Operating Instructions Fire Alarm System EBL128

image

Contents

1. 66 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 23 2 Disable zone address H2 B2 All addressable alarm points also addressable manual call points connected to the COM loop can be individually disabled Disabled alarm points zone address are listed in menu H4 U1 Disabled alarm points zone address can be automatically re enabled or they have to be re enabled via menu H2 B6 Text in display Comments Access According to chapter Access see page 62 Scroll to menu H2 Scroll to menu B2 Write zone number and Press A to accept address e g O1 01 Press 1 for aut re enabling and accept or change the time max 24 hours Press A to Default is current time 3 hours accept LED Disablements L8 will light up If more disablements shall be done continue like above If not press Return to menu B2 Scroll or press Return to menu H2 Scroll or press Return to log off 67 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 23 3 Disable output H2 B3 Control outputs can be individually disabled Disabled output will stay in or return to the normal condition for the output respectively Disabled outputs are listed in menu H4 U1 Text in display Comments Press A 0 MIO 3361 or
2. It is possible to clear the week average sensor value for each sensor individually see chapter Clear weekly average H8 S2 page 103 See also chapter Acknowledge SERVICE signal H8 S1 page 102 NOTE Authorised service personnel only must do the reset to default value Used incorrectly it can cause nuisance fire alarms 82 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 25 4 Rev 2 EBL128 Operating Instructions V1 0 x Sensors activating SERVICE signal H4 U4 Service signal is indicated by LED Service L12 The week average sensor value is over the service level respectively for one or more sensors Regarding the service signal levels see Planning Instructions chapter Service signal Menu H4 U4 is a list of the sensor s activating service signal NOTE Service signal is only information that a sensor has to be cleaned replaced soon The service signal has to be acknowledged see chapter Acknowledge SERVICE signal H8 S1 page 102 Tertia display anne Access According to chapter Access see page 62 Scroll to menu H4 Scroll to menu U4 e A Press A to accept L a list in which you can scroll Press Return to menu U4 If there are no sensors in the list menu U4 will be shown again Scroll or press Return to menu H4 Scroll or press Return to log off 83 Panasonic Electric Works Fire amp Security Technology Europe AB MEW
3. According to chapter Access see page 62 ASI 3377 or ASB 3378 or AOU 3364 1 C i e output SO S1 2 C i e output RO 3 C i e exp board relay output Press A to accept A Regarding the ASI Depending on the 3377 amp ASB 3378 chosen type 0 1 2 or 3 unit outputs the following will be 0 high priority shown 1 low priority Write the data Press A to accept LED Disablements L8 will light up If more disablements shall be done continue like above If not press Return to menu B3 Scroll or press Return to menu H2 Scroll or press Return to log off Relay board 0 1 Relay output 0 7 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 23 4 Disable all control extinguishing venti lation and alarm device outputs H2 B4 Outputs programmed as type 0 control general type 1 fire ventilation type 2 extinguishing system and type 3 alarm devices can for the type respectively be disabled all at the same time Disabled output means that even if the control expression trigger condition for the output respectively is fulfilled the output will not be activated Disabled outputs are shown in menu H4 U1 The outputs will be disabled until re enabled again via H2 B8 NOTE This function for alarm devices is not the same as push button Silence alarm devices P3 see
4. Automatically due to external FFD WASV SSD 01 02 alt disturbance Cold restart S W SSW 04 20 NOTE During the restart the Fault tx output will be activated the supervised 24 V DC outputs SO S1 will be not supervised and SO S1 programmed as normally high will be low for a few seconds During the restart no fire alarm can be activated and the buzzer will sound until the following text messages is show in the display EBL128 Checking program memory And for a second if everything is all right else see Memory fault below IONE SLING 514 6 a 6 0 A fault is now generated and the following text message will be shown in the display FAULT Date Restart code xx addr yyyy MM DD Time HH MM 5 Both rectifier and battery disconnected 5 All alarm points zones units outputs COM loop etc that were disabled disconnected before a warm restart will remain disabled after the restart provided it was not removed in the new downloaded SSD If removed this disablement will be terminated 55 If this happens often call for service personnel engineer 59 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 20 1 Rev 2 EBL128 Operating Instructions V1 0 x Regarding code xx and yyyy see page 48 This fault is also indicated by LEDs Fault tx activated L11 and General fault L7 After the fault is acknowledged via m
5. Evacuate is only valid in the Belgian and Ukrainian conventions 7 LED test is only valid in the Czech convention 8 Alert Annunciation Acknowledge is only valid in the Polish convention Disable is only valid in the Australian convention 14 Panasonic Electric Works Fi MEW00509 Rev 2 LED indicator Service yellow yellow General fault yellow Disablements yellow Test mode yellow Door open yellow Fault tx activated yellow Fault Disablements Alarm devices yellow System fault yellow EBL128 is not running because of S W CPU memory fault Fault Disablements Output for fire brigade tx routing equipment is Fire brigade tx yellow Fire brigade tx delay re amp Security Technology Europe AB EBL128 Operating Instructions V1 0 x LED indicators on the Control Panel CP Indicating Fault s i e not acknowledged fault s and or acknowledged but not corrected fault s Something is disabled disconnected via a menu or automatically via Single encapsulated reset gt One or more zones are in test mode A door is open in EBL128 or an ext FBP One or more not acknowledged faults Output for fault tx routing equipment is also activated if not disabled before Test of routing equipment in progress see menu H1 One or more sensors have reached the service level See menu H4 U6 One or more outputs type 3 alarm device ar
6. Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x Re enable output 0 If more re enablements 0 Loop unit 1 S 2 RO 3 RE ACCEPT shall be done continue like above If not press Return to menu B7 Scroll or press Return to menu H2 Scroll or press Return to log off 73 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 23 8 Re enable all control extinguishing venti lation or alarm device outputs H2 B8 Disabled outputs are listed in menu H4 U1 When all outputs have been re enabled the LED Disablements L8 will be turned OFF if there are no other disablements When all outputs type 3 alarm devices have been re enabled the LED Fault Disablements Alarm devices L13 will be turned OFF TRE TE Access According to chapter Access see page 62 Scroll to menu H2 Scroll to menu B8 A 3 Press 0 control output 1 extinguishing output 2 ventilation output 3 alarm devise output Press A to accept A Press A to accept Depending on the LED Disablements L8 chosen type 0 1 2 or 3 will turned off the following will be If type 3 alarm devices are re enabled also the LED Fault Disablements Alarm devices L13 will be turned off shown Press o a lia Bae or ugu and press A to accept or
7. Safe shut down of control unit menu H8 S4 will save the SSW data except the week average sensor values in a Flash ROM before you power off EBL128 Before the first Safe shut down this memory is empty After each Safe shut down the latest SSW data is saved When EBL128 is powered up the RAM working memory will after the restart read the SSW data saved in the Flash ROM NOTE After any restart a new week average sensor value will be calculated within two minutes for all the analog smoke detectors Thereafter a new average sensor value will be calculated each week Here follows a table describing different reset alternatives and how the data respectively is affected During these two minutes all fire alarms from analog smoke detectors will be suppressed 58 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x Action Data etc Data etc Restart code which will be which will be deleted not deleted Power down and then power SSW SSD 00 up again Cold restart FFD WASV S W Via menu H8 S4 Safe shut down FFD WASV SSD 00 alt 03 of control unit Cold restart S W SSW Automatically after download of FF WASV SSD 03 site specific data SSD via a PC S W SSW amp Win128 Warm restart D Automatically after download of FFD WASV SSD 00 alt 03 S W or text file viaa PC amp S W SSW Win1 28 Cold restart
8. H9 C1 110 Activate interlocking output H9 C2 111 Reset interlocking output H9 C3 112 Disable interlocking output H9 C4 113 Re enable interlocking output H9 C5 114 Change access code for daily duties H10 ___ 115 Annual control 116 Battery maintenance 117 How to avoid unnecessary nuisance fire alarms 118 Revision history 120 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 1 Introduction EBL128 Operating Instructions is a document with information of special interest for the end user and the fire brigade personnel as well as service commissioning engineers who should read this document in conjunction with the EBL128 Planning Instructions since most of the information in one of the documents is not found in the other document and vice versa A Product Leaflet and the EBL128 drawings according to the valid Table of drawings are also available Due to continual development and improvement different S W versions are to be found This document is valid for S W version 1 0 x On the date of the document is x 3 EBL128 is produced for many countries accordingly the look the texts the functions etc might vary Products Consists of one or more parts H W according to a Product Parts List A product has e atype number e g 4550 e an article number often the type no but sometimes is a country code added e g 4550SE e
9. in EBL128 e The buzzer in EBL128 sounds steady continuous e Output R1 for routing equipment Fault tx is activated e Programmable output for general fault is activated e Programmable output for general charge fault is activated if it is a charge fault e LED Fault tx activated L11 is turned ON e LED General fault L7 is turned ON e LEDs Fault Disablements Alarm devices L13 System fault L14 and or Fault Disablements Fire brigade tx L15 might be turned ON as well depending on the type of fault e A fault message incl date and time is shown in the display Example of a fault message FAULT No reply xx xx gt Date MMDD Time HH MM Press gt to see the technical address FAULT No reply techn address xxx lt S Date MMT DD Time HH MM Press to see the zone address e If more than one fault is activated the text More faults is added after the time e Ifa fault has been corrected before it has been acknowledged the status text Serviced is added after the time e Fire alarm presentation has higher priority than the fault messages During fire alarm presentation the faults can be shown via the special fire alarm menu X2 see page 32 All faults are latched and have to be acknowledged which is done via menu H6 see page 98 In this menu H6 can up to 100 faults be listed e Not corrected and not acknowledged faults e Not corrected but ac
10. the AA function can be continuously enabled Off 0 Via this menu H2 B10 it is possible to de activate disable the AA function i e the AA function will be disabled for the alarm points zones programmed for Alert Annunciation in spite of the time channel is on or if they are programmed to be continuously enabled The AA function will stay de activated disabled until re activated re enabled again via this menu Text in display ae Access According to chapter Access see page 62 Scroll to menu H2 Scroll to menu B10 A lert tion f c L Write 0 or 1 and press A to accept A De toraiere a i Scroll or press Return to OCF B1 menu H2 Scroll or press Return to log off 76 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 24 Set calendar and clock H3 When required the clock can be corrected so that the time stamps for fire alarms faults etc will be correct NOTE The RTC component has no built in battery i e if EBL128 is out of power no mains and no battery backup the date day of the week and time have to be set when EBL128 is powered up again In this menu is also the S W system program version shown NOTE The information shown in the display will be saved when you press A If you don t want to change anything e g if you only want to see the S W version press Return instead of
11. A to return to menu H3 Access According to chapter Access see page 62 Scroll to menu H3 Set calendar and clock ACCE Pie HS A Date YY MM DD Time hh mm ss Here is the S W version Weekday W 1 M 7 S VER vvvvvvvvvvvv_ shown e g VER 1 0 The time shown is the time when A was pressed in menu H3 When required edit the date time and or weekday Press A The clock starts again from the date time etc shown in the display NOTE Press Return instead of A to return to menu H3 if no changes are to be done A or Set calendar and clock Scroll or press Return to Return ACCEPT H3 log off 77 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 25 Present system status on H4 display 25 1 Disablement H4 U1 A list of all disablements done via menu H2 Bx NOTE Disablements by time channel s are listed in menu H4 U2 ann Scroll to menu H4 A When A is pressed the disablements will be shown in the display Some examples Comments According to chapter Access see page 62 Press A for presentation in the display L a list in which you can scroll If there are no disablements and if Return is pressed menu U1 will be shown again Scroll or press Return to menu H4 Scroll or press Return to log off On this row can also be shown adding information
12. Electric Works Fire amp Security Technology Europe AB MEW00509 29 6 Action Access Scroll to menu S5 A Write the zone and address WAN Return Write the zone and address WAS Rev 2 EBL128 Operating Instructions V1 0 x Activate address in alarm mode H8 S5 One alarm point zone address not a whole zone can be manually activated i e be set in alarm status NOTE All outputs standard and programmable which would have been activated by a real fire alarm from the same alarm point will be activated by this manually activated alarm as well Text in display Comments According to chapter Access code for service and maintenance see page 101 Press A to accept activate the fire alarm Normal fire alarm presentation in the EBL128 FBP display If more alarm points have to be set in alarm status press Return to select another zone address and continue as above Press A to accept start the fire alarm 106 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x What happens by reset of the fire alarm s is depending on a if you still are in menu H8 S5 and single encapsulated reset is used b if you still are in menu H8 S5 and multiple reset is used or if you are logged out by pressing Return two times or automatically after 10 minutes Alternative a S
13. The fuse is not replaceable More components might also be broken The main board has to be replaced FAULT High current consumption in CU EBL128 current consumption including battery charging is over 1 8 A and because of this the battery charging is turned off Normally this fault only appears when starting up expanding an EBL128 FAULT Interlocking input AA PP An interlocking input is not activated within the time set for fault activation 5 255 seconds The time is counted from the activation of the output in the interlocking combination area point FAULT Key cabinet The key cabinet has been opened without a prior fire alarm i e somebody has opened the key cabinet illegally or The key cabinet has not been closed within 5 minutes after reset of all fire alarms FAULT Loop unit xx xx gt Press gt to see the technical address 45 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x FAULT Loop unit techn address xxx The communication with the unit is not all right i e the unit is out of order faulty For detector types 33xx 43xx in NORMAL mode The built in self verification function has reported a fault status FAULT Low battery capacity Battery voltage lt 21 9 V The battery is presumably too old FAULT Low mains e Mains voltage below 187 V AC Blown fuse 230 V AC or no vol
14. a product name e g EBL128 Control amp Indicating Equipment 128 addresses H w A H W e g a printed circuit board has e atype number e g 1556 e an article number often the type no but sometimes is a country code added e g 1556SE e a product name e g Main Board 128 addr e ap c b number e g 9261 3A and can also have a configuration e g CFG 1 and a revision e g REV 2 e sometimes a S W S W A S W has e aversion number e g V1 0 or V1 0 x e sometimes additional information such as Convention different functions facilities Language etc File name K PRO FIRE 128 Doc V1 0 x MEW00509 doc gt Dimensions amp overviews connection diagrams etc Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x PC S W A PC S W is a program used for programming commissioning etc It has a version number Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 2 Rev 2 EBL128 Operating Instructions V1 0 x Definitions Explanations 2 1 2 2 2 2 1 2 2 2 2 2 3 2 2 4 2 2 5 2 2 6 2 2 7 Definitions explanations abbreviations etc frequently used or not explained elsewhere in the document PEWF amp STE AB Panasonic Electric Works Fire amp Security Technology Europe AB Alarm point Unit which can generate a fire alarm in EBL128 i e a sensor a conventional
15. acknowledged see chapter Acknowledge FAULTS H6 page 98 there is a 5 minutes delay before a new key cabinet fault can be generated again 7 Input 10 or COM loop I O unit 3361 can be used 37 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 15 Rev 2 EBL128 Operating Instructions V1 0 x Alarm reset 15 1 15 2 15 2 1 15 2 2 Pre warning reset Pre warning is automatically reset Fire alarm reset NOTE The detectors having activated the fire alarms shall after reset be inspected tested and replaced when required One of the following alarm reset alternatives is valid This is selected via Win128 Multiple reset is default Multiple reset All the fire alarms will be reset by pressing Reset P3 According to the EN54 2 standard NOTE The push button has to be pressed in for min 0 5 sec When all fire alarms are reset LEDs Fire L1 and Alarms queued L2 are turned OFF and the display is empty All outputs for fire alarm have also been reset i e de activated If a key cabinet is installed the key to the building has to be put back into the key cabinet within 5 minutes If not a fault will be generated and a fault message will be shown in the display see chapter Key cabinet alarm reset page 40 Single encapsulated reset This function set in Win128 is a violation to the EN54 2 standard Fire alarm reset Each fire alarm has to be
16. alarm status it will activate a new fire alarm within 20 seconds According to the EN54 2 standard When Single encapsulated reset is performed an alarm point or zone still in alarm status will not activate a new fire alarm It becomes encapsulated i e automatically disabled and has to be re enabled via menu H2 B4 or B5 before it can activate a new fire alarm again LED Disablements L8 is indicating that one or more zones alarm points have been encapsulated automatically disabled NOTE When Multiple reset is used encapsulated reset can be done by pressing Reset P4 and 0 1 sec later also press Alarms queued P1 and hold them pressed for gt 0 5 sec The fire alarm displayed in the LCD first row to the left will be encapsulated or the whole zone conventional will be encapsulated Alert Annunciation Regarding the function see chapter Alert Annunciation alarm AA alarm page 34 and EBL128 Planning Instructions chapter Alert Annunciation Reset of the AA alarm can be done via push button Reset on an AA unit 1735 1736 an AA controller 1740 or in EBL128 AA alarms will be reset all at a time NOTE Reset via an external unit is only possible during the investigation time and only AA alarm s can be reset not normal fire alarms Co incidence alarm Co incidence alarm is automatically reset i e when the alarm point is no longer in alarm status See also chapter Co incidence alar
17. chapter Silence Alarm devices page 22 This function has higher priority than Silence alarm devices Textin display Sn Access According to chapter E _ Access see page 62 Scroll to menu H2 Scroll to menu B4 A gt Press 0 control output 1 extinguishing output 2 ventilation output 3 alarm devise output Press A to accept A Press A to accept Depending on the LED Disablements L8 chosen type 0 1 2 or 3 will light up the following will be If type 3 alarm devices are disabled also the LED Fault Disablements Alarm devices L13 will light up shown Press o a ee aY or m3 and press A to accept or Return to menu B4 Scroll or press Return to menu H2 Scroll or press Return to log off 69 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 23 5 Re enable zone H2 B5 Disabled zones are listed in menu H4 U1 Re enabling via this menu has higher priority than automatic re enabling Zones disabled via the Encapsulation function see chapter Single encapsulated reset page 38 have to be re enabled via this menu before they can activate a new alarm When all zones have been re enabled the LED Disablements L8 will be turned OFF if there are no other disablements NOTE It is not possible to collectively re enable a number of alarm
18. detector a manual call point etc Smoke detector Two types of analog and conventional smoke detectors are available photo electric optical and ionization Sensor Sensor Analog detector Analog detector Contains an A D converter EBL128 pick up the digital values sensor values for each detector individually All evaluations and decisions are then made in EBL128 Analog detectors are addressable an address setting tool is used An analog detector has to be plugged in an ASB Analog Sensor Base ASB A sensor is plugged in an ASB which is connected to a COM loop see below Conventional detector Detector with two states normal or fire alarm The detector contains a closing contact and a series alarm resistor Some types are plugged in a CDB see below but some types are water proof and are not plugged in any base Conventional detectors are normally plugged in a CDB see below and connected to a conventional zone line with end of line device Conventional Detector Base CDB A conventional detector is plugged in a CDB and connected to a conventional zone line input Addressable A unit with a built in address device e g a manual call point Each unit is individually identified handled and indicated in EBL128 The unit can consequently be an I O unit to which one or more conventional alarm points can be connected on the zone line Panasonic Electric Works Fire amp Security Techno
19. during physical connection disconnection of units it is highly recommended to have the zone line disconnected disabled i e voltage free dead Disconnected disabled zone line is indicated by LED Disable ments and is listed in menu H4 U1 Access According to chapter Access code for service and maintenance see Scroll to menu A2 A Write 0 or 1 and press A to accept Depending on if 0 or Write the 4580 board no 1 is chosen one of 0 3 and the zone line the following will be input no 0 7 Press A shown 7 to accept Write 0 or 1 and press A to accept or press Return menu Al Scroll or press Return to H5 Scroll or press Return to log off 89 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 26 3 Calibration of supervised outputs H5 A3 The voltage outputs SO S1 in EBL128 and VOO VO1 in 3364 are supervised monitored When all the units sounders etc have been connected including required capacitors and when the SSD download is ready a calibration has to be done Function If the actual value differs from the calibrated value a small tolerance or if the calibrated value is outside the calibration range 470nF 5x470nF a fault will be generated NOTE Each output s logic is programmable via Win128 to be normally low default or normally high 24V Only outputs programmed to
20. g 45 ss seconds e g 45 The above information might be replaced with some other information The type of information and the priority order are as follows 1 Fire alarms Co incidence alarms Pre warnings Evacuate information only valid in some conventions 2 3 4 5 Faults not acknowledged 6 Disablements 7 Zones in Test mode 8 Interlocking inputs outputs active NOTE The different type of alarms faults etc are described in other parts of this document Fire alarm have a log off function i e if a menu window is open when a fire alarm is activated an automatic menu log off will take place and the fire alarm will be presented in the display instead Some information is available and some actions are possible to perform via the Fire alarm menu X1 X9 see chapter Fire alarm page 29 17 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 7 Rev 2 EBL128 Operating Instructions V 1 0 x Access levels 7 1 7 2 Access level 2A 2B 3A 3B EBL128 has five access levels for different kind of users Scroll browse through the queued alarms Required action None Door closed Fire brigade key Fire brigade key access code for level 2B or 3A Fire brigade key access code for level 3A PC Win128 connected PC access code for level 3B PC Win128 connected PC access code for level 3B User
21. has to be downloaded in EBL128 S W Software System program The S W makes the microprocessor in EBL128 work It is factory downloaded but a new version can be downloaded on site Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 3 Rev 2 EBL128 Operating Instructions V1 0 x Overview 3 1 3 2 3 3 3 4 3 5 The EBL128 c i e EBL128 is a microprocessor controlled intelligent fire alarm c i e intended for analog addressable smoke and heat detectors Also conventional detectors and manual call points can be used Programmable inputs control outputs and I O units are available Up to 128 addresses can be connected to EBL128 EBL128 is fully compliant with the European standard EN54 parts 2 and 4 and the front is fully SS3654 compliant S W versions Due to continual development and improvement different S W versions can be found You can update the S W in EBL128 on site Documents The following documents are available e Planning instructions e Drawings e Operating instructions Normally information that is found in one document is not to be found in another document i e the documents complement each other Also a Product Leaflet is available http www mfstech com news html Applications EBL128 is intended for small and medium installations The intelligent c i e offer the system designer and end user a technically sophisticated range of facilities and functions Pr
22. in the downloaded SSD EAUS Site speek le data SSD EBE x The fault has to be acknowledged and it can last up to 10 minutes before the communication returns to communicate in the A direction only 49 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x rr BP 1826 1828 Ext Fire Brigade Panel There is no SSD Site Specific Data downloaded to the unit or something is wrong in the downloaded SSD INU IES T OUEPUEC SX This is valid for the EBL128 voltage outputs SO and S1 If the output is programmed for sounders type 3 alarm devices it is also indicated by LED Fault Disablements Alarm devices L13 blinking If the output is programmed for fire brigade tx type 4 routing equipment it is also indicated by LED Fault Disablements Fire brigade tx L15 blinking Calibration not performed via menu H5 A3 Short circuit break on the connected cable equipment Connected equipment might be stolen End of line capacitor s missing or not correct value see drawing 128 22 NOTE The calibrated value has to be in the range 470 nF 5 x 470 nF 2350 nF FAULT Output x techn addr xxx This is valid for COM loop output unit outputs If the output is programmed for sounders type 3 alarm devices it is also indicated by LED Fault Disablements Alarm devices L13 blinking If the output is programmed
23. not programmed for fire alarm at short circuit A programmable input is used for an external fault to be presented in EBL128 with a fault message 51 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 16 2 Fault acknowledge The LEDs Fault tx activated L11 and General fault L7 are turned ON LEDs Fault Disablements Alarm devices L13 System fault L14 and or Fault Disablements Fire brigade tx L15 might be turned ON as well Output for routing equipment Fault tx is activated Output for general fault is activated Output for general charge fault might be activated A fault message date and time is shown in the EBL128 display After the time might be shown More faults more than one fault is generated After the time might be shown Serviced the fault is already serviced corrected e Login according to chapter Access page 62 e Use menu H6 access code for level 2B required for fault acknowledge see chapter Acknowledge FAULTS H6 page 98 Menu H6 is a list showing a maximum of 100 faults not acknowledged faults and or acknowledged but not corrected faults The first fault in the list is the most recent fault When a fault is acknowledged and corrected it will be removed from the list and a new fault can be shown if there are more than 100 Corrected faults are shown in the event log me
24. points that have been individually disabled via menu H2 B2 Action Text in display Comments Access According to chapter Access see page 62 Scroll to menu H2 Scroll to menu B5 If there are no zones to re enable menu B5 will be shown again L a list in which you can scroll If it s the correct zone to re enable press A to accept If not scroll or write the wanted zone and press A to accept If more re enablements shall be done continue like above If not scroll or press Return to menu H2 Scroll or press Return to log off 70 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 23 6 Re enable zone address H2 B6 Disabled alarm points zone address are listed in menu H4 U1 Re enabling via this menu has higher priority than automatic re enabling Alarm points disabled via the Encapsulation function see chapter Single encapsulated reset page 38 have to be re enabled via this menu before they can activate a new alarm When all alarm points have been re enabled the LED Disablements L8 will be turned OFF if there are no other disablements Text in display Comments Access According to chapter Access see page 62 Scroll to menu H2 Scroll to menu B6 If there are no zone addresses to re enable menu B6 will be shown again L a list in which you can scroll If it s the correct
25. text in the Action and Text in display columns Use T and 4 to scroll between the main menus H1 H10 Use A to accept Some main menus have sub menus Use 1 and J to scroll between the sub menus e g B1 B10 Use A to accept NOTE The menus are circular i e if you scroll with L and the last menu is reached the first menu comes up next It is also possible to make quick jumps within each menu e g in menu H1 press 6 for a quick jump to menu H6 0 menu H10 Instead of a menu identification e g B1 the letter L can be shown which means that it is a List Use T and J to scroll in the list gt to get more If lt or is shown in a menu use lt or information Use lt and gt to move the cursor in a menu Use Return to return from a sub menu to the main menu H1 H10 Use Return to log off from a main menu H1 H10 There will be an automatic log off 60 minutes after the last action i e if the key pad push buttons have not been used for 60 min 62 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 22 Perform monthly test H1 EBL128 and the installation shall be tested on a regular basis If one twelfth of the alarm points are tested each month the whole installation will be tested after one year In test mode only the alarm points are tested i e no outputs no sounders will be act
26. to the wanted menu and press A 28 Up to 128 alarms can be presented in the display Alarm ZONE and or ZONE ADDRESS The alarms will be printed like they are presented in the display i e as an alarm point ZZ AA or a zone ZZ and alarm text if programmed 30 Access code is not required 31 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 14 2 1 1 14 2 1 2 14 2 1 3 Rev 2 EBL128 Operating Instructions V1 0 x Display alarms X1 Press A First row Explanations in chapter Fire alarm page 29 Second row All fire alarms up to 128 alarms will be displayed one at a time in chronological order i e the first alarm 001 will be the same alarm as displayed on the first row 001 of 003 alarm number one of three alarms in the system is displayed to the left One alarm is an alarm point ZZ AA or a zone ZZ Press v to see the next alarm 002 of 003 alarm number two of three alarms in the system is displayed to the left Press v to see the next alarm 003 of 003 alarm number three of three alarms in the system is displayed to the left Display faults X2 Press A Only the fault message for the fault respectively will be displayed here not date time and status information Press Vv to see the next fault Display disablements X3 NOTE Also zones in Test mode will be displayed via this menu Press A 32 Panasonic
27. zone address to re enable press A to accept If not scroll or write the wanted zone address and press A to accept A If more re enablements shall be done continue like above If not scroll or press Return to menu H2 Scroll or press Return to log off 71 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 23 7 Re enable output H2 B7 Disabled outputs are listed in menu H4 U1 When all outputs have been re enabled the LED Disablements L8 will be turned OFF if there are no other disablements When all outputs type 3 alarm devices have been re enabled the LED Fault Disablements Alarm devices L13 will be turned OFF o A If there are no outputs to Comments According to chapter Access see page 62 Press 0 MIO 3361 or ASI 3377 or ASB 3378 or AOU 3364 1 C i e output S0 S1 2 C i e output RO 3 C i e exp board relay output Press A to accept Depending on the re enable menu B7 will be chosen type 0 1 2 or 3 R k shown again the following will be L a list in which you can shown scroll Regarding the ASI 3377 amp ASB 3378 unit outputs O high priority 1 low priority If it s the correct output to re enable press A to accept If not scroll or write the wanted output and press A to accept Relay board 0 1 Relay output 0 7 72
28. 1 Voltage in A direction 2 Voltage in B direction 3 Voltage in both direc tions 1 2 or 3 selected is indicated by LED Disablements L8 The communication is now turned off on the COM 92 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x loop but there is still voltage in the A direction This state will last until another alternative is selected or the service mode is turned off E g 0 A Service mode for COM loop Scroll or press Return to ACCEPT A5 H5 Scroll or press Return to log off The service mode can also be turned off via menu H5 A1 i e Re connect 1 COM loop 93 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 26 6 Show information about Site Specific Data H5 A6 Information about the latest downloaded Site Specific Data SSD is shown New SSD can be downloaded via a PC and Win128 Access According to chapter Access code for service and maintenance see Scroll to menu A6 A YY year MM month DD day hh hour mm minute A Scroll or press Return to E H5 Scroll or press Return to log off 70 As written in the field Name in the Win128 dialog box Control Unit Properties If there is no SSD downloaded to EBL128 the following text message will be shown No SSD downloaded 94 Panasonic Electric Works
29. 8 S7 As a protection against unauthorised personnel programming the system via Win128 an access code 3B for levels 3B and 4 for PC connection is required For security reasons the default code should be changed NOTE This code requires eight 8 digits Access According to chapter Access code for service and maintenance see page 101 A The digits are replaced E EEK in the display Wrong access code was entered Try again a Correct access code was PT entered The access code is now changed and the sub menu H8 S7 is shown Scroll or press Return to menu H8 Scroll or press Return to log off NOTE After change of access code it is recommended do a Safe shutdown of EBL128 see menu H8 S4 This will save the SSW data e g the new code in a Flash ROM see page 58 109 Panasonic Electric Works Fire amp Security Technology Europe AB Rev 2 MEW00509 30 EBL128 Operating Instructions V1 0 x Interlocking outputs and inputs H9 30 1 Action Scroll to menu H9 MAT Depending on activated output and or input the following will be shown Activated interlocking outputs inputs H9 C1 Text in display 110 According to chapter Access see page 62 This is a list in which you can scroll AA interlocking combination Area PP interlocking combination Point within the area Press Return to menu Cl Scroll or press Return to menu H9 Scr
30. Electric Works Fire amp Security Technology Europe AB MEWO00509 Rev 2 EBL128 Operating Instructions V1 0 x Press W to see the next disablement NOTE After all disablements will zones in Test mode be displayed 14 2 1 4 Disable zone X4 Press A Write a zone number 01 32 and press A If more zones are to be disabled repeat the procedure 14 2 1 5 Disable zone address X5 This function is useful e g for a manual call point not to continue to generate alarms because of a broken glass Press A E g Write a zone address and press A If more zone addresses are to be disabled repeat the procedure 14 2 1 6 Re enable zone X6 Press A E g This is a list of disabled zones Scroll to or write the wanted zone number and press A If more zones are to be re enabled repeat the procedure 33 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 14 2 1 7 14 2 1 8 14 2 1 9 14 2 2 Rev 2 EBL128 Operating Instructions V1 0 x Re enable zone address X7 Press A E g This is a list of disabled zone addresses Scroll to or write the wanted zone address and press A If more zone addresses are to be re enabled repeat the procedure Disable Re enable control X8 Press A E g To disable press 0 and A To re enable press 1 and A For more information see chapter Disable all control extinguishing
31. Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 26 7 Display current consumption on COM loop H5 A7 An average current consumption value can be displayed for the COM loop NOTE No or very small current consumption will not be presented correctly precisely Access According to chapter Access code for service and maintenance see Return Scroll or press Return t H5 Scroll or press Return to log off 95 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 26 8 Display statistics for COM loop H5 A8 The statistics can be used during commissioning service etc Pollings are the number of pollings questions sent out by EBL128 to the units connected on the COM loop Parity is the received number of parity faults and parity faults in relation to the pollings Bit length is the received number of bit length faults and bit length faults in relation to the pollings No of bits is the number of bit faults and bit faults in relation to the pollings Bit fault incomplete answer The Parity Bit length and No of bits values shall normally be 0 or as close to 0 as possible If not there are some communication problems that have to be investigated Check the COM loop connections and the loop units Check so that the COM loop cable is not placed too close to high voltage cables etc that
32. O00509 Rev 2 EBL128 Operating Instructions V1 0 x 25 5 Event log H4 U5 This is a list of the latest events in EBL128 The event list can also be read via Win128 NOTE The event logging is disabled as long as menu H4 U5 is open A Se Access According to chapter Access see page 62 Scroll to menu H4 Scroll to menu US Press A to accept When A is pressed an event will be shown in the display The most recent event e g will be shown i e use AX to scroll upwards in the list Press Return to menu US X 0 EBL128 X 1 Win128 X 2 Web128 Scroll or press Return to menu H4 Scroll or press Return to log off amp More than one alarm point in zone 32 have activated fire alarm 84 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 25 6 Show configuration H4 U6 Menu H4 U6 can be used to see the settings done via Win128 Language The language for the texts shown in the EBL128 display The text language file nnnn sst is selected and downloaded via the Win128 menu Download software texts to control unit dialog box Convention Because of country specific functions etc different conventions have to be used The default convention is selected the first time Win128 is opened but can if required be changed in the Win128 Settings dialog box Terin display anne Access According to chapter Acc
33. Panasonic Operating Instructions MEW00509 Revision 2 Fire Alarm System EBL128 V1 0 x Date of issue 2006 04 03 Date of rev 2006 08 31 Author Jan Pettersson This page has deliberately been left blank Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x Table of contents 2 1 2 2 Introduction Definitions Explanations PEWF amp STE AB Alarm point 2 2 1 Smoke detector 2 22 Sensor 2 2 3 Analog detector 2 2 4 Analog Sensor Base ASB 2 2 5 Conventional detector 2 2 6 Conventional Detector Base CDB 2 2 7 Addressable 2 2 8 Old detector 2 2 9 Conventional zone line 2 2 10 Addressable zone interface 2 3 2 4 2 5 2 6 Dal 2 8 2 9 2 10 2 11 2 12 2 13 2 14 2 15 2 16 3 1 3 2 3 3 3 4 3 5 6 1 7 1 7 2 Output unit Output Control output Short circuit isolator Display unit COM loop Control Unit C U C LE Fire Brigade Panel FBP Control panel CP LED External Indicator LED Display LCD Door open Key switch SSD Site Specific Data S W Software System program Overview The EBL128 c i e S W versions Documents Applications PC S W Control amp Indicating Equipment LED indicators and push buttons Normal operation The display in EBL128 Access levels Access level 1 Access level 2A COTCCOCOCODMAAAAAAAHOwHOOANNANIAYNAIAYNNANAAAN A p pb ek oe Ww me o0o0o0o0
34. Return to menu B4 Scroll or press Return to menu H2 Scroll or press Return to log off 74 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 23 9 Disable or re enable outputs for routing equipment H2 B9 Disabled outputs are listed in menu H4 U1 Outputs for routing equipment fire brigade tx fault tx can be disabled and re enabled via this menu Disabled output will stay disabled until re enabled again via this menu Can be useful during an installation and test period when only local alarms are required Disabled output is indicated by LEDs Disablements L8 and Fault Disablements Fire brigade tx L15 Text in display ee Access According to chapter Access see page 62 Scroll to menu H2 Scroll to menu B9 l A c To move the cursor press k d k gt Edit and or press A to accept A e or re ena f Scroll or press Return to i e pment return to H2 Scroll or press Return to log off 75 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 23 10 De activate alert annunciation function H2 B10 Normal function 1 For alarm points zones programmed for Alert Annunciation via Win128 is normally the AA function enabled via a time channel e g enabled daytime during working hours and disabled night time As an alternative
35. Rev 2 EBL128 Operating Instructions V1 0 x ZZ zone number 01 32 for the most recent zone in alarm Displayed also if only one alarm point is in alarm The information in the field C No nn nn 01 32 the total number of zones not alarm points in alarm The information in the field D A user definable alarm text max 40 characters for the alarm displayed in the field A Some Fire alarm examples One alarm point e g detector 12 45 One zone e g zone 14 a conventional zone line input More than one alarm point in one zone e g detectors 12 45 amp 46 The LED s Alarms queued L2 are indicating that more than one alarm point is in alarm Press the button Alarms queued P1 to see the other alarm One alarm point in two zones e g detectors 12 45 amp 13 02 The LED s Alarms queued L2 are indicating that more than one alarm point is in alarm Press the button Alarms queued P1 to see the other alarm More than one alarm point zone 30 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 14 2 1 Rev 2 EBL128 Operating Instructions V1 0 x LED s Alarms queued L2 are blinking 0 4 0 4 sec indicating more than one fire alarm To scroll through the alarms use the push button Scroll P1 The fire alarms are stored in a circular buffer and when scrolling from the last to the first alarm the LEDs Alarms queued will be turn
36. SW data e g the new code in a Flash ROM see page 58 115 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 32 Annual control The building occupier is highly recommended once a year to do some tests beside the monthly tests To avoid the Fault tx output to be activated it can be disabled via menu H2 B9 or via an open door se chapter Door open page 26 Regarding the fault condition see chapters Fault page 41 and Fault messages page 42 NOTE Most faults have a time delay EBL128 should be tested as follows e Perform monthly test menu H1 e Remove the battery fuse F2 on the main board 4556 The following fault message is to be shown FAULT Battery not connected CU e Put back the fuse and acknowledge the fault Menu H6 e Check the manual call point glasses Take required measures Use the manual call point alarm test key to activate some fire alarms e Check that the control outputs that should be activated really are activated according to programmed control expressions e Reset the fire alarms 116 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 33 Battery maintenance The batteries 2 x 12 V 15 18 Ah are placed inside EBL128 Larger batteries have to be placed outside EBL128 supervises the batteries and a fault will b
37. also chapter Disable all control extinguishing ventilation and alarm device outputs H2 B4 page 69 1 When more than one fire alarm is activated 20 Including Addressable siren 3377 and Addressable sounder base 3378 22 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 9 Silence buzzer The buzzer in EBL128 will sound for e pre warning 0 8 5 sec e co incidence alarm When only one zone address alarm point is in alarm status 0 8 5 sec e fire alarm 0 4 0 4 sec e fault continuous e disablements and faults 2 sec directly after the door to EBL128 is closed e activated interlocking input 0 8 0 8 sec if this option is selected via Win128 Press Silence buzzer P2 to silence the buzzer In case of a new alarm or if the push button Silence buzzer is pressed again the buzzer will automatically sound again NOTE This is also valid for pre warning co incidence alarm etc Silence buzzer by open door In Win128 can the function Silence Buzzer by Door Switch be selected The buzzer will then be turned off as long as the EBL128 door is open This function is a violation to the EN54 2 standard I Not valid if the buzzer is silenced by the open door 23 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 10 Disable Re enable all contr
38. ange access code for daily duties access level 2B 7 4 Access level 3A When the door has been opened the fire brigade key switch has been activated LED Door open is lit the service maintenance personnel have access like in access level 2A and 2B and after access code for level 3A the following menus H5 Service A1 Disconnect Re connect COM loop A2 Disconnect Re connect zone line input A3 Calibration of supervised outputs A4 Sensitive fault detection mode A5 Service mode for COM loop A6 Show information about site specific data A7 Display current consumption on COM loop A8 Display statistics for COM loop A9 Activate address setting mode for DU H8 Maintenance S1 Acknowledge SERVICE signal S2 Clear weekly average S3 Test alarm devices S4 Safe shut down of control unit S5 Activate address in alarm mode S6 Change access code for service and maintenance access level 3A S7 Change access code for PC communication 7 5 Access level 3B Used by Service maintenance commissioning engineers when a PC i e Win128 is to be connected to EBL128 for backup download of site specific data S Tf the code for access level 3A has already been used to logon to access level 2B a new logon to access level 3A is not required 20 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x Connect the PC and logon to EBL128 from the PC 7 6 Acce
39. ated via this sub menu S3 which makes it possible to test the alarm devices without to much disturbance on site The test can not be started if fire alarm is already activated in EBL128 When the test starts the alarm devices will sound for approx 5 seconds be silent for approx 25 seconds sound for approx 5 seconds 4 and so on NOTE Also disabled and silenced alarm devices will be tested Text in display Comments According to chapter Access code for service and maintenance see page 101 Write 1 or 0 and press A to accept The test will now continue until stopped via this sub menu S3 or automatically after one hour or if a fire alarm is activated Scroll or press Return to return to menu H8 Scroll or press Return to log off Including Addressable siren 3377 and Addressable sounder base 3378 74 The output activation will be steady continuous For the alarm devices 3377 and 3378 the tone with the highest priority level and type alarm device will be automatically selected 104 Panasonic Electric Works Fire amp Security Technology Europe AB Rev 2 EBL128 Operating Instructions V1 0 x MEW00509 29 5 Action Access Scroll to menu S4 A WAM Power down up or A or after 5 min Safe shut down of control unit H8 S4 It s not recommended to power down EBL128 without first doing a safe shut down Safe shut down will save the SSW i
40. be normally low can be supervised monitored Access According to chapter Access code for service and maintenance see page 87 Disconnect Re connect COM loop ACCEPT Al A Calibration in progress Please wait Scroll to menu A3 Calibration of supervised outputs ACCEPT A3 Calibration of supervised outputs Calibration is ready ACCEPT A3 Scroll or press Return to H5 Scroll or press Return to log off NOTE After the calibration it is recommended to do a Safe shutdown of control unit see menu H8 S4 This will save the SSW data e g the calibration values in a Flash ROM see page 58 68 An end of line capacitor 470nF in the last unit or a capacitor 470nF in up to five units As an alternative an output can via Win128 be set to not supervised 90 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 26 4 Sensitive fault detection mode H5 A4 Sensitive fault detection mode means that the time delay is reduced for all type of faults which makes it possible find faults during the commissioning instead of later NOTE Don t forget to turn this mode off after the commissioning Access According to chapter Access code for service and maintenance see page 87 heal nsi Press A or 1 and A to accept ON is indicated by LED Fault tx activated L11 and the Fault output for routing equipment This mode i
41. ccess white al Return white te fas a Operation function Used to acknowledge the faults shown in menu H6 Also used to acknowledge SERVICE signal see menu H8 S1 Not used in EBL128 Used to log on i e to get access to the menu tree via an access code to carry out disablements etc In conjunction with fire alarm some information is available and some actions are possible to perform via the Fire alarm menu X1 X9 without log on see chapter Fire alarm page 29 Used to stop input of data leave a menu one step up and to log off Numeric keys for the figures 0 9 Used to clear delete just written data Used to accept a menu and accept input of data Left right keys are used to move the cursor in a menu Up down keys are used to scroll between the menus 16 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 6 Rev 2 EBL128 Operating Instructions V1 0 x Normal operation 6 1 When EBL128 is in normal operation i e no fire alarms and normally no faults no disablements no service signal no zones in test mode no activated interlocking in outputs and or no open doors only the LED Operation L6 is to be lit The display in EBL128 The display will in normal operation show the following information EBLI28 Date YYYY MM DD Time hh mm ss YYYY Year e g 2005 MM Month 02 DD Day e g 28 hh hours e g 21 mm minutes e
42. cess According to chapter Access see page 62 Scroll to menu H7 Perform ZONE TEST NC CHD ie A Zone to be set in TEST MODE NOTE In Danish DBI Ee west T R Te Start test ACCEPT convention only one zone Write zone numbers Zone to be set in TEST MODE Press A to start the test e g 01 02 03 04 oL DA 03 04 Start test AC CHE a mode 2 03 WAN Zones are set in test mode LED Test mode L9 wait will light up Zone in TEST MODE Perform the tests Ol 04 End test ACCEPT The zone s will stay in test mode until the test mode is ended but after 60 minutes or if you press Return two times you will be out logged from menu H7 Perform the test as quickly as possible since the output s for routing equipment fire brigade tx are disabled also the parts of the zones in test mode not visible for the test personnel are disabled In order to shorten the testing time any time delay for the detectors zones in test mode will be disabled i e fire alarm will be detected faster than normally In the tested alarm point the LED will light up and the LED s Fire L1 in EBL128 will light up about ten 99 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x seconds then the alarm point will be automatically reset A sensor in test mode will not be able to activate fault After 60 minutes or You are now out logged Return from menu H7 but
43. croll or press Return to Reset menu H8 Scroll or press Return to log off Alternative b Reset NOTE Multiple reset is default By Single encapsulated reset each point has to be reset individually See also chapter Alarm reset page 38 7 Alarm reset is selected via Win128 Control Unit Properties tab Advanced 107 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 29 7 Rev 2 EBL128 Operating Instructions V1 0 x Change access code for service and maintenance H8 S6 For security reasons the default code should be changed Access Scroll to menu S6 Enter the old code the new code and the new code again Comments According to chapter Access code for service and maintenance see page 101 The digits are replaced in the display Wrong access code was entered Try again Correct access code was entered The access code is now changed and the sub menu H8 S6 is shown Scroll or press Return to menu H8 Scroll or press Return to log off NOTE After change of access code it is recommended do a Safe shutdown of EBL128 see menu H8 S4 This will save the SSW data e g the new code in a Flash ROM see page 58 108 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 29 8 Change access code for PC communication H
44. d FAULT Battery techn address xxx This is valid for an external power supply e g 3366 connected on the COM loop e Batteries 2 x 12 V are missing or not correctly connected e Battery fuse is blown 42 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x FAULT Cables mixed COM loop The two wires L SA and C SB have been mixed alternated Check so that the wire connections are correct according to drawing 128 21 FAULT Charging ext power supply The fault is to be found in the external power supply equipment A fault output is connected to a programmable input in the EBL128 system Check the input as well FAULT Charging techn addr xxx This is valid for an external power supply e g 3366 connected on the COM loop The battery charging function is not working all right The charger board 3367 may have to be replaced FAULT Checksum system program A fault in the EBL128 S W This is very serious Call for service personnel engineer immediately FAUNE CUE OLE SCN lt SCrA This fault is indicating a cut off break on the loop or that the COM loop voltage is too low at the end of the loop i e lt 12 V DC SCI n lt gt SCI n describes between which Short Circuit Isolators SCI s the cut off is located n A B 0 1 2 3 4 5 6o0r 7 A amp B is the built in isolator i
45. d B direction the unit can not be found Check the unit s address with the programming tool 3314 Faulty unit Detector might be removed un plugged from its base Double break or short circuit on the COM loop Note There will also be a fault message FAULT Cut off loop or FAULT Short circuit loop FAULT No reply AAU x AAU 1735 1736 Alert Annunciation Unit EBL128 can not communicate with the unit Check edit the address and the S W mode in the unit or edit the SSD FAULT No reply EPU x EPU 1728 Ext Presentation Unit EBL128 can not communicate with the unit Check edit the address and the S W mode in the unit or edit the SSD FAULT No reply expansion board x Valid for the 8 zones exp board 4580 and the 8 relays exp board 4581 mounted in the c i e EBL128 EBL128 can not communicate with the board Check edit the address Check the ribbon cable connections 4 The time is programmable in Win128 Max 30 min according to the EN54 2 standard Default value depending convention 47 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x HAUL NO reply EBET FBP 1826 1828 Ext Fire Brigade Panel EBL128 can not communicate with the unit Check edit the address and the S W mode in the unit or edit the SSD FAULT Read write site data SSW Some external influence
46. e disabled Blinking One or more supervised outputs type 3 alarm device have generated fault s disabled via menu H2 B3 or via an open door Blinking Routing equipment power supply output or one or more supervised outputs type 4 routing equipment have generated fault s The alert annunciation function is enabled i e the time channel controlling this function is on 10 See also chapter Door open page 26 1 This is also valid when EBL128 has no contact with a unit with such an output e g a 3377 3378 3361 etc 12 The LED is turned on during restart and stays on for restart code other than 00 and 03 until the fault is acknowledged S Main board terminal block J1 11 12 This is also valid when EBL128 has no contact with a unit with such an output e g an I O unit 3361 etc S The Alert Annunciation function is described in the EBL128 Planning Instructions chapter Alert annunciation The LED L16 will be on if the AA function is enabled for at least one alarm point zone Normally is only one time channel used for this function but two or more channels can be used The AA function can as an alternative be continuously on 15 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x Push buttons Keypad on the Control Panel CP Key push button Fault acknowledge yellow Paper feed white A
47. e activated if something goes wrong They are rechargeable sealed Lead Acid batteries and maintenance free but the producer s instructions are always to be followed The ambient temperature affects the battery capacity self discharge and life span It should if possible not be higher than normal room temperature For highest safety batteries used in a fire alarm installation should never be older than four years 117 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 34 How to avoid unnecessary nuisance fire alarms We all realise when life buildings production facilities etc shall be saved it is of utmost importance that an initial fire is detected as soon as possible That s why more and more automatic fire alarm systems are installed In an automatic fire alarm installation especially if smoke detectors sensors are used everybody in the building needs to be informed how to avoid so called unnecessary nuisance fire alarms To avoid trouble and unnecessary expenses there are a couple of things to bear in mind Here are some advice and tips Tobacco smoke The detectors sensors can not sense the difference between smoke and smoke They can not separate tobacco smoke from smoke from a fire Intensive tobacco smoking in connection with bad ventilation can cause a fire alarm Welding grinding cutting sawing amp drilling This kind of j
48. e chapter Alarm reset page 38 14 2 Fire alarm 128 alarms points or zones can be presented in the EBL128 display See also chapter The display in EBL128 page 17 According to the ENS54 2 standard in case of a fire alarm the following will happen The buzzer in EBL128 sounds 0 4 sec each 0 4 sec 0 4 0 4 sec e LEDs Fire L1 are blinking 0 4 0 4 sec e Output for routing equipment Fire brigade tx e Outputs for fire alarm are activated e In the EBL128 display and ext FBP display the fire alarm s will be presented See below Fire alarm presentation in the EBL128 display B 1234567890123456789012345678901234567890 C I O ENN D A Field for the first alarm point or zone in alarm By scrolling each alarm will be shown in this field B Field for the most recent zone in alarm C Field for total number of zones in alarm D Field for alarm text User definable Comments to the different fields The information in the field A NNN ZONE ADDR ZZ AA or NNN ZONE ZZ NNN a serial number for the displayed alarm i e 001 for the first activated alarm ZZ AA 002 for the second alarm and so on ZZ zone number 01 32 AA address 01 99 The information in the field B LAST ZONE zz 7 Outputs programmed for General fire alarm and outputs programmed for the activated fire alarm s 29 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509
49. e g e Automatic re enablement HH MM e by open door in CU 78 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 25 2 Disablement by time channel H4 U2 A list of all disablements by time channel s NOTE Other disablements are listed in menu H4 U1 A TE A When A is pressed the disablements will be shown in the display e g When scrolling in the list the message No more zone addresses disabled by time channel found in the system can be shown 79 Comments According to chapter Access see page 62 Press A for presentation in the display L a list in which you can scroll If there are no disablements and if Return is pressed menu U2 will be shown again Scroll or press Return to menu H4 Scroll or press Return to log off Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 25 3 Sensor values H4 U3 The very first week average sensor value is calculated within 2 minutes after SSD download amp restart During these 2 minutes fire alarm from analog smoke detectors are suppressed and the sensor value 000 will be shown The Performance factor and Min Max values are updated each night 00 00 i e the values shown are from the previous day Text in display Comments According to chapter hee E g 01 01 A Ty
50. e input can be disabled via menu H5 A2 Don t forget to re enable via menus H2 B4 B9 or use automatic re enablement for zones and alarm points Disablements are indicated by LED Disablements L8 and are also shown in the display An example Zone 01 is disabled More More is indicating two or more disablements Disablements and faults are indicated by a 2 sec beep when an open EBL128 door is being closed Disable zone H2 B1 When a whole zone is disabled all alarm points within the zone are disabled including the addressable manual call points All zones can be disabled Disabled zones are listed in menu H4 U1 Disabled zones can be automatically re enabled or they have to be re enabled via menu H2 B5 57 See chapter The display in EBL128 page 17 regarding priority order 65 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO00509 Rev 2 EBL128 Operating Instructions V1 0 x Text in display Comments Access According to chapter Access see page 62 Scroll to menu H2 Write zone number e g Press A to accept Press 1 for aut re enabling and accept or change the time max 24 hours Press A to Default is current time 3 hours accept LED Disablements L8 will light up If more disablements shall be done continue like above If not press Return to menu B1 Scroll or press Return to menu H2 Scroll or press Return to log off
51. ed off for approx three seconds When the Scroll button has been used the first alarm will be automatically displayed again after 20 seconds If an ext FBP 1826 with a built in printer is connected the printer will print each fire alarm e g xxx Fire Alarm ZONE ADDR 12 45 Time HH MM Date MM DD Alarm text for 12 45 or xxx Fire Alarm ZONE 14 Time HH MM Date MM DD Alarm text for zone 14 Reset of the fire alarms see chapter Alarm reset page 38 Fire alarm menu X1 X9 During the fire alarm presentation a special fire alarm menu can be used If this menu option is excluded via Win128 it is a violation to the EN54 2 standard Fire alarms can be displayed via this menu but first of all it can be used to display faults and disablements in the system Alarm points zones control outputs and alarm devices can also be disabled re enabled via this menu During the fire alarm presentation press button Access and the alarm text will be replaced with the following 001 ZONE ADDR 12 45 LAST ZONE 12 No O1 Display alarms ACCEPT X1 A IY A gt and Return can be used like in the normal menu tree see chapter Access page 62 The original presentation the alarm text will be automatically displayed again approx 20 seconds after the push buttons A Vv 4 gt or Return are no longer used Press A or scroll
52. ensor values H4 U3 80 25 3 1 Reset of a week average sensor value 82 25 4 Sensors activating SERVICE signal H4 U4 83 25 5 Event log H4 U5 84 25 6 Show configuration H4 U6 85 26 Service H5 86 26 1 Access code for service and maintenance 87 Disconnect Re connect COM loop H5 A1 88 26 2 Disconnect Re connect zone line H5 A2 89 26 3 Calibration of supervised outputs H5 A3 90 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 26 4 26 5 26 6 26 7 26 8 26 9 27 28 29 29 1 29 2 29 3 29 4 29 5 29 6 29 7 29 8 30 30 1 30 2 30 3 30 4 30 5 31 32 33 34 35 EBL128 Operating Instructions V1 0 x Sensitive fault detection mode H5 A4 91 Service mode for COM loop H5 A5 92 Show information about Site Specific Data H5 A6 94 Display current consumption on COM loop H5 A7 95 Display statistics for COM loop H5 A8 96 Activate address setting mode for DU H5 A9 97 Acknowledge FAULTS H6 98 Perform ZONE TEST test mode H7 99 Maintenance H8 101 Access code for service and maintenance 101 Acknowledge SERVICE signal H8 S1 102 Clear weekly average H8 S2 103 Test alarm devices H8 S3 104 Safe shut down of control unit H8 S4 105 Activate address in alarm mode H8 S5 106 Change access code for service and maintenance H8 S6 _ 108 Change access code for PC communication H8 S7 109 Interlocking outputs and inputs H9 110 Activated interlocking outputs inputs
53. ent will be activated as well indicated by the LED Fire brigade tx L15 e After another 30 seconds the test will be ended and all the outputs and LEDs will return to normal i i nn starts at 60 and will count down to 00 Scroll or press Return to log off NOTE This output is activated in normal state 64 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 23 Rev 2 EBL128 Operating Instructions V1 0 x Disable or re enable H2 23 1 A whole zone one or more alarm points within a zone and or control outputs can be disabled via menus H2 B1 B3 This possibility can be used when a temporary disablement is wanted e g craftsmen working in the premises etc A disabled alarm point will not activate Pre warning fire alarm or fault Addressable manual call points can be disabled when required but shall normally not be disabled NOTE When a whole zone is disabled also the addressable manual call points will be disabled e Zones 01 32 can be disabled via menu H2 B1 e All alarm points zone address can be individually disabled via menu H2 B2 e All outputs can be individually disabled via menu H2 B3 Disabled output will stay in or return to the normal condition for the output respectively NOTE e All Interlocking outputs can be individually disabled via menu H9 C4 e The COM loop can be disabled via menu H5 A1 e A zone lin
54. enu H6 the LEDs will be turned OFF if there are no other faults After a cold restart required disablements have to be done Memory fault In case of a fault in the S W system program the following text message will be shown in the display This is also indicated by LED System fault L14 and the buzzer sounds steady continuous The Fault tx output is activated A new download of the S W system program is required NOTE After SSD download see chapter SSD programming amp download page 54 the following messages might be shown The last one means that the SSD have not been correctly downloaded A new SSD download has to be performed Boot menu The Boot menu should be used by authorised personnel only NOTE Vital data can be erased via this menu The Boot menu is opened as follows Perform a cold restart i e Power down power up EBL128 The following text messages will be shown in the EBL128 display And after that for a second When the text Booting appears press Access and 0 1 sec later also press 1 and the Boot menu will be shown 60 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x Press 1 to perform a restart you will also leave the Boot menu Press 2 to open the Erase memory menu see below The Erase memory menu Press 1 to erase the SSD memory Press 2 to erase the SSW memory Pre
55. ess see page 62 Scroll to menu H4 tat Scroll to menu U6 Press A to accept Press Return to menu U6 Scroll or press Return to menu H4 Scroll or press Return to log off In order to present all language specific characters correct also the Control unit language has to be set to the correct language This is done in the Win128 settings dialog box 6 To set change the convention in Win128 Level 2 has to be selected and to do this a password is required 85 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 26 Service H5 When commissioning an installation at power up etc and by maintenance programming etc menu H5 can be used to get certain information and help Only authorised personnel have access to the level 3A menus Access code for level 3A is required Via a PC and Win128 access code 3B for levels 3B and 4 you can e download upload backup Site Specific Data SSD e download new S W text file settings configuration etc e create and download the alarm texts shown in the display in EBL128 ext FBP AAU EPU Connected to the D connector J3 RS232 on the main board 86 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO00509 Rev 2 EBL128 Operating Instructions V1 0 x 26 1 Access code for service and maintenance Access code to level 3A is re
56. et outputs for alarm red devices C Evacuate green Used to activate the sounders i e the outputs for alarm devices Led test green i Used to activate all LEDs on the front for a short while U Alert Annunciation sed to acknowledge alert annunciation signal Acknowledge green Reset green Used to reset the fire alarm s Has to be pressed for gt 0 5 Disable yellow R Jsed to disables all zones in alarm state CP LED indicators on next page 5 Multiple reset Default All fire alarms will be reset simultaneously Single encapsulated reset The fire alarm displayed in the LCD first row to the left will be reset When more than one fire alarm is activated LEDs Alarms queued are lit each fire alarm has to be individually reset The encapsulation function is described in chapter Single encapsulated reset page 38 NOTE 1 When Multiple reset is used encapsulated reset can be done by pressing Reset P4 and 0 1 sec later also press Alarms queued P1 and hold them pressed for gt 0 5 sec The fire alarm displayed in the LCD first row to the left will be encapsulated or the points in alarm status within one zone will be encapsulated or the whole zone conventional will be encapsulated NOTE 2 When Single encapsulated reset is used you can make a Multiple reset by pressing Reset P4 and 0 1 sec later also press A in the keypad and hold them pressed for gt 0 5 sec
57. etc on the front i e the Fire Brigade amp Control Panel see below Fire Brigade Panel FBP The Fire Brigade Panel is a part of the EBL128 front intended for fire alarm presentation etc for the fire brigade personnel A separate unit an external FBP can also be connected to EBL128 In the ext FBP a printer can be included Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 2 10 2 11 2 12 2 13 2 14 2 15 2 16 Rev 2 EBL128 Operating Instructions V1 0 x Control panel CP The Control Panel is a part of the EBL128 front intended for the building occupier service personnel etc to communicate with EBL128 LED LED Light Emitting Diode Yellow green or red optical indicator lamp External Indicator LED A unit with an LED Connected to an ASB CDB or a detector with a built in LED for external indication Lit when the built in LED is lit Display LCD LCD Liquid Crystal Display Display for presentation of fire alarms fault messages etc Normally alphanumeric characters and backlight Door open Key switch A door key switch which has to be activated in order to get access to the push buttons on the front Indicated by the LED Door open SSD Site Specific Data This data is unique for each installation All alarm points presentation numbers alarm texts programmable outputs etc are programmed configured in the PC program Win128 and
58. ext file shall be downloaded do not forget to mark the checkbox Download texts and select the path and the text file e g English_texts_EBL128_V V sst Download software texts to control unit M Download software Select EBL128 program file KSPR OJSEBL1285EBL128_1 1 BIN Browse M Download texts Select text file KSPR OJSEBL128 English_texts_EBL128_1 1 sst Browse Port Baud COM1 X 57600 2 Select Port on the PC and baud rate If the download is not successful it might depend on to high baud rate 3 Start the download i e click Start The download status is indicated in the progress bar LED Operation L6 will be turned off LED General fault L7 is indicating that EBL128 is in the so called Boot mode LEDs Alarms queued L2 are Makes the microprocessor work 51 Normally a new text file will come together with a new S W file NOTE Only a text file can be downloaded If so do not mark the checkbox Download software 56 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x indicating the Flash memory programming In the EBL128 display is the following information shown Software download in progress 4 To the left of the progress bar is a indicator It will show approx 90 when the download is ready and EBL128 will automatically do a restart 5 After the restart the indicat
59. for fire brigade tx type 4 routing equipment it is also indicated by LED Fault Disablements Fire brigade tx L15 blinking Calibration not performed via menu H5 A3 Short circuit break on the connected cable equipment Connected equipment might be stolen End of line capacitor s missing or not correct value see drawing 128 28 NOTE The calibrated value has to be in the range 470 nF 5 x 470 nF 2350 nF FAULT Wrong type expansion board x Valid for the 8 zones exp board 4580 and the 8 relays exp board 4581 mounted in the c i e EBL128 The board is not the same type as programmed in the SSD Change the programming via Win128 or the board 50 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x Press gt to see the technical address The unit is not the same type as programmed in the SSD Change the programming via Win128 or the unit Press gt to see the technical address or the expansion board 4580 number and input number a Valid for the Multi purpose I O unit 3361 connected on the COM loop monitored zone line input Z Break on the zone line or wrong no end of line capacitor short circuit if not programmed for fire alarm at short circuit b Valid for the 8 zones exp board 4580 mounted in the c i e EBL128 Break on the zone line wrong no end of line capacitor short circuit if
60. g Instructions V1 0 x Return two times you will be logged out from menu H1 Perform the test as quickly as possible since the output s for routing equipment fire brigade tx are disabled also the parts of the zones in test mode not visible for the test personnel are disabled In order to shorten the testing time any time delay for the detectors zones in test mode will be disabled i e fire alarm will be detected faster than normally In the tested alarm point the LED will light up and the LEDs Fire L1 in EBL128 will light up about ten seconds then the alarm point will be automatically reset A detector in test mode will not be able to activate fault After 60 minutes or one sst mode 2 You are no longer in menu Return H1 but still in test mode Bam NOTE See chapter The display in EBL128 page 17 regarding priority order When required 7 in TEST MODI Press A to end the test Access code te mode A A f uti nent The LED Test mode is gt turned OFF Some national regulations also require a routine test of the routing equipment Press A for no test or press 1 and A to start such a test The following will happen e EBL128 Fault tx output will be de activated indicated by the LED Fault tx activated L11 A 60 seconds count down starts e After 30 seconds EBL128 Fire brigade tx output and corresponding programmable outputs type 4 routing equipm
61. ght and all LCD pixels are lit Alert Annunciation Acknowledge The button Alert Annunciation Acknowledge P5 has the same function as the Acknowledge button on an AA unit 1735 1736 Disable When the push button Disable P5 is pressed all zones in fire condition will disabled 25 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 12 Rev 2 EBL128 Operating Instructions V1 0 x Door open 12 1 12 2 12 3 A special key is used to open the EBL128 door to get access to the front see chapter Access levels page 18 The same type of key is also used to open the ext FBP door the key switch Door open is indicated by LED Door open L10 LED Door open Valid for the door in EBL128 or an external FBP connected to EBL128 Door open in EBL128 is indicated by LED Door open in EBL128 and all ext FBPs connected to EBL128 Door open in an ext FBP is indicated by LED Door open in EBL128 and all ext FBPs connected to EBL128 Outputs for routing equipment Fire brigade tx and Fault tx In Win128 the following can be programmed O Disable by door in the control unit Door open in EBL128 will disable the output s for routing equipment Fire brigade and fault tx Disabled outputs for routing equipment are indicated by the LED Disablements L8 and Fault Disablements Fire brigade tx L15 and listed in menu H4 U1 In the display is shown Fire alarm
62. has caused a fault in the SSW the data that is changed during operation i e sensor values access codes etc This is very serious Call for service personnel engineer immediately FAULT Restart code xx addr yyyyyyyyyyy C i e EBL128 restart has occurred See also page 58 xx 00 Power up Restart Power supply connected xx 01 Watchdog Reset xx 02 Accidental jump to reset vector xx 03 Restart after SSD Software text file download xx 04 19 Unexpected interrupt xx 20 S W monitoring fault NOTE xx 00 and 03 are normal Only acknowledge the fault xx 01 02 or 04 20 appearing often call for service personnel engineer yy y memory address before restart Write down the address and inform the service personnel engineer FAULT Several faults on COM loop Two breaks cut offs or two short circuits or one break one short circuit on the loop First correct the presented fault and the next fault will be presented PAURI Short circuit internal OM kaos Short circuit on the connection ribbon cable to or between the expansion boards 458x in the c i e EBL128 BAUM Short circuit SCL ni lt gt SCN 48 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x SCI n lt gt SCI n describes between which Short Circuit Isolators SCI s the short circuit is located n A B 0 1 2 3 4 5 6
63. he list e g to acknowledge more faults or press Return to menu H6 Scroll or press Return to log off 72 When the list is empty i e when all faults are acknowledged and corrected you will automatically return to menu H6 98 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 28 Perform ZONE TEST test mode H7 Normally zones are tested during the monthly test via menu H1 see page 63 Via menu H7 it is possible to perform the zone test solely In test mode only the alarm points are tested i e no outputs no sounders will be activated during the test Alarm devices can be tested via menu H8 S3 If a real fire alarm is activated by an alarm point not in test mode the normal fire alarm functions will be activated i e fire alarm presentation outputs sounders activated routing equipment fire brigade tx activated etc but the zone s in test mode will remain in test_mode until the test mode is ended During the fire alarm the zone s in test mode can be displayed via menu X3 see chapter Display disablements X3 page 32 See also chapter The display in EBL128 page 17 There will be an automatic ending of the test mode one hour after the latest tested alarm point zone NOTE If the door in EBL128 is left open the output s for routing equipment fire brigade tx might be disabled if set so in Win128 Ac
64. igh max 2 55 The detector is mounted in an unstable environment See also Planning Instructions chapter Performance factor Table showing the algorithms and the shortenings respectively Algorithm Short name nnnnnn Normal sensitivity amp Normal detection 15 s N 15 High sensitivity amp Normal detection 15 s H 15 Low sensitivity amp Normal detection 15 s L 15 Normal sensitivity amp Slow detection 35 s N 35 High sensitivity amp Slow detection 35 s H 35 Low sensitivity amp Slow detection 35 s L 35 Heat algorithm Class A1 Al Heat algorithm Class A2 S A2 Heat algorithm Class B S B Decision algorithm Dec Default is N 15 and A1 respectively 61 If some other short name is wanted it can be changed in Win128 Up to six characters can be used In the DBI Danish convention up to five characters Low sensitivity and or slow detection 35 s might not fulfil the EN54 7 specifications amp Analog multi detector 4300 only 81 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 25 3 1 Reset of a week average sensor value If a sensor analog smoke detector is replaced without having generated SERVICE signal its week average sensor value has to be set to the default value If not the new clean sensor will inherit the old sensor s week average sensor value
65. in alarm status at the same time normal fire alarms will be activated in EBL128 See also EBL128 Planning Instructions See EBL128 Planning Instructions 35 General heavy smoke heat alarm and individual alarm points zones 3 The alarms will be printed like they are presented in the display i e as ZONE ADDR or ZONE 35 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x eee Heavy smoke ZONE ADDR 12 45 Time HH MM Date MM DD Alarm text for 12 45 or xxx Heavy smoke ZONE 14 Time HH MM Date MM DD Alarm text for zone 12 Se Heavy Neal Ane ZONE ADDR 12 45 Time HH MM Date MM DD Alarm text for 12 45 or A ea yea er ZONE 14 Time HH MM Date MM DD Alarm text for zone 14 Heavy smoke heat alarm will be reset when the fire alarm respectively is reset see chapter Alarm reset page 38 36 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 14 4 14 4 1 14 4 2 14 4 2 1 14 4 3 Rev 2 EBL128 Operating Instructions V1 0 x Key cabinet alarm One programmable input can be used to connect a key cabinet The fire brigade uses a key cabinet to store a key to the building NOTE In the Danish DBI convention the key cabinet alarm function is a little different see below Key cabinet opened before a fire alarm If the key cabinet is opened bef
66. ions V1 0 x personnel can use P8 without any access code to get access to the menu X1 X9 i e to scroll through all the fire alarms see all point alarms etc 7 3 Access level 2B When the door has been opened the fire brigade key switch has been activated LED Door open is lit the building occupier has access like in access level 2A and after access code for level 2B or 3A the following menus H1 Perform monthly test H2 Disable or re enable B1 Disable zone B2 Disable zone address B3 Disable output B4 Disable all control ventilation exting or alarm devices outputs B5 Re enable zone B6 Re enable zone address B7 Re enable output B8 Re enable all control ventil exting or alarm devices outputs B9 Disable Re enable outputs for routing equipment B10 De activate alert annunciation function H3 Set calendar and clock H4 Present system status on display U1 Disablement U2 Disablement by time channel U3 Show values U4 Sensors activating SERVICE signal U J5 Show event log U6 Show configuration H6 Acknowledge FAULTS H7 Perform ZONE TEST Test mode H9 Interlocking outputs and inputs C1 Activated interlocking outputs inputs C2 Activate interlocking output C3 Reset interlocking output 19 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x C4 Disable interlocking output C5 Re enable interlocking output H10 Ch
67. ire L1 are blinking 0 4 0 4 sec the buzzer sounds 0 8 5 sec and there is a Co incidence alarm presentation in the display Co incidence alarm detector ZZ AA or Co incidence alarm zone ZZ If there are Co incidence alarms generated in other zones the LEDs Alarms queued L2 are blinking and the Co incidence alarms will be automatically scrolled each 5 second Co incidence alarm is automatically reset i e when the alarm point zone is no longer in alarm status see chapter Alarm reset page 38 Heavy smoke alarm Heavy heat alarm An analog detector generates heavy smoke heat alarm for a higher alarm level than the fire alarm level i e fire alarm is already activated by the same detector Heavy smoke heat alarm is a confirmation on that the smoke or heat is increasing and can be used for special actions e g activation of smoke ventilation etc In case of a heavy smoke heat alarm the following will happen e Outputs programmed for heavy smoke heat alarm are activated e Ifan ext FBP with a built in printer 1826 is connected the printer will print each heavy smoke heat alarm e g 32 Tf two or more two unit dependent alarm points zone addresses in the same zone are in alarm status at the same time normal fire alarms will be activated in EBL128 See also EBL128 Planning Instructions 33 Tf two or more two zone dependent zones in the same group are
68. ivated during the test Alarm devices can be tested via menu H8 S3 If a real fire alarm is activated by an alarm point not in test mode the normal fire alarm functions will be activated i e fire alarm presentation outputs sounders activated routing equipment fire brigade tx activated etc but the zone s in test mode will remain in test mode until the test mode is ended During the fire alarm the zone s in test mode can be displayed via menu X3 see chapter Display disablements X3 page 32 See also chapter The display in EBL128 page 17 NOTE If the EBL128 door is left open the output s for routing equipment fire brigade tx might be disabled if set so in Win128 There will be an automatic ending of the test mode one hour after the latest tested alarm point zone See also chapter Perform ZONE TEST test mode H7 page 99 Text in display Comments According to chapter Access Access see page 62 The buzzer in EBL128 sounds and all dots in the display are shown for 3 seconds NOTE In Danish DBI convention only one zone Press A to start the test mode Write zone numbers e g 01 02 03 04 The zone s will stay in test mode until the test mode is ended but after 60 minutes or if you press LED Test mode L9 will light up Perform the tests 63 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operatin
69. knowledged faults e Corrected serviced but not acknowledged faults If a fault can not be corrected it is important to contact service personnel engineer immediately NOTE As a warning faults and disablements are also indicated by a 2 sec beep when an open c i e door is being closed 41 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 16 1 Fault messages Below follows a list of all fault messages in alphabetical order FAULT 24 V for external equipment The output is turned off because the current output limit is exceeded FAULT 24 V for routing equipment The output is turned off because the current output limit is exceeded Also indicated by LED L15 blinking FAULT 24 V output techn address xxx This is valid for an external power supply e g 3366 connected on the COM loop The output might be turned off The current output limit is exceeded FAULT AAU x AAU 1735 1736 Alert Annunciation Unit The unit is programmed as another type of unit than the SSD says or fault in the unit PAUL ye akeery e Batteries 2 x 12 V are missing or not correctly connected e Fuse F2 on the main board is blown e Another battery fuse is blown e g if the batteries are placed outside EBL128 FAULT Battery charging The battery charging function is not working all right The main board 4556 may have to be replace
70. lated reset 15 2 3 Alert Annunciation 15 2 4 Co incidence alarm 15 3 Heavy smoke heat alarm reset 15 4 Key cabinet alarm reset 16 Fault 37 38 38 38 38 38 39 39 40 40 41 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 16 1 Fault messages 42 16 2 Fault acknowledge 52 17 Commissioning an EBL128 53 18 SSD programming amp download 54 18 1 SSD programming 54 18 2 Auto generating SSD 54 18 3 SSD download 54 18 4 Download of Alarm texts 55 19 Software S W download 56 19 1 Download of S W in EBL128 c i e 56 19 2 Earlier S W version download 57 19 3 S W download in Display Units 57 20 Restart 58 20 1 Boot menu 60 21 Access 62 22 Perform monthly test H1 63 23 Disable or re enable H2 65 23 1 Disable zone H2 B1 65 23 2 Disable zone address H2 B2 67 23 3 Disable output H2 B3 68 23 4 Disable all control extinguishing ventilation and alarm device outputs H2 B4 69 23 5 Re enable zone H2 B5 70 23 6 Re enable zone address H2 B6 71 23 7 Re enable output H2 B7 72 23 8 Re enable all control extinguishing ventilation or alarm device outputs H2 B8 74 23 9 Disable or re enable outputs for routing equipment H2 B9 75 23 10 De activate alert annunciation function H2 B10 76 24 Set calendar and clock H3 77 25 Present system status on display H4 78 25 1 Disablement H4 U1 78 25 2 Disablement by time channel H4 U2 79 25 3 S
71. logy Europe AB MEW00509 2 2 8 2 2 9 2 2 10 2 3 2 4 2 5 2 6 2 7 2 8 2 9 Rev 2 EBL128 Operating Instructions V 1 0 x Old detector Conventional detector with a closing contact short circuit no alarm resistor or detector with two breaking contacts Conventional zone line Zone line input on an T O unit intended for one or more conventional alarm points End of line dive in the last alarm point Addressable zone interface Unit with a zone line input intended for one or more conventional alarm points End of line device in the last alarm point Output unit Addressable unit with programmable control outputs e g an I O unit To be connected to a COM loop see below Output Control output Defined or programmable function Relay or supervised monitored voltage output in EBL128 or an output unit Short circuit isolator Addressable unit for automatic disconnection of a part of a COM loop see below in case of a short circuit on the loop Display unit Unit for fire alarm presentation incl alarm texts if programmed Connected to an RS485 line COM loop Loop a cable with two wires to which all the addressable MFSTech units can be connected It starts in EBL128 and it returns back to EBL128 Control Unit C U C LE Control Unit C U Control and Indicating Equipment A unit e g EBL128 to which the alarm points are connected Indicates fire alarm fault condition
72. m two unit zone dependence page 35 4 E g a manual call point with a broken glass 39 Panasonic Electric Works Fire amp Security Technology Europe AB Rev 2 EBL128 Operating Instructions V1 0 x MEW00509 15 3 15 4 Heavy smoke heat alarm reset If a heavy smoke heat alarm has been activated it will be reset at the same time as the corresponding fire alarm is reset Also the output s will be reset i e de activated Key cabinet alarm reset Not valid for the Danish DBI convention see chapter Key cabinet alarm Danish DBI convention page 37 After reset of the key cabinet alarm fire alarm a fault message is shown in the display to inform the user that the key cabinet has been opened FAULT Key cabinet Date MMT DD Time HH MM If the key cabinet is closed again the status information Serviced is added FAULT Key cabinet Date MM DD Time HH MM Serviced This key cabinet fault message is to be acknowledged the same way as a normal fault see chapter Fault acknowledge page 52 When the key cabinet fault is acknowledged the LED General fault L7 will be turned OFF if the key cabinet is closed and if there are no other faults in the system 40 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 16 Fault In case of a fault condition the following has happened will happen
73. message The alarm texts will be printed out if an ext FBP 1826 with a printer is connected All alarm texts up to 40 alphanumeric characters each are created and downloaded via Win128 See Planning Instructions chapter Alarm texts See also the Win128 help chapters help topics e g Download and the Display unit menu respectively 2 Also valid for the Ext Presentation unit 1728 and the Alert Annunciation units 1735 1736 55 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 19 Rev 2 EBL128 Operating Instructions V1 0 x Software S W download 19 1 The latest version of the EBL128 software is factory downloaded before the delivery Due to continual development and improvement different S W versions can be found A new S W version can be downloaded via Win128 on site The valid S W version can be read in menu H3 or via Win128 See also the Win128 help chapter help topic Download Software Download of S W in EBL128 c i e To download new software S W a PC and Win128 are used Before download the PC has to be connected to the RS232 connector J3 in EBL128 on the main board 1 Start Win128 Log on to EBL128 In the Tools menu select Download Software to open the dialog box and do the required settings i e mark the checkbox Download software select the path and the S W file e g EBL128_V V bin V V version number e g 1 1 If also a t
74. might cause communication disturbance problems NOTE All values are set to 0 after a restart and when you re connect the COM loop via menu H5 A1 Access According to chapter Access code for service and maintenance see Press gt to go forward Press to go back or press A to menu A8 Scroll or press Return to H5 Scroll or press Return to log off 7l Note The values are not updated continuously i e the shown values were valid when A was pressed in menu A8 To see the new actual values go back to menu A8 and then press A again Normally only the Pollings value should be changed 96 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 26 9 Activate address setting mode for DU H5 A9 This function can be used by commissioning service engineer to activate the address setting mode in the following Display Units connected to the RS485 interface in EBL128 e Ext Presentation unit EPU 1728 e Alert Annunciation unit AAU 1735 1736 e Ext Fire Brigade Panel FBP 1826 1828 A specific unit or all units can be activated for address setting NOTE The units have to be in operation and in quiescent condition i e the units have to have an address set already Access According to chapter Access code for service and maintenance see Scroll to menu A9 Acti A mo Write the unit s address J 9 All units P
75. n a Flash memory and also put the CPU at rest See also chapter Restart page 58 It s recommended to do a safe shut down after commissioning the installation and after calibration of supervised outputs change of access code etc NOTE By restart and power down the Fault tx relay which is powered in quiescent normal state will be powerless i e the relay contacts will alternate Text in display Acknowledge SERVICE signal AC CHE Meso Safe shite down OF CONCLOL UNIE ACCEPT S4 For safe shut down control unit press ACCEPT Control unit ready for power down To restart without power down press ACCEPT Normal restart indication see page 58 FAULT Restart code 0x addr 0 Date mm dd Time hh mm Serviced Comments According to chapter Access code for service and maintenance see page 101 The SSW is now saved the CPU is at rest and the CU is ready to be powered down NOTE If you change your mind regarding power down press A to restart the CU or wait 5 min for an aut restart When the CU is powered up again there will be a restart After the restart power up there will be a fault which has to be acknowledged see chapter Acknowledge FAULTS H6 page 98 Restart code 03 power up code 00 All LEDs incl Operation L6 will be turned off as well as the com munication on the COM loop RS232 485 serial lines and the input IO 105 Panasonic
76. n the EBL128 A direction and B direction respectively i e if no SCI 4370 is used the information will always be SCIA lt gt SCI B If one SCI 4370 no 0 is used the information will be SCIA lt gt SCI 0 or SCI O lt gt SCI B and so on If it is a single break cut off on the loop there will be no other fault messages If there are several breaks on the loop the message shows the last isolator before the break in the A direction incl the following isolator There will also be a FAULT No reply message for each unit that EBL128 can not find and FAULT Several faults NOTE Each 10 minute a new attempt is made to communicate in the A direction only When the breaks are repaired corrected the communication 43 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x automatically returns to communicate in the A direction only FAULT Earth fault minus EAU I Earth caulet pihus Earth fault is detected The system voltage is normally 24 V DC 24 V to earth is normally 12 5 V 0 V to earth is normally 11 5 V Voltage to earth lt 3 4 V Earth fault minus Voltage to earth gt 18 3 V Earth fault plus Check all cables for damage etc The function can not be guaranteed Call for service personnel engineer FAULT Earth fault techn address xxx This is valid for an external power su
77. nic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 29 3 Clear weekly average H8 S2 If a sensor analog smoke detector is replaced without having generated SERVICE signal its week average sensor value has to be cleared and set to a default value If not the new clean sensor will inherit the old sensor s value The week average sensor value has to be cleared for each replaced sensor individually First replace the sensor then clear the week average sensor value as soon as possible The very first week average sensor value after clearing will be calculated within one hour Thereafter a new average sensor value will be calculated each week NOTE Authorised service personnel only must use this menu Used incorrectly it can cause nuisance fire alarms from a sensor or no fire alarm at all Text in display Comments Access According to chapter Access code for service and maintenance see page 101 Scroll to menu S2 A y Write the wanted zone address and or press A to accept A l Scroll or press Return to return to menu H8 Scroll or press Return to log off 103 Panasonic Electric Works Fire amp Security Technology Europe AB Rev 2 EBL128 Operating Instructions V1 0 x MEW00509 29 4 Access oe to menu S3 E g n wA Test alarm devices H8 S3 The programmable outputs of type Alarm device can be collectively activ
78. nic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 35 Revision history Revision 1 Information added revised in the following chapters paragraphs 14 2 14 2 1 3 16 1 17 22 26 2 26 5 and 28 Revision 2 Information added revised in the following chapters paragraphs 7 2 3 7 4 7 5 7 6 21 26 26 1 29 1 and 29 8 120 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 121 This page has deliberately been left blank Panasonic i Panasonic Electric Works Fire amp Security Technology Europe AB Citadellsvagen 23 SE 211 18 Malm Sweden Tel 46 0 40 697 70 00 Fax 46 0 40 697 70 99 info mfstech com www panasonic fire security com ISO 9001 Bek NATIONAL ACCREDITATION OFCERTIACATION BODIES
79. nu H4 US5 e All faults have to be individually acknowledged one by one push button Fault acknowledge P6 Use Tord keys to scroll e Ifa fault has been serviced corrected before it has been acknowledged the text Serviced is added after the time It still has to be acknowledged e When a fault is corrected and acknowledged it will disappear from the list H6 e When all faults have been acknowledged the LED Fault tx activated L11 will be turned off and output for routing equipment Fault tx is reset as in normal operation e As long as there are faults not acknowledged faults and or acknowledged but not corrected faults the LED General fault L7 will be lit and general fault and maybe general charge fault output s are activated 52 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 17 Commissioning an EBL128 Before you connect any power to EBL128 all other cable connections shall be made Check once more that the connections are correct 1 Remove the rectifier power supply fuse F1 and the battery fuse F2 on the main board or the fuse between the batteries Connect the batteries to the main board Connect the rectifier to the mains 230 V AC Put back the rectifier fuse F1 on the main board Put back the battery fuse ON ee ee ie LED Operation L6 indicates that the 24 V DC power sup
80. nu H9 Scroll to menu C3 This is a list in which you can scroll If there are no activated outputs menu C3 will be shown again Press A for reset or Return no reset to menu C3 A gt S erle i Scroll or press Return to or menu H9 Scroll or press Return Return to log off 112 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 30 4 Disable interlocking output H9 C4 Interlocking outputs Type Interlocking will be disabled via this menu but not via menu H2 B3 The Interlocking Combination Area Point is to be entered to disable the output If 00 00 is entered all interlocking outputs will be disabled at the same time All interlocking outputs can be disabled Disabled interlocking outputs are listed in menu H4 U1 The LED Disablements L8 is also indicating one or more disabled interlocking outputs Action Text in display Access According to chapter Access see page 62 Scroll to menu H9 A A Write the area and point AG 3 Press A to accept and or e g 01 OL Return to menu C4 A Scroll or press Return to menu H9 Scroll or press Return to log off 113 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 30 5 Action Access Scroll to menu H9 A Scroll to menu C5 TAS A or Return Rev 2 EBL128 Operating Ins
81. o0o ep j o 0 na N Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 7 3 Access level 2B TA Access level 3A 7 5 Access level 3B 7 6 Access level 4 8 Silence Alarm devices 8 1 Disable Re enable alarm devices 9 Silence buzzer 10 Disable Re enable all control extinguishing and ventilation outputs 11 Evacuate LED Test Alert Annunciation Acknowledge and Disable 11 1 Evacuate 11 2 LED Test 11 3 Alert Annunciation Acknowledge 11 4 Disable 12 Door open 12 1 LED Door open 19 20 20 21 22 22 23 24 25 25 25 25 25 26 26 12 2 Outputs for routing equipment Fire brigade tx and Fault tx 26 12 3 Silence buzzer 13 Technical address Presentation number 13 1 Technical address for COM loop units 13 2 Presentation number 14 Alarm types 14 1 Pre warning 14 2 Fire alarm 14 2 1 Fire alarm menu X1 X9 14 2 2 Alert Annunciation alarm AA alarm 26 27 27 27 28 28 29 31 34 14 2 3 Co incidence alarm two unit zone dependence __ 35 14 3 Heavy smoke alarm Heavy heat alarm 14 4 Key cabinet alarm 14 4 1 Key cabinet opened before a fire alarm 35 37 37 14 4 2 Key cabinet opened in conjunction with a fire alarm _ 37 14 4 3 Key cabinet alarm Danish DBI convention 15 Alarm reset 15 1 Pre warning reset 15 2 Fire alarm reset 15 2 1 Multiple reset 15 2 2 Single encapsu
82. o0r 7 A amp B is the built in isolator in the EBL128 A direction and B direction respectively i e if no SCI 4370 is used the information will always be SCIA lt gt SCI B If one SCI 4370 no 0 is used the information will be SCIA lt gt SCI 0 or SCI O lt gt SCI B and so on There will also be a FAULT No reply message for each unit that EBL128 can not find If there are several short circuits on the loop the message shows the last isolator before the break in the A direction incl the following isolator There will also be shown FAULT Several faults NOTE Each 10 minute a new attempt is made to communicate in the A direction only When the short circuits are repaired corrected the communication automatically returns to communicate in the A direction only FAULT Site specific data SSD The Site Specific Data SSD is not downloaded correctly a checksum fault etc A new SSD download via Win128 is required If the fault can not corrected it is very serious Call for service personnel engineer immediately FAULT Site specific data SSD AAU x AAU 1735 1736 Alert Annunciation Unit There is no SSD Site Specific Data downloaded to the unit or something is wrong in the downloaded SSD FAUNT Site sSpeciinile data SSD IEW xx EPU 1728 Ext Presentation Unit There is no SSD Site Specific Data downloaded to the unit or something is wrong
83. obs cause smoke Carpet welding Welding of plastic carpets causes a smoke that can be almost invisible but it still influences the smoke detectors sensors Cooking fumes toasting amp candles It is not only normal smoke that influences smoke detectors sensors It is all kinds of combustion products caused by cooking frying grilling toasting etc Warning Be careful when there are smoke detectors sensors near such activity Special environments Certain premises and environments can influence smoke detectors sensors and cause alarms It can be ions from plastics flour dust oil haze aerosols strong perfumes strong ventilation insecticides disinfecting sprays etc If many odd and unnecessary alarms occur the environment must be examined and perhaps other detector types have to be chosen Steam hot air Smoke and heat detectors are influenced by steam and hot air e g from an oven dry blower heater etc 118 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x Exhausts Exhausts from cars trucks lift trucks lawn mowers etc influences smoke detectors sensors If windows and doors are open exhausts can slip in that way Lack of maintenance Smoke detectors sensors are influenced by their environment and become dirty In an analog system like EBL128 a Service signal is given when it is time to clean or exchange the
84. ogramming and commissioning is very easy via the PC S W Win128 PC S W Win128 is used for programming and commissioning i e to e create download upload backup the site specific data SSD e download new S W version settings conventions configurations EBL128 data etc e create download the alarm texts shown in the display in EBL128 ext FBP and or AA units Win128 shall have the same version number as the EBL128 S W version number e g 1 0 x Only x may be different Old SSD files can be used with a newer EBL128 S W version Open and save the old SSD file in the new Win128 version before the download If a backup is required use the same Win128 version as the EBL128 version 10 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 4 Control amp Indicating Equipment Depending on country convention configuration etc the look language and functions might vary Figure 1 shows an EBL128 with a Swedish front EBL128 is housed in a grey metal cabinet The door has a Plexiglas ahead of the front see Figure 1 A key is required to open the door to get full access to the push buttons on the front i e the Fire Brigade Panel FBP and the Control Panel CP Silence buzzer FBP Silence l Venti F Ventilation alarm devices 7 Fire brigade tx 7 Operation aa Evacuate CP Figure 2 The EBL128 front The l
85. ol extinguishing and ventilation outputs All control outputs programmed as type 0 control general 1 fire ventilation 2 extinguishing system can via menu H2 B4 be collectively disabled This is indicated by the LED Disablements L8 They will remain disabled until they are re enabled again via menu H2 B8 See also chapter Disable all control extinguishing ventilation and alarm device outputs H2 B4 page 69 24 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 11 11 1 11 2 11 3 11 4 Rev 2 EBL128 Operating Instructions V1 0 x Evacuate LED Test Alert Annunciation Acknowledge and Disable This function is only valid in some conventions m A front with the push button P5 is required Evacuate When the push button Evacuate P5 is pressed all outputs programmed for sounders type 3 alarm devices will be collectively turned ON steady continuous This is indicated by the following information in the EBL128 display Evacuate in progress The sounders will remain ON until they are turned OFF by pressing the push button Evacuate P5 again NOTE The alarm devices sounders will in this case be activated steady continuous irrespective of the fact that the outputs can be set to something else for fire alarm e g intermittent LED Test When the push button LED Test P5 is pressed all LEDs on the front the LCD back li
86. oll or press Return to log off Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 30 2 Activate interlocking output H9 C2 The output in each interlocking combination area point can be manually activated via this menu The corresponding interlocking input will be monitored in the same way as if the output was activated by its control expression Reset has to be performed via menu H9 C3 Access According to chapter Access see page 62 Scroll to menu H9 Scroll to menu C2 Write the area and point gt 1 Press A to accept and or e g 01 OL Return to menu C2 Scroll or press Return to menu H9 Scroll or press Return to log off 111 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 30 3 Reset interlocking output H9 C3 All activated interlocking outputs are listed in this menu Interlocking output activated via its control expression and with latching output selected in Win128 The output has to be reset via this sub menu C3 Interlocking output activated via its control expression and with latching output not selected The output can be reset via this sub menu C3 Interlocking output activated via menu H9 C2 The output has to be reset via this sub menu C3 Access According to chapter Access see page 62 Scroll to me
87. ook might vary depending on _ the country language configuration etc shown here is a front with English texts See also chapter LED indicators and push 11 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x The fire brigade personnel can use the FBP to see which alarm point zone having activated the fire alarm s In the display LCD 2x40 alphanumeric characters the information displayed on the first row is depending on how many alarm points zones having activated fire alarm and also convention On the second row is for the activated alarm point zone an alarm text shown if programmed See chapter Fire alarm page 29 Required fire brigade personnel manoeuvres are performed via the FBP in EBL128 or via external FBPs 1826 1828 The CP is used to communicate with EBL128 e g for commissioning monthly tests and maintenance Access codes for different access levels are required A keypad is used to get access to the menu tree i e the main and sub menus for the different manoeuvres etc The CP holds several system status LEDs 12 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 5 LED indicators and push buttons LEDs and push buttons can vary according to configuration convention country language See also Figure 2 page 11 LED indicators on the Fire B
88. or will show 100 Close the dialog box Regarding the restart see also chapter Restart page 58 6 LED Operation L6 will be turned on and LED General fault L7 and LEDs Alarms queued L2 will be turned off 19 2 Earlier S W version download For some reason it might by required to download an earlier S W version The procedure is the same as for a new S W 19 3 S W download in Display Units New S W for the 1728 1735 1736 amp 1826 1828 units can also be downloaded via Win128 The PC has to be connected to the RS232 connector J2 in the unit respectively See the Win128 help chapter help topic Display unit menu and the Technical Description for the unit respectively 57 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 20 Restart A restart will delete or not delete the data in EBL128 Here follows an explanation of the different data abbreviations and a table showing how the data respectively is affected cold or warm restart FF Fire alarms and Faults D Disablements FFD Fire alarms Faults and Disablements SSW Sensor values access codes supervised output calibration values log buffers and in some conventions the alarm counter SSD Site Specific Data i e all the installation programming created and downloaded via Win128 S W Software i e the EBL128 system program WASV Week Average Sensor Values
89. ore a fire alarm e g if somebody illegally breaks into the key cabinet a key cabinet alarm i e a fire alarm will be generated Example Key cabinet alarm ZONE KE Nov Call Alarm from key cabinet It will be printed like a normal fire alarm if an ext FBP with printer is available see chapter Fire alarm page 29 Key cabinet alarm is reset like a normal fire alarm see chapter Fire alarm reset page 38 This alarm will also generate a fault message see chapter Key cabinet alarm reset page 40 It is indicated by LED Fault L8 NOTE The Fault tx output will not be activated by this fault Key cabinet opened in conjunction with a fire alarm The fire brigade personnel can open the key cabinet if a fire alarm already is activated in EBL128 In this case there will be no key cabinet alarm or fault generated when the key cabinet is opened Restoring the key after a fire alarm When all fire alarms are reset see chapter Alarm reset page 38 the key has to be restored in the key cabinet within 5 minutes If not a fault will be generated see chapter Key cabinet alarm reset page 40 Key cabinet alarm Danish DBI convention NOTE Only valid for the Danish DBI convention When the key cabinet is opened the Fault tx output will be activated and a key cabinet fault will be generated FAULT Key cabinet Date MM DD Time HH MM In Danish FEJL N gleskab When this fault is
90. orks Fire amp Security Technology Europe AB Rev 2 EBL128 Operating Instructions V1 0 x MEW00509 18 4 Download in progress When the download is completed in a correct way the following text message will be shown Download completed successfully Control unit will now restart Now an automatic warm restart will take place see chapter Restart page 58 If the download was not completed or incorrect the following text message will be shown Checksum fault in downloaded data Conte colunn E wall Mow Festart Now an automatic warm restart will take place see chapter Restart page 58 After the restart another text message will be shown in the display FAULT Site specific data SSD Date MIME DID Time HH MM This text message means that the SSD have not been downloaded correctly i e try to download the SSD once more Download of Alarm texts When a fire alarm is activated i e an addressable alarm point the presentation number Zone Address is shown on the first row in the EBL128 display and in any ext FBP display On the second row is a user definable alarm text shown if programmed See also chapter Fire alarm page 29 Each alarm point can have a unique text message When several alarms are activated in one or more zones and only the zone numbers are shown each zone can have a unique text message Each zone line input can have a unique text
91. pe 4301 This is a list in which Access see page 62 Press A to accept Write the presentation number and or press A to accept you can scroll or use gt to see the next Depending on information window for the type the gt the selected sensor following will Press Return back to be shown nn Start Sensor examples Scroll or write a new A Type 3308 3309 presentation number or press Return to menu U3 NOTE XX X m XX X obscuration per meter 9 A Perf Factor see below A Type 4300 A IP this table nnnnnn algorithm short name see separate table page 81 80 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x gt Sensor 01 03 technical address 003 Momentary XX C Min SOKO Max XX C gt Sensor 01 03 Current algorithm nnnnnn Return Start Sensor 00 00 Write the presentation number and or press A to accept or press Return to menu U3 Return Sensor values Scroll or press Return to menu H4 Scroll or press Return to log off When scrolling the message Please Wait might be shown for a second and No more sensors found in the system before lowest and after highest possible number respectively Perf Factor Performance factor Low min 0 The detector is mounted in a stable environment H
92. ply rectifier and or battery is okay 7 An automatic restart will now take place see chapter Restart page 58 8 The site specific data SSD is now to be downloaded see chapter SSD programming amp download page 54 See also chapter Calibration of supervised outputs H5 A3 page 90 45 Tf a lot of units especially units with high internal capacitance are connected to EBL128 the total momentary inrush current consumption for these units might be too high for the power supply s electronic short circuit protection and EBL128 will not start working properly In such a case put back the battery fuse before the rectifier fuse i e the batteries have to be reasonably charged or temporarily disconnect some of the units in order to reduce the current consumption while EBL128 is powered 53 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 18 Rev 2 EBL128 Operating Instructions V1 0 x SSD programming amp download 18 1 18 2 18 3 The Site Specific Data SSD for an installation is created programmed via the PC program Win128 which also is used to download the SSD into the EBL128 c 1 e and or 1728 1735 1736 amp 1826 1828 units The SSD will be saved in a file named Xxxxx Win128 SSD programming The SSD programming can be made in your office and afterwards be downloaded to EBL128 on site Auto generating SSD If you are on site the Auto generate func
93. pply e g 3366 connected on the COM loop Check all cables connected to the unit FAULT EPU x EPU 1728 Ext Presentation Unit The unit is programmed as another type of unit than the SSD says or a faulty unit FAULT Expansion board x Valid for the 8 zones exp board 4580 and the 8 relays exp board 4581 mounted in the c i e EBL128 Internal fault on the board and it has probably to be replaced FAULT External fuses The fault is to be found in the external power supply blown fuses etc A fault output is connected to a programmable input in the EBL128 system Check the input as well FAULT External power supply The fault is to be found in the external power supply A fault output is connected to a programmable input in the EBL128 system Check the 4l The fault has to be acknowledged and it can last up to 10 minutes before the communication returns to communicate in the A direction only 44 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x input as well FAULT Factory settings The fault has to do with the battery charging accuracy The main board has to be replaced relatively soon in order to keep the batteries fully charged BAU EBE X FBP 1826 1828 Ext Fire Brigade Panel The ext FBP is programmed as another type of unit than the SSD says or a faulty unit FAULT Fuse on COM loop
94. quired If logon to level 2B was made with level 3A code no code is required here Access According to chapter Access page 62 ee SS If logon was made with code for level 3A no code is needed Enter code for level The digits are replaced 3A four digits in the display Wrong access code was entered Try again Correct access code was entered Sub menu H5 A1 is shown Press A to accept scroll or press Return to menu H5 87 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x Disconnect Re connect COM loop H5 A1 To avoid damage on the units and EBL128 during physical connection disconnection of loop units it is highly recommended to have the loop disconnected disabled i e the loop is voltage free dead Disconnected disabled loop is indicated by LED Disablements and is listed in menu H4 U1 NOTE When you disconnect and re connect the COM loop all the statistics shown in menu H5 A8 will be erased and set to 0 Access According to chapter Access code for service and maintenance see E g 0 A gcn ME M LOG Scroll or press Return to H5 Scroll or press Return to log off 88 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO00509 Rev 2 EBL128 Operating Instructions V1 0 x 26 2 Disconnect Re connect zone line H5 A2 To avoid damage on the units and EBL128
95. r then acknowledge the service signal as soon as possible The very first week average sensor value after the SERVICE signal is acknowledged will be calculated within one hour Thereafter a new week average sensor value will be calculated each week NOTE If a sensor is replaced without activating service signal it has to be reset to the default sensor value via menu H8 S2 see chapter Clear weekly average H8 S2 page 103 Text in display Comments Access According to chapter Access code for service and maintenance see page 101 Acknowledge SERVICE signal ACCHE Me Si Sensor xx xx technical address xxx If there are no sensors to needs service acknowledge menu S1 will be shown again L a list in which you can scroll If it is the correct sensor to acknowledge press Fault acknowledge If not scroll or write the wanted sensor and press Fault acknowledge or press Return to S1 Fault acknowledge The service signal for that sensor is now acknowledged and_ If more service signal the next sensor will be shown in the display acknowledgements shall be done continue like Sensor yy yy technical address yyy above If not press needs service Return to menu S1 Return Acknowledge SERVICE signal Scroll or press Return to ACCEPT S1 menu H8 Scroll or press Return to log off LED Service L12 will be turned off when all sensors have been acknowledged 102 Panaso
96. reset one by one Press Reset P3 to reset the fire alarm shown in the display on the first row to the left NOTE The push button has to be pressed in for min 0 5 sec Output s programmed for this fire alarm will also be reset i e de activated If more than one fire alarm is activated i e if LED s Alarms queued L2 are lit the next fire alarm in the queue is now shown in the display on the first row to the left It has to be reset the same way as the first one 38 Tf there is a fault condition e g caused by the fire a fault message will now be shown in the display When Single encapsulated reset is used you can make a Multiple reset by pressing Reset P4 and 0 1 sec later also press A in the keypad and hold them pressed for gt 0 5 sec 38 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 15 2 3 15 2 4 Rev 2 EBL128 Operating Instructions V1 0 x When all fire alarms are reset LED s Fire L1 and Alarms queued L2 are turned OFF and the display is empty All outputs for fire alarm are now also reset i e de activated If a key cabinet is installed the key to the building has to be put back into the key cabinet within 5 minutes If not a fault will be generated and a fault message will be shown in the display see chapter Key cabinet alarm reset page 40 Encapsulation function Normally if an alarm point or zone is reset while still in
97. ress A to accept A Acti i f Scroll or press Return to CCEP1 H5 Scroll or press Return to log off The address has thereafter to be edited in the unit respectively 97 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 27 Acknowledge FAULTS H6 Regarding fault indication etc see chapter Fault page 41 All faults are latched i e all faults have to be acknowledged See also chapter Fault acknowledge page 52 All fault events are stored in the event log and can be listed See also chapter Event log H4 U5 page 84 In this menu H6 are up to 100 faults listed e Not corrected and not acknowledged faults e Not corrected but acknowledged faults e Corrected serviced but not acknowledged faults i Scroll to menu H6 Acknowledge FAULTS ACCEPT H6 A FAULT Xxxxxxxx Date MM DD Time HH MM See comments Fault acknowledge FAULT Xxxxxxxx Date MM DD Time HH MM Acknowledged Return Acknowledge FAULTS ACCEPT H6 Comments According to chapter Access see page 62 This is a list in which you can scroll The first fault in the list is the most recent fault If a fault is corrected the text Serviced is shown To acknowledge the fault shown in the display press Fault acknowledge P6 The fault is now Acknowledged When the fault is corrected it will be removed from the list Scroll in t
98. rigade Panel FBP LED indicator Indicating Fire 5 red Fire alarm also pre warning heavy smoke heat alarm key cabinet alarm amp co incidence alarm Alarms queued 2 red More than one unit zone have generated fire alarm Extinguishing red Output s for extinguishing equipment activated Ventilation yellow Output s for fire smoke ventilation equipment activated corresponding programmable output s i e type 4 routing equipment activated Test of routing equipment in progress see menu H1 Operation green Power on i e the power supply rectifier and or battery are connected and working properly Fire brigade tx red Output for fire brigade tx routing equipment and or FBP push buttons on next page Co incidence alarm two unit dependent alarm L5 can be programmed to indicate when its normal trigger condition is met or when a programmable input is activated e g L5 can be turned on when an input is activated by a Fire brigade tx output 13 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x Push buttons on the Fire Brigade Panel FBP Push button Operation function Alarms queued black Used when LEDs Alarms queued L2 are lit to scroll browse through the queued alarms zones Silence buzzer Used to silence the buzzer in EBL128 yellow Silence Alarm devices Used to silence the sounders i e to res
99. routing disabled by open door in CU Silence buzzer In Win128 the following can be programmed O Silence buzzer by door switch The buzzer will be turned off as long as the EBL128 door is open This function is a violation to the EN54 2 standard 2 In the ext FBP 1828 when the key is turned to the position open access 26 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 13 Rev 2 EBL128 Operating Instructions V1 0 x Technical address Presentation number 13 1 13 2 Technical address for COM loop units The technical address in EBL128 is used when programming via Win128 all units connected to the COM loop The technical address is also used to identify which unit has generated a fault The technical address is equal to the address that is set in each unit connected to the COM loop Regarding the Address setting tool 3314 Addresses 001 127 can be set not 000 Presentation number For each fire alarm point zone line input a presentation number NN NN has to be programmed The presentation number is shown in the display in EBL128 and in Ext FBP 1826 1828 Alert Annunciation unit 1735 1736 and Ext Presentation unit 1728 to identify the point zone generating a fire alarm It is also used to disable re enable fire alarm points zones and in control conditions expressions to activate the programmable outputs Together with the presentation n
100. s Anybody Fire alarm handling Installation handling daily duties e g monthly tests disablements etc Fire brigade personnel Building occupier Service maintenance Service maintenance personnel Service maintenance Service maintenance commissioning commissioning the system engineer etc via Win128 Service maintenance Service maintenance commissioning commissioning the system engineer etc via Win128 The access codes can be changed To change a code you have to know the valid code or use a code for a higher access level Access level 1 With the door closed anybody has access to the push button Alarms queued P1 to scroll browse through the queued alarms Access level 2A When the door has been opened the fire brigade key switch has been activated LED Door open is lit the fire brigade personnel have access to the push buttons keypad to P2 Silence the buzzer in EBL128 P3 Silence the alarm devices sounders in the system P4 Reset fire alarm s P5 Evacuate start the sounders P7 Paper feed not used in EBL128 P8 Access in conjunction with a fire alarm The fire brigade 17 Only valid in the Belgian convention See chapter LED indicators and push buttons page 13 for explanation of use in other conventions 18 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instruct
101. s ON until turned OFF in this menu A4 E g 1 A Scroll or press Return to H5 Scroll or press Return to log off NOTE Don t forget to turn this mode off after the commissioning 91 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 26 5 Rev 2 EBL128 Operating Instructions V1 0 x Service mode for COM loop H5 A5 This mode can be used when commissioning an installation and by maintenance The COM loop communication polling will be turned off but there will still be voltage 24 V DC on the loop in the A direction only in the B direction only or in both directions at the same time depending on if 1 2 or 3 is selected in this menu A volt meter can be used e g to check the voltage voltage drop on different places on the loop It is recommended to do this check also when EBL128 is power supplied via the backup battery only since the voltage can be up to 3 V lower compared with when it is power supplied via the rectifier i e via 230 V AC due to the battery condition backup duration etc NOTE If short circuit is detected on the loop when in service mode the loop will be disabled and a fault message will be displayed independent of where on the loop the short circuit is situated Access According to chapter Access code for service and maintenance see page 87 to menu A5 E g 1 A Press A to accept Press 0 Service mode is off
102. smoke detectors sensors The alternative is to exchange detectors at even intervals to be on the safe side Change in activities or wrong choice of detector If the activities in the premises are altered the detector choice might also need altering Due to special environments see above an in appropriate detector type might have been chosen from the beginning and thus cause unnecessary alarms Miscellaneous Choosing another type of detector e g a multi detector with both heat and smoke detection can solve certain problems Note that the coverage area can be different for different types of detectors It is however not always the best action to change detector type Here is a list of other actions programmed via Win128 which can be used e Another alarm algorithm can be used e g during working hours e Co incidence two units fire alarm activation can be used e Inan installation with addressable detectors sensors e g EBL128 the affected detectors can be individually disabled or whole zones when the work is in progress Bear in mind that the smoke spreads and consideration must be taken to adjacent detectors zones Disablements can be done automatically via a time channel built in or external or via menu H2 B1 B3 Automatic re enabling can be used e If there is an alarm organisation for the on site personnel the alert annunciation function can be used e Pre warning can be used 119 Panaso
103. ss 3 to erase the texts memory Erasing SSD Erasing SSW and Erasing texts respectively will be shown and then the Erase memory menu will be shown again Press Return to go back to the Boot menu NOTE After erasing the SSW perform a Power down power up restart directly NOTE All other alternatives are strictly forbidden to use These are only for use at trouble shooting controlled by Panasonic personal 61 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 21 Access To use the key pad in EBL128 to get access to the menu tree it is necessary to log on with an access code for level 2B or 3A See also chapter Access levels page 18 Open the EBL128 door level 2A press the Access button P8 and continue as follows Action Text in display Comments Access Access code Enter code for level 2B Access code The digits are replaced or 3A four digits in the display NO ACCESS Wrong access code was entered Try again Perform monthly test Correct access code was ACCEPT H1 entered Menu H1 is shown Press A to accept to perform monthly test or scroll jump to the next menu H2 H10 Explanations Action in the table use push button key e g signed Access Text in display in the table what is shown in the display in EBL128 c 1 e Comments in the table Comments to the
104. ss level 4 Used by Service maintenance commissioning engineers when a PC i e Win128 is to be connected to EBL128 for download of new S W settings configurations C U data on line status checking etc Connect the PC and logon to EBL128 from the PC 21 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 8 Rev 2 EBL128 Operating Instructions V1 0 x Silence Alarm devices 8 1 In EBL128 on the FBP there is a push button P3 Silence Alarm devices If the push button Silence Alarm devices is pressed during a pre warning a fire alarm or a Co incidence alarm the following will happen e LEDs Fire L1 and Alarms queued 6B changes from blinking 0 4 0 4 to steady continuous e Activated outputs programmed for sounders type 3 alarm devices will be silenced In case of a new alarm or if the push button Silence Alarm devices is pressed again the sounders will automatically sound again and the LEDs Fire and Alarms queued starts blinking NOTE This is also valid for Pre warning and Co incidence alarm Disable Re enable alarm devices All outputs programmed for sounders type 3 alarm devices can via menu H2 B4 be collectively disabled This is indicated by LED Disablements L8 and LED Fault Disablements Alarm devices L13 steady continuous NOTE They will remain disabled until they are re enabled again via menu H2 B8 See
105. tage e Rectifier voltage below 21 V DC Fuse F1 on the main board might be blown FAULT Low voltage System voltage lt 21 V DC FAULT Low voltage techn address xxx This is valid for an external power supply e g 3366 connected on the COM loop The power output is turned off because the unit s internal voltage is lt 19 V DC FAULT Mains e Loss of mains i e no 230 V AC the fault is activated after 1 300 minutes e Blown fuse 230 V AC FAULT Mains external power supply Loss of mains i e no 230 V AC to the ext power supply equipment the fault is activated after 1 300 minutes Check 230 V AC fuses A fault output is connected to a programmable input in the EBL128 system Check the input as well 4 The time is programmable in Win128 Max 30 min according to the EN54 2 standard Default value depending convention 46 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x FAULT Mains techn address xxx This is valid for an external power supply e g 3366 connected on the COM loop e Loss of mains i e no 230 V AC in the loop unit the fault is activated after 1 300 minutes e Blown fuse 230 V AC FAULT No reply xx xx gt Press gt to see the technical address PAUL No reply techm address xxx S In spite of communication in both directions COM loop A direction an
106. than the fire alarm level Pre warning can be used when an early alarm and or an early action is required e g a soft computer shut down Normal alarm devices routing equipment etc will not be activated In case of a pre warning the following will happen The buzzer in EBL128 sounds 0 8 sec each 5 sec 0 8 5 sec e LEDs Fire L1 are blinking 0 4 0 4 sec e Outputs programmed for pre warning are activated e On the first row in the EBL128 display the presentation number zone address is shown for the first pre warning e On the second row an alarm text the fire alarm message will be shown if programmed Example pre warning zone 12 address 45 within zone 12 Pre warning detector 12 45 alarm text Example pre warning zone 12 Pre warning zone 12 alarm text 23 This is done via a programmable input 4 This function is normally used only for smoke detectors See EBL128 Planning Instructions Any programmable input can also be used to activate a pre warning 2 Outputs programmed for General pre warning and outputs programmed for the activated pre warning s 28 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x LEDs Alarms queued L2 blinking are indicating more than one pre warning and they will be automatically scrolled each 5 second Pre warning is automatically reset se
107. the Doin NOTE See chapter The display in EBL128 page 17 EAT ns eee regarding priority order When required Press A to end the test Access code mode Scroll to menu H7 wAY The LED Test mode is turned OFF If more zones are to be tested continue as above If not scroll or press Return to log off 100 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 29 Maintenance H8 29 1 Access code for service and maintenance Access code to level 3A is required If log on to level 2B was made with code for level 3A no code is required here Access According to chapter Access page 62 ae A If log on was made with code for level 3A no code is needed Enter code for level The digits are replaced 3A four digits in the display Wrong access code was entered Try again Correct access code was entered Sub menu H8 S1 is shown Press A to accept scroll or press Return to menu H8 101 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 29 2 Acknowledge SERVICE signal H8 S1 See chapter Sensors activating SERVICE signal H4 U4 page 83 When a sensor analog smoke detector that has generated SERVICE signal is acknowledged the sensor will be given a default sensor value as for a new clean sensor i e first replace the senso
108. tion can be used to create the SSD Open a new installation in Win128 connect the PC to the RS232 connector J3 in EBL128 on the main board and log on In Tools menu select Auto generate The COM loop units and the FBP AAU units connected to EBL128 will now be identified and listed in Win128 i e the SSD will be auto generated with default settings for all units Save the installation SSD The SSD can be downloaded see below to EBL128 directly or be edited before the download SSD download The PC with Win128 has to be connected to the RS232 connector J3 in EBL128 on the main board Open the wanted installation xxxxx Win128 and log on to EBL128 In Tools menu select Download SSD to open the dialog box Download SSD To Control Unit Download FBP AAU 7 EPU I Notify when download ready Save 55D to file Progress Mark the required checkbox es Click Start download Information will be shown in the dialog box progress bar and in the display in EBL128 46 xxxxx A suitable name of the installation 47 Access code for level 4 shall be entered via the PC i e via Win1 28 48 Each unit have to be running i e be connected power supplied and the address mode etc have to be set NOTE During this check the COM loop will be disconnected disabled and no alarms or faults can be activated Disconnected COM loop is indicated by the LED Disablements L8 54 Panasonic Electric W
109. tructions V 1 0 x Re enable interlocking output H9 C5 Disabled interlocking outputs are listed in menu H4 U1 Interlocking outputs Type Interlocking will be re enabled via this menu but not via menu H2 B7 If 00 00 is entered all interlocking outputs disabled via 00 00 in menu H9 C4 will be re enabled at the same time According to chapter Text in display Access see page 62 This is a list in which you can scroll If there are no disabled outputs menu C5 will be shown again Press A for re enable or Return not re enable to menu C5 Scroll or press Return to menu H9 Scroll or press Return to log off 114 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 31 Change access code for daily duties H10 For security reasons the default code should be changed Textin display ee Access According to chapter Access see page 62 Scroll to menu H10 e e Enter the old code the e gt The digits are replaced new code and the new Ne oc i in the display code again Wrong access code was entered Try again Correct access code was entered The access code is now changed and the menu H10 is shown Scroll or press Return to log off NOTE After change of access code it is recommended do a Safe shutdown of EBL128 see menu H8 S4 This will save the S
110. umber an alarm text with up to 40 alphanumeric characters can be displayed if programmed via Winl28 NN NN gt 00 99 01 99 The adress within the zone 00 Zone number only will be displayed E g for a one or more conventional detectors connected to a MIO 3361 or an zone line input 4580 gt 01 32 Zone number NOTE Only the zone numbers 01 32 can be used 27 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 Rev 2 EBL128 Operating Instructions V1 0 x 14 Alarm types In case of a fire analog detectors sensors conventional smoke and or heat detectors manual call points and programmable inputs can generate fire alarm If somebody illegally breaks into a key cabinet this will also generate a fire alarm a key cabinet alarm The analog detectors can also generate other type of alarms i e Pre warning Heavy smoke alarm Heavy heat alarm and a two unit zone dependent alarm point zone can generate a Co incidence alarm EBL128 can handle and present up to 128 fire alarms alarm points and or zones Zone numbers 01 32 can be used and in each zone the alarm point address numbers 01 99 can be used The fire alarms will be shown in the EBL128 display and in Ext FBP 1826 1828 Alert Annunciation unit 1735 1736 and Ext Presentation unit 1728 14 1 Pre warning An analog detector will generate a pre warning for a lower alarm level
111. ventilation and alarm device outputs H2 B4 page 69 Disable Re enable alarm devices X9 Press A E g To disable press 0 and A To re enable press 1 and A For more information see chapter Re enable all control extinguishing ventilation or alarm device outputs H2 B8 page 74 Alert Annunciation alarm AA alarm Indications actions etc as for a normal fire alarm except that EBL128 output for routing equipment Fire brigade tx will not be activated directly An AA alarm is indicated by the LED Fire brigade tx delay L16 The AA alarm has to be acknowledged within an acknowledge time and reset within and an investigation time otherwise will the output for routing equipment Fire brigade tx be activated See EBL128 Planning Instructions for more information regarding the AA function Acknowledgement and reset of the AA 31 Tn Polish CNBOP convention the push button Evacuate P5 can be used for AA Acknowledge 34 Panasonic Electric Works Fire amp Security Technology Europe AB MEW00509 14 2 3 14 3 Rev 2 EBL128 Operating Instructions V1 0 x alarm can be done on an AA unit 1735 1736 or an AA controller 1740 See also chapter Alarm reset page 38 Co incidence alarm two unit zone dependence When only one two unit dependent alarm point i e one zone address is in alarm status or when only one two zone dependent zone is in alarm status the LEDs F