1. Mechanical extraction of condenser air into ceiling space or preferably out of the building is advised See page 19 for Freeblock refrigeration unit safety and service guidelines Preparation Installation Manual Room Location Ventilation amp Condenser Air Extraction Power Supply Preparation Installation Manual SKOPE MISA Cool amp Freezer Rooms Positioning the Room Before assembling the room decide where to position it The room is installed from the inside so can be positioned in place in tight spaces Once installed the room should not be moved We recommend that the room is installed in the coolest place possible Do not install the refrigeration unit in direct sunlight The ambient temperature around the Freeblock refrigeration unit must not exceed 43 C Check manufacturers specifications if installing a third party refrigeration unit The room should be installed either away from walls to enable access for cleaning or sealed to the walls to prevent harbourage of vermin Enclosed areas above the room must be pest proffed Allow adequate space for the door to open and close properly Self closing swing doors are aligned and tensioned at the factory and must be unobstructed Refrigeration units must be supported well to allow for easy cleaning Ensure adequate extraction or ventilation is available Prevent any noise nuisance to nearby residences and businesses Refrigeration units should be placed away f
2. SKOPE MISA Cool amp Freezer Rooms Installation Manual SKOPE MISA Cool amp Freezer Rooms 1 Specifications Compliance SKOPE Industries Limited MISA cool and freezer rooms comply with the Australian and New Zealand building code the Australian Food Safety Standard 3 2 3 food premises and equipment and the Australian Standard AS 4674 2004 design construction and fitout of food premises Modular Rooms MISA Freeblock Construction Insulation Door s 100mm polyeutherane foam Self closing solid foamed swing door Dimensions Model KLC1AF2M KLC2AF2M KLC3BF2M KLC3CF2M KLCACF2M KLCADF2M KLCSDF2M KLCSEF2M KLC6EF2M Internal ee dimensions mm 2230 2230 2230 2230 2230 2230 2230 16 25 FB 20G 3030 3030 2230 18 56 FB 26G 3430 3030 2230 Internal height 2m also available in 2 4m Technical specifications Model FB 3G FB 7G FB 13G FB 16G FB 20G FB 26G FB 3N FB SN FB 6N FB 13N FB 20N FB 28N 32 CAmbient Ambient 43 C Ambient Supply Nominal LL Nominal Current range C Volts capacity draw capacity draw Watts Amps Watts Amps 27 27 29 fis E pee a 27 280 770 27 70 27 mo 96 3i Ws 3 AB1 2o 290 1320 48 no 48 380 400 3 phase 890 DERI 380 400 3 phase ze en l m Specifications Installation Manual SKOPE MISA Cool amp Freezer Rooms MISA Drop In Technical specifications Nominal Current
3. refrigeration unit up and insert the evaporator into the wall space Access can be made easier by lifting the ceiling corner above the refrigeration unit Space 2 Ensure the refrigeration unit is fully inserted and flush with the interior wall surface 3 Use the large cam lock tool to lock the refrigeration unit into position Remove the front panel from the refrigeration unit to access the top cam locks The bottom cam locks are accessed from inside the room 4 Refit the front cover 5 Connect up the electrical components see page 21 complete the room inspection see page 23 and installation checklist see back page Installation Installation Manual Refrigeration Unit Wiring Interior Light Installation Installation Manual SKOPE MISA Cool amp Freezer Rooms Electrics All electrical wiring should be completed by a licenced electrician and installed in accordance with the relevant electrical wiring rules and regulations AS NZS 3000 Once the room has been assembled and the unit fitted the refrigeration unit electrical wiring can be connected Two electrical cables exit the top of the refrigeration unit One of these is the mains supply cable and the other is the door switch cable The mains supply cable is made up of active neutral and earth wires We recommend that single phase Freeblock refrigeration units are hard wired to a 20 Amp circuit with isolation switch and that 3 phase Free
4. an approved SKOPE registered installer and in accordance with the installation guidelines set out in this MISA installation manual SKOPE warrants that for the period of two years commencing on Commissioning Installation Manual Commissioning Installation Manual SKOPE MISA Cool amp Freezer Rooms the date of purchase or 6 months from the date of manufacture whichever is earlier the MISA products will be free from any defect in workmanship or material Where there is any conflict between this installation manual and the SKOPE Warranty Terms the SKOPE Warranty Terms shall prevail SKOPE s sole obligation should the products be found upon inspection by or on behalf of SKOPE not to meet the warranty is to at SKOPE s option repair or replace the products without charge provided that the liability of SKOPE shall in no event exceed the purchase price of the products The application of any warranty provided by SKOPE for MISA products is expressly excluded where a defect malfunction or failure of refrigeration equipment is due to inadequate ventilation and the customer s recourse will be solely against the installer SKOPE MISA Cool amp Freezer Rooms 3 Preparation Safety First Always observe safety precautions when using any electrical appliance Read these instructions carefully and retain them for future reference When the appliance is used by or near young children or infirm persons close supervision is necessary es
5. the door heater electrical box to access the heater wire terminals Pry the edge of the door opening off to access the heater wire Servicing Installation Manual MISA Installation and Commissioning Checklist The following checklist must be completed by the installer after the room has been installed A completed copy must stay on site and a copy sent to SKOPE for warranty registration warranty skope co nz Site Details Approved installer Customer s name Address of installation Date of installation Description of work Compliance The installation has been completed in accordance with the MISA installation manual thecustomer s plans and specifications theterms of local authority consents all relevant laws regulations building codes and standards Construction Tick to indicate the following key installation details have been adhered to There is adequate ventilation and airflow around the refrigeration unit If adequate airflow is not available a suitable heat extractor has been installed The room has been installed on a flat and level concrete surface as per the installation manual Room inspection has been performed O O OHOL The supplied roof supports have been used to support the room roof Operation Tick to indicate everything is operating correctly Airflow is unimpeded on the inside and outside of the room The refrigeration unit is operating correctly The door is seal
6. Installation Manual 10 SKOPE MISA Cool amp Freezer Rooms Parts Standard The following parts are required for a standard room installation Additional Room Parts parts may be required 2 N aay Parts list No Description 1 Floor panel Grey silver colour Tread side up 2 Fast fit insert Used to align panels quickly and correctly 3 Edge piece Used to create right angle corners 4 2 Way corner cap Used to join edge pieces 5 Wall Ceiling panel Standard panels are white Available in different sizes 6 Ceiling hanger Used to hang ceiling on top edge pieces on top of walls 7 Wall panel with door Plastic cap to cover cam lock holes White for walls and ceiling and silver for floor 9 Internal ramp used at base of door 10 Refrigeration unit 11 Bell alarm and internal light indicator Not pictured Plastic cover for interior corners 8 Cam lock cover Additional The following parts may be required in place of or in addition to the parts Parts listed above Preparation Installation Manual Additional parts list No item Description Fitted behind door to minimise cool air loss during door 12 Air curtain opening U Channel Not pictured For use with concrete floor room U Channel corner kit Not pictured For use with concrete floor room Edge piece joiner kit Not pictured Used to join edge pieces from end to end 3 Way corner kit Not pictured For use with mult
7. Installation Manual MAN10745 Rev 4 4 Mar 2014 MISA SKOPE MISA Cool amp Freezer Rooms SKOPE Refrigeration CONTACT SKOPE SKOPE INDUSTRIES LIMITED A B N 73 374 418 306 PO Box 7543 Baulkham Hills B C NSW 2153 Australia Freephone 1800 121 535 Fax 1800 121 533 E mail misa skope co nz Website www skope com INSTALLATION amp WARRANTY For installation and warranty enquiries please call SKOPE on 1800 121 535 MISA SKOPE MISA Cool amp Freezer Rooms Installation Manual MAN10745 Rev 4 4 Mar 2014 2013 SKOPE Industries Limited All rights reserved SKOPE Industries Limited reserve the right to alter specifications without notice SEKE E is a registered trademark of SKOPE Industries Limited CONTENTS Specifications 0 0 0 RR RII 4 Commissioning Installation Guidelines 2 0 6 Preparation Positioning the Room 0 0 ee eee 9 UNPACKING saura ee cao how TA ee rapie EUST 10 PartS og tee eed Beate ee ae ene oe on eg we eee 11 Installation Tools and Materials Required 0 0 0 0 0c eee eee 12 Fitting Parts Together 0 0 0 0 cece 13 Room Installation aaan aa aaa 14 Freeblock Refrigeration Unit 0 0 0 0 cee eee 19 ElectricS 2222 ee ee ee ee 21 Room INSBPECHON uua sack ara anna 23 Drop In Refrigeration Unit llle 24 5 Servicing Cleaning 25 OO 3 ere ae ee eee ee ee ee ee eee 25
8. Model eur o Supply capacity draw range C Volts Watts Amps MB7SF 27 MB13SF 2 7 MB16SF 5to 10 2 9 MB20SF 4 9 MB26SF 2 5 MB4NSF 2 7 MB9NSF 25 to 5 2 MB15NSF 4 1 Refer to the MISA Drop In specification sheet PSS0336 for detailed MISA Drop In specifications Specifications Installation Manual SKOPE MISA Cool amp Freezer Rooms 2 Commissioning Registration Compliance Ventilation Installation Checklist Warranty Installation Guidelines MISA cool rooms freezer rooms and drop in refrigeration units must only be installed by an approved SKOPE registered installer To register the installer must complete the SKOPE online registration form available on the SKOPE website www skope com SKOPE will confirm if the installer is approved as a SKOPE registered installer for MISA products The installer must follow the installation guidelines as set out in this MISA installation manual for the construction of MISA Cool and Freezer rooms All cool room panels and equipment supplied by SKOPE must be installed in accordance with all relevant laws regulations building codes and standards Building Codes SKOPE may provide information regarding aspects of the Building Codes but this is provided as general information only and does not detract from the installer s responsibility to ensure that all equipment is installed in accordance with the Building Codes The installer must check if the ins
9. act 2 amp 7 Door heater Electronic The MISA Freeblock refrigeration unit is fitted with electronic controller Controller Refer to the electronic controller documentation supplied with the refrigeration unit for further information Installation Installation Manual Installation Installation Manual SKOPE MISA Cool amp Freezer Rooms Room Inspection Once the room has been assembled and the refrigeration unit fitted inspect that the room is assembled correctly by shutting yourself inside the room If no light filters through the room is assembled correctly If light does filter through realign the panels to seal any gaps and check that the door is correctly fitted see page 25 After checking that the room is assembled correctly fit the plastic caps over the cam lock holes The white caps are for the walls and the silver caps are for the floor 23 SKOPE MISA Cool amp Freezer Rooms Safety Installation Drainage Ventilation Enclosures Power Supply Controller 24 Drop In Refrigeration Unit The following information applies to SKOPE MISA Drop In refrigeration units For information on SKOPE MISA Freeblock refrigeration unit installation refer to Freeblock Refrigeration Unit on page 19 If the room is supplied with a third party drop in unit or remote refrigeration system refer to the documentation provided with the drop in or remote refrigeration unit for further information When installing usin
10. ands from cuts o The unit is not suitable for use in explosive environments therefore the use of the unit in an explosion dangerous atmosphere is absolutely forbidden o The unit is not suitable for use in corrosive environments In such cases protect the condenser coil and evaporator coil with appropriate means n Servicing must be completed by trained personnel or manufacturer according to the provisions supplied by EN378 o When maintenance or servicing involves operations on the refrigeration circuit empty the system and allow it to reach atmospheric pressure n Do not discharge the refrigerant gas into the atmosphere Refrigerant gas must always be recovered by specialised technicians using suitable equipment n Quantity and quality of the refrigerant charge are indicated on the data plate n Do not use alternative refrigerants especially inflammable fluids e g hydrocarbons or air Do not modify or alter the refrigerating circuit or its components n The unit shall only be used following the instructions indicated by the supplier Any incorrect use can result in damage to the unit and represents a serious danger for peoples health 19 SKOPE MISA Cool amp Freezer Rooms Drainage Ventilation amp Condenser Air Extraction Power Supply 20 Installation o The user shall protect the system from external fire hazards o The user is strongly recommended to contact the manufacturer before attempting an
11. block units are connected to a suitable circuit as required as specified on the unit rating label The door switch cable is wired up to a door switch located above the door The door switch must be fitted to freezer rooms and is optional on cool rooms If not being used the door switch should be left open circuit A light kit is supplied with the room and must be fitted Australian standards require the light and light switch to be fitted inside the room and the indicator light fitted outside the room The indicator light illuminates when the interior light is on The light should be mounted inside the room under the evaporator or on the ceiling The light switch should be mounted inside the room next to the door The light indicator should be mounted beside the door on the outside of the room A licenced electrician must be used to wire up the light light switch and light indicator see diagram below Legend No Description 1 Refrigeration unit 2 Room 3 Interior light 4 Indicator light 5 Light switch 21 SKOPE MISA Cool amp Freezer Rooms 22 Door Heater The door heater wires are located behind inside the door panel around the Wiring door opening The door heater electrical box is fixed to the door panel and can be removed by undoing the fixing screws Refer to the wiring diagram below for door heater wiring details Legend No Description 1 amp 8 Power supply 3 amp 4 Heater valve 5 amp 6 Remote cont
12. e hard wired to a 20 Amp circuit with isolation switch and that 3 phase Freeblock units are connected to a suitable circuit as required as specified on the unit rating label SKOPE MISA Cool amp Freezer Rooms Unpacking The room is supplied in two packs The first pack contains all the parts required to build the room and the second pack contains the SKOPE supplied refrigeration unit where applicable Freeblock refrigeration unit pictured It is not necessary to unpack the refrigeration unit until the room has been built f JOH WE if To unpack the room 1 Open the first pack containing the room parts Keep the strapping and wooden cross piece as they are required to assist with removal of the refrigeration unit 2 Lift the door from the top of the pack Ensure the door is kept upright to avoid potential misalignment 3 Remove the box from the pack The box includes small parts 4 Remove the plastic film from the edge pieces 5 Lay the remaining parts out on the ground Start with the edge pieces then the wall panels and then the ceiling and floor panels To unpack the refrigeration unit 1 Remove the cover from the crate 2 Retrieve the strapping from the first pack and thread it through the hook on top of the refrigeration unit Tie into a secure knot to form a loop 3 Insert the wooden cross piece into the loop and lift the Freeblock refrigeration unit from the pack Preparation
13. g maintaining or servicing the Drop In refrigeration unit follow the safety and service guidelines on page 18 The SKOPE MISA Drop In refrigeration unit is designed to be located on top of the cool freezer room Follow the instructions supplied with the Drop In refrigeration unit Once installed have the Drop In refrigeration unit commissioned by a licenced technician before initial start up Although the unit has its own condensation tray high heat and humidity may cause the tray to overflow To compensate for this the Drop In refrigeration unit must be installed with a drain connection to a waste outlet There must be adequate ventilation and airflow around the Drop In refrigeration unit Poor ventilation will void the warranty The unit condensing temperature must not exceed 45 C If adequate airflow is not available mechanical air extraction must be used Mechanical extraction of condenser air into ceiling space or preferably out of the building is advised If the Drop In refrigeration unit is enclosed the enclosure must have an air intake grille and the ceiling above must have adequate extraction to the outside of the building This must be in place prior to room installation and should be done based on the installer recommendations This work is not the responsibility of SKOPE or the SKOPE approved installer We recommend that single phase Freeblock refrigeration units are hard wired to a 20 Amp circuit with isolation switch and tha
14. hole on one of the parts Floor panel room part Lt cm Cam lock 910 3 Er tool Cam hole Edge piece room part 2 Rotate the tool clockwise to lock the room parts together 13 SKOPE MISA Cool amp Freezer Rooms Room Installation The steps below detail installation of a standard four sided cool room Before installing ensure the site has been properly prepared The room should be built in place not moved into place after installation Ensure the room sits on a level surface There must be no more than 5mm difference between each end of the floor Level flooring prevents panel misalignment and ensures that the door shuts and correctly seals IMPORTANT Ensure the room is installed on a level surface Standard MISA The steps below apply to rooms with a standard MISA floor If installing a Floor floor less or set down room refer to the steps on the next page To install a standard MISA floor 1 Lay the floor panels into position according to the plan The textured tread side of the panels should face up 2 Apply a bead of silicone between the floor panels 3 Align the floor panels with fast fit inserts 4 Lock the floor panels together with cam locks 5 Check the floor is level and in the correct position 6 Apply a bead of silicone approximately 20mm out from the floor perimeter on the ground surface 7 Use fast fit inserts to align the floor panel edge pieces around the floor pa
15. ing correctly adjust door if necessary C Heater element s are operating correctly freezer rooms only Please record the following information and tick the boxes once installation has been completed and the room powered up for the first time Note Any issues or irregularities must be investigated and rectified to specifications Ambient air on air onto condenser must not exceed 43 C The ambient air on temperature at condenser when first powered up after 15 minutes after 30 minutes after 60 minutes Unit current draw Amps Power supply _ 240V single phase 415V three phase
16. iple cell rooms Not pictured For use with freezer rooms 11 SKOPE MISA Cool amp Freezer Rooms L Installation 12 Cam Lock Tools Mastic Tools and Materials Required The following tools and materials are required for a standard room installation Additional tools and materials may be required Tools list Item Description Cam lock tool Used to lock panels and panel edges together Silicone Used to seal panels and panel edges Mastic Recommended for wall panels in hot humid areas Knife Unpacking Gloves To be worn during installation Two cam lock tools are supplied One is for use with the room to lock panels and panel edges together supplied with room and the other is used to lock the MISA Freeblock refrigeration unit into place supplied with MISA Freeblock refrigeration unit Do not apply more than 1 5kg of pressure on the tools when locking the cams Excessive pressure will damage cam locks IMPORTANT Do not apply more than 1 5kg of pressure on the cam lock tool when locking the cams The room cam lock tool is suitable for use m with 60mm panels and requires modification for use with 100mm panels To modify the cam lock tool for use on both 60mm and 100mm panels remove the sleeve from the pointed end of the tool Sleeve Pointed end Room cam lock tool The cam lock tool can also be used to assist with moving panels Insert the tool into the cam holes and use the tool as a handle to
17. lift and manoeuvre panels see image below Cam hole Door panel Silicone and Silicone should be used to ensure secure attachment and to keep moisture and grime from out of small gaps and spaces Mastic should be used in areas with high heat and humidity Installation Installation Manual Fast Fit Inserts Panel Cam Locks Installation Installation Manual SKOPE MISA Cool amp Freezer Rooms Fitting Parts Together Panels and edge pieces are fitted together using fast fit inserts panel cam locks and sealant in between panels and end pieces Fast fit inserts are plastic plates which slot into the edges of panels and edge pieces One fast fit insert should be used on every second cam lock Fast fit insert Fast fit insert in place Fast fit inserts ensure correct alignment and assist with locking the panels together As a general rule a fast fit insert should be used on every second slot where practical Cam locks are built into floor wall and ceiling panels They cannot be removed or replaced The cams move through three stages when locking open closed and locked A hook extends out from the cam when rotated fits into the slot on the aligned room piece and pulls in to seal the two pieces together Do not apply more than 1 5kg of pressure on the tool when locking the cams Excessive pressure will damage the panels To lock the cams 1 Align two room parts and insert the pointed tip into the cam
18. m locks Ensure the top edge of the edge piece is level with the top of the wall panel 3 Fita second corner wall panel to create a right angle Use fast fit inserts to align and lock in place with wall panel cam locks Continued over page Installation 16 Installation Manual SKOPE MISA Cool amp Freezer Rooms 4 Continue fitting back and side wall panels working from the back towards the front of the room Use fast fit inserts to align wall panels correctly and lock in place with cam locks Note Rooms fitted with MISA Freeblock refrigeration unit will include a shorter panel The refrigeration unit is installed above this panel Vz 5 Fit the top edge pieces on top of the back and side walls 6 Slot the ceiling support brackets into the edges of the ceiling panel s T Lift the ceiling panel s onto the room walls hang using the ceiling supports and lock into place If fitting multiple ceiling panels fit the rear panel first and work forward 8 Fit the front of the room If the door panel makes up a corner start with this If the door panel has wall panels on either side start from one side and work across Do not fit the door panel last Continued over page Installation 47 Installation Manual SKOPE MISA Cool amp Freezer Rooms 9 Fitthetop edge piece s on top of the front wall 10 Slot a 2 way corner cap into each corner of the ceiling 11 Fit a corner insert i
19. nel perimeter see page 13 8 Lock floor panel edge pieces to the floor panels with cam locks page 13 Continued over page Installation Installation Manual 14 SKOPE MISA Cool amp Freezer Rooms 9 Silicone and slot a 2 way corner cap into each corner of the floor The corner cap edges slide under the floor edge pieces for a tight fit Floorless The room can be installed directly onto a concrete surface without using Room MISA panel flooring U Channels are used to support the wall panels The Installation U Channel frame must be bolted in place and sealed with silicone prior to fitting the wall panels Freezer rooms without a MISA floor must be installed onto insulated concrete U Channel rooms must always be installed by a qualified technician IMPORTANT Freezer rooms without a MISA floor must be installed onto insulated concrete Follow the steps below to install the U Channel floor frame To install the U Channel frame 1 Mark out the room on floor according to plan with a chalk string line Ensure the line is square and correct 2 Lay out the U Channel corners as pictured 3 Lay the U Channel lengths on the chalk line The lengths will need to be cut on one end to fit 4 Check to make sure all sides are square The easiest way to do this is to measure the diagonals from corner to corner the measurements must be mm perfect 5 Silicone and fix the back and sides not the door fron
20. nment and Door lock amp Gasket Alignment below Door Ifa door is out of alignment follow the steps below to realign it Alignment 1 realign the door 1 Open the door and remove the top door hinge cover 2 Close the door and loosen the two adjustment screws 3 Move the top of the door left or right as necessary to align correctly 4 Once the door is correctly aligned tighten the two adjustment screws and refit the door hinge cover Servicing 8 Installation Manual SKOPE MISA Cool amp Freezer Rooms Door Lock amp The door lock can be adjusted to ensure the door closes and gasket seals Gasket on the door opening If the gasket is not sealing correctly follow the steps Alignment below to adjust the door lock as necessary To realign the gasket 1 Open the door and use a small screwdriver to unclip and remove the door handle cover from the inside of the door Loosen the two adjustment screws Move the lock section of the handle in or out as necessary to align correctly Once the door is correctly aligned tighten the two adjustment screws and refit the door lock cover Door Heater The door heater wire runs around the perimeter of the door opening Refer Wire to page 22 for wiring information Follow the steps below to access the door heater wire To access the door heater wire 1 2 26 Ensure the refrigeration unit is isolated from the power supply Open the door Remove
21. nto each corner inside the room 12 Fit the ramp inside the room at the bottom of the door frame Drill holes as necessary and fix in place with supplied fixing screws 13 If supplied fit the air curtain to the top of the door frame Light amp Bell A light and bell alarm kit is supplied with the room and must be fitted Alarm Kit Australian standards require the light and light switch to be fitted inside the room and the indicator light fitted outside the room The indicator light illuminates when the interior light is on The door safety bell should be fitted to the door fitting instructions are included with the bell The light should be mounted inside the room under the evaporator or on the ceiling The light switch should be mounted inside the room next to the door The light indicator should be mounted beside the door on the outside of the room A licenced electrician must be used to wire up the light light switch and light indicator see page 21 for more information satiation Installation Manual Introduction Safety and Service Guidelines Installation Installation Manual SKOPE MISA Cool amp Freezer Rooms Freeblock Refrigeration Unit The SKOPE MISA Freeblock side mount is a wall mounted refrigeration unit which is easily positioned and locked onto the side of the room using the supplied cam lock tool The standard opening size for the refrigeration unit is 800mm wide x 400mm hign The follo
22. pecially to ensure children do not play with it Do not use this appliance for other than its intended use Do not cover the grilles or block the entry or exhaust of airflow by placing objects up against the refrigeration unit Do not close in or cover the refrigeration unit Do not probe any opening Only use this appliance with the voltage specified on the cabinet rating label Ensure the appliance has adequate ventilation as this is essential to economical high performance Be careful not to touch moving parts and hot surfaces For your own safety and that of others ensure that all electrical work is done by authorised personnel Ensure all necessary safety precautions are observed during installation or removal of the refrigeration unit Do not store explosive substances such as aerosol cans with a flammable propellant in this appliance Please contact SKOPE Customer Services for advice regarding disposal of this appliance WARNING Always disconnect the refrigeration unit from the mains power supply before cleaning or maintenance CAUTION Never overload the power supply which could damage the appliance and product See the rating label for the safe power supply and current draw CAUTION There must be adequate ventilation and air flow around the Freeblock refrigeration unit The ambient temperature around the condenser must not exceed 43 C A poorly ventilated Freeblock refrigeration unit may overheat
23. rom neighbouring bedroom windows office windows multiple walls and corners Ensure the room sits on a level surface There must be no more than 5mm difference between each end of the floor Level flooring prevents panel misalignment and ensures that the door shuts and correctly seals IMPORTANT Ensure the room is installed on a level surface If the room is being installed without a MISA floor additional site preparation such as floor surface preparation should be completed prior to room installation Freezer rooms without a MISA floor should be installed onto insulated concrete External cold and freezer rooms are not permitted unless an approved enclosed access is provided There must be adequate ventilation and air flow around the Freeblock refrigeration unit Poor ventilation will void the warranty The ambient temperature around the condenser must not exceed 43 C A poorly ventilated Freeblock refrigeration unit may overheat Mechanical extraction of condenser air into ceiling space or preferably out of the building is advised This appliance must be installed in accordance with the relevant electrical wiring rules and regulations AS NZS 3000 A suitable isolation switch acting in all supplies must be incorporated in the fixed supply wiring Refer to the rating label for power supply requirements The rating label is located on the Freeblock refrigeration unit We recommend that single phase Freeblock refrigeration units ar
24. t of the U Channel frame to the ground with concrete plugs 6 Cut the front U Channel frame piece into two pieces to allow for the door opening To calculate the door opening size measure the overall size of the door frame and add 24mm 12mm each side for door trim For example if the door is 800mm wide the cut out opening size should be 824mm Continued over page Installation ag Installation Manual SKOPE MISA Cool amp Freezer Rooms 7 Make a 30mm x 30mm square cut to each side of the front of the U Channel door side to allow the door bottom gasket seal to close on the face of the curved U Channel 8 Silicone and fix the two front pieces of the U Channel frame to the ground with concrete plugs 9 The room can now be assembled Use mastic inside the U Channel and slot the wall panels into the U Channel Walls and Use the supplied plan to piece together different sized wall and ceiling Ceiling panels Due to variance of room configuration and or the place of installation it may be necessary to reorder these steps For example the ceiling may need to be moved into position prior to fitting all walls due to limited space above the room or the door maybe fitted on a side wall rather than a front wall To install the walls and ceiling 1 Starting at the back wall fit a corner wall panel and lock into place 2 Fit a wall panel edge piece Use fast fit inserts to align and lock in place with wall panel ca
25. t 3 phase Freeblock units are connected to a suitable circuit as required as specified on the unit rating label Refer to Electrics on page 21 for more information Refer to the rating label for power supply requirements The rating label is located either on the cabinet interior or on the Freeblock refrigeration unit The electronic controller control panel should be located beside the room door Installation Installation Manual SKOPE MISA Cool amp Freezer Rooms 5 Servicing Cleaning Room Periodically wipe the inside and outside of the room with a damp cloth Use neutral or slightly alkaline detergent and rinse and dry the panels after cleaning Isolate the refrigeration unit from the power supply when cleaning around electrical components Condenser To ensure trouble free performance the condenser coil must be kept clean Coil We strongly urge monthly cleaning with a soft brush to remove dust and fluff and a thorough cleaning every six months The condenser coil must be kept clean for efficient and reliable operation Always isolate the refrigeration unit from the power supply when cleaning the condenser coil Door Door Seal To ensure the room operates correctly and efficiently the door must close and seal correctly To check this enter the room and shut the door No light should filter around the door opening If light is filtering through check the door and gasket for alignment and adjust as necessary see Door Alig
26. tallation is within the tropical zone which includes everywhere north of Byron Bay Queensland If the installation is within the tropical zone the installer must consider the tropical environment which may require under floor heater wires or other additions The installer must ensure all electrical and refrigeration work is carried out by licensed technicians The installer must ensure adequate heat extraction and ventilation is in place If not in place the installer must advise the customer of requirements and advise to have ready and in place for installation The installer not SKOPE is responsible for ventilation of the refrigeration equipment Installation must be completed in accordance with the MISA installation manual provided by SKOPE The installer must obtain an accurate MISA room plan from the customer prior to beginning an installation The installer must carry out a site inspection prior to confirmation of room order to ensure adequate ventilation of the refrigeration unit and correct dimensions and placement of the room and refrigeration system After the room has been installed the installer must complete the MISA installation checklist found on the back page of this manual A completed copy of the checklist must stay on site and a copy sent to SKOPE Subject to the conditions and exclusions set out in the SKOPE Warranty Terms http www skope com support warranty and provided that the installation is completed by
27. wing information applies to SKOPE MISA Freeblock side mount refrigeration units For information on SKOPE MISA Drop In refrigeration unit installation refer to Drop In Refrigeration Unit on page 24 If the room is supplied with a third party drop in unit or remote refrigeration system ceiling or wall panels will need to be cut to fit the refrigeration unit If it is necessary to cut into the panels ensure measurements are correct before cutting and take care when cutting as the panels are delicate Do not cut through cam locks Ensure that the ceiling panels have adequate support for the refrigeration unit If more ceiling support is required hangers on wires attached to the cool room roof can be used The wires can be attached to either the building internal roof beam s Or alternatively a strengthening beam or plate can be installed across the top of the room to support the refrigeration unit Refer to the documentation provided with the drop in or remote refrigeration unit for further information IMPORTANT The refrigeration unit is heavy and requires two or more people to lift When installing using maintaining and servicing the Freeblock refrigeration unit follow the safety and service guidelines below n Installation must be carried out in strict compliance with the diagrams and instructions supplied by the manufacturer Electrical connections must meet all relevant safety standards Use safety gloves to protect your h
28. y intervention on the unit and any use not corresponding to the manufacturers directions in particular the field of application Please enquire about the possible dangers connected with improper use of the unit Note Damages due to improper connections void any warranties Although the unit has its own condensation tray high heat and humidity may cause the tray to overflow To compensate for this the Freeblock refrigeration unit must be installed with a drain connection to a waste outlet There must be adequate ventilation and or extraction for air flow around the Freeblock refrigeration unit Poor ventilation will void the warranty The ambient temperature around the condenser must not exceed 43 C A poorly ventilated Freeblock refrigeration unit may overheat Mechanical extraction of condenser air into ceiling space or preferably out of the building is advised We recommend that single phase Freeblock refrigeration units are hard wired to a 20 Amp circuit with isolation switch and that 3 phase Freeblock units are connected to a suitable circuit as required as specified on the unit rating label Refer to Electrics on page 21 for more information Refer to the rating label for power supply requirements The rating label is located either on the cabinet interior or on the Freeblock refrigeration unit Follow the steps below to install the Freeblock refrigeration unit To install the refrigeration unit 1 Carefully lift the
Download Pdf Manuals
Related Search
Related Contents
CVNC -M5 User Guide - John J. Jacobs BEAT6 USB - user manual COMPLETE DeVilbiss SB-E2-360-J User's Manual MODE D`EMPLOI - Exile Investissements Bedienungsanleitung zu Audiolab 8200 CDQ - Hi English-US Operating instructions 酸化エチレン処理技術 液化炭酸株式会社 Super Star Super Star X-treme Super Rake Super Star 48V Operating Manual iSOLATE501 Copyright © All rights reserved.