Home
Installation and Operating Instructions
Contents
1. It will take approximately thirty seconds for a smooth flow of water to be obtained whilst air and any debris is being dispersed from the shower When a smooth flow of water is obtained rotate the temperature control from 1 to 10 and back again several times to release any trapped air from within the unit Once the flushing out has been completed stop the water flow by pressing the STOP button Fit the sprayhead to the flexible hose and place in the sprayhead holder The shower is now ready for normal operation T100si OPERATING THE SHOWER Ensure the commissioning procedure has been carried out When the electricity supply to the shower is switched on at the isolating switch the POWER indicator will light To start the shower Water will flow by pressing any of the three buttons COLD ECONOMY or HIGH To stop the shower Press the STOP button and the phased shutdown will commence Water will cease to flow after approximately four seconds To use the control buttons There are three control buttons high cold and economy fig 37 The upper button red symbol sa high power setting which allows the highest flow achievable for your preferred temperature This setting should normally be regarded as optimum shower performance throughout the year Temperature adjustment at this setting is via the temperature control The centre button blue symbol is for cold water only A
2. Scottish and Northern Ireland Customer Service T 08457 626591 Trade Installer Hotline T 024 7632 5491 Fax 024 7632 4564 www tritonshowers co uk E mail technical triton plc uk
3. 4 4 2 2 Is water supply mains or tank fed 4 2 3 If tank fed re plumb to mains water supply or see 4 2 5 4 2 4 If mains fed ensure that mains stopvalve is fully open and that there are no other restrictions in the supply whilst shower is in use or see 4 2 5 4 2 5 Fit a pump to give minimum pressure contact Customer Service for advice 4 3 1 Switch to full power setting and re adjust the flow rate via the temperature control to give required temperature 4 4 1 Have unit checked by suitably qualified electrician or contact Customer Service FAULT FINDING continued Problem Symptom Cause Action cure 5 Shower varies 5 1 Water pressure has 5 1 1 Wait until the water pressure resumes to from normal dropped below minimum normal Low pressure indicator extinguishes temperature to cold required Indicator lit during use 6 Pressure relief 6 1 Blocked sprayhead 6 1 1 Clean sprayplate and then fit a new PRD device has operated water ejected from 6 2 Twisted blocked 6 2 1 Check for free passage through hose PRD tube flexible shower hose Replace hose if necessary and then fit new PRD 6 3 Sprayhead not 6 3 1 Fit new PRD Commission unit with removed whilst sprayhead removed commissioning Note Identify cause of operation before fitting new PRD unit When fitting a new PRD follow the commissioning procedure It is advised all electrical maintenance repairs to the shower should be carried out by a suit
4. holder assembly The screw inside the slider holder is now accessible Slider holder assembly With an appropriate screw driver tighten the screw fig 33 Re assemble in the reverse order Fig 34 Temperature control at minimum flow setting O power Fig 35 low pressure Temperature control at maximum flow setting COMMISSIONING The first operation of the shower is intended to flush out any remaining unit debris and to ensure the heater unit contains water before the elements are switched on This operation must be carried out with the flexible hose screwed to the outlet but without the sprayhead attached The COLD position must be used Ensure the outlet of the flexible hose is directed to waste Before turning on the electric and mains water supplies to the shower ensure that the temperature control is rotated fully clockwise to 10 the minimum flow position fig 34 NOTE Failure to turn the control to 10 may cause the PRD to operate Turn on the water supply to the shower at the isolating stopvalve and then switch on the electricity supply to the shower at the isolating switch The POWER indicator will light WARNING Press the COLD button only fig 35 and wait until water starts to flow from the flexible hose Slowly rotate the temperature control fully anti clockwise to 1 the maximum flow position fig 36
5. the unit if the sprayhead or spray hose becomes damaged DO NOT restrict flow out of the shower by placing sprayhead in direct contact with your body DO NOT operate the shower if water ceases to flow during use or if water has entered inside the unit because of an incorrectly fitted cover 1 GENERAL 1 1 Isolate the electrical and water supplies before removing the cover 1 2 Read all of these instructions and retain them for later use 1 3 DO NOT take risks with plumbing or electrical equipment 1 4 Isolate electrical and water supplies BEFORE proceeding with the installation 1 5 The unit must be mounted onto the finished wall surface on top of the tiles DO NOT tile up to unit after fixing to wall 1 6 Contact Customer Service see back page if any of the following occur a If it is intended to operate the shower at pressures above the maximum or below the minimum stated b If the unit shows a distinct change in performance c If the shower is frozen 1 7 If it is intended to operate the shower in areas of hard water above 200 ppm temporary hardness a scale inhibitor may have to be fitted For advice on the Triton Scale Inhibitor contact Triton Customer Service 1 8 The sprayplate and cartridge must be cleaned regularly with descalent to remove scale and debris otherwise restrictions to the flow on the outlet of the unit will result in higher temperatures and could also cause the Pressure Relief Device in unit to ope
6. 0mA residual current device RCD should be installed in all UK electric and pumped shower circuits This may be part of the consumer unit or a separate unit 3 7 Switch off immediately at isolating switch if water ceases to flow during use 3 8 Other electrical equipment i e extractor fans pumps must not be connected to the circuits within the unit 3 9 Switch off at isolating switch when not in use This is a safety procedure recommended with all electrical appliances 3 10 As with all electrical appliances it is recommended to have the shower and installation checked at least every two years by a competent electrician to ensure there is no deterioration due to age and usage T100si INTRODUCTION This book contains all the necessary fitting and operating instructions for your Triton T100si electric shower Please read them carefully The shower installation must be carried out by a suitably qualified person and in the sequence of this instruction book Care taken during the installation will ensure a long trouble free life from your shower SPECIFICATIONS Electrical Nominal power rating at 240V 8 5kW 40A MCB rating 9 5kW 40A MCB rating Nominal power rating at 230V 7 8kW 40A MCB rating 8 7kW 40A MCB rating Water Inlet connection 15mm diameter Outlet connection 1 2 BSP male thread Entry Points Water bottom or back Cable top or back Materials Backpla
7. 10051 O power Low pressure indicator Selector a E mode indicators O Ma __ gt low pressure changes in ambient water temperature NOTE The preferred number on economy will give a different temperature to the same number position on high To decrease the shower temperature Turn the temperature control anti clockwise this will increase the flow of water through the shower and is indicated by lower numbers To increase the shower temperature Turn the temperature control clockwise this will decrease the flow of water through the shower and is indicated by higher numbers NOTE It is advisable to be certain that the showering temperature is satisfactory by testing with your hand before stepping under the sprayhead There will always be a time delay of ten to fifteen seconds between selecting a flow rate and the water reaching the stable temperature for that flow rate Caution It is recommended that persons who may have difficulty understanding or operating the shower controls should not be left unattended whilst showering Special consideration should be given to young children and the less able bodied WARNING After any servicing of mains water supply always ensure the unit is started on COLD in order to purge any air in the pipework OPERATING FUNCTIONS Power on indicator fig 38 When the electricity supply to the shower is switched on at the isolating switch the P
8. 7 Power PCB 8 Stabilising valve 9 Solenoid valve 10 Guide pockets 11 Can and element assembly 12 Thermal cut out main 13 Earth connection 14 Outlet temperature limiter inside cover fig 2 16 Cover tags 17 Control PCB Pack contents Shower unit Four position sprayhead Riser rail kit and fittings Soap dish Flexible hose Screw fixing kit Instructions guarantee etc T100si ELECTRICAL REQUIREMENTS WARNING THIS APPLIANCE MUST BE EARTHED The installation supply cable and circuit protection must conform with IEE wiring regulations and be sufficient for the amperage required The following notes are for guidance only 1 The shower must only be connected to a 230 240V ac supply If you are installing a shower with a kilowatt rating above 9kW it is advisable to contact the local electricity supply company 1 1 The electrical rating of the shower is shown on the rating label fig 3 within the unit a ae 4 1 If your consumer unit has a rating below A 80A or if there is no spare fuse way then the Nuneaton Warks installation will not be straight forward and may CV 4NR i E e MODELA Se require a new consumer unit serving the house or E just the shower 230 240V ru IPX4 J a MAX PRESSURE Approved 4 2 You will need to contact the local electricity IERECSIES company They will check the circu
9. OWER indicator will light Low pressure indicator fig 38 If this indicator lights this means the water pressure has fallen below the minimum required for correct operation of the shower resulting in the low pressure cut out operating This switches off power to the heating elements preventing any maintained temperature rises water will continue to flow Power will automatically be restored when adequate water pressure returns Selector mode indicators fig 38 Adjacent to each control button there is an indicator that lights when the button is pressed visually indicating which shower mode is in operation PEZ TI ON Phased shutdown In use when the stop button is pressed power is switched off to the elements Water will continue to flow for a few seconds flushing out any remaining hot water This ensures the next immediate user will not receive a slug of hot water if standing under the sprayhead when starting the shower Temperature limiter During normal operation if an overheat temperature is sensed power to the elements will be reduced Water will continue to flow When the temperature has cooled sufficiently power to the elements will be automatically restored to the previous setting at the time of interruption Safety cut out The unit is fitted with a non re settable thermal cut out safety device In the event of abnormal operation which could cause unsafe temperatures within the unit the device will dis
10. THE RISER RAIL WARNING Check there are no hidden cables or pipes before drilling holes for wall plugs Use great care when using power tools near water The use of a residual current device RCD is recommended Lever Slider holder assembly j pa thin end Tapered Decide the position for the rail on the wall within the shower area Proceed as follows A Offer one of the two brackets to the wall for the lower position only Note there are three holes in the brackets but two screws will usually be sufficient However the centre hole must be used so mark this and either of the other two Drill and plug the wall The wallplugs provided are suitable for most brick walls use an appropriate masonry drill but if the wall is plasterboard or a soft building block you must use special wallplugs and an appropriate drill obtainable from most hardware stores Replace the bracket to the wall and secure to the wall with the screws supplied fig 18 Locate the rail onto this lower bracket ensuring the rail engages fully on the bracket Ensure the indent in the riser rail engages into the cut out on the bracket end fig 19 B Locate the second bracket on top of the rail Again mark the centre hole plus one of the other two holes Ensure the rail is vertical Remove the bracket and rail Drill and plug the wall C With the saddle spacer and lever parts to hand scre
11. TRITON eae e A T1005 electric shower QA a aah Mt A D TRITON 7100si Installation and Operating Instructions INSTALLERS PLEASE NOTE THESE INSTRUCTIONS ARE TO BE LEFT WITH THE USER 2180223G Jan 2002 CONTENTS Page Important safety information 1 Introduction 2 Advice to users 2 Key to main components 3 Electrical requirements 4 5 Water requirements 6 Siting of the shower 6 7 Fixing the shower to the wall 8 Plumbing connections 9 Electrical connections 10 Replacing the cover 11 Fitting the riser rail 12 Fitting the hose and sprayhead 13 Commissioning 14 Operating the shower 15 16 Operating functions 16 17 Adjusting the sprayhead 17 Cleaning 18 Cleaning the filter 19 Temperature flow rate graph 19 Spare parts 20 21 Fault finding 22 23 Guarantee service policy etc rear cover To ensure the product suitability for commercial and multiple installations please contact Triton s specification advisory service prior to installation Telephone 024 7632 5491 Facsimile 024 7632 4564 E mail technical triton plc uk T100si PLEASE READ THIS IMPORTANT SAFETY INFORMATION Products manufactured by Triton are safe and without risk provided they are installed used and maintained in good working order in accordance with our instructions and recommendations DO NOT operate shower if frozen or suspected of being frozen It must thaw out before using DO NOT operate
12. ably qualified person T100si UKAS QUALITY MANAGEMENT AMOrRCHROS Company TRITON STANDARD GUARANTEE Triton Plc guarantee this product against all mechanical and electrical defects arising from faulty workmanship or materials for a period of two years for domestic use only from the date of purchase provided that it has been installed by a competent person in full accordance with the fitting instructions Any part found to be defective during this guarantee period we undertake to repair or replace at our option without charge so long as it has been properly maintained and operated in accordance with the operating instructions and has not been subject to misuse or damage This product must not be taken apart modified or repaired except by a person authorised by Triton Plc This guarantee applies only to products installed within the United Kingdom and does not apply to products used commercially This guarantee does not affect your statutory rights What is not covered 1 Breakdown due to a use other than domestic use by you or your resident family b wilful act or Service Policy In the event of a complaint occurring the procedure should be followed 1 Telephone Customer Service on 024 7637 2222 08457 626591 in Scotland and in Northern Ireland having available the model number and power rating of the product together with the date of purchase 2 Triton Customer Service will be able to confirm wh
13. ble of at least 4mm cross sectional area These parts include metal baths radiators water pipes taps and waste fittings 6 For close circuit protection DO NOT use a rewireable fuse Instead use a suitably rated miniature circuit breaker MCB or cartridge fuse see table A 6 1 In the interest of electrical safety a 30mA residual current device RCD should be installed in all UK electric and pumped shower circuits This may be part of the consumer unit or a separate unit 7 A 45 amp double pole isolating switch with a minimum contact gap of 3mm in both poles must be incorporated in the circuit 7 1 It must have a mechanical indicator showing when the switch is in the OFF position and the wiring must be connected to the switch without the use of a plug or socket outlet 7 2 The switch must be accessible and clearly identifiable but out of reach of a person using a fixed bath or shower except for the cord of a Table B r N Twin and earth PVC insulated cable CURRENT CARRYING CAPACITY clipped direct or installed inan in conduit buried in a non insulated wall or trunking insulated wall 6mm 6mm 6mm 32A 38A 46A 10mm 10mm 10mm 43A 52A 63A 16mm 16mm 16mm 57A 69A 85A Note Cable selection is dependent on de rating factors cord operated switch and should be placed so that it is not possible to touch the switch body while standing in a bath or shower cubicle It should be readily access
14. connect the heating elements It will require a visit from a qualified engineer to determine the nature of the fault and replace the safety device once the unit has been repaired ADJUSTING THE SPRAYHEAD Four sprayhead patterns are available fig 39 Adjustment is by turning the bezel on the sprayhead in either direction until the desired pattern is obtained MAXI A full spray perfect for a relaxing shower ULTRA A focused spray for a refreshing satisfying shower NEEDLE A tingling fine spray for a highly invigorating shower JET A concentrated spray for an exhilarating shower l h W pi dit jing CMS ULTRA NEEDLE T100si WARNING Do not use powerful abrasive or solvent cleaning fluids when cleaning the shower as they may damage the plastic fittings CLEANING Do not use abrasive or solvent cleaning fluids The shower unit riser rail hose etc should be cleaned using a soft cloth and warm water It is advised before cleaning to turn the isolation switch off thus avoiding the shower being accidentally switched on IT IS IMPORTANT TO KEEP THE SPRAYHEAD CLEAN TO MAINTAIN THE PERFORMANCE OF THE SHOWER The hardness of the water will determine the frequency of cleaning For example if the shower is used every day in a very hard water area it may be necessary to clean the sprayhead on a weekly basis Sprayplat
15. djustment of the temperature control at this setting will only increase or decrease the force of the water from the sprayhead t will not alter the water temperature The lower button red symbol is an economy setting for using less power when the ambient mains water temperature is high during hot months Temperature adjustment at this setting is via the temperature control NOTE If the stated flow rate required for the unit cannot be met due to low water pressure it will be necessary to operate the unit on this setting during the warmer months because of flow rate limitations entering the unit To adjust the shower temperature The water temperature is altered by increasing or decreasing the flow rate of the water through the shower via the temperature control fig 37 After obtaining your preferred showering temperature the number can be remembered and left as the normal setting and should only need to be altered to compensate for seasonal gt A ON Fig 37 Stop Stop ae Bes button Nao TRITON 7100s1 power low pressure High N e Py G Cold my z gt Economy Temperature control NOTE IN NORMAL USE IT IS IN ORDER TO LEAVE THE WATER SUPPLY PERMANENTLY ON TO THE SHOWER UNIT BUT AS WITH MOST ELECTRICAL APPLIANCES THE UNIT MUST BE SWITCHED OFF AT THE ISOLATING SWITCH WHEN NOT IN USE T100si Fig 38 stop a Power on TRITON indicator T
16. e removal There is no need to remove the sprayhead from the hose Using the removal tool supplied fig 40 locate the three raised bosses into the three recesses in the sprayplate Hold in firmly and twist anti clockwise fig 41 This movement may turn the cartridge assembly as well until it reaches a stop Hold the cartridge firmly and continue to twist anti clockwise Having loosened the sprayplate sufficiently it can be unscrewed and removed completely fig 42 Clean the sprayplate with a suitable brush or preferably leave it to soak overnight in a mild proprietary descalent Ensure all traces of scale are removed and thoroughly rinse in clean water afterwards Before replacing the sprayplate switch the power back on at the isolating switch and direct the hose and sprayhead to waste Turn the temperature control fully anti clockwise Press the COLD button This operation will flush out any loose scale deposits in the unit and sprayhead Stop after approximately thirty seconds Refit the sprayplate by screwing clockwise Use the tool to screw the sprayplate tight CLEANING THE FILTER The inlet filter is situated in the inlet pipe which is part of the solenoid valve fig 43 To gain access to the filter will require the trimplate to be removed and disconnecting and removal of the compression fitting Also depending on the incoming pipework arrangements if there is not enough slack in the
17. e to terminal marked D Neutral cable to terminal marked N Live cable to terminal marked L IMPORTANT Fully tighten the terminal block screws and ensure that no cable insulation is trapped under the screws Loose connections can result in cable overheating NOTE The supply cable earth conductor must be sleeved The outer sheath of the supply cable must be stripped back to the minimum NOTE The elements on UK models are to 240V specification and will give a lower kW S rating if the voltage supply is below 240V DNI Bl Fig 14 Y gt 1 Terminal block 7 Thermal cut out The supply cable must be secured either by 2 Earth post outlet routing through conduit or in trunking or by pl Paa PE BE UE corneas socket embedding in the wall in accordance with IEE 5 Solenoid valve 10 Element regulations 6 Thermal cut out main 11 Control PCB The use of connections within the unit or other N points in the shower circuit to supply power to other equipment i e extractor fans pumps etc will invalidate the guarantee Terminal r ae i LO LI block DO NOT switch on the electricity supply until ES 41 the cover has been fitted ae O O l L N O cht e H a T100si REPLACING THE COVER Refit the trimplate and secure with the two screws Turn the stabiliser valve spindle fully clockwise until the arm
18. ether the fault can be rectified by either the provision of a replacement part or a site visit from a qualified Triton service engineer 3 If a service call is required it will be booked and the date of call confirmed In order to expedite your request please have your postcode available when booking a service call 4 It is essential that you or an appointed representative who must be a person of 18 years of age or more is present during the service engineer s visit and receipt of purchase is shown 5 A charge will be made in the event of an aborted service call by you but not by us or where a call under the terms of guarantee has been booked and he failure is not product related i e scaling and urring incorrect water pressure pressure relief device operation electrical installation faults 6 If the product is no longer covered by the guarantee a charge will be made for the site visit and or any parts supplied 7 Service charges are based on the account being settled when work is complete the engineer will then request payment for the invoice If this is not made to he service engineer or settled within 10 working days a 10 administration charge will be added ollowing neglect c any malfunction resulting from the incorrect use or quality of electricity gas or water or incorrect setting of controls d faulty installation 2 Repair costs for damage caused by foreign objects or substances 3 Total loss of
19. g screws fig 7 and lift the cover from the backplate To facilitate the pipe and cable connections remove the two screws fig 8 and take off the trimplate Entry positions for the mains water are from the bottom or from the rear Cable entry is via the top or rear NOTE Deviations from the designated entry points will invalidate product approvals If bottom surface entry is required for the mains cold water then the necessary aperture will need to be cut out in the trimplate and cover fig 9 If surface cable entry from the top is required then a small area will need to be cut out in the backplate fig 10 If installing a feed pipe from the rear or bottom the centre of the inlet valve to the wall surface is 20mm fig 11 NOTE If entry is from the rear the nut of the compression fitting will be partially behind the surface of the wall fig 11 This area MUST be left clear when plastering over the pipework in order to make the nut accessible for future adjustments After choosing the site for the shower use the backplate as a template and mark the two fixing holes fig 12 Drill and plug to suit the fixing screws supplied The wallplugs provided are suitable for most brick walls use an appropriate masonry drill but if the View from underneath wall is plasterboard or a soft building block you must use special wallplugs and an appropriate drill
20. g ring in compliance with Water Regulations Screw the flexible hose to the shower outlet and sprayhead fig 30 ensuring the supplied washers are in place at both ends of the flexible hose Place the sprayhead into the holder fig 31 and check that it fits correctly NOTE The holder is slightly tapered and the sprayhead and hose will only fit from one direction Important It is the conical end of the hose which grips into the holder The sprayhead will not fit in the holder without the hose attached However at this stage disconnect the sprayhead and lay aside until the shower unit has been Fig 30 commissioned Sprayhead TIGHTENING THE SPRAYHEAD Shower In the unlikely event of the sprayhead dropping down in use because the holder is loose this can be remedied by re tightening the screw inside the holder unit To gain access to this screw one of the wall mounting brackets must be removed the top one is preferable as the rail can be left in position on the lower bracket Washers First remove the sprayhead and hose from the holder Insert a small screw driver into the slot on he trim cover fig 32 and carefully prise off the cover Unscrew the fixing screws holding the bracket and remove it from the wall and rail Holding the rail unlock the lever and slide off the ever and holder assembly Remove the lever and saddle from the slider
21. hits the stop fig 15 Turn the temperature control on the cover so that it points to 10 fig 16 Important Before finally fitting the cover the following steps must be taken a Check plumbing connections for water tightness b Check terminal block screws are fully tightened c Check the temperature control on the cover is pointing to 10 d Ensure pipe and cable entering the unit do not prevent the cover locating correctly to the backplate Offer the cover to the unit Attached to the control PCB inside the cover is a ten way ribbon cable The ribbon cable connector must be plugged into the socket located at the top right of the power PCB situated inside the unit fig 17 The connector can only be correctly plugged in one way The ribbon cable also has a coloured edge which is to the left when correctly fitted to the socket NOTE The ribbon cable is pre formed to fold flat when the cover is fitted Carefully locate the cover tags into the guide pockets on the backplate and ensure wires are not trapped Guide into position so that the knob spindle locates correctly minor adjustment may be necessary to align the knob and spindle Should any difficulty arise re check the points above Whilst applying slight pressure to the front cover secure in position with the three retaining screws Coloured FITTING
22. ible to switch off after using the shower 8 Where shower cubicles are located in any rooms other than bathrooms all socket outlets in those rooms must be protected by a 30mA RCD 9 The current carrying capacity of the cable must be at least that of the shower circuit protection see table B 9 1 To obtain full advantage of the power provided by the shower use the shortest cable route possible from the consumer unit to the shower 9 2 It is also necessary to satisfy the disconnection time and thermal constraints which mean that for any given combination of current demand voltage drop and cable size there is a maximum permissible circuit length 10 The shower circuit should be separated from other circuits by at least twice the diameter of the cable or conduit 10 1 The current rating will be reduced if the cabling is bunched with others surrounded by thermal loft or wall insulation or placed in areas where the ambient temperature is above 30 C Under these conditions de rating factors apply and it is necessary to select a larger cable size 10 2 In the majority of installations the cable will unavoidably be placed in one or more of the above conditions This being so it is strongly recommended to use a minimum of 10mm cabling throughout the shower installation 10 3 In any event it is essential that individual site conditions are assessed by a competent electrician in order to determine correct cable size and pe
23. it and carry out Fig 3 what is necessary They will also check the main ss i MODEL No 00000000 bonding SERIAL No 00000000 5 The earth continuity conductor of the 7 electrical installation must be effectively Fig 4 schematic of installation circui connected electrically to all exposed metal parts of other appliances and services in the room in panes which the shower is to be installed to conform to isolating switch current IEE regulations Table A Shower Reb unit i oN mer une CIRCUIT PROTECTION unit cartridge rating mcb fuse 7 0kW 30 32A 30A ae 7 5kW 32A 35A ined 8 0kW 40A 35A 20A or 100 supp 8 5kW 40A 45A 9 0kW 40A 45A 9 5kW 40 45A 45A 10 5kW 45A 45A Ne No y 2 Before making any sort of electrical connection within the installation ensure that no erminal is live If in any doubt switch off the whole installation at the consumer unit 3 The shower must be connected to its own independent electrical circuit IT MUST NOT be connected to a ring main spur socket outlet ighting circuit or cooker circuit 3 1 The electrical supply must be adequate for he loading of the unit and existing circuits 4 Check your consumer unit main fuse box has a main switch rating of 80A or above and that it has a spare fuse way which will take the fuse or mcb necessary for the shower fig 4 T100si ELECTRICAL REQUIREMENTS 5 1 All exposed metallic parts in the bathroom must be bonded together using a ca
24. jointing compounds on any pipe fittings for the installation SITING OF THE SHOWER WARNING The shower must not be positioned where it will be subjected to freezing conditions FOR EASE OF SERVICING THE UNIT MUST ALWAYS BE MOUNTED ON THE SURFACE OF TILED WALLS NEVER TILE UP TO THE UNIT Refer to figure 6 for the correct siting of the shower Position the unit where it will NOT be in direct contact with water from the sprayhead Position the shower unit vertically Allow sufficient room between the ceiling and the shower to access the cover top screws NOTE Water regulations require the sprayhead be constrained by a fixed or sliding attachment so that it can only discharge water at a point not less than 25mm above the spill over level of the relevant bath shower tray or other fixed appliance The use of the supplied soap dish will y in most cases meet this requirement butifthe pz gt sprayhead can be placed within a bath basin or Shower unit can shower tray then a double check valve or similar i Pe mounted either must be fitted in the supply pipework to prevent i i back flow Y i Pressure relief safety device a j A pressure relief device PRD is designed into the j j shower unit which complies with European standards The PRD provides a level of appliance RA protection should an excessive build up of i shower pressure occur within the shower eee DO NOT operate the showe
25. obtainable from most hardware stores fa Fig 9 Screw top fixing screw into position leaving the base of the screw head protruding 6mm 0 25in out from the wall remove Hook the backplate over the top screw and fit the Y bottom fixing screw into position 4 Do not fully tighten the screws at this stage as Z the fixing holes are elongated to allow for out of A square adjustment after the plumbing connections have been completed backplate T100si PLUMBING CONNECTIONS Plumbing to precede wiring WARNING The outlet of the shower acts as a vent and must NOT be connected to anything other than the hose and sprayhead supplied DO NOT use jointing compounds on any pipe fittings for the installation DO NOT use soldered fittings within the vicinity of the shower unit Compression fittings MUST be used to connect to the inlet of the shower Push on fittings must NOT be used as full engagement cannot be guaranteed NOTE An additional stopvalve complying with Water Regulations MUST be fitted in the mains water supply to the shower as an independent means of isolating the water supply should maintenance or servicing be necessary Important Before completing the connection of the water supply to the inlet of the shower flush out the pipework to remove all swarf and system debris This can be achieved by connecting a hose to the pipework and turning on the mains water supply long en
26. ough to clear the debris to waste Procedure Turn off water supply either at the mains stopvalve or the isolating stopvalve Connect the mains water supply to the inlet of the shower via 15mm copper stainless steel or plastic pipe using a 15mm x 15mm elbow compression fitting DO NOT use excessive force when making these connections Ensure the backplate is square on the wall and ighten the two retaining screws which hold it to he wall Turn on the mains water supply and check for eaks in the pipework connection to the shower NOTE At this stage no water can flow through he unit Va remove View from rear of backplate T100si G a ELECTRICAL CONNECTIONS Fig 13 SWITCH OFF THE ELECTRICITY SUPPLY Fig 13 shows a schematic wiring diagram The cable entry points are shown in figure 1 The cable can be surface clipped hidden or via 20mm conduit NOTE Conduit entry can only be from rear Route the cable into the shower unit and connect to the terminal block fig 14 as follows Earth cabl
27. pipework it could mean the removal of the unit from the wall When cleaning the wire mesh filter do not use a sharp object as it will cause damage It is preferable to use an old toothbrush or similar Centigrade Temperature flow rate graph 0 C ambient 8 5kW and 9 5kW units 50 Auto Reset Occurs 9 5kW 8 5kW Economy Flowrate litres minute T100si Ref Description Part No 1 4 mode sprayhead all chrome 22420120 Sprayhead holder 83306190 Brackets pr 83306160 Riser rail 7042409 Flexible hose chrome 22007500 Soap dish white 22008960 Cover assembly 85100100 Terminal block amp wires 82200280 Ref Description T100si Part No 9 Heater can assembly 10 11 12 13 14 15 16 17 8 5kW 9 5kW Thermal cut out PRD amp O ring Stabiliser valve assembly Outlet pipe assembly c w wires Solenoid valve assembly Trimplate Power PCB Control PCB Wire kit TCO shield 83304110 84500290 22009860 83301330 82600700 83304160 83304130 7051656 7072052 7072060 83306330 7052871 T100si FAULT FINDING IMPORTANT Switch OFF the electricity at the mains supply and remove the circuit fuse before removing the cover from the shower while attempting any fault finding inside the unit P
28. r with a damaged or kinked shower hose or a blocked sprayhead which can cause the PRD to operate When commissioning the sprayhead must be Height of sprayhead H Mains cold water supply bottom Soap dish and back only H retaining 1 ring H removed from the flexible hose while at the same a E L time the temperature control must be at the Sesh J e minimum flow position Failure to follow this 25mm minimum must not procedure may also cause the PRD to operate AA e tot 3 de Spillover y l 1 metre Ensure the shower is positioned over a bath or level jii j from base shower tray because if the PRD operates then a e ita l pe water will eject from the bottom of the unit ies Se LLL Should this happen turn off the electricity and CT l water supplies to the shower at the isolating i switch and stopvalve Contact Customer Service s _Fig 6 for advice on replacing the PRD Diagrammatic view not to scale Important The unit must be mounted on a flat surface which covers the full width and length of the backplate It is important that the wall surface is flat otherwise difficulty may be encountered when fitting the cover and subsequent operation of the unit may be impaired T100si FITTING THE SHOWER TO THE WALL NOTE The control knob is an integral part of the cover do not attempt to remove it Unscrew the two top and one bottom retainin
29. rate 1 9 This product is not suitable for mounting into steam rooms or steam cubicles 2 PLUMBING 2 1 The plumbing installation must comply with Water Regulations Building Regulations or any particular regulations as specified by Local Water Company or Water Undertakers and should be in accordance with BS 6700 2 2 The supply pipe must be flushed to clear debris before connecting to the shower unit 2 3 DO NOT solder pipes or fittings within 300mm of the shower appliance as heat transfer can damage components 2 4 DO NOT fit any form of outlet flow control as the outlet acts as a vent for the heater can 2 5 DO NOT use excessive force when making connections to the flexible hose or sprayhead finger tightness is sufficient 2 6 All plumbing connections MUST be completed BEFORE making the electrical connections 3 ELECTRICAL 3 1 The installation must comply with BS 7671 Requirements for electrical installations IEE wiring regulations or any particular regulations as specified by the local Electrical Supply Company 3 2 This appliance MUST be earthed 3 3 In accordance with The Plugs and Sockets etc Safety Regulations 1994 this appliance is intended to be permanently connected to the fixed wiring of the electrical mains system 3 4 Ensure all electrical connections are tight to prevent overheating 3 5 Fuses do not give personal protection against electric shock 3 6 To enhance electrical safety a 3
30. rmissible circuit length Mains electric supply via double pole switch isolatin switc Shower unit Switch may Isolating be wall stopvalve _ mounted in accordance with IEE regs Diagrammatic view not to scale Separate permanently connected supply from consumer unit Fig 5 WATER REQUIREMENTS The installation must be in accordance with Water Regulations Byelaws To ensure activation of the heating elements the shower must be connected to a mains water supply with a minimum running pressure of 100 kPa 1 0 bar at a minimum flow rate of eight litres per minute for the 8 5kW rated model and nine litres per minute for the 9 5kW rated model For both units the maximum static pressure must be 1 000 kPa 10 bar NOTE If the stated flow rates are not available it may not be possible to achieve optimum performance from the unit throughout the year During periods of high ambient temperatures it may be necessary to select a low power setting to achieve your preferred shower temperature The water supply can be taken from a cold water storage cistern provided there is a minimum head of ten metres above the sprayhead It must be an independent supply to the shower only If it is intended to operate the shower at pressures above the maximum or below the minimum stated contact Customer Service for advice Fig 5 shows a typical system layout Do not use
31. roblem Symptom Cause Action cure 1 Shower 1 1 Interrupted power 1 1 1 Blown fuse or circuit breaker Check supply inoperable no supply Renew or reset fuse or circuit breaker If it fails water flow again consult a qualified electrician 1 2 Unit malfunction 1 1 2 Power cut Check other appliances and if necessary contact local Electricity Supply Co 1 2 1 Have unit checked Ring Customer Service 2 Water too hot 2 1 Not enough water flowing through the shower 2 2 Blockage in supply 2 3 Increase in ambient water temperature 2 1 1 Increase the flow rate via temperature control 2 1 2 Blocked sprayhead clean blocked sprayplate 2 2 1 Check if stop taps are fully open Check if blockage in inlet filter 2 3 1 Switch to economy power setting and re adjust flow rate to give required temperature 3 Water temperature cycling hot cool at intervals 3 1 Heater cycling on outlet temperature limiter 3 1 1 See Water too hot causes 2 1 2 2 and 2 3 and their appropriate action cures If it continues contact Customer Service 4 Water too cool or cold 4 1 Too much flow 4 2 Water pressure below minimum stated on rating label 4 3 Reduction in ambient water temperature 4 4 Electrical malfunction or safety cut out has operated 4 1 1 Reduce flow rate via temperature control 4 2 1 Check low pressure indicator If lit continue with remainder of checks If not lit see 4 1 amp 4
32. te cover controls sprayhead ABS Sprayplate Acetal Elements Minerally insulated corrosion resistant metal sheathing Dimensions Height 338mm Width 208mm Depth 95mm Standards and Approvals Splashproof rating IPX4 Complies with the requirements of current British and European safety standards for household and similar electrical appliances Complies with requirements of the British Electrotechnical Approvals Board BEAB Meets with Compliance with European Community Directives CE Due to continuous improvement and updating specification may be altered without prior notice Replacement parts can be ordered from Customer Service See spare parts for details and part numbers ADVICE TO USERS The following points will help you understand how the shower operates A The electric heating elements operate at a constant rate at your chosen power setting It is the flow rate of the water passing through the heater can which determines the water temperature at any given setting The slower the flow the hotter the water becomes and the faster the flow the cooler the water B During Winter the ambient mains water supply will be cooler than in Summer so to maintain your same showering temperature you will have to decrease the water flow The number displayed at the temperature control will therefore vary throughout the year as you adjust the position of the temperature control to maintain yo
33. the product due to non availability of parts 4 Compensation for loss of use of the product or consequential loss of any kind 5 Call out charges where no fault has been found with the appliance 6 The cost of repair or replacement of pressure relief devices sprayheads hoses riser rails and or wall brackets isolating switches electrical cable fuses and or circuit breakers or any other accessories installed at the same time 7 The cost of routine maintenance adjustments overhaul modifications or loss or damage arising therefrom including the cost of repairing damage breakdown malfunction caused by corrosion furring pipe scaling lime scale system debris or frost Replacement Parts Policy Availability It is the policy of Triton to maintain availability of parts for the current range of products for supply after the guarantee has expired Stocks of spare parts will be maintained for the duration of the product s manufacture and for a period of five years thereafter In the event of a spare part not being available a substitute part will be supplied Payment The following payment methods can be used to obtain spare parts 1 By post pre payment of pro forma invoice by cheque or money order 2 By telephone quoting credit card MasterCard or Visa details 3 By website order www tritonshowers co uk Triton Plc Shepperton Park Caldwell Road Nuneaton Warwickshire CV11 4NR Customer Service T 024 7637 2222
34. ur desired showering temperature C The stabiliser valve minimises variations in shower temperature during mains water pressure changes If changes in shower temperature are experienced during normal use it will most likely be caused by the water pressure falling near to or below the minimum level The drop in pressure may be due to water being drawn off at other points in the house whilst the shower is in use If pressure drops appreciably below the minimum the heating elements will automatically cut out If ever the water becomes too hot and you cannot obtain cooler water first check that the sprayplate in the sprayhead has not become blocked DO NOT place items such as soap or shampoo bottles on top of the unit Liquid could seep through the joint between the cover and backplate and possibly damage the sealing rubber Important When first installed the unit will be empty It is essential the unit should contain water before the elements are switched on As this unit has electronic control it is vital that the commissioning procedure is followed Failure to carry out this operation will result in damage to the unit and will invalidate the guarantee KEY TO MAIN COMPONENTS inside unit fig 1 1 Top cable entry 2 Bottom pipe entry 3 Rear pipe entry area 4 Rear cable entry area 5 Wall screw fixing 6 Terminal block
35. w the saddle two or three turns into the lever fig 20 Place the saddle and lever into the slider holder assembly fig 21 so that the holes align then slide onto the rail fig 22 Tighten to the rail by turning the lever When tight the lever should be facing forwards and not pointing to the wall If not slacken off and remove from the rail Rotate the saddle and lever 180 within the slider holder assembly then replace onto the rail and tighten Ensure the tapered thin end of the spray head holder is in the uppermost position D Place the rail onto the installed lower bracket Replace the upper bracket onto the rail and secure the bracket to the wall with the screws supplied fig 23 E Place a trim cover onto each bracket ensuring the large protrusion at the narrow end of the trim cover engages into the slot between the rail and T100si bracket fig 24 before pushing and clicking the foe other end into place fig 25 Fig 26 F Snap the soap dish onto the rail fig 26 below the holder assembly Prise open the soap dish collar and fit onto the rail fig 27 below the dish Note the collar is slightly tapered and should be fitted thinner section uppermost Ensure it locates firmly in the soap dish fig 28 so that it holds the dish at the required height on the rail FITTING THE HOSE AND SPRAYHEAD Feed the flexible hose through the appropriate soap dish aperture fig 29 in order that the dish acts as a retainin
Download Pdf Manuals
Related Search
Related Contents
Opmaak 1 - King Food for PETS Amana 1W10287572A User's Manual Manual Depresión de Flujo Neutrónico en las Barras Combustibles de UO チャイルドシートアセスメント Cap.18 mode emploi Fujitsu CELSIUS H920 Copyright © All rights reserved.
Failed to retrieve file