be initialized e lf two Sites are merged to form one Site the Stations with the same addresses in the added Site must each be given a new address e The Initialize station procedure issues the Station an address within the Site according to the configuration in Cerberus Engineering T ool A standalone Station does not have to be initialized If you use a number of network cards on the PC observe the information in the chapter IP settings for several network cards in document A6V 10210424 See chapter Applicable documents 21 Building Technologies Fire Safety A6V 10210416 f_en_ 14 01 2013 Connectivity and communication with Station Initializing S tation Initialize Station NOTICE Connection module card cage FCA2006 A1 defective or installed incorrectly Control panels identified incorrectly e g FC 726 identified as FC724 e Check that the connection module card cage FCA2006 A1 is installed correctly gt The PC is connected locally to the
13. gt 8 29 Building Technologies Fire Safety A6V 10210416 f_en_ 14 01 2013 General commissioning steps Switch on detector line 30 6 7 6 8 6 9 6 10 6 11 Switch on detector line 1 4 GYD In the main menu select Topology gt Hardware tree gt Station gt Line card gt Detector line Press the More Options softkey and select E xecute commands Select the Detector line ON command The yellow MENSAJES DE DESCONEXIONES LED goes out The C NET detector line is switched on Switching off the detector line 1 4 GYD In the main menu select Topology gt Hardware tree gt Station gt Line card gt Detector line Press the More Options softkey and select E xecute commands Select the Detector line OF F command The yellow MENSAJES DE DESCONEXIONES LED lights up The C NET detector line is switched off Restarting the detector line 1 4 GYD In the main menu select Topology gt Hardware tree gt Station gt Line card gt Detector line Press the More Options softkey and select E xecute commands Select the Restart line command The C NET detector line is restarted The following message is displayed following restart Command executed Switching off Zone 1 3 GYD Select Topology gt Detection tree gt Area gt Section gt Zone in the main menu Press the More Options softkey and se
14. 108 You will find information about installing and uninstalling the components in document A6V10210390 See chapter Applicable documents 1 First disconnect the negative battery terminals then the positive terminals 2 Remove the disconnect terminal block that is mounted on a DIN rail in the housing The mains connection is interrupted Exchange the components 4 Re insert the disconnect terminal block The mains connection is intact gt The Station starts First connect the negative battery terminals then the positive terminals 6 Enter the date and time To do this select the Settings administration gt System commands gt Set system time menu items 7 If need be carry out partial commissioning Date and time are not saved in the Station The date and time must be reset to restart the Station S pare parts e You will find details for ordering spare parts for Stations in document A6V 10227652 e You will find details for ordering Detectors and accessories in document A6V 10225323 See chapter Applicable documents See also Applicable documents gt 8 Building Technologies Fire Safety A6V 10210416 f en 14 01 2013 Repair Fault messages on the Person Machine Interface 24 3 Fault messages on the Person Machine Interface
15. 2 74 Familiarize yourself with the information in P reparation and security gt 71 Connect the PC to the Station Link gt 20 Enable the Station Press lt MENU gt and enter a valid PIN Update the firmware of the additional CPUs if there is a higher firmware version status Select the local connection as the connection type Link gt 84 Load the configuration from the Station to the PC Link gt 24 Disconnect the PC from the Station Link gt 20 Building Technologies Fire Safety A6V 10210416 f en 14 01 2013 Updating the firmware of the Station Updating the firmware of the additional CPUs only Overview 20 3 2 R outer station and E thernet station You can update the additional CPUs in a networked Station via C WEB LAN In this way you can update networked Stations without disconnecting the network connection and restoring the factory setting You will find additional information about the individual steps on the specified pages gt Familiarize yourself with the information in P reparation and security gt 71 gt A GAP with DHCP must be configured for the connection with the PC via C WEB LAN 1 Load the configuration from the Station or your archive to the PC Link gt 24 2 Connect the PC to the C WEB LAN via the Ethernet switch MM FN2008 A1 3 Enable the Station Press lt MENU gt and enter a valid PIN 4 Update the fi
16. Link gt 24 Disconnect the PC from the Station Link gt 20 SR Ww Building Technologies Fire Safety A6V 10210416 f en 14 01 2013 Removing or replacing non stationary devices Base without loop contact 18 2 3 18 2 3 1 Replacing a non stationary device of a different type You will find additional information about the individual steps on the specified pages 1 Switch the C NET detector line off Link gt 30 2 Remove the C NET device from its base The Station detects that the device is missing and reports a Fault 3 Delete the C NET device individually on the Person Machine Interface on the control panel Link gt 31 4 Insert the new C NET device in the base 5 Read in the C NET devices Link gt 31 6 Connect the PC to the Station Link gt 20 7 Load the configuration from the Station to the PC Link gt 24 8 Replace the C NET device in the Zone Link gt 63 9 Load the configuration from the PC to the Station Link gt 23 10 Disconnect the PC from the Station Link gt 20 Replacing a device in the Zone 1 Select the Zone in which you have replaced a device in Cerberus Engineering Tool The Find or Find and replace functions can be used to do this 2 Replace the C NET device You will find more information in document A6V10210424 See chapter Applicable documents See also Applicable documents gt 8
17. On CeteCtOn iner a a a aLa 30 6 8 Switching off the detector line ssssseesssessserressssssrrrnntssstrrnennnnsssernnnnnnsssent 30 6 9 Restarting the detector line ssssssssssssressesssesiirrrtesssnnirnrttsssnrnrnnnnssssnnrnnnn 30 6 10 Switching Off ZONME ccceeeeeeee cece eeeeeeee tees ee eeecaaaeeeeeeeeeteecaaaeeeeeeeeeseeenaeeeeeees 30 6 11 SWICHING 0N ZONE siie e aeaa aE a A aeeai aani 30 6 12 Reading iN GOVICES aai aanerer aa aaaea an a a aai 31 6 13 Detaching the device 20 eee e cece ccceeeee eee eee teeecaeee tener etteeaaaeee sees etteecaaaeeeeeeeeetene 31 3 Building Technologies A6V 10210416 f_en_ Fire Safety 14 01 2013 6 14 Delete the device on Person Machine Interface ccccccceesseseeeeeeeeeeeettaees 31 6 15 Remove the element ccccccceeeeeeeeeccneeeeeeeeeeeecaaaeeeeeeeeteeeaaaaaeeeeeeeteeenaaaes 32 6 16 Switching On test MOE cece cette eeeeeecaaee eee eeeeeeecaaeeeeeeeeeetecsaaaeeeeees 32 6 17 Switch On normal operation eecceeeeeeee eee eeeeccaeeeeeeeeeeeeeecaaeeeeeeeeeesecccaeeeeeees 32 6 18 Rectify localization CrrOrs ccccccceeeeeeeecceeeeeeeeeeeeeecaaeeeeeeeeseeecaaaeeeeeeetenenaaaes 33 6 19 Checking Site TUNC Misrin ai 33 6 20 COMpPIGHON WOT Kese e 34 7 A Commissioning stand alone Station without PC aasssssssssnnnnnnnnnnnnnnnna 35 7 4 Configuring the power SUPDI c cceeeeeeeeeeeeeeceeeeeeeeeeeeeeaaeeeeeeeeeeeeetaeeeeeees 36 7 2
18. QUALITY LETTER PITCH 10 CPI LINE SP 6 LPI CHAR W NORMAL CHAR H NORMAL ATTRIB NONE PAGE LG 12 0 IN LFT END 1COLM TOP MRG 1 LINE LANGUAGE LATIN 9 CHR SET SET1 AGM OFF PRF SKP NO SKIP ZEROFNT NO SLSH CR CODE CR ONLY LF CODE LF amp CR RGHTEND WRAP ND 99 Building Technologies A6V10210416_f_en_ 14 01 2013 Commissioning external printer 100 Function Value MENU 2 EMULATE DPL24C FONT COUR 10 QUALITY LETTER PITCH 10 CPI LINE SP 6 LPI CHAR W NORMAL CHAR H NORMAL ATTRIB NONE PAGE LG 11 0 IN LFT END 1COLM TOP MRG 1 LINE LANGUAGE PAGE 437 CHR SET SET2 PRF SKP NO SKIP ZEROFNT NO SLSH DC3 CDE ENABLE CR CODE CR ONLY LF CODE LF amp CR RGHTEND WRAP E ND HARDWRE PPR OUT DETECT PRT DIR BI DIR BUZZER ON WORD LG 8 BIT BUFFER NONE INTRFCE SERIAL FORMAT 8NONE 1 BAUD RT 9600 PROTOCL XON XOF DSR IGNORE DUPLEX FULL CTS IGNORE CD IGNORE ND Building Technologies Fire Safety A6V10210416_f_en_ 14 01 2013 Commissioning external printer Function Value ADJ UST CNT ORG 1 61N CNTFINE 1 180 CUT ORG 1 6 IN CUTFINE 1 180 CNT LFT 0 90 CUT LFT 0 90 CUT ADJ 0 360 CNT AD 0 360 CNTADJ L 0 360 END CONFIG TEAROFF AUTO TEARPOS VISIBLE TEAR EN 4SEC
19. Station 1 Highlight the Station you want to initialize in the Hardware tree 2 Select the Commissioning gt Initialize station menu item The following window is opened Initialize station 3 Click on Start The following window is opened Set access level Set the station to access level 3 4 Press lt MENU gt on the Station and enter a valid PIN Click on OK in the Set access level window The Station is initialized gt The Station is restarted After afew minutes the Buzzer sounds twice 6 Press lt Acknowledge gt on the Person Machine Interface to switch off the Buzzer Do not perform any more actions on the Station until the Buzzer has sounded for the second time See also Loading data to the Station gt 21 22 Building Technologies A6V10210416_f_en_ Fire Safety 14 01 2013 Connectivity and communication with Station Loading configuration from the PC to the Station 5 5 Loading configuration from the PC to the Station You can use the Download site function to load the configuration of one Site from the Cerberus Engineering Tool on the PC into the Station NOTICE Different network configuration in Cerberus Engineering Tool and networked Site When the selection displayed for Download site is manually modified in special cases it may be necessary to reset a Station
20. appears if no customer text is assigned to the Zone either Building Technologies Fire Safety A6V10210416 f en 14 01 2013 A Commissioning stand alone Station without PC Setting detector parameter sets 7 3 Setting detector parameter sets 1 5 Select Topology gt Detection tree gt Area gt Section gt Zone gt Detect in the main menu Press the More Options softkey Select E xecute commands Select the corresponding command SelectPS MANNED Select PS UNMANNED Select PS Select the desired parameter set The following message is displayed Command executed 37 Building Technologies Fire Safety A6V 10210416 f_en_ 14 01 2013 B1 Commissioning stand alone Station with PC without pre configuration 8 B1 Commissioning stand alone Station with PC without pre configuration First auto configure the Station in this commissioning variant Then adapt the auto configuration manually in Cerberus E ngineering T ool iJ The procedure in this chapter is only valid for standalone Stations Prerequisites e The detector lines and C NET devices are installed e The acceptance test has been carried out for the detector lines e The Station is installed but the batteries are not connected yet J The cables for the detector lines and the mains supply have been inserted in the Station but not yet connected Cerbe
21. gt Commissioning preferences 26 Building Technologies Fire Safety A6V 10210416 f en 14 01 2013 General commissioning steps Preparing Station for commissioning 6 General commissioning steps The following chapter contains general commissioning steps that are referred to in several chapters 6 1 Preparing Station for commissioning 1 2 10 Connect the cables for the detector lines and the periphery devices Connect the power supply mains and batteries The Station starts and reads in the internal hardware During start up the AVERIA LED flashes and the display shows the progress During start up the firmware version F FXS7211 is displayed Wait until the display indicates the selection of the BDV Press the Install softkey and confirm with the Yes softkey The Station restarts During this process the AVERIA LED flashes and the display shows the progress Wait until only the green Sistema Servicio LED lights up the display shows the normal condition and the Station can be operated Press lt MENU gt and select the Login logout menu item You are prompted to enter a PIN Enter the PIN and confirm with lt ok gt The User successfully logged in message is displayed The main menu is shown on the display Check the firmware of the Station to ensure that itis up to date To do this select the Topology gt Hardware tree gt St
22. gt 33 7 Remedy any errors you notice and load the corrected configuration from the PC to the Station Link gt 23 8 Disconnect the PC from the Station Link gt 20 See also Applicable documents gt 8 Replacing stationary devices of the same type NOTICE Incorrect assignment between detector detector group and customer text Inaccurate messages in the event of an alarm e You must not change the C NET topology at the same time as adding extra devices e After extending or changing a Site always run a test to check the assignment between detector detector group and customer text 68 You will find additional information about the individual steps on the specified pages 1 Switch the C NET detector line off Link gt 30 Replace the C NET device with a device of the same type Several devices can be replaced Rectify localization errors Link gt 33 Connect the PC to the Station Link gt 20 Load the configuration from the Station to the PC Link gt 24 Test the function of the Site Link gt 33 Remedy any errors you notice and load the corrected configuration from the PC to the Station Link gt 23 8 Disconnect the PC from the Station Link gt 20 You will find information about installing and uninstalling in the documentation for the corresponding C NET device Refer to document A6V 10227639 for information on how t
23. you can create a back up file of the Site configuration The following conditions must be satisfied for a complete back up e Allof the Stations in the Site must be networked and commissioned e The Site IDs for all Stations must match the Site ID for the Site loaded in Cerberus E ngineering T ool e The BDVs for all Stations must be compatible with the BDV for the Site loaded in Cerberus E ngineering T ool The BDVs are compatible when the major version and the minor version are identical The bugfix version is not relevant for the compatibility e The country codes of the BDVs for all Stations must match the BDV for the Site loaded in Cerberus E ngineering T ool You will find Information about BDV names and versions in document A6V10210424 See chapter Applicable documents If the above mentioned conditions are not satisfied a corresponding message is displayed and an incomplete back up file created In this instance incomplete is added to the file name of the back up file Creating a back up gt The Site is opened in Cerberus Engineering T ool gt The PC is connected to a Station 1 Select Commissioning gt Create backup embedded configuration The Create backup embedded configuration and Connect windows are opened Create Connect d Local connection O Connection to GAP O Connection to address 2 Select Connect in the window and click
24. 102 Building Technologies A6V10210416_f_en_ Fire Safety 14 01 2013 Maintenance Testing and measuring instruments 23 3 Testing and measuring instruments The following table shows an overview of the test devices and measuring instruments used Test Required auxiliaries Comment Voltage current and resistance measuring Universal measuring instrument Measuring ranges Voltage AC DC 1 500 V Current DC 100 mA 5A Resistance 10 0 10 MQ Measurement error lt 2 Internal resistance 220 kQ Testing batteries Battery tester Load resistance 5Q Poll diagnosis data Maintenance PC with Cerberus Engineering Tool For requirements see document A6V10210424 See chapter Applicable documents Insert and remove FD720 point detectors Detector exchanger DX791 Adapter for detector exchanger FDUD491 Compatible with all FD720 point detectors Some detectors also require the adapter for detector exchanger FDUD491 Test FD720 point detectors Test gas REF 8 S recommended REF 8 hot air fan Test manual call points line devices and alarm devices Test linear smoke detector FDL241 9 Adjustment kit FDLU291 Adjustment device and black alarm test filter Test flame detector F DF2x1 9 LE3 Test lamp Test C NET detector line Line tester FDUL221 23 4 Preparatory work Inform the system owner Inform the system owner of the scop
25. 14 01 2013 General commissioning steps Rectify localization errors Element Command Area Non MCP zones det test END MCP zones det test END Section Non MCP zones det test END MCP zones det test END Zone Detector test END Commands under Execute commands iJ You can also switch to normal operation at superordinate level for the command in question Test mode can also be exited in the Zone Section or Area for example Switching Zone to normal operation There is a shortened procedure for switching individual Zones to normal operation 1 Select Message summary gt Test message in the main menu 2 Select the displayed Zone in test mode and press the Execute Commands softkey 3 Select the Detector test END command The Zone is switched to normal operation gt The yellow DETECTORES EN PRUEBAS LED goes out 6 18 Rectify localization errors 1 Use Topology gt Hardware tree gt Station gt Line card gt Detector line to select the corresponding detector line in the main menu 2 Press the More Options softkey and select E xecute commands w Select the Accept replaced devices command The fault messages are no longer displayed iJ If devices are missing or the device types do not correspond to the C NET topology error messages will continue to be displayed 6 19 Checking Site function Test the func
26. 18 1 18 1 1 18 1 2 iJ 60 Removing or replacing non stationary devices The product range includes bases with or without a loop contact Base with loop contact If an C NET device is removed the loop contact prevents the C NET detector line from being interrupted and thereby prevents a fault message The work described in this chapter may be performed when the C NET detector line is switched on Temporarily removing an individual non stationary device It may be possible that an C NET device must be temporarily removed from the base Afterwards the same C NET device must be re inserted at exactly the same place in the C NET 1 Remove the C NET device The control panel detects that the C NET device is missing and reports a Fault Perform the necessary activities Re insert the C NET device in the C NET in the same previous position Acknowledge the Fault IPUR If this Fault is no longer displayed the control panel updates the settings of the re inserted C NET device If this Fault is still displayed and or the detector line is not in normal operation the detector line has to be restarted The work described in this chapter may be performed when the C NET detector line is switched on See also Restarting the detector line gt 30 Replacing non stationary devices of the same type You will find additional information about the individual steps on the specified pages
27. CUTLOAD BUTTON DECODE DIRECT AREACNT DISABLE ON LOAD ONLINE LOCK NONE IIS I DISABLE CONT PE EDGE GATHER DISABLE CUT CTL SPEED SKIP PR ENABLE STATUS ENABLE BANDCTL ENABLE TOF CTL DRIVER ND Settings required 101 Building Technologies A6V10210416_f_en_ Fire Safety 14 01 2013 Maintenance General 23 Maintenance 23 1 General General rule It is assumed that the Site was commissioned in accordance with the existing directives i e all functions have been tested and the system data have been saved and archived Protocol The measuring values according to specifications to be recorded belong to the technical documentation in the system file NOTICE Non observance of rules during maintenance work Insufficient maintenance and damage to the Site or parts thereof e Always de energize the Station first before connecting fitting or removing components Prevent electrostatic discharge If undertaking work on components you must use an EMC mat Do not touch the modules unnecessarily with your bare hands Do not unnecessarily switch off the Site or parts thereof for long periods of time 23 2 Spare parts You will find details for ordering spare parts for Stations in document A6V10227652 e You will find details for ordering Detectors and accessories in document A6V 10225323 See chapter Applicable documents See also Applicable documents gt 8
28. Detector line 15 L Line tester Updating the firmware 95 116 Load From PC to station 21 23 From station to PC 24 Load data to PC Site 24 Load data to the station Site 23 Localization error 33 M Main CPU Updating the firmware 79 Maintenance 102 Manual call point Replace 69 MCL USB adapter Updating the firmware 88 Measuring instrument 103 Merge Sites 42 Mimic display driver Updating the firmware 93 N Network cable Moving 110 Networked station 40 Normal operation 32 O ON Detector line 30 P Password 79 81 84 86 PC Connect to station 20 Disconnecting from station 20 PMI Fault indicators 109 Power supply Configuring 36 Testing 105 Pre configuration Definition of terms 18 Primary Setup Tool 47 Building Technologies Fire Safety A6V 10210416 f en 14 01 2013 Index Printer Testing 106 R Radio gateway FDCW221 94 Updating the firmware 94 Radio gateway FDCW241 94 Updating the firmware 94 Read in Definition of terms 18 Device 31 Remove Device 60 65 Device base without loop contact 62 Device stationary 67 Device temporary 64 Replace Device base without loop contact 62 Device different types 61 63 Device same type 60 Device stationary 68 Manual call point 69 Restart station 112 S Scalance X204 2 46 Security module firewall FN2009 A1 49 Serial line tester Updating the firmware 97 Series number 15 Set parame
29. Entering customer texts using the Person Machine Interface ce 36 7 3 Setting detector parameter Sets ccceeccceeecceeeeeeeeeeeeeeecaeeeeeeeeeeteetsaeeeeeees 37 8 B1 Commissioning stand alone Station with PC without pre CONITIQUIF At OND ae etic esa es ance aa aaa aA a ES a a a ETa 38 9 B2 Commissioning stand alone Station with PC with PFO CONFIQUIATION ccccceeecceeeeeeeeeeeeeeeneeeeenneenaeneaaaananaaaanaaaeaaananaaaeaeneanaaaas 39 10 C Commissioning networked Stations ccccccceeesseeeeeeeeseeeeseeeeeeeeeeeeees 40 11 Adding a Station to an existing Site c eeeceeeeseeeseeeeeeeeeeeeeeesseeeeeeeees 41 12 Merging two Sites ccccccecsseeeseeeee eee eeeeeeeeneeeeeeeeeesaaeesaeeeeeeeeeeseeeseeeeeeseeeenenees 42 12 1 Adding Site B to Site Aw ccccecccceeee cere eeeeecaaeeeeeeeeeeeeaaaeeeeeeeeteeensaaaeeeeees 43 12 2 Connecting Sites physically to one ANOthEN cccceeeeeeeeeeeeeeeeeeeeeeeestteeeeeees 45 13 Commissioning Ethernet switch MM FN2008 A1 cceeeeeeeeeeeeeeeeeees 46 13 1 Install Primary Setup TOOI cccccccceceeeeceeeeeeeeeeeeeeecccaeeeeeeeeeeeeccaeeeeeeeeeteensaaaes 47 13 2 7ANSS1 0 1018 eak 0 0 2 s See re 47 13 3 Configure FN2008 A1 using Internet browser ccccceecceteeeeeeeeeeteetteeeeeeees 48 14 Commissioning safety module firewall FN2009 A1 sseeeeeeeeeeeeeeees 49 14 1 Installin
30. Fire Detection System External Printer Application Note A6V 10225323 FD720 Cerberus PRO Synova AlgoRex Detector System Equipment Overview A6V 10227639 FDCW241 radio gateway technical manual A6V10227652 FS720 Cerberus PRO Fire Detection System Components Spare Parts Repair Parts A6V10229261 List of compatibility A6V10260976 FS720 Fire Detection System Site Conversion 008250 FDUL221 Line Tester Operation 008860 FT201x floor repeater terminal floor repeater display installation 009771 Open source software OSS licenses 009854 FDUZ221 MCL USB adapter Installation Building Technologies Fire Safety A6V10210416 f en 14 01 2013 About this document Technical terms iJ 1 2 Technical terms Term Explanation Al Alarm indicator BDV Base data variant C NET Addressed detector line ES Product version MCL Maintenance and commissioning link MCP Abbreviation for Manual call point You will find additional technical terms and their explanation in document A6V 10210355 in the chapter Glossary See chapter Applicable documents See also Applicable documents gt 8 1 3 History of changes The reference document s modification index applies to all languages into which the reference document is translated The first edition of a language version or a country variant may for example have the modification index d instead of a if th
31. PC to the Station Link gt 23 Test the function of the Site Link gt 33 10 Remedy any errors you notice and load the corrected configuration from the PC to the Station Link gt 23 11 Disconnect the PC from the Station Link gt 20 12 Perform the completion tasks Link gt 34 O 0 S o n ee w 40 Building Technologies A6V10210416_f_en_ Fire Safety 14 01 2013 Adding a Station to an existing Site 11 Adding a Station to an existing Site Prerequisites The detector lines and C NET devices are installed The acceptance test has been carried out for the detector lines The Station is installed but the batteries are not connected yet The cables for the detector lines and the mains supply have been inserted in the Station but not yet connected Cerberus E ngineering T ool is installed on the PC The current firmware and BDV are available on the PC You will find additional information about the individual steps on the specified pages Commissioning 1 OOS aw Sw TN Re oO 11 12 In Cerberus E ngineering Tool create the Station to be integrated and configure it if required Prepare the Station for commissioning without BDV installation Link gt 28 Connect the PC to the Station Link gt 20 Initialize the Station Link gt 21 Read in the C NET devices Link gt 31 Load the configuration from
32. The C NET detector line is not connected to the control panel and is disconnected from the power supply when the C NET devices are being installed wired and inserted The C NET detector line is tested with the line tester FDUL221 The control panel is commissioned by the commissioning personnel 3 1 1 Installing devices with serial number iJ Before inserting or connecting an C NET device stick the serial number on the layout plan The adhesive strip with the serial number can be found on the bottom of the device 1 Installand wire the C NET devices and stick the serial number for each device on the layout plan 2 Install the detector dust caps on the optical point detector if necessary 3 Install the designation plate if necessary 3 1 2 Installing devices according to the wiring sequence 1 Install and wire the C NET devices and document the wiring sequence in the layout plan 2 Install the detector dust caps on the optical point detector if necessary 3 Install the designation plate if necessary 15 Building Technologies A6V 10210416 f_en_ Fire Safety 14 01 2013 Mounting Installation Mount and install Station 3 1 3 Checking the detector line NOTICE Simultaneous connection of line tester and C NET detector line to the control panel Damage to line tester or control panel e Do not connect the line tester and the C NET detector line to the control panel at the same time
33. When C NET devices have been swapped over in their bases e g while work is carried out the Line is not fault free The following message is shown on the display of the Person Machine Interface for each C NET device that has been swapped over Zone Serial no ID Nr Device missing If the C NET detector line was restarted the following message is displayed for each swapped C NET device Zone Serial no ID Nr Dev location fault To enable the Station to become fault free again at least the device types in the corresponding bases must be correct Faults of C NET devices of the same type that have been swapped over can then be rectified using the Person Machine Interface without having to find the original base Procedure iJ You will find additional information about the individual steps on the specified pages Rectify localization errors Link gt 33 Connect the PC to the Station Link gt 20 Load the configuration from the Station to the PC Link gt 24 Disconnect the PC from the Station Link gt 20 BN 110 Building Technologies A6V10210416_f_en_ Fire Safety 14 01 2013 Repair Error message Topology is invalid 24 7 Error message Topology is invalid If the topology of a C NET detector line is invalid after the detector line has been read in the error message Topology is invalid is displayed The table below shows invali
34. You will find additional information about the individual steps on the specified pages The detector line has been commissioned Switch the test mode on Link gt 32 Initiate the detector Link gt 59 Switch normal operation on Link gt 32 P wW Nr y Test the logged test activations Link gt 59 17 1 Activate the detector gt DETECTORES EN PRUEBAS is switched on 1 Activate all automatic Detectors and Manual call points using the corresponding tools 2 Write down the sequence of the test activations The alarm indicator for the activated detector flashes at each test activation If an external alarm indicator is connected and correspondingly configured the external alarm indicator also lights up You will find information about triggering detectors in document A6V10212047 See chapter Applicable documents See also Applicable documents gt 8 17 2 Testing logged test activations 1 Test the logged test activations This can be done in two ways Person Machine Interface Select Event memory in the main menu Cerberus E ngineering Tool Select the Commissioning gt Upload site event memory menu items 2 Rectify existing errors if necessary e g if the alarm indicator has not flashed or no test entries exist 59 Building Technologies A6V 10210416 f_en_ Fire Safety 14 01 2013 Removing or replacing non stationary devices Base with loop contact 18
35. are loaded to the Station 20 7 2 PMI amp mainboard FCM2027 gt Familiarize yourself with the information in the chapter P reparation and security 1 Select Update gt FW update main and additional CP Us from the menu bar 2 a Password check window is open enter the password 1234 and click on The Confirmation window opens 3 NOTICE Data loss Save the configuration data before updating the firmware 4 Click on Yes The FW update main and additional CPUs window opens FW update main and additional CPUs 81 Building Technologies A6V 10210416 f_en_ Fire Safety 14 01 2013 Updating the firmware of the Station Updating the firmware of the main CPU and the additional CPUs 5 Select the firmware version you want and click on Start The following window is opened Information e FCM2004 JI Set 538 2 on the FCM2004 to ON and press 532 for about five seconds OR FCM2027 Press 532 in combination with the Acknowledge button on the front of the FCM2027 for about five seconds FCc2004 Select update mode U pressing 58 on the Front of the FCC200 4 Confirm mode holding 58 Notice Do not power off or reset the system while the Firmware update is running Close the update dialog after the update process has been finished Press OK to continue 6 Keep the S32 button on the rear of the operating unit pressed and press lt Acknowledge gt on the Person Mach
36. iJ 16 3 2 Acceptance test gt The C NET detector line is not connected to the control panel 1 Connect the line tester FDUL221 to the newly installed C NET detector line 2 Testthe C NET detector line for short circuits open lines and earth faults 3 Check the number of the devices on the C NET detector line using the display on the line tester 4 Check the branch off position of the stubs and the number of devices at the stubs Check the type of all C NET devices 6 Remedy any errors you notice and carry out the acceptance test again You will find information on the line tester in document 008250 See chapter Applicable documents Error when reading in the devices If there are too many devices on the C NET detector line for them all to be displayed on the line tester a message to this effect is displayed Proceed as follows should this happen e Read in the devices from both sides of the loop To do this change over the detector line cables as follows Connect the feed line of the detector line to connection socket B Connect the return line of the detector line to connection socket A The devices are read in from the other side of the loop This allows the devices which previously couldn t be read in to be displayed Mount and install S tation 1 Mount and install the Station according to the information in document A6V10210390 See chapter Applicable documents 2 Inse
37. more stations Stations are connected FN2008 A1 is configured Building Technologies Fire Safety A6V10210416 f en 14 01 2013 Commissioning safety module firewall FN2009 A1 Configure FN2008 A1 using Internet browser 14 Commissioning safety module firewall FN2009 A1 This description focuses on correctly configuring and integrating the S ecurity module firewall FN2009 A1 in the fire detection installation More information about the product can be found on the data carrier in the scope of supply and at the following address http support automation siemens com Manufacturer designation Scalance 612 iJ A configuration is available via the localization manager We recommend using the configuration and if necessary making system specific adaptations Commissioning 1 Install the Security Configuration Tool software Link gt 50 2 Select the type and enter the MAC address Link gt 50 3 Enter the network settings Link gt 51 Load configuration 4 Create IP service definitions Link gt 54 5 Create firewall rules Link gt 55 Load configuration iJ The Security module firewall FN2009 A1 is a class A equipment and may cause radio interference in residential areas If interference does occur observe the relevant information in document A6V10210390 See chapter Applicable documents iJ The FN2009 A1 has no IP address in the factory setting You must manually assi
38. net Mask from 255 255 255 0 to 255 255 0 0 Enter the following network data Router IP 192 168 201 1 Network ID 192 168 0 0 Confirm input with OK The router network data is entered Load the network settings to FN2009 A1 438N FY V MAC address is entered IP addresses are entered Highlight the FN2009 A1 module in the project Select the Transfer gt To Module menu The network settings are loaded to F N2009 A1 Network settings are entered 53 Building Technologies Fire Safety A6V 10210416 f_en_ 14 01 2013 Commissioning safety module firewall FN2009 A1 Creating IP service definitions 14 4 Creating IP service definitions NOTICE Different BACnet port settings in FN2009 Al and Cerberus Engineering T ool No communication possible e Configure the same BACnet port in FN2009 A1 and Cerberus E ngineering Tool 1 Open the Options gt IP Service Definitions menu The IP Service Definitions window is opened E IP Services ICMP Service Groups Group Management Name Protocol Source Port Target Port Add IP Service Remove IP Service OK Cancel Help Select the IP Services tab Click on Add IP Service gt One row can be edited for one IP service 4 Enter the two IP services required as shown in the figure above Name Tool Protocol udp Source Port Target Port 51000 Name BACnet Protocol u
39. on OK The Site configuration is loaded to the PC and saved as a back up file The advancement status is displayed in the Create backup embedded configuration window 25 Building Technologies Fire Safety A6V 10210416 f en 14 01 2013 Connectivity and communication with Station Creating a back up of the Site configuration Create backup embedded configuration ID Panel text Status 1 Alarming pre configured Uploading configuration data for backup CLEL IEEE ELITE Creating embedded configuration backup Back up file e The back up file is saved in the following directory as standard C Documents and Settings All Users Application Data S iemens F X7230 e The back up file has the following name lt Site name gt _ lt back up counter gt _incomplete fsc Example Test_Site_007_incomplete fsc Site name Name of the Site Back up counter Three digit number that is automatically assigned to each back up incomplete If it was not possible to create a complete back up incomplete is added to the file name e A maximum of ten Site back up files are saved If more than ten back up files are created the oldest file is automatically deleted iJ In the pre settings you can define that a back up file is created automatically each time a configuration is loaded from the PC to the Station using the Download site command To do this select Options gt Preferences
40. on the additional CPUs Link gt 86 Au FWD Update the firmware if required of the additional CPUs again if there is a higher firmware version available Link gt 84 8 Load the configuration from the Station to the PC Link gt 24 9 Disconnect the PC from the Station Link gt 20 10 Restore the network connection Updating several Stations simultaneously You can update the firmware of max eight networked Stations simultaneously The Stations and the CPU cards must be connected to one another via C WEB LAN Example Several Stations are connected to each other via one or several Ethernet switch MM FN2008 A1 You will find additional information about the individual steps on the specified pages gt Familiarize yourself with the information in P reparation and security gt 71 gt A GAP with DHCP must be configured for the connection with the PC via C WEB LAN The Stations are displayed together V gt You can update not more than eight Stations simultaneously 1 Import the new firmware into Cerberus E ngineering Tool Select the File gt Import new FW package menu item and open the file you want 73 Building Technologies Fire Safety A6V 10210416 f_en_ 14 01 2013 Updating the firmware of the Station Updating the firmware of the additional CPUs only Overview Se a 8 9 Load the configuration from the Station or your archiv
41. power supply Check the curent consumption 1 Measure the current consumption during E mergency power operation and for alarms with the highest alarm level local alarm and global alarm 2 Compare the measurement values with the calculation value for emergency current capacity Checking the batteries 1 Measure the battery voltage 23 V min max asymmetry 1 V 2 Measure the charging current 3 Check the battery load capacity The load test should only be performed if the battery charge currentis below 50 mA 4 Disconnect the batteries from the charger Do not subject the connections to strain unnecessarily Connect the battery tester to both batteries load resistance 5 Q Test duration for battery 7 Ah 20 minutes Test duration for battery 12 Ah 30 minutes OOD SE OO Measure the battery voltage when the tester is connected During the test the battery voltage should not drop below 11 V per battery and not below 23 V for both batteries Always replace both batteries Checking for power supply faults 1 Disconnect the mains supply cable The following message is displayed Mains failure 2 Disconnect the battery supply cable The following message is displayed Supply failure Checking the mains supply cable 1 Check whether the site mains supply cable is correctly fuse protected and labeled fire detection system 2 Check whether installed overvoltage dischargers are in order 105 Bui
42. same time as adding extra devices e After extending or changing a Site always run a test to check the assignment between detector detector group and customer text 19 1 1 19 1 2 66 You will find additional information about the individual steps on the specified pages Switch the C NET detector line off Link gt 30 Fit and wire the new devices Link gt 66 Read in the C NET devices Link gt 31 Connect the PC to the Station Link gt 20 Load the configuration from the Station to the PC Link gt 24 Configure the new devices Link gt 66 Load the configuration from the PC to the Station Link gt 23 Test the function of the Site Link gt 33 Remedy any errors you notice and load the corrected configuration from the PC to the Station Link gt 23 10 Disconnect the PC from the Station Link gt 20 O o SO n Pen S Mount and wire new devices During an extension of the line all possible wiring work on the bases must be carried out from devices that have already been localized When replacing these devices these must be re inserted in exactly the same place observe the serial number 1 Remove these devices from their bases 2 Fitand wire the new devices like bases 3 Insert the new devices into the new bases and write down the serial numbers on the layout plan Configure a new device 1 Extend the configuration in Cerberus Engineering T oo
43. successfully logged in message is displayed The main menu is displayed Select the Topology gt Hardware tree gt Station menu items The elements of the Station are listed Select module 101 or module 102 CPU FCM20xx Press the More Options softkey and select E xecute commands Select the Reset module command The Station restarts gt After a few minutes the Buzzer sounds twice Press lt Acknowledge gt on the Person Machine Interface to switch off the Buzzer Do not perform any more actions on the Station until the Buzzer has sounded for the second time With the S32 button FCM2027 112 The switches S 38 1 and S 38 2 are set to the OFF position on the PMI amp mainboard FCM2004 On the PCB of the operating unit press and hold down the S 32 button for lt 25S gt The Station restarts gt After afew minutes the Buzzer sounds twice Press lt Acknowledge gt on the Person Machine Interface to switch off the Buzzer Do not perform any more actions on the Station until the Buzzer has sounded for the second time Building Technologies Fire Safety A6V 10210416 f en 14 01 2013 Repair Restoring factory setting on the Station 24 9 Restoring factory setting on the Station There are the following ways in which to restore the factory se
44. the connection type Select Local connection to establish a connection to the connected standalone or SAFEDLINK Station Select Connection to GAP to establish a connection via GAP toa networked Station Enter the address of the Station you want to update in the Target station address field If you want to update the GAP Station itself enter 0 4 Click on OK The following window is opened The checkboxes for the CPUs that can be updated are checked FW update additional CPUs Update Type part no Name Address Installed version Update to version Status FCI2002 A1 A5Q00005545 07 Onboard I Os FCI2002 11 1 2 11 1 2 11 FDnet FCI2002 45Q00005545 07 C NET line card onboard FCL2001 1 2 3 3 9 3 5 0 Installed firmware version not supported FN2001 A1 45000012851 11 SAFEDLINK interface FN2001 1 4 1 4 2 1 4 2 1 CPLD on FCM2004 A5Q00005163 05 Degrade interface 1 4 3 4 0 2 4 0 2 FCM2004 A1 A5Q00005163 05 PMI board interface 1 4 5 2 2 0 2 2 2 Installed firmware version not supported gt 84 Building Technologies A6V10210416_f_en_ Fire Safety 14 01 2013 Updating the firmware of the Station Update the firmware of the additional CPUs 5 10 11 Select the CPUs you want to update and click on Start The following window is opened Set access level ep Set the station to access level 3 J Cancel Press lt ME
45. to the Stations and click on Start The Setaccess level window may be opened with the Set the station to access level 3 prompt Press lt MENU gt on the Station enter the PIN and press lt ok gt 23 Building Technologies Fire Safety A6V 10210416 f en 14 01 2013 Connectivity and communication with Station Loading configuration from the Station to the PC 24 5 6 Set access level ep Set the station to access level 3 Cancel 4 Click on OK in the Set access level window The Action confirmation window opens 5 Click on Yes The configuration is loaded to the Station The advancement status is displayed in the Download site window The Station restarts gt After a few minutes the Buzzer sounds twice 6 Press lt Acknowledge gt on the Person Machine Interface to switch off the Buzzer Do not perform any more actions on the Station until the Buzzer has sounded for the second time 1 Examples of special cases e A Station will be added to a networked Site and a new network configuration will be loaded upon initialization of this Station different from the global network configuration of the connected Site e During the Download site procedure a Station is temporarily not accessible Both examples can result in the Station no longer starting after the Download site p
46. 0210416_f_en_ 14 01 2013 Updating the firmware of the peripheral devices Updating the firmware of the floor repeater display FT2011 21 3 Updating the firmware of the floor repeater display FT2011 A WARNING Incorrect assignment between detector detector group and customer text Misleading messages in the event of an alarm e Never change the wiring during the firmware update The firmware must be updated individually for each floor repeater display Preparation gt The floor repeater display is fed by a 24 V external power supply or by the C NET detector line gt The driver for the MCL USB adapter FDUZ221 is installed on the PC 1 Select File gt Import new FW package 2 Open an F FXS7211 XX_x_x zip file that matches the Site in the selection window 3 Open the device and connect the PC via the MCL USB adapter to the device FT2011 FDUZ221 Connect the PC to the floor repeater display FDUZ221 MCL USB adapter interface USB MC LINK X100 Connection for the MCL USB adapter FT2011 Floor repeater display 91 Building Technologies A6V 10210416 _f_en_ Fire Safety 14 01 2013 Updating the firmware of the peripheral devices Updating the firmware of the floor repeater display FT2011 Updating the firmware 1 Select Update gt FW update standard peripheral device S D The FW update standard peripheral device window opens Cerberus Engineering Tool establ
47. 3 Updating the firmware of the peripheral devices Updating the firmware of the radio gateway FDC W241 The FW update standard peripheral device window is closed after updating The device is restarted A success message is indicated 4 Remove the MCL USB adapter The firmware is updated Manually setting device to update mode Proceed as follows if you are prompted to manually set the device to update mode in step 1 1 Setthe DIP switch S 200 1 to ON The device is set to update mode 2 Click on OK in the FW update standard peripheral device window Set the DIP switch S 200 1 to OFF 4 Go to Update firmware step 2 x2 21 bli S200 H FT2001 Al Printed circuit board view 21 5 Updating the firmware of the radio gateway FDCW241 You must update the firmware of the radio gateway FDC W241 with a SWING Tool and the MCL USB adapter FDUZ227 You will find information on this in document A6V 10227639 See chapter Applicable documents See also Applicable documents gt 8 94 Building Technologies A6V10210416_f_en_ Fire Safety 14 01 2013 Updating the firmware of the peripheral devices Updating firmware on the line tester FDUL221 21 6 Updating firmware on the line tester FDUL221 This chapter relates to the line tester FDUL221 device version with MC link connection order no A5Q00022100 Preparation gt The driver for the M
48. 8 2 OFF ON S32 S38 mi a The Station restarts 3 Set the S38 1 switch to OFF after the restart After a few minutes the Buzzer sounds twice 4 Press lt Acknowledge gt on the Person Machine Interface to switch off the Buzzer Do not perform any more actions on the Station until the Buzzer has sounded for the second time 5 Enter the date and time To do this select the Settings administration gt System commands gt Set system time menu items PMI amp mainboard FCM2027 1 Keep the S32 button on the rear of the operating unit pressed and simultaneously press lt Reset gt on the Person Machine Interface at the same time until the Station restarts gt 2 s FCM2027 BO Corb poll 32 E 4 The Station restarts gt After a few minutes the Buzzer sounds twice 2 Press lt Acknowledge gt on the Person Machine Interface to switch off the Buzzer Do not perform any mo
49. 8 2013 Copyright Siemens Switzerland Ltd Technical specifications and availability subject to change without notice Document ID A6V10210416 f_en_ Edition 14 01 2013 Manual FS 720
50. A1 and I O card horn monitored FC12009 A1 With the I O card remote transmission FC12007 A1 and I O card horn monitored FC1I2009 A1 the monitored outputs are monitored for short circuit and open line The resistance values of the lines may be read in and stored at the push of a button If a deviation from the quiescent value is detected the control panel evaluates a short circuit or an open line The following outputs must be calibrated upon commissioning e FC1I2007 Al OUT1 to OUT3 e FC1I2009 A1 OUT1 to OUT8 You will find more information about the F C12007 A1 and FC12009 A1 I O cards and planning monitored outputs in documents A6V10210362 and A6V10210368 See chapter Applicable documents I O card FCI2007 A1 and or FCI2009 A1 501 Button Procedure 1 Check the connected lines for short circuit and open line 2 Connect the lines During the commissioning of the control panel fault messages are indicated provided that there are any deviations from the basic settings 3 Press the 501 button The resistance values are read in iJ You can also read in the resistance values via the control panel s Person Machine Interface 58 Building Technologies A6V10210416_f_en_ Fire Safety 14 01 2013 Testing detectors Activate the detector 17 Testing detectors The commissioning personnel perform the function test for the automatic fire detectors and the Manual call points iJ
51. Activate the Manual call point using the corresponding tools You will find information about this in the Manual call point documentation Building Technologies Fire Safety A6V 10210416 f en 14 01 2013 Updating the firmware of the Station Preparation and security 20 20 1 Updating the firmware of the Station Preparation and security The following points must be observed before updating the firmware A e The firmware must be updated individually for each Station Exception Stations networked via C WEB LAN See the chapter Updating several Stations simultaneously e Data backup When the firmware of the main CPU is updated the configuration data event memories and the alarm counter value are deleted Load the configuration data and event memories before updating in Cerberus Engineering Tool You will find more information about the event memory and the alarm counter in document A6V 10210424 See chapter Applicable documents e Converting the configuration data Updating the firmware requires the configuration data to be converted if the new firmware and existing configuration are not compatible with one another e BDV compatibility The BDVs are compatible when the major version and the minor version are identical The Bug fix version is not relevant for the compatibility You will find Information about BDV names and versions in document A6V10210424 See chapter
52. CL USB adapter FDUZ221 is installed on the PC gt The line tester is fed either internally with batteries or via a mains adapter 1 Select File gt Import new FW package 2 In the selection window open the most recent file with the corresponding language F FXS2007 XX_xX_X_ zip 3 Connect the device to the PC via the MCL USB adapter FDUZ221 MC Link Connect the PC to the line tester FDUZ221 MCL USB adapter interface USB MC LINK FDUL221 Line tester DC Supply with network adapter DC 24V 625 mA B Battery compartment 2 x 9 V If the device has no MC link connection itis an older device version with an RS232 connection You will find more information on this in the next chapter Updating the firmware 1 Select Update gt FW update FDUL221 line test device The FW update FDUL221 line test device window opens Cerberus Engineering Tool establishes the connection to the device and sets the device to update mode The latest firmware package and the latest firmware version are suggested 2 Click on Start Ifthe hardware version is not compatible click on Cancel and check the hardware version Replace the hardware and start again at point 1 The status bar indicates the update progress The FW update FDUL221 line test device window is closed after updating The device is restarted A success message is indicated Remove the MCL USB adapter The firmware is upd
53. INStrUCtiONS cceccceeeeeeee eee eeeccceeee eee ee eeeeaaaeeeeeeeeeseeaaaeeeeeeeeeseeentaaeeeeees 11 2 2 Safety regulations for the method of operation ccccceceeeeeeeeeeeeeeeettteeeeees 12 2 3 Standards and directives complied With ceeecceeeeeeeeeeeeeeeeeeeeeeeeeesnteeeeeees 14 2 4 Release Notesin a a E NE EN 14 3 Mounting Installation cccccccessseesseeeeeeeeeeeneeeceeeeeeeeeeeaeeeseeeeeseeeesaeeeseeeeeeenees 15 3 1 Installing and checking the detector liN ccececieeeceeeeeeeeeeeeeeetteeeeeeeeeeteee 15 3 1 1 Installing devices with serial number cccccccceeeeeteeeeeeeeeeeeetaees 15 3 1 2 Installing devices according to the wiring sequence 15 3 1 3 Checking the detector lin ccceeeeeeeeeeeeeeceeeeeeeeeeeeeeecaaeeeeeeeeetees 16 3 2 Mount and install Station 0 0 0 2 cece ccc ceeeeeeee eee eeeceeeeeeeeeeeeeeeaaaeeeeeeeeeeescaaeeeeeees 16 4 COMMISSIONING OVEFVICW cccsceeeeeeeeeeeeeeeeeeeneneeeeeeeeeaneeceneeeseeeeeaeeeseeeeeeeeees 17 4 1 Commissioning VAIANKS ccceee ee ceeceeee eee e ee eeeecaaeeeeeeeeeteeaaaeeeeeeeeeteeedaeeeeeees 17 4 2 Definition Of tOrMS ccccceeeeceeecenee este eee e ee cceee teers eeteeaaeeeeeeeeeteeccaaeeeeeeeeenee 18 4 3 Brief instructions on operating the Station c cccccceccececseeeeeeeeeeeeeessneeeeeees 19 5 Connectivity and communication with Station sssssssssssssnnsnsnnnnnnnnnnnnnnns 20 5 1 Co
54. NU gt on the Station and enter a valid PIN Click on OK in the Set access level window The CPUs are updated The Information window is opened after updating Note the update information and information about other procedures in the Information window Click on OK gt The Station is restarted After a few minutes the Buzzer sounds twice Press lt Acknowledge gt on the Person Machine Interface to switch off the Buzzer Do not perform any more actions on the Station until the Buzzer has sounded for the second time Click on Close in the FW update additional CP Us window See also Preparation and security gt 71 85 Building Technologies Fire Safety A6V 10210416 f en 14 01 2013 Updating the firmware of the Station Testing the firmware version of the additional CPUs 20 9 Testing the firmware version of the additional CPUs If you have updated the firmware of the main CPU and the additional CPUs ina single step FW update main and additional CPUs you must then test the firmware version of the additional CPUs to ensure that the CPUs were updated correctly Update the firmware if required of the additional CPUs again if there is a higher firmware version available To test the firmware version on the additional CPUs proceed as follows 1 Select Update gt FW update additional CPUs from the menu bar 2 Ifthe Password check window i
55. S2007 XX_X_X_ Zip 3 Connect the device to the PC via the RS232 interface in the battery compartment BS Connectthe PC to the serial line tester FDUL221 Line tester RS 232 Serial port for the direct connection to the P C S Serial interface RS 232 DC Supply with network adapter DC 24 V 625 mA B Battery compartment 97 Building Technologies A6V10210416_f_en_ Fire Safety 14 01 2013 Updating the firmware of the peripheral devices Updating firmware on the line tester with serial interface FDUL221 Updating the firmware 1 Select Update gt FW update serial FDUL221 line test device The FW update serial FDUL221 line test device window opens Cerberus Engineering Tool establishes the connection to the device and sets the device to update mode gt The latest firmware package and the latest firmware version are suggested 2 Click on Start The status bar indicates the update progress The FW update serial FDUL221 line test device window is closed after updating The device is restarted A success message is indicated 3 Disconnect the connection with the PC The firmware is updated Manually setting device to update mode Proceed as follows if you are prompted to manually set the device to update mode in step 1 1 Keep the 4 and v buttons on the device pressed and click on OK in the FW update serial FDUL221 line test device window Another FW upda
56. SIEMENS TAO OURO a A a i FS720 Fire detection system Commissioning Maintenance Troubleshooting IP4 A6V10210416_f en_ Building Technologies 14 01 2013 Control Products and Systems Impressum 2 Impressum Technical specifications and availability subject to change without notice 2013 Copyright by Siemens Switzerland Ltd Transmittal reproduction dissemination and or editing of this document as well as utilization of its contents and communication thereof to others without express authorization are prohibited Offenders will be held liable for payment of damages All rights created by patent grant or registration of a utility model or design patent are reserved Issued by Siemens Switzerland Ltd Infrastructure amp Cities Sector Building Technologies Division International Headquarters Gubelstrasse 22 CH 6301 Zug Tel 41 41 724 2424 www siemens com buildingtechnologies Edition 14 01 2013 Document ID A6V10210416 f en_ Building Technologies Fire Safety A6V 10210416 f en 14 01 2013 Table of contents 1 About this COCUMENN cteeeeeeeeeeeeeeceeeee nenen eneninda 7 1 1 Applicable GOCUMENTS ccceeeeeeeeecteeeeeeeeeteeeaaaeeeeeeeeeeeaceaaaaeeeeeeetenenaaaes 8 1 2 TPechniGalitOrmS suiran manana oe met deinen te 9 1 3 History of Change S cit s2isiriiiterati one nennnonomenadicianiene 9 2 SM OEY al E A A E EEEE 11 2 1 Safety i
57. T detector line Auto configuration of Station Auto configuration results in the following One Section is created for each C NET detector line One Zone is created for each Sensor Channel Automatic detectors and M anual call points One Technical zone is created for each Input Channel For all Output channels and for each C NET detector line one Control is created One Control is created for each alarm sounder External alarm indicators are not auto configured Each Section and each Zone contains customer text such as detector line no zone no and serial number of the device Detailed information about the result of auto configuration can be found in the List of compatibility The logical elements incl customer texts are created in Cerberus E ngineering Tool prior to commissioning Inthe Detection task card up to and including Zone level Inthe Control task card up to and including C ontrol level Fire control E vac control Counter control In addition the logical elements can subsequently be assigned as far as possible for alarming and control Logical channels can be preconfigured This makes sense if customer texts are to be configured down to this level The C NET devices can be read in using one command via the Person Machine Interface In this process the C NET devices are listed without sections and zones being created i e no c
58. X Manned operation and Unmanned operation operating modes Check automatic switchover from Manned operation to Unmanned X operation on the basis of the event memory entries Check activation of the remote transmission equipment with ALARM X Intervals for the function test 23 11 Completion work 1 Activate a test alarm through the system operator with remote transmission Issue subsequent instructions if necessary Ensure that the system file is available and up to date Powe copy with the Site and a copy in the office Replace all used material Cancel all blockings and OFF statuses Oo oy Un Have the revision confirmed by the system owner Check the master data sheet phone no contact person etc Update the system data when the central configuration is changed Archive a 107 Building Technologies A6V 10210416 f_en_ Fire Safety 14 01 2013 Repair Disconnecting Station from the power supply 24 24 1 Repair Disconnecting Station from the power supply Work on an open Station e g changing components cabling etc must only be performed when the Station is current free For this purpose the batteries must be disconnected and the mains connection must be interrupted The Station cannot be shut down NOTICE Connecting or removing components during operation Damage to components e Do not connect or remove components during operation 24 2
59. a Fault 2 Delete the C NET device individually on the Person Machine Interface on the control panel Link gt 31 Insert the new C NET device in the base Read in the C NET devices Link gt 31 Connect the PC to the Station Link gt 20 Load the configuration from the Station to the PC Link gt 24 Replace the C NET device in the Zone Link gt 61 Load the configuration from the PC to the Station Link gt 23 Disconnect the PC from the Station Link gt 20 SO 00 S 0y Or B The work described in this chapter may be performed when the C NET detector line is switched on Replacing a device in the Zone 1 Select the Zone in which you have replaced a device in Cerberus Engineering Tool The Find or Find and replace functions can be used to do this 2 Replace the C NET device You will find more information in document A6V 10210424 See chapter Applicable documents 61 Building Technologies Fire Safety A6V10210416_f_en_ 14 01 2013 Removing or replacing non stationary devices Base without loop contact 18 2 18 2 1 18 2 2 62 Base without loop contact If a C NET device is removed the detector line is interrupted from this point If the device is on a stub or sub stub communication between the control panel and downstream devices is interrupted These devices are shown as missing on the control panel The work described in this chapt
60. ated GLL w 95 Building Technologies Fire Safety A6V 10210416 f en_ 14 01 2013 Updating the firmware of the peripheral devices Updating firmware on the line tester FDUL221 Manually setting device to update mode Proceed as follows if you are prompted to manually set the device to update mode in step 1 1 Simultaneously press the 4 v and v buttons on the device while in the F W update FDUL221 line test device window pressing OK Another FW update FDUL221 line test device window is opened and you are prompted to release the buttons 2 Only release the v button The device is set to update mode Release the 4 and v buttons 4 Click on the OK button in the FW update FDUL221 line test device window and go to Update firmware step 2 96 Building Technologies A6V10210416_f_en_ Fire Safety 14 01 2013 Updating the firmware of the peripheral devices Updating firmware on the line tester with serial interface FDUL221 21 7 Updating firmware on the line tester with serial interface FDUL221 This chapter relates to the line tester FDUL221 device version with RS 232 connection order no up to A5Q00004397 02 Preparation gt The line tester is supplied via a mains adapter gt AnRS232 portis available on the PC 1 Select File gt Import new FW package 2 In the selection window open the most recent file with the corresponding language F FX
61. ating diagnosis report To update the firmware versions for the creation of the diagnosis report the configuration data must be loaded in Cerberus E ngineering T ool gt 1 The configuration data for the Station is loaded to Cerberus Engineering T ool Select Commissioning gt Diagnostics report from the menu bar The Reports window opens Select Diagnostics report in the Report type field Select the page format page orientation file name and memory location of the report in the Output settings section Click on Create report The report is created and displayed You will find more information about creating reports and the diagnosis report in document A6V10210424 See chapter Applicable documents See also Applicable documents gt 8 87 Building Technologies Fire Safety A6V 10210416 f_en_ 14 01 2013 Updating the firmware of the peripheral devices Updating the firmware of the MCL USB adapter FDUZ221 88 21 21 1 Updating the firmware of the peripheral devices You need the following tools to update the firmware of the periphery devices e Cerberus Engineering T ool e MCL USB adapter FDUZ221 If the hardware product version is not compatible with the current firmware a corresponding error message is displayed during the update process In this instance the hardware must be replaced in accordance with the information in the Release Notes
62. ation gt More Options gt Show details menu items The Station version and configuration data are displayed Update the firmware if necessary Enter the date and time To do this select the Settings administration gt System commands gt Set system time menu items iJ Additional messages may be displayed depending on the configuration of the Station 27 Building Technologies Fire Safety A6V10210416_f_en_ 14 01 2013 General commissioning steps Preparing Station for commissioning without BDV installation 6 2 6 3 6 4 Preparing Station for commissioning without BDV installation 1 Connect the cables for the detector lines and the periphery devices 2 Connect the power supply mains and batteries The Station starts and reads in the internal hardware During start up the AVERIA LED flashes and the display shows the progress During start up the firmware version F FXS7211 is displayed 3 Wait until the display indicates the selection of the BDV The Station is prepared for commissioning It is not necessary to install the BDV for the further procedure This saves having to restart the Station Auto configuring Station 1 Select Topology gt Hardware tree gt Station in the main menu 2 Press the More Options softkey and select E xecute commands 3 Select the Auto configure station command The Stati
63. atus of the component You will find the meaning of the indications in document A6V10210368 See chapter Applicable documents See also Applicable documents gt 8 109 Building Technologies A6V 10210416 f_en_ Fire Safety 14 01 2013 Repair Communication problems in networked systems 24 5 Communication problems in networked systems Date and time are not permanently saved in the Station If this data is not defined correctly itis not possible to communicate with the corresponding Station in the network or via Cerberus E ngineering T ool Date and time The date and time must be checked regularly for the following reasons e The deviation of the internal clock is up to four minutes per month e When data is downloaded and when a Station is restarted the internal clock does not continue working e Ifa Station is de energized the date and time of the internal clock is lost Moving the network cable from one Station to the next Wait at least two minutes before inserting the cable into the next S tation If Stations are fitted close to one another you may be able to move the network cable from one Station to the next without first having to execute the Commissioning gt Disconnect command in Cerberus E ngineering T ool If this is done a connection cannot be immediately re established on the next S tation 24 6 Non stationary devices of the same type have been Swapped over
64. ccceeceteeeeeeeeeeeeeeaees 75 20 4 Update only the BDV 0 ooo eee cece cere ee eee eee eter eee tteaaaaeee sees etteecaaaaeeeeeeeeneeee 76 20 4 1 Standalone station and SAFEDLINK station cc seeceeeeeseeeeetees 76 20 4 2 Router station and Ethernet station c ccccceecceeceeeeeeeeeeeeeeeaees 76 20 5 Converting the configuration cccceeeeeeeeeeeeeeeeeeeeeeeeeeeeeeaaeeeeeeeeeeescnaaeeeeees 77 20 6 Setting Windows firewall 0 cccccccccceeeeee eee eeeeccaeeeeeeeeeteecaaeeeeeeeeeteeesaaeeeeees 77 20 7 Updating the firmware of the main CPU and the additional CPUs 0 79 20 7 1 PMI amp mainboard FOM2004 cece cece eeeeeeceeeeeeeeeeeeeaaaes 79 20 7 2 PMI amp mainboard FOM2027 cccccceccccceeteeeeeeeeeeeeeceneeeeeeeeeeeeenaaaes 81 20 8 Update the firmware of the additional CPUS cccccceeeeeeeeeeeeeeeeeeeeeeeees 84 20 9 Testing the firmware version of the additional CPUS sssssssssssseeeeeeeee 86 20 10 Creating diagnosis report ccc cece eee eeecceneee eee ee eeeeecaaeeeeeeeetteeecaaaeeeeeeeeteeee 87 21 Updating the firmware of the peripheral devices ccccssssesseeeeeeeeeees 88 21 1 Updating the firmware of the MCL USB adapter FDUZ221 ceceeeeetee 88 21 2 Updating the firmware of the floor repeater terminal FT2010 ceeeeeee 89 21 3 Updating the firmware of the floor repeater display FT2011 ceeee
65. cuments See also B Applicable documents gt 8 19 Building Technologies Fire Safety A6V 10210416 f_en_ 14 01 2013 Connectivity and communication with Station Connecting the PC to the station 5 5 1 5 2 Connectivity and communication with Station A PC does not have to be directly connected to a Station to be able to communicate with a Station in the Site The PC can be connected to any place in the Ethernet Detailed information about the connection variants can be found in the Establishing connection from PC to FS720 network chapter in document A6V10210424 See chapter Applicable documents See also Applicable documents gt 8 Connecting the PC to the station For most commissioning maintenance and repair work a PC with installed Cerberus E ngineering T ool is required The figure below shows the connection between the PC and Station Rear panel of operating unit and PC LAN Ethernet connection 1 Cable type CAT 5 or CAT 7 crossover max 100 m Disconnecting PC from the Station As the IP address is bound to the MAC address while there is a connection between the PC and the Station and as it remains in the cache even in the case of a short break in the connection of lt 2 min you must observe the following instructions NOTICE Incorrect disconnection of Station Establishing a connection to other Station is not possible e D
66. d topologies Stub on stub or loop interrupted Stub on stub on loop Several stubs starting from same location on loop Loop on loop Invalid topologies Troubleshooting 1 Check the detector line with the line tester FDUL221 You will find information on this in document 008250 See chapter Applicable documents 2 Create a valid topology Rectify the fault by changing over the wiring or plan the detector line again If there are several stub outputs between two C NET devices change over the wiring or add a line separator FDCL221 between each stub 3 Read in the C NET detector line again See also Reading in devices gt 31 111 Building Technologies A6V 10210416 f_en_ Fire Safety 14 01 2013 Repair Restart Station 24 8 iJ FCM2004 Restart Station The configuration of the Station remains the same There are the following ways in which to restart the S tation Via the menu on the display e With the S32 button Via the menu on the display 1 Press lt MENU gt The PIN input dialog is indicated Enter a valid PIN and confirm with lt ok gt The User
67. ded to FN2009 A1 56 Building Technologies A6V10210416_f_en_ Fire Safety 14 01 2013 Commissioning the fire brigade periphery module FC12001 D1 15 Commissioning the fire brigade periphery module FC1I2001 D1 The fire department periphery module FC12001 D1 monitors the monitored inputs and outputs for short circuit and open line The resistance values of the lines may be read in and stored at the push of a button If a deviation from the quiescent value is detected the control panel evaluates a short circuit or an open line The following table shows the monitored inputs and outputs Terminal Pin Function X4 4 5and1 2 Remote transmission or transmission device RT Alarm and release element FSE X5 7 8 Key depot tamper monitoring X6 5 6 Local alarm X4 X5 X6 View of the fire department periphery module X4 X6 Connection terminals S101 Button Procedure 1 Check the connected lines for short circuit and open line 2 Connect the lines During the commissioning of the control panel fault messages are indicated provided that there are any deviations from the basic settings 3 Press the push button 101 The resistance values are read in 57 Building Technologies A6V 10210416 f_en_ Fire Safety 14 01 2013 Commissioning I O card remote transmission FC12007 A1 and I O card horn monitored F C12009 A1 16 Commissioning I O card remote transmission FC1I2007
68. devices are installed The acceptance test has been carried out for the detector lines The Station is installed but the batteries are not connected yet The cables for the detector lines and the mains supply have been inserted in the Station but not yet connected Cerberus Engineering T ool is installed on the PC The current firmware and BDV are available on the PC iJ You will find additional information about the individual steps on the specified pages Commissioning 1 WO Ot OY oe ee mY Ke oO 11 12 In Cerberus E ngineering Tool create a Site and configure it manually to the Zone level Prepare the Station for commissioning without BDV installation Link gt 28 Connect the PC to the Station Link gt 20 Load the configuration from the PC to the Station Link gt 23 Read in the C NET devices Link gt 31 Load the configuration from the Station to the PC Link gt 24 Adapt the configuration in Cerberus Engineering Tool Link gt 29 Load the configuration from the PC to the Station Link gt 23 Test the function of the Site Link gt 33 Remedy any errors you notice and load the corrected configuration from the PC to the Station Link gt 23 Disconnect the PC from the Station Link gt 20 Perform the completion tasks Link gt 34 39 Building Technologies Fire Safety A6V 10210416 f_en_ 14 01 2013
69. dp Source Port Target Port 47808 Required IP services are created Select the ICMP tab Click on Add ICMP Service One row can be edited for one ICMP service 7 Enter the two optional ICMP services required as shown in the figure below Name ICMPO Type Echo Request Code No code Name ICMP 1 Type Echo Reply Code No code Optional IP services are created 54 Building Technologies A6V10210416 f_en_ Fire Safety 14 01 2013 Commissioning safety module firewall FN2009 A1 Creating firewall rules 14 5 _ x IP Service Definitions IP Services ICMP Service Groups Group Management Name Type Code Echo Request No Code Echo Reply No Code Add ICMP Service Remove ICMP Service 8 Confirm input with OK IP Service Definitions are created Creating firewall rules gt IP service definitions are created gt The network addresses are known 1 Right click on the module for which you want to create firewall rules 9 Security Configuration Tool Router_Cfg_Smpl_1 Project Edit Insert Transfer view Options Help cola ee ALB IOI poc Global Fw Rulesets Fw IP Rulesets Fw MAC Rulesets 5 All Modules GERE ga S612V2 S6 Insert Module Copy Paste Delete Rename Properties 2 Select Properties The Module Properties window for the selected module is displayed 55 Build
70. e and expected duration of work and also that Site operation will be restricted For large scale systems fill out the system shutdown notification sheet and have this signed by the system owner Block system components Block the following system components e Remote alarm log out on the receiving centre e Fire controls and alarm equipment e Extinguishing stations Specify the procedure Stipulate the times for the following test sequences with the system owner e Test alarms including remote transmission Performance check for Fire controls Additional instructions if required Clarifications if required 103 Building Technologies A6V10210416_f_en_ Fire Safety 14 01 2013 Maintenance Test system data 104 23 5 23 6 Test system data System test manual Ensure that the system test manual is available and up to date Remote transmission Check that the phone numbers and the names of the remote transmission receivers are up to date Data backup for Site 1 Check that the system data are saved Two copies must be archived with the Site one copy with the technical department 2 Update the system data when the configuration is changed 3 Note the date of execution in the system test manual Firmware 1 Read out the firmware version from the Station To do this select Topology gt Hardware tree gt Station gt More Options gt Show details in the main men
71. e are address conflicts at Stations levels and suggests a possible new address 43 Building Technologies A6V 10210416 f_en_ Fire Safety 14 01 2013 Merging two Sites Connecting Sites physically to one another FXS7212 merge sites wizard Station re addressing Some stations may have to be re addressed during the merge Please define the correct address if required Station Site Original address New address FC722 Station 1 Test Site Fsc 3 FC722 Station 2 Test Site fsc 2 FC724 Station 3 Test Site Fsc 3 FC724 Station 4 Test Site fsc 4 FC722 Station 11 Test Site fsc 11 FC724 Station 12 Test Site Fsc 12 FC724 Station 13 Test Site Fsc 13 FC724 Station 14 Test Site fsc 14 FC724 Station 15 Test Site fsc 15 FC724 Station 16 Test Site Fsc 16 FC722 Test_Site_B Fsc 17 FC 22 Test_Site_B fsc 18 FC724 Test_Site_B fsc 19 FC724 Test_Site_B fsc 20 FC724 Test_Site_B fsc 5 FC724 Test_Site_B fsc 6 Reconfigure network 6 Check the suggested addresses for the Stations in Site B and adapt them if necessary The New address column can be edited 7 Check the Reconfigure network checkbox if you want to reset the existing network configurations for the original Sites All network configuration values are then reset to the standard values 8 Click on Finish The Sites are merged The following window is opened In the Required action column you are shown which Station
72. e reference document already has this modification index The table below shows this document s history of changes Modification index Edition date Brief description f 01 2013 Chapter S etting Windows firewall for Windows 7 updated e 05 2012 Edition for IP 4 New Revised Updating the firmware of the main CPU and _ Creating diagnosis report additional CPUs in a single step Restart the station Addition to chapter Setting Windows firewall Checking S ite function for Windows 7 Updating several Stations simultaneously Update the firmware of the additional CPUs via GAP Creating a back up of the Site configuration Replacing the C NET device 20 s wait time instead of 40 s Updating the firmware of the peripheral devices Resetting the line card no longer necessary Updating the FDCW241 FDCW221 removed Commissioning I O card remote transmission FC12007 A1 and I O card horn monitored FC12009 A1 Restoring factory settings Checking the detector line 9 Building Technologies Fire Safety A6V 10210416 f_en_ 14 01 2013 About this document History of changes Modification index Edition date Brief description d 07 2010 Edition for MP 3 0 XS History of changes redefined and standardized Ethernet switch MM FN2008 A1 and safety module firewall FN2009 A1 added Merging two sites chapter added Chapter on Site conversion rem
73. e to the PC Link gt 24 Convert the configuration if necessary and rectify conversion faults Link gt 77 Connect the PC to the Ethernet switch MM FN2008 A1 Update the firmware on the main CPU and the additional CPUs Link gt 79 Set each Station individually in update mode You can set the Stations in update mode without any waiting time one directly after the other Wait until the update of each Station is completed Initialize each Station individually Link gt 21 To do so you must connect the PC to each Station locally Link gt 20 Test the firmware version on the additional CPUs on each Station Link gt 86 Update the firmware if required of the additional CPUs again if there is a higher firmware version available Link gt 84 Load the configuration from the Station to the PC Link gt 24 Disconnect the PC from the Station Link gt 20 10 Restore the network connection if required 20 3 Updating the firmware of the additional CPUs only Overview If the Station firmware is up to date and components have been changed then it is only necessary to update the additional CPUs The procedure for updating the firmware depends on the Station function The procedures are described in the following chapters 20 3 1 Standalone station and SAFEDLINK station iJ You will find additional information about the individual steps on the specified pages gt 1
74. e update progress The FW update FDUZ221 MCL USB adapter window is closed after updating The device is restarted A success message is indicated When the device is ready for operation the green LED lights up 3 Disconnect the MCL USB adapter from the PC The firmware is updated Updating the firmware of the floor repeater terminal FT2010 WARNING Incorrect assignment between detector detector group and customer text Misleading messages in the event of an alarm e Never change the wiring during the firmware update The firmware must be updated individually for each floor repeater terminal Preparation gt The floor repeater terminal is fed by a 24 V external power supply or by the C NET detector line gt The driver for the MCL USB adapter FDUZ221 is installed on the PC 1 Select File gt Import new FW package Open an F FXS7211 XX_xX_X_ zip file that matches the Site in the selection window 3 Open the device and connect the PC via the MCL USB adapter to the device FT2010 MC Link FDUZ221 Connect the PC to the floor repeater terminal FDUZ221 MCL USB adapter interface USB MC LINK X100 Connection for the MCL USB adapter FT2010 Floor repeater terminal 89 Building Technologies Fire Safety A6V10210416 f en 14 01 2013 Updating the firmware of the peripheral devices Updating the firmware of the floor repeater terminal FT2010 Updating the fir
75. eeee 91 21 4 Updating firmware of mimic display driver FT2001 A1 eeeeeeeeeeeee rete 93 21 5 Updating the firmware of the radio gateway FDCW241 00 0 eect ee eee 94 5 Building Technologies A6V10210416 f_en_ Fire Safety 14 01 2013 21 6 Updating firmware on the line tester FDUL221 oo cece eeeneeeeeeneeeeeteaes 95 21 7 Updating firmware on the line tester with serial interface FDUL221 97 22 Commissioning external printer ccceseeeeeeeeeeeeeeeeeeeeeeeeeeeaeeeseneeeeeeenenees 99 23 Maintenance aca ce a deena ante eden en den dentine ended econ 102 23 1 GEMS A basa hacntecatesaseanhscstedanesnssswhaasteduieanneawiuastsetesettes 102 23 2 Spare PAS tee aea aaraa aa anna aana ai Aa aaia A awed A Aaa a aA A Aaaa E a 102 23 3 Testing and measuring iNStrUMENtS eseeseeeeeeerrrererrrrserrrrrerrinrserrrreerreesnt 103 23 4 Preparatory WOTK wiissectctcsssassiasisdeneacnapatasaieeeterdiapasanaveeciandiasasaeiveyiaeiianabaaaiaeed 103 23 5 Testsystem Oat a saarien aa SS 104 23 6 esting the Station sisii ee at oa E N 104 23 7 Check the power supply 0 ceeeeeecceeee cece ee eeeeeaaeeeeeeeetteeeaaaaeeeeeeeeteescaaeeeeeees 105 23 8 Testing the printer iscivivieiieidtaa eee tate ea eh tee akan 106 23 9 Checking Site TUNC tioN nadania aiaiai nAn En EAn ESAS 106 23 10 Intervals for testing the system function ssssssssssseiessssssssrrrrrsssssrrrrrnnsssens 106 23 11 Completion WOrK sssssssssseressssssss
76. eeeeeeeeecceaeeeeeeeeeteccaaeeeeeeeeeseensaaeeeeees 67 19 4 Connecting a SUD StUD tO a IOOP cceeeeeeeeeeeeeceetee eee eeeeteecaaaeeeeeeeeeteeceaaeeeeees 68 19 5 Replacing stationary devices of the same tyPe cceceeeeeeeeeeeeeeeeeeeeeeeeeees 68 19 6 Replacing Manual call point of the Same type ceeeeeeeeeeeeeeetteeeeeeeeetteee 69 19 6 1 Switching on the replace mode ccceeeeeeeeeeeeeeeeeeectteeeeeeetenees 69 19 6 2 Switching off replace MOG cccccceeeeeeeeeeeeteeeeeeeeeteeetaeeeeeeeeeeteee 70 19 6 3 Testing Manual Call pOint c cc eeeeceeeeeeeeeeeenee sete eeteeetaeeeeeeeeetteee 70 20 Updating the firmware of the Station cccccssseesseeeeeeeeeseeeeseeeeeeeeenenees 71 20 1 Preparation and security ecccceeeeeeeeeeeeetceee eee e eee eeecaaeeeeeeeeeeeecdaaeeeeeeeetneee 71 20 2 Updating the firmware of the main CPU and the additional CPUs Overview 72 20 2 1 Standalone station and SAFEDLINK station seeceeeeesteeeeees 72 20 2 2 Router station and Ethernet station ccccccceceeeeeeeeeeeeeeeeeeeeeeeeaees 73 20 2 3 Updating several Stations simultaneously ccsssseeeeeseesteeeeeeeeee 73 20 3 Updating the firmware of the additional CPUs only Overview c0c00 74 20 3 1 Standalone station and SAFEDLINK station c c eeeeeeeeseeeeeees 74 20 3 2 Router station and Ethernet station cc cccccc
77. eeeeeeeeteeenaaaes 61 18 1 3 Replacing non stationary devices of different tyP S ssseeeeeeee 61 18 1 3 1 Replacing a device in the Zone 0 2 eee eeeeceeeeeeeeeeeeeeeeetteeeeeeeeeeeeseaaaes 61 4 Building Technologies A6V10210416 f_en_ Fire Safety 14 01 2013 18 2 Base without loop COMtACt eee e ee eecceeee eee e eee eeeeccaaeeeeeeeeeeeeaaaaeeeeeeeseeecccaaeeeeeees 62 18 2 1 Temporarily removing an individual non stationary device 62 18 2 2 Replacing non stationary devices of the same typ ceeeee 62 18 2 3 Replacing a non stationary device of a different type 63 18 2 3 1 Replacing a device in the ZOne 0 ecececeeeeeeeeeeeeeeetteeeeeeeeeeteee 63 18 3 Temporarily removing multiple non stationary devices cseeesseetessseeeeeeeeeee 64 18 4 Permanently removing non stationary devices cccceeeeeeeeeeeeeeceteeeeeeeeetees 65 19 Change and extend the detector line ccssseeeceeeeeeeeeeseeeeeeeeeeseneeeseeeeeeeees 66 19 1 Extending the detector line to include additional devices cccceeeeeeeeeeees 66 19 1 1 Mount and wire new devViCes c ccccceeeceeeeeceeeeeeeeeeeeeeeciteeeeeeeeeetees 66 19 1 2 Configure a new deVICE 00 eee cece cette eee eee eeettee eee e eee teeeaaaeeeeeeeetteee 66 19 2 Permanently removing Stationary devices cceceeceecceneeeeeeeeeeeeetteeeeeeeeeetees 67 19 3 Convert two Stubs into a lOOD ccceeeeee
78. ements using the Find function You will find more information in document A6V 10210424 See chapter Applicable documents See also Applicable documents gt 8 Switching on test mode 1 Select Topology gt Detection tree in the main menu 2 Select the element you want to switch to test mode Area Section or Zone 3 Press the More Options softkey and select Execute commands 4 Select a command from the following table The yellow DETECTORES EN PRUEBAS LED lights up The element is in test mode Element Command Area Non MCP zones det test MCP zones det test Section Non MCP zones det test MCP zones det test Zone Detector test Switch on normal operation There is a shortened procedure for switching individual Zones to normal operation The procedure is described in the following section Switching Zone to normal operation Switching Area Section or Zone to normal operation 1 Select Topology gt Detection tree in the main menu 2 Select the element you want to switch to normal operation Area Section or Zone Press the More Options softkey and select E xecute commands Select a command from the following table The element is switched to normal operation The yellow DETECTORES EN PRUEBAS LED goes out G G amp F a Building Technologies Fire Safety A6V 10210416 f en
79. eparation and security gt 71 1 2 Select Update gt FW update main and additional CP Us from the menu bar If the Password check window is open enter the password 1234 and click on OK The Confirmation window opens NOTICE Data loss Save the configuration data before updating the firmware Click on Yes The FW update main and additional CPUs window opens 79 Building Technologies Fire Safety A6V10210416_f_en_ 14 01 2013 Updating the firmware of the Station Updating the firmware of the main CPU and the additional CPUs 5 Select the firmware version you want and click on Start The following window is opened Information e FCM2004 I Set 538 2 on the FCM2004 to ON and press 532 for about five seconds OR FCM2027 Press 532 in combination with the Acknowledge button on the front of the FCM2027 for about five seconds FCc2004 Select update mode U pressing 58 on the Front of the FCC200 4 Confirm mode holding 58 Notice Do not power off or reset the system while the Firmware update is running Close the update dialog after the update process has been finished Press OK to continue 6 Set the S38 2 switch to ON on the rear of the operating unit 7 Press the S32 button for approx 5 s until the Station restarts FCM2004
80. er may only be performed when the C NET detector line is switched off Temporarily removing an individual non stationary device Instances may arise when a C NET device has to be temporarily removed from the base Afterwards the same device must be re inserted at exactly the same place in the C NET Mark the allocation of the devices to the respective base to avoid additional work steps You will find additional information about the individual steps on the specified pages 1 Switch the C NET detector line off Link gt 30 2 Remove the C NET device from its base 3 Perform the tasks 4 Re insert the C NET device in the corresponding position 5 Switch the C NET detector line on Link gt 30 If detectors have been swapped over or are missing the following messages are shown on the display of the Person Machine Interface Zone Serial no ID Nr Dev location fault See also Non stationary devices of the same type have been swapped over gt 110 Replacing non stationary devices of the same type You will find additional information about the individual steps on the specified pages 1 Switch the C NET detector line off Link gt 30 Replace the C NET device with a device of the same type Several devices can be replaced r Rectify localization errors Link gt 33 Connect the PC to the Station Link gt 20 Load the configuration from the Station to the PC
81. f en 14 01 2013 Removing or replacing non stationary devices Permanently removing non stationary devices 18 4 Permanently removing non stationary devices The procedure in this chapter applies both for the base with loop contact and the base without loop contact iJ You will find additional information about the individual steps on the specified pages Switch the C NET detector line off Link gt 30 Remove the C NET devices and their bases Link gt 31 Switch the C NET detector line on Link gt 30 Delete the C NET devices individually via the Person Machine Interface on the control panel Link gt 31 Connect the PC to the Station Link gt 20 Load the configuration from the Station to the PC Link gt 24 Remove the logical elements in Cerberus E ngineering T ool Link gt 32 Load the configuration from the PC to the Station Link gt 23 Disconnect the PC from the Station Link gt 20 e Ww P Ee O 0 Se oo u 65 Building Technologies A6V10210416_f_en_ Fire Safety 14 01 2013 Change and extend the detector line Extending the detector line to include additional devices 19 19 1 Change and extend the detector line Extending the detector line to include additional devices NOTICE Incorrect assignment between detector detector group and customer text Inaccurate messages in the event of an alarm e You must not change the C NET topology at the
82. following message is shown following successful reading in Command executed Detaching the device If you want to remove an C NET device for good uninstall the device and if required the base and connect the wires of the detector line You will find more information about installing and uninstalling in the documentation for the corresponding C NET device Delete the device on Person Machine Interface 1 Mark the corresponding device fault message 2 Press the More Options softkey 3 Select the Show topology menu item The logical channel is displayed For some devices Device is displayed directly 4 Press the More Options softkey 5 Select the J ump to link menu item The physical channel is displayed 6 Press the Upper level softkey gt Device is displayed 7 Press the More Options softkey 8 Select the Execute commands menu item 9 Select the Remove delete device command The control panel deletes the physical representation of the removed device The logical channel element remains in the Zone 31 Building Technologies Fire Safety A6V 10210416 f_en_ 14 01 2013 General commissioning steps Remove the elements 32 6 15 6 16 6 17 Remove the elements If you have uninstalled an C NET device for good the corresponding elements e g the Zone must be removed from the logical structure trees in Cerberus Engineering Tool You can search for el
83. for the dropdown list field is displayed g Security Configuration Tool Configuration2 C Program Files Siemens Sg Project Edit Insert Transfer View Options Help Darl an elx al io o l 2 All Modules E Modulet O VPN Groups Br Module1 S602 4192 2 Select S612V2 Type is selected Building Technologies Fire Safety A6V 10210416 f en 14 01 2013 Commissioning safety module firewall FN2009 A1 Entering network settings 14 3 Entering MAC address gt The MAC address is known 1 Double click on the field below the MAC Address designation gt The MAC address can be edited 2 Enter the MAC address for the FN2009 A1 MAC address is entered Entering network settings gt The network topology is known gt Advanced Mode is selected e Enter the network settings in the following order External IP address IP Address ext Routing mode Routing Mode Router network data Router Load the network settings to FN2009 A1 Entering external IP address IP Address ext 1 Double click on the field below the IP Address ext designation The external IP address for the FN2009 A1 can be edited 2 Enter the following IP address 10 169 29 80 Entering routing mode Routing Mode The following settings apply for the planned network access to GAP with activated DHCP server 192 168 201 X must be changed accordingly for network access to
84. g Security Configuration Tool cccecccecceneeeeeeeeeeeeecieeeeeeeeeeeeetaaaes 50 14 2 Selecting type and entering MAC address ccccceecceececneeeeeeeeeeeeeeteeeeeees 50 14 3 Entering network SettingS cccccceceeecceeeeeeeeeeeeeeecaeeeeeeeeeeeeccaaeeeeeeeeteeneaaaes 51 14 4 Creating IP service definitions ccccccceecececceeeeeeeeeeeeeeecaeeeeeeeeeeseectneeeeeees 54 14 5 Creating firewall rules cccccceeeececcceeeeeeeeeeeeeeeaaaeeeeeeeeeeeeaaaaeeeeeeeeseeeccaaeeeeeees 55 15 Commissioning the fire brigade periphery module FCI2001 D1 57 16 Commissioning I O card remote transmission FCI2007 A1 and I O card horn monitored FCIZ009 A1 eeceeeeeeeeeeeeeeeeeeeeeeeeeeeeeseeeeeeeeeeeeaeeeenaeeeeeaaes 58 17 Testing ie 0 0 se 59 17 1 Activate the Aetector cccccccceeeeeeeeeeeneeeeeeeeteeccaaeeeeeeeeeseecaaeeeeeeeeeseessieeeeeees 59 17 2 Testing logged test ACtivatiOnS cccccceceeeeeeeecceeeeeeeeeeteeccaeeeeeeeeeeeeetnaeeeeeees 59 18 Removing or replacing non stationary devices cccccssseesseeeeteeeeeeees 60 18 1 Base with loop CONtACt ceeeeeeeeeee eee e eee eeecceee eter ee eteecaaeeeeeeeeetteccaaeeeeeeeeenee 60 18 1 1 Temporarily removing an individual non stationary device 60 18 1 2 Replacing non stationary devices of the Same type cesses 60 18 1 2 1 Replacing a device 20 cece cece eeeeecteeeeeeeeeteeecaaa
85. gn the IP address NOTICE FN2009 A1 is not in the factory setting and already has an IP address Itis not possible to upload a new configuration e Press the Reset button on the live FN2009 A1 49 Building Technologies A6V10210416_f_en_ Fire Safety 14 01 2013 Commissioning safety module firewall FN2009 A1 Installing Security Configuration Tool iJ 50 14 1 14 2 Installing Security Configuration Tool The Security Configuration Tool software is included in the scope of supply for the FN2009 A1 e Install the Security Configuration Tool software Vv The software is installed in the standard path SIMATIC gt SCALANCE Security gt Security Configuration Tool FN2009 Al can be configured The FN2009 A1 is displayed as 612V2 in the Security Configuration Tool Selecting type and entering MAC address The corresponding MAC address can be found on the front of the FN2009 A1 The FN2009 A1 is type 612V2 Preparation gt The PC is connected to FN2009 Al gt Security Configuration Tool is started 1 Create a new project using the Project gt New menu and enter the administrative project data User name and Password 2 Save the new project 3 Select View gt Advanced Mode More entry masks for required settings can be viewed Selecting type 1 Highlight the field below the Type designation The button
86. ine Interface at the same time for approx 5 s until the Station restarts FCM2027 o o 4 ga Fy eosaaneo H 3 oak cle Coral n ios N A peeping sound confirms the function is being executed The firmware is updated and the Station restarts several times This procedure takes up to ten minutes 7 Click on OK in the Information window The FW update main and additional CP Us window is displayed FW update main and additional CPUs ed 82 Building Technologies A6V10210416_f_en_ Fire Safety 14 01 2013 Updating the firmware of the Station Updating the firmware of the main CPU and the additional CPUs 8 Click on Close in the FW update main and additional CP Us window once the Station has restarted The following window is opened gt amp Information FCM2004 J Set 538 2 on the FCM2004 to OFF OR FCM2027 Reboots automatically after a successful update Initialize the station and check the Fw of additional CPUs 9 Click on OK After the restart the Station display shows the available BDVs It is not necessary to install a BDV at this point iJ Initializing the Station instead of installing the BDV saves time During initialization the BDV and the configuration data are loaded to the Station
87. ing Technologies Fire Safety A6V10210416 f en 14 01 2013 Commissioning safety module firewall FN2009 A1 Creating firewall rules 3 Select the Firewall Settings tab The following window is displayed without entries xi a VPN Ea Routing Modus E DHCP Server E Network H Firewall Settings E SSL Certificate X Time Synchronization 8 Logging Be Nodes IP Rules E MAC Rules inactive Action Direction Source IP__ Destination iP _ Service Bandwidth Mbps External gt Internal 10 169 29 82 192 168 0 0 16 EngTool Engineering tool access External gt Internal lempO Ping Internal gt External lernp1 Ping External gt Internal lemp1 Ping Internal gt External lernpO Ping External gt Internal BACnet BACnet Internal gt External BACnet BACnet External gt Internal all DEFAULT Internal gt External all DEFAULT 4244444444 reais ieee Add Rule Remove Rule s s IP Service Definitions OK Cancel Help Click on Add Rule for each firewall rule you would like to create Select the corresponding settings and IP services from the dropdown list fields 4 5 6 Enter the required IP addresses 7 Confirm input with OK The firewall rules are created Loading the firewall rules to FN2009 A1 gt The firewall rules are created 1 Highlight the FN2009 A1 module in the project 2 Select the Transfer gt To Module menu item The firewall rules are loa
88. ing firmware of mimic display driver FT2001 Al WARNING Incorrect assignment between detector detector group and customer text Misleading messages in the event of an alarm e Never change the wiring during the firmware update The firmware must be updated individually for each mimic display driver Preparation gt The mimic display driver is fed by a 24 V external power supply or by the C NET detector line gt The driver for the MCL USB adapter FDUZ221 is installed on the PC 1 Select File gt Import new FW package 2 Open an F FXS7211 XX_x_x_ zip file that matches the Site in the selection window 3 Connect the PC to the device via the MCL USB adapter FT2001 A1 MC Link FDUZ221 Connection of the PC to the mimic display driver FDUZ221 MCL USB adapter interface USB MC LINK X2 Connection for the MCL USB adapter FT2010 Mimic display driver Updating the firmware 1 Select Update gt FW update standard peripheral device The FW update standard peripheral device window opens Cerberus Engineering Tool establishes the connection to the device and sets the device to update mode gt The latest firmware package and the latest firmware version are suggested 2 Select the firmware package that matches the Site 3 Click on Start The status bar indicates the update progress 93 Building Technologies Fire Safety A6V 10210416 f en_ 14 01 201
89. ink in document A6V10210424 See chapter Applicable documents The FN2008 A1 has no IP address in the factory setting You must manually assign the IP address See also Applicable documents gt 8 Building Technologies Fire Safety A6V 10210416 f en 14 01 2013 Commissioning Ethernet switch MM FN2008 A1 Install Primary Setup Tool 13 1 Install Primary Setup Tool iJ The Primary Setup Tool software is included in the scope of supply for the FN2008 A1 e Start Primary Setup Tool installation Primary Setup Tool is installed The DLC and PROFINET RT protocols are installed Primary Setup Tool recognizes one or more connected FN2008 A1 without IP address via the DLC protocol iJ The FN2008 A1 is displayed as X204 2 in the Primary Setup Tool 13 2 Assign IP address iJ The FN2008 A1 is displayed as X204 2 in the Primary Setup Tool gt Primary Setup Tool is installed on the PC gt Several FN2008 A1 are physically linked in the system 1 Connect the PC to any available FN2008 A1 port P1 P 4 using a network cable 2 Startthe Primary Setup Tool via Start gt P rograms gt Simatic Primary Setup Tool lists one or more FN2008 A1 X204 2 3 Select each FN2008 A1 one after the other and issue a unique IP address 192 168 1 xxx to each FN2008 A1 4 Click on the connected FN2008 A1 in the tree view and select the Load menu item The assigned IP add
90. ion installation with the firmware version MP 1XS e Update the firmware if necessary The table below provides an overview of the procedure for commissioning the Stations The letters A B1 B2 and C refer to the detailed descriptions in the following chapters Standalone control panel Networked Stations Without No pre A Not possible ae oa i e Auto configuration r F pete Adaptations on the Person Machine Interface With Cerberus Engineering Tool Without pre Bl configuration Auto configuration Adaptations in Cerberus E ngineering Tool Initialize the Stations for networking Read in C NET devices line by line Assign the logical elements in ee ooo With pre B2 Cerberus Engineering Tool configuration Read in devices line by line Assign the logical elements in Cerberus Engineering Tool Commissioning variants 17 Building Technologies A6V10210416_f_en_ Fire Safety 14 01 2013 Commissioning overview Definition of terms 4 2 Definition of terms Auto configuration iJ P re configuration Read in by line Adaptations Non stationary C NET devices Stationary C NET devices 18 Auto configuration is performed using a command on the Person Machine Interface In this process the C NET devices are read in and a configuration created There are two types of auto configuration Auto configuration of an individual C NE
91. irrrstsssstiirrrstssstrirnnntssstnnnnnnnnasstnnnnnnnnsnsnnnnnn 107 24 Repaik r ateist ieiet ri coip lao latela aaia tac lanata taalani o iiSi 108 24 1 Disconnecting Station from the power supply eeeseeeesseseseseeressssserrrrrrssssss 108 24 2 S Pals PANSis drat tata tote ea a A eee 108 24 3 Fault messages on the Person Machine Interface 109 24 4 Fault indicators On COMPONENES ceeeeeeeee eee e eee eeeeeeeeeeeeeeeeeeeetaaeeeeeeeeetees 109 24 5 Communication problems in networked SYStOMS ccceeeeeeeeeeeeeeettneeeeees 110 24 6 Non stationary devices of the same type have been swapped over 5 110 24 7 Error message Topology iS invalid ccceeeeeeeeeceeeeeeeeeeeeeeecttaeeeeeeeeeeeees 111 24 8 Restart Station i dan taka t ed te eta aa aiaia 112 24 9 Restoring factory setting on the Station ceeeeceeeeeeeeeeeeeeteeeeeeeeeeetees 113 INGOX T ii SRR RE Rr TE 115 6 Building Technologies A6V10210416 f_en_ Fire Safety 14 01 2013 About this document Applicable documents About this document Goal and purpose This document provides information and work steps for installing commissioning maintaining and repairing the fire detection system FS 720 More information can be found in the corresponding documents under Applicable documents To understand this document you must have complete knowledge of document A6V10210355 See chapter Applicable documents
92. isconnect the PC from the Station as described in the following instructions 20 The connection between the PC and the Station must be disconnected as follows 1 Select Commissioning gt Disconnect in Cerberus E ngineering T ool 2 Disconnect the cable connection between PC and Station 3 Wait22 min before you establish a connection to another Station Building Technologies Fire Safety A6V 10210416 f en_ 14 01 2013 Connectivity and communication with Station Loading data to the Station 5 3 Loading data to the Station Data is loaded from Cerberus E ngineering T ool to the Station when the following commands are performed Initialize station e Download site If you use a number of network cards on the PC observe the information in the chapter IP settings for several network cards in document A6V10210424 See chapter Applicable documents The table below shows which data is overwritten in the station S tation Command Overwrites the Sets the address Overwrites the BDV of the Station configuration Initialize station 2 Yes Yes Yes Download site Yes No Yes 2 1Command is only performed for the Station that is connected to the PC via LAN 2 The configuration of all Stations in the Site can be overwritten as an option See also Loading configuration from the PC to the Station
93. ishes the connection to the device and sets the device to update mode The latest firmware package and the latest firmware version are suggested 2 Select the firmware package that matches the Site 3 Click on Start S S S S If the hardware version is not compatible click on Cancel and check the hardware version Replace the hardware and start again at point 1 The status bar indicates the update progress The FW update standard peripheral device window is closed after updating The device is restarted A success message is indicated 4 Remove the MCL USB adapter and lock the device The firmware is updated Manually setting device to update mode Proceed as follows if you are prompted to manually set the device to update mode in step 1 1 Keep the More alarms 1 and Silence buzzer 2 buttons pressed at the same time and disconnect the C NET plug X1 from the printed circuit board 2 Wait at least ten seconds and re insert the C NET plug X1 S The device is setto update mode 3 Click on the OK button in the FW update standard peripheral device window and go to Update firmware step 2 FT2011 Front view FT2011 printed circuit board 92 Building Technologies Fire Safety A6V10210416_f_en_ 14 01 2013 Updating the firmware of the peripheral devices Updating firmware of mimic display driver FT2001 A1 21 4 Updat
94. l e g in the Detection tree 2 Allocate the read in devices to the elements of the detection tree or the control tree in Cerberus Engineering T ool 3 If required configure additional Controls also for several Stations using the layout plan or finalize available Controls Building Technologies Fire Safety A6V 10210416 f en 14 01 2013 Change and extend the detector line Permanently removing stationary devices 19 2 Permanently removing stationary devices iJ You will find additional information about the individual steps on the specified pages 1 Switch the C NET detector line off Link gt 30 2 Remove the C NET devices Link gt 31 3 Switch the C NET detector line on Link gt 30 The control panel reports a Fault per missing device 4 Delete the C NET devices on the Person Machine Interface Link gt 31 5 Connectthe PC to the Station Link gt 20 6 Load the configuration from the Station to the PC Link gt 24 7 Remove the logical elements in Cerberus E ngineering Tool Link gt 32 8 Load the configuration from the PC to the Station Link gt 23 9 Disconnect the PC from the Station Link gt 20 19 3 Convert two stubs into a loop iJ You will find additional information about the individual steps on the specified pages gt The two stubs are assigned to the same line pair e g Line 11 and Line 12 1 Switch both the C NET detecto
95. l of the product apply atthe place of operation then these must also be taken into account together with the safety regulations in the product documentation Electrical installations A WARNING Electrical voltage Electric shock e Work on electrical installations may only be carried out by qualified electricians or by instructed persons working under the guidance and supervision of a qualified electrician in accordance with the electrotechnical regulations 12 e Wherever possible disconnect products from the power supply when carrying out commissioning maintenance or repair work on them e Lock volt free areas to prevent them being switched back on again by mistake Label the connection terminals with external external voltage using a DANGER External voltage sign e Route mains connections to products separately and fuse them with their own clearly marked fuse e Fitan easily accessible disconnecting device in accordance with IEC 60950 1 outside the installation e Produce earthing as stated in local safety regulations Building Technologies Fire Safety A6V 10210416 f en 14 01 2013 Safety Safety regulations for the method of operation Assembly installation commissioning and maintenance e If you require tools such as a ladder these must be safe and must be intended for the work in hand When starting the fire control panel ensure that unstable conditions cannot arise
96. lding Technologies A6V 10210416 f_en_ Fire Safety 14 01 2013 Maintenance Testing the printer 23 8 23 9 23 10 Testing the printer 1 Check the roll of paper in the printer and ensure that there are spare rolls available 2 Initiate the printer test and check the print out for legibility and correct printing 3 Check whether the events are correctly printed out You will find more information about the printer in document A6V10211076 See chapter Applicable documents See also Applicable documents gt 8 Checking Site function Test the functions of the Site in the various test modes You will find information about testing a Site in the chapter Testing in document A6V10211076 See chapter Applicable documents See also Applicable documents gt 8 Intervals for testing the system function Self test for the Detectors The Self test is an automatic performance check for FD720 Detectors The function of the Detectors must be checked regularly on site despite this Detector inspection e Annual visual check of all Detectors Replace Detectors that are badly soiled or mechanically damaged Function test The following table shows the intervals recommended for the function check National specifications always take priority Function Activity Interval years ih Z Software Check date and time X Detector lines Activate an Automatic detecto
97. lect E xecute commands Select the Off command The yellow MENSAJES DE DESCONEXIONES LED lights up The Zone is switched off Switching on Zone 1 4 GYD Select Topology gt Detection tree gt Area gt Section gt Zone in the main menu Press the More Options softkey and select E xecute commands Select the On command The yellow MENSAJES DE DESCONEXIONES LED goes out The Zone is switched on Building Technologies Fire Safety A6V 10210416 f en 14 01 2013 General commissioning steps Reading in devices 6 12 Reading in devices NOTICE Incorrect order for reading in a loop Error when reading in a loop The C NET detector lines are detected as stubs during the first system start up e g Line 11 Line 12 2 digit line number even if they are connected as a loop e Always select the first Line to read in a loop in this case Line 11 Line 12 is then read in automatically After reading in a loop is indicated with a 1 digit line number in this case as Line 1 e Proceed in the same way from Line 21 22 loop 2 to Line 41 42 loop 4 6 13 6 14 1 In the main menu select Topology gt Hardware tree gt Station gt Line card gt Detector line 2 Press the More Options softkey and select Execute commands 3 Select the Read in installed devices command gt The C NET devices are read in The
98. lete the process A New Rule has now been set and appears in the Inbound Rules list It is necessary to make additional settings for the new rule 1 Right click the new rule and select Properties 2 Inthe lt rule name gt Properties window select the Protocol and Ports tab 3 Set the following values Protocol type UDP Local port Specific Ports and enter the value range 50067 50070 in the box Remote port All P orts 4 Confirm with OK The new firewall rule is now configured NOTICE Security vulnerability in operating system due to open ports Unauthorized access to your PC e Deactivate the firewall rule configured above after the firmware update 78 Building Technologies Fire Safety A6V10210416 f en 14 01 2013 Updating the firmware of the Station Updating the firmware of the main CPU and the additional CPUs 20 7 Updating the firmware of the main CPU and the additional CPUs The procedure for updating the main CPU and additional CPUs depends on whether the PMI amp mainboard FCM2004 or FCM2027 is used in the Station The procedures are described in the following chapters PMI amp mainboard FCM2004 PMI amp mainboard FCM2004 gt 79 PMI amp mainboard FCM2027 gt 81 PMI amp mainboard FCM2027 20 7 1 PMI amp mainboard FCM2004 gt Familiarize yourself with the information in P r
99. lling and uninstalling in the documentation for the corresponding Manual call point IO 00 Sh 0y gr Bo Od N 19 6 1 Switching on the replace mode 1 Select Functions gt All functions gt Detector in the main menu 2 Inthe Zone enter the Zone address and press lt ok gt 3 Enter the detector address in Detect and press lt ok gt 4 Select the Device replace mode ON menu item D The following message is shown following successful switching on Command executed gt The yellow MENSAJES DE DESCONEXIONES LED lights up The C NET detector line is de energized 69 Building Technologies A6V 10210416 f_en_ Fire Safety 14 01 2013 Change and extend the detector line Replacing Manual call point of the same type 19 6 2 19 6 3 70 Switching off replace mode 1 2 3 4 gt D D Select Functions gt All functions gt Detector in the main menu Enter the zone address in Zone and press lt ok gt Enter the detector address in Detect and press lt ok gt Select the Device replace mode OFF menu item The following message is shown following successful switching off Command executed The yellow MENSAJES DE DESCONEXIONES LED goes out The yellow DETECTORES EN PRUEBAS LED lights up The Manual call point is in test mode Testing Manual call point 1 2 Check whether the Manual call point is in test mode using the LED
100. mation about converting Sites See chapter Applicable documents Converting the configuration gt The Site you want to convertis saved and loaded in Cerberus E ngineering Tool 1 Select the Edit gt Convert site menu item The following window is opened Convert site Choose BDY for conversion F FX52004 x5_en 2 32 11 10 O6E eBDY Expert mode BDV Convert Cancel 2 Select the BDV you want and click on Convert The Action confirmation window opens 3 Click on Yes gt The Site is converted 20 6 Setting Windows firewall The Windows firewall may prevent the PC connecting to the Station In this case the firewall must be switched off in Windows XP or firewall rules set in Windows 7 when working with the fire detection installation To do this proceed as follows iJ You must have administrator rights to make the following settings Windows XP gt You have administrator rights on your PC 1 Open the Windows start menu 2 Select Settings gt Control panel gt Administrative Tools gt Services 3 Right click on Windows F irewall Internet Connection Sharing ICS in the new window e Select All Tasks gt E xit in the context menu 5 Once the work is complete reactivate the firewall To do this proceed as described above but select All Tasks gt Start in the context menu NOTICE Security vulnerability i
101. mware 1 Select Update gt FW update standard peripheral device S S The FW update standard peripheral device window opens Cerberus E ngineering T ool establishes the connection to the device and sets the device to update mode The latest firmware package and the latest firmware version are suggested Select the firmware package that matches the Site Click on Start S S S If the hardware version is not compatible click on Cancel and check the hardware version Replace the hardware and start again at point 1 The status bar indicates the update progress The FW update standard peripheral device window is closed after updating The device is restarted A success message is indicated 4 Remove the MCL USB adapter and lock the device The firmware is updated Manually setting device to update mode Proceed as follows if you are prompted to manually set the device to update mode in step 1 1 Keep the More alarms 1 and Reset 2 buttons pressed at the same time and disconnect the C NET plug X1 from the printed circuit board 2 Wait at least ten seconds and re insert the C NET plug X1 D The device is setto update mode 3 Click on the OK button in the FW update standard peripheral device window and go to Update firmware step 2 FT2010 Front view FT2010 printed circuit board 90 Building Technologies Fire Safety A6V1
102. n English international Document identification The document ID is structured as follows ID code Examples ID_ModificationIndex_Language COUNTRY A6V10215123 a de DE multilingual or international A6V10215123 a_en_ A6V10315123 a_ _ 7 Building Technologies Fire Safety A6V 10210416 f_en_ 14 01 2013 About this document Applicable documents 8 1 1 Conventions for text marking Markups Special markups are shown in this document as follows gt Requirement for a behavior instruction Intermediate result of a behavior instruction gt End result of a behavior instruction gt X Reference to a page number Text Quotation reproduced identically lt Key gt Identification of keys Supplementary information and tips The i symbol identifies supplementary information and tips for an easier way of working Applicable documents Document ID Title A6V10210355 FS720 Fire Detection System System Description A6V10210362 FS720 Fire Detection System P lanning A6V10210368 FS720 Fire Detection System Product Data A6V10210390 FS720 Fire Detection System Mounting Installation A6V10210424 FS720 Fire Detection System Configuration A6V10211076 FC72x FT 724 Fire Control Panel Fire Terminal Operation A6V10212047 Automatic Fire Detector Technical Manual A6V10224853 FS20 FS720
103. n operating system due to deactivated firewall Unauthorized access to your PC e Activate the firewall after the firmware update 77 Building Technologies A6V 10210416 f_en_ Fire Safety 14 01 2013 Updating the firmware of the Station Setting Windows firewall iJ Windows 7 There are different ways of adjusting the firewall rules in Windows 7 The method described below has been tested successfully Make the following settings for the Windows 7 firewall gt You have administrator rights on your PC 1 Open the Windows start menu 2 Select Control Panel gt All Control Panel Items gt Administrative Tools gt Local Security Policy gt Windows Firewall with Advanced Security 3 Select Advanced settings gt Inbound Rules gt New Rule This opens the New Inbound Rule Wizard 4 Select Rule Type and activate Program Click Next gt to confirm and enter the program path to F F XS 2002 exe Example C Program Files x86 Siemens F F X2030 XL_en_1 V4 0 6 Click Next gt to confirm and then confirm the default setting Allow the connection in the next step Action 7 Inthe next step Profile remove the check mark from the Domain box The Private and Public boxes are checked 8 Click Next gt to confirm and enter an appropriate name in the next step Name such as S20 application 9 Click Finish to comp
104. ng 1 2 3 pi 2 a i 42 Add Site B to Site A Link gt 43 Initialize all Stations that have a new address Link gt 21 Load the configuration of all Stations in Site A from the PC to the Station Link gt 23 Connect the Sites physically to one another Link gt 45 Load the configuration of the merged Site from the Station to the PC Link gt 24 Adapt the configuration in Cerberus E ngineering Tool Link gt 29 Load the configuration from the PC to the Station Link gt 23 Test the function of the Site Link gt 33 Remedy any errors you notice and load the corrected configuration from the PC to the Station Link gt 23 Building Technologies Fire Safety A6V10210416_f_en_ 14 01 2013 Merging two Sites Adding Site B to Site A 12 1 Adding Site B to Site A gt Site A is opened in Cerberus Engineering T ool 1 In the Edit menu select the Merge sites menu item The following window is opened 2 FXS7212 merge sites wizard Welcome to the FXS7212 merge sites wizard Tt will guide you through the process of merging two sites Please make sure that the sites that you want to merge are both based on the same BDY and that all stations of both sites contain the same firmware versions Master site C Documents and Settings All Users Application Data Siemens F FX7230 XS_en_2 V3 0 sites Test Site fsc Please select the si
105. nk gt 86 St O UT oe wo Update the firmware if required of the additional CPUs again if there is a higher firmware version available Link gt 84 Load the configuration from the Station to the PC Link gt 24 Disconnect the PC from the Station Link gt 20 Building Technologies Fire Safety A6V10210416_f_en_ 14 01 2013 Updating the firmware of the Station Updating the firmware of the main CPU and the additional CPUs Overview 20 2 2 20 2 3 Router station and Ethernet station You will find additional information about the individual steps on the specified pages gt Familiarize yourself with the information in P reparation and security gt 71 gt A GAP with DHCP must be configured for the connection with the PC via C WEB LAN 1 Import the new firmware into C erberus E ngineering T ool Select the File gt Import new FW package menu item and open the file you want Load the configuration from the Station or your archive to the PC Link gt 24 Convert the configuration if necessary and rectify conversion faults Link gt 77 Connect the PC to the C WEB LAN via the Ethernet switch MM FN2008 A1 Update the firmware on the main CPU and the additional CPUs Link gt 79 Initialize the Station Link gt 21 Remove the network connection to the Station and connect the PC locally to the Station Link gt 20 7 Test the firmware version
106. nnecting the PC to the Station cccccceccceeceeeeeeeeeeeteeeneeeeeeeeeeseeesnaaeeeeees 20 5 2 Disconnecting PC from the Station cc cceeeeeeeeeeeecceeeeeeeeeeeeeeceeeeeeeeeeteee 20 5 3 Loading data to the Station cccceeceeeeeeeeeececeeeeeeeeeeeeeccaeeeeeeeeeetesssaeeeeeees 21 5 4 initializing Station 2 0 cece eee eee eect eee esse eee Ta a aaa Na Ea AER EEAS 21 5 5 Loading configuration from the PC to the Station ccccccccccccceceeeeeeeeeeeeees 23 5 6 Loading configuration from the Station to the PC cccccccccccccececceeeeeeeeeeeeees 24 5 7 Creating a back up of the Site configuration sssssrssrrrnrrnrnnnnnnnnnnnnnnnnn na 25 6 General COMMISSIONING StEPS eccceeeseeeeeeeeeeeeeeeeeeeeseeeeeeeeeeeeeeeseeeeeeeeees 27 6 1 Preparing Station for COMMISSIONING ccceeeeeeeeeeetteeeeeeeeeeeeetteeeeeeeeeetees 27 6 2 Preparing Station for commissioning without BDV installation 00 28 6 3 Auto Configuring Station cccccccceeceecccceeeeeeeeeeeeeceaaeeeeeeeeeeeeccaaeeeeeeeeeeeeniaaaes 28 6 4 Auto configuring the detector line c cscccceeeeeeeeeeeneeeeeeeeeeeeecaaeeeeeeeeeeeeeaaaes 28 6 5 Loading automatically created configuration to the PC ccccccccccceeeeeeeeeeees 29 6 6 Adapting configuration ccccccccceeeeeeeeccnneeeeeeeeeeeccaaeeeeeeeeeeeeccaaeeeeeeeeeeeeeaaaes 29 6 7 SWItCh
107. nts gt 8 45 A6V 10210416 f_en_ 14 01 2013 Building Technologies Fire Safety Commissioning Ethernet switch MM FN2008 A1 Connecting Sites physically to one another 13 Commissioning Ethernet switch MM FN2008 A1 This description focuses on correctly integrating the Ethernet switch MM FN2008 A1 in the fire detection installation More information about the product can be found on the data carrier in the scope of supply and at the following address http support automation siemens com Manufacturer designation Scalance X204 2 NOTICE Alternate products for Ethernet switch MM FN2008 A1 No compliance with EN 54 e Foran EN 54 compliant fire detection installation you must use the permitted Ethernet switch MM FN2008 A1 46 The Ethernet switch MM FN2008 A1 is a class A equipment and may cause radio interference in residential areas If interference does occur observe the relevant information in document A6V 10210390 See chapter Applicable documents Commissioning 1 Install the Primary Setup Tool software Link gt 47 2 Assign the IP address Link gt 47 3 Configure FN2008 A1 using the Internet browser Link gt 48 4 In Cerberus E ngineering Tool create the links you want e g for the following monitoring functions in a Technical zone Redundant power Display error contact You will find detailed instructions on creating a l
108. o replace radio detectors See chapter Applicable documents See also Applicable documents gt 8 ad a a Oe wy Building Technologies Fire Safety A6V 10210416 f en 14 01 2013 Change and extend the detector line Replacing Manual call point of the same type 19 6 Replacing Manual call point of the same type NOTICE Incorrect assignment between detector detector group and customer text Inaccurate messages in the event of an alarm e You must not change the C NET topology at the same time as adding extra devices e After extending or changing a Site always run a test to check the assignment between detector detector group and customer text iJ You will find additional information about the individual steps on the specified pages Switch on the replace mode Link gt 69 Replace the Manual call point with a Manual call point of the same type Switch off the replace mode Link gt 70 Test the Manual call point Link gt 70 Switch normal operation on Link gt 32 Connect the PC to the Station Link gt 20 Load the configuration from the Station to the PC Link gt 24 Test the function of the Site Link gt 33 Remedy any errors you notice and load the corrected configuration from the PC to the Station Link gt 23 10 Disconnect the PC from the Station Link gt 20 You will find more information about insta
109. odules and spare parts e Components and spare parts must comply with the technical specifications defined by Siemens Only use products specified or recommended by Siemens e Only use fuses with the specified fuse characteristics e Wrong battery types and improper battery changing lead to a risk of explosion Only use the same battery type or an equivalent battery type recommended by Siemens Batteries must be disposed of in an environmentally friendly manner Observe national guidelines and regulations Disregard of the safety regulations Before they are delivered Siemens products are tested to ensure they function correctly when used properly Siemens disclaims all liability for damage or injuries caused by the incorrect application of the instructions or the disregard of danger warnings contained in the documentation This applies in particular to the following damage Personal injuries or damage to property caused by improper use and incorrect application Personal injuries or damage to property caused by disregarding safety instructions in the documentation or on the product Personal injury or damage to property caused by poor maintenance or lack of maintenance 13 Building Technologies Fire Safety A6V 10210416 f_en_ 14 01 2013 Safety Standards and directives complied with 2 3 2 4 Standards and directives complied with A list of the standards and directives complied with is available from
110. on is auto configured The following message is shown following successful auto configuration Command executed You will find detailed information on the result of the auto configuration in the List of compatibility See chapter Applicable documents See also Applicable documents gt 8 Auto configuring the detector line NOTICE Incorrect order for reading in a loop Error when reading in a loop The C NET detector lines are detected as stubs during the first system start up e g Line 11 Line 12 2 digit line number even if they are connected as a loop e Always select the first Line to read in a loop in this case Line 11 Line 12 is then read in automatically After reading in a loop is indicated with a 1 digit line number in this case as Line 1 e Proceed in the same way from Line 21 22 loop 2 to Line 41 42 loop 4 28 Building Technologies Fire Safety A6V 10210416 f en 14 01 2013 General commissioning steps Loading automatically created configuration to the PC iJ 6 5 6 6 1 Inthe main menu select Topology gt Hardware tree gt Station gt Line card gt Detector line Press the More Options softkey and select E xecute commands Select the Auto configure line command The C NET detector line is auto configured D po wN The following message is shown following successful auto configuration
111. onary 67 Removing for good 65 Replace base without loop contact 62 Replacing different types 61 63 Replacing same type 60 Replacing stationary 68 Swapped 110 Temporarily remove 64 Download 21 23 E Error message Topology is invalid 111 Ethernet switch MM FN2008 A1 46 Event memory 71 Expand Detector line 66 Site 41 External printer 99 F Factory reset 113 Factory setting 113 115 Building Technologies A6V 10210416 f_en_ Fire Safety 14 01 2013 Index Fault indicators 109 FCI2007 A1 I O card RT 58 FC12009 A1 I O card horn monitored 58 FDUL221 line tester Updating the firmware 95 FDUL221 serial line tester Updating the firmware 97 FDUZ221 MCL USB adapter Updating the firmware 88 Fire brigade periphery module F C12001 D1 57 Firewall Security module firewall FN2009 A1 49 Windows firewall 71 77 Floor repeater display Updating the firmware 91 F loor repeater terminal Updating the firmware 89 FN2008 Al Ethernet switch MM FN2008 A1 46 FN2009 A1 safety 49 FT2001 A1 mimic display driver Updating the firmware 93 FT2010 floor repeater terminal Updating the firmware 89 FT2011 floor repeater display Updating the firmware 91 FUJITSU DL3750 99 Function test 33 106 106 Fuse 25 H Hardware reset station 112 I O card horn monitored FC12009 A1 58 I O card RT FC12007 A1 58 Indication of faults Component 109 Initialize station 21 21 Install
112. orresponding logical elements are created in the Detection tree and Control tree The following procedures are examples of adaptations Entering customer text for logical elements Changing detector parameter sets Configuring alarm devices Controls Configuring Configuring the power supply Point detectors installed on a base apart from radio detectors All devices apart from point detectors e g Manual call point Radio detector Input output modules Alarm sounder Line separator Radio gateway Floor repeater terminal Floor repeater display Mimic display driver Building Technologies Fire Safety A6V10210416 f en 14 01 2013 Commissioning overview Brief instructions on operating the Station 4 3 Brief instructions on operating the Station Buttons Description 8 Opens the main menu MENU gt lt 4 gt and lt gt Navigation buttons for selecting the next or previous entry in a list lt lt gt and gt Navigation buttons for changing to a higher or lower level in the hierarchy ok Opens or runs a selected entry or menu item lt k gt Cancels all operating procedures and closes an open list or lt C gt an open window lt 1l gt to gt Buttons on the keypad to enter e PIN Shortcut Address Parameter Customer text You will find detailed instructions for operating the Stations in document A6V10211076 See chapter Applicable do
113. oved Reference to doc A6V10244961 S ite conversion added Revised chapters Updating the firmware of the Station Restarting S tation Restoring Station to factory setting Loading configuration from the PC to the Station Chapter structure changed c 08 2009 Modifications for MP1XS b 05 2009 Modifications for MP1XS a 11 2008 First edition 10 Building Technologies Fire Safety A6V 10210416 f en 14 01 2013 Safety Safety instructions 2 1 Safety Safety instructions The safety notices must be observed in order to protect people and property The safety notices in this document contain the following elements Symbol for danger Signal word Nature and origin of the danger Consequences if the danger occurs Measures or prohibitions for danger avoidance Symbol for danger A This is the symbol for danger It warns of risks of injury Follow all measures identified by this symbol to avoid injury or death Additional danger symbols These symbols indicate general dangers the type of danger or possible consequences measures and prohibitions examples of which are shown in the following table General danger Explosive atmosphere Voltage electric shock A Laser light A Batte Heat Signal word The signal word classifies the danger as defined in the following table Signal word Danger level DANGER DANGER identifies a dangerous situation
114. peration without power X1 pin1 BATT X1 pin4 COMMON supply unit X1 pin2 CONV X1 pin4 COMMON X1 pin3 MAINS X1 pin4 COMMON Configuring the power supply You will find the pin assignments in document A6V10210368 See chapter Applicable documents See also Applicable documents gt 8 Entering customer texts using the Person Machine Interface 1 Select Topology gt Detection tree gt Area gt Section gt Zone in the main menu 2 Select the element you want to label with a customer text 3 Press the More Options softkey and select Execute commands 4 Select the Set customer text command 5 Enter the customer text using the numeric keypad 6 Press lt ok gt to save the customer text There is no need to restart the Station Showing the customer text on the display e Allelements apart from Zone If a message associated with an element appears the corresponding customer text is displayed If no customer text is assigned to this element the customer text of the next superordinate element e g Detector gt Line gt Line card appears e Zone element If an alarm message for a Zone appears the customer text of the detector sensor is displayed The customer text of the Zone appears if no customer text is assigned to the Detector The customer text of the next superordinate element Detector gt Zone gt Section gt Area
115. r and a Manual call point per Line X C NET Activate all M anual call points Trigger all automatic fire detectors Check all Detectors for soiling and application X Check the function of the input output modules X On each Line check whether a short circuit or open line triggers a X Fault Check the loop line function During short circuit also check the separator function 106 Building Technologies Fire Safety A6V 10210416 f en 14 01 2013 Maintenance Completion work Function Activity Interval years 1 2S Fire controls Check activation of the Controls up to and with the interface X Check the effects of the Controls owned by the customer Arrange a X time with the customer Mains failure Check how long ittakes until the Emergency power operation fault message is displayed during power failure Alarm devices In Emergency power operation check all alarm devices taking the X following event category into account Pre ALARM ALARM Fault Check the remote transmission equipment in accordance with the X manufacturer s instructions Alarm organization Check the function of the delay times t1 and t2 Activate a global alarm with an Automatic detector in the Unmanned operation operating mode Activate a local and global alarm by setting a Manual call point to the
116. r lines off Link gt 30 2 Wire both stubs to a loop You will find more information about this in document A6V10210390 See chapter Applicable documents 3 Read in the C NET devices Link gt 31 Start with the first Line in the example Line 11 The second Line is adopted and the loop is formed in this example Line 1 4 Connectthe PC to the Station Link gt 20 5 Load the configuration from the Station to the PC Link gt 24 6 Testthe function of the Site Link gt 33 7 Remedy any errors you notice and load the corrected configuration from the PC to the Station Link gt 23 8 Disconnect the PC from the Station Link gt 20 See also Applicable documents gt 8 67 Building Technologies Fire Safety A6V 10210416 f_en_ 14 01 2013 Change and extend the detector line Connecting a sub stub to a loop iJ 19 4 19 5 Connecting a sub stub to a loop You will find additional information about the individual steps on the specified pages 1 Switch the C NET detector line off Link gt 30 2 Physically connect the sub stub to the loop Y ou will find more information about this in document A6V10210390 See chapter Applicable documents 3 Read in the C NET devices Link gt 31 4 Connect the PC to the Station Link gt 20 5 Load the configuration from the Station to the PC Link gt 24 6 Test the function of the Site Link
117. re actions on the Station until the Buzzer has sounded for the second time 3 Enter the date and time To do this select the Settings administration gt System commands gt Set system time menu items 114 Building Technologies A6V10210416_f_en_ Fire Safety 14 01 2013 Index Index A Acceptance test 16 Alarm counter 71 Auto configuration 35 Definition of terms 18 Detector line 29 station 28 B Back up 25 C Commissioning 17 According to wiring sequence 15 Auto configuration 35 Networked station 40 Overview 17 Standalone station with PC with pre configuration 39 Standalone station with PC without pre configuration 38 Standalone station without PC 35 With serial number 15 Without PC 35 Communication problems 110 Component Indication of faults 109 Configuration Conversion 77 Load to station 21 23 Loading to PC 24 Connecting a sub stub to a loop 68 Connection to the station 20 Connectivity 20 Conversion 77 Configuration 77 Convert stubs into loops 67 CPU Updating the firmware 79 CPU other Updating the firmware 84 Customer text 36 D Date time 110 Deleting Device 31 Detector Test mode 32 Testing 59 Detector inspection 106 Detector line Auto configure 29 Expand 66 Install 15 ON 30 Restart 30 Switch off 30 Testing 15 Detector self test 106 Device Remove 60 Remove base without loop contact 62 Removing stati
118. ress is saved to the F N2008 A1 5 Repeat the Load process for each FN2008 Al Each FN2008 A1 in the system has an individual IP address 47 Building Technologies Fire Safety A6V 10210416 f_en_ 14 01 2013 Commissioning Ethernet switch MM FN2008 A1 Configure FN2008 A1 using Internet browser 13 3 iJ Configure FN2008 A1 using Internet browser A configuration is available via the localization manager We recommend using the configuration and if necessary making system specific adaptations NOTICE Incorrect settings of the ports Malfunction e The factory setting auto negotiation for the ports may not be changed 48 1 Open the Internet browser and enter the FN2008 A1 s address in the address field The login window opens 2 Login User name admin Password admin 3 Select System gt Passwords in the tree view and set a new password for the following fields New User Password New Admin Password 4 Confirm the entered password with Confirmation Click Set Values 6 Select X204 2 gt Ring in the tree view and check the Enable ring redundancy checkbox Select the Automatic Redundancy Detection redundancy mode 7 Select X204 2 gt Fault Mask in the tree view and check the Enable Link Down Monitoring checkbox for each connected port Port 5 and 6 Ring Port 1 The connected Station Port 2 to 4 only if
119. rmware of the additional CP Us if there is a higher firmware version status Select the connection via GAP and enter the address of the Station you want to update Link gt 84 5 Load the configuration from the PC to the Station Link gt 23 6 Load the configuration from the Station to the PC Link gt 24 7 Disconnect the PC from C WEB LAN 75 Building Technologies Fire Safety A6V10210416_f_en_ 14 01 2013 Updating the firmware of the Station Update only the BDV 20 4 20 4 1 20 4 2 76 Update only the BDV If the old and new BDVs are compatible identical major and minor versions and there is no new firmware version available for the main CPU itis also only possible to update the BDV You will find Information about BDV names and versions in document A6V10210424 See chapter Applicable documents The procedure for updating the BDV depends on the Station function The procedures are described in the following chapters See also Applicable documents gt 8 Standalone station and SAFEDLINK station You will find additional information about the individual steps on the specified pages gt Familiarize yourself with the information in P reparation and security gt 71 1 Import the new BDV into Cerberus E ngineering T ool Select the File gt Import new BDV menu item and open the file you want 2 Load the configuration from the Station or your archi
120. rocedure and the above actions having to be carried out See also Loading data to the Station gt 21 Loading configuration from the Station to the PC The Upload site function can be used to load the configuration of a Site to Cerberus E ngineering Tool on the PC gt The Site is opened in Cerberus Engineering T ool gt The PC is connected to the Station gt Station and Cerberus E ngineering Tool have the same Site ID gt Station and Cerberus Engineering Tool are in the same organizational unit 1 Select Commissioning gt Upload site The Upload site and Connect windows are opened Connect Upload ID Station Local connection Status O Connection to GAP O Connection to address Cancel 2 Select Connect in the window and click on OK The Stations are listed in the Upload site window Building Technologies Fire Safety A6V 10210416 f en 14 01 2013 Connectivity and communication with Station Creating a back up of the Site configuration 3 Select the Stations whose configuration you would like to load to Cerberus Engineering Tool and click on Start The Action confirmation window opens 4 Click on Yes The configuration is loaded to the PC The advancement status is displayed in the Upload site window Creating a back up of the Site configuration With the Create backup embedded configuration function
121. rt the cables for the detector lines and the mains supply into the housing but do not yet connect the the cables 3 Insert the batteries but do not yet connect them You will find information about mounting and installation of Stations components in the A6V 10210390 document See chapter Applicable documents See also Applicable documents gt 8 Building Technologies Fire Safety A6V 10210416 f en 14 01 2013 Commissioning overview Commissioning variants 4 Commissioning overview The Stations on the C WEB such as control panels FC 722 FC724 and fire terminals FT724 are connected to the power supply and commissioned by the installation and commissioning personnel e Networked Stations must only be commissioned with Cerberus E ngineering Tool e Standalone control panels can be commissioned with or without Cerberus Engineering T ool NOTICE Alternative commissioning procedure Faults during operation e Only the procedures described in this document are permitted 4 1 Commissioning variants In order to satisfy Directive 89 106 EEC the Construction Products Directive CPD the firmware of a newly installed fire detection installation must be current market package version MP1XS or higher NOTICE Firmware version of a newly installed fire detection installation not updated No CPD conformity e Compare the firmware version of a newly installed fire detect
122. rus Engineering Tool is installed on the PC e The current firmware and BDV are available on the PC iJ You will find additional information about the individual steps on the specified pages Commissioning 1 Prepare the Station for commissioning Link gt 27 2 Perform auto configuration Auto configure Station Link gt 28 OR Auto configure detector lines individually Link gt 28 Connect the PC to the Station Link gt 20 Load the automatically created configuration to the PC Link gt 29 Adapt the configuration in Cerberus Engineering T ool Link gt 29 Load the configuration from the PC to the Station Link gt 23 Test the function of the Site Link gt 33 Remedy any errors you notice and load the corrected configuration from the PC to the Station Link gt 23 9 Disconnect the PC from the Station Link gt 20 10 Perform the completion tasks Link gt 34 o N o n e w 38 Building Technologies A6V10210416_f_en_ Fire Safety 14 01 2013 B2 Commissioning stand alone Station with PC with pre configuration 9 B2 Commissioning stand alone Station with PC with pre configuration In this commissioning variant in Cerberus E ngineering T ool first manually configure a Site up to Line level Then read in the C NET devices and adapt the configuration manually in Cerberus E ngineering T ool Prerequisites The detector lines and C NET
123. s need initializing and for which Stations a download is sufficient FXS7212 merge sites wizard Merge completed The merge of the two sites was successfully completed Please acomplish the Following actions For the stations Station Site Original address New address Required action FC724 Station 3 Test Site fsc DOWNLOAD FC724 Station 4 Test Site fsc DOWNLOAD FC722 Station 11 Test Site fsc DOWNLOAD FC724 Station12 Test Site fsc DOWNLOAD FC724 Station 13 Test Site fsc DOWNLOAD FC724 Station 14 Test Site fsc DOWNLOAD FC724 Station 15 Test Site fsc DOWNLOAD FC724 Station 16 Test Site Fsc DOWNLOAD FC722 Test_Site_B fsc INITIALIZE FC722 Test_Site_B fsc INITIALIZE FC724 Test_Site_B Fsc INITIALIZE FC724 Test_Site_B fsc INITIALIZE FC724 Test_Site_B fsc DOWNLOAD Show the log file Save report as file 9 Click on Show the log file to view the protocol 10 Click on Save report as file to save and print a merging report This report also shows which Stations must be initialized 11 Click on the OK button to close the window 44 Building Technologies A6V10210416 f_en_ Fire Safety 14 01 2013 Merging two Sites Connecting Sites physically to one another 12 2 Connecting Sites physically to one another Connect the two Sites physically to one another You will find more information in document A6V 10210390 See chapter Applicable documents See also Applicable docume
124. s open enter the password 1234 and click on OK The following window is opened Connect Local connection Target station address 3 Select the connection type Select Local connection to establish a connection to the connected standalone or SAFEDLINK Station Select Connection to GAP to establish a connection via GAP toa networked Station In the field Target station address enter the address of Station If you want to create a connection to GAP Station itself enter 0 4 Click on OK The following window is opened FW update additional CPUs Update Type part no Name Address Installed version Update to version Status FCI2002 41 45000005545 07 Onboard I Os FCI2002 ii 1 2 11 1 2 11 FDnet FCI2002 45000005545 07 C NET line card onboard FCL2001 1 2 3 3 9 3 5 0 Installed firmware version not supported FN2001 A1 45000012851 11 SAFEDLINK interface FN2001 1 4 1 4 2 1 4 2 1 CPLD on FCM2004 A5Q00005163 05 Degrade interface 1 4 3 4 0 2 4 0 2 FCM2004 A1 A5Q00005163 05 PMI board interface 1 4 5 2 2 0 2 2 2 Installed firmware version not supported gt 5 Test the firmware version on the additional CPUs 6 Click on Cancel in the FW update additional CP Us window 86 Building Technologies A6V10210416_f_en_ Fire Safety 14 01 2013 Updating the firmware of the Station Creating diagnosis report 20 10 Cre
125. te serial FDUL221 line test device window is opened and you are prompted to release the buttons 2 Release the buttons The device is set to update mode Click on the OK button in the FW update serial FDUL221 line test device window and go to Update firmware step 2 98 Building Technologies A6V10210416_f_en_ Fire Safety 14 01 2013 Commissioning external printer 22 Commissioning external printer The external FUJ ITSU DL3750 printer can be installed and commissioned using the operating manual The operating manual is on the CD delivered with the printer To operate the printer on the fire detection system FS 720 settings that differ from the default values must be made in the following functions e MENU 1 Assignment of print functions to MENU1 in the printer Person Machine Interface e MENU 2 Assignment of print functions to MENU2 in the printer Person Machine Interface e HARDWRE Changing the printer hardware options e ADJ UST Changing the setting options for the print position e CONFIG Changing the configuration options The printer must be set to configuration mode in order to do this You will find information on this in document A6V 10224853 See chapter Applicable documents The following table shows the options to be set Function Value MENU 1 EMULATE XL24E FONT COUR 10
126. te to merge with the master site ki C Documents and Settings All Users Application Data siemens F FX7230 x5_en_2 V3 0 sites Test_Site_B fsc Browse Merged site C Documents and Settings All Users Application Data Siemens F FX7230 5_en_2 V3 0 Sites Test_Site_A B fsc 29 N Enter the path and name of Site B that you would like to merge with Site A Enter the path and name of the new merged Site Click on Next gt The conditions for merging are checked The results are listed in the window below FXS7212 merge sites wizard Merge sites precheck The merge precheck shows the Following results Check Test Site fsc Test_Site_B fsc Result Equal BDY F FX52004 XS_en_2 32 11 10_06E F FX52004 XS_en_2 32 11 10_06E Version gt 31 1 0 ok ok Not standalone station no no Equal business channel PCI Max number of stations 10 Max number of safedlink 6 Max number of safedlink subnets 2 Max number of ethernet 3 Max number of BACnet client elements 2 Not unresolved references no Equal usage of the sections Equal usage of the plannumber Equal usage of the two digit detector address Equal usage of the inherit customer text Cancel 5 Click on Next if ok is everywhere in the Result column If ok is not everywhere click on Cancel and ensure that all the conditions that are listed in the Check column are satisfied Cerberus Engineering Tool checks whether ther
127. ted yet The cables for the detector lines and the mains supply have been inserted in the Station but not connected iJ You will find additional information about the individual steps on the specified pages Commissioning 1 2 3 If necessary configure the power supply Link gt 36 Prepare the Station for commissioning Link gt 27 Perform auto configuration Auto configure Station Link gt 28 OR Auto configure detector lines individually Link gt 28 Adapt the auto configuration in the Person Machine Interface e g Changing customer texts Link gt 36 Setting parameter sets of the C NET devices Link gt 37 Test the function of the Site and remedy the problems if any Link gt 33 Perform the completion tasks Link gt 34 35 Building Technologies Fire Safety A6V10210416_f_en_ 14 01 2013 A Commissioning stand alone Station without PC Configuring the power supply 36 7 1 7 2 Configuring the power supply If the Station is equipped with a power supply and batteries the power supply does not have to be configured In all other cases the power supply must be configured This may be done by wiring accordingly The following table shows the cases in which the monitoring signals of the power supply must be re wired Operation mode Connector on Connect with periphery board Operation without X1 pin1 BATT X1 pin4 COMMON batteries O
128. ter set Use Person Machine Interface 37 Site Expand 41 Load data to PC 24 Load data to the station 23 Merge 42 Test intervals 106 Spare parts 102 108 Stand alone station 35 38 39 station Auto configure 28 Disconnect power 108 Factory setting 113 Hardware reset 112 Initialize 21 21 Load data 21 Mount and install 16 Resetting 113 Restart 112 Switching off 108 Swapped Device 110 Switch off Detector line 30 Switching off station 108 System data 104 T Test 33 106 Test intervals 106 106 Test mode 32 Detector 32 Exit 32 Test unit 103 Testing Detector 59 59 Detector line 15 Function 106 Power supply 105 Printer 106 System data 104 Time date 110 Topology is invalid 111 U Uninstalling Device 31 Update BDV 76 Updating the firmware Additional CPUs 84 Main CPU and additional CPUs 79 Periphery devices 88 station 71 Upload 24 117 Building Technologies A6V 10210416 f_en_ Fire Safety 14 01 2013 Index W Windows firewall 71 77 Z Zone ON 30 Switch off 30 118 Building Technologies A6V10210416 f_en_ Fire Safety 14 01 2013 Index 119 Building Technologies A6V 10210416 f_en_ Fire Safety 14 01 2013 Issued by Siemens Switzerland Ltd Infrastructure amp Cities Sector Building Technologies Division International Headquarters Gubelstrasse 22 CH 6301 Zug Tel 41 41 724 24 24 www siemens com buildingtechnologies 200
129. the Station to the PC Link gt 24 Adapt the configuration in Cerberus E ngineering T ool Link gt 29 Load the configuration from the PC to the Station Link gt 23 Test the function of the Site Link gt 33 Remedy any errors you notice and load the corrected configuration from the PC to the Station Link gt 23 Disconnect the PC from the Station Link gt 20 Perform the completion tasks Link gt 34 41 Building Technologies Fire Safety A6V 10210416 f_en_ 14 01 2013 Merging two Sites Setting detector parameter sets 12 Merging two Sites You can merge two Sites to form one Site Prerequisites e Both Sites are in the same organizational unit e Both Sites have the same firmware version and BDV version version 32 or higher Both Sites have one network Both Sites combined have at most the allowed number of Stations for a Site Both Sites combined have at most the allowed number of SAFEDLINK sub nets for a Site e Wiring between the two Sites is prepared The Ethernet switch MM FN2008 A1 is installed in the Stations intended as router station and connected to an optical network C WEB LAN Large SAFEDLINK sub nets are in the original state and not yet divided Ethernet sub net are in the original state iJ You will find additional information about the individual steps on the specified pages Commissioni
130. the standby router or with IP address details 51 Building Technologies Fire Safety A6V 10210416 f en 14 01 2013 Commissioning safety module firewall FN2009 A1 Entering network settings gt Module 1 is highlighted in the View window 1 Press lt F 4 gt on the keyboard or open the Edit gt Properties menu gt The Module Properties window is displayed Module Properties Module1 a 2 Select the Routing Mode tab gt The following entry mask is displayed Module Properties Routing Smpl Adu 192 168 201 2 F Allow Intemal gt Extemal for all users external IP address internal IP address _ Direction 3 Check the Routing active checkbox 4 Enter the following internal module IP address 192 168 201 2 5 Confirm input with OK Internal sub net mask is automatically created gt Routing Mode is active 52 Building Technologies A6V10210416_f_en_ Fire Safety 14 01 2013 Commissioning safety module firewall FN2009 A1 Entering network settings Entering router network data Router The following settings apply for the planned network access to GAP with activated DHCP server Open the Module Properties window again The Network tab is displayed Click on Add Router The Sub net Mask 255 255 255 0 is already entered Correct the Sub
131. tions of the Site in the various test modes You will find information about testing a Site in the chapter Testing in document A6V10211076 See chapter Applicable documents See also Applicable documents gt 8 33 Building Technologies A6V 10210416 f_en_ Fire Safety 14 01 2013 General commissioning steps Completion work 6 20 Completion work 1 Check the time and date and reset these To do this select S ettings administration gt System commands gt Set system time in the main menu 2 Setthe PIN for the access levels 1 2 1 2 2 and 3 To do this select S ettings administration gt Create PIN in the main menu Fit the housing cover 4 Label the installation plate which should be outside on the housing with the site number and the date of commissioning To do this use a Solvent resistant pen 34 Building Technologies A6V10210416_f_en_ Fire Safety 14 01 2013 A Commissioning stand alone Station without PC Completion work 7 A Commissioning stand alone S tation without PC iJ The procedure in this chapter is only valid for standalone Stations In this commissioning variant a Station withouta PC and a Cerberus E ngineering Tool are commissioned Prerequisites The detector lines and C NET devices are installed The acceptance test has been carried out for the detector lines The Station is installed but the batteries are not connec
132. to the factory setting as well as a Initialize station e Do not modify the selection displayed for Download site in normal cases e Check the sequence when loading different configuration states in special cases 1 e After any change of the network configuration make sure that all Stations in the Site for the Download site procedure are selected and can be accessed e Temporarily update non accessible Stations to the latest status of the global network configuration prior to integration in the network If you use a number of network cards on the PC observe the information in the chapter IP settings for several network cards in document A6V 10210424 See chapter Applicable documents The Site is opened in Cerberus E ngineering T ool The PC is connected to the Station Networked Stations are initialized Station and Cerberus E ngineering Tool have the same Site ID Station and Cerberus Engineering T ool are in the same organizational unit PV VV VV Select Commissioning gt Download site The Download site and Connect windows are opened Download site gt Connect Status O Connection to GAP O Connection to address a 2 Select Connect in the window and click on OK The Stations are listed in the Download site window 3 Select the Stations whose configuration you would like to load from Cerberus Engineering Tool
133. tting on the Station e Via the menu on the display e With the S32 button NOTICE Restoring factory setting on the Station The configuration of the Station is deleted e Save the configuration data for the Station before restoring the factory setting Via the menu on the display 1 Press lt MENU gt You are prompted to enter a PIN 2 Enter a valid PIN and confirm with lt ok gt The User successfully logged in message is displayed The main menu is displayed 3 Select the Topology gt Hardware tree gt Station menu items 4 Press the More Options softkey and select E xecute commands 5 Select the Factory reset command gt The Station restarts gt After a few minutes the Buzzer sounds twice 6 Press lt Acknowledge gt on the Person Machine Interface to switch off the Buzzer Do not perform any more actions on the Station until the Buzzer has sounded for the second time 7 Enter the date and time To do this select the Settings administration gt System commands gt Set system time menu items 113 Building Technologies A6V 10210416 f_en_ Fire Safety 14 01 2013 Repair Restoring factory setting on the Station PMI amp mainboard FCM2004 1 Set the S38 1 switch to ON on the rear of the operating unit 2 Press the S32 button for gt 2s until the Station restarts FCM2004 s32 Hs S38 1 S3
134. u 2 Do not replace current firmware versions with the current version if this is not necessary to correct faults or add functions Event memory Check the content of the Event memory and take the necessary measures Change in use Verify whether a change of use or changes to the building have an effect on the configuration and perform the necessary corrections Pending modification applications Check that all pending modification applications such as corrections to the diagrams or modifications to the fire brigade orientation plans have been completed Testing the Station Check the hardware e Check the condition of the housing and the components e Check the fixture of screws terminals and plug connections e Check that the batteries are not leaking inspection Check labeling Check that the inscription strips are correct and still easily legible Building Technologies Fire Safety A6V 10210416 f en 14 01 2013 Maintenance Check the power supply 23 7 Check the function 1 Enter the password 2 Initiate the lamp test 3 Check switchover of operating modes from Manned operation to Unmanned operation and vice versa 4 Switch an Area off and on again 5 Check the operation of an alarm 6 Check the operation of a Fault 7 Block operation Clean the operating unit Clean the display and the front plate with a wet cloth Do not use any caustic solvents Check the
135. ve to the PC Link gt 24 3 Convert the configuration and rectify conversion faults Link gt 77 4 Connect the PC to the Station Link gt 20 5 Enable the Station Press lt MENU gt and enter a valid PIN 6 Load the converted configuration from the PC to the Station Link gt 23 7 Disconnect the PC from the Station Link gt 20 Router station and Ethernet station You will find additional information about the individual steps on the specified pages gt Familiarize yourself with the information in P reparation and security gt 71 1 Import the new BDV into Cerberus E ngineering T ool Select the File gt Import new BDV menu item and open the file you want 2 Load the configuration from the Station or your archive to the PC Link gt 24 Convert the configuration and rectify conversion faults Link gt 77 4 Remove the network connection to the Station and connect the PC Link gt 20 5 Enable the Station Press lt MENU gt and enter a valid PIN 6 Load the converted configuration from the PC to the Station Link gt 23 Disconnect the PC from the Station Link gt 20 8 Restore the network connection Building Technologies Fire Safety A6V10210416 f en 14 01 2013 Updating the firmware of the Station Converting the configuration 20 5 Converting the configuration In document A6V10260976 you will find detailed infor
136. vent memory to Cerberus E ngineering T ool before updating the firmware NOTICE Power failure during the firmware update Firmware is not updated and Station is not working The firmware update cannot be repeated and must be performed by the manufacturer e Do not disconnect the Station from the power supply during the firmware update 20 2 20 2 1 72 See also Updating several Stations simultaneously gt 73 Updating the firmware of the main CPU and the additional CPUs Overview The procedure for updating the firmware depends on the nature and function of the Station The procedures are described in the following chapters Standalone station and SAFEDLINK station You will find additional information about the individual steps on the specified pages gt Familiarize yourself with the information in P reparation and security gt 71 1 Import the new firmware into Cerberus E ngineering T ool Select the File gt Import new FW package menu item and open the file you want Load the configuration from the Station or your archive to the PC Link gt 24 Convert the configuration if necessary and rectify conversion faults Link gt 77 Connect the PC to the Station Link gt 20 Update the firmware on the main CPU and the additional CPUs Link gt 79 Initialize the Station Link gt 21 Test the firmware version on the additional CPUs Li
137. which will result directly in death or serious injury if you do not avoid this situation WARNING WARNING identifies a dangerous situation which may result in death or serious injury if you do not avoid this situation CAUTION CAUTION identifies a dangerous situation which could result in slight to moderately serious injury if you do not avoid this situation NOTICE NOTICE identifies possible damage to property that may result from non observance 11 Building Technologies Fire Safety A6V10210416_f_en_ 14 01 2013 Safety Safety regulations for the method of operation How risk of injury is presented Information about the risk of injury is shown as follows A A WARNING Nature and origin of the danger Consequences if the danger occurs e Measures prohibitions for danger avoidance How possible damage to property is presented Information about possible damage to property is shown as follows NOTICE Nature and origin of the danger Consequences if the danger occurs e Measures prohibitions for danger avoidance 2 2 Safety regulations for the method of operation National standards regulations and legislation Siemens products are developed and produced in compliance with the relevant European and international safety standards Should additional national or local safety standards or legislation concerning the planning assembly installation operation or disposa
138. your Siemens contact Release Notes Limitations to the configuration or use of devices in a fire detection installation with a particular firmware version are possible A A WARNING Limited or non existent fire detection Personal injury and damage to property in the event of a fire e Read the Release Notes before you plan and or configure a fire detection installation e Read the Release Notes before you carry out a firmware update to a fire detection installation NOTICE Incorrect planning and or configuration Important standards and specifications are not satisfied Fire detection installation is not accepted for commissioning Additional expense resulting from necessary new planning and or configuration e Read the Release Notes before you plan and or configure a fire detection installation e Read the Release Notes before you carry outa firmware update to a fire detection installation 14 Building Technologies A6V10210416_f_en_ Fire Safety 14 01 2013 Mounting Installation Installing and checking the detector line 3 Mounting Installation 3 1 Installing and checking the detector line Most C NET devices are installed on a base and can be changed with ease The bases of non stationary C NET devices and stationary C NET devices must be installed and uninstalled when the C NET detector line is switched off and disconnected from the power supply Prerequisites