FIRECLASS, installation manual, doc. version 1.0, FC-A-BAC-CNF

image

Contents

1. network card Network Baud Rate use switches is the preferred setting Do not change configuration file configuration BACnet See Step 8 on Page 2 for details Network Wiring use switches is the preferred setting Do not change Style Segment Address Just displays the value etwork Ring Delay Setaccording to the Peer Limit values as shown in Table 2 etwork Peer Limit Maximum network node number including head end system etwork Idle Time Set according to the Peer Limit values as shown in Table 2 etwork Slot Time Set according to the Peer Limit values as shown in Table 2 etwork Reply Set to 25 Timeou etwork Reply Set to 3 Retry etwor Set to 3 Broadcast Repeat etwork No Token Set to 500 Timeou etwork Token Set to 52 Timeou PTP ACK timer Set to 3 Code The string created during installation If necessary re run the sh install command on the Moxa of the binary files in the Moxa device device to obtain the hardware ID string as described in the installation guide Generate Generates the file Please refer to the installation instructions PDF file FTP Send 2 Moxa button See Steps 9 and 10 on Page 2 Table 1 General tab details cont 6 10 Configuration information Doc version 1 0 FIRECLASS Fire detection system FIRECLASS BACnet converter Configuration Settings Det
2. 0 4 2 5 0 5 1 and 5 2 This setting must be the same as configured in FIRECLASS Express set to version 5 2 Database version Connector s node The revision number from FIRECLASS Express database The FIRECLASS N node number from the Site Details dialog in FIRE CLASS Express This number should be used to identify a change in the project data of FIRECLASS Express If the number here and in FIRECLASS Express are not the same then an update of the BACnet IF configuration is needed The XML file should be re exported from FIRECLASS Express then read again using the Update button This setting must be the same as configured in FIRECLASS Express in the FIRECLASS network Master Node Supervising control panel of the FIRECLASS network As set in the Site Details dialog in FIRECLASS Express Card Type Select TLI8OOEN Please update the TLI8OOEN firmware to 1 1 and configure the last value Older TLI8OO and TLISOOEN with old firmware will need setting TLISOO EN 1 0 Time keeper The node number of the time keeper This is taken from the XML device list file and is not editable The BACnet IF control panel can be configured to be the time keeper in FIRECLASS Express Use logical address Fixed to no Refresh Refresh frequency in seconds of analogue values for FIRECLASS points such as temperature dirti ness and so on This is used if any analogue values are presented to BACn
3. 10 29 87 5 10 29 88 5 10 29 Table 2 Values for Peer Limit dependant PTP Parameters Configuration information Doc version 1 0 Table 2 Values for Peer Limit dependant PTP Parameters 7 10 Configuration Settings Details FIRECLASS Fire detection system FIRECLASS BACnet converter Table 2 Values for Peer Limit dependant PTP Parameters Peer Limit Idle Time Ring Slot Time Peer Limit Idle Time Ring Slot Time Delay Delay 89 5 11 31 97 6 11 31 90 6 11 31 98 6 12 33 91 6 11 31 99 6 12 33 92 6 11 31 Table 2 Values for Peer Limit dependant PTP Parameters 93 6 1 31 94 6 11 31 Panels tab Settings 95 6 11 31 This tab lists all panels which have been configured and imported from FIRECLASS Express 96 6 1 31 The following columns are provided Column Comments Panel node Panel number Address of panel in FIRECLASS Network State BACnet address of state of panel It can be normal or alarm It also provides flags about fault and isolation deisolation If present then state will be presented to BACnet Silence Sounders On Off Evacuate BACnet address of silence resound info It shows that sounders are silenced or not This BACnet address accepts com mands and allows to silence resound panel BACnet address of info about sounders switched off It is NOT information abo
4. ECLASS Express export to FCG For details refer to the FIRECLASS Express help You specify a path and name for an export file Place this in a suitable project folder The file will contain configu ration details of the FIRECLASS fire alarm system such as the zones and points 4 Locate the BACnet Converter installation PC On this PC navigate to the following BACnet Configurator executa ble and open it this is the path suggested in the instal lation guide C Program Files FIRECLASS BACnet_x_yy BACnet Con figurator exe 5 To start anew BACnet configuration skip to Step 6 Or you might want to update an existing saved configu ration ina BNP file To do this use File gt Open navi gate to the BNP file and open it Now go to the General tab and click Update Then nav igate to the exported XML file and open it you might need to copy this file across from the FIRECLASS Express PC The configuration settings from the XML file are now compared to the existing BACnet configuration set tings Any changes between the two are merged as fol lows If loop points have been set to Empty in the XML file they will be deleted from the BACnet IF configura tion f loop points or zones have been added in the XML file they will be inserted into the lists and their BAC net ID will be initialized with none 6 Tostartanew BACnet configuration switch to the Gen eral tab and click Load Now navigate to the exporte
5. FIRECLASS Fire detection system FIRECLASS BACnet converter FIRECLASS BACnet converter FIRECLASS BACnet converter Oy No 557 202 135 UC 7101 Ready Universal Communicator Fig 1 UC 7107 computer This guide leads you through the process of creating and implementing configurations for the FIRECLASS BACnet Interface This must always be carried out as follows As part of anew FIRECLASS BACnet interface installa tion After the BACnet Converter Moxa device firmware has been updated When there is a new issue of the BACnet Configurator program see below This will automatically make corrections for example to the BACnet IDs in the various Value columns see below You must have first installed the FIRECLASS BACnet Inter face as described in the installation guide The installation guide also provides an introduction to the interface To create or update a configuration 1 Locate a PC running FIRECLASS Express It will be eas ier if this is the same PC used for the BACnet Converter installation Start FIRECLASS Express and open the project file PJQ containing the fire alarm control panel configu ration Check that the processing capacity of the Moxa inter face device will not be exceeded Each device can inter face around 2 000 points to BACnet These may be located on different panels For more points a second Moxa device is needed Configuration information Doc version 1 0 3 In FIR
6. SS points in total Dirtiness BACnet address of dirtiness read from Please note that not all points provides this kind of data detector HINT It is not allowed to configure to retrieve values from more than 100 FIRECLASS points in total Description Description of point primary language Taken from FIRECLASS Express It ll be replaced during upgrade Table 5 Points tab details FIRECLASS Hillcrest Business Park Dudley West Midlands DY2 9AP UK www fireclass co uk FI R E LASS FC A BAC CNF doc version 1 0 26 March 2013 Subject to change without notice
7. This section provides information on making the settings in the various tabs of the BACnet Configurator This section just explains the variously possibilities which are available in the BACnet IF Configurator Please refer further down where every tab is described in detail The settings must be written into the BACnet project BNP file This stores the settings for future use In addition this file must be present before the configuration can be trans ferred to the Moxa device see above Panels Zones and Point Tabs Initially no FIRECLASS points will be interfaced to BACnet so the columns of the tabs will contain the following none where the associated device can provide ana logue values where the device does not provide an analogue value only a state You need to interface the required points as described below not all points will necessarily need to be interfaced The procedure is the same for all tabs To interface an FIRECLASS point 1 From the row and column headings decide on a cell you want to interface to BACnet This will be a cell con taining none Alternatively you can select a range of cells rather than a single cell For details see the section below 2 Right click on the none entry This will replace none with the BACnet ID Right click again if you want to switch back to none Configuration information Doc version 1 0 FIRECLASS Fire detection system FIRECLASS BACn
8. ails Hidden settings Note that there is a section in the GUI for making PTP settings This section is normally hidden but becomes visible when loading an FIRE CLASS Express project where a TLIBOOEN net work card is used The names of the PTP param eters are the same as used In FIRECLASS Express the same settings must be made as in FIRECLASS Express otherwise incorrect opera tion of the entire networked system could result Peer Limit Table 2 lists the values for Peer Limit Peer Limit Idle Time Ring Slot Time Delay 1 26 3 3 16 27 3 4 17 28 3 4 17 29 3 4 17 30 3 4 17 31 3 4 17 32 3 4 17 33 3 4 17 34 3 4 17 35 3 4 17 36 3 5 19 37 3 5 19 38 3 5 19 39 3 5 19 40 3 5 19 41 3 5 19 42 3 5 19 43 3 5 19 44 3 5 19 45 3 6 21 46 3 6 21 47 3 6 21 48 3 6 21 49 3 6 21 50 3 6 21 51 3 6 21 Peer Limit Idle Time Ring Slot Time Delay 52 3 6 21 53 3 6 21 54 4 7 23 55 4 7 23 56 4 7 23 57 4 7 23 58 4 7 23 59 4 7 23 60 4 7 23 61 4 7 23 62 4 7 23 63 4 8 25 64 4 8 25 65 4 8 25 66 4 8 25 67 4 8 25 68 4 8 25 69 4 8 25 70 4 8 25 71 4 8 25 72 5 9 27 73 5 9 27 74 5 9 27 75 5 9 27 76 5 9 27 77 5 9 27 78 5 9 27 79 5 9 27 80 5 9 27 81 5 10 29 82 5 10 29 83 5 10 29 84 5 10 29 85 5 10 29 86 5
9. ails FIRECLASS Fire detection system FIRECLASS BACnet converter Points tab Settings This tab lists all points which are imported from FIRECLASS Express The following columns are provided Column Meaning Comments Panel node Panel number of point Human The physical point address in a human Address readable format Ch Channel address of the point A O value relates to a point on the main board that is a loop or XBUS point A 1 value relates to an RBUS point ChA If Channel is O the items this relates to are as follows O XBUS 1 loop A 2 loop B 3 loop C and so on If Channel is 1 then this relates to an RBUS address Cat For loop points this is always O Real For XBUS points this is 2 Pt Point address Type The type of the device Zone Point zone State BACnet address of state of given point It If present then state will be presented to BACnet accepts commands and allows to iso late out of service and de isolate point It also provides flags for fault Value 1 BACnet address of analogue value read Please note that not every FIRECLASS panel provides this Value2 from given point If unit is provided by kind of data FC460PH provides value 1 and value2 Value3 FIRECLASS panels then it ll be properly FC420CP none of them set on BACnet HINT It is not allowed to configure to retrieve values from more than 100 FIRECLA
10. d XML file and open it 7 Make your BACnet Converter configuration settings For details see the section Making the Settings below 8 Use File gt Save or File gt Save As to save toa BNP file of your choice To copy the configuration to the Moxa device 1 Connect the BACnet configuration PC to the Moxa device using the crossover Ethernet cable supplied with the device 2 Open a Command Prompt window Start menu gt All Programs P Accessories gt Command Prompt Enter the command telnet 192 168 3 127 where 192 168 3 127 is the IP address of the Moxa device Use the new address if you have changed this 1 10 Making the Settings FIRECLASS Fire detection system FIRECLASS BACnet converter If you are asked for a username skip to Step 5 Or the connection may fail In this case your PC probably has incompatible IP settings so carry on at the next step this provides an example method of how to connect with the default Moxa device IP settings 3 Onthe PC go to the Local Area Connection settings Internet Protocol TCP IP Properties Note the setting for IP address so you can return to it later Then set this to 192 168 3 1 Note the setting for Subnet mask so you can return to it later Then set this to 255 255 255 0 Repeat the telnet 192 168 3 127 command 5 After a successful connection of the telnet command enter the username of root At the password promp
11. et This value must be at least 300 seconds Please take into account that every FIRECLASS panel is able to answer 2 5 requests per second So this Refresh value should be greater than number of points 2 5 Eventlog Server EVs since Reset This is experimental Please do not tick this Table 1 General tab details 4 10 Configuration information Doc version 1 0 FIRECLASS Fire detection system FIRECLASS BACnet converter Configuration Settings Details Control Comments Serial Port Name Device name of the serial port inside Do not change this the Moxa device Default value dev ttyMO Baud rate TLISOOEN supports all offered val The baud rate must be the same as configured by dip ues Please use the highest baudrate switches on the TLIBOOEN card which does not cause communica tion faults seen in the log console Data Bits Not editable Parity Not editable Stop Bits Not editable BACnet BACnet ID BACnet ID of FIRECLASS converter Set any unique value According to BACnet specification it Must be unique across the whole can be up to 4194303 BACnet network However normally this value does not need be to be changed Network BACnet network of FIRECLASS Set any unique value According to BACnet specification it converter Must be unique in whole can be up to 65535 Normally this value does not need be BACnet networks changed Res
12. et converter Configuration Settings Details Multiple Selection As mentioned in Step 1 of the procedure To interface an FIRECLASS point you can make multiple selections To do this you can use the following methods Click to select a cell then shift click on another cell All the cells between the two will be selected Click on a cell then Ctrl click on any other additional cells you want to select Click on the fist column in one row to select all the cells in the row Ctrl click on any additional row or cells you want to select Click on the column header to select all the cells in the column Ctrl click on any additional columns or cells you want to select A click on a header will sort the column Depending on the content of the column the sorting will be either a numerical or an alphanumerical order A second click on the header will reverse the order Configuration Settings Details The sections below provide details information on each of the Configurator settings Configuration information Doc version 1 0 Project Details tab Settings Project Name display the FIRECLASS Express project name Project Description allows a customer to add comments and hints about this BACnet project as free and unformat ted text It is pre filled with the FIRECLASS Express revision number when the xml export file has been loaded or updated Template Language is used to define the control group numbers for some commands E
13. ither set it to English or German In this case fixed control group numbers will be used in the BACnet IF The third setting manual allows to choose other control group numbers than normally used in FIRECLASS Express General tab Settings This tab takes all relevant settings of this BACnet project Danger of corruption There is a danger of corrupting the FIRECLASS network To avoid this be careful when making the Gen eral tab settings and make sure they corre spond to the project configuration 3 10 Configuration Settings Details FIRECLASS Fire detection system FIRECLASS BACnet converter Control Comments Project File Exported XML file The path and file name of the FIRECLASS Express exported XML file Create the XML file in FIRECLASS Express by exporting to FCG See the FIRECLASS Express help file for details Load button Loads information from the FIRECLASS Express export file Used when creating a new BACnet IF configuration Update button Updates with information from the FIRECLASS Express export file Except the correction of device types that do not provide all Value 1 2 and 3 or Dirtiness values see the sec tion Points tab Settings on page 10 BACnet ID references are not affected and remain the same Protocol Configuration Protocol version Supported by the BACnet interface are the Protocol versions 3
14. t also enter root the password does not appear as you type 6 Enter the command sequence cd home sh install Take care to enter the sequence exactly as shown the characters are important As a shortcut you could copy and paste the text above using right click menu options 7 Note the reported hardware ID string for the next step Then enter the telnet command exit 8 Switch back to the BACnet Configurator and go to the General tab Enter the hardware ID string into the Code box Subsequently click on Generate configuration file and specify a suitable project folder for the file for example the BACnet installation folder The file is saved as configuration BACnet If you encounter an error it is probably because you had forgotten to insert the hardware ID string see Step 7 9 Inthe BACnet Configurator General tab click on the Send 2 Moxa button This will transfer the con figuration to the Moxa device with the same IP address as configured under General Tab gt IP Addr The default IP address of the Moxa device is 192 168 3 127 2 10 10 To repeat the transfer of the configuration navigate to the project directory and run the new Windows shell file Send2Moxa_ProjectName bat 11 Reboot the Moxa device power down and up again 12 The software installation is complete Ensure that you revert to the original IP Settings if changed Making the Settings
15. tart This password enables warm Please change the default password resetting of the FIRECLASS system network Time offset to UTC FIRECLASS converter time offset in minutes to GMT Values lt O means east direction i e Europe Asia val ues gt O means west i e Americas BACnet APDU APDU Timeout The time when an APDU will time Only change this value when instructed by support out Segment The time when an APDU segment Only change this value when instructed by support Timeout will time out APDU Retries The number of repeats when an APDU must be re sent Only change this value when instructed by support Table 1 General tab details cont Configuration information Doc version 1 0 5 10 Configuration Settings Details FIRECLASS Fire detection system FIRECLASS BACnet converter Configuration can be edited Control Meaning Comments IP Network Manual If ticked then the following settings Both the converter and connector functions normally run on the same Moxa device For large systems these functions can be split and run on separate Moxa devices Converter IP IP address of the Moxa device Default localhost Converter Port UDP port of the Moxa device Connector IP IP address FIRECLASS Connector Default localhost Connector Port UDP port of FIRECLASS Connector PTP parameters for TLI Only visible when using a TLI8OO EN
16. ut sounding or not This BACnet address is accepts commands and allows to switch off sounders or become sounders to ready BACnet address of info about evacuat ing panel the evacuation state It accepts commands It is NOT information of sounding or not It s info about readi ness to sounding or silenced sounders German based templates only In other templates this function is not used If present then the evacuation state will be presented to BACnet Description Description of panel Taken from FIRECLASS Express Table 3 Panels tab details 8 10 Configuration information Doc version 1 0 FIRECLASS Fire detection system FIRECLASS BACnet converter Configuration Settings Details Zones tab Settings This tab lists all zones which are imported from FIRECLASS Express The following columns are provided Panel node Panel number for given zone Zone ID Physical zone number State BACnet address of state of zone It can be normal or alarm It accepts com mands and allows to make isolation out of service or deisolation of zone It pro vides flags about fault in zone If present then state will be presented to BACnet Description Description of given zone It ll be replaced during upgrade Taken from FIRECLASS Express Table 4 Zones tab details Configuration information Doc version 1 0 9 10 Configuration Settings Det

Download Pdf Manuals

image

Related Search

Related Contents

Veranda FNS PKT G H 39 WC Installation Guide  Bedienungsanleitung Prenotool BVM 500  Fresh Air Globe Instructions  Manual de instrucciones - Grabador de red NVR IDIS  40回記念誌 - 東京黒百合会  IBM Ethernet / 8Gb FC CFFh  Les nouvelles recettes de Rémy Manuel d`utilisation  Equip 19" Patch Panel ISDN So, 25-Port, black  zum ca. 1,9MB    