Installation and user guide Inverter - X-Sol Danmark X
Contents
1. Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 1 7 nstallation f N 5 Connect the AC voltage connection cable to the inverter e 8 88 GND Protective ground conductor N Neutral conductor L Feed in phase GNDN L Terminal Assignment 6 Tighten the terminals with a tightening N torque of 1 5 Nm 3 4 4 Configuration of the grounding of the PV modules The inverter meets all requirements in terms of technical safety Depending on the grounding of the connected PV modules the following work may need to be carried out on the inverter Grounding of the Inverter setup PV modules Not grounded Factory setup No further grounding measures required Negative grounding Install grounding strap Connect grounding jumper Positive grounding Install grounding strap Connect grounding jumper Swap internal cables Install grounding strap WARNING Risk of electric shock and damage to the inverter gt Only install the grounding strap on grounded PV modules The grounding strap is included in the enclosed grounding kit 1 8 Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 4 gt 17 a I ZU oS s 2 m m ore 2 NEG
2. 6 4 1 Setup gt General Setup This menu shows some of the general parameters of the inverter These parameters can be changed with the owner password Parameters Meaning Language The preferred language is defined during installation Date and time The date and time are set during the installation Password Owner password factory setting 0003 CO rate Avoided CO emissions based on 0 7 kg kWh Yield rate Feed in rebate in the relevant country Yield currency Currency in the relevant country 3 characters Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 43 Menu on the inverter 6 4 2 Setup gt Network Setup This menu shows the settings for the connected Ethernet network see also section Connection between inverter and computer on page 58 These parameters can be changed with the owner password Parameters IP address Subnet mask Gateway Master setting 6 4 3 Setup gt Inverter Setup Meaning Unique network address for the inverter Sub network address first part of the IP address Network transmission to a different network If multiple inverters are connected to each other one of the inverters must be configured as the master and all the others as slaves This menu shows the basic data of the inverter These data are set at the factory and cannot be changed il You will need to have these data available for service situations Parameters M
3. Back Next INSTALLATION MENU a CAUTION No inverter operation or malfunction of the inverter gt Make sure that the selected country is actually correct for the installation site Otherwise it may be impossible to operate the inverter or its operation may contravene local and national regulations because incorrect threshold values are used a N e g relating to power derating Input the settings in accordance with the requirements of the grid operator The country setting can only be changed for a period of 5 hours after initial operation and feed in starts After this the menu is no longer accessible for the owner il Depending on the selected country there may also be further queries Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 29 Placing into operation 4 3 8 Screen lock If no user operation is performed on the inverter the background illumination is auto matically switched off after the set waiting time Factory setting 60 seconds Possible settings 0 30 99 seconds If the setting 0 is selected the background illumination remains activated at all times The value currently set for the display timeout is displayed 1 Press OK to call up the menu 2 Use the arrow keys V A to choose the required timeout duration 3 Press OK to confirm the revised setup 4 Use the D key to select Next 5 Pres
4. If the inverter that has been replaced is a master and master functionality is required on this inverter e g connection to the internet via this inverter proceed as follows 1 Temporarily reconfigure one of the existing inverters as the master inverter 2 Take the new inverter into operation in the network as a Slave In the process the settings are copied from the temporary master 3 Configure the new inverter as the master The temporary master then reverts to slave status The new master has the same settings as the old one 32 Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Operation of the inverter 5 Operation of the inverter In normal operation the inverters operate fully automatically so no manual interventions are required for the feed in into the grid 5 1 Control elements and displays gt 1 Operation display see following pages Normal Running 35456789123 a la 2 LEDs ou z Ao bo 3 Navigation keys OD see Page 23 a To Menu Mon 16 01 2012 09 43 eV 3 z Meaning of the LEDs Symbol Colour Meaning Action N Red Fault gt Check alarms Inverter is in shutdown mode AN Yellow Caution gt Check warning and Inverter is still running but only messages Green with limited functions amp Green Normal operation Inverter is feeding electricity into the grid
5. IP addresses The IP addresses of the computer and inverter must be in the same area i e the first eight digits of the IP addresses must be identical If necessary one of the IP addresses has to be changed see below Example IP address of the inverter 192 168 10 x IP address of the computer 192 168 10 y Here x and y must be different numbers between 1 and 254 The default IP address set for the inverter is 192 168 10 20 Changing the IP address of the inverter gt Enter the desired IP address under Setup gt Network Setup Changing the IP address of the computer gt Enter the following addresses in the network menu of the system controller IP address 192 168 10 10 Subnet mask 255 255 255 0 58 Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Web server 71 2 Connection via network internet If multiple inverters are connected via a CAN bus only the master inverter needs an to be connected to the router switch ots La Wi a CAN Ethernet With DHCP Dynamic Host Configuration Protocol With DHCP a router or switch generally distributes the required parameters such as IP address and subnet mask to the devices in the network 1 Connect the master inverter and the router switch to each other using a CAT5 Ethernet cable 2 Under Setup gt Network Setup enter the IP addr
6. jumper If the DC is correctly plugged contact the installation company If the inverter is in shutdown mode switch off the AC side first and then the DC side Wait for 30 seconds and switch the AC side and DC side back on again If the fault persists contact the installation company If the inverter is in shutdown mode switch off the AC side first and then the DC side Wait for 30 seconds and switch the AC side and DC side back on again If the fault persists contact the installation company Check whether the ambient temperature is within the permitted limits Check whether there is adequate ventilation Check whether the correct minimum distances have been maintained as stated in this installation and user guide Make sure that the inverter is protected against direct sunlight Make sure that the ventilation system is clean Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Faults and troubleshooting Code Message Meaning Remedy E13 Low inverter The internal gt The inverter will restart once the temperature temperature of temperature is back within the the inverter is permitted range too low gt lf the fault persists contact the installation company E14 Current power PV power gt Check whether there is adequate limitation exceeds the ventilation nominal power gt Check whether the correct of the inverter minimum distances have been maintained as stated i
7. 99 A Ue v INSTALLATION MENU a 4 3 6 Master Slave When multiple inverters that are networked with each other 1 Use the gt key to select Next 2 Press OK to confirm Next via the CAN network are installed one inverter can be configured as the master and the others as slaves For this to be possible all inverters in the network must be switched on The master inverter automatically transfers the setting values to the other inverters via the CAN network A CAN network can comprise one master and up to 29 slaves il PLATINUM recommends a slave configuration for standalone inverters The current status Master Yes No is displayed 1 Press OK Set as Master unit No 2 Use the arrow Yes No Press OK 3 revised setup 4 Use the D key 5 Press OK Back Next INSTALLATION MENU a 28 Installation and user guide for PLATINU o call up the menu keys V A to select to confirm the to select Next o confirm Next M inverters 2100 H 3000 H 4000 H 4600 H Placing into operation 4 3 7 Country setting Grid code The currently set country is displayed 1 Press OK to call up the menu 2 Use the arrow keys V A to select the required country A 3 Press OK to confirm the y Grid code Germany 126 revised setup 4 Use the D key to select Next 5 Press OK to confirm Next
8. II AC side III Yes DC side insulation test AC side AFI 1 7 Ill Full graphic LCD 170 x 76 pixels Storage capacity sufficient for operating time of 20 years Integrated web server HF transformer with electric isolation Convection cooling Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 87 Taking out of operation 11 Taking out of operation N DANGER Risk of death due to high DC and AC voltages gt Wear insulating protective clothing and face protection gt Inverters are only to be uninstalled by trained specialist personnel The trained specialist personnel must be granted permission by the energy provider responsible gt Switch off mains voltage supply safety device gt Set the switch knob of the DC isolator to 0 gt Wait at least 60 minutes until the capacitors are discharged gt Make sure that no voltage is applied to the DC cables WARNING Injury may result if the inverter falls gt Get a second person to help with assembly and disassembly gt Wear safety shoes during assembly and disassembly gt Ensure that the inverter is positioned securely The procedure for taking inverters out of operation is the reverse of that for installation and assembly 88 Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Disposal 12 Disposal Packaging and replaced parts are to be disposed of in ac
9. Inverter System Energy Log Data Log Total Number of Inverters User name password sender e mail address recipient e mail 1 recipient e mail 2 SMTP server Time of notification time interval sending etc FTP server ID user name password SMTP port 2 Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 39 enu on the inverter Menu settings can also be input via the web server see chapter 7 6 3 Status menu Inverter Status Plant Status STATUS 6 3 1 Status gt Active Alarms This menu shows detailed information about warnings and alarms that are displayed at the top left in the status bar during operation The alarm messages are listed in section Event Log on page 75 40 Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Menu on the inverter 6 3 2 Status gt Inverter Status This menu shows the operating mode operating parameters and any faults that are present on the inverter Parameters Meaning Input parameters a Values from the PV modules to the inverter current voltage and power Output parameters Feed in values from the inverter to the grid current voltage and power Inverter peak power value Highest power value attained on this day Energy today Total energy yield during the course of the day Temperature Temperature inside the inverter Insulation resistance Safe insulation value for the
10. a Connect grounding jumper Installation gt Connect the grounding strap between the DC grounding terminal 17 and NS WARNING Risk of electric shock and damage to the inverter gt Only install the grounding jumper on grounded PV modules The grounding jumper is included in the enclosed grounding kit a S 18 Z ia Dane GNDIPE ON oY p Eitem 2a O Oj O O Oj O O gt Plug in the grounding jumper at the connector 18 according to the grounding of the PV modules Not grounded No jumper Positive grounding Pin 1 and pin 2 Negative grounding Pin 2 and pin 3 Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 19 Installation Swap over the internal cables if the PV modules are positively grounded WARNING Risk of electric shock and damage to the inverter gt Only swap over the internal cables if the PV modules are positively grounded At the factory black cables are assigned to the connections N1 to N4 and red cables to the connections P1 to P4 In the case of negatively
11. d an 2 Use the arrow keys V A and lt gt to A change the password 3 Press OK to confirm the changed Vv password 4 Use the D key to select End Press OK to confirm End o INSTALLATION MENU a Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 31 Placing into operation 4 311 Final checks The installation has been successfully completed if the operation display comes on and only the green LED is lit up Final checks in a network Check the following at every inverter in the network Only the green LED is on All of the inverters in the network have the same country settings including further country specific settings Proceed as follows in the event of faults in the network Perform a network scan to determine how many inverters have been recognised in the network Commands gt Plant Commands gt Reset Number of Inverters Check the CAN connection Check the jumper settings Repeat the installation process if necessary Repeat the network scan after every test step until the number of detected inverters matches the actual number present in the network 4 4 Commissioning after replacement of a device 4 4 1 After replacement of a slave The master inverter automatically detects the replacement and takes the new device into operation as a slave The device number is retained 4 4 2 After replacement of the master
12. 81 Maintenance 79 8 2 Cleaning 79 9 Faults and troubleshooting 80 9 1 Checklist in the event of faults 80 9 2 Event list 80 9 3 Faults and troubleshooting 85 10 Technical data 86 11 Taking out of operation 88 12 Disposal 89 4 Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 1 Introduction 11 PLATINUM H Inverters in the PLATINUM power ranges see Technic Introduction H series are single phase feed in inverters for different al data on page 86 Inverters in the PLATINUM H series are equipped with an integrated web server which allows data to be viewed and evaluated via a network or via the internet Up to 30 PLATINUM H inverters can be connected to form a single inverter system via the CAN network 1 2 About this manual This installation and operating manual describes the installation and operation of the PLATINUM inverters of the types 2100 H 3000 H 4000 H 4600 H Additional documents The following additional doc www platinum nes com uments are available in the download area of our website Detailed installation and user guide Information on fault curre Detailed list of events for Overview of country and Declaration of conformity Manufacturer s warranty 1 3 Symbols used 1 3 1 Notes nt protection devices detecting eliminating faults grid codes and certificates Notes give tips on how to work easily and safely or contain further in
13. H 4600 H 2000W 2 900W 3 800W 4 400W 9 0A 13 0 A 170 A 20 0A 16 0A 16 0A 2 000VA 2 900VA 3 800VA 4 400VA 10 5 A 15 2 A 19 7 A 23 0 A 13 A 20A 25 A 25 A 7W 230 V 20 50 Hz 5 1 feed in phase 1 monitoring phase n a n a 446 mQ 379 MQ lt 1W Yes 0 9 ind 0 9 cap 45 0A 20 A max duration 5 ms 2100 H 3000 H 4000H 4600 H 96 9 97 0 97 2 97 3 96 0 96 2 96 6 96 9 2100 H 3000 H 4000 H 4600 H Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Interfaces DC isolation device DC connection AC connection Network Ambient conditions Operating temperature Max temperature for rated power Storage temperature Rel Humidity Max operating altitude Protection class Level of contamination Inverter data Weight 2100 H 3000 H 4000 H 4600 H Dimensions H x W x D Overvoltage category Reverse voltage protection DC Ground fault monitoring Protection class overvoltage protection Optical display Integrated datalogger Switching concept Cooling concept Technical data H Optional switch integrated in device for isolation from generator field DC connector Multi Contact MC4 Screw type terminals Ethernet CAN H 25 C to 65 C 45 C 30 C to 80 C 4 to 99 2000 m IP66 in accordance with DIN EN 60529 Il external and internal use possible la 19 kg 21 kg 610 x 353 x 154 mm DC side
14. Inverter is switched off Power lt 7 W Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 33 Operation of the inverter 5 2 Operation display 5 2 1 Start screen 1 Status bar 2 Operation display Now 3 Tothe main menu 4 Date and time n SN Now DC AC Voltage V 450 240 Current A 9 1 16 6 Power W 4100 exeyere Mon 16 01 2012 09 43 The start screen is always displayed if no button has been pressed for 1 minute f a screen saver is activated blank screen any button can be pressed to display the start screen 5 2 2 Navigation from the start screen VIA Switch between main display and status bar call menu lt gt Switch between time periods Now Today Month Year and Plant overview 5 2 3 Operation display Now The values for current voltage and DC AC power for the PV plant DC and the Voltage V 450 240 feed in AC are displayed numerically Current A Sh 16 6 The current power is displayed as a bar graph 0 nominal power Now Power W 4100 3990 34 Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Operation of the inverter 5 2 4 Operation display Today The following values are displayed in this screen Today s yield in Wh and as a graphical representation 1 35 EUR u 1 D D Wachee Today s peak power in Wp vee ERD he Feed in rebate generat
15. Plant Last 12 months Setup GS Power Customer data Customer name site etc Plant System data Model serial no etc Information General Date time CO rate earnings rate earnings currency setup Alarm Notification setup Address of sender and recipient setup Inverter alarms Time alarms Network TCP IP Network IP address network subnet mask network gateway User User account account Change password Edit accounts Event log Display Events for the selected day Status Plant Alarms Overview Plant Help Logout p 62 Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Web server 74 Home A e E OO BP Statistics Setup Event log Status Help Logout System Status S Site T 14 16 27 Jul 2012 110371195041 unit PV2 v Normal a KO Running VN ww DA Production Status 340 3 Eai_ Hanuni nn 1696 7 4 1 Menu bar The web server offers the following menus Icon Meaning Icon Meaning A Home screen Status b Nea Statistics Help Setup Logout Event Log gt Click the icon of the required menu in the menu bar The selected menu is opened Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 63 Web server 7 4 2 Selected inverter plant Display In the area on the right the values for the following operating data are displayed for the selected inverter or for the entire plant Input Current v
16. match those on the display If all of these points are OK but still no electricity is being fed in Contact the installation company 9 2 Event list The inverter automatically detects problems in the operating status and displays mes sages in plain text on the screen Detailed information about warnings and alarms can be viewed in the Event Log menu The inverter distinguishes between two types of message W Warning yellow LED is on A Alarm red LED is on If an alarm is present the inverter switches off automatically A warning is displayed if e g the feed in power drops below the threshold of 7 W www platinum nes com When contacting with the PLATINUM service department have the serial number and event code to hand il The complete event list can be downloaded from our website 80 Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Faults and troubleshooting Code Message Meaning Remedy E01 Field fault PV module gt Contact the installation company failure E02 Input protective DC switch open gt Switch on the DC switch switch open gt f already switched on contact the installation company E03 Inverter failure Inverter failure gt Contact the installation company E04 Output protect AC protective gt Switch on the AC protective ive switch open switch open switch gt f already switched on contact he installation company E05 Grid fault No
17. or selected inverter for the last 7 days The web server totals the performance data and displays the following cumulative values Energy generation Energy generated during the selected period Earnings Earnings for the energy generated CO savings CO emissions saved as a result of the energy generated Detailed values are displayed if you hover with the mouse over the graphics 7 5 3 Last 12 months Each of the last 12 months is shown as a bar in the graphic The remaining information corresponds to the information for the Last 7 days Download energy values gt Click gt 4 on the right above the last bar The energy values for the last 12 months are downloaded as an html file 76 Setup The Setup menu contains the following submenus GS Power Plant Information General setup Alarm setup Network User account 7 6 1 Navigation The Setup menu contains the following navigation icons Icon Meaning us Exit menu without saving el Save changes Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 67 Web server 7 6 2 Setup gt GS Power Plant Information 2 Statistics Event log Status Help Logout Plant Information gt General settings coman Aarmsetup 7 onde mm Installation date 17 01 2011 E Network Service by src sencede o TE Unit name unit PVi Message Model THEIA 4 4HE Serial numbe
18. 00 H 4000 H 4600 H Installation 3 3 Assembly 3 3 1 Safety instructions pe WARNING Injury may result if the inverter falls gt Use fixing materials suited to the assembly wall and the weight of the inverter gt Wear safety shoes during assembly and disassembly gt Ensure that the inverter is positioned securely PLATINUM recommends that the inverter should not be installed in living quarters J re N CAUTION Damage to the inverter due to excessive buildup of dust Avoid excessive build up of dust Avoid build up of dust with electrically conductive dust particles In order to comply with the requirements of standard IEC 62109 a possibility must be provided for tool free isolation of the solar generator If the design does not feature an integrated DC isolator an external isolation device is mandatory this must be easily accessible er Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Installation 3 3 2 Mounting the inverter f N 1 Choose a suitable location for mount ing When doing so note the follow ing Mount the inverter in a suspended vibration free position The wall chosen for mounting must 150 150 be suitable for the weight and E temperature 90 C Make sure the correct dimensions and distances are maintained The display should be at eye level approx 1 60 m off the floor The inverte
19. 2 version Version number of the DSP2 software Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 45 Menu on the inverter 6 4 4 Setup gt Plant Setup This menu displays useful information about the PV plant The owner password is required in order to change the information Parameters Company customer name Site site name Installation date Service date Area of responsibility Device name Message Plant apparent power 46 Meaning Name of the operator customer Site description Date of initial operation Date of last service Field for messages from the service personnel The inverter is displayed with this name in the list of inverters linked to the master device Extra field for additional messages The product of voltage times current for the entire PV plant kVA Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Menu on the inverter 6 4 5 Setup gt Grid Configuration This menu shows the settings for the grid based on the selected country This menu has the following submenus Active Power Derating Reactive Power Production Power Balancing Active Power Setting Grid Connect GRID SETUP These parameters can be changed with the owner password for a period of 5 hours after feed in to the grid starts Please contact the Service department if you need to make changes after this Installation and user gui
20. 4000 H 4600 H 4 Placing into operation 4 1 Switching on Start installation Cancel Placing into operation Switch on mains voltage supply safety device Switch on the DC voltage via the DC isolator on the underside of the device or via the external isolation device The Start installation prompt appears on the display Cancel is highlighted Use the D key to select OK Press the OK key to start the installation 4 2 Navigation in the Installation Menu 4 2 1 Key functions The following keys are available for navigation in the Installation Menu Key Function A Scroll up Increase value V Scroll down Reduce value lt Navigate one page or value to the left Key Function gt Navigate one page or value to the right a Select option Go to next level x Cancel operation Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Return to previous menu item 23 Placing into operation 4 2 2 Alpha numerical keypad In some menus a keypad containing letters or numbers is displayed so that the user can input alphanumerical text Key Function Key Function N Capital lower case letters OK Confirm entry and exit Dot decimal point Clear Delete entire entry Ww Space Cancel Exit entry without saving a Delete last character 123 Switch to number keypad ABC Switch to l
21. Installation and user guide Inverter 2100 H 3000 H 4000 H 4600 H PLATINUM ae a co 4 an fe a E EN As at 09 2012 Material no 753 840 AB Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Contents Contents 1 Introduction 5 1 1 PLATINUM H 5 1 2 About this manual 5 1 3 Symbols used 5 1 4 Symbols on product and packaging 6 2 Safety 7 2 1 Intended usage 7 22 Improper usage 7 23 Personnel requirements 7 2 4 General safety instructions 7 3 Installation 8 3 1 Scope of delivery 8 3 2 Unpacking 8 3 3 Assembly 9 3 4 Connection 12 4 Placing into operation 23 4 1 Switching on 23 4 2 Navigation in the Installation Menu 23 4 3 Installation Menu 25 4 4 Commissioning after replacement of a device 32 5 Operation of the inverter 33 5 1 Control elements and displays 33 5 2 Operation display 34 5 3 Isolation from the generator field 37 Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 3 Contents 6 Menu on the inverter 38 6 1 Menu operation 38 6 2 Menu tree 39 6 3 Status menu 40 6 4 Setup menu 43 6 5 Commands menu 51 6 6 Alarm Setup menu 53 6 7 Event Log menu 56 6 8 Statistics menu 57 7 Web server 58 ZA Connection between inverter and computer 58 7 2 Starting the web server 61 73 Menu tree 62 74 Home 63 75 Statistics 66 76 Setup 67 77 Event Log 75 78 Status 76 79 Help 78 7 10 Logout 78 8 Maintenance and cleaning 79
22. assigned MS Please note An ISP can change the SMTP IP address without prior notification gt f e mail protocols suddenly cease check whether the IP address has been changed 6 6 2 Alarm Setup gt Inverter Alarms Settings for the sending of notifications What is sent when to e mail addresses 1 and 2 and how frequently Parameters Meaning Notification time Time for sending the e mail with production data hours Notification time Time for sending the e mail with production data minutes Time interval Interval between two notifications in minutes Send production on Sends the energy yield data to e mail 1 at the e mail 1 indicated time Send mode on e mail 1 Sends the operating mode changes to e mail 1 sent immediately Send alarm on e mail 1 Sends a warning or alarm to e mail 1 sent immediately Send production on Sends the energy yield data to e mail 1 at the e mail 2 indicated time Send mode on e mail 2 Sends the operating mode changes to e mail 1 sent immediately Send alarm on e mail 2 Sends a warning or alarm to e mail 1 sent immediately 54 Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Menu on the inverter 6 6 3 Alarm Setup gt Portal Setup This menu shows settings for uploading data to the web portal Every hour the average values for the energy data for 15 minutes at a time are uploaded This upload is not possible if no user na
23. avoidance of injuries and plant damage Operating hours Total running time of the inverter since it was first taken into operation Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 41 Menu on the inverter 6 3 3 Status Plant Status This menu shows the operating mode status and operating parameters of the plant Parameters Plant mode Plant status faults Number of inverters Number of active inverters Number of inverter alarms Number of inverter warnings nput current nput power Output current Output voltage Output power Energy today 42 Meaning Operating mode is displayed For details of possible operating modes see section 5 2 6 Plant status is displayed For details of possible statuses see section 5 2 6 Total number of inverters in the plant Total number of active inverters in the plant Number of event alarms in the plant Number of event warnings in the plant Total current from the PV modules to the inverters Total power from the PV modules to the inverters Total grid feed in current from all active inverters Total grid feed in voltage from all active inverters Total grid feed in power from all active inverters Total energy production of the plant today Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Menu on the inverter 6 4 Setup menu Network Setup Inverter Setup Plant Setup Grid Setup
24. cable connection insert Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 1 3 nstallation 3 If required cut open the cable insert 11 to a width of around 1 mm for the Ethernet cable y N 4 Insert the Ethernet cable 12 in the cable insert A gt 5 Route the CAN cable 13 through the bore s in the cable grommet 6 Feed all network cables into the hous ing from below 14 Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Installation 7 Tighten the network screw connec tions A 8 Connect the CAN cable to the terminal block 14 When doing this make sure that the lines L and H are not accidentally swapped over during connection Incoming line left hand terminals L and H Outgoing line right hand terminals L and H 9 At the master inverter connect the plug of the Ethernet cable with the lug C J facing towards the rear into the socket 15 Termination Termination via an internal terminating resistor ensures correct operation of the network This is done by means of a jumper which lies across the CAN terminal block and short circuits two pins No jumper is fitted at the factory so the termina
25. cordance with the regulations of the country in which the inverter was installed Do not dispose of PLATINUM inverters in household waste Inverters can be fully returned to PLATINUM at the end of their service life PLATINUM inverters can be disposed of via municipal waste management for electrical devices Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 89 Diehl AKO Stiftung amp Co KG Pfannerstra e 75 83 88239 Wangen im Allg u Germany Tel 49 7522 73562 www platinum nes com
26. de for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 47 Menu on the inverter Setup gt Grid Configuration gt General Grid Setup Parameters Grid code Description Nominal grid voltage Nominal grid frequency Grid configuration Feed in Voltage limit min Voltage limit max Voltage time limit min Voltage time limit max Frequency limits min Frequency limits max Frequency time limit min Frequency time limit max Average AC voltage for isolation 48 Meaning Grid code country code for the installation Designation of the grid protection standards Nominal voltage of the local grid Nominal frequency of the local grid Local grid configuration TN TT IT undefined Feed in phase depending on the grid configuration TN TT No setting L1 L2 L3 IT No setting L1 L2 L1 L3 L2 L3 Information If changes are made to the feed in phase the energy log for the plant will need to be re created see Commands gt Plant Commands gt Re create Plant Energy Log Only then are the feed in phases correctly displayed in the Plant Overview Lower shutdown threshold for the local grid voltage Upper shutdown threshold for the local grid voltage Shutdown time lower voltage limit Shutdown time upper voltage limit Lower shutdown threshold for the local grid frequency Upper shutdown threshold for the local grid frequency Shutdown time lower frequency limit Shutdown time upper frequenc
27. earthed PV modules this assign ment needs to be swapped over f N gt Swap over the cables at the following connections swap red and black P4 ee BE caa N4 ei 2 Femina o N1 and P1 P3 2 5 BH fe ef SS N2 and P2 P2 N3 and P3 P1 8 G N4 and PA IE J J This concludes the work inside the inverter The lower cover can be closed again N gt Attach the lower cover with the four screws 8 20 Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Installation 3 4 5 Connect DC voltage Va A DANGER Risk of death due to high DC voltage A voltage is present at the PV modules when it is bright gt Before connecting the inverter check whether voltage is applied to the generator s DC voltage connection Before connecting the inverter check whether the polarity of the DC voltage is correct gt f voltage is applied wear insulating protective clothing and face protection gt Ensure that the cable plug has engaged completely with the socket gt Detach the DC voltage cable only if the inverter is not in operation gt Make sure that the DC isolator or a central isolation device can be accessed fre
28. ed today in EUR CO emissions avoided today in kg 00 04 08 12 16 20 24 on calibrated electricity meters The operation displays Month and Year show the same values relating to the affected period il The values displayed by the inverter may differ from those displayed 5 2 5 Operation display Plant overview The following values are displayed in this screen Voltage and current at the three feed in li 12 phases Voltage V 230 229 231 Current total power as a value and bar Current A 22 9 16 6 24 0 graph 0 nominal power Active Power kW 14 6 Plant overview Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 35 Operation of the inverter 5 2 6 Status bar SN Running 123456789123 Status Operating Serial number mode Status displays and operating modes are also indicated by the LEDs Status display Meaning LED Normal Inverter is operating with no warnings or Green alarms limited functions Green Alarm Inverter is in shutdown mode an alarm is Red present 1 Warning Inverter is still running but only with Yellow Operating Meaning LED Sleep mode Automatic shutdown input power level Yellow is insufficient Startup Initialisation of input values and network Yellow conditions Green Operation Electricity is fed into the grid Green De rating Output power is reduced to prevent the Yellow inverter from overhea
29. ely WARNING Risk of electric shock and damage to the inverter and or PV plant gt Use only the original DC voltage Multi Contact MC4 cable plug gt Only connect PV modules that meet the requirements of IEC 61730 class A gt Ensure that the max DC voltage permitted is not exceeded gt Ensure that the max direct current permitted per string is not exceeded gt Make sure that the lower cover is closed before making the DC voltage connection If more than one string is connected make sure that the quantity and type of solar modules and the voltage of strings to be connected in parallel are the same Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 21 nstallation f N 1 Fit original Multi Contact MC4 AR connectors to each string of the DC voltage cable Make sure that the polarity is correct here a 2 Take off the protective caps from the required DC voltage connections String 1 Connections N1 and P1 String 2 Connections N2 and P2 String 3 Connections N3 and P3 N negative P positive 3 Connect the prepared DC voltage connectors to the DC voltage connections In the process make sure that the connectors lock in place correctly N1 r il Fit protective caps to plug connectors that are not used on the inverter k 22 Installation and user guide for PLATINUM inverters 2100 H 3000 H
30. equired menu and confirm by pressing 6 1 2 Exiting the menu 1 Keep pressing the x key until the main menu appears 2 Exitthe main menu by pressing Back The start screen is displayed 6 1 3 Navigation keys 38 Key Function Key A Scroll up gt Increase value V Scroll down a Reduce value lt Navigate one page or value to x the left Function Navigate one page or value to the right Select option Go to next level Cancel operation Return to previous menu item Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 6 2 Menu tree Menu on the inverter Alarm setup Event Log Statistics Status Active alarms Inverter status Input parameters output parameters inverter peak power value energy today temperature isolation resistance operating hours Plant status Setup General setup Language date and time password CO rate yield rate yield currency Network setup IP address subnet mask gateway master setting Inverter setup Model serial number SW version numbers HW version numbers etc Plant setup Company customer name site date of install ation maintenance date area of responsibility device name message apparent power of plant Grid configuration Country country code etc Commands Inverter Energy Log Data Log Web Administrator commands Account Plant commands Notification Setup Inverter alarms Portal setup
31. ess 000 000 000 000 and press OK to confirm The router switch assigns the network parameters automatically to the inverter The inverter performs a restart Without DHCP Dynamic Host Configuration Protocol Without DHCP it is necessary to assign a unique address in the network that is not already in use to the inverter 1 Connect the master inverter and the router switch to each other using a CAT5 Ethernet cable 2 Under Setup gt Network Setup enter a unique IP address and press OK to confirm The inverter performs a restart Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 59 Web server 71 3 Access from the internet Prerequisites v A static IP address in the local network with without DHCP see previous section has been assigned to the inverter Setting up port forwarding in the local network router Refer to the Advanced Settings for the router switch Port 80 of the router switch must be forwarded to the static IP address of the inverter The external IP address of the local network can be found under http whatismyip com C ON If adynamic IP address is assigned to the local network by your internet il service provider ISP it is unlikely that the external IP address will remain constant for any length of time For this reason it makes sense to have a free account set up at No IP or another similar provider with a normal internet address for the local n
32. ess of the internet service provider s SMTP server in digits SMTP port 25 default or as defined by the ISP User name As defined by the ISP Password As defined by the ISP Sender e mail address Corresponds to the IP address of the inverter Receiver e mail 1 E mail address of recipient 1 in standard format Receiver e mail 2 E mail address of recipient 2 in standard format 70 Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Web server Setup gt Alarm Setup gt Inverter Alarms gt Energy Production A e 2 Statistics Status Help Logout Energy Production Alarm Setup Interval None Hourly gt Daily Inverter Alarms lt Send production on e mail 1 Send production on e mail2 v The recipients and timings for automatic transmission of energy production are selected in this menu Setup gt Alarm Setup gt Inverter Alarms gt Status E O Status Help Logout Status Alarm Setup i Send mode one mail1 I Send alarm on e mail 1 I fave Saas gt Send mode on e mail2 I Send alarm on e mail2 I Upload service diagnostics Upload C u In this menu e mail recipients are selected for automatic notification about operating modes and alarms Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 71 Web server 7 6 5 Setup gt Network CAUTION No connection betwee
33. etter keypad Text entry 1 If the required input field is highlighted yellow e g Customer name press the OK key to open the on screen keypad 2 Use the arrow keys V A and lt V D to select the required letter or number field 3 Press the OK key several times as required until the correct character is dis played in the text window top row this works in a similar way to the buttons ona mobile phone 4 Repeat steps 1 and 2 for the remaining characters 5 Once the entry is complete press the OK key on the on screen keypad to close the keypad A maximum of 19 characters can be displayed in the text window 24 Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Placing into operation il Text can be easily entered at the PC keyboard via the integrated web server 4 3 Installation Menu Va il S To transfer all settings correctly the Installation menu needs to be run through once in full When multiple inverters that are networked with each other via the CAN network are installed one inverter can be configured as the master and the others as slaves For this to be possible all inverters in the network must be switched on lf the inverter is configured as a master see section 4 3 5 it will automatically transfer the settings to the remaining inverters in the CAN network Every inverter is automatically allocated an ID number during initial operation This
34. etwork To do this the router needs to be capable of forwarding its IP address to the No IP service If the router is unable to do this but has a dynamic IP address the No IP setting will need to be updated at regular intervals J It should be possible to reach the web server of the inverter with these settings 60 Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Web server 7 2 Starting the web server The website is displayed optimally with Firefox 6 0 or Internet Explorer 8 0 or later versions Establishing a connection to the inverter 1 Launch the browser and enter the internal or external IP address or web address of the inverter when using No IP or similar in the address bar of the browser The login screen is displayed User name Password 2 Enter the user name and password and press Sign in to confirm The home screen is displayed see page 63 The following default access data are set up User name admin Password admin tis absolutely essential that the user name and password are changed when the web server is connected to the internet Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 61 Web server 7 3 Menu tree a 3 Home Plant System status Status Normal Warning Alarm inverter Mode Running Inactive etc Production status Today Month Year Statistics Plant Last 7 days
35. f an alarm is active for the selected inverter or for the entire plant it is marked with a yellow warning triangle 76 Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Web server 7 8 2 Status gt Overview ge a Plant This menu offers an overview of the technical profile of the inverter plant Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 77 Web server 7 8 3 Status gt Plant Output Energy Energy Energy power today month total w Wh kwh MWh ID Serial number Unit name Made Status This menu shows the operating mode status and some of the feed in data for the individual inverters in the plant 7 9 Help This menu displays contact information 710 Logout This menu is used to exit the web server The login screen is displayed again 78 Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Maintenance and cleaning 8 Maintenance and cleaning x DANGER Risk of death due to electric shock Only allow inverters to be opened by the PLATINUM Service department or by service partners authorised by PLATINUM Xe wo S DANGER A N Risk of death due to high DC and AC voltages gt Wear insulating protective clothing and face protection gt Maintenance and cleaning is to be performed only by trained specialist personnel The trained specialist personnel must be granted permission by
36. f present move the switch knob of I the DC isolator on the underside of the device to the 0 position er a Take off the lower cover gt Remove the four screws 8 from the lower cover and take off the cover WAYS followed when the connections are established Connect the network Connect the AC voltage Configure the grounding of the PV modules Mount the lower cover Connect the DC voltage il For safety reasons it is ESSENTIAL that the following sequence is Al OR WON 1 2 Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Installation 3 4 2 Network connection The inverter is equipped with two different network connections N CAN for communication between multiple inverters Ethernet for communication between the integrated web server of the Ethernet master and a computer or the internet Lit T Be cl e an overall length of up to 100 m il Up to 30 PLATINUM H inverters can be connected into a network with Network cable CAN cross section 0 21 mm max 100 m Ethernet CAT 5 shielded twisted pair cable with pre assembled RJ45 plugs Connect 1 Unscrew the network screw connection 10 from the left hand underside of the inverter 2 Take out the three way screwed
37. formation 1 3 2 Structure of warning S WARNING WORD Type source a nd consequence of the hazard gt Measures to avoid the hazard Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Introduction 1 3 3 Hazard levels in warnings Symbol Warning word DANGER WARNING CAUTION CAUTION Probability of occurrence Consequences of non observance Imminent danger Death serious injury Potential danger Death serious injury Potential danger Minor injury Potential danger Damage to property 1 4 Symbols on product and packaging The following symbols are used on the type plate on the bottom right hand side of the inverter Symbol Meaning High voltage Risk of electric shock Discharge time 60 minutes High voltages may still be present in the interior of the inverter up to 1 hour after it is switched off Hot surface The cooling element on the rear of the inverter can get very hot and reach temperatures of up to 90 C Read the manual Read this manual before carrying out any work on the in verter Disposal Do not dispose of PLATINUM inverters in household waste Packaging and replaced parts are to be disposed of in accordance with the regulations of the country in which the inverter was installed Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Safety 2 Safety 2 1 Intended usage Inverters are to be u
38. grid detected gt Check the AC protective switch No synchronisa Measure whether the grid voltage tion with the grid is present at the AC terminals gt Make sure that the DC switch es is are switched on and that the DC power is gt 7 W Fault in the coun gt Check the country settings try settings E06 GUI fault Display not gt Switch off the AC side and wait responding 3 seconds gt Switch the AC side back on again and wait 30 seconds gt lf the fault persists contact the installation company E07 High voltage on DC voltage gt Contact the installation company the input side threshold of 600 V DC exceeded E08 Low voltage on DC voltage too gt This fault will automatically be the input side low to operate the inverter Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H rectified when the PV voltage reaches 230 V gt If the fault is displayed even dur ing daylight and the PV voltage is gt 230 V contact the installation company 81 Faults and troubleshooting Code Message Meaning Remedy E09 Low PV isolation PV isolation gt Check the position of the DC E10 E11 E12 82 resistance Failure on the DC side Failure on the AC side High inverter temperature resistance is below the per mitted minimum threshold Inverter fault on the DC side Inverter fault on the AC side Maximum permitted internal inverter temperature exceeded
39. lectrical Electronic amp Information Technologies Technical connection conditions of the energy supplier responsible National and international regulations and provisions Ensure that all protection devices are working correctly Observe the operating conditions refer to Technical data on page 86 Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 7 Installation 3 Installation 3 1 Scope of delivery Inverter Wall bracket Brief guide Installation materials Grounding kit 3 2 Unpacking gt CAUTION Risk of injury gt Wear safety shoes when unpacking the inverter and during installation gt Ensure that the inverter is positioned securely S 1 Place the box the correct way up on the floor note the lettering 2 Cut through the seal and open the box on the top side 3 Take out the wall bracket from the A 1 packaging 4 Take off the upper padding elements N 5 Raise the inverter by its underside and i lift it by the handles 1 out of the box 6 Remove the lower padding element 7 Take out the installation materials and the grounding kit 8 Take out the brief guide J Enclosed installation materials Seals for the AC connection Jumpers for grounding and network termination Fastening and locking clamp for anti theft protection 8 Installation and user guide for PLATINUM inverters 2100 H 30
40. me has been entered The portal settings are compatible with the Meteocontrol settings Parameters Meaning FTP server IP IP address of the FTP server User name User name for the FTP server Password Password for the FTP server SMTP port 2 The number of the SMTP port of the SMTP server for uploading e mails to the portal Default setting 25 Only a master inverter can upload data to the FTP server Additional costs may accrue for external FTP service offerings 55 Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Menu on the inverter 6 7 Event Log menu Time Description 08 02 2012 09 22 E5 GridFault Warning 09 20 E26 FreqHigh Warning 09 19 E24 FreqHigh Warning 09 15 E23 OutVoltLow Warning Off gl EVENT LOG a This menu shows information about the events that have been logged by the inverter The events are listed in descending order The possible alarm messages are listed in section Event Log on page 75 Warning On Event has occurred Warning Off Event cancelled 56 Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Menu on the inverter 6 8 Statistics menu STATISTICS 6 8 1 Statistics gt Inverter This menu shows a summary of the key statistics of the inverter for Today Last month Last year Since startup Parameters Meaning Energy Total energy yield
41. n mode Yellow Shutdown Inverter system fault or unstable operating Red conditions Service Inverter can be manually overwritten Yellow 2 o 00 Current electricity production The current electricity production is shown as a bar diagram ranging from 0 W to the nominal power of the plant or selected inverter 7 4 4 Production status The yield of the plant or selected inverter is displayed in this area Today Display of the feed in curve for today 0 24 h Month The yield for each day in the current month is shown as a bar diagram 1 31 Year The yield for each month in the current calendar year is shown as a bar diagram Detailed values are displayed if you hover with the mouse over the graphics Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 65 Web server 7 4 5 Language selection The web server offers the following menu language options Icon Language Icon Language English ia French German E Italian i Spanish I E gt Click the icon for the required language The operator guidance language is changed over 7 5 Statistics Logout 9367 8 ae 1657kg 7 5 1 Selected inverter plant The plant or individual inverter is selected in the same way as on the home screen 66 Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Web server 7 5 2 Last 7 days The graphic shows the feed in curve for the plant
42. n the inverter and the network internet Do not make any changes to the network data unless the network is being reconfigured DHCP Network IP address 192 168 10 20 Network subnet mask 255 255255 0 Default gateway 0 0 0 0 TCP IP User Account U ia The system will reboot after changing the IP address C u A DHCP Values are automatically obtained for the network settings in this setup screen Network IP address IP address of the inverter connected via Ethernet cable Network subnet mask E g 255 255 255 0 Network gateway Address of the router in the network DNS server IP IP address of the Domain Name Server 72 Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Web server 7 6 6 Setup gt User Account BR OO Event log Status Help Logout User Account Current User Name admin Access Level 3 Change Password Enter current Enter new Re enter new N User account The upper part of this menu shows the current user with his her access authorisation level Change password In this area the password can be changed for the user displayed above Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 73 Web server Edit account After pressing the button Edit account you will see the list of users created on this web server User name Password Access level admin III Dele
43. n this installation and user guide gt Make sure that the inverter is protected against direct sunlight gt Make sure that the ventilation system is clean E15 Communication Internalcommu If the inverter is in shutdown fault nication fault mode switch off the AC side first and then the DC side gt Wait for 30 seconds and switch the AC side and DC side back on again gt If the fault persists contact the installation company E16 Ventilation fault No internal air gt Contact the installation company circulation E17 Fuse fault One or more gt Contact the installation company fuses or safety switches have blown E18 Active current gt Contact the installation company limitation E19 Reactive power gt Contact the installation company compensation Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 83 Faults and troubleshooting Code Message Meaning Remedy E20 Microprocessor Diagnosis sup gt f the inverter is in shutdown fault port in service mode switch off the AC side first situation and then the DC side gt Wait for 30 seconds and switch the AC side and DC side back on again gt lf the fault persists contact the installation company E21 Grounding cur gt Contact the installation company rent fault E22 High AC voltage AC voltage too gt The inverter will be restarted high feed in once the voltage is back within interrupted the permitted range gt Check
44. number can be changed and freely assigned in a further step The inverters on which no data is entered display different screen content depending on the menu If data cannot be entered the inverter displays the start screen During initial operation all inverters connected to the CAN network are disabled The configuration process cannot be performed if the DC voltage is missing or too low Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 25 Placing into operation 4 3 1 Overview The Installation Menu contains the following menu items Start installation Language Date Time Bus ID RS485 can be skipped Configure as master Country setting grid code Screen lock Customer name Site Message 1 Message 2 Owner password a N Changing the date and time can cause saved data to be overwritten or il lead to gaps in data logging During initial operation the date and time must be entered completely and correctly once The country setting can only be changed for the first 5 hours after feed in starts After this the menu is no longer accessible for the owner J 4 3 2 Selecting the language Once the Installation Menu has been launched the currently selected language is displayed language P 1 Press OK to call up the menu 2 Use the arrow keys V A to select A the desired language 3 Press OK to confirm the language Vv selection 4 Use the g
45. odel Serial number Part number Version GUI software part no GUI software version GUI hardware part number 44 Meaning Inverter model Unique identification for every inverter also to be found on the type plate Identification for every inverter hardware configuration within PLATINUM Unique version name for tracking the development of different inverter versions within PLATINUM GUI Graphical User Interface The GUI enables interaction with the inverter via the display Version of the GUI software Identification for the GUI card hardware Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Menu on the inverter Parameters Meaning GUI hardware version Version number of the GUI hardware SW1 part number Part number of the DSP1 software DSP1 Digital Signal Processing The DSP microprocessor is used to control the energy conversion in the inverter SW1 version Version number of the DSP software Part number of the control Part number of the DSP card board Version of the control Version designation for the DSP control hardware board Part number of the main Identification for the main board all of the board components and subsystems of the inverter are mounted on the main board Version of the main board Unique version number for tracking the development of the different main board versions SW2 part number Part number of the DSP2 software SW
46. of the inverter in kWh Yield Earnings for the energy fed in by the inverter e g in euro Avoided CO CO emissions avoided by the inverter in comparison to fossil emissions fuels in kg Peak power Highest instantaneous power of the inverter in W 6 8 2 Statistics gt Plant This menu shows a summary of the key statistics of the plant for Today Last month Last year Since startup Parameters Meaning Energy Total energy yield of the plant in kWh Yield Earnings for the energy fed in by the plant e g in euro Avoided CO CO emissions avoided by the plant in comparison to fossil fuels emissions in kg Peak power Highest instantaneous power of the plant in W Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 57 Web server 7 Web server The inverter has an internal web server which supplies detailed information about operation warnings alarms and the energy feed in 71 Connection between inverter and computer The plant power can be monitored via a remote query from a computer The connection between the inverter and the computer can be established either directly or via a network or the internet 71 1 Direct connection A If multiple inverters are connected via a CAN bus only the master inverter needs i G to be connected to the router switch Ethernet CAN J
47. oltage power Output Current voltage power Operating hours only for an individual inverter Selection In the area at the top right either the entire plant or an individual inverter can be selec ted 09 Apr 2013 1 Move the mouse over the light coloured field with the plant or inverter name Eee 277 A list of the inverters in the plant is 113371127536 4 4HE t mit Neueste Software displayed 2 Select an inverter The system status production status and operating hours of the selected inverter are displayed 114771126851 114771126944 114771126903 113371127009 114771126852 113371127240 113371127425 7 4 3 System status The System status area shows the status and operating mode of the plant or selected inverter Status Meaning LED Normal Inverter is operating with no warnings or alarms Green A Warning Inverter is still running but only with limited Yellow functions Green Alarm Inverter is in shutdown mode an alarm is present Red 64 Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Web server Meaning LED Sleep mode Automatic shutdown input power level is Yellow insufficient Startup Initialisation of input values and network Yellow conditions Green Operation Electricity is fed into the grid Green De rating Output power is reduced to prevent the inverter Yellow from overheating Green Close down Inverter is in shutdow
48. r 110371195179 GUI Software revision 1 32 GUI Part number 405020 009 SW1 Revision 3 01 SW1 Part No 404148 009 SW2 Revision 201 SW2 Part No 404105 009 C u RE This menu allows you to provide a plant description that suits your own requirements You will need to have these data available for service situations Data displayed in black can be edited Data that are greyed out are defaulted by the system and cannot be edited 68 Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 7 6 3 Setup gt General Setup DEE Status Help Logout Ev Web server Date Time Time zone General settings CO2 Rate 0 01 99 99 Earnings Rate 0 01 99 99 Earnings Currency 13 Feb 2013 16 46 The following data can be set in this menu Date Time Time zone CO rate in kg kWh Rebate per kWh Earnings currency Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 69 Web server 7 6 4 Setup gt Alarm Setup Setup gt Alarm Setup gt Notification Setup SMTP Server Alarm Setup SMTP Port eo Be aaa Setup User name Password Sender Mail Address Receiver Mail Address 1 Receiver Mail Address 2 C u nt The addresses for automatic notification via e mail are set up in this menu SMTP server IP addr
49. r must be easily ac 400 Q O m cessible without additional tools or equipment _ s l J 2 Fix the wall bracket to the assembly Dimensions in mm wall with suitable fixing materials 3 3 Lift the inverter and insert the upper mountings 2 in the upper slots 3 on the wall bracket 4 Align the lower mountings 4 on the lower slots 5 10 Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Installation 4 5 Slide the inverter onto the bracket A Qi Qi I 7 Anti theft protection Two clamps are included in the scope of delivery with the aid of which the inverter can be protected against theft A padlock is not included in the scope of delivery 1 Mount the fastening clamp 6 with two screws on the underside of the inverter 2 Guide the locking clamp 7 through the fastening clamp 3 Insert the padlock through the eyelet on the locking clamp and lock Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 11 Installation 3 4 Connection 3 4 1 Preparatory work 1 If present disconnect the DC voltage side with the external disconnect R device from the solar generator An 2 I
50. rent Fault bypass gt Contact the installation company Damaged varis Contact the installation company tors on the DC side 9 3 Faults and troubleshooting Fault Cause Remedy No longer any e mail Changed SMTP gt Find out the new SMTP IP protocols IP address address from your internet service provider ISP Obviously incorrect Fault in the gt On the master inverter run Re values in the statistics Energy Log create Plant Energy Log see Commands gt Plant Commands menu Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 85 Technical data 10 Technical data Input variables Max PV power Max DC power cos 1 MPPT voltage range Max input voltage Max MPPT input current Number of string inputs Number of MPP trackers Short circuit current Output variables Nominal power cos 1 Nominal current Max apparent power Max AC current Fuse protection on the AC side Min start power Network voltage frequency Feed in monitoring phases Max permitted grid impedance Z Standby consumption Short circuit strength Power factor cos Max short circuit current Max switch on current Efficiency Max efficiency Euro efficiency Type name 86 2100 H 3000 H 4000 H 4600 H 2 350Wp 3 450Wp 4 450Wp 5 150 Wp 2100W 3 000W 4 000W 4 600 W 230 V 480 V 600 V 9 5A 13 5 A 18 0 A 21 0 A 3 1 14 2 A 20 2 A 270A 31 5 A 2100 H 3000 H 4000
51. requency Connection max Maximum frequency for renewed grid connection frequency 50 Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Menu on the inverter 6 5 Commands menu nal Plant Commands COMMANDS 6 5 1 Commands gt Inverter Commands This menu is used to display the results collected in the datalogger Parameters Meaning Delete Energy Log Deletes the entries in the energy log and the cumulative values of the inverter Delete Data Log Deletes the 15 minute average power values of the inverter ResetWeb Administrator Resets the administrator password to Admin Account Self test Starts the self test Italy only Self test result Displays the results of the last self test Italy only Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 51 Menu on the inverter 6 5 2 Commands gt Plant Commands This menu is used to display the results collected in the datalogger Parameters Delete Energy Log Delete Data Log ResetTotal Number of Inverters Re create Plant Energy Log 52 Meaning Deletes the entries in the energy log and the cumulative values of the plant Deletes the 15 minute average power values of the plant Updates the total number of inverters when inverters are added or removed Re creates the energy log of the plant based on the energy logs of the inverters that are currently connected and being operated in
52. s OK to confirm Next Screen timeout INSTALLATION MENU a 4 3 9 Customer name Site Message 1 Message 2 Every inverter in the network can be identified using the following data Customer name Name of the operator Site Site of the inverter or plant Message 1 Message 2 Data fields for additional identification information The data entry method is the same in all four fields 30 Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Placing into operation Customer Name Site Message 1 Message 2 is displayed 1 Press OK to call up the menu 2 Press the OK key again to display the on screen keypad 3 Enter the required text max 19 characters 4 Press the OK key on the on screen keypad when the entry is complete 5 Use the gt key to select Next Press OK to confirm the entry 7 Press OK to confirm Next Customer name Back Next D INSTALLATION MENU a 4 3 10 Owner password CAUTION Risk of unauthorised manipulation of the inverter gt Do not leave the owner password in its default setting make sure you change it to a different 4 digit value gt r gt The owner password needs to be changed on every inverter This inform ation is not transmitted from the master to the slaves Pi The password is displayed as 1 Press OK to call up the menu
53. sed solely for the purpose of feeding photovoltaically generated solar energy into the public grid All other usage does not comply with the regulations 2 2 Improper usage The inverters are not to be used in island grids The inverters are not to be used in vehicles The inverters are not to be used in areas at risk of explosion flour dust sawdust etc The inverters are not to be exposed to direct sunlight The inverters are not to be used in areas in which the ammonia content of the air exceeds 20 ppm All warranty claims will be rendered null and void in the event of failure to comply with the warranty terms or the information provided in this operating and installation manual 2 3 Personnel requirements The inverter may only be installed and put into operation in accordance with this installation and user guide by trained specialist personnel for example Service partners who are authorised by PLATINUM Authorised specialist personnel with knowledge of the applicable guidelines and standards 2 4 General safety instructions The inverters are to be used in their original state without independent modifications and in a technically perfect condition Steps must be taken to ensure that the following are adhered to when assembling and connecting the inverter and the PV system Guidelines and regulations valid in the respective country Provisions of the trade associations T V VDE Association for E
54. t key to select Next 5 Press OK to confirm Next net The user interface is then displayed in the chosen language INSTALLATION MENU a 26 Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Placing into operation 4 3 3 Setting the date The currently set date is displayed Sa R 1 Press OK to call up the menu ate u 2 Use the arrow keys V A and lt gt to A enter the current date in the format 00 00 2008 DD MMYYYY Yy 3 Press OK to confirm the changed date 4 Use the D key to select Next Badk m 5 Press OK to confirm Next INSTALLATION MENU A 4 3 4 Setting the time The currently set time is displayed 1 Press OK to call up the menu 2 Use the arrow keys V A and lt gt A to enter the current time using the o 9 4 3 24 hour clock Yy 3 Press OK to confirm the changed time 4 Use the D key to select Next 5 Press OK to confirm Next INSTALLATION MENU a Time 09 43 lead to gaps in data logging During initial operation the date and time must be entered completely and correctly once il Changing the date and time can cause saved data to be overwritten or Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 27 Placing into operation 4 3 5 Bus ID RS485 You can skip this step if you have a CAN network Bus ID RS485
55. t Warning Off 8 2012 07 27 04 59 33 E24 FreqHigh Warning On 9 2012 07 27 04 59 33 E5 GridFault Warning On 10 2012 07 26 04 58 51 E24 FreqHigh Warning Off 11 2012 07 26 04 58 51 E5 GridFault Warning Off 12 2012 07 26 04 58 44 E24 FreqHigh Warning On 13 2012 07 26 04 58 44 E5 GridFault Warning On 14 2012 07 25 05 14 59 E24 FreqHigh Warning Off Pages 23456789101112 4P gt gt For all inverters connected to the PC internet the current events are displayed in chronological descending sequence Navigation Via calendar Select the required day in the calendar The events for this day are displayed in chronological descending sequence Scroll Via the buttons ii Downloading the Event Log gt Click The events for the selected period are downloaded as a txt file Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 75 Web server 7 8 Status The Status menu contains the following submenus Alarm Overview Plant Selecting the inverter plant In the status menu bar on the far right you can select either the entire plant or an individual inverter see Home menu 7 81 Status gt Alarm Plant Fuse fault Grid Grid Grid C frequency Grid High output DC current VDR fault DC side Comm failure Fan failure DNO Remote trip This screen shows all potential warnings and alarms that can occur on an individual inverter or on the overall plant I
56. te Del Delete Delete Delete Del Delete owner ws guest ss User Account gt Delete Delete Delete Fo ON DoH PWN 2 21 fe 81 5 5 7 N fo w o pal A In the default setting three users with different access authorisation levels are set up The user name and password are identical in the default setting A maximum of 10 users can be maintained Access authorisation levels Level User Rights 3 admin Full read write access 2 owner Read write access to all data Exception User Accounts and Network Setup 1 guest Read access to all data No access to the Setup menu CAUTION Risk of unauthorised access to the web server Change all passwords during configuration of the system Do not use standard passwords 74 Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Web server 7 7 Event Log A e t 2 Statistics Setup Status Help Logout Date Time Description 1 2012 07 27 14 13 49 System Reset Info On 2 2012 07 27 05 14 52 E24 FreqHigh Warning Off SMTWTFS 3 2012 07 27 05 14 52 E5 GridFault Warming Off 1234567 4 2012 07 27 05 14 27 E24 FreqHigh Warning On 89 80 2132 38 14 io ab fe see an 5 2012 07 27 05 14 27 E5 GridFault Warning On 22 22 24 25 26 27 28 6 2012 07 27 04 59 36 E24 FreqHigh Warning Off et 7 2012 07 27 04 59 36 E5 GridFaul
57. the energy provider responsible Before every maintenance or cleaning task Switch off mains voltage supply safety device gt Set the switch knob of the DC isolator to 0 gt Wait at least 60 minutes until the capacitors are discharged gt Make sure that no voltage is applied to the DC cables 81 Maintenance Have the inverter serviced at least once a year by the PLATINUM Service department or by a service partner who is authorised by PLATINUM 8 2 Cleaning CAUTION Destruction of the inverter gt The inverters must not be cleaned with a steam cleaner To ensure effective cooling regularly clean the cooling element on the rear of the inverter Suitable tools for this Vacuum cleaner Soft brush Compressed air Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 79 Faults and troubleshooting 9 Faults and troubleshooting 9 1 Checklist in the event of faults If the inverter is not feeding any electricity into the grid check the following Are all of the connections in the system correctly attached Are both the AC protective switch es and the DC protective switch es switched on Is there enough solar radiation to generate electricity gt 7 W Are the operating mode display LEDs normal Are any warnings or alarms shown on the display see Event Log Do the values for the PV voltage PV current and PV power
58. the country settings gt lf the fault persists contact the installation company E23 Low AC voltage AC voltage too gt The inverter will be restarted low feed in once the voltage is back within interrupted the permitted range gt Check the country settings gt lf the fault persists contact the installation company E24 High frequency Grid voltage gt The inverter will be restarted on the output frequency is once the frequency is back within side above the upper the permitted range limit gt Check the country settings gt lf the fault persists contact the installation company E25 Low frequency Grid voltage gt The inverter will be restarted on the output frequency is once the frequency is back within side below the lower the permitted range limit gt Check the country settings gt lf the fault persists contact the installation company 84 Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Code Message Faults and troubleshooting E26 High DC current on the output side E27 Output current imbalance E28 Grid fault but still working E29 VDR fault on the DC side Meaning Remedy DC share of grid The inverter will attempt to feed in current is restart as soon as the fault is too high rectified gt lf the fault persists contact the installation company Imbalance gt Contact the installation company between the output current phases only for 3 phase cur
59. the system This process may take several minutes It requires that all of the inverters in the plant are in operation Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Menu on the inverter 6 6 Alarm Setup menu Z Inverter Alarms Portal Setup ALARM SETUP 6 6 1 Alarm Setup gt Notification Setup Setting for remote monitoring of notifications and alarms including settings for the mail server sender s and e mail recipient s Parameters Meaning User name E mail user name Password User password for the mail server Sender e mail address Valid e mail address required in order to send notifications Receiver Email 1 Address for the notification to recipient 1 Receiver Email 2 Address for the notification to recipient 2 SMTP server Simple Mail Transfer Protocol server for the sending of e mails SMTP Port 1 Number of the SMTP port of the SMTP server Default setting 25 Notes on e mail settings The SMTP server forwards the e mails to the recipient Many companies have their own SMTP server while private individuals generally use the SMTP server of their internet service provider ISP Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 53 enu on the inverter Va operated by the same internet service provider ISP a new SMTP server il If an inverter is moved or connected to a different network that is not will need to be
60. ting Green Close down Inverter is in shutdown mode Yellow Shutdown Inverter system fault or unstable Red operating conditions Service Inverter can be manually overwritten Yellow 00000 36 Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Operation of the inverter 5 3 Isolation from the generator field On devices with a DC power switch The DC isolator on the underside of the device allows the solar generator to be switched on and off Position 0 Solar generator switched off Position 1 Solar generator switched on PLATINUM recommends activating the DC isolator once a year to prevent the contacts from fusing together PLATINUM recommends operating the DC isolator when the power is at its lowest during the night or late in the evening On devices with no DC power switch gt Disconnect the DC side from the solar generator using the external isolation device Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 37 Menu on the inverter 6 Menu on the inverter 6 1 Menu operation 6 11 Call up menu In the start screen use the V key to switch to the bottom display line The Menu field is highlighted the rest of the screen is greyed out 2 Press to call up the menu 1 The main menu is displayed Event Log MAIN MENU a Statistics 3 Use the navigation keys to select the r
61. ting resistance is not activated The terminating jumper is included with the supplied installation materials Inverters in the network Jumper position Meaning Individual standalone Jumper inserted Terminating resistance activated inverter First last inverter in the at Jumper inserted Terminating resistance activated network All other inverters in the Terminating resistance de No jumper i network activated Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 1 5 nstallation XN N 1 At each inverter check that the jumper 16 is in the correct position in ac cordance with the table above 2 If not correct the jumper position accordingly 3 4 3 Connect the AC voltage va DANGER Risk of death due to high AC voltage gt Switch off the mains voltage supply AC side before connecting the inverter safety device gt Make sure that the central isolation device can be accessed freely gt Only connect the inverter toTN or TT networks see IEC 60364 1 with 230 V gt Observe max fuse protection permitted on the AC voltage side see Technical data on page 86 gt Establish the AC voltage connection with a circuit breaker PLATINUM recommends a type C miniature circuit breaker gt f an external residual current protective device is required PLATINUM recommends using a residual current protective device RCD of t
62. ve power Only for CosPhi P method Automatic adjustment based on the grid code Y point Defines the CosPhi setting for each device Only for CosPhi P method Automatic adjustment based on the grid code Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H 49 Menu on the inverter Setup gt Grid Configuration gt Power Balancing This menu displays the power balancing between the phases according to the selected grid standard Parameters Meaning Name Name of the grid standard for power balancing Enable Enables or disables power balancing Imbalance limits Balancing of the power per phase Maximum permitted imbalance limits in VA Setup gt Grid Configuration gt Active Power Settings This menu displays the settings for the effective power according to the selected grid standard Parameters Meaning Name Profile name of the effective power settings Enable fixed Enable disable fixed effective power limit Eff power setpt Fixed effective power limit in W Setup gt Grid Configuration gt Grid Connection This menu displays the limits for reconnection of the inverter according to the selected grid standard Parameters Meaning Name Name of the grid connection standard Vac Min connection Minimum voltage for renewed grid connection V max connection Maximum voltage for renewed grid connection Connection min Minimum frequency for renewed grid connection f
63. y limit Limit values for isolation based on the average voltage over a specific time period e g average voltage gt 253 V AC over a period of 10 minutes Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Menu on the inverter Setup gt Grid Configuration gt This menu displays the limits for the effective power according to the selected grid standard Parameters Name Enable Start frequency Isolating frequency Slope Recovery rate Meaning Name of the grid standard for power derating Enables or disables power derating Frequency at which power derating starts Frequency at which power derating ends and the inverter is isolated from the grid Slope of the effective power curve in Hz Recovery rate of the inverter in min Setup gt Grid Configuration gt Reactive PowerYield This menu displays the method for monitoring the reactive power generation according to the selected grid standard Parameters Name Method PF Setpt Number of points PntX1 PntX8 PntY1 PntY8 Meaning Name of the grid standard for reactive power Method for feeding in reactive power Deactivated CosPhi P based on characteristic curve CosPhi fixed Fixed power factor value Only for CosPhi fixed method Number of XY points used for the characteristic curve with a max of 8 points each Only for CosPhi P method X point Defines the percentage of the effecti
64. ype A a N CAUTION Destruction of the inverter Never connect inverters between two phases gt Never mix up the phases with PE or N gt f several inverters are connected distribute them across the three phases so that the differences in feed in power between the phases do not exceed the maximum permitted unbalanced load of the grid operator KL J 16 Installation and user guide for PLATINUM inverters 2100 H 3000 H 4000 H 4600 H Installation Prepare the connection cable for the AC voltage electrician and depends on the cable length and installation situation Min cross section 6 mm Max cross section 16 mm il Dimensioning the wire cross section is the responsibility of the 1 Protect the AC voltage connection lines with appropriate fuses see Technical data on page 86 2 Strip 18 mm of insulation from the AC voltage connection lines and add wire end sleeves Connect y plied seals must be used to ensure that the requirements for safety class il The AC connection screw fitting does not have a seal One of the sup IP65 are met 1 Unscrew the AC screw connection 9 from the right hand underside of the inverter 2 Route the prepared AC voltage connection line through the AC screw connection Use a seal if required 3 Feed the AC voltage connection line into the housing from below 4 Tighten the AC screw connection