Operating Instructions Fire Alarm System EBL512

image

Contents

1. Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev 27 6 A Operating Instructions Fire alarm system EBL512 V2 6 x Sensors activating SERVICE signal H4 U6 Service signal is indicated by LED Service L12 The sensor week average value is below or over the service level respectively for one or more sensors Regarding the service signal levels see Planning Instructions chapter Service signal Menu H4 U6 is a list of the sensor s activating service signal NOTE Service signal is only information that the sensors have to be cleaned replaced soon The service signal has to be acknowledged see chapter Acknowledge SERVICE signal H8 S4 page 139 It is not possible to get a print out from menu H4 U6 According to chapter Access see page 86 L a list in which you can scroll Press Return to menu U6 If there are no sensors in the list menu U6 will be shown again Scroll or press Return to menu H4 Scroll or press Return to log off 115 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 27 7 Rev Event log H4 U7 Operating Instructions Fire alarm system EBL512 V2 6 x This is a list of events Type and number of events in the list etc can be set in Win512 see Planning Instructions and Win512 help From this menu it is possible to get a print out The events can be listed Via display See
2. The battery might be too old Cables fuses etc for externally placed batteries might cause a voltage drop Check adjust the rectifier power supply voltage 24 V DC Check the charging voltage over the battery respectively 13 5 13 8 depending on the actual charging step Check the voltage over a disconnected battery fully charged 63 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x gt 13 V In the New Zealand convention only The battery charging is turned off 60 minutes every 24 hour A battery voltage lt 24 4 V during these 60 minutes will generate a fault If a fault is generated it will automatically be Serviced after these 60 minutes FAULT Low main PWS control unit xx Mains voltage below 187 V AC Blown fuse 230 V AC or no voltage Rectifier voltage below 21 V DC Fuse F1 on the charger board 1557 1657 is blown FAULT Low voltage control unit xx System voltage lt 21 V DC Check adjust so that the rectifier output voltage is 24 V DC FAULT Low voltage output unit xxxxxx The external power supply s system voltage lt 21 V DC Check adjust so that the rectifier output voltage is 24 V DC FAULT Mains control unit xx The fault is activated 1 300 minutes after Loss of mains i e no 230 V AC Blown fuse 230 V AC Blown fuse F1 on Charger board 1557 1657 Battery charging
3. e On the second row a user definable text message that for fire alarm will be shown if programmed Example pre warning zone 123 address 45 within zone 123 Pre warning detector 123 45 user definable text message Example pre warning zone 123 Pre warning zone 123 user definable text message If more than one pre warning is generated the LEDs Alarms queued L2 are blinking and the pre warnings will be automatically scrolled each five seconds Pre warning is automatically reset see chapter Alarm reset page 50 15 2 Fire alarm The system can handle up to 15360 fire alarms Up to 512 fire alarms will be shown in the c i e display No more fire alarms will be shown until one or more of the 512 alarms are reset See also chapter Alphanumeric display LCD in EBL512 page 20 Regarding POINT 999 nn nn 00 29 99 see NOTE at the end of this chapter According to the EN54 2 standard in case of a fire alarm the following will happen e The buzzer in EBL512 sounds 0 4 sec each 0 4 sec 0 4 0 4 sec e LEDs Fire L1 are blinking 0 4 0 4 sec e Output for routing equipment Fire brigade tx and outputs type 4 routing equipment are activated See also NOTE below e Outputs for fire alarm are activated amp Outputs programmed for General pre warning and outputs programmed for the activated pre warning s Via Win512 can Point alarm presentation
4. P4 Reset fire alarm s P5 Evacuate i e turn on the sounders P7 Paper feed when a built in printer is available P8 Get access after logon to level 2 4 i e menus functions in the system NOTE In conjunction with a fire alarm the fire brigade personnel can use P8 without any access code to get access to the menu X1 to scroll through all the fire alarms e g see all point alarms From access level 1 the user can logon to access level 2 3 and 4 respectively See following chapters 23 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 7 3 Access level 2 From access level 1 the user can logon to access level 2 which gives access to the following menus H1 Perform monthly test H2 Disable or re enable H4 Present system status on display and printer U5 Show sensor values C3 Reset interlocking output C5 Re enable interlocking output H10 Change access code for daily duties access level 2 A door is open in one or more control units and or external Fire Brigade Panels See chapter Door open page 34 24 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 7 4 Access level 3 From access level 27 the user can logon to access level 3 which gives access to the followin
5. Fire brigade tx Reset Operation Evacuate Figure 2 The EBL512 front FBP upper dark grey part and CP lower light grey part The look might vary according to configuration convention etc e g English texts as in the figure See also chapter LED indicators and push buttons The fire brigade personnel use the FBP to take required operational control of the system and to see which alarm point zone s having generated fire alarm In the alphanumeric display LCD 2x40 alphanumeric characters the information displayed on the first row is depending on how many alarm points zones having generated fire alarm and also convention On the second row is a user definable text message shown if programmed for an alarm point or a zone The CP is to communicate with the system i e for commissioning monthly tests maintenance etc Access codes for different access levels are required A keypad is used to get access to the system a menu tree with main and sub menus and for different manoeuvres The CP has several system status LEDs 15 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 5 LED indicators and push buttons LEDs and push buttons can vary according to type and configuration convention country language See also Figure 2 page 15 LED indicators on the Fire Brigade Panel FBP LED indic
6. Operating Instructions Fire alarm system EBL512 V2 6 x Direction for communication on COM BS4 loop H5 A3 The communication direction is normally automatically changed 28 4 every minute to ensure that the wires are okay all the way To make trouble shooting easier e g during the commissioning it is possible to lock the communication on a COM or BS4 loop in one direction FAULT No reply techn no xxxxxx will be generated with a reduced delay time This function can be used to list all technical numbers behind a loop cut off NOTE since they require communication in both directions at the same time The locking only works as long as you see the text Loop cut off and short circuit faults can not be generated COM loop is currently communicating in A direction alternatively B direction in menu A3 When you log out or if you are automatically logged out after 60 min the communication will start in the A direction Access According to chapter Access code for service H5 see page 120 Scroll to menu A3 Direction for communication on COM BS4 loop ACCEPT A3 Press A or 1 and A to accept O COMB SA ACCEPT Select type of loop 0 Lock COM loop Controll unit Write loop number board ACCEPT number and control unit number Press A to Lock direction on BS4 loop accept Board 0 Control unit 00 ACCEPT Mightbe the B direction is shown instead COM loop
7. Panasonic Operating Instructions MEW01165 Revision Fire Alarm System EBL512 V2 6 X Author Jan Pettersson Date of issue 2009 03 12 Date of rev This page has deliberately been left blank Panasonic Electric Works Fire amp Security Technology Europe AB Operating Instructions Fire alarm system EBL512 V2 6 x MEWO01165 Rev Table of contents 1 Introduction 2 Definitions Explanations 2 1 PEWF amp STE AB 22 Alarm points 2 2 1 2 2 2 2 2 3 2 2 4 2 25 2 2 6 2 2 7 2 2 8 2 2 9 2 2 10 2 2 11 Smoke detector Sensor Analog detector Analog Sensor Base ASB Conventional detector Conventional Detector Base CDB Addressable Detector Base ADB Addressable Old detector Conventional zone line input External line ADB input Addressable zone interface 2 3 Output unit 2 4 Output Control output 2 5 Short circuit isolator ISO 2 6 Display unit DU Del COM loop 2 8 BS4 loop 2 9 Control Unit C U C LE 2 10 Fire Brigade Panel FBP 2 11 Control panel CP 2 12 System 2 13 Network TLON LonWorks Echelon Node TLON Conn board Gateway Sub net Backbone net Router Repeater 10 2 14 LED 2 15 External Indicator LED 2 16 Display LCD 2 17 Door open Door Key switch 2 18 Site Specific Data SSD 2 19 Software S W System program 3 Overview 3 1 The EBL512 system 3 1 1 3 1 2 3 1 3 Expansion boards Printer Powe
8. Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 32 2 Activate interlocking output H9 C2 The output in each interlocking combination area point can be manually activated via this menu The corresponding interlocking input will be monitored in the same way as if the output was activated by its control expression Reset has to be performed via menu H9 C3 Access According to chapter Access see page 86 _ i Scroll to menu C2 Write the area and point Press A to accept and or Return to menu C2 Scroll or press Return to menu H9 Scroll or press Return to log off 149 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 32 3 Reset interlocking output H9 C3 All activated interlocking outputs are listed in this menu Interlocking output activated via its control expression and with latching output not selected The output can be reset via this menu Interlocking output activated via its control expression and with latching output selected in Win512 The output has to be reset via this menu Interlocking output activated via menu H9 C2 The output has to be reset via this menu Interlocking output activated via Web server II The output has to be reset via this menu Access According to chapter Ac
9. Perform the test as quickly as possible since the output s for routing equipment fire brigade tx are disabled also the parts of the zones in test mode not visible for the test personnel are disabled In order to shorten the testing time any time delay for the detectors zones in test mode will be disabled i e fire alarm will be detected faster than normally In the tested alarm point the LED will light up and the LEDs Fire L1 in the C U will light up about ten seconds then the alarm point will be automatically reset The printer if available will print out every tested alarm point Zone xxx Address xx Time HH MM A sensor in test mode will not be able to activate fault 132 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x After 60 minutes or r 1 1 L You are no longer in menu Return H7 but still in test mode Return When required Zo n TES Press A to end the test Access code id CCEE mode Scroll to menu H7 A The LED Test mode is turned OFF If more zones are to be tested continue as above If not scroll or press Return to log off NOTE During the test the following information will be shown in all other c i e displays Zones in test mode 001 002 003 004 In DBI Danish convention only one zone NOTE_2 If an alarm point e g a manual call point is in a
10. page 20 NOTE The inside switch has no function if the outside switch see below is activated ON 28 G When more than one fire alarm is activated Including Addressable siren 3377 and Addressable sounder base 3378 27 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 8 2 New Zealand FB Silence switch outside switch NOTE The functions in this chapter are valid for the New Zealand convention only The New Zealand FB Silence switch is also called the outside switch since it is placed outside the c i e The outside switch is a key switch connected to a programmable input with the trigger condition New Zealand FB Silence switch The outside switch can be in two states The outside switch is turned ON i e from not activated to activated state e All programmable outputs of type Alarm devices are disabled i e they can not be activated The inside switch se above has no function e LED s Fire on the front changes from blinking to steady continuous e The c i e built in buzzer is silenced e A fault is generated FAULT FB Silence switch active The outside switch is turned OFF i e from activated to not activated state e The fault FAULT FB Silence switch active will be Serviced e Any alarm point zone in fire alarm state will automatically be dis
11. Control Unit XX 00 29 for different languages e g DD MM YYYY hh hours e g 21 mm minutes e g 45 ss seconds e g 45 Bottom second row The information on the bottom row 40 characters can be created via Win512 i e it is user definable LCD backlight When the information above is shown in the LCD the backlight is OFF As soon as any other information see below is shown in the LCD the backlight is turned ON The information on the top row 40 characters is included in the text file downloaded in EBL512 i e the information could be different than the one showed above 20 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x In order to reduce the current consumption the LCD backlight will be turned OFF if the c i e is powered only by the second power source i e the battery 6 1 3 The LCD information priority order The different type of alarms faults etc listed below are described in other parts of this document The LCD information priority order is as follows 1 Fire alarms Normal fire alarms Heavy smoke heat alarms and Key cabinet alarms Co incidence alarms Pre warnings Quiet alarms Normally used on the Australian market only AAF zone alarms Used in the Australian convention only Di OV a eS Evacuate information only valid in some conven
12. FAULTS H6 page 132 there is a 5 minutes delay before a new key cabinet fault can be generated again Alarm Acknowledgement Facility AAF One or more Alarm Acknowledgement Facility Controls are used in the system During the Acknowledgement Period 10 60 sec there is an indication in the control unit display AAF zone zz activated During the Investigation Period 0 3 min there is an indication in the c i e display AAF zone zz investigation in progress See EBL512 Planning Instructions chapter Alarm Acknowledgement Facility AAF for more information regarding the AAF function 58 The AAF Control is available on the Australian market only 47 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01165 15 6 15 7 Operating Instructions Fire alarm system EBL512 V2 6 x Quiet alarm Normally used on the Australian market only One or more smoke detectors programmed for quiet alarm e g used for fan control stop start depending on the type of fan have passed the fire alarm level Quiet alarm is normally used in conjunction with the I O Matrix board 4582 an application board for fan control and an I O unit 3361 for fan control NOTE These units are available on the Australian market only Indications and actions LEDs Fire L1 are blinking 0 4 0 4 sec the buzzer sounds 0 8 5 sec and there is a Quiet alarm presentat
13. V2 6 x 31 12 Change access code for maintenance H8 S11 For security reasons the default code should be changed Access According to chapter Access code for maintenance see page 135 Scroll to menu S9 Enter the old code the The digits are replaced new code and the new in the display code again The code was not correct Try again The code was correct and is now changed to the new code Scroll or press Return to menu H8 Scroll or press Return to log off NOTE After change of access code it is recommended do a Safe shutdown of the control unit see menu H8 S8 This will save the SSW data e g the new code in a Flash ROM see page 83 If the valid access code is unknown a back door code is available 147 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 32 Interlocking outputs and inputs H9 32 1 Activated interlocking outputs inputs H9 C1 Access According to chapter Access see page 86 Scroll to menu H9 A C A PE HH MM This is a list in which you can scroll Depending on activated output and or input the AAA interlocking comb following will be l E oa area shown ble me PP interlocking comb point within the area Press Return to menu Cl Scroll or press Return to menu H9 Scroll or press Return to log off 148
14. also the parts of the zones in test mode not visible for the test personnel are disabled In order to shorten the testing time any time delay for the detectors zones in test mode will be disabled i e fire alarm will be detected faster than normally In the tested alarm point the LED will light up and the LEDs Fire L1 in the c i e will light up about ten seconds then the alarm point will be automatically reset The printer if available will print out every tested alarm point Zone xxx Address xx Time HH MM A sensor in test mode will not be able to activate fault After 60 minutes or Zones in test mode 001 002 003 You are no longer in menu Return H1 but still in test mode Return NOTE See chapter Alphanumeric display LCD in EBL512 page 20 regarding priority order When required Zone in TEST MODE Press A to end the test Access code 001 002 003 004 End test ACCEPT mode AN A Test of routing equipment 0 The LED Test mode is il wee 0 No ACCEPT turned OFF Some national regulations also require a routine test of the routing equipment Press A for no test and press 1 and A to start such a test The following will happen in the system e The c i e Fault tx output will be de activated indicated by the LED Fault tx activated L11 A 60 seconds count down starts e After 30 seconds also the c i e Fire brigade tx output and corresponding programmable outputs
15. be selected which is a violation to the EN54 2 standard 4 Outputs programmed for General fire alarm and outputs programmed for the activated fire alarm s 39 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x e Inthe c i e display and ext FBP display the fire alarms are presented as follows NOTE Normally the c i e relay output Fire brigade tx is used as output for Routing equipment This output will be activated for fire alarm from any alarm point or zone line input If the fire alarm routing equipment has provision for transmission of several fire alarm signals and the alarm receiver has provision for reception of several fire alarm signals the alarm receiver can take different actions depending on if it is a fire alarm type A or B If a fire alarm type B is received it will indicate that only one analog addressable smoke heat or multi detector is activated which could be a nuisance alarm If a fire alarm type A is received it is probably a real fire since fire alarm is then activated from e Two or more analog addressable smoke heat or multi detectors e Any manual call point e Any zone line input e Any programmable input with the trigger condition General Fire Fire alarm presentation in the EBL512 display B 1234567890123456789012345678901234567890 C A Field for the first alarm point or zone
16. menu H8 S3 Access According to chapter Access code for service H5 see page 120 Scroll to menu A7 Display statistics for COM loop ACCEPT A7 For which CU 00 and COM loop 0 shall Write control unit and loop statistics be displayed ACCEPT number Press A to accept If the control unit don t exist or don t answer this message will be shown Pollings 1234567 Parity 000000 00 0 Bit 000000 00 0 Answer 000000 00 0 Press A to menu A7 Display statistics for COM loop Scroll or press Return to ACCEPT A7 H5 Scroll or press Return to log off 106 Note The values are not live updated i e the shown values were valid when A was pressed in menu A7 To see the actual values press A to menu A7 press A and write control unit and loop number again and press A Normally is only the value Pollings changed 126 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 28 9 Select unit on COM loop to use for trigging H5 A8 This function is used by service engineer and by R amp D for troubleshooting On the pin respectively you will get a pulse to trig an oscilloscope etc COM loop Main board 1556 JP2 upper pin Each unit not giving a correct answer Main board 1556 JP2 lower pin A specific unit is being polled BS4 loop Autronica interface board 1584 in the c i e BY3 lef
17. possible to get a print out When all control outputs have been re enabled The LED Disablements L8 will be turned OFF if there are no other disablements in the system Action Access Scroll to menu H2 Scroll to menu B6 MAN Depending on the chosen type 0 1 2 3 resp 4 the following will be shown Text in display Disable or re enable Disable zone ACCEPT H2 ACCEPT B1 Re enable control output Re enabille control output type 0 C hoopunit 12S 225R SERE 4ZES ACCEPT ACCEPT B6 4 ES not valid in Swedish SBF convention Re enable 00 0000 output 0 Re enable Control unit 00 SO Re enable Control unit 00 RO ACCEPT Re enable output 0 ACCEPT L Re enable output for extinguishing controll unit 00 relay board 0 ACCEPT L system on 1583 board CU 00 96 Comments According to chapter Access see page 86 Press 0 RU4 2265 or SU4 2262 2263 or MIO 3361 or ASI 3377 or ASB 3378 1 S0 S3 2 RO R1 3 Relay board 1581 4 1583 board output Extinguishing system Press A to accept If there are no outputs to re enable menu B6 will be shown again L a list in which you can scroll Regarding the ASI 3377 amp ASB 3378 units Output O high priority 1 medium priority 2 low priority If it s the correct output to re enable press A to accept If not scroll or
18. to identify the point zone generating fire alarm It is also used to disable re enable fire alarm points zones and in control conditions expressions to activate the programmable outputs Together with the presentation number a user definable 40 characters text message alarm text can be displayed if programmed 00 99 01 99 The address within the zone 00 Zone number only will be displayed e g for one or more conventional detectors connected to a zone interface ADB MIO or 8 zones expansion board input 001 999 Zone number NOTE 1 Zone numbers 001 999 can be used but more than 512 alarm points or zones per c i e is a violation to the EN54 2 standard NOTE 2 When the function Redundancy in distributed system is used it is presented as 999 xx The zone number 999 is indicating that it is an alarm from a Control Unit and the address xx is indicating from which CU xx xx could be an individual CU xx 00 29 or several CU s xx 99 4 Also in the Alert Annunciation Units and Presentation Units Display Units The presentation number or a user definable 40 characters text message can also be shown in the old type of display units connected to the COM loops 37 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 15 Operating Instructions Fire alarm system EBL512 V2 6 x Alarm types 15 1 In case of a fire analog detectors sensors conventio
19. unit e Put back the fuse and acknowledge the fault e Remove fuse F8 on the output p c b The following fault message is to be shown FAULT Superv output 3 tech no xxxxxx NOTE xxxxxx is depending on output unit and control unit e Check the manual call points the glass Take required measures Use the manual call point alarm test key e Check some control outputs Are they activated according to programmed control expressions 154 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 35 How to change paper in the printer When the paper roll is almost empty a red line appears on one edge of the paper Change the paper roll before it s completely empty Always have a spare paper roll on site Change the paper roll as follows e Read all instructions before changing the paper roll e Open the control unit door Unlock the metal inner door by removing the screw placed on top to the left of the inner door Open the inner door e Remove the old paper roll carefully cut the paper so that the paper within the printer remains there e Take the new paper roll tape the new paper to the old paper and place the paper roll on the printer e Press the Paper feed button P7 until the new paper comes out of the printer Cut off the paper and lock the inner door Close the control unit door 155 Pana
20. 2 Operating Instructions Fire alarm system EBL512 V2 6 x Definitions Explanations 2 1 2 2 2 2 1 2 2 2 2 2 3 2 2 4 2 2 5 2 2 6 2 2 7 Definitions explanations abbreviations etc frequently used or not explained elsewhere in the document PEWF amp STE AB Panasonic Electric Works Fire amp Security Technology Europe AB Alarm points Units which can generate a fire alarm in the control unit i e analog detectors sensors conventional detectors manual call points etc Smoke detector Analog and conventional photoelectric optical smoke detectors are available Sensor Sensor Analog detector Analog detector Contains an A D converter The Control Unit pick up the digital values sensor values for each detector individually All evaluations and decisions are then made in the c i e Analog detectors are addressable an address setting tool is used for detector types 33xx 430x Old installations A DIL switch in the ASB see below is used for address setting for detectors 2xxx An analog detector has to be plugged in an analog sensor base ASB Analog Sensor Base ASB A sensor is plugged in an ASB which is connected to a COM loop see below Old installations Analog sensor base types 2xxx have a DIL switch for the COM loop address setting Conventional detector Detector with only two statuses i e normal and fire alarm The detector contains a closing conta
21. 3 Disconnect loop H8 S2 137 31 4 Re connect loop H8 S3 138 31 5 Acknowledge SERVICE signal H8 S4 139 31 6 Clear weekly average H8 S5 140 31 7 De activate alert annunciation function H8 S6 141 31 8 Test alarm devices H8 S7 142 31 9 Safe shut down of control unit H8 S8 143 31 10 Activate address in alarm mode H8 S9 144 31 11 Synchronize the control units H8 S10 146 31 12 Change access code for maintenance H8 S11 148 32 Interlocking outputs and inputs H9 149 32 1 Activated interlocking outputs inputs H9 C1 149 32 2 Activate interlocking output H9 C2 150 32 3 Reset interlocking output H9 C3 151 32 4 Disable interlocking output H9 C4 152 32 5 Re enable interlocking output H9 C5 153 33 Change access code for daily duties H10 154 34 Annual control 155 35 How to change paper in the printer _ 156 36 Replacing a TLON connection board and or a main board 157 37 Battery maintenance 158 38 How to avoid unnecessary nuisance fire alarms 159 39 Information regarding radioactive radiation source161 40 Revision history 162 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 1 Introduction EBL512 Operating Instructions is a document intended to be used by the end user a
22. Be careful when there are smoke detectors sensors near such activity Special environments In certain premises a special environment can exist which can influence smoke detectors sensors and cause alarm It can be ions from plastics flour dust oil haze aerosols strong perfumes strong ventilation insecticides disinfecting sprays etc If many odd and unnecessary alarms occur the environment must be examined and perhaps other detector types have to be chosen Steam hot air Smoke and heat detectors are influenced by steam and hot air e g from an oven dry blower heater etc 158 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x Exhausts Exhausts from cars trucks lift trucks lawn mowers etc influences smoke detectors sensors If windows and doors are open exhausts can slip in that way Lack of maintenance Smoke detectors sensors are influenced by their environment and become dirty In an analog system like EBL512 a Service signal is given when it is time to clean or exchange the smoke detectors sensors The alternative is to exchange detectors at even intervals to be on the safe side Change in activities or wrong choice of detector If the activities in the premises are altered the detector choice might also need altering Due to special environments see above an in appropriate detecto
23. C LE Control Unit Control and Indicating Equipment Unit to which the alarm points are connected via a COM loop Indicates fire alarm fault condition etc Fire Brigade Panel amp Control Panel see below included or not included Printer included or not included Fire Brigade Panel FBP Unit intended for fire alarm presentation etc for the fire brigade personnel Can be a part of the control unit front or a separate unit external FBP In the ext FBP a printer can be included or not included Control panel CP A part of the control unit front intended for the building occupier service personnel etc to communicate with the control unit system System Several control units connected via a TLON network co operating control units Network TLON LonWorks Echelon Node TLON Conn board Gateway Sub net Backbone net Router Repeater Brief explanations to the words expressions to be found in connection with a network See also separate TLON Technical description TLON TeleLarm Local Operating Network a LonWorks based network for communication between several units nodes The protocol is LonTalk and the transmission works with doubly terminated bus topology Echelon FTT 10 To connect a control unit to the network a TLON connection board is plugged in the control unit Old installations Some control units not prepared for network connection could be connected vi
24. Check the fan and the cables connections FAULT FB Silence switch active Only valid in the New Zealand convention New Zealand FB Silence switch outside switch is turned ON i e from not activated to activated state FAUD REBBE ISG 7oloosicel ox Ul sox FBP 1826 1828 The unit is programmed as another type of unit than the SSD says or fault in the unit FAULT Fuse 1580 8 zones board x CU xx DET8 1580 8 zones expansion board 61 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x Check for blown fuse on the 1580 board FAULT Fuse 1582 FBP board x CU xx External Fire Brigade Panel interface board 1582 Check for blown fuses on the 1582 board FAULT Fuse 1584 Autron board x CU xx BS4 1584 Autronica interface board Blown fuse on the 1584 board The fuse is not replaceable The board has to be replaced FAULT Fuse 1587 board x CU xx External Fire Brigade Panel DU interface board 1587 Check for blown fuses on the 1587 board FAULT Fuse on COM loop x CU xx The fuse is not replaceable More components might also be broken The main board 1556 has to be replaced FAULT Fuse output unit techn no xxxxxx Fuse F9 on the output unit p c b is blown FAULT High Current loop x 1584 x CU xx Autronica interface board BS4 The current consumption is gt 60 mA on the BS4 loop
25. Control unit will now restart Now an automatic reset restart will take place see chapter Restart page 83 If the download was not okay the following text message will be shown Checksum fault in downloaded data Control unit will now restart Now an automatic reset restart will take place see chapter Restart page 83 After the reset restart another text message will be shown in the display FAULT Site specific data SSD CU nn Date MM DD Time HH MM This text message means that the SSD have not been downloaded i e a new download has to be performed Control Units ina TLON network The SSD for all control units can be downloaded via one control unit Start the download from Win512 The download will now be performed to the control units one at a time according to the chapter Single Control Unit above When the download to a control unit is completed that control unit will automatically restart see chapter Restart page 83 User definable text messages download When a fire alarm is activated e g an addressable alarm point the presentation number Zone amp Address will be shown on the first row in the control units and the ext FBP s alphanumeric display On the second row will be shown a user definable text message alarm text if programmed Each alarm point can have a unique text message When several alarms are activated in one or more zones and only the zone numbe
26. Outputs programmed for heavy smoke heat alarm are activated e Each heavy smoke heat alarm is printed e g xxx Heavy smoke Point 123 45 Time HH MM Date MM DD User programmable text message if progr or zone 123 Time HH MM Date MM DD User programmable text message if progr wee Heavy heat Point 123 45 Time HH MM Date MM DD User programmable text message if progr or Zone 123 Time HH MM Date MM DD User programmable text message if progr Heavy smoke heat alarm will be reset when the fire alarm respectively is reset see chapter Alarm reset page 50 Key cabinet alarm One programmable input per c i e can be used to connect a key cabinet The fire brigade uses a key cabinet to store a key to the building NOTE In the DBI Danish convention the key cabinet alarm function is a little different see below Key cabinet opened before a fire alarm If the key cabinet is opened before a fire alarm e g if somebody illegally breaks into the key cabinet a key cabinet alarm i e a fire alarm will be generated Example Key cabinet alarm xx control unit number POINT KEY xx Nor 001 Alarm from key cabinet It will be printed like a normal fire alarm when printer is available see chapter Fire alarm page 39 Key cabinet alarm is reset like a normal fire alarm see chapter Fire alarm reset page 50 55 General heavy smoke
27. Security Technology Europe AB MEW01165 15 2 1 Rev Operating Instructions Fire alarm system EBL512 V2 6 x Reset of the fire alarms see chapter Alarm reset page 50 NOTE NOTE NOTE NOTE NOTE NOTE NOTE POINT 999 nn and POINT 999 99 Zone number 999 could indicate that the alarm is activated by one or more control units in the system In this case nn 00 29 is indicating a single slave unit and nn 99 is indicating several control units connected in parallel Normally the user definable text message alarm text on the second row will indicate if it is a normal alarm point or a slave unit units For more information see Planning Instructions chapter Redundancy in distributed systems NOTE 1 The fire alarm presentation in the EBL512 display is for the New Zealand convention only different than described above The serial number for the displayed alarm is replaced with the information ALM as follows two examples ALM Point 123 46 LAST 234 56 No OO1 This is a user defined alarm text ALM Zone 123 Noss OOL This is a user defined alarm text If the fire alarm is acknowledged see page 53 ALM will be replaced with ACK If the fire alarm or the acknowledged alarm is isolated see page 53 ALM will be replaced with ISO Fire alarm menu X1 X7 The special fire alarm menus X1 X7 can only be used if at least one fire alarm is activated If this f
28. Silence switch outside switch is turned OFF from activated to not activated any fire alarm and acknowledged alarm will be isolated disabled Isolated alarms are indicated in the fire alarm list in the LCD by ISO in front of the alarm respectively see page 42 Isolated alarms do not activate any control outputs do not activate the output for routing equipment Fire brigade tx do not activate the c i e buzzer and do not activate the LED s Fire in the c i e Isolated alarms ISO have to be reset like normal fire alarms ALM Isolated alarms have to be re enabled via menu H2 B5 before they can activate a new fire alarm again LED Disablements L8 is indicating that one or more zones alarm points are isolated disabled 52 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 17 Fault In order not to generate any faults unnecessarily all faults are delayed e g for COM loop and zone line input faults the delay time is approx 45 seconds In case of a fault condition the following has happened will happen in the control unit e The buzzer in the c i e sounds continuously steady ON e Output for routing equipment Fault tx is activated e Programmable output s for general fault is are activated and output s for general charge fault might be activated e LED Fault tx activat
29. V2 6 x 27 3 Doors open H4 U3 The LED Door open L10 is lit to indicate that one or more doors are open See chapter Door open page 34 This menu is a list of all open doors and it is also possible to get a print out Access According to chapter Access see page 86 Scroll to menu U3 Press 1 for an automatic print out of all open doors Press A for presentation in the display L a list in which you can scroll If there are no open doors and if Return is pressed menu U3 will be shown again Press A and menu U3 will be shown again Scroll or press Return to menu H4 Scroll or press Return to log off 105 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 27 4 Scroll to menu H4 Scroll to menu U4 Rev Operating Instructions Fire alarm system EBL512 V2 6 x Activated 2 zone address dependent zone address H4 U4 Two unit dependent in Win512 When only one zone or one zone address alarm point is in alarm status the buzzer in the c i e sounds 0 8 5 sec and there is a Co incidence alarm presentation in the c i e display The unit s or zone s in Co incidence alarm status is are shown in this menu from which it is also possible to get a print out ZAARA IE Proge Co incidence alarm detector User definable text message or Co incidence alarm zone ZZZ User definable text message if pro
30. W SSW Reset command from Win512 FFD SSD SSI or TLON Manager S W SSW Automatically due to external SSD SSI disturbance S W SSW Automatically after download SSD SSI of site specific data SSD via a S W SSW PC amp Win512 NOTE During restart the following will happen The Fault tx relay output will be activated The S0 S3 voltage outputs programmed as normally high supervised will be low not supervised for a few seconds 83 Restart affects the control unit where it is performed and that control unit s data in a system 84 If this memory is empty when the power supply returns new week average sensor values will be calculated within two minutes During the two minutes all fire alarms from analog smoke detectors will be suppressed 85 See Safe shut down of control unit above 36 Tf this happens often call for service personnel engineer 82 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x The restart begins and might last up to 2 minutes During the restart no fire alarm can be activated and the following text messages will be show in the alphanumeric display Checking program memory And after that if everything is all right else see Memory fault below IBXCYONESLING 4 aree A fault is now generated in the system and the following text message
31. Works Fire amp Security Technology Europe AB MEW01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 25 2 Disable zone address H2 B2 Addressable alarm points also addressable manual call points connected to the COM loop can be individually disabled Disabled alarm points zone addresses are listed in menu H4 U1 from which it is also possible to get a print out Disabled alarm points zone addresses have to be re enabled via menu H4 B2 Access According to chapter Scroll to menu H2 Disable or re enable ACCEPT Disable ACCEPT Scroll to menu B2 address ACCEPT Disable zone 000 Address ACCEPT Write zone number and Disable zone 001 Address Press A to accept address e g 001 01 ACCEPT Automatic re enabling 0 0 No 1 Yes Press 1 for aut re enabling and accept or Time HH MM ACCEPT change the time max 24 hours Press A to accept LED Disablements L8 will light up Default is current time 3 hours Disable zone 000 Address 00 If more disablements shall be done continue ACCEPT i like above If not press Return to menu B2 Scroll or press Return to menu H2 Scroll or press Return to log off 91 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 25 3 Disable control output H2 B3 Control outputs can be individuall
32. alarm system EBL512 V2 6 x 27 8 Configuration H4 U8 In a control unit the menu H4 U8 can be used to see the following settings made in Win512 Tools menu for that specific control unit Number of addresses that can be used i e xxx 128 256 or 512 set in EBL512 settings dialog box Language The language for texts presented in the alphanumeric display print outs Language file nnnn SST to be downloaded is selected in Download software dialog box Convention Different countries have different conventions i e country specific functions etc The convention is set changed via Win512 menu Tools Settings Win512 Settings dialog box It is not possible to get a print out from this menu Action Text in display Comments Access According to chapter Access see page 86 Scroll to menu H4 Present system status on display and printer ACCEPT H4 A Disablement Printout a l vesp wale Scroll to menu U8 Show configuration Press A to accept U8 A Max number of allowed loop units xxx Press Return to menu Language nnnnnnnnnn Conv cceccecccecce U8 Return Show configuration Scroll or press Return to menu H4 Scroll or press Return to log off 8 To set change the convention in Win512 Level 2 has to be selected and a password is required 117 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructi
33. alarm system EBL512 V2 6 x Push buttons on the Fire Brigade Panel FBP Push button Operation function Alarms queued black Used when LEDs Alarms queued L2 are lit to scroll browse through the queued alarms zones Function see chapter Fire alarm page 39 under LEDs Alarms queued Silence Alarm devices red Used to silence the sounders i e outputs for alarm devices 4 Reset green Has to be pressed for gt 0 5 sec Used to reset the fire alarm s Used to reset co incidence alarm Ps Evacuate green z Used to activate the sounders i e outputs for alarm devices P2 Silence buzzer yellow Used to silence the buzzer in the c i e P1 P2 P3 P P5 In the New Zealand convention the inside switch In Belgian British Standard and British Standard Marine Application conventions has P3 to be activated before P4 can be used Multiple reset Default All fire alarms in the system will be reset simultaneously Single reset The fire alarm displayed in the LCD first row to the left will be reset When more than one fire alarm is generated LEDs Alarms queued are lit each fire alarm has to be individually reset Single encapsulated reset Fire alarm reset is like Single reset Encapsulation function is described in EBL512 Planning Instructions chapter System properties settings Encapsulated unit zone disabled unit zone NOTE 1 When Multiple reset or Si
34. blinking and the Co incidence alarms will be automatically scrolled each 5 second A Co incidence alarm can be manually reset with the Reset button P4 on the c i e front or automatically reset after 5 minutes i e if the zone alarm point is no longer in alarm status see chapter Alarm reset page 50 The function 2 zone address dependence can be turned on off via a time channel Heavy smoke alarm Heavy heat alarm An analog detector generates heavy smoke heat alarm for a higher alarm level than the fire alarm level i e fire alarm is already activated by the same detector Heavy smoke heat alarm is a confirmation on that the smoke or heat is increasing and can be used for special actions e g activation of smoke ventilation etc In case of a heavy smoke heat alarm the following will happen 5 LED Acknowledge on 2235 is indicating that the push button Acknowledge has been activated A busy system can cause a time delay up to 10 seconds before the fire alarm is acknowledged 3 Tf two or more zones or units zone addresses dependent on each other are in alarm status at the same time normal fire alarm will be activated in the system See also EBL512 Planning Instructions See EBL512 Planning Instructions 45 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev 15 4 15 4 1 Operating Instructions Fire alarm system EBL512 V2 6 x e
35. comes up next Quick jump can be used within each menu e g in menu H1 press 6 for a quick jump to menu H6 1 and 0 within 1 sec 10 Instead of a menu identification e g B1 the letter L can be shown which means that it is a List Use 1 and to scroll in the list Use lt and gt to move the cursor in a menu Use Return to return from a sub menu to the main menu H1 H10 Use Return to log off from a main menu H1 H10 There will be an automatic log off 60 minutes after the last action i e if the key pad or a push button has not been used for 60 min 85 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 24 Perform monthly test H1 The control unit and the installation shall be tested on a regular basis If one twelfth of the alarm points are tested each month the whole installation will be tested after one year In test mode only the alarm points are tested i e no outputs no sounders will be activated during the test Alarm devices can be tested via menu H8 S7 If a real fire alarm is activated for example by an alarm point not in test mode the normal fire alarm functions will be activated i e fire alarm presentation outputs sounders activated routing equipment fire brigade tx activated etc See also chapter Alphanumeric display LCD in EBL512 page 20 NOTE If the cont
36. eight digits and is available from the producer if you are authorized The Key is shown in Win512 and the procedure is described in the Win512 help 81 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 22 Restart A restart will delete or not delete the data in the control unit Here follow an explanation of the different data abbreviations and a table showing how the data respectively is affected FFD Fire alarms faults and disablements SSW Week average sensor values access codes supervised output calibration values and log buffers Alarm counter when applicable SSD Site specific data i e all the installation programming downloaded from Win512 SSI EBL512 settings downloaded from Win512 S W Software i e the control unit system program Safe shut down of control unit menu H8 S8 will save the SSW data in a Flash ROM before you power off de energize the control unit Before the first Safe shut down this memory is empty After each Safe shut down the latest SSW data is saved When the power supply returns the control unit RAM working memory will after the restart read the SSW data saved in the Flash ROM a Action Data etc which Data etc which will be deleted will be not deleted Control unit power OFF a ie en SSI then power ON again RESET jumper JP4 on the SSD SSI main board 1556 S
37. four years 157 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 38 How to avoid unnecessary nuisance fire alarms We all realise when life buildings production facilities etc shall be saved it is of utmost importance that an initial fire is detected as soon as possible That s why more and more automatic fire alarm systems are installed In an automatic fire alarm installation especially if smoke detectors sensors are used everybody in the building needs to be informed how to avoid so called unnecessary nuisance fire alarms To avoid trouble and unnecessary expenses there are a couple of things to bear in mind Here are some advice and tips Tobacco smoke The detectors sensors can not sense the difference between smoke and smoke They can not separate tobacco smoke from smoke from a fire Intensive tobacco smoking in connection with bad ventilation can cause a fire alarm Welding grinding cutting sawing amp drilling These kind of jobs cause smoke Carpet welding Welding of plastic carpets causes a smoke that can be almost invisible but it still influences the smoke detectors sensors Cooking fumes toasting amp candles It is not only normal smoke that influences smoke detectors sensors It is all kinds of combustion products caused by cooking frying grilling toasting etc Warning
38. heat alarm and individual alarm points zones 5 When printer is available e g control unit 1549 57 Input I0 I3 or COM loop input unit can be used 46 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 15 4 2 15 4 2 1 15 4 3 15 5 Operating Instructions Fire alarm system EBL512 V2 6 x This alarm will also generate a fault message see chapter Key cabinet alarm reset page 52 It is indicated by LED Fault L8 NOTE The Fault tx output s will not be activated by this fault Key cabinet opened in conjunction with a fire alarm The fire brigade personnel can open the key cabinet if a fire alarm already is activated in the c i e In this case there will be no key cabinet alarm or fault generated when the key cabinet is opened Restoring the key after a fire alarm When all fire alarms in the system are reset see chapter Alarm reset page 50 the key has to be restored in the key cabinet within 5 minutes If not a fault will be generated see chapter Key cabinet alarm reset page 52 Key cabinet alarm DBI convention NOTE Valid for the DBI Danish convention only When the key cabinet is opened the Fault tx output s will be activated and a key cabinet fault will be generated FAULT Key cabinet control unit xx Date MM DD Time HH MM In Danish FEJL N gleskab central xx When this fault is acknowledged see chapter Acknowledge
39. in alarm By scrolling each alarm will be shown in this field B Field for the most recent last zone in alarm C Field for total number of zones in alarm D Field for alarm text User definable Only one alarm point activated in a zone is presented as zone address POINT or LAST Two or more alarm points activated in a zone is presented as zone only ZONE or LAST 4 Plus Alert Annunciation and Ext Presentation units In the old ext FBPs 2425 2426 and 2428 only the ten first fire alarms will be displayed 7 In New Zealand convention the presentation is different and described in separate documents 40 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x One alarm point POMNAn Zeta No 001 User definable text message for 123 45 More than one alarm point in a zone or One conventional zone zone line input ZONE 123 No 001 User definable text message for zone 13 More than one zone ZONE 234 LAST 567 No 002 User definable text message for zone 234 Only one alarm point in each zone POINT 122745 LAST 789 01 No 003 User definable text message for 123 45 LAST The most recent zone address that has activated fire alarm No The total number of zones where fire alarm is activated User definable text message alarm text For an alarm point it i
40. is mounted in a stable environment High max 2 55 The detector is mounted in an unstable environment See also Planning Instructions chapter Performance factor 112 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x Sensor values and setting alarm algorithm for the Analog heat detector 3308 3309 Access According to chapter Access see page 86 Scroll to menu H4 Present system status on display and printer ACCEPT H4 A Disablement Printout 1l yes U1 Scroll to menu US Sensor values To make a printout press Printout 1 else press A to accept Enter technical number 000000 Write the sensor s techn number and or press A to accept Sensor 000003 in This is a list in which Momentary XX C you can scroll or use gt to see the next information window for the selected sensor Press Return to Enter technical number Sensor 000003 A1 short name see Current algorithm Al separate table page 109 Press Return to Enter technical number or press Access to change the algorithm Access Access code _ If login was made with code for level 3 no code is needed Enter code for level 3 4 Access code The digits are replaced in the display B oo ata 000003 Current A1 Use gt or Change algorithm 000003 Current A1 Al A2 B A Algorithm
41. only have to be set when the power is turned on the control unit for the first time If required the clock might be corrected so that the time stamps for fire alarms faults etc will be correct In this menu is also the S W system program version shown The calendar and clock can be set in any c i e for the whole system Every day at midnight the calendar and clock will be synchronised NOTE The information shown in the display will be saved when you press A If you don t want to change anything e g if you only want to see the S W version press Return instead of A to return to menu H3 Access According to chapter Access see page 86 Scroll to menu H3 Set calendar and clock ACCEPT H3 Date YY MM DD Time hh mm ss Here is the S W version Weekday W 1 M 7 S VER Vvvvvvvvvvvvv_ shown e g VER 2 4 The time shown is the time when A was pressed in menu H3 NOTE The date is in some conventions languages Change the date time shown as DD MM YY and or weekday The clock starts again from the date time etc shown in the display NOTE Press Return instead of A if no changes are to be done A or Set calendar and clock Scroll or press Return to Return ACCEPT H3 log off The capacitor can supply the RTC for a couple of days When the power has been turned off it is recommended to check set the date and time in menu H3 101 Panasonic
42. the unit or something is wrong in the downloaded SSD FAULT Supervised output x CU xx If the output is programmed for sounders type 3 alarm devices it is also indicated by LED Fault Disablements Alarm devices L13 blinking If the output is programmed for fire brigade tx type 4 routing equipment it is also indicated by LED Fault Disablements Fire brigade tx L15 blinking x 0 SO Short circuit break on the connected cable equipment and or blown fuse F5 or F6 on the connection board x 1 S1 Short circuit break on the connected cable equipment and or blown fuse F7 or F8 on the connection board x 2 S2 Short circuit break on the connected cable equipment x 3 S3 Short circuit break on the connected cable equipment e Connected equipment might be stolen e Resistor s missing or not correct value see dwg 512 42 FAULT Superv output x tech no xxxxxx If the output is programmed for sounders type 3 alarm devices it is also indicated by LED Fault Disablements Alarm devices L13 68 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x blinking If the output is programmed for fire brigade tx type 4 routing equipment it is also indicated by LED Fault Disablements Fire brigade tx L15 blinking Check fuses F1 F8 on the output unit p c b Short circuit break on the connected w
43. to move the cursor in a menu Jp down keys are used to scroll between the menus the AA function is enabled for at least one alarm point zone Normally is only one time channel used for this function but two or more channels can be used The AA function can as an alternative be continuously on 19 Tn the New Zealand convention only used to acknowledge a Fire alarm i e the alarm information ALM in the LCD is changed to ACK 19 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01165 6 Rev Operating Instructions Fire alarm system EBL512 V2 6 x Normal operation 6 1 6 1 2 When the control unit system is in normal operation quiescent state i e no fire alarms no faults no disablements no service signals no zones in test mode no activated interlocking in outputs no open doors and or Alert Annunciation function not enabled only the LED Operation L6 should be lit Alphanumeric display LCD in EBL512 In normal operation quiescent state some system information is shown in the LCD in the control unit System information on the top first row The display LCD will in normal operation and in quiescent state show the information below The exact look is dependent on the convention language Top first row YYYY Year 2009 MM Month e g 02 February NOTE The way the date is DD Day e g 28 presented can be different CU XX
44. type 4 routing equipment will be activated indicated by the LED Fire brigade tx L15 e After another 30 seconds the test will be ended and the outputs and LEDs will return to normal 1 A Test of routing equipment in progress nn starts at 60 and will nn seconds left count down to 00 Monthly test is completed ACCEPT Perform monthly test Scroll or press Return ACCEPT H1 log off 88 This output is activated in normal state 87 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x NOTE_1 During the test the following information will be shown in all other c i e displays Zones in test mode 001 002 003 004 In DBI Danish convention only one zone NOTE_2 If an alarm point e g a manual call point is in alarm state when the test mode is ended there will not be a fire alarm activated Instead the alarm point will be disabled and has to be re enabled again via menu H2 B5 When the Fire door closing function is used the fire door will be closed when the detectors controlling the door are tested via the test mode 88 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 25 Disable or re enable H2 A whole zone one or more alarm points within a zone and or control outputs can be disabled v
45. write the wanted output and press A to accept Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x If more re enablements shall be done continue like above If not press Return to menu B6 Scroll or press Return to menu H2 Scroll or press Return to log off 97 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 25 7 Re enable non reset zone address H2 B7 NOTE This menu is no longer valid See chapter Single encapsulated reset page 51 Menu H2 B5 shall be used instead Text in display Comments Access to chapter Access see page ee Scroll or press Return t menu H2 Scroll or press Return to log off 98 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 25 8 Disable Re enable all control exting and ventilation outputs H2 B8 Outputs programmed as type 0 control general type 1 fire ventilation and or type 2 extinguishing system can be disabled all at the same time Disabled control output means that even if the control expression trigger condition for the output respectively is fulfilled the output will not be activated Disabled control outputs are indicat
46. 0 Access According to chapter Access code for maintenance see page 135 Scroll to menu S4 Acknowledge SERVICE signal ACCEPT S4 Sensor xxxxxx needs service If there are no sensors to acknowledge menu S4 will be shown again L a list in which you can NOTE The list order in this menu is as follows berets In it is the correct Paar sensor to acknowledge a Technical number order in the control unit this menu is 8 a press Fault acknowledge A If not scroll or write the b Technical number order in the rest of the system wanted sensor and press Fault acknowledge or press Return to S4 Fault acknowledge The service signal for that sensor is now acknowledged and_ If more service signal the next sensor will be shown in the display acknowledgements shall be done continue like Sensor yyyyyy needs service above If not press Return to menu S4 Acknowledge SERVICE signal Scroll or press Return to ACCEPT S4 menu H8 Scroll or press Return to log off LED Service L12 will be turned off when all sensors have been acknowledged 138 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 31 6 Clear weekly average H8 S5 If a sensor analog smoke detector is replaced without having generated SERVICE signal its week average sensor value has to be set to the default
47. Alternative A below Via a print out See Alternative 1 below NOTE open The event logging is disabled as long as menu H4 U7 is Action Access Scroll to menu H4 Scroll to menu U7 Alternative A Alternative 1 Write number of events to be printed e g 010 Text in display Present system status on display and printer ACCEPT Disablement Printout l yes Event log Printout 1l yes When A is pressed an event will be shown in the display e g FIRE ALARM zone 123 address 45 MM DD HH MM XX or FIRE ALARM zone 456 Many alarms in zone MM DD HH MM XX How many events should be printed 000 ACCEPT How many events should be printed 010 ACCEPT Comments According to chapter Access see page 86 Press A for display presentation or Press 1 for print out The most recent event will be shown i e use AX to scroll upwards in the list Press Return to menu U7 XX in the example control unit number XX 99 Win512 Press A to start print out AN Printing started To stop printing press C and 0 simultaneously ACCEPT Show event log Printout l yes Scroll or press Return to menu H4 Scroll or press Return to log off More than one alarm point in zone 456 have activated fire alarm 116 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire
48. CD back light and all LCD pixels are lit 12 3 Alert Annunciation Acknowledge The button Alert Annunciation Acknowledge P5 has the same function as the Acknowledge button on an AA unit 1735 1736 12 4 Disable When the push button Disable P5 is pressed all zones in fire condition will disabled 37 As from version 2 3 x one programmable input per c i e can as an alternative be used to turn ON OFF the Evacuate function 33 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 13 Operating Instructions Fire alarm system EBL512 V2 6 x Door open 13 1 13 2 A special key is used to open the control unit door to get access to the front system see chapter Access levels page 22 The same type of key is also used to open the ext FBP door Door open is indicated by LED Door open L10 In Win512 System dialog box Door open tab the following can be programmed default settings shown LED Door open Indication door open affected by Door in any control unit or any external FBP Door open ina C U is indicated by LED Door open in all C U s and in all ext FBPs Door open in an ext FBP is indicated by LED Door open in all C U s and in all ext FBPs O Door in any control unit Door open in a C U is indicated by LED Door open in all C U s and in all ext FBPs Door open in an ext FBP is indicated by LED Door open in that ext FBP only O Do
49. CU xx Fault in the extinguishing system equipment connected to the 1583 German Fire Brigade Panel interface board in control unit No xx FAULT 1583 GFBP interface board CU xx German Fire Brigade Panel interface board e Fault on no communication to 1583 board in control unit No xx Check address setting and connections on the board Check programming Win512 e Check the fuses F1 and F2 on the 1583 board 54 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x FAULT 1584 Autronica board x CU xx Autronica interface board Fault on no communication to 1584 board No x in control unit No xx Check address setting and connections on the board Check programming Win512 PAURE T ISe board Se CU Tox External Fire Brigade Panel DU interface board Fault on no communication to 1587 board No x in control unit No xx Check address setting and connections on the board Check programming Win512 FAULT 24 V for ext equipment CU xx Check the fuses F2 and F4 on the connection board 1555 Supervised output S2 is also supplied via F2 and F4 FAULT 24 V for routing equipment CU xx Check the fuses F1 and F3 on the connection board 1555 Supervised output S3 is in some conventions configurations supplied via F1 and F3 Indicated by LED L15 blinking FAULT 24 V out output unit xxxxxx
50. Control Unit in a TLON network Make two TLON networks one Delete a Control Unit in a TLON network Programming SSD download Check All Loop Units Single Control Unit Control Units in a TLON network User definable text messages download Using old SSD New system program S W version download __ A single control unit c i e Control Units in a TLON network Earlier S W version download EBLS512 settings download Control Units in a TLON network Restart 46 47 Key cabinet opened in conjunction with a fire alarm _ 47 47 47 48 48 50 50 50 50 50 51 51 51 52 52 52 52 33 53 54 55 72 73 73 73 74 74 75 75 76 76 76 77 77 78 79 79 80 80 82 82 83 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 22 1 Boot menu 85 23 Access 86 24 Perform monthly test H1 87 25 Disable or re enable H2 90 25 1 Disable zone H2 B1 91 25 2 Disable zone address H2 B2 92 25 3 Disable control output H2 B3 93 25 4 Re enable zone H2 B4 95 25 5 Re enable zone address H2 B5 96 25 6 Re enable control output H2 B6 97 25 7 Re enable non reset zone address H2 B7 99 25 8 Disable Re enable all control exting and ventilation outputs H2 B8 100 25 9 Disable Re enable alarm devices H2 B9 101 26 Set calendar and clock H3 102 26 1 Daylight saving time 103 27 Present system status on disp
51. Data SSD The SSD is unique for each installation All alarm points presentation numbers user definable text messages programmable outputs etc are created in the PC program Win512 and also downloaded in EBL512 with Win512 Software S W System program The S W makes the control unit the microprocessor work It is factory downloaded but a new version can be downloaded in EBL512 on site 11 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 3 Operating Instructions Fire alarm system EBL512 V2 6 x Overview 3 1 3 1 2 The EBL512 system EBL512 is a microprocessor controlled intelligent fire alarm system intended for analog addressable smoke detectors as well as conventional detectors and manual call points Programmable control outputs and output units are available Up to 512 addresses can be connected to each control unit c i e EBL512 is available in several types versions and configurations It can be connected to a TLON network a system with up to 30 control units Each control unit has access to all information EBL512 is designed according to the European standard EN54 part 2 and 4 The front conforms to S3654 Expansion boards In the control unit c i e it is possible to mount up to six expansion boards The following types are available 1580 8 zones expansion board 1581 8 relays expansion board 1582 External FBP interface board 1583 Ger
52. EBL512 settings menu Tools EBL512 settings and download them again They will then be downloaded with the same Win512 version as the S W and the fault will normally be corrected 71 Tt is not possible to merge two TLON Networks into one or copy one system and paste into another system 74 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01165 19 Operating Instructions Fire alarm system EBL512 V2 6 x Programming SSD download 19 1 19 2 The PC program Win512 is used for programming of the site specific data SSD and to download it into the EBL512 control unit s and or 1728 1735 1736 amp 1826 1828 units connected to an Ext FBP DU interface board 1587 When the units are running i e the power is turned on and the TLON network is running the SSD download can take place The PC has to be connected to the D connector J1 in a control unit main board 1556 Start Win512 Now you have to log on to the control unit In Win512 menu Tools Download you select the unit s to which the SSD is be downloaded For security reasons the SSD i e the installation will be automatically saved after the download Check All Loop Units In the Win512 COM loop icon pop up menu select Check All Loop Units This function can be used after or before the download of SSD The function is as follows The control unit will find all units that are connected on the COM
53. Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 26 1 Daylight saving time Use daylight saving time is selected via Win512 If selected the time is automatically changed when the Daylight saving time period starts and stops respectively e Forward 1 hour the last Sunday in March 02 00 gt 03 00 Backward 1 hour the last Sunday in October 03 00 gt 02 00 102 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 27 Present system status on display and printer H4 A printer is factory mounted in control unit 1549 Printer 1558 is an option for control unit 1548 27 1 Disablement H4 U1 A list of all disablements in the system Also alarm point s and or zones disabled via the function Single encapsulated reset see page 51 is shown in the list In this case a zone will be displayed as ZZZ 00 i e zone number and address 00 Disablements by time channels are listed in menu H4 U2 From this menu it is also possible to get a print out Action Text in display Comments Access According to chapter Access see page 86 A Press 1 for an automatic rin print out of all disablements in the system Press A for presentation in the display A d the gt L a list in which you can pe i scroll If there are no l l disablement
54. FAULT High Voltage 1584 board x CU xx Autronica interface board BS4 The BS4 loop voltage is gt 16V normally it is 14V 0 1V FAULT ID fault display unit xxxxxx The display unit is not the same type as programmed Change the 62 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x programming or the unit FAULT Interlocking input AAA PP An interlocking input is not activated within the time set for fault activation 5 255 seconds The time is counted from the activation of the output in the interlocking combination area point FAULT Key cabinet control unit xx The key cabinet has been opened without a prior fire alarm i e if somebody has opened the key cabinet illegally or The key cabinet has not been closed within 5 minutes after reset of all fire alarms in the system FAULT L C mixed COM loop x CU xx The two wires L SA and C SB have been mixed alternated Check so that the wire connections are correct according to drawing 512 41 FAULT LON board 1590 control unit xx TLON connection board 1590 No communication connection with the TLON network The board has to be changed FAULT Loop unit technical number xxxxxx The communication with the unit is not all right i e the unit is out of order faulty FAULT Low battery capacity CU xx Battery internal resistance is too high
55. S WOO On Unie ACCEPT 0 COM loop 1 BS4 loop 2 Expansion board 1580 3 Addr zone interface 2226 2335 3361 MIO Press A to accept A Re connect COM Loop 0 Write the required numbers Press A to Depending on the accept chosen type 0 1 2 or 3 the following will be shown Re connect input technical no 000000 ACCEPT A Re connect type 0 0 COM 1 BS4 Continue to re connect or 2 DET8 3 Loop Unit ACCEPT press Return to menu S2 LED Disablements will be turned off if there are no other disablements in the system Return Re connect loop Scroll or press Return to ACCEPT S3 return to menu H8 Scroll or press Return to log off 137 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 31 5 Acknowledge SERVICE signal H8 S4 See chapter Sensors activating SERVICE signal H4 U6 page 116 When service signal from a sensor is acknowledged the sensor is given a default sensor value for a new clean sensor i e first replace the sensor then acknowledge the service signal as soon as possible The first week average sensor value after acknowledge will be calculated within one hour and after that each week NOTE If a sensor is replaced without having generated service signal it has to be reset to the default sensor value see chapter Clear weekly average H8 S5 page 14
56. Technology Europe AB MEW01165 16 3 16 4 16 5 16 6 Operating Instructions Fire alarm system EBL512 V2 6 x zone alarm point is no longer in alarm status See also chapter Co incidence alarm 2 zone address dependence page 45 Heavy smoke heat alarm reset If a heavy smoke heat alarm has been activated it will be reset at the same time as the corresponding fire alarm is reset Also the output s will be reset i e de activated Key cabinet alarm reset Not valid for the DBI Danish convention see chapter Key cabinet alarm DBI convention page 47 After reset of the key cabinet alarm fire alarm a fault message is shown in the display to inform the user that the key cabinet has been opened PAUND Key cabinet Control Umit sx Date MM DD Time HH MM NOTE The date is in the Ukrainian and the Australian conventions S W version gt 2 2 3 shown as DD MM If the key cabinet is closed again the status information Serviced is added This key cabinet fault message is to be acknowledged the same way as a normal fault see chapter Fault acknowledge page 72 When the key cabinet fault is acknowledged the LED General fault L7 will be turned OFF if the key cabinet is closed and if there are no other faults in the system Quiet alarm reset Quiet alarms are non latching i e they will be automatically reset when the alarm point zone is no longer above alarm level Ou
57. The output current is gt 4A The output might also be turned off PFAUCT AAU xx 1587 board x CU xx AAU 1735 1736 The unit is programmed as another type of unit than the SSD says or fault in the unit Uline s Alarm input Iba boari x CU xox The zone line input x on the 1580 board placed in control unit xx master is used for a single slave unit control unit or several control units connected in parallel i e the board is used for Redundancy in distributed system The input x is in fire alarm state but there is no activated fire alarm 55 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x in any control unit and no fault on the TLON Network Check the connections e g of the alarm resistor in the slave unit units FAULT Alarm input tech no xxxxxx The zone line input Input 0 on the 3361 unit with technical number XXXXxx is used for a single slave unit control unit or several slave units connected in parallel i e the unit is used for Redundancy in distributed system The Input 0 is in fire alarm state but there is no activated fire alarm in any control unit and no fault on the TLON Network Check the connections e g of the alarm resistor in the slave unit units FAULT ASF COM loop x control unit xx ASF 2370 Addressable short circuit isolator This message is only shown
58. X and alternating Synchronization in progress for CU X X is the last digit in the control unit number e g 8 for CU no 18 and 28 Synchronization completed lt Blank gt There is no control unit with that number in the system Access Scroll to menu S10 According to chapter Access code for maintenance see page 135 Press 1 and A to start the synchronisation or press A to go directly to the field Synchronization completed or press Return to menu S10 During the synchronization the information on each position on row 2 is changing all the time 28 CUs are shown in the example i e 15 amp 16 are not programmed Press A to continue Month MM day DD and time for the latest completed synchronization S Tf the CU restarts in conjunction with this fault the synchronization will start automatically otherwise it has to be started via this menu 145 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 146 Press Return to menu S10 Or press 1 and A to start the synchronisation or press A to go directly to the field Synchronization completed Scroll or press Return to menu H8 Scroll or press Return to log off Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512
59. a a serial interface and a Gateway A network can be one sub net FTT 10 or several sub nets connected via routers In the TLON Network a sub net a channel LonWorks A summing up name for the market of Echelon Corporation Inc technology 10 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 2 14 2 15 2 16 2 17 2 18 2 19 Operating Instructions Fire alarm system EBL512 V2 6 x Repeaters are used to increase the maximum cable length node to node in a network Router or Repeater is the same type of unit different configuration All network programming configuration are made with the PC program TLON Manager LED LED Light Emitting Diode Yellow green or red optical indicator lamp External Indicator LED A unit with an LED Connected to an ASB CDB or a detector with a built in LED Old installations Also connected to an ADB Lit when the built in LED is lit Display LCD LCD Liquid Crystal Display Display in the c i e or Display unit for presentation of fire alarms fault messages etc Normally 40 alphanumeric characters and backlight Door open Door Key switch In EBL512 there is a door switch which is activated when the control unit door is open In some other units this door switch is replaced with a key switch The LED Door open is indicating door open key switch in position open Site Specific
60. a menu H1 Via this menu H7 it is possible to perform the zone test solely In test mode only the alarm points are tested i e no outputs no sounders will be activated during the test Alarm devices can be tested via menu H8 S7 If a real fire alarm is activated for example by an alarm point not in test mode the normal fire alarm functions will be activated i e fire alarm presentation outputs sounders activated routing equipment fire brigade tx activated etc See also chapter Alphanumeric display LCD in EBL512 page 20 NOTE If the control unit door is left open the output s for routing equipment fire brigade tx might be disabled if set so in Win512 There will be an automatic ending of the test mode one hour after the latest tested alarm point Access According to chapter Access see page 86 Scroll to menu H7 Perform ZONE TEST ACCEPT H7 Zone to be set in TEST MODE NOTE In DBI Danish APA ERE SERENE ERAN Start Eest ACCEPT convention only one zone Write zone numbers Zone to be set in TEST MODE Press A to start the test e g 001 002 003 001 002 003 004 Start test ACCEPT mode 004 A Zones are set in test mode LED Test mode L9 wait will light up Zone in TEST MODE Perform the tests 001 002 003 004 End test ACCEPT The zone s will stay in test mode until the test mode is ended but after 60 minutes or if you press Return two times you will be logged out from menu H7
61. abled isolated l e it has to be re enabled via menu H2 BS5 e Any alarm point zone in fire alarm state will automatically change state to Isolated alarm and in the fire alarm list presented in the LCD will ALM be changed to Iso Two examples 30 This is valid also if the fire alarm is activated after the outside switch is turned ON Always latched regardless of if faults are programmed to be not latched Since this fault is always latched it has to be acknowledged via menu H6 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 9 Disable Re enable alarm devices The outputs programmed for sounders type 3 alarm devices can via menu H2 B9 be collective disabled for one more or all control units This is indicated by LED Disablements L8 and LED Fault Disablements Alarm devices L13 steady ON In case of a fire the sounders will remain disabled i e the alarm devices will not sound They will remain disabled until they are re enabled again via menu H2 B9 See also chapter Disable Re enable alarm devices H2 B9 page 101 29 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 10 Silence buzzer The EBL512 built in buzzer will sound for e pre warning 0 8 5 sec e Co incid
62. and install download it according to the separate TLON network documentation Open the SSD for the current system via Win512 Add one control unit and the units connected to it and download the new SSD according to chapter Programming SSD download page 76 Make two TLON networks one It is very important that two or more presentation numbers Zone Address in the systems are not the same The system properties have to be the same Use one of the systems and add to it the control units etc from the other system If it is known from the beginning that two systems shall be one in the future it is possible to give the control units in the system respectively the final control unit numbers right from the beginning in order to get the correct technical numbers in the system documents NOTE Two or more presentation numbers Zone Address in the systems must not be the same Delete a Control Unit in a TLON network Physically disconnect the control unit which will generate faults in the other control units Acknowledge the faults Open the current project in TLON Manager delete one control unit according to the separate TLON network documentation Open the SSD for the current system via Win512 Delete one control unit and the units connected to it and download the new SSD according to chapter Programming SSD download page 76 Tf you after S W download get FAULT Configuration control unit xx read the
63. arm devices In the control unit on the FBP there is a push button P3 Silence Alarm devices If the push button Silence Alarm devices is pressed during a pre warning a fire alarm or a Co incidence alarm the following will happen e LEDs Fire L1 and Alarms queued 28 L2 changes from blinking 0 4 0 4 to steady ON e activated outputs programmed for sounders type 3 alarm devices will be turned OFF In case of a new alarm or if the push button Silence Alarm devices is pressed again the sounders will automatically sound again and the LEDs Fire and Alarms queued starts blinking NOTE This is also valid for Pre warning and Co incidence alarm 8 1 Silence alarm devices inside switch NOTE The functions in this chapter are valid for the New Zealand convention only The button Silence alarm devices P3 is called the inside switch and has the following function The inside switch toggles between two states e Alarm devices disabled All programmable outputs of type Alarm devices are disabled i e they can not be activated e Alarm devices not disabled All programmable outputs of type Alarm devices enabled i e they can be activated If the inside switch is in its disabled state when the c i e door is being closed the buzzer will beep once and the message Silence switch left active will be shown in the LCD For priority order see chapter Alphanumeric display LCD in EBL512
64. at even if the control expression trigger condition for output respectively is fulfilled the output will not be activated Disabled alarm devices are indicated by LED Fault Disablements Alarm devices L13 and LED Disablements L8 and is also shown in menu H4 U1 The outputs in one or more control units can be disabled or the outputs in all control units The outputs will be disabled until re enabled again via this menu NOTE This function is not the same as push button Silence alarm devices P3 see chapter Silence Alarm devices page 27 This function has higher priority than Silence alarm devices Action Text in display Comments Access According to chapter Access see page 86 Scroll to menu H2 Disable or re enable ACCEPT H2 A Disable zone ACCEPT BI Scroll to menu B9 Disable Re enable alarm devices ACCEPT B9 A Disable 0 or Re enable 1 alarm Press 1 or 0 write the devices 1 CU 99 99 lt ALI ACCEPT CU number or 99 for all CUs and press A to accept A Disable Re enable alarm devices Scroll or press Return to ACCEPT B9 menu H2 Scroll or press Return to log off 100 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 26 Set calendar and clock H3 The RTC component has a capacitor as a backup power supply Normally date day of the week and time
65. at has to be enabled via Win512 for the c i e respectively Note Pre warnings activated in any control unit in the system will be presented in all control units and all programmable outputs in the system with trigger condition pre warning will be activated if not disabled An analog detector will generate a pre warning for a lower alarm level than the fire alarm level Pre warning can be used when an early alarm and or an early action is required e g a soft computer shut down Normal alarm devices routing equipment etc will not be activated 4l In the New Zealand convention only a Fire alarm ALM can be changed to an Acknowledged alarm ACK or an Isolated alarm ISO 4 See EBL512 Planning Instructions Any programmable input can also be used to activate a pre warning Regarding the BS4 exp board 1584 for Autronica devices BS4 loops pre warning can also be generated by detector s connected to address units 38 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x In case of a pre warning the following will happen e The buzzer in the control unit sounds 0 8 sec each 5 sec 0 8 5 sec e LEDs Fire L1 are blinking 0 4 0 4 sec e Outputs programmed for pre warning are activated e On the first row in the c i e display the presentation number zone address is shown for the first pre warning
66. ation number Technical number for COM loop units Technical number for BS4 loop units Presentation number Alarm types Pre warning Fire alarm 15 2 1 Fire alarm menu X1 X7 15 2 2 Alert Annunciation AA alarm 15 2 3 15 3 Heavy smoke alarm Heavy heat alarm Co incidence alarm 2 zone address dependence __ 35 35 36 37 38 38 39 42 45 45 46 Panasonic Electric Works Fire amp Security Technology Europe AB Operating Instructions Fire alarm system EBL512 V2 6 x MEWO01165 Rev 15 4 Key cabinet alarm 15 4 1 Key cabinet opened before a fire alarm 15 4 2 15 4 3 Key cabinet alarm DBI convention 15 5 15 6 15 7 16 16 1 16 2 Alarm Acknowledgement Facility AAF Quiet alarm Alarm Acknowledgement Facility AAF Alarm reset Pre warning reset Fire alarm reset 16 2 1 Multiple reset 16 2 2 Single reset 16 2 3 Single encapsulated reset 16 2 4 Alert Annunciation 16 2 5 Co incidence alarm 16 3 16 4 16 5 16 6 16 7 16 8 17 17 1 17 2 18 18 1 18 2 Heavy smoke heat alarm reset Key cabinet alarm reset Quiet alarm reset Alarm Acknowledgement Facility AAF reset Acknowledged alarm Isolated alarm Fault Fault messages Fault acknowledge Commissioning an installation Single Control Unit Control Units in a TLON network 18 2 1 TLON network installation 18 3 18 4 18 5 19 19 1 19 2 19 3 19 4 19 5 20 20 1 20 2 20 3 21 21 1 22 Add a
67. ator Indicating Fire 5 red Fire alarms also Pre warning Heavy smoke heat alarm Alert Annunciation alarm Quiet alarm amp Key cabinet alarm Alarms queued 2 red More than one unit zone have generated fire alarm Use push button Alarms queued P1 to scroll L1 L2 L3 L4 6 Extinguishing red Output s for extinguishing equipment activated Activated extinguishing Ventilation yellow Output s for fire smoke ventilation equipment activated Activated fire ventilation equipment activated Test of routing equipment in progress see menu H1 L Operation green Power on i e the power supply rectifier and or battery are connected and working properly FBP push buttons on next page L5 Fire brigade tx red Output for fire brigade tx routing equipment and or corresponding programmable output s i e type 4 routing 7 See chapter Alarm types page 38 In the New Zealand convention also Acknowledged alarm ACK 8 L3 L4 and L5 can as an alternative be programmed to indicate when a programmable input is activated i e input trigger condition Activated Extinguishing Activated fire ventilation and Activated routing equipment respectively e g L5 can be turned on when a programmable input is activated by an activated routing equipment output 16 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire
68. batteries to the charger board 1557 1657 Connect the rectifier to the mains 230 V AC Replace the rectifier fuse F1 and the battery fuse F2 or F3 on the charger board 1557 1657 LED Operation L6 indicate that the 24 V DC power supply rectifier and or battery is okay An automatic restart will now take place see chapter Restart page 83 The site specific data SSD can now be downloaded see chapter Programming SSD download page 76 The SSD is created via the PC program Win512 See also chapter Calibration of supervised outputs H5 A1 page 121 Control Units ina TLON network In a TLON network there is two or more control units connected A TLON connection board 1590 is required in each control unit connected to the network When the 1590 board is on place and the cables are connected for each control unit do as follows 1 Take away the rectifier fuse F1 and a battery fuse F2 or F3 on the charger board 1557 1657 Connect the batteries to the charger board 1557 1657 Connect the rectifier to the mains 230 V AC Replace the rectifier fuse F1 and the battery fuse F2 or F3 on the charger board 1557 1657 LED Operation L6 indicate that the 24 V DC power supply rectifier and or battery is okay An automatic reset restart will now take place see chapter Restart page 83 The TLON connection board is mounted on the main board 1556 Network cable connections a
69. can not be found Check the unit s address DIL Switch in some unit or with programming tool 3314 in some units Faulty unit Detector removed from its base Double break on the COM BS4 loop Note Single break gives the fault message FAULT Cut off FAULT Output unit techn no xxxxxx e Fault in the output unit RAM e Fault in the output unit EPROM e Fault in the output unit EEPROM site specific data Replace the output unit output unit p c b FAULT Read write site data SSW CU xx SSW data that is changed during operation i e sensor values access 65 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x codes etc e If the C U was made powerless i e no mains and no the battery without first doing a Safe shut down of control unit via menu H8 S8 see page 143 this fault might be generated when the C U is powered again After fault acknowledge the SSW will get default values and the fault will be corrected serviced e Some external influence has caused a fault in the SSW This is very serious Call for service personnel engineer FAULT Restart CU nn code xx yyyyyyyyyy Control unit restart has occurred See also page 83 nn Control unit number 00 29 NOTE nn 55 TLON conn board 1590 not programmed e g after it has been replaced See TLON Manager Operating Instr x
70. cess see page 86 Scroll to menu H9 Scroll to menu C3 can scroll If there are no activated outputs menu C3 will be shown again Press A for reset or Return no reset to menu C3 Scroll or press Return to menu H9 Scroll or press This is a list in which you Return to log off 150 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 32 4 Disable interlocking output H9 C4 Interlocking outputs Type Interlocking can be disabled via this menu but not via menu H2 B3 The Interlocking Combination Area Point is to be entered to disable the output If 000 00 is entered all interlocking outputs will be disabled at the same time Up to 200 interlocking outputs can be disabled Disabled interlocking outputs are listed in menu H4 U1 from which it is also possible to get a print out The LED Disablements L8 is also indicating one or more disabled interlocking outputs Access According to chapter Access see page 86 Scroll to menu H9 Press A to accept and or Return to menu C3 Scroll or press Return to menu H9 Scroll or press Return to log off 151 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 32 5 Re enable interlocking output H9 C5 Disabled inter
71. collective disabled for one more or all control units This is indicated by LED Disablements L8 They will remain disabled until they are re enabled again via menu H2 B8 See also chapter Disable Re enable all control exting and ventilation outputs H2 B8 page 100 3 Also the Extinguish equipment output on the German FBP interface board 1583 32 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 12 Evacuate LED Test Alert Annunciation Acknowledge and Disable These functions are only valid in some conventions A front with the push button P5 is required See also chapters Control Unit page 14 and LED indicators and push buttons page 16 12 1 Evacuate When the push button Evacuate P5 is pressed all outputs programmed for sounders type Alarm devices will be collectively turned ON steady continuous This is indicated by the following information in the EBL512 display Evacuate in progress The sounders will remain ON until they are turned OFF by pressing the push button Evacuate P5 again NOTE The alarm devices sounders will in this case be activated steady continuous irrespective of the fact that the outputs can be set to something else for fire alarm e g intermittent 12 2 LED Test When the push button LED Test P5 is pressed all LEDs on the front the L
72. ct and a series alarm resistor Normally plugged in a conventional detector base CDB see below connected to a conventional zone line input with an end of line device Some types are connected directly on zone line Old installations An addressable detector base ADB for conventional detectors see below could be connected directly to a COM loop Conventional Detector Base CDB A conventional detector is plugged in a CDB connected to a conventional zone line input Addressable Detector Base ADB Old installations An ADB for conventional detectors see above could be connected directly to a COM loop Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 2 2 8 2 2 9 2 2 10 2 2 11 2 3 2 4 2 5 2 6 2 7 Operating Instructions Fire alarm system EBL512 V2 6 x Addressable A unit with a built in address device i e each unit is individually identified handled and indicated in the c i e The unit can be an I O unit with a zone line input to which one or more conventional alarm points can be connected Old detector Old installations Conventional detector with a closing contact i e a short circuit no alarm resistor or a detector with two breaking contacts Conventional zone line input External line Input intended for one or more conventional alarm points End of line device in the last alarm point Old installations ADB Addressable zone inter
73. d 719 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 4 If so the PC program Key512 is used to get a Password for the number specified in the Key field Only authorised personnel have access to Key512 5 When the password is typed click OK NOTE If a running EBL512 system shall be downgraded bear in mind that the Site Specific Data SSD created in a new Win512 version e g 2 6 1 can not be opened in an earlier Win512 version e g 2 2 5 New SSD has in this case to be created in the earlier Win512 version 80 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 21 Operating Instructions Fire alarm system EBL512 V2 6 x EBL512 settings download 21 1 EBLS12 settings are normally factory downloaded before the delivery It is however possible to download the following on site e The number of addresses max loop units e Serial number normally not changed e Date normally not changed e Adhesive type Type 1 old Type 2 new acc to EN54 If you wish to download new EBLS12 settings a PC and Win512 are used Before download the PC has to be connected to the D connector J1 in the control unit main board 1556 in question 1 Start Win512 In the Tools menu open the EBL512 settings dialog box 2 Set the c i e in Bootstrap m
74. de for level 2 or 3 or 4 Building occupier Installation handling daily duties e g monthly tests dis ablements etc Service Service maintenance 3 EFEK Fire brigade key Access code for level 3 or 4 4 KEET Fire brigade key Access code for level 4 maintenance personnel Service maintenance commissioning the system Service maintenance commissioning engineer Service Service maintenance commissioning commissioning the engineer system etc via Win512 5 kkkkkkkk PC Win5 12 connected PC access code for level 5 The access codes can be changed To change a code you have to know the valid code or use a code for a higher access level Retailers are informed regarding the default access code respectively 22 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 7 1 Access level 0 With the door closed anybody has access to the push button Alarms queued P1 via a circular opening in the plexiglass to scroll browse through the queued alarms 7 2 Access level 1 When the door has been opened via the fire brigade key and the door switch has been activated LED Door open is lit the user fire brigade personnel has access to the push buttons keypad to P2 Silence the buzzer in the c i e EBL512 P3 Silence the alarm devices sounders in the system
75. ded to an EBL512 with the latest version 77 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01165 20 Operating Instructions Fire alarm system EBL512 V2 6 x New system program S W version download 20 1 The latest software S W version of the EBL512 system program is factory downloaded before the delivery Due to continual development and improvement different S W versions can be found The valid S W version can be read in menu H3 or via Win512 New S W can on site be downloaded via Win512 See also the Win512 help chapter help topic Download Software New S W for the 1728 1735 1736 amp 1826 1828 units connected to an Ext FBP DU interface board 1587 can also on site be downloaded via Win512 See the Win512 help chapter help topic Display unit menu and the Technical Description for the unit respectively A single control unit c i e A single c i e must not have a TLON connection board 1590 mounted To download a new software system program version a PC and Win512 are used Before download the PC has to be connected to the D connector J1 in the control unit main board 1556 in question 1 Start Win512 In the Tools menu open the Download software dialog box and do the required settings e g the path for the S W BIN file and or the language SST file Do not forget to mark the checkbox respectively 2 Set the c i e in Bootstra
76. dress H2 B5 Disabled alarm points zone addresses are listed in menu H4 U1 Alarm points and or zones disabled via the function Single encapsulated reset see page 51 have to be re enabled via this menu A zone will be displayed as ZZZ 00 i e zone number and address 00 Alarm points and or zones disabled when the New Zealand FB Silence switch outside switch is turned OFF have to be re enabled via this menu before they can activate a new alarm Re enabling via this menu has higher priority than automatic re enabling When all alarm points zones have been re enabled The LED Disablements L8 will be turned OFF if there are no other disablements in the system Access According to chapter Access see page 86 _ an If there are no zone Scroll to menu B5 addresses to re enable menu B5 will be shown again L a list in which you can scroll If it s the correct zone address to re enable press A to accept If not scroll or write the wanted zone address and press A to accept If more re enablements shall be done continue like above If not scroll or press Return to menu H2 Scroll or press Return to log off 95 Panasonic Electric Works Fire amp Security Technology Europe AB Operating Instructions Fire alarm system EBL512 V2 6 x MEW01165 25 6 Rev Re enable control output H2 B6 Disabled outputs are listed in menu H4 U1 from which it is also
77. e a new fire alarm within 20 seconds It has to be re enabled via menu H2 B5 before it can activate a new fire alarm This function set in Win512 is a violation to the EN54 2 standard LED Disablements L8 is indicating one or more disablements in the system NOTE When Multi reset or Single reset is used encapsulated reset can be done by pressing Reset P4 and 0 1 sec later also press Alarms queued P1 and hold them pressed for gt 0 5 sec By Single reset and by Multiple reset The fire alarm displayed in the LCD first row to the left will be reset and disabled or the points in alarm status within one zone will be reset and disabled or the whole zone conventional will be reset and disabled Alert Annunciation Regarding the function see chapter Alert Annunciation AA alarm page 45 and EBLS512 Planning Instructions chapter Alert annunciation Reset of the AA alarm s can be done via push button Reset on an AA unit 1735 1736 or an AA controller 1740 or in the c i e If more than one AA alarm is activated they will be reset all at a time NOTE Reset via an external unit is only possible to do during the investigation time and AA alarm s only not normal fire alarms Co incidence alarm A Co incidence alarm can be manually reset with the Reset button P4 on the c i e front or automatically reset after 5 minutes i e if the 50 Panasonic Electric Works Fire amp Security
78. e technical number NNNNNN is used when programming all units connected to the BS4 loops Technical number is also used to identify which unit has generated a fault NN NNN 01 99 The address on the BS4 loop Don t have to be in sequence The connections on the BS4 loop don t have to be in sequence The address is set on DIL switches in each unit 0 3 BS4 loop number 4 7 Board number 00 29 The control unit address number Don t have to be in sequence The connections to the TLON network don t have to be in sequence The address is set with a PC SW TLON Manager NOTE In the technical number for unit connected to a BS4 loop the board number 4 Autronica interface board 0 the board number 5 Autronica interface board 1 the board number 6 Autronica interface board 2 and the board number 7 Autronica interface board 3 in the control unit In fault messages for Autronica interface boards the following information is shown Control unit 00 29 BS4 board 0 3 and if required BS4 loop 0 3 3 Can only be used in Swedish SBF convention 36 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01165 Operating Instructions Fire alarm system EBL512 V2 6 x 14 3 Presentation number For each fire alarm point input zone a presentation number NNN NN has to be programmed The presentation number is shown in the c ie and ext FBP display s
79. ed L11 is turned ON indicating that the output for routing equipment Fault tx is activated e LED General fault L7 is turned ON e LEDs Fault Disablements Alarm devices L13 System fault L14 and or Fault Disablements Fire brigade tx L15 might be turned ON as well e A fault message incl date and time is shown in the display NOTE The way the date is presented could be different for different languages e g DD MM Example of a fault message FAULT No reply techn no xxxxxx Date MM DD Time HH MM e If more than one fault is activated the text More faults is added after the time e Ifa fault has been corrected before it has been acknowledged the status text Serviced is added after the time e Fire alarm presentation has higher priority than the fault messages During fire alarm presentation the faults can be shown via the special fire alarm menu X1 see page 43 Faults have to be acknowledged which is done via menu H6 see page 132 This menu is a list of all not acknowledged and acknowledged but not corrected faults Some units may also have an internal delay time which makes the delay time even longer e g the Multipurpose I O unit 3361 has an internal delay time of 30 seconds which results in 45 30 75 seconds delay time in total 6t For faults generated in other control units the buzzer can be suppressed Suppressed not suppressed is set via Win512 Contr
80. ed by LED Disablements L8 and is shown in menu H4 U1 The outputs in one or more control units can be disabled or the outputs in all control units The outputs will be disabled until re enabled again via this menu Access According to chapter Access see page 86 Scroll to menu H2 Disable or re enable ACCEPT H2 A Disable zone ACCEPT B1 Scroll to menu B8 Disable Re enable all control exting and ventilation outputs ACCEPT B8 A Disable 0 or Re enable 1 outputs 1 Press 1 or 0 write the CURIS MCS Se A ACCEPT CU number or 99 for all CUs and press A to accept A Disable Re enable all control exting Scroll or press Return to and ventilation outputs ACCEPT B8 menu H2 Scroll or press Return to log off 0 Including Addressable siren 3377 and Addressable sounder base 3378 Also the Extinguish equipment output on the German FBP interface board 1583 NOTE Outputs disabled for a specific control unit e g CU 03 can not be collectively re enabled via CU 99 You have to re enable the outputs for the specific control unit s e g CU 03 99 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 25 9 Disable Re enable alarm devices H2 B9 Outputs programmed as type 3 alarm device sounder can be disabled all at the same time Disabled alarm devices means th
81. efinable text messages shown in the alphanumeric display in the C U ext FBP Display units Win512 shall have the same or higher version number as the EBL512 S W version number e g 2 6 x and 2 6 x respectively Backup require the same version number in Win512 and EBL512 Old files can be opened and saved in a higher version of Win512 and thereafter downloaded TLON Manager is used for network programming The former Charger board for EBL512 had the type no 1557 13 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 4 Control Unit Figure 1 The EBL512 Control Unit 1548 1549 The look might vary according to configuration country etc The control unit c i e is housed in a grey metal cabinet The door has a Plexiglas ahead of the FBP part see Figure 1 To open the door access level 1 a key is required supplied When the door is open you fully see the front the Fire Brigade Panel FBP and Control Panel CP see Figure 2 page 15 To open the inner door for the purpose of maintenance or servicing a screwdriver is required 14 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x c e eeeee Extinguishing e e Silence buzzer Ventilation Alarms queued Silence 4 alarm devices
82. ement not performed ACCEPT Don t forget to re enable via menus H2 B4 B6 B8 or B9 H8 S3 H9 C5 or use automatic re enablement for zones and alarm points Disablements are indicated by LED Disablements L8 and are also shown in the display An example Zone 001 is disabled Morera More is indicating two or more disablements Disablements and faults are indicated by a 2 sec beep when an open control unit door is being closed 8 NOTE See chapter Alphanumeric display LCD in EBL512 page 20 regarding priority order 89 Panasonic Electric Works Fire amp Security Technology Europe AB Operating Instructions Fire alarm system EBL512 V2 6 x MEWO01165 25 1 Rev Disable zone H2 B1 When a whole zone is disabled all alarm points within the zone are disabled except the addressable manual call points Disabled zones are listed in menu H4 U1 from which it is also possible to get a print out Access Scroll to menu H2 Write zone number e g 001 90 According to chapter Access see page 86 Press A to accept Press 1 for aut re enabling and accept or change the time max 24 hours Press A to accept LED Disablements L8 will light up If more disablements shall be done continue like above If not press Return to menu B1 Scroll or press Return to menu H2 Scroll or press Return to log off Panasonic Electric
83. en the c i e has no contact with a unit with such an output e g a 3377 3378 3361 etc 16 Connection board 1555 terminal block P1 37 38 fuses F1 and F3 17 This is also valid when the c i e has no contact with a unit with such an output e g a 3361 etc S The Alert Annunciation function is described in the EBL512 Planning Instructions chapter Alert annunciation The LED L16 will be on if 18 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x Push buttons Keypad on the Control Panel CP Key push button Operation function Fault acknowledge Used to acknowledge the faults shown in menu H6 Also used yellow to acknowledge SERVICE signal see menu H8 S4 Paper feed white Used for paper feed when a built in printer is available in the C 1 e Access white Used to log on i e to get access to the menu tree via an access code to carry out disablements etc In conjunction with fire alarm some information is available and some actions are possible to perform via the Fire alarm menu X1 X9 without log on see chapter Fire alarm page 39 ial Return white Used to stop input of data leave a menu one step up and to log off Li 1 9 and0 Numeric keys for the figures 0 9 TOE Used to clear delete just written data A Used to accept a menu and accept input of data Left right keys are used
84. en uploaded Check the settings change when required See 3 amp 4 above Click Download In the log view will be shown System information has been downloaded Close the dialog box 8 Remove jumper JP1 BOOT Do a reset restart see 3 above Regarding the reset restart see chapter Restart page 83 Follow the same procedure in each control unit 20 2 Control Units in a TLON network All control units connected to a TLON network shall have the same S W version For download of new S W in each control unit follow the procedure described above Since some control units do not have contact with some control units during the downloading the following faults might be generated FAULT CU xx has no contact with CU xx FAULT CU xx has wrong information The faults have to be acknowledged 20 3 Earlier S W version download For some reason it might by required to download an earlier S W version This is done the same way as for a new S W version but with the following additions 1 The Win512 version designed for the S W version to be downloaded has to be used 2 After the download the EBL512 settings shall be read edited if required e g the no of addresses and then downloaded again 3 The dialog box Please enter your password might be displayed 81 E g if a new control unit with the latest S W version downloaded by delivery shall be added to a system with an older S W version downloade
85. ence alarm 2 zone dependent or 2 unit dependent When only one zone or one zone address alarm point is in alarm status 0 8 5 sec e fire alarm and acknowledged alarm 0 4 0 4 sec e fault continuous e activated interlocking input 0 8 0 8 sec if this option is selected via Win512 e Quiet alarm 0 8 5 sec Press Silence buzzer P2 to silence the buzzer In case of a new alarm or if the push button Silence buzzer is pressed again the buzzer will automatically sound again NOTE This is also valid for pre warning co incidence alarm etc Silence buzzer by open door In Win512 System dialog box can the function Silence Buzzer by Door Switch be selected The buzzer will then be turned off as long as the control unit door is open This function is a violation to the EN54 2 standard Old front For the function described above the new front with the push button Silence buzzer P2 is required The discontinued front without the push button Silence buzzer results in the following function The buzzer is silenced via the control unit door Switch i e the buzzer will be silent as long as the door is open EBLS512 c i e 1550 This unit has no front The built in buzzer is always disabled Valid for the New Zealand convention only Silence buzzer by the outside switch When the New Zealand FB Silence switch outside switch is turned ON i e from not activated to acti
86. epending on a if you still are in menu H8 S9 and single reset is used b if you still are in menu H8 S9 and multiple reset is used or if you are logged out by pressing Return two times or automatically after 10 minutes 143 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x Alternative a Activate address in alarm mode Scroll or press Return to ACCEPT S9 menu H8 Scroll or press Reset Return to log off Alternative b Blank Reset NOTE 114 Multiple reset is default By Single reset each point has to be reset individually 14 Alarm reset is selected in the Win512 System dialog box 144 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev 31 11 m 1 ae AY Operating Instructions Fire alarm system EBL512 V2 6 x Synchronize the control units H8 S10 Synchronization can also be done via Win512 The control units have to be synchronized when e The following fault message is shown FAULT CU xx has wrong information See chapter help topic View Faults in the Win512 help 5 e During the synchronization there will be displayed information for the control unit respectively The information is shown on the second row in positions 1 to 30 i e one position for each control unit 00 29 Synchronization not started
87. ested and replaced when required One of the following alarm reset alternatives is valid This is selected via Win512 Multiple reset is default NOTE In the Belgian British Standard and British Standard Marine Application conventions the alarm devices have to be silenced P3 before the reset button P4 can be used Multiple reset All the fire alarms will be reset by pressing Reset P4 According to the EN54 2 standard NOTE The push button has to be pressed in for min 0 5 sec When all fire alarms are reset LEDs Fire L1 and Alarms queued L2 are turned OFF and the display is empty All outputs for fire alarm have also been reset i e de activated If a key cabinet is installed the key to the building has to be put back into the key cabinet within 5 minutes If not a fault will be generated and a fault message will be shown in the display see chapter Key cabinet alarm reset page 52 Single reset Each fire alarm has to be reset one by one This function set in Win512 is a violation to the EN54 2 standard Press Reset P4 to reset the fire alarm shown in the display on the first row to the left NOTE The push button has to be pressed in for min 0 5 sec Output s programmed for this fire alarm will also be reset i e de activated 60 Tf there is a fault condition e g caused by the fire a fault message will now be shown in the display When Single reset or Single enca
88. external fault see fault message 70 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 17 2 Fault acknowledge The LEDs Fault tx activated L11 and General fault L7 are turned ON LEDs Fault Disablements Alarm devices L13 System fault L14 and or Fault Disablements Fire brigade tx L15 might be turned ON as well Output s for routing equipment Fault tx is are activated Output s for general fault is are activated Output s for general charge fault might be activated A fault message date and time is shown in the EBL512 display s After the time might be shown More faults more than one fault is generated in the system After the time might be shown Serviced the fault is already serviced corrected Serviced will never be shown if the faults are set to be Not latched e Login according to chapter Access page 86 e Use menu H6 access level 2 for fault acknowledge see chapter Acknowledge FAULTS H6 page 132 Menu H6 is a list showing a maximum of 200 faults not acknow ledged faults and or acknowledged but not corrected faults The first fault in the list is the most recent fault When a fault is acknowledged and corrected it will be removed from the list and a new fault can be shown Corrected faults are shown in the event log menu H4 U7 e All faults have
89. f more zones are to be disabled repeat the procedure Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev 15 2 1 5 15 2 1 6 15 2 1 7 15 2 2 Operating Instructions Fire alarm system EBL512 V2 6 x Re enable zone X5 ZONE 123 LAST 789 No 003 Re enable zone ACCEPT X5 Press A E g ZONE I2 LAS 789 No 003 Re enable zone ZZZ ACCEPT This is a list of disabled zones Scroll to or write the wanted zone number and press A If more zones are to be re enabled repeat the procedure Disable Re enable control X6 ZONE 123 DAST 789 NO 003 Disable Re enable control ACCEPT X6 Press A E g ZONE 3 ILS LAST 789 No 003 Disi SO On ne cial ih Control gt Ii ACCEPT To disable press 0 and A To re enable press 1 and A For more information see chapter Disable Re enable all control exting and ventilation outputs H2 B8 page 100 Disable Re enable alarm devices X7 ZONE 123 LAST 789 No 003 Disable Re enable alarm dev ACCEPT X7 Press A E g ZONE 123 EAST 789 No 003 Dis 0 or re en 1 alarm dev ACCEPT To disable press 0 and A To re enable press 1 and A For more information see chapter Disable Re enable alarm devices H2 B9 page 101 Alert Annunciation AA alarm When the AA function is enabled indicated by the LED Fire br
90. face input intended for one or more conventional alarm points End of line resistor in the last alarm point ADB input Addressable zone interface Old installations Ext line conventional zone line intended for one or more conventional alarm points End of line resistor in the last alarm point Output unit Addressable unit with programmable control outputs Connected to a COM loop see below Output Control output Defined or programmable function Relay output or voltage output supervised monitored in the c i e or an output unit Short circuit isolator ISO Addressable unit for automatic disconnection of a part segment of a COM loop see below in case of a short circuit on the loop According to EN54 2 One ISO is required per 32 alarm points on the COM loop Display unit DU Addressable unit for fire alarm presentation incl user definable text messages if programmed COM loop Loop a cable with two wires to which all the addressable units can be connected Starts in the c i e and it returns back to the c i e Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 2 8 2 9 2 10 2 11 2 12 2 13 Operating Instructions Fire alarm system EBL512 V2 6 x BS4 loop Loop a cable with two wires to which all the addressable Autronica BS100 units can be connected Starts in the c i e and it returns back to the c 1 e Control Unit C U
91. for sensor 000003 is changed from Al TOB 113 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x Return Enter technical number 000000 Write the sensor s techn number and or press A to accept or press Return to carry out the change of algorithm s Return Alarm algorithms have been changed The affected CU s will now restart ACCEPT A Sensor values Menu U5 will be shown Printout 1l yes for a few seconds and then the affected control unit s will restart See chapter Restart page 83 NOTE The new algorithm will not be in use until after the restart In case of an automatic log off and one or more algorithms are changed the affected control unit s will restart Sensor values and setting alarm algorithm for the Analog multi detector 3316 The procedure is similar to the procedure for 3304 and 3308 respectively When using gt the smoke detector information will be shown before the heat detector information The algorithms can only be changed one at a time i e if both algorithms are to be changed start with the smoke detector algorithm and continue with the heat detector algorithm as follows If a smoke detector algorithm shall be changed do as for 3304 If a heat detector algorithm shall be changed use gt to pass the smoke detector windows Then do as for 3308 114
92. g menus normally used by service personnel Same menus as in access level 2 plus the following H8 Maintenance S1 Disable or re enable outputs for routing equipment Fire S11 Change access code for maintenance access level 3 26 If code for access level 3 or 4 has been used to logon to access level 2 new logon to access level 3 is not required 25 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 7 5 Access level 4 From access level 27 the user can logon to access level 4 which gives access to the following menus normally used by Service Commissioning Engineers Same menus as in access level 2 and 3 plus the following A7 Display statistics for COM loop A11 Change access code for service access level 4 7 6 Access level 5 Used by Service Commissioning Engineers when a PC shall be connected to the control unit i e when Win512 shall be used for backup download of Site Specific Data S W settings configurations C U and system data on line status checking etc Connect the PC and logon to EBL512 from Win512 7 If code for access level 4 has been used to logon to access level 2 new logon to access level 4 is not required 26 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 8 Silence Al
93. gr Present system status on display and printer ACCEPT H4 Disablement Printout l yes Activated 2 zone address dependent zone address Printout 1l yes When A is pressed the active zone amp address or zone will be shown in the display e g Co incidence alarm detector ZZZ AA L or Co incidence alarm zone ZZZ L Printing started To stop printing press C and 0 simultaneously ACCEPT Activated 2 zone address dependent zone address Printout 1l yes One alarm point or zone has activated a Co incidence alarm ZZZ zone number AA address According to chapter Access see page 86 Press 1 for an automatic print out Press A for presentation in the display This is a list in which you can scroll If there are no alarms and if Return is pressed menu U4 will be shown again Press A and menu U4 will be shown again Scroll or press Return to menu H4 Scroll or press Return to log off When two or more zones or units zone addresses dependent on each other are in alarm status at the same time normal fire alarm will be activated in the system 106 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 27 5 Access Scroll to menu H4 A Disablement Printout l yes Scroll to menu US Rev Sensor values H4 U5 Operating Instructions Fire alarm system EBL512 V2 6 x The very f
94. has been turned off for some security reason e g too high current consumption Valid for Charger board 1657 FAULT Mains ext power supply CU xx The fault is activated after 1 300 minutes because of e Loss of mains i e no 230 V AC to the ext power supply equipment e Blown fuse 230 V AC The time is programmable in Win512 Max 30 min according to the ENS54 2 standard Default value depending convention 64 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x FAULT Mains output unit xxxxxx The fault is activated after 1 300 minutes because of Loss of mains i e no 230 V AC Blown fuse 230 V AC Blown fuse F1 or F5 on the output unit rectifier p c b Battery charging is turned off i e the total current consumption incl the battery charging current is too high gt 4 5 A Valid for the Ext power supply unit 3366 Mains OK output in 3366 is high Mains OK input in 3364 is high FAULT No reply board x loop x CU xx This is valid for the I O Matrix board 4582 no x connected on COM loop x in the control unit no xx e Check the board s address i e the I O Matrix board no Jumpers JP1 and JP2 on the board e Check if the board is disconnected from the loop FAULT No reply techn no xxxxxx In spite of the control unit is communicating in both directions one or more units
95. he Short name set in Win512 can be lt 5 characters When scrolling the message Please Wait might be shown for a second and No more sensors found in the system before the lowest and after the highest possible technical number in the system NOTE If an algorithm is set changed via menu H4 US the site specific data SSD in the c i e is not equal to the SSD file downloaded from Win512 i e a back up is required to update the SSD file xxxxxx 512 If an algorithm is set changed via menu H4 U5 the information in menu H5 A4 will be changed from Downloaded xxxx to Modified by CU xxxx Follow the instructions for 3304 3308 3309 and 3316 respectively 110 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x Show sensor values and setting alarm algorithm for the Analog photo electric detector 3304 Access According to chapter Access see page 86 Scroll to menu H4 Present system status on display and printer ACCEPT H4 A Disablement Printout 1l yes U1 Scroll to menu US Sensor values To make a printout press Printout l yes 1 else press A to accept Enter technical number 000000 Write the sensor s techn number and or press A to accept A Sensor 000001 This is a list in which Momentary XX X m Weekly XX X m you can scroll or use gt to see the next information w
96. ia menus H2 B1 B3 This possibility can be used when a temporary disablement is wanted e g craftsmen working in the premises etc The function Enhanced disablement is enabled as default i e disabled alarm points will not activate Pre warning fire alarm or fault If this function is not enabled via Win512 fault can be activated but not pre warning or fire alarm This is a violation to the EN54 2 standard Addressable manual call points can be disabled but shall normally not be disabled However when a whole zone is disabled the addressable manual call points will not be disabled for safety reasons Up to 512 whole zones can be disabled via menu H2 B1 Up to 200 alarm points zones address can be individually disabled via menu H2 B2 and or COM BS4 loops zone interface inputs and or MIO inputs can be disabled via menu H8 S2 Alarm points disabled via time channels are not limited and must not be counted Up to 200 outputs can be individually disabled via menu H2 B3 Disabled output will stay in or return to the normal condition for the output respectively Disabled outputs via menu H2 B8 and menu H2 B9 are not limited and must not be counted Up to 200 Interlocking outputs can be individually disabled via menu H9 C4 All interlocking outputs disabled via 000 00 are not limited and must not be counted It is not possible to exceed the limits A warning will be shown Max disablements reached Disabl
97. ialog box Clear SSD 84 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 23 Access To use the key pad in the control unit to get access to the menu tree it is necessary to logon with an access code for level 2 3 or 4 See also chapter Access levels page 22 Open the door in the control unit level 1 press the Access button P8 and continue as follows YYYY MM DD EBL512 CU XX hh mm ss A user definable text C O Enter the code 4 digits Access code The digits are replaced in the display NO ACCESS The access code was not correct Try again Perform monthly test The access code was ACCEPT H1 correct This is menu H1 Press A to accept to perform monthly test or scroll jump to the follow ing menus H2 H10 Explanations Action in the table use push button key e g signed Access Text in display in the table what is shown in the alphanumeric display in the control unit c i e Comments in the table Comments to the text in the Action and Text in display columns Use Tt and J to scroll between the main menus H1 H10 Use A to accept Some main menus have sub menus Use T and 4 to scroll between the sub menus e g B1 B9 Use A to accept NOTE The menus are circular i e if you scroll with J and the last menu is reached the first menu
98. igade tx delay L16 the indications print outs actions etc are as for a normal fire alarm except the c i e output for routing equipment fire brigade tx will not be activated The AA alarm has to be acknowledged within an acknowledge time and reset within an investigation time otherwise the output s for routing equipment fire brigade tx will be activated See EBL512 Planning Instructions for more information regarding the AA function Acknowledgement l In the Polish CNBOP and Czech conventions the push button Evacuate P5 can be used for AA Acknowledge 44 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01165 15 2 3 15 3 Operating Instructions Fire alarm system EBL512 V2 6 x and reset of the AA alarm can be done on a Display unit 2235 an AA unit 1735 1736 or an AA controller 1740 See also chapter Alarm reset page 50 Co incidence alarm 2 zone address dependence When only one zone or one zone address alarm point is in alarm status the buzzer sounds 0 8 5 sec and there is a Co incidence alarm presentation in the display Co incidence alarm detector ZZZ AA user definable text message or Co incidence alarm zone ZZZ user definable text message See also chapter Activated 2 zone address dependent zone address H4 U4 page 107 If more than one Co incidence alarm are generated the LEDs Alarms queued L2 are
99. in the system is disabled disconnected NOTE Also valid for Single encapsulated reset Test mode yellow One or more zones are in test mode Door open yellow A door is open L11 Fault tx activated yellow One or more not acknowledged faults in the system and the output Fault tx routing equipment is activated i e this output must not be disabled L7 L8 L9 10 L Test of routing equipment in progress see menu H1 L12 Service yellow One or more sensors have reached the service level See menu H4 U6 Fault Disablements One or more outputs type 3 alarm device in the Alarm devices yellow system are disabled Blinking One or more supervised outputs type 3 alarm device have generated fault s L14 System fault yellow EBL512 is not running because of S W CPU memory fault Fault Disablements Output s for fire brigade tx routing equipment Fire brigade tx yellow is are disabled via menu H8 S1 or H2 B3 or via an open door Blinking Routing equipment power supply output or one or more supervised outputs type 4 routing equipment have generated fault s L16 Fire brigade tx delay The alert annunciation function is enabled i e time yellow channel controlling this function is on In Australian and New Zealand conventions this button is used to disable all zones in alarm 4 See also chapter Door open page 34 15 This is also valid wh
100. indow for the selected sensor Press Return to Enter technical number gt Sensor 000001 Min XX X m NOTE Perf Factor X XX m Max XX X m XX X m XX X obscuration per meter Perf Factor see below this table gt Sensor 000001 N 15 short name see Current algorithm NAIS separate table page 109 Press Return to Enter technical number or press Access to change the algorithm Access Access code _ If login was made with code for level 3 no code is needed Enter code for level 3 4 Access code The digits are replaced digits in the display Change algorithm 000001 Current N 15 Use gt or L 15 L 35 N 15 N 35 H 15 H 35 nym Change algorithm 000001 Current N 15 Minis IE SS NAIS INI SNS etl H5 111 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x Write the sensor s techn number and or press A to accept or press Return to carry out the change of algorithm s Menu US will be shown for a few seconds and then the affected control unit s will restart See chapter Restart page 83 NOTE The new algorithm will not be in use until after the restart In case of an automatic log off and one or more algorithms are changed the affected control unit s will restart Perf Factor Performance factor Low min 0 The detector
101. ing Instructions chapter Power supply for more information S W versions Due to continual development and improvement different S W versions can be found When installing a new control unit in a system with older control units you might have to update the S W in the old control units It is highly recommended to have the same S W version in all control units but as from S W version 2 X x the same S W version is required in all control units Documents The following documents except this document are available e Planning instructions e Drawings Normally information that is found in one document is not to be found in another document i e the documents complement each other Applications The EBL512 system is intended for small medium and large installations The intelligent control units offer the system designer and end user a technically sophisticated range of facilities and functions Programming PC S W Win512 and commissioning of the control unit system is very easy Start with one control unit and then when required add more units The TLON network makes it possible to install the control units in one building or in many buildings PC S W Win512 is used for programming and commissioning of one or more control units e create download backup upload of site specific data SSD e download of S W settings conventions configurations C U amp system data etc e create download the user d
102. ing fault indication etc see chapter Fault page 54 See also chapter Fault acknowledge page 72 All faults i e not acknowledged faults acknowledged faults and corrected serviced faults are stored in the event log and can be listed see chapter Event log H4 U7 page 117 In menu H6 are up to 200 faults listed not_acknowledged and acknowledged but not corrected not serviced faults Access According to chapter Access see page 86 A J This is a list in which you can scroll The first fault in the list is the most recent fault If a fault is corrected the text Serviced is shown To acknowledge the fault shown in the display press Fault acknowledge Fault acknowledge 7 The fault is now Acknowledged If when the fault is corrected it is no longer shown in this list Scroll in the list e g to acknowledge more faults or press Return to menu H6 Scroll or press Return to log off 108 Tf faults are selected via Win512 to be not latched the text Serviced will never be shown 10 When the list is empty i e when all faults are acknowledged and corrected serviced you will automatically return to menu H6 131 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 30 Perform ZONE TEST test mode H7 Normally zones are tested during the monthly test vi
103. ion in the display Quiet alarm detector ZZZ AA user definable text message Programmable outputs for quiet alarm e g 3361 outputs controlling supply air fans and standard fans i e any output with a control expression containing the trigger conditions no 42 Quiet Alarm Zone or no 43 Quiet Alarm Zone Address Alarm Acknowledgement Facility AAF Used on the Australian market only One or more Alarm Acknowledgement Facility Controls are used in the system During the Acknowledgement Period 10 60 sec there is an indication in the control unit display AAF zone zz activated During the Investigation Period 0 3 min there is an indication in the c i e display AAF zone zz investigation in progress See EBL512 Planning Instructions chapter Alarm Acknowledgement Facility AAF for more information regarding the AAF function 5 The AAF Control is available on the Australian market only 48 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 16 Operating Instructions Fire alarm system EBL512 V2 6 x Alarm reset 16 1 16 2 16 2 1 16 2 2 Pre warning reset Pre warning is automatically reset Fire alarm reset In the New Zealand convention fire alarms normal fire alarms ALM acknowledged alarms ACK and isolated alarms ISO NOTE The detectors having activated fire alarm shall after reset be inspected t
104. ire alarm menu is disabled via Win512 it is a violation to the EN54 2 standard Press Access no access code and the user definable text message will be replaced as follows ZONE 123 LAST 789 No 003 Display alarms ACCEPT X1 A Y A gt and Return are used like in the normal menu tree see chapter Access page 86 The original presentation the user definable text message will be automatically displayed again 20 seconds after the latest time any of the push buttons A Vv AN gt and Return was used Scroll 4N to the wanted menu and press A 42 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 15 2 1 1 Display alarms X1 First row Explanations in chapter Fire alarm page 39 Second row All fire alarms also several alarm points in one zone will be displayed in zone address order i e up to 15360 alarms Press A E g Point Zone address for alarm no 00001 yr Point Zone no for alarm no 00002 and so on 15 2 1 2 Display faults X2 Press A E g Only the fault message for the fault respectively is displayed here not date time and status information 15 2 1 3 Display disablements X3 Press A E g 15 2 1 4 Disable zone X4 Press A E g Write zone number and press A I
105. ires Wrong no end of line resistor One or more connected units have been removed stolen FAULT Wire to exting system CU xx Short circuit cut off on the wires from the 1583 German Fire Brigade interface board in control unit No xx to the connected extinguishing system equipment FAULT Wrong type board x loop x CU xx This is valid for the I O Matrix board 4582 no x connected on COM loop x in the control unit no xx e Check the board type set with jumpers JP4 and JP5 on the I O Matrix board The type should be the same as programmed via Win512 FAULT Wrong type of unit tech no xxxxxx The unit is not the same type as programmed Change the programming or the unit FAULT Zone line input tech no xxxxxx Detector mounted in an ADB 2330 faulty removed detector or Ext line input to an ADB 2330 break on a wire or wrong no end of line resistor or Zone interface 2335 2226 input break on a wire or wrong no end of line resistor or Zone interface 2226 No ext power supply or Multi purpose I O unit 3361 monitored zone line input Z break on a wire or wrong no end of line capacitor short circuit if not programmed for fire alarm at short circuit User programmable text External fault Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x Programmable input is used for an
106. irst week average sensor value is calculated within 2 minutes after SSD download amp restart During these 2 minutes can no fire alarm be activated and the sensor value 000 will be shown The Performance factor and Min Max values are updated each night 00 00 i e the values shown are from the previous day Regarding the British Standard Marine Application convention see chapter Algorithm setting via menu H4 U5 page 111 Text in display Present system status on display and printer ACCEPT H4 Sensor values Printout l yes Comments According to chapter Access see page 86 Press A or 1 to accept Here follows the alternative A no printout The alternative 1 printout follows below wat E g 000001 A Start Sensor 000000 Type 3304 Sensor 000001 Momentary XX X m Weekly XX X m Depending on gt the type the following will 3 be shown Sensor 000001 Min Perf Factor X XX m Max XX X m XX X m Sensor 000001 Current algorithm nnnnnn A Type 23xx 22xx amp AUT Sensor 000002 Momentary XXX Weekly XXX AN Type 3308 3309 Sensor 000003 Mare SE Momentary XX C Max XX C gt HAN Sensor 000003 Current algorithm nnnnnn Type 3316 Sensor OOOOON Momentary XX X m Weekly XX X m 3 Sensor 00000N Min XX X m Perf Factor X XX m Max XX X m 107 Write the
107. is currently communicating in A direction Press A to change See NOTE above DAA 8 direction Press Return When you select a BS4 loop the text in this menu will still be to finish the locking and Return COM loop Direction for communication on COM BS4 loop ACCEPT A3 return to menu A3 Scroll or press Return to H5 Scroll or press Return to log off An Autronica interface board 1584 is required in the control unit 122 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 28 5 Show information about Site Specific Data H5 A4 Information regarding the current site specific data SSD is shown New SSD can be downloaded via a PC and Win512 Access According to chapter Access code for service H5 see page 120 Scroll to menu A4 Show information about site specific data ACCEPT A4 Name XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX YY year MM month Downloaded YY MM DD hh mm ACCEPT DD day TE bel CENO below hh hour mm minute Show information about Scroll or press Return to site specific data ACCEPT A4 H5 Scroll or press Return to log off If there is no SSD downloaded to the control unit the following text message will be shown No SSD downloaded NOTE In the British Standard Marine Application convention it is possible to change the alarm algorithm for some type of a
108. larm state when the test mode is ended there will not be a fire alarm activated Instead the alarm point will be disabled and has to be re enabled again via menu H2 B5 When the Fire door closing function is used the fire door will be closed when the detectors controlling the door are tested via the test mode 133 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 31 Maintenance H8 31 1 Access code for maintenance Access code for access level 3 is required for menu H8 NOTE If login to level 2 was made with code for level 3 or 4 no code to access level 3 is required here Access According to chapter Access see page 86 A A When required see above enter the access code for level 3 Enter the code 4 digits i The digits are replaced in the display The access code was not correct Try again The access code was 1 1 correct This is menu S1 Press A to accept or scroll to the following menus S2 S8 134 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 31 2 Disable or re enable outputs for routing equipment H8 S1 Outputs for routing equipment fire brigade tx fault tx can be disabled via this menu They stay disabled until re enabled again via this menu Can be useful during an in
109. lay and printer H4 104 27 1 Disablement H4 U1 104 27 2 Disablement by time channel H4 U2 105 27 3 Doors open H4 U3 106 27 4 Activated 2 zone address dependent zone address H4 U4 107 27 5 Sensor values H4 US5 108 27 5 1 Reset of a week average sensor value 110 27 5 2 Algorithm setting via menu H4 U5 111 27 6 Sensors activating SERVICE signal H4 U6 116 27 7 Event log H4 U7 117 27 8 Configuration H4 U8 118 28 Service H5 119 28 1 Access code for service H5 120 28 2 Calibration of supervised outputs H5 A1 121 28 3 Sensitive fault detection mode H5 A2 122 28 4 Direction for communication on COM BS4 loop H5 A3 123 28 5 Show information about Site Specific Data H5 A4 ___ 124 28 6 Display current consumption in unit H5 A5 125 28 7 Display current consumption COM BS4 loop H5 A6 __ 126 28 8 Display statistics for COM loop H5 A7 127 28 9 Select unit on COM loop to use for trigging H5 A8 __ s 128 28 10 Activate address setting mode for DU H5 A9 129 28 11 Change access code for PC communication H5 A10 _ 130 28 12 Change access code for service H5 A11 131 29 Acknowledge FAULTS H6 132 30 Perform ZONE TEST test mode H7 133 31 Maintenance H8 135 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 31 1 Access code for maintenance 135 31 2 Disable or re enable outputs for routing equipment H8 S1 136 31
110. locking outputs are listed in menu H4 U1 from which it is also possible to get a print out Interlocking outputs Type Interlocking can be re enabled via this menu but not via menu H2 B6 If 000 00 is entered all interlocking outputs disabled via menu H9 C4 and 000 00 will be re enabled at the same time Text in display Access According to chapter Access see page 86 Scroll to menu H9 Scroll to menu C5 This is a list in which you can scroll If there are no disabled outputs menu C5 will be shown again Press A for re enable or Return not re enable to menu C5 Scroll or press Return to menu H9 Scroll or press Return to log off 152 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 33 Change access code for daily duties H10 For security reasons the default code should be changed Access According to chapter Access see page 86 Scroll to menu H10 Enter the old code the A The digits are replaced new code and the new jo in the display code again The code was not correct Try again The code was correct and is now changed to the new code Scroll or press Return to log off NOTE After change of access code it is recommended do a Safe shutdown of the control unit see menu H8 S8 This will save the SSW data e g the new c
111. login was made with code for level 4 no code is needed The digits are replaced in the display The access code was not correct Try again 119 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 28 2 Calibration of supervised outputs H5 A1 Supervised monitored outputs The voltage outputs SO S3 in each control unit The voltage outputs VOO VO1 in the COM loop output unit 3364 The voltage outputs 0 3 in the COM loop output units 2262 amp 2263 When all alarm devices sounders etc have been connected including required end of line devices and when the SSD download is ready a calibration has to be done Function If the actual value differs from the calibrated value a small tolerance or if the calibrated value is outside the calibration range a fault will be generated NOTE Each output s logic is programmable via Win512 i e normally low default or normally high 24V but during the calibration the outputs will automatically be low i e a normally high output will be low during the calibration a few seconds Access According to chapter Access code for service H5 see page 120 Calibration of supervised outputs ACCEPT Al A Calibration in progress Please wait Calibration of supervised outputs Calibration is ready ACCEPT A1 Scroll or press Return to H5 Scroll or
112. loop The addresses 0 127 will be reported to Win512 For all 430x 33xx units and some of the other units the type of unit will also be reported All differences compared to the Win512 SSD will be listed in the Win512 log view and can be saved and or printed out NOTE During this check the COM loop will be disconnected disabled and no alarms or faults can be activated Disconnected COM loop is indicated by the LED Disablements L8 Single Control Unit Start the downloading from Win512 A text message will be shown in the alphanumeric display in the control unit Download in progress Block nnnn out of xxxx When the download is completed the following text message will be shown 72 Tt is very important that the two first digits in the EBL512 S W version and the Win512 version are the same e g for EBL version 2 6 1 shall Win512 version 2 6 x be used Access code for level 5 shall be entered via the PC Win512 After the download to a control unit an automatic reset restart will take place A number of faults might then be generated e g due to not connected units This will cause heavy traffic on the network which might affect delay the SSD download to the other units 75 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev 19 3 19 4 Operating Instructions Fire alarm system EBL512 V2 6 x Download completed successfully
113. lso be shown after a short circuit on the loop when short circuit isolators are used communication in both directions A double break will give the message FAULT No reply It can also be indicating a too long COM loop cable i e all units are not found until the communication is performed in both directions NOTE Communication in both directions lasts for about ten minutes before a new attempt to communicate in one direction is performed If the break remains a new ten minutes period starts and so on If the fault is acknowledged and the break is corrected during a ten minutes 58 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x period it will not disappear from the list until the end of the ten minutes period 8 zones expansion board DET8 This is indicating a break cut off or a missing end of line resistor on input x zone line on the 1580 board placed in control unit xx It can also be a detector that have been removed stolen from its base NOTE The input can as an alternative be used for a single slave unit control unit or several control units connected in parallel i e it is used for Redundancy in distributed system In such a case the output for routing equipment fire brigade tx in the slave unit respectively works as a detector 1584 Autronica interface board BS4 Cut off b
114. man FBP interface board 1584 Autronica interface board four BS4 loops 1587 External FBP DU interface board Regarding the expansion boards see also the EBL512 Planning Instructions and drawings Printer Control unit 1549 is equipped with a printer In control unit 1548 it is possible to mount a Printer 1558 In Ext Fire Brigade Panel 1826 it is possible to mount a Printer 1535 Power supply The main power source is a built in rectifier 1537 230 V AC 1 5 A 1 24 V DC 4 5 A The second power source is a backup battery 2 x 12 V In the c i e is space for two 24 27 Ah batteries Larger batteries up to 60 Ah has to be placed outside the c i e The batteries and the rectifier are connected to the Charger board Max two 1582 1587 boards together per control unit 1582 will be replaced by 1587 4 Max one 1583 board per control unit 1583 board is not possible to use in Swedish SBF convention 5 Max four 1584 boards per control unit 1584 board is only possible to use in Swedish SBF convention 12 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 3 2 3 3 3 4 3 5 Operating Instructions Fire alarm system EBL512 V2 6 x 1657 which handles the charging of the batteries etc Low or High current charging mode is selected depending on the wanted backup battery capacity backup time and or the EBL512 current consumption See the EBL512 Plann
115. nal smoke and or heat detectors manual call points and programmable inputs can generate fire alarm If somebody illegally breaks into a key cabinet this will also generate a fire alarm a key cabinet alarm A fire alarm could be an Alert Annunciation alarm i e the activation of the routing equipment fire brigade tx is delayed during an acknowledgement time and an investigation time respectively In the Australian convention only an Alarm Acknowledgement Facility function can be used During the Acknowledgement Period and the Investigation Period respectively there will be an indication in the c i e display The analog detectors can also generate two other types of alarm i e Pre warning and Heavy smoke alarm Heavy heat alarm Two unit dependent addressable alarm points normally only smoke detectors and 2 zone dependent zones can generate a Co incidence alarm Quiet alarm is normally used for fan control and require hardware found on the Australian market only EBLS512 can present up to 512 fire alarms alarm points and or zones Zone numbers 001 999 can be used and in each zone the alarm point address numbers 01 99 can be used The fire alarms will be shown in the EBL512 display LCD and in Ext FBP 1826 1828 Alert Annunciation unit 1735 1736 and Ext Presentation unit 1728 Regarding the different alarm types etc see the following chapters Pre warning Activation of Pre warning is an option th
116. nalog detectors see chapter Algorithm setting via menu H4 U5 page 111 If one or more alarm algorithms are changed the following infor mation will be shown instead of the information shown above Name XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX YY year MM month Modified by CU YY MM DD hh mm ACCEPT DD day hh hour mm minute If an algorithm is set changed via menu H4 US the site specific data SSD in the c i e is not equal to the SSD file downloaded from Win512 i e a back up is required to update the SSD file XXXxxx 512 Modified by CU will be changed back to Downloaded after the next SSD download and the alarm algorithms will be according to that SSD 104 Logical Name as written in Win512 dialog box System Properties tab System Data 123 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 28 6 Display current consumption in unit H5 A5 The resolution is not very high i e the displayed values give only a rough idea of the current consumption Control unit The total current consumption including the charging current at 24V for the selected control unit c i e when it is connected to the mains 230 V AC i e this function is not working by battery backup Charging The battery charging current for the selected control unit c i e This is at 24 V i e before the DC DC converter for batter
117. nasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 22 1 Boot menu The Boot menu should be used by authorised personnel only NOTE Vital data can be erased via this menu The Boot menu is opened as follows Perform a reset restart e Power off power on or e Jumper JP4 on the main board The following text messages will be show in the LCD Checking program memory And after that Bootimans nie When the text Booting appears press Access and 0 1 sec later also press 1 and the Boot menu will be shown 1 Reset 2 Clear mem 4 Read AD 5 MSClo ck 6 Checksum 7 Cursor 8 Texts Press 1 to perform a reset restart you will also leave the Boot menu Press 2 to open the Clear memory menu see below The alternatives 3 8 are for R amp D use only The Clear memory menu les S80 2 SS 3 Sys INEO 4 Bela omnimnfto S i Teks Press 1 to clear the SSD memory Press 2 to clear the SSW memory The alternatives 3 5 are for R amp D use only Erasing SSD and Erasing SSW respectively will be shown and then the Clear memory menu will be shown again Press Return to go back to the Boot menu NOTE After clearing the SSW perform a Power off power on reset restart directly 87 Can also be done in Win512 EBL512 settings d
118. nction of the control unit can not be guaranteed Call for service personnel engineer FAULT Earth fault output unit xxxxxx Check all cables connected to the output unit FAUT TPU sex ISS 7cloosugc x CU x EPU 1728 The unit is programmed as another type of unit than the SSD says or fault in the unit PAULL TExpansion board x oop x CUR This is valid for the I O Matrix board 4582 no x connected on COM loop x in the control unit no xx There is some internal fault on the board 60 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x FAULT External FBP x board x CU xx The control unit i e the 1582 board can not communicate with the ext FBP or data converter Check the connections Check the cable break Check the address DIL Switch in the ext FBP Is correct address set Several ext FBPs have the same address Faulty ext FBP FAULT External fuses control unit xx The fault is to be found in the external power supply blown fuses etc FAULT External power supply CU xx The fault is to be found in the external power supply connected to input in control unit xx BAUM E Ran CONTEO UNIE AX The LED Fault is lit on a fan control module connected to control unit xx Fan no xx has been activated but the corresponding I O unit 3361 input has not been activated within 30 seconds e
119. nd the fire brigade personnel as well as service commissioning engineers Due to continual development and improvement different S W versions are to be found This document is valid for S W version 2 6 x On the date rev date of the document x 0 Since the EBL512 control unit c i e is produced for many countries the look the texts the functions etc might vary Products Consists of one or more parts HW according to a Product Parts List A product has e atype number e g 1548 e an article number often the type no and sometimes is a country code added e g 1548SE e a product name e g EBL512 control unit 128 addresses without printer HW A HW e g a printed circuit board has e atype number e g 1556 e an article number often the type no and sometimes is a country code added e g 1556SE e aproduct name e g Main Board 128 addr e ap c b number e g 9261 3A and can also have a configuration e g CFG 1 and a revision e g REV 2 e sometimes a S W S W A S W has e aversion number e g V2 6 x e sometimes additional information such as Convention different functions facilities Language Number of addresses etc PC S W A PC S W is a program used for programming commissioning etc It has a version number File name K PRO FIRE 512 Doc 2 6 x MEWO1 165 Rev doc Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165
120. ng generated SERVICE signal its week average sensor value has to be set to the default value otherwise the new clean sensor will inherit the old sensor s value Itis possible to clear the week average sensor value for each sensor individually see chapter Clear weekly average H8 S5 page 140 See also chapter Acknowledge SERVICE signal H8 S4 page 139 NOTE Authorised service personnel only must do the reset to default value Used incorrectly it can cause nuisance fire alarms If some other short name is wanted it can be changed in Win512 Up to six characters can be used In the DBI Danish convention up to five characters Low sensitivity and or slow detection 35 s might not fulfil the EN54 7 specifications 7 Analog multi detector 3316 only 109 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 27 5 2 Algorithm setting via menu H4 U5 NOTE Algorithm setting via menu H4 US is only valid for the _ British Standard Marine Application convention The alarm algorithm can be set changed via menu H4 U5 for the following detectors 3304 in NORMAL mode 3308 3309 in NORMAL mode 3316 in NORMAL mode the Decision algorithm is not possible to use No alternative algorithm can be used No values offset level etc can be set via menu H4 U5 i e these values have to be set via Win512 T
121. ngle reset is used encapsulated reset can be done by pressing Reset P4 and 0 1 sec later also press Alarms queued P1 and hold them pressed for gt 0 5 sec By Single reset The fire alarm displayed in the LCD first row to the left will be encapsulated By Multiple reset The fire alarm displayed in the LCD first row to the left will be encapsulated or the points in alarm status within one zone will be encapsulated or the whole zone conventional will be encapsulated NOTE 2 When Single reset or Single encapsulated reset is used you can make a Multiple reset by pressing Reset P4 and 0 1 sec later also press A in the keypad and hold them pressed for gt 0 5 sec 12 Co incidence alarm One unit zone in a 2 unit zone dependence is activated 13 In some conventions this button is not used no designation text In Belgian British Standard Hungarian and Ukrainian conventions this button is used for the Evacuate function In Polish CNBOP Bulgarian and Czech conventions this button is used for Alert Annunciation Acknowledge 17 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x LED indicators on the Control Panel CP LED indicator Indicating General fault yellow Fault s i e not acknowledged fault s and or acknowledged but not corrected fault s Disablements yellow Something
122. nsion board 1580 3 Addr zone interface 2226 2335 2821 or 3361 MIO Press A to accept A Disconnect COM Loop 0 Write the required ACCEPT numbers Press A to Depending on the ul chosen type 0 1 2 or BS4 Loop 0 Board 0 CU 3 the following will be ACCEPT shown i accept DET8 input 0 Board 0 ACCEPT Disconnect input technical no 000000 ACCEPT A Disconnect type 0 0 COM 1 BS4 LED Disablements 2 DEMS as Loops UNIE ACCEPT indicates disconnected loops etc Continue to disconnect or press Return to menu S2 Return Disconnect loop Scroll or press Return to ACCEPT S2 return to menu H8 Scroll or press Return to log off Only valid for input 0 as a zone line input Z i e trigger cond no 19 136 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x Don t forget to re connect the loop zone line again via menu H8 S3 31 4 Re connect loop H8 S3 Disconnected disabled loops zone lines via menu H8 S2 are indicated by LED Disablements and listed in menu H4 U1 NOTE When you re connect a COM loop all the statistics shown in menu H5 A7 will be erased and set to 0 Access According to chapter Access code for maintenance see page 135 Scroll to menu S3 Re connect loop ACCEPT S3 Re connect type 0 0 COM 1 BS4 Press 22DET8S
123. o chapter Access code for service H5 see page 120 A Select type of loop Press A to accept Write loop number board number 0 3 and control or unit number Press A to n 1 a AT A N 4 h pa accept If the control unit don t exist or don t answer this message will be shown The current consumption accuracy is 5 mA Scroll or press Return to H5 Scroll or press Return to log off 105 An Autronica interface board 1584 is required in the control unit 125 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 28 8 Display statistics for COM loop H5 A7 The statistics can be used during commissioning service etc Pollings are the number of pollings questions sent out by the control unit to the units connected on the COM loop Parity are the received number of parity faults and faults in relation to pollings Bit are the received number of bit faults and faults in relation to pollings Answer are the received number of answer faults no answers and faults in relation to pollings The Parity Bit and Answer values shall normally be 0 or as close to 0 as possible If not there are some communication problems that have to be investigated Check the COM loop connections and the loop units All values are set to 0 after restart and or after re connection of COM loop
124. oactive radiation source Americium 241 When the sensor detector gets dirty and when service signal has been activated in the system contact your local dealer for replacement of the sensors detectors Metal objects must absolutely not be stuck into the sensor detector Static electricity might destroy the detector Defective faulty discarded and replaced sensors detectors shall be taken care of as radioactive waste They shall be packed in chock absorbing material to make a stable parcel PLEASE NOTE Damaged sensors detectors shall also be packed in a sealed packet whose surface must not be contaminated that is not be soiled with loose radioactive dust 160 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 40 Revision history 161 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 162 This page has deliberately been left blank Panasonic Panasonic Electric Works Fire amp Security Technology Europe AB Jungmansgatan 12 SE 211 19 Malm Sweden Tel 46 0 40 697 70 00 e Fax 46 0 40 697 70 99 info fste eu pewg panasonic com www panasonic fire security com wian E es E mi ISO 9001
125. ode i e set jumper JP1 BOOT in position on the main board 1556 3 Do a reset restart i e set jumper JP4 RESET in position momentarily approx 1 second 4 The buzzer will now sound intermittent and LED LD101 starts blinking indicating that the control unit is in Bootstrap mode 5 In the Win512 settings dialog box click Read The buzzer will be silenced the actual settings shown and in the Win512 log view will be shown System information has been uploaded Write the new settings in the fields respectively Do like 3 amp 4 above Click Download The buzzer will be silenced and a Win512 box will be displayed Click OK NOTE If Max loop units are changed a Please enter your password dialog box will be shown 8 When the download is ready in the Win512 log view it will be shown System information has been downloaded 9 Read see 3 4 amp 5 above to verify the new settings 10 Remove jumper JP1 BOOT Do a reset restart see 3 above Regarding the reset restart see chapter Restart page 83 Follow the same procedure in each control unit Control Units in a TLON network All control units connected to a TLON network have the same convention via the SSD download but the number of addresses max loop units and the language can vary if required 82 To change the Max loop units a separate password for download is required This password is in conjunction with a Key
126. ode in a Flash ROM see page 83 If the valid access code is unknown a back door code is available 153 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 34 Annual control The building occupier is highly recommended once a year to do some tests beside the monthly tests To avoid the Fault tx output s to be activated they can be disabled via menu H8 S1 or via an open door se chapter Door open page 34 Regarding the fault condition see chapters Fault page 54 and Fault messages page 55 NOTE Most of the faults have a delay Each control unit should be tested as follows e Perform monthly test menu H1 e Remove one battery fuse F2 or F3 on the charger board 1557 1657 The following fault message is to be shown FAULT Battery not connected CU xx NOTE xx is depending on control unit e Put back the fuse and acknowledge the fault Menu H6 e Remove fuse F5 not F1 F4 on the connection board 1555 The following fault message is to be shown FAULT Supervised output 0 CU xx NOTE xx is depending on control unit e Put back the fuse and acknowledge the fault When output units type 2262 2263 are installed e Remove the battery fuse F3 on the rectifier p c b The following fault message is to be shown FAULT Battery output unit xxxxxx NOTE xxxxxx is depending on output unit and control
127. ode for PC communication The code was correct and ACCEPT A10 is now changed to the new code Scroll or press Return to H5 Scroll or press Return to log off NOTE After change of access code it is recommended do a Safe shutdown of the control unit see menu H8 S8 This will save the SSW data e g the new code in a Flash ROM see page 83 129 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 28 12 Change access code for service H5 A11 For security reasons the default code should be changed Access According to chapter Access code for service H5 see page 120 Scroll to menu A11 Enter the old code the The digits are replaced new code and the new in the display code again The code was not correct Try again n The code was correct and N N is now changed to the new code Scroll or press Return to H5 Scroll or press Return to log off NOTE After change of access code it is recommended do a Safe shutdown of the control unit see menu H8 S8 This will save the SSW data e g the new code in a Flash ROM see page 83 If the valid access code is unknown a back door code is available 130 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 29 Acknowledge FAULTS H6 Regard
128. ol Unit Properties 65 In Win512 fault latching or not fault latching can be selected Fault latching default each fault always have to be acknowledged No fault latching corrected faults will automatically be removed from the fault list menu H6 53 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x If a fault can not be corrected it is important to contact service personnel engineer immediately NOTE As a warning faults and disablements are also indicated by a 2 sec beep when an open c i e door is being closed 17 1 Fault messages Below follows a list of all fault messages in alphabetical order FAULT 1580 8 zones board x CU xx 8 zones expansion board DET8 Fault on no communication to 1580 board No x in control unit No xx Check address setting and connections on the board Check programming Win512 FAULT 1581 Relay board x CU xx 8 relays expansion board Fault on no communication to 1581 board No x in control unit No xx Check address setting and connections on the board Check programming Win512 FAULT 1582 FBP interface board x CU xx External Fire Brigade Panel interface board Fault on no communication to 1582 board No x in control unit No xx Check address setting and connections on the board Check programming Win512 FAULT 1583 Extinguishing system
129. ons Fire alarm system EBL512 V2 6 x 28 Service H5 When commissioning an installation and by maintenance power on and programming a control unit a system menu H5 is used to get certain information and help Only authorised personnel have access to level 4 menus Access code for level 4 is required Via a PC and Win512 access code for level 5 you can e download backup site specific data SSD e download of S W settings configurations C U amp system data e create and download the user definable text messages shown in the alphanumeric display in the C U ext FBP and in the Display units Via a PC and TLON Manager you can do the TLON network programming configuration TLON Manager is used for programming of network data addresses etc 9 Connected to the D connector J1 on the main board 1556 100 Connected to the modular connector J2 on the main board 1556 118 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev 28 1 Operating Instructions Fire alarm system EBL512 V2 6 x Access code for service H5 Access code to level 4 is required If login to level 2 was made with code for level 4 no code is required here Scroll to menu H5 Enter code for level 4 f 4 digits The access code was correct This is menu H5 A1 Press A to accept scroll or press return to menu H5 According to chapter Access page 86 If
130. ontrol unit again 142 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 31 10 Activate address in alarm mode H8 S9 One alarm point address not a whole zone can be set in alarm status The built in LED in the alarm point detector will be turned on to indicate the alarm Among other applications this function is used for installations on ships NOTE All outputs standard and programmable which would have been activated by a real fire alarm from the same alarm point will be activated by this manual alarm as well Access According to chapter Access code for maintenance see page 135 Scroll to menu S9 Activate address in alarm mode ACCEPT Select zone 000 address 00 ACCEPT Write the zone and Select zone 123 address 45 Press A to accept start address ACCEPT the fire alarm POINT 123 45 NOR Normal fire alarm User definable text if programmed presentation in the control unit s FBPs display If more alarm points have to be set in alarm status press Return to select another zone address and continue as above Select zone 000 address 00 ACCEPT Write the zone and Select zone 012 address 34 Press A to accept start address ACCEPT the fire alarm POTN 122 45 T TAST 012534 No 002 User definable text if programmed What happens by reset of the fire alarm s is d
131. or in control unit or external FBP connected to own control unit Door open in a C U is indicated by LED Door open in that C U and all ext FBPs connected to that C U Door open in an ext FBP is indicated by LED Door open in the C U it is connected to and all ext FBPs connected to that C U O Doorin control unit Door open in a C U is indicated by LED Door open in that C U and in all ext FBPs connected to that C U Door open in an ext FBP is indicated by LED Door open in that ext FBP only Outputs for routing equipment Fire brigade tx and Fault tx Disablement of routing equipment No disablement Door open in a C U or an ext FBP will not disable the output s for routing equipment Fire brigade and fault tx O Disable by door in any control unit Door open in any C U will disable the output s for routing equipment Fire brigade and fault tx in all C U s O Disable by door in any control unit or any external FBP Door open in any C U or any ext FBP will disable the output s for routing equipment Fire brigade and fault tx in all C U s Disabled outputs for routing equipment are indicated by the LED Disablements L8 and Fault Disablements Fire brigade tx L15 and listed in menu H4 U1 38 Tn the ext FBP 1828 when the key is turned to the position open 34 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Ins
132. p mode i e set jumper JP1 BOOT in position on the main board 1556 3 Do a reset restart i e set jumper JP4 RESET in position momentarily approx 1 second 4 The buzzer will now sound intermittent and LED LD101 starts blinking indicating that the control unit is in Bootstrap mode 5 Start the downloading click Download The buzzer will now be silenced and LED LD101 is turned on continuously 77 Tt is recommended that the two first digits in the EBL512 S W version and the Win512 version are the same e g for EBL version 2 6 1 shall Win512 version 2 6 x be used 18 When a c i e has a TLON connection board 1590 mounted it is expected to be one c i e in a TLON network and TLON network programming is required 7 Tf the new S W file comes together with a text file download it as well 8 Also the LED System fault L14 starts blinking 78 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 6 During the download of the S W and or text file some information will be shown in the Win512 log view and when the download is ready Downloading completed successfully will be shown for the S W and text file respectively Close the dialog box 7 Open the Tools menu and open the EBL512 settings dialog box See 3 amp 4 above Click Read In the log view will be shown System information has be
133. press Return to log off NOTE After the calibration it is recommended do a Safe shutdown of the control unit see menu H8 S8 This will save the SSW data e g the calibration values in a Flash ROM see page 83 101 Control unit and 2262 2262 outputs One end of line resistor 33K in the last unit or one resistor 33K in up to five units 3364 outputs One end of line capacitor 470 nF in the last unit or one capacitor 470 nF in up to five units 102 4K7 50K and 470 5x470 nF respectively 120 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 28 3 Sensitive fault detection mode H5 A2 To increase the possibilities to detect faults during the commissioning it is possible to use the Sensitive fault detection mode The time delay for each fault will be reduced NOTE Don t forget to turn off this mode after the commissioning Access According to chapter Access code for service H5 see page 120 Scroll to menu A2 A Press A or 1 and A to accept ON is indicated by LED Fault tx activated L11 and the Fault output for routing equipment This mode is ON until turned OFF in this menu A2 Scroll or press Return to H5 Scroll or press Return to log off or m 1 ue WAN 121 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev
134. psulated reset is used you can make a Multiple reset by pressing Reset P4 and 0 1 sec later also press A in the keypad and hold them pressed for gt 0 5 sec 49 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 16 2 3 16 2 4 16 2 5 Operating Instructions Fire alarm system EBL512 V2 6 x If more than one fire alarm is activated i e LEDs Alarms queued L2 are lit the next fire alarm in the queue is now shown in the display on the first row to the left It has to be reset the same way as the first one When all fire alarms are reset LEDs Fire L1 and Alarms queued L2 are turned OFF and the display is empty All outputs for fire alarm are now also reset i e de activated If a key cabinet is installed the key to the building has to be put back into the key cabinet within 5 minutes If not a fault will be generated and a fault message will be shown in the display see chapter Key cabinet alarm reset page 52 Single encapsulated reset Like Single reset but with an encapsulation function as well Normally when an alarm point or zone having activated fire alarm is reset when still in alarm status it will activate a new fire alarm within 20 seconds According to the EN54 2 standard When Single encapsulated reset is performed an alarm point or zone still in alarm status will not only be reset but also disconnected i e it will not activat
135. r is stopped via this menu H8 S7 or if a fire alarm is activated in the system Access According to chapter Access code for maintenance see page 135 Scroll to menu S7 Test alarm devices ACCEPT S7 Test alarm devices on CU 00 99 All Write a CU no or 99 ACCEPT for all CUs and press A to accept Test alarm devices Scroll or press Return to ACCEPT S7 return to menu H8 Scroll or press Return to log off H1 Including Addressable siren 3377 and Addressable sounder base 3378 The output activation will be continuously steady For the alarm devices 3377 and 3378 the tone with the highest priority level and type alarm device will be automatically selected 141 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 31 9 Safe shut down of control unit H8 S8 It s not recommended to power off a control unit i e no 230 V AC and no battery without first doing a safe shut down of control unit Safe shut down will save the SSW and put the CPU at rest See also chapter Restart page 83 It s recommended to do a safe shut down after commissioning the installation and after the calibration of supervised outputs change of access code etc in order to save the new values codes etc Safe shut down can be performed from any control unit and any control unit can be selected e g a control unit withou
136. r supply 3 2 S W versions 3 3 Documents 3 4 Applications 3 5 PC S W OOOO OCOCOCCOCADBDAABDBAHADAHDH SF N e ooo oO 10 11 11 11 11 11 11 12 12 12 12 12 13 13 13 13 Panasonic Electric Works Fire amp Security Technology Europe AB Operating Instructions Fire alarm system EBL512 V2 6 x MEW01165 Rev 4 Control Unit 5 LED indicators and push buttons 6 Normal operation 6 1 Alphanumeric display LCD in EBL512 6 1 1 System information on the top first row 6 1 2 LCD backlight 6 1 3 The LCD information priority order 7 7 1 7 2 7 3 74 7 5 7 6 8 8 1 8 2 9 10 10 1 11 Access levels Access level 0 Access level 1 Access level 2 Access level 3 Access level 4 Access level 5 Silence Alarm devices Silence alarm devices inside switch New Zealand FB Silence switch outside switch Disable Re enable alarm devices Silence buzzer Buzzer Disable Re enable all control extinguishing and ventilation outputs 12 Acknowledge and Disable 12 1 12 2 12 3 12 4 13 13 1 13 2 14 14 1 14 2 14 3 15 15 1 15 2 Evacuate LED Test Alert Annunciation Evacuate LED Test Alert Annunciation Acknowledge Disable Door open LED Door open 14 16 20 20 20 20 21 22 23 23 24 25 26 26 27 27 28 29 30 31 32 33 33 33 33 33 34 34 Outputs for routing equipment Fire brigade tx and Fault tx 34 Technical number Present
137. r type might have been chosen from the beginning and thus cause unnecessary alarms Miscellaneous Choosing another type of detector can solve certain problems Bear also in mind that the coverage area can be different for different types of detectors It is however not always the best action to change detector type Here is a list of other actions programmed via Win512 which can be used e Another alarm algorithm can be used e Alarm delay for smoke detectors sensors can be used e Two zone or two unit dependent co incidence fire alarm activation can be used e Inan installation with addressable detectors sensors e g EBL512 the affected detectors can be individually disabled or whole zones when the work is in progress Bear in mind that the smoke spreads and consideration must be taken to adjacent detectors zones Disablements can be done automatically via a time channel built in or external or via menu H2 B1 B3 Automatic re enabling can be used e If there is an alarm organisation for the personnel on site the alert annunciation function can be used e Pre warning can be used 159 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 39 Information regarding radioactive radiation source The installation might contain old smoke sensors detectors of the ionization type They contain a small radi
138. re made on the connection board 1555 T B P1 72 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev 18 2 1 18 3 Operating Instructions Fire alarm system EBL512 V2 6 x 7 When all control units are power supplied the TLON network installation have to be done before the site specific data SSD can be downloaded see chapter Programming SSD download page 76 8 See also chapter Calibration of supervised outputs H5 A1 page 121 If you know that one or more of the control units are to be started up later do as follow Create in Win512 the SSD only for the control units that shall be connected now Wait to download the SSD until the TLON Network installation is ready In TLON Manager do the TLON Network programming for the project i e only the control units that shall be connected now Start up the control units according to chapter Control Units in a TLON network page 73 i e turn power on and do the TLON Network installation of the control units Download the SSD Later when one or more control units shall be stated up Open the project in TLON Manager add the control unit s and install download it according to the separate TLON network documentation Open the SSD in Win512 and add the control unit s and download the SSD to all control units NOTE For highest security the function Redundancy in distributed system can be used in a sys
139. reak on the BS4 loop This is indicating a single break on the loop Communication has to be performed in both directions to find all units Each 10 minute is an attempt made to comm in one direction again This is indicating a single break on the COM loop x when one or more short circuit isolators are connected on the loop 59 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x Communication has to be performed in both directions to find all units The break is to be found in the specified segment e g ASF 3 lt gt CU between short circuit isolator no 3 and the control unit Each 10 minute is an attempt to comm in one direction made again FAULT Display unit xxxxxx Display unit out of work Fault in the display unit EEPROM site specific data Download the data again or change the EEPROM and download the data again FAULT Double addresses techn no XxXxxxx Two or more units connected to a BS4 loop 1584 board have been given the same address Check the units FAULT Earth fault plus CU xx FAULT Earth fault minus CU xx Earth fault is detected System voltage is normally 24 V DC 24 V to earth is normally 12 5 V O V to earth is normally 11 5 V Voltage to earth lt 3 4 V Earth fault minus Voltage to earth gt 18 3 V Earth fault plus Check all cables for damage etc The fu
140. rol unit door is left open the output s for routing equipment fire brigade tx might be disabled if set so in Win512 There will be an automatic ending of the test mode one hour after the latest tested alarm point zone See also chapter Perform ZONE TEST test mode H7 page 133 Access According to chapter Access see page 86 Perform monthly test ACCEPT H1 A Check that all LEDs light up ACCEPT The buzzer in the C U sounds and all dots in the display are shown All LED s light up incl LED s in units connected via I O Matrix board 4582 When printer is available it will print out Zone to be set in TEST MODE NOTE In DBI Danish FEM ENE T AR Pe Start test ACCEPT convention only one zone Write zone numbers Zone to be set in TEST MODE Press A to start the test e g 001 002 003 001 002 003 004 Start test ACCEPT mode 004 86 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x Zones are set in test mode LED Test mode L9 Warts ts will light up Zone in TEST MODE Perform the tests 001 002 003 004 End test ACCEPT The zone s will stay in test mode until the test mode is ended but after 60 minutes or if you press Return two times you will be logged out from menu H1 Perform the test as quickly as possible since the output s for routing equipment fire brigade tx are disabled
141. rs are shown each zone can have a unique text message Each zone line input can have a unique text message Downloading is performed in a consecutive order i e 0 1 2 3 4 29 amongst the selected control units but the control unit where the PC is connected will automatically be the last one to get the SSD downloaded 7 Also valid for the Ext Presentation unit 1728 and the Alert Annunciation units 1735 1736 76 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 19 5 Operating Instructions Fire alarm system EBL512 V2 6 x The user definable text messages will be printed out when a printer is available See also chapter Fire alarm page 39 Unique user definable text messages for each alarm point and each zone line input can also be shown in Display units 2235 2236 connected on the COM loops All user definable text messages up to 40 alphanumeric characters each are created and downloaded via Win512 See Planning Instructions chapter User definable text messages See also the Win512 help chapters help topics Download and Display unit menu An older DOS based PC program NEWTEXT can also be used see Planning Instructions chapter Display units addressable See also Win512 help Using old SSD Site Specific Data SSD created in an earlier Win512 version can be opened in e g the latest Win512 version edited if required saved and downloa
142. ructions Fire alarm system EBL512 V2 6 x A If more disablements shall be done continue like above If not press Return to menu B3 Scroll or press Return to menu H2 Scroll or press Return to log off 93 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 25 4 Re enable zone H2 B4 Disabled zones are listed in menu H4 U1 Re enabling via this menu has higher priority than automatic re enabling When all zones have been re enabled The LED Disablements L8 will be turned OFF if there are no other disablements in the system NOTE It is not possible to collectively re enable a number of alarm points zone address that are individually disabled via menu H2 B2 Access According to chapter Access see page 86 Scroll to menu H2 If there are no zones to re enable menu B4 will be shown again L a list in which you can scroll If it s the correct zone to re enable press A to accept If not scroll or write the wanted zone and press A to accept If more re enablements shall be done continue like above If not scroll or press Return to menu H2 Scroll or press Return to log off 94 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 25 5 Re enable zone ad
143. ructions Fire alarm system EBL512 V2 6 x fault in program area n n 1 or 2 The ext FBP will not work FAULT Configuration control unit xx Fault in the SSI EBL512 settings downloaded from Win512 FAULT CU xx has no contact with CU xx Can be shown in conjunction with new S W download e Check the TLON network cable connections e Faulty TLON connection board 1590 e No power supply to the control unit FAULT CU xx has wrong information Can be shown in conjunction with new S W download and or when commissioning a system One or more control units might have data stored that is not the same in all control units If a control unit restarts in conjunction with this fault a synchronization will start automatically otherwise a synchronization has to be started via menu H8 S10 or via Win512 NOTE It is important that all control units that are supposed to exist SSD downloaded via Win512 are running and are connected to the TLON network The TLON network programming has to be done FAULT CU xx high current consumption The control unit current consumption is gt 2 5A gt 3 6A in alarm state and because of this the battery charging is turned off and will be so until the current consumption has decreased to lt 2 5A lt 3 6 A again PAULL Cut oft EOM loop x CU Xx This is indicating a single break on the loop Communication has to be performed in both directions to find all the units It might a
144. rvice personnel engineer immediately FEAUGT Comm AAU Sx 1587 board a CU xx AAU 1735 1736 e The contact with the AAU is interrupted Check the cable all connections and the 1587 board Is correct complete SSD downloaded via Win512 Check the address setting 1587 board the AAU SW mode setting etc If there is a program memory fault in the AAU there will be a fault message in the AAU display Memory fault in program area n n 1 or 2 The AAU will not work PAULE Comm HEU x 158 board x CU xx EPU 1728 e The contact with the EPU is interrupted Check the cable all connections and the 1587 board Is correct complete SSD downloaded via Win512 Check the address setting 1587 board the EPU SW mode setting etc If there is a program memory fault in the EPU there will be a fault message in the EPU display Memory fault in program area n n 1 or 2 The EPU will not work WADIC Comin BSS xr loe yoq eieel zp CU xox FBP 1826 1828 e The contact with the ext FBP is interrupted Check the cable all connections and the 1587 board Is correct complete SSD downloaded via Win512 Check the address setting 1587 board the ext FBP SW mode setting etc If there is a program memory fault in the ext FBP there will be a fault message in the ext FBP display Memory 57 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Inst
145. s and if NR Return is pressed menu U1 will be shown again On this row can be j l l ian shown adding infor mation e g Automatic 1 l re enablement HH MM E i or by open door in CU aes Xx Press A and menu U1 i will be shown again Return Scroll or press Return to or menu H4 Scroll or press A Return to log off 103 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 27 2 Disablement by time channel H4 U2 A list of all disablements by time channel s in the system From this menu it is also possible to get a print out NOTE Other disablements are listed in menu H4 U1 Text in display Access According to chapter Access see page 86 ae Scroll to menu U2 n Press 1 for an automatic print out of all disablements in the system Press A for presentation in the display L a list in which you can scroll If there are no disablements and if Return is pressed menu U2 will be shown again Press A and menu U2 will be shown again Scroll or press Return to menu H4 Scroll or press Return to log off When scrolling in the list the message No more zone addresses disabled by time channel found in the system can be shown 104 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512
146. s the individual free text for the alarm point if programmed or the default control unit text if programmed User definable text message For a zone it is the individual free text for the zone if programmed or the text Many alarms in zone LEDs Alarms queued L2 blinking 0 4 0 4 sec More than one fire alarm is activated To scroll through the zones use the push button Scroll P1 The fire alarms are stored in a circular buffer and when scrolling from the last to the first alarm the LEDs Alarms queued will be turned off for three seconds The first alarm will be automatically displayed again 20 seconds after the latest time the Scroll button was used The printer will print each fire alarm e g xxx Fire Alarm Point 123 45 Time HH MM Date MM DD User programmable text message if progr or Zone 123 Time HH MM Date MM DD User programmable text message if progr 48 More than one alarm point in the same zone If no user definable text message is programmed the text Many alarms in zone will be shown 4 Up to 512 alarms can be presented in the display Alarm ZONE and or ZONE ADDRESS depending on zone or point alarm presentation but all possible alarms 15360 can be stored When printer is available e g control unit 1549 The alarms will be printed like they are presented in the display i e as point alarms or zone alarms 41 Panasonic Electric Works Fire amp
147. sensor s techn number and or press A to accept This is a list in which you can scroll or use gt to see the next information window for the selected sensor Press Return to the Start Sensor Scroll or write a new techn number or press Return to menu US NOTE XX X 3 m XX X obscuration per meter XXX sensor value Perf Factor see below this table nnnnnn algorithm short name see separate table page 109 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x Sensor 00000N Current algorithm nnnnnn 3 Sensor OOOOO0ON Min OCC Momentary XX C Mane sea 3 Sensor 00000N Current algorithm nnnnnn Return Start Sensor 000000 Write the sensor s techn number and or press A to accept or press Return to menu U5 Sensor values Scroll or press Return Printout l yes to menu H4 Scroll or press Return to log off When scrolling the message Please Wait might be shown for a second and No more sensors found in the system before the lowest and after the highest possible technical number in the system Here follows the alternative 1 printout Scroll to menu US Sensor values Press 1 to accept Printout l yes U5 Start Sensor 000000 Write the techn numbers End Sensor and or press A to accept Printing s
148. sonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 36 Replacing a TLON connection board and or a main board By the TLON network programming some unique data will be stored in a memory on the 1590 TLON connection board and some unique data will be stored in a memory on the 1556 Main board After replacing a TLON connection board to another or replacing both a TLON connection board and a main board do Replace Update and Save in TLON Manager After replacing a main board to another not the TLON connection board do Update and Save in TLON Manager 156 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 37 Battery maintenance The batteries 2 x 12 V 24 Ah are normally placed in the control unit Larger batteries lt 60 Ah are placed outside the control unit The control unit supervises the batteries and a fault will be generated if something goes wrong They are rechargeable sealed lead acid batteries and normally maintenance free The producer s instructions shall always be followed The ambient temperature affects the battery capacity self discharge and life span It should not be higher than normal room temperature approx 20 22 C For highest safety batteries used in a fire alarm installation should never be older than
149. stallation test period when only local alarms are required Disabled outputs are indicated by LEDs Disablements L8 and Fault Disablements Fire brigade tx L15 Disabled outputs are listed in menu H4 U1 Access According to chapter Access code for maintenance see page 1 4 O E or re enable outputs for O Ta equipment ACCEPT S1 Routing equipment for FIRE 1 FAULT 1 To move the cursor press l enabled 0 disabled ACCEPT 5 Edit and or press A to accept Disable or re enable outputs for Scroll or press Return to routing equipment ACCEPT S1 return to H8 Scroll or press Return to log off 135 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 31 3 Disconnect loop H8 S2 Before physical connection disconnection of loop units etc the loop or zone line shall be disconnected disabled i e there will be no voltage on the loop to avoid damage on the units and the c i e BS4 loop require an Autronica interface board 1584 in the control unit DETS8 loop zone line requires an 8 zones expansion board 1580 in the control unit Text in display Comments Access According to chapter Access code for maintenance see page 135 Scroll to menu S2 Disconnect loop ACCEPT S2 Disconnect type 0 0 COM 1 BS4 Press 2 DES 3 L00p Unit ACCEPT 0 COM loop 1 BS4 loop 2 Expa
150. t pin A specific unit is being polled Autronica interface board 1584 BY3 right pin 0 V BS4 board Autronica interface board 1584 Access According to chapter Access code for service H5 see page 120 Scroll to menu A8 Select unit on COM BS4 loop to use for trigging ACCEPT A8 A Select type of loop 0O COM 1 BS4 Select type of loop Press ACCEPT A to accept 00 Loop 0 Address 000 Write control unit number ACCEPT board number 0 3 loop number and address Press or nyt A Y 1 OF Address 00 ACCEPT A to accept Select type of loop 0 0 ComM 1 BS4 Select type of loop Press ACCEPT A to accept or press Return to menu A8 Select unit on COM BS4 loop to use for Scroll or press Return to trigging ACCEPT A8 H5 Scroll or press Return to log off 107 The pin might be removed from the p c b 127 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 28 10 Activate address setting mode for DU H5 A9 This function can be used by commissioning service engineer to activate the address setting mode in the following Display Units connected to an Ext FBP DU interface board 1587 in the c i e e Ext Presentation unit 1728 e Alert Annunciation unit 1735 1736 e Ext FBP 1826 1828 A specific unit or all units connected to one 1587 board can be activated for address se
151. t a front has to be shut down from another control unit NOTE activated By restart and power off the Fault tx output s will be n a Scroll to menu S8 Write the C U number 1 yes and NA Safe shut down of control unit ACCEPT S8 Shut down control unit 00 0 lL ea wes Wo ACCEPT Please Wait In the CU that will be shut down when a front is available Ready for shut down break the power Automatic restart within nnn seconds In the CU s that will not be shut down Control unit xx ready for power off No reply from the selected CU xx i e no safe shut down No reply from control unit FAULT Restart CU xx code xx yyyyyyy Date mm dd hh mm NOTE The date is in the Ukrainian convention S W version gt 2 2 3 and the Australian convention shown as DD MM Time Serviced According to chapter Access code for maintenance see page 135 Shown for 3 sec then one of the three alternatives Count down starts from nnn 300 seconds Disconnect the power supply mains and battery When the power supply is connected again or after 300 seconds if powered all time there will be an automatic reset restart After restart power on see page 83 there will be a fault activated This fault has to be acknowledged see chapter Acknowledge FAULTS H6 page 132 13 Tf not a fault FAULT Read write site data SSW CU xx might be generated when you power up the c
152. tarted To stop printing press Press A and menu U5 C and 0 simultaneously ACCEPT will be shown again Start Sensor 000000 Write the sensor s techn number and or press A to accept or press Return to menu US Sensor values Scroll or press Return Printout l yes to menu H4 Scroll or press Return to log off Perf Factor Performance factor Low min 0 The detector is mounted in a stable environment High max 2 55 The detector is mounted in an unstable environment See also Planning Instructions chapter Performance factor Table showing the algorithms and the shortenings respectively 108 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 27 5 1 Operating Instructions Fire alarm system EBL512 V2 6 x Algorithm Short name nnnnnn gt Normal sensitivity amp Normal detection 15 s N 15 High sensitivity amp Normal detection 15 s H 15 Low sensitivity amp Normal detection 15 s L 15 Normal sensitivity amp Slow detection 35 s N 35 High sensitivity amp Slow detection 35 s H 35 Low sensitivity amp Slow detection 35 s L 35 Heat algorithm Class A1 Al Heat algorithm Class A2 S A2 Heat algorithm Class B S B Decision algorithm Dec Default is N 15 and A1 respectively Reset of a week average sensor value If a sensor analog smoke detector is replaced without havi
153. te disable the AA function i e the AA function will be disabled for the alarm points zones programmed for Alert Annunciation in spite of the time channel is on or if they are programmed to be continuously enabled The AA function will stay de activated disabled until re activated re enabled again via this menu Access According to chapter Access code for maintenance see page 135 Scroll to menu S6 De activate alert annunciation function ACCEPT S6 A Alert annunciation function 1 Write 0 or 1 and press i iNeniell OET ACCEPT A to accept A De activate alert annunciation function Scroll or press Return to ACCEPT S6 return to menu H8 Scroll or press Return to log off 140 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 31 8 Test alarm devices H8 S7 The programmable outputs type Alarm device can be collectively activated via this menu H8 S7 which make it possible to test the alarm devices The test can not be started if fire alarm is activated in the system One or all control units can be selected When the test starts the alarm devices will sound for approx 5 seconds be silent for approx 25 112 seconds sound for approx 5 seconds and so on NOTE Also disabled and silenced alarm devices will be tested The test will continue for one hou
154. tem with a TLON Network One control unit is a master unit and the other control units in the system are slave units that are connected to the master unit via a separate network and a 1580 board in the master unit For more information see Planning Instructions chapter Redundancy in distributed system TLON network installation A project a system with two or more control units has to be created in the PC program TLON Manager or has been created earlier A PC is connected to the modular connector J2 in the control unit main board 1556 Open the project in TLON Manager and install download the project see separate TLON network documentation Add a Control Unit in a TLON network When adding a control unit to a running installation you have to have the same software S W version in all control units Often the new control unit has a newer version than the existing control units Normally the latest version is the best to use i e the control units in the running installation have to be upgraded As an alternative it is possible to download an earlier S W version in the new control unit 73 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 18 4 18 5 Operating Instructions Fire alarm system EBL512 V2 6 x Both alternatives are described in chapter New system program S W version download page 79 Open the current project in TLON Manager add one control unit
155. tions 24 In the New Zealand convention 7 Faults not acknowledged a Silence switch left active 8 Disablements b Alarm routing equipment isolated 9 Zones in Test mode c Fault routing equipment isolated 10 Interlocking in outputs active Tn the Australian and New Zealand conventions the LCD backlight will not be turned OFF even if the c i e is powered only by the second power source 22 In the New Zealand convention also Acknowledged alarms ACK and Isolated alarms ISO NOTE A Fire alarm has a log off function i e if a menu window is open when a fire alarm is activated the fire alarm will be presented instead Some information is available and some actions are possible to perform via the Fire alarm menu X1 X9 see chapter Fire alarm page 39 Require special equipment available on the Australian market only Require special equipment available on the New Zealand market only 21 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 7 Access levels EBL512 has six access levels for different kind of users Access Access code Required action Users Action level password N A Scroll browse Door closed through the queued alarms 1 N A Fire brigade key Fire brigade Fire alarm handling to open the door personnel Use menu X1 9 2 pears Fire brigade key Access co
156. to be individually acknowledged one by one push button Fault acknowledge P6 Use or 4 keys to scroll e Ifa fault has been corrected before it has been acknowledged the text Serviced is added after the time It still has to be acknowledged e When a fault is corrected and acknowledged it will disappear from the list H6 e When all faults have been acknowledged output s for routing equipment Fault tx is are reset i e the LED Fault tx activated L11 will be turned off e As long as there are faults i e not acknowledged faults and or acknowledged but not corrected faults the LED General fault L7 will be lit and general fault and maybe general charge fault output s are activated 67 Indicating that output for routing equipment Fault tx is activated 6 Via Win128 the faults can be set to be not latched Corrected faults will in this case automatically disappear from the list without being acknowledged before 71 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01165 18 Operating Instructions Fire alarm system EBL512 V2 6 x Commissioning an installation 18 1 18 2 Before you connect the power supply to a control unit all other cable connections shall be made Check once more that they are correct Single Control Unit 1 Take away the rectifier fuse F1 and a battery fuse F2 or F3 on the charger board 1557 1657 Connect the
157. tputs activated by quiet alarm will be de activated In some cases after a programmable delay time Alarm Acknowledgement Facility AAF reset NOTE The AAF function is used in conjunction with an AAF Control which is available on the Australian market only The indication in the control unit display during the Acknowledgement Period 10 60 sec and the Investigation Period 0 3 min respectively will automatically disappear when e the AA process ends because no detector in the AAF zone is over the fire alarm level e the AA process ends up in a fire alarm which has higher priority Regarding Fire alarm reset see above 51 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 16 7 16 8 Operating Instructions Fire alarm system EBL512 V2 6 x Acknowledged alarm NOTE Valid for the New Zealand convention only A fire alarm presented in the LCD can be acknowledged by pressing the button Acknowledge fault P6 Acknowledged alarms are indicated in the fire alarm list in the LCD by ACK in front of the alarm see page 42 This indication is the only difference between a fire alarm and an acknowledged alarm Acknowledged alarms ACK have to be reset like normal fire alarms ALM Isolated alarm NOTE Valid for the New Zealand convention only A fire alarm ALM or an acknowledged alarm ACK presented in the LCD can be isolated as follows When the New Zealand FB
158. tructions Fire alarm system EBL512 V2 6 x 14 Technical number Presentation number 14 1 Technical number for COM loop units The technical number NNNNNN is used when programming all units connected to the COM loops Technical number is also used to identify which unit has generated a fault 000 127 The address on the COM loop Avoid address 000 Start at 001 Don t have to be in sequence The connections on the COM loop don t have to be in sequence The address is set on a DIL switch in some units and with a programming tool 3314 in some units 0 3 COM loop number 00 29 The control unit address number Don t have to be in sequence The connections to the TLON network don t have to be in sequence The address is set with a PC SW TLON Manager Regarding DIL Switch address setting see dwg 512 71 Regarding the address 000 Address 000 can not be set with the Address setting tool 3314 i e only addresses 001 127 can be used A brand new detector has address 000 factory set Connected on the COM loop the LED will start blinking every second as information that an address has to be set before the detector will work 35 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01165 Rev 14 2 Operating Instructions Fire alarm system EBL512 V2 6 x Technical number for BS4 loop units Autronica interface board 1584 four BS4 loops is required in the control unit Th
159. tting NOTE The units have to be in operation and in quiescent condition i e the units have to have an address already Access According to chapter Access code for service H5 see page 120 Scroll to menu A9 Activate address setting mode for DU ACCEPT A9 Activate address setting mode for DU Write control unit number CU 00 1587 board 0 DU 00 ACCEPT the board number 0 1 and the unit s address 99 All units on the selected 1587 board Press A to accept Activate address setting mode for DU Scroll or press Return to ACCEPT A9 H5 Scroll or press Return to log off The address is thereafter edited in the unit respectively 128 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 28 11 Change access code for PC communication H5 A10 As a protection against unauthorised personnel programming the system via Win512 an access code level 5 for PC connection is required For security reasons the default code should be changed NOTE This code requires eight 8 digits Access According to chapter Access code for service H5 see page 120 Scroll to menu A10 Change access code for PC communication ACCEPT A10 Access code T The digits are replaced New code xkxxx Verify Kee HK in the display Incorrect access code NO change The code was not correct Try again Change access c
160. value otherwise the new clean sensor will inherit the old sensor s value It is possible to clear the week average sensor value for each sensor individually NOTE First replace the sensor then clear the week average value as soon as possible Authorised service personnel only must do this Used incorrectly it can cause nuisance fire alarms The first week average sensor value after clearing will be calculated within one hour and after that each week Action Text in display Comments According to chapter Access code for maintenance see page 135 Scroll to menu S5 Clear weekly average ACCEPT S5 Enter technical number to clear 000000 Write the wanted techn ACCEPT no and or press A to accept Clear weekly average Scroll or press Return to ACCEPT S5 return to menu H8 Scroll or press Return to log off 139 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 31 7 De activate alert annunciation function H8 S6 Normal function 1 For alarm points zones programmed for Alert Annunciation via Win512 is normally this function enabled via a time channel e g enabled daytime during working hours and disabled night time As an alternative for alarm points zones programmed for Alert Annunciation can this function be continuously enabled Off 0 Via this menu H8 S6 it is possible to de activa
161. vated state the buzzer is silenced until the outside switch is turned OFF 3 Acknowledged alarm in the New Zealand convention only Not valid if the buzzer is silenced by the open door 35 See page 28 30 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 10 1 Operating Instructions Fire alarm system EBL512 V2 6 x Buzzer If there is a fault or disablement when the door to EBL512 is being closed the EBL512 built in buzzer will give a 2 seconds beep directly after the door is closed One fault message or disablement will be shown in the LCD but more faults and or disablements will be indicated by the word more NOTE In the New Zealand convention if any of the outputs for routing equipment Fire brigade tx and Fault tx is disabled when the door to EBL512 is being closed the EBL512 built in buzzer will give a 2 seconds beep directly after the door is closed Routing quipment left isolated will be shown in the LCD This information has higher priority then the normal fault messages and disablements 31 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 11 Disable Re enable all control extinguishing and ventilation outputs All control outputs programmed as type 0 control general 1 fire ventilation 2 extinguishing system can via menu H2 B8 be
162. when the control unit works in Sensitive fault detection mode menu H5 A2 A short circuit shorter faster than the time delay for an ordinary fault has occurred on the COM loop Can be used for commissioning maintenance purposes FAULT Battery not connected CU xx Batteries 2 x 12 V are missing or not connected correctly ones F2 F3 on the charger board 1557 1657 is are blown Other battery fuse is blown e g when the batteries are placed outside the control unit In the New Zealand convention only Battery voltage is below 24 4 V This check is done every 14 minute every 30 second in the New Zealand convention i e after correcting the fault it might take up to 14 min 30 seconds until it disappears from the fault list FAULT Battery output unit xxxxxx Check the output unit battery connections fuse F3 on the power supply board in the output unit FAULT Charging ext power supply CU xx The fault is to be found in the external power supply equipment 56 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x FAULT Charging output unit xxxxxx The charging function in the external power supply unit is not OK The p c b has to be replaced FAULT Checksum system program CU xx A fault in the control unit xx S W The main board 1556 might have to be replaced This is a very serious fault Call for se
163. will be shown in the display FAULT Restart CU nn code xx yyyyyyyyyy Date MM DD Time HH MM Regarding code xx and yy y see page 67 This fault is also indicated by LEDs Fault tx activated L11 and General fault L7 After fault acknowledge menu H6 the LEDs will be turned OFF if there are no other faults After reset a synchronization of the control units starts automatically See also chapter Synchronize the control units H8 S10 page 146 After reset required disablements have to be done Memory fault In case of a fault in the S W system program the following text message will be shown in the display Memory fault in program area xxx This is also indicated by LED System fault L14 and the buzzer sounds steady The Fault tx output is activated A new download of S W system program is required NOTE After the SSD download see chapter Programming SSD download page 76 the following might be shown in the display Checksum fault in downloaded data Control unit will now restart After the restart see above and the text message FAULT Restart CU nn code xx yyyyyyyyyy Date MM DD Time HH MM Serviced Another text message will be shown in the display FAULT Site specific data SSD CU nn Date MM DD Time HH MM This text message means that the SSD have not been downloaded A new download has to be performed 83 Pa
164. x 00 Power On Restart Power supply connected xx 01 Watchdog Restart xx 02 Accidental jump to reset vector xx 03 External restart caused by external watchdog user e g after SSD download or jumper JP4 RESET on the main board 1556 has been used xx 4 19 Unexpected interrupt xx 20 S W monitoring fault xx 00 or 03 is normal If xx 01 02 or 04 20 appear often call for service personnel engineer yy y memory address before restart FAULT Sensor techn no xXxXxxxx e The sensor 22xx 23xx is removed from its sensor base 2210 2312 Faulty sensor The analog detector 33xx 43xx in NORMAL mode The built in self verification function has reported a fault status Detector removed from its base generates FAULT No reply FAULT Short circuit COM loop x CU xx Short circuit on COM loop x short circuit isolator is not connected on the loop Check the loop NOTE As long as there is a short circuit the COM loop is disabled Each 10 minute is an attempt made to re enable the loop again 66 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 8 zones expansion board DET8 This is indicating short circuit on input x zone line on the 1580 board The wires cable might have been damaged NOTE As long as there is a short circuit the zone is disabled Each minute is an attempt made to re enable the
165. y charging voltage etc NOTE Control unit current gt 3800 mA is presented as gt 3800 mA Charging current lt 100 mA can not be correctly presented The displayed Charging value xxxx mA shall be multiplied by two when High current charging mode has been selected via jumper JP2 on the Charger board 1657 JP2 shunted High current charging mode Access According to chapter Access code for service H5 see page 120 Scroll to menu A5 Display current consumption in unit ACCEPT A5 A From which control unit shall current Write control unit number consumption be displayed 00 ACCEPT Press A to accept i Se le If the control unit don t exist or don t answer this message will be shown Display current consumption in unit Scroll or press Return to ACCEPT A5 H5 Scroll or press Return to log off Current consumption control unit 00 Control unit xxxx mA Charging xxxx mA YS 124 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x 28 7 Display current consumption COM BS4 loop H5 A6 The resolution is not very high i e the displayed values give only a rough idea of the current consumption The current consumption an average value for each COM loop and BS4 loop can be displayed NOTE No or very small current consumption can not be presented correctly precisely Access According t
166. y disabled Disabled output will stay in or return to the normal condition for the output respectively Disabled outputs are listed in menu H4 U1 from which it is also possible to get a print out Access According to chapter Access see page 86 Scroll to menu H2 Disable or re enable ACCEPT H2 A Disable zone ACCEPT BI Scroll to menu B3 Disable control output ACCEPT BS Disable output control unit 00 Type 0 Write C U No and Cle optnmatte SER EREA bom AC CH ram press 0 RU4 2265 or SU4 2262 2263 or MIO 3361 or AOU 3364 or 4 ES not valid in Swedish SBF convention ASI 3377 or ASB 3378 1 S0 S3 2 RO R1 3 Relay board 1581 4 1583 board output Extinguishing system Press A to accept A Disable 00 0000 control output 0 Regarding the AOU Depending on the ACCEPT 3364 unit s output 2 chosen type 0 1 2 3 Digable s The fire door functions resp 4 the following will not be disabled will be shown Regarding the ASI Disable RO 3377 amp ASB 3378 ACCEPT units Control output Disable relay board 0 output 0 O high priority ACCEPT 1 medium priority 2 low priority Disable output for extinguishing system Write the data on 1583 board CU 00 ACCEPT Press A to accept LED Disablements L8 will light up 92 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Inst
167. zone again 1584 Autronica interface board BS4 Short circuit or current consumption gt 167mA on the BS4 loop short circuit isolator is not connected on the loop Check the loop NOTE As long as there is a short circuit the BS4 loop is disabled Each 10 minute is an attempt made to re enable the loop again Short circuit on the COM loop x one or more short circuit isolators are connected on the loop Check the specified and isolated segment on the loop e g CU lt gt ASFO between the control unit and short circuit isolator no 0 Each 10 minute is an attempt made to re enable the isolated segment again Some external influence or after download has caused a checksum 67 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01165 Rev Operating Instructions Fire alarm system EBL512 V2 6 x fault in the from Win512 downloaded Site Specific Data SSD An SSD download is required This is very serious Call for service personnel engineer immediately SSD AAU Sox i Sis Pole x GU XX AAU 1735 1736 There is no SSD Site Specific Data downloaded to the unit or something is wrong in the downloaded SSD VADs SSD PU sox i6 board x CU xox EPU 1728 There is no SSD Site Specific Data downloaded to the unit or something is wrong in the downloaded SSD FAUT Ss SSID INE sox Se Doorda CU sa FBP 1826 1828 There is no SSD Site Specific Data downloaded to