1. 37239 NSE for freeing tubes from rubber seal Used on lt RUBBER TUBE STAY 33335 L and SY for staggered MESABI Cores only 39292 SS RUBBER TUBE STAY END PIECE F 33085 V style S for staggered Cores only 39300 cores SSS BOTTOM FELT AIR BAFFLE 33083 NE core width SG RUBBER SEAL LOCKING GROOVE 4 see chart and section view below SS 2 BOTTOM HEADER PLATE bolted S RUBBER PLUG ssssccsssssesssssessssesssssessssesessueeesssesenseeensnes 96630 Note Plugs are for temporary plugging of ferrule holes until replacement tubes can be installed Plugs must be installed dry and are not recommended for systems operating over 15 P S I ST AY INSTALLATION 48350 for removing and installing tubes Used on L style cores W ITS Tube Installation Tool P N 77050 See page 6 gt lt Figure 8 5 22 14 Used HEADER PLATE HOLE SEAL AND TUBE END M style CLEANING BRUSH P N 99785 LUBE BRUSH P N 63451 cores If you are not sure of your core style contact L amp M Customer Service Core Style Top Bottom Lube P N Seal Seal LOCKING STAY GROOVE SEAL U sed on P N 87530 or P N my WB must be used style at the bottom The cores tube bead will
2. 103 kPa and submerge in water 2 Seal any leaks at the test fittings and or cover plates 3 Repair any other leaks as needed 4 Cycle test after successful initial test Hold pressure at 15 psi 103 kPa for 15 minutes Note that the time starts after all leaks are fixed and air bubbles have subsided Cycle to zero psi and pressure back up to 15 psi 103 kPa Hold at 15 psi 103 kPa for one minute Repeat three more times and then hold the last cycle pressure at 15 psi 103 kPa for five minutes Should any leaks appear fix them and start the cycle test over If you have any questions regarding the procedures described in this Service Manual please contact L amp M Radiator and ask for Customer Service See back page for contact information VIC F D P eb 1 L amp M RADIATOR FACTORY DIRECT SALES AND SERVICE Because so many of our radiators and heat exchangers are a custom design all sales are on a factory direct basis This assures that our customers receive a product that meets their cooling heating requirements offered to them at the least possible price We ship most parts within 24 hours On site technical and engineering assistance is available almost anywhere in the world within a few days notice Manufactured and distributed by L amp M Radiator Toll Free 800 346 3500 U S A and Canada Web Site www mesabi com Email cool mesabi com L amp M Radiator Inc L amp M Radiator
3. FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED IN NO EVENT WILL L amp M S LIABILITY INCLUDE ANY SPECIAL INCIDENTAL CONSEQUENTIAL OR PUNITIVE DAMAGES EVEN IF L amp M KNEW OF THE LIKELIHOOD OF SUCH DAMAGES Any action or lawsuit for breach of the limited warranty in these L amp M terms and conditions must be commenced in Minnesota This warranty supersedes all previously published warranties MESABI PRODUCT SPECIFIC WARRANTY Covers e Radiators e Cores Air To Air Coolers e Low Pressure Oil Coolers amp Fuel Coolers maximum 50 psi 345 kPa In addition to the MESABI General Warranty L amp M Radiator further warrants the MESABI heat exchangers listed above against seal leakage during normal operation for 48 months from date of invoice MESABI is a registered trademark of L amp M Radiator Inc and ITS is a trademark of L amp M Radiator Inc Standard Parts of a Typical Radiator Core Tube Styles Exploded view of a typical O Se x lt J Sold As Assemblies Only MESABI water jacket p 22 NN r DESCRIPTION NO S32 ITS Additional SS 2 TOP HEADER PLATE bolted Individual Q TOP RUBBER SEAL see chart below SH TOP FELT AIR BAFFLE 33082 Tube 57 core width Suppo rt S35 BREAKER
4. Inc Hibbing Minnesota U S A Independence lowa U S A L amp M Radiator Inc L amp M Radiator Inc El Paso Texas U S A Yankton South Dakota U S A 5 tne wortd Stan jard hanger reuiabitity L amp M QUALITY POLICY The Quality Policy of L amp M Radiator is to produce a quality engineered guality manufactured product through continuous improvement that we deliver to the customer s satisfaction WORLD HEADQUARTERS L amp M Radiator Inc 1414 East 37th Street Hibbing Minnesota 55746 U S A Telephone 218 263 8993 ISO 9001 2008 Fax 218 263 8234 ceatiriep L M de Mexico S A de C V L amp M Radiator Pty Ltd Calle De La Plata y Los Nogales Cnr Kew amp Kathleen Streets Parque Industrial Welshpool Western Australia 6016 Hermosillo Sonora Mexico Telephone 61 8 93616855 Telephone 011 52 662 251 0480 Fax 61 8 94703075 Fax 011 52 662 251 0638 Email cool mesabi com au Email ventas lym com mx MESABI and RTTS are registered trademarks of L amp M Radiator Inc System Protector BOSS V Tube Core CSC and Captured Seal Cooler are trademarks of L amp M Radiator Inc Copyright 2008 L amp M Radiator Inc
5. M P N 48350 This tool has a semicircular form on the end of the handle Place this end on the formed bead of the tube and push F downward tk a until seated as a be shown Fig 7 Now complete the row of tubes Precaution should be taken to make sure formed bead is seated into bottom seal and that the tubes are straight and aligned to assure maximum air flow If you are working with an ITS system refer to page 3 and page 7 Fig 9 for identification use L amp M tube installation tool P N 77050 to pull the tube into the bottom seal See Fig 8 Hook the slotted end of the tool behind the front tab on the ITS tube support Using the tool and your free hand center the bottom end of the tube into the bottom seal At the same time guide the dovetail slots into the tabs on the ITS tube support Once in place and with the tool P N 77050 still hooked onto the ITS tube support pull the tube into the bottom seal until the formed 2 9 bead is seated into the locking groove of the bottom seal Push the remaining tubes in this row Use the same procedure on all remaining rows except the front side row Tube Installation continued STEP 2 CONTINUED Tube Support Orientation All illustrations front side as viewed from top A ITS can be used on H L or V style cores Make sure the tabs on the ITS tube supports are facing to the front and to the right FRONT FRO
6. first It is important to start on the air exit side Work from the top to the bottom Concentrate on small areas and work slowly Wash until the water exiting the opposite side is free from dirt and debris Complete this side and then repeat the process from the other side EPOXY COATED CORES Epoxy coated cores must be cleaned with care to assure the coating is not damaged 1 A high pressure hot water washer can normally be used Use a fresh water supply Water temperature should not exceed 180 F Do not steam clean The nozzle should be kept approximately 12 inches away from the core CAUTION We do not recommend a pressure rating because as epoxy ages the coating does become brittle and might be damaged at higher pressures We recommend that you try your cleaning method on a portion of a single tube first 2 Wash the core thoroughly and methodically starting at the top and working towards the bottom Do not wash in one area for extended periods The core will be clean when the water exiting the core Is clean 3 Blow off excess water with air Epoxy coatings are not meant for submergent duty L amp M Radiator does not warrant against corrosion but this coating properly cared for will help increase the service life and efficiency of your cooling system INTERNAL CLEANING In most cases just flushing the inside of the tubes with a high pressure hot water washer with soap will do the job Rinse thoroughly with clea
7. hot water just prior to installing e Make sure you use proper seal part number See Seal amp Lube Chart on page 3 With your thumb start the new MESABI seals into the holes and push them part way in Care must be taken not to install seals too far into the header plate A properly installed seal has a crowned or convex top surface and the tube hole is slightly flared at the opening A seal that is installed too far into the header has a concave top surface and the tube hole is noticeably smaller in diameter as shown in Fig 5 Over installed seals will make tube installation more difficult and are much more likely to be damaged during tube installation The use of a hammer directly on the seal can easily cause seals to be installed too far into the header plate L amp M recommends the use of a flat plate 3 8 x 3 x 6 placed over the seals Hitting with a rubber mallet will allow the seals to be properly installed ON THE LEFT Properly installed seal RIGHT Seal installed too far into header gt INCORRECT gt CORRECT Lubricating Seals and Tube Ends For ease of tube installation and to minimize the chance of scuffing or tearing rubber seals during tube installation both top and bottom seals and both tube ends must be thoroughly lubricated using L amp M lube see Seal amp Lube Chart on page 3 for proper lube part number Using a 1 2 diameter brush L amp M P N 63451 and a minimal amount of lu
8. MESABI Please read and follow instructions carefully before proceeding with any service work and or repairs Consult factory before proceeding with any possible warranty claims 2009 5 Radiator Cores Waranty scsctteasnunenncomadonccuucedevmastinteetiwaaaloneriaeacuarsas Page 2 Standard Parts amp TOOIS Page 3 External Cleaning Page 4 Epoxy Coated Core External Cleaning Page 4 Internal Cleaning Page 4 REMOVING TUDES Pages 4 amp 5 Cleaning Tube Ends Page 5 Installing Seals Page 5 OO FIC AIO MN Page 5 Installing TUDES Pages 6 amp 7 Pressure Testing Page 7 Manufacturing amp Parts Facilities Page 8 CONTACT L amp M S CUSTOMER SERVICE DEPARTMENT PRIOR TO REPAIRS WHERE WARRANTY CLAIM IS A POSSIBILITY FAILURE SO MAY VOID WARRANTY MESABI GENERAL WARRANTY Consult L amp M before proceeding with warranty claims or repairs Failure to do so may void this limited warranty This limited warranty allocates the risk of failure of the product s between the buyer and L amp M and is reflected in the purchase pr
9. NT C M Stay a j FRONT NOTE If you are working with an older stay style that has rubber tube stays see Exploded View page 3 and need assembly assistance please contact L amp M Customer Service STEP 3 Before you install the front side row install the felt air baffles Caution To prevent seal leaks do not allow the felt baffles to be pushed top or pulled bottom into the seal hole when installing the front row of tubes STEP 4 If applicable If you are working with the ITS or stay support system install the appropriate support bar as shown in Fig 10 T z 7 n gt t 2 2 5 4 1 A i Te P a The support bar part number has been stamped on the outside face Use the L amp M Radiator Technical Drawing and Parts List for proper installation Using a rubber mallet gently tap the bar into place and secure to the side member PRESSURE TESTING Pressure testing procedure that follows recommends testing to 15 psi 103 kPa You should test to pressure rating specified on tag attached to your cooler If there is no pressure rating specified please contact L amp M customer service with the part number of your cooler Caution Always bring air pressure up slowly and always wear protective gear 1 Pressurize with compressed air to 15 psi
10. bricant apply a thin film into each seal hole and onto each tube end Tube Installation CAUTION If a tube seems difficult to install into a seal STOP and figure out WHY One of the following reasons could be the answer 1 A tube or seal with inadequate lubrication 2 Improperly installed seal that could be pushed too far into the header plate hole 3 Damaged tube end 4 Trying to insert the tube into the seal at too steep of an angle 5 Tube is not centered in seal NOTE If for any of the above reasons a tube is difficult to install the seal should be removed and inspected for any scuffing marks tears or cuts If there is any doubt replace the seal HELPFUL HINTS f you are working with a center tank core the bottom core must be assembled before the top core e Minimize the angle of the tube as it s being installed into the top seal e Make sure the tube is centered in the bottom seal before any force is applied to pull or push into place e For ease of tube installation install the tubes behind the side member gussets in each row first Install the tubes behind the left side gussets working towards the core center Then going to the far right hole in the same row install the tubes working towards the core center e Individual rubber tube stays and in some cases tube stay ends are necessary to interlock the tubes For part numbers see page If more detailed information is required for pr
11. ice L amp M warrants that MESABI products will conform to L amp M s written quotation specifications and drawings MESABI framework components are warranted for 18 months from the date of invoice against defects in materials and workmanship during normal usage L amp M warranty against seal leakage during normal operation is stated in individual product literature L amp M s liability is limited to the rework replacement at L amp M s sole option of products parts manufactured by L amp M that are determined by L amp M to be defective in workmanship or material or do not meet L amp M s quoted specifications L amp M product warranty does not apply if the product has been subjected to abnormal use or conditions unauthorized modifications or repair corrosion misuse neglect abuse accident improper installation or other acts which are not the fault of L amp M including damage caused by shipping L amp M does not warranty products incorporated into L amp M products that are not manufactured by L amp M Buyer s sole recourse with respect to such products will be subject to the warranty of the individual manufacturer OTHER THAN AS STATED HEREIN L amp M MAKES NO REPRESENTATION OR WARRANTY OF ANY KIND EXPRESSED OR IMPLIED AS TO MERCHANTABILITY OR FITNESS FOR PARTICULAR PURPOSE OR ANY OTHER MATTERS WITH RESPECT TO THE SALE OF L amp M PRODUCT S AND ALL IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS
12. ing tabs the tube must be raised high enough so that the interlocking tab clears the adjacent groove as shown in Fig 4 Cleaning Tube Ends Before the original tubes are reinstalled the tube ends must be clean of foreign material L amp M recommends polishing the tube ends with a polishing wheel Grainger 5A725 use Qty 5 together and a copper polishing compound Grainger 769 If the debris cannot be removed by polishing L amp M recommends using a piece of fine grit emery cloth or steel wool If there is a lot of debris on the tube ends use a 6 or 8 diameter wire wheel brush with a wire size of 006 or 008 Larger diameter wire sizes could damage the tube ends Try installing a tube If it does not slide easily into the top and bottom seals try polishing the tube ends as per above Seal Installation HELPFUL HINTS L amp M recommends installing new MESABI seals when tubes are removed e After removing the old seals clean the plate holes of any foreign debris with L amp M P N 99785 header plate hole cleaning brush placed in an electric or air drill e Clean out inside of tanks and blow out plate holes with air e Install new seals in clean dry holes Do not apply any lubricant to header plate holes e the core has a center tank do not install seals at the bottom of the top core until all the tubes are installed in the bottom core e For ease of seal installation soak seals in
13. n water Tube Removal HELPFUL HINTS e Clean the core prior to removing tubes e To avoid bending or kinking tube ends reduce the angle of the tube as it s being pulled from the top seal e f the core has a center tank remove the top core tubes and seals first e f the core has an ITS Individual Tube Support or stay system with support bars mark the bars front and back before removing to ease reassembly e To assist in the removal process spray WD 40 on the top end of tubes e f tubes are difficult to remove try using the breaker tool and removal tool simultaneously STEP 1 Loosen the tube by using Breaker Tool L amp M P N 37239 as shown in Fig 1 The Breaker Tool should be placed at top or bottom not at middle when freeing tube from seal Lightly twist the tube back and forth to loosen tube from seals STEP 2 After tube is free place upper jaw of Installation Tool P N 48350 around the round portion of tube just below the flattened portion Place lower jaw on top of bottom seal see Fig 2 Squeeze handles of tool together and raise tube only enough to clear bottom seal Tube Removal continued STEP 3 Put down tool and swing tube out just far enough to allow it to be pulled down and out of its top seal as shown in Fig 3 Remove all tubes in the row repeating the above procedure If you are working with any of L amp M s ITS or stay systems with interlock
14. oper assembly of cores using tube stays and tube stay ends contact one of the L amp M manufacturing facilities listed on back page f your core style includes plastic tube supports see page 7 for ITS or stay orientation prior to starting STEP 1 To minimize installation angle tubes in any given row must be installed from the closest header plate edge Use a minimum of angle and a slight twisting pushing motion to push the top end of the tube into the top seal Push it far enough in so the bottom of the tube clears the top of the bottom seal If you are working with any of L amp M s ITS or stay systems you will need to insert the tube far enough into the top seal to allow clearance for the tabs to be aligned with the grooves when the tube is pulled down into the bottom seal See Figs 4 and 6 Please note that when ITS or stays with interlocking tabs and grooves are present the bottom end of the tube should be centered in the seal and then pulled down slightly into the seal so that the tabs engage the adjacent grooves NOTE See page 7 for ITS or stay orientation in the core STEP 2 Center bottom end of tube into respective seal in the bottom header plate Then push tube down and into seal until the formed bead is seated into the locking groove of the bottom seal This may be done by grasping tubes by hand and pulling the tube downward until seated or by using Installation Tool L amp
15. seat in the seal inner 35780 87530 35780 87530 Air to Air Oil Cooler and Locomotive can be any style of above F H L M V Tube Locking design Plate Cleaning STANDARD EXTERNAL CLEANING To maintain efficiency and assure maximum life of a MESABI Core reasonable care must be taken when cleaning Most radiator shops use a hot alkaline soap caustic soda or chemical additives in their boil out tanks which attacks solders If a MESABI tube is soaked in such a solution the solder bond between the finning and tube will be adversely affected If it is Known that the particular solution used is not harmful to solder then it will not hurt the solder used on the MESABI tube Be sure to completely rinse the cleaned tube core in clean water after removing from the boil out tank In most cases it may be best to blow out any dry dirt with a high pressure air gun prior to washing the core with a high pressure hot water washer For general external cleaning a high pressure hot water washer with or without soap can be used at pressures up to 1200 psi 8274 KPa CAUTION To prevent fin deformation you must stay a few inches away from the core and spray straight into the core not at an angle If the cooler is still in the machine you may have to use an offset angled nozzle so that you can spray straight into the core If there is any doubt try your cleaning method on a small portion of the core
Download Pdf Manuals
Related Search
Related Contents
DSC-W70 SERVICE PARTS MANUAL 602907 Miele DGC 5080 XL Installation - Billiger.de イメージアップキャラクター 着ぐるみの貸出について SLX-M131R取扱説明書 Télécharger le manuel utilisateur. Lincoln Electric IDEALARC CV-250 User's Manual Manual del propietario YTGas® 2006 Perú WS 6750 weather station user manual Technical Details Copyright © All rights reserved.