1. 30 VDC Permissible load max R acc to power supply 900 Q at 30 V 600 Q at 24 V 400 Q at 20 V Fig 7 Note that twisted leads must be used for the output signal Camille Bauer AG VK 616 4 Aargauerstr 7 CH 5610 Wohlen Switzerland Supply Sensor Pt100 Type 616 7111 4100 000 Voltage Range 0 100 C Ord 616 123456 123 001 12 30V Output 4 20mA Fig 8 Example of a nameplate 8 Configuring the transmitter The transmitter is configured via the serial interface of a PC For the configuration a special advantage is that devices of both the standard and Ex executions with and without a separate power supply connection can be configured The following accessories are required PC software V 600 plus Programming cablee PK 610 Ancillary cable for SINEAX Type VK 616 A PC with an RS 232 C interface Windows 3 1x 95 98 NT or 2000 is also required The configuration procedure and choice of parameters is explained by the menu guided configuration program Safe area SINEAX VK 616 Ancillary cable Interface PK 610 OFF f ON Programming connector OFF Connect separate power supply to SINEAX Fig 7 ON Power supply provided by PC Fig 9 Configuring of SINEAX VK 616 without the power supply For this case the switch on the interface must be set to ON Hazardous area Safe area Fig 10 Configuring the SINEAX V
2. 141 440 EMV Fachgrundnorm Messverfahren EMC Generic Standard Measurement methods St raussendung EN 50 081 2 1993 EN 55011 1992 1 5 meter St rfestigkeit EN 50 082 2 1994 IEC 1000 4 2 1991 Immunity IEC 1000 4 3 1995 2 3 PC software V600 plus on CD Eee A Download free of charge under 146 557 ae ee ae http www camillebauer com Richtlinie Directive Operating Instructions VK 616 Bd 73 23 EWG Elektrische Betriebsmittel zur Verwendung innerhalb bestimmter Spannungs 137 902 grenzen Niederspannungsrichtlinie CE Kennzeichnung 95 in German 73 23 EEC Electrical equipment for use within certain voltage limits Low Voltage Direc tive Attachment of CE mark 95 Operating Instructions VK 616 Bf EN Norm Standard __ IEC Norm Standard 5 einen 142 076 EN 61 010 1 1993 IEC 1010 1 1990 A1 1992 Die explosionsgeschutzte Ausf hrung dieses Produkts stimmt mit der Europ ischen 5 5 Richtlinie 94 9 EG berein Operating Instructions VK 616 Be 142 125 The explosion protected variant of this product has been manufactured according the in English European directive 94 9 Ort Datum Wohlen den 6 November 2000 Place date Unterschrift o i A M Ulrich Signature Leiter Entwicklung Diese Erkl rung bescheinigt die bereinstimmung mit den This declaration certifies compliance with the above mentioned genannten Richtlinien beinhaltet jedoch keine Zusicherung directives but does no
3. the PK 610 interface 9 Commissioning Switch on the measuring input and the power supply The ambient temperature must be between 10 and 80 C for standard instruments and 10 and max 57 C for Ex versions depending on P see type exa mination certificate Fig 14 SINEAX VK 616 72 74 electrically isolated 10 Maintenance No maintenance is required 13 Declaration of conformity C E EG KONFORMIT TSERKL RUNG DECLARATION OF CONFORMITY 11 Accessories and spare parts Dokument Nr VK616 GT DOC Document No Description Order No Hersteller Camille Bauer AG Manufacturer Switzerland Programming cable PK 610 Anschrift Aargauerstrasse 7 Address CH 5610 Wohlen Interface Produktbezeichnung Programmierbarer Temperatur Messumformer DSUB 9p F mit galvanischer Trennung Product name Programmable temperatur transmitter 137 887 Input output electrically isolated am Typ Type SINEAX VK616 Das bezeichnete Produkt stimmt mit den Vorschriften folgender Europ ischer Richtlinien berein nachgewiesen durch die Einhaltung folgender Normen 1 meter The above mentioned product has been manufactured according to the regulations of the following European directives proven through compliance with the following standards Ancillary cable SINEAX type VK 616 Nr No Richtlinie Directive 89 336 EWG Elektromagnetische Vertraglichkeit EMV Richtlinie 89 336 EEC Electromagnetic compatibility EMC directive
4. K 616 types 616 73 74 when the transducer and or the sensor are in the hazardous are Depending on whether the device is programmed with or without a separate power supply the switch on the PK 610 interface is to be set to ON or OFF See Fig 9 The earthing conditions must be observed when program ming the instrument e g the instrument is installed in the plant If for the VK 616 72 74 one of the input wires is earthed or for the VK 616 71 73 one of the power supply or input wires is earthed a PC without an earth connection must be used when programming e g a notebook running on the batteries Under no circumstances should a PC be used running from a power supply with an earth connection as this will damage the transducer For devices of the explosion protection type intrinsically 12 Dimensional drawings safe the PC or laptop must support a voltage level of 500 Veff between the RS 232 interface and earth e g battery operation In particular check other peripheral devices that are connected If the above voltage level is not supported e g operation from the mains power supply the earth connection of the programming cable PK 610 must be connected to the potential equalization conductor At the same time it must be ensured that the programming circuit of the VK 616 is potential free Fig 11 Connect the Fig 12 Remove the earth connection to the earth connection from PK 610 interface
5. Safety precautions to be strictly observed are marked with following symbols in the Operating Instructions A A The instruments must only be disposed of in the correct way Contents Read first and then sccavessactessenceisccentiedvncscudadcoumecbaseecsaasdacumteshinsioss lt OCODE OL SUPDIV wate sin cressnitciasastinloretintriaduaatindasdientuadeieisieisdadsanmubiednnte gt Bref descriptor weraiah cavineaosicceacatuntsctundnacansncttutcemtevbeessnesinsadsiumtussideness W enee Eo i E E E E E E T Securing the terminal head of the temperature Sensor Installation in the plant sista cscusenctitsiduntidswnanended lt Guberdowsstesessdudantunbiesoess Electrical connections aiaeracescncantsctundneconcscadadcemievbewsatesnsadsiamtessideness Configuring the transmitter oo cicciiscccsticsenessncsesectanteeeisieensecseiasinerssss lt COMMISSION G eaen i a eE aea eei 10 MaimtenaNnG esencreccecsars piiama ad eiai aaiae 11 Accessories and spare Palrts cccccsscccssececeseeceeeeseeeeeseeeeeseeeenes 12 Dimensional drawings rice cteccscutaeieteuctsndsiecmsercsewtanble tensiqeatereatuntdessces 13 Declaration Of CONfOrmity sxiccacsentectuntoescnecautedecwtaneiesctaendeneiuatunniesends OonooakhWDND 1 Read first and then The proper and safe operation of the device assumes that the Operating Instructions are read and the safety warnings given in the various Sections 6 Installation in the plant 7 Electr
6. compensated The output signal is a current in the range 4 20 mA The input measuring range signalling and other parameters are pro grammed with the aid of a PC and the corresponding software The sensor circuit is monitored for open and short circuits and the output responds in a defined manner if one is detected The power supply of 12 30 V DC is connected together with the signal by the two leads connected to the measurement output loop powered Explosion proof intrinsically safe EEx ia IIC T6 versions rounds off the series of transmitters Transmitters supplied as standard versions are configured as follows Measuring input Pt 100 for three wire connection Measuring range 0 600 C Measuring output 4 20 MA Open circuit supervision Output 21 6 mA Mains ripple suppression For frequency 50 Hz 4 Technical data Measuring input gt Input variable and measuring range configured Measuring ranges Input variables Min Max Limits span span Temperatures with resistance thermometers for two three or four wire connection Pt 100 IEC 60 751 200 to 850 C 50K 850 Ni 100 DIN 43 760 60 to 250 C 250 K Temperatures with thermocouples Type B E J K N R S T acc to IEC 60 584 1 Type L and U DIN 43 710 acc to type 2mV 80 mV Type W5 Re W26 Re Type W3 Re W25 Re acc to ASTM E 988 90 Cold junction compensation Internal Incorporated Pt 100 o
7. ical connections 8 Configuring the transmitter 9 Commissioning are observed The device should only be handled by appropriately trained per sonnel who are familiar with it and authorised to work in electrical installations Unauthorized repair or alteration of the unit invalidates the warranty 2 Scope of supply Figs 1 and 2 Transmitter one of the two versions 1 Order Code Significance of the 2nd and 3rd digits Standard not electrically isolated Standard electrically isolated EEx ia IIC T6 not electrically isolated EEx ia IIC T6 electrically isolated 0 Basic configuration programmed 1 Configured to order Fig 1 Operating Instructions Programmable Temperature Transmitter SINEAX VK 616 Mcamite BAUER Camille Bauer LTD Aargauerstrasse CH 5610 Wohlen Switzerland Phone 41 56 618 21 11 Fax 415661835 35 e mail info camillebauer com http www camillebauer com VK 616 Be 142125 01 06 06 1 Operating Instructions 2 each in German French and English 1 Type Examination Certificate 3 only for intrinsically safe explosion proof devices 3 Brief description The programmable SINEAX VK 616 is a two wire head mounted trans mitter It is designed for installation in the terminal head of a temperature sensor DIN 43 729 shape B It is used for measuring temperature in conjunction with a thermocouple or resistance thermometer Thermocouple non linearities are automatically
8. ign the transmitter in the lower part of the terminal head and secure it using two chease headed screws 1 and two springs 2 See Fig 3 Connect the leads acc to section 7 Electrical connections 7 1 Alternative measurement connections Connect the measuring leads to suit the application as given in Table 1 Table 1 Measuring input TC External cold junction compensation Internal cold junction compensation with Pt100 connected to the terminals Internal cold junction compensation with incorpo rated Pt100 1 KL me NU SG SS Fig 4 SINEAX VK 616 71 73 not electrically isolated Fig 5 SINEAX VK 616 72 74 electrically isolated Fig 3 Spring mounting on the insert in the terminal head 6 Installation in the plant Mount the thermometer transmitter according type screwed sliding terminal screws flange etc at the prescribed location Make sure that the ambient temperature stays within the per missible limits Standard instruments 25 and 80 C Ex version 25 to max 57 C depending on P see type examination certificate 7 Electrical connections The leads are connected to the 6 Philips head screw terminals on the front of the transmitter The maximum wire gauge is 2 x 1 5 mm see Fig 6 The applicable enclosure Protection Class for the terminals is IP 00 according to EN 60 529 Also note that
9. lt in 7 1 1 2 Internal cold junction compensation with Pt100 connected to the terminals For this alternative a Pt100 is connected to terminals 1 and 4 Ter minals 1 and 2 must be connected Set the configuration software to internal thermo element and Pt100 on terminals 7 1 1 3 External cold junction compensation When using a cold junction thermostat please observe that the correct reference temperature is configured The connection between the cold junction thermostat and the transducer is made with copper wires 7 1 2 Connection to resistance thermometers 7 1 2 1 Two wire connection Terminals and 2 and 3 and 4 must be connected in the case of a two wire measurement The lead resistance must not be greater than 30 Q per lead 7 1 2 2 Three wire connection Terminals 1 and 2 must be connected in the case of a three wire measurement It is not necessary to compensate the leads providing the three leads have identical resistances The lead resistance must not be greater than 30 Q per lead 7 1 2 3 Four wire connection The four wire measurement is independent of lead resistance within wide limits and therefore no compensation is necessary The lead resistance must not be greater than 30 Q per lead 7 2 Measuring output leads output powering circuit Connect the measuring output leads analog output and power supply to terminals and acc to Fig 7 Permissible power supply 12
10. r with Pt 100 connected to the terminals External Via cold junction thermostat 0 60 C configurable output powering circuit Impressed DC current linear with temperature 4 20 mA 2 wire technique Measuring output gt gt Output signal IA Standard range Power supply V 12 V Max output current mA R_ max ext kQ Load max Q with 20 mA output A External resistance load 900 600 0 ea 10 36 12 24 30 Power supply V Programming connector on the transmitter Interface Serial interface Open and short circuit sensor circuit supervision Signalling modes Output signal configurable to the value the output had immediately prior to the opern or short circuit hold value a value between 4 and 21 6 mA The short circuit indicator is only active for the RTD 100 Q at 0 C three and four wire measuring mode Power supply gt _ DC voltage Supply 12 30 VDC max residual ripple 1 p p supply must not fall below 12 V Protected against wrong polarity 5 Securing the terminal head of the temperature sensor The SINEAX VK 616 is suitable for mounting on an insert that is fitted into a temperature sensor with a Shape B DIN terminal head The length of the leads to the insert has to conform to the height of the particular terminal head Figures 4 and 5 Thread the leads through the hole in the centre of the transmitter Al
11. t include a property assurance von Eigenschaften Die Sicherheitshinweise der mitgelieferten The safety notes given in the product documentations which are Produktdokumentationen sind zu beachten part of the supply must be observed
12. the data required to carry out the prescribed measure ment must correspond to those marked on the nameplate of SINEAX VK 616 Sensor Range Output Supply Voltage see Fig 8 the total loop resistance connected to the output receiver plus leads does not exceed the maximum permissible value R see Measuring output in Section 4 Technical data the measurement input and output cables should be twisted pairs and run as far as possible away from heavy current cables In all other respects observe all local regulations when selecting the type of electrical cable and installing them In the case of Intrinsically safe explosion proof the supplementary information given on the type examination certification the EN 60 079 14 and also local regulations applicable to electrical installation in explosion hazard areas must be taken into account RTD Three wire connection Two wire connection Four wire connection Notes 7 1 1 Connection to thermocouples Pay attention to correct polarity when connecting thermocouples If the lead from the thermocouple to the transmitter has to be extended be sure to use thermally compensated leads suitable for the particular type of thermocouple 7 1 1 1 Internal cold junction compensation with incorporated Pt100 Connect terminals A and 4 when using internal compensation by comparison Set the configuration software to internal thermo element and Pt100 bui
Download Pdf Manuals
Related Search
dk dk metcalf dkoldies dk hardware dkk to usd dka icd 10 dkim checker dkng stock dk donuts dka medical abbreviation dk bonanza dks stock dk hardware supply dka symptoms dka vs hhs dk horse dka criteria dka protocol dkk to eur dkm games dkny women dk12 login dk country dkny be delicious dkm login dkk to euro
Related Contents
Providing Resources in Education with Parents 第91回定時株主総会 招集ご通知 Digital University® Framework “ADES User Manual” Version 2.0 EXSYS EX-11099 NEURODYN Esthetic Descargar Aider les pauvres, histoire politique et associative CB 1/23 Eco CB 1/25 Eco CB 1/28 Eco Dossier de Presse 2014 - Belfort `、貴励磁作動形プレーキ Copyright © All rights reserved.