Home

INSTALLATION MANUAL

image

Contents

1. ez siewApyded ns esonAyauiq zZ 2 LZ ebajsnyepnnw sooy 07 5 usa Z 6 npnjun n uou 5 mepibese ejnjn oy rseuiuejny e106 eziwuepewe ununun ez 5 apeins a nlen znod es ez npejyodpaud ez 1 1uA nounopajseu s apoyz ns pz wagio un uenrepuejs ulersofoxes shige uemunfipeou efejozed sojsiiqje el pey ez snu pounu hsnw je ed ejf pey eB jes ns snjuawnyop sniuruuou sn eque snuepuejs snApounu neiwsz exunne zz Winw dioni Jeseuouen 99 h ewaouo WLHAWANOL widetHelo eH 168101981040 ejeypueunf asyejeynsey piau ny eGepueuunyop ejstej Ion e j stuiGuef sesnnejsen uo Oz iuuiseu z npejys ofel qesodn as ep pod ur ipepuejs z IUpepys 6 ejunrjonujsur ejeyuuojuoo juoyeuun eyeyuuojuoo gL weloynsui 1u zseu 7 alpobz es suem zn ez weiyuniem pod uofuffoezieuuou wou y
2. 1 jo uae ep po sou e ses jueios spnb zuene nod S ewou 5 no 5 xne e e seujojuoo uos 60 uepem gewab als gep Jajun ueupeidsjueiuodsque uejueuunyop jueunopulov 1epo ue uuioN 20 suononusul Ino pasn Jey papinold 5 ennew ou Jayjo JO s piepuejs AIWOJUOD are Lo W81213810092 0 34H3l 8BVE 39 QVAINYOANO9 30 0Y VEV1930 39 A 8800X82 5I3 A 8800H82 5I3 A 8800X8O l3 A dH800HgO5I3 as OB eIejoap anb e sojueuredinbe so anb epepijiqesuodsai ealsnjoxe ens qos ejepep Ca 90 LomyLg 10130 ojouo Wangna dla lontoryxoLD ari BAMYUQ GD 20 euoizeJelupip vjsenb e imo e 1yooaredde 116 ayo eyiiqesuodsei elidoud ej opos CT 90 1 e eoe enb je anb esun ns ofeg E 60 Bunejyien doreem Jnnyesedde
3. 65 resistance Symptom 7 Space heating capacity shortage at low outdoor Recommended diameter inch 1 temperatures Refrigerant Type R410A POSSIBLE CAUSES CORRECTIVE ACTION Charge kg 17 Backup heater operation is not Check that the backup heater Expansion vessel activated operation status field setting 4 00 Volume 0 6 is turned on refer to the chapter 1 Field settings in the ln installation manual Maximum working pressure b 3 0 Check whether or not the thermal MWP bar protector of the backup heater has Pump been activated refer to 5 2 Main components of the outdoor unit on Type water cooled page 6 Backup heater thermal No of speed 3 protector in the installation manual Nominal ESP of the EKMBUH for location of the reset button Cooling kPa 49 7 45 8 Check if booster heater and backup Heating kPa 472 34 0 heater are configured to operate simultaneously field setting 4 01 Sound level refer to the chapter Field settings in Sound power cooling dBA 63 63 the EKCB installation manual S sound ling 9 REY 48 50 Check whether or not the thermal aunel Eso Golling CES fuse of the backup heater is blown Sound power heating dBA 61 62 refer to 5 2 Main components of B the outdoor unit on 6 Backup Sauna Besse 982 48 28 heater thermal fuse in the Internal water volume 5 5 installation manual of the EKMBUH Pressure
4. 3P350991 1 lt gt 10 lt g gt sjueypo uoo y bua uoneuuoju 93 80 7002 Auquedwod 93 96 9002 wiseu s npejys n asoy es ep zalan zn rr eui uopaepuegs es npes n umueunyop WIUAEWOU oqeu wjolnpajseu fepinodpo AUAyod s npejnos ugarzn n nos ez npepyodpaid ez o uegjey ey Je e Bulujessmioy Japun apuan u ou eupue 1 paw 19 1 nsestoynui u Bye eisynumgee uenjueunwop ef uelprepuejs uelneeinas Jeneeisen L 1A n S NI essip ennyedsai Z Jeuonynijsu eA es Ne urupe lepun jeje epuefoj yoo Je ennyedsei p Jesynisu IOA pjoyuey essip je jespnuoj e jueumyop jeja 18 prepuejs epueboj Japjoylano QL INBUDI O WeLHAWAMOL Wwi dg weLdetieLo wmoi tauo 10
5. P DAIKIN altnerma INSTALLATION MANUAL Unit for air to water heat pump system EBHQO006BBV3 EBHQ008BBV3 15 0 00 9 00 1ee1sepioo pue7 AN NDIIVO OW3 VnO LGS0 vGz802 bv 08N vuxaa L0Z S0 913920 49 1 NIMIVO 196 yeJejo nuno uepujele lt g gt eio euisexynies lt gt 10 pied lt gt lt gt s epe ns A g QUAJSIZ auAmzod e lt y gt guapann ojoq oye 2 nyeyuries Je e eyses welennizod lt g gt 150 810 2 UN v ey lt gt byeyymes jebed lt g gt eys udsnu diey 11 y eyAyeysnu diey N SC pc EZ 2001824 zz lt g gt lt g gt 10 lt y gt 8 OH KOUEN OEM Z anjoadsal lweymesdod iu zsfeiuzod 2 11 7 se 0 ouefuefiuuzi ef oyey weujeld pl eumpejnnu eu UNY euiste jas elan yalg JAPY ZL peu relig LL eBuupuee 5 YA OL JepyeuneuoA ejfuejeu Siuunsibag ez luz wouejd A pz sounfeuipyided un
6. 10 3 Setting the pre pressure of the expansion vessel When it is required to change the default pre pressure of the expansion vessel 1 bar keep in mind the following guidelines Use only dry nitrogen to set the expansion vessel pre pressure E Inappropriate setting of the expansion vessel pre pressure will lead to malfunction of the system Therefore the pre pressure should only be adjusted by a licensed installer 10 4 Connecting the water circuit Water connections must be made in accordance with all applicable legislations and the outlook drawing delivered with the unit respecting the water in and outlet NOTICE Be careful not to deform the unit piping by using excessive force when connecting the piping If dirt gets in the water circuit problems may occur Therefore always take into account the following when connecting the water circuit Use clean pipes only the pipe end downwards when removing burrs Wi Cover the pipe end when inserting it through wall so that dust and dirt enter m Use a good thread sealant for the sealing of the connections The sealing must be able to withstand the pressures and temperatures of the system it must also be resistant to the used glycol in the water W When using non brass metallic piping make sure to insulate both materials from each other to prevent galvanic corrosion Because brass is a soft material use appropriate tooling for conn
7. 81002 8 60 WA 0 8 o WOO opiooe ep 80 0 3301010 AML Louda arl O c 190 1012 105819 0 9 90 ns dpayd jusnouejsn JU9ZIpop eZ ap seuoroisodsip sej cQ huieyejed hyeysonu snueyre zz ue ueDuijedeq ap BisuoyueeJe o po eH LZ 7 4 pjouueu M ZL sep xne 0 ejejenou JeAejse QZ ueyoy n ilua LL uap 20 ggojop nfuenejsodn qo 6 eu1esjeuiuejseq je esjebenber apun Q jo suoisno d ayy Buiwoj o L0 07 2 9EE09N3 yejejo euuejn oy ununq cz ejueAouejsn onfeAerzipo pz orl Saugo ToiApoonorhoUdX Uosgounodu ALL oun amrloinonoy ovp u o ouniocdu o ognovoxo 0 oi arl 10m3 20 je 10012181 asou pesn euo oped e e 0 ijone o s prepuejs iuuojuoo ouos 90 seuoponijsui SEASONU ep Sopezijin uees anb audwa s s oneuou 5 n s aquainBis s e uoo pepruuojuoo ue upisa 60 9200 ez ap eemioon uliz uejueuunoop
8. compartment that meets with your customer s approval The unit is designed to be installed in an outdoor location 5 2 110 11 12 1314 15 W The space around the unit is adequate for maintenance and la servicing refer to 7 2 Service space of the outdoor unit on page 9 The space around the unit allows for sufficient air circulation There must be sufficient space for air passage and no obstructions around the air intake and the air exhaust see Installing near a wall or obstacle on page 8 There must be sufficient space for carrying the unit into and out of the site There is no danger of fire due to leakage of inflammable gas The site must be free from the possibility of flammable gas leakage in a nearby place W The equipment is not intended for use in a potentially explosive atmosphere 1 Outdoor unit EBHO BBV3 Choose a place solid enough to bear the weight and vibration of 2 Backup heater EKMBUH 6V3 optionally the unit where the operation noise will not be amplified 3 Heatexchanger 4 Heatexchanger refrigerant side All piping lengths and distances have been taken into 5 Water outlet consideration 6 Water inlet 7 Refrigerant outlet 8 Refrigerant intlet Maximum allowable distance between the 9 Air purge valve domestic hot water tank and the outdoor unit 10 Shut off valve water accessory only for installations with a domestic hot 11 Drain and fill valve water tank installed The thermistor cable 10m 12 Pump
9. are compatible with the water used in the system and with the materials used in the unit Select piping diameter in relation to required water flow and available external static pressure ESP of the pump The recommended water piping diameter is 1 The minimum required water flow for the unit operation is 12 l min When the water flow is lower than this minimum value flow error H will be displayed and the operation of the unit will be stopped NOTICE It is strongly recommended to install an additional filter on the heating water circuit Especially to remove metallic particles from the field heating piping it is advised to use a magnetic or cyclone filter which can remove small particles Small particles can damage the unit and will not be removed by the standard filter of the heat pump unit 10 2 Checking the water volume and expansion vessel pre pressure The unit is equipped with an expansion vessel of 6 litre which has a default pre pressure of 1 bar To assure proper operation of the unit the pre pressure of the expansion vessel might need to be adjusted and the minimum and maximum water volume must be checked 1 Check that the total water volume in the installation excluding the internal water volume of the outdoor unit is 101 minimum Refer to Technical specifications on page 18 to know the internal water volume of the outdoor unit INFORMATION In most applications this minimum water volume wil
10. is at standstill inside the system freezing is very likely to happen and damaging the system in the process Piping insulation The complete water circuit inclusive all piping must be insulated to prevent condensation during cooling operation and reduction of the heating and cooling capacity as well as prevention of freezing of the outside water piping during winter time The thickness of the sealing materials must be at least 13 mm with 120 039 W mK in order to prevent freezing on the outside water piping If the temperature is higher than 30 C and the humidity is higher than RH 8096 then the thickness of the sealing materials should be at least 20 mm in order to avoid condensation on the surface of the sealing Water piping freezing prevention Protect the water piping against water freezing during the winter period e g by using an external field supplied heater tape or glycol solution 11 IMPORTANT INFORMATION REGARDING THE REFRIGERANT USED This product contains fluorinated greenhouse gases covered by the Kyoto Protocol Do not vent gases into the atmosphere Refrigerant type R410A value 1975 1 GWP global warming potential 12 ELECTRICAL WIRING WORK Refer to the installation manual of the EKCB indoor unit 13 START UP AND CONFIGURATION Refer to the installation manual of the EKCB indoor unit Installation manual 14 DAIKIN EBHQ006 008BBV3 Unit for air to water heat pump
11. relief valve prevents excessive water pressure in the water circuit 23 bar Installation manual DAIKIN EBHQ006 008BBV3 Unit for air to water heat pump system 4P347825 1A 2013 04 5 3 Main components of the outdoor unit switch box Terminal blocks The terminal blocks allow easy connection of field wiring Thermistor interconnection cable connector The electric wiring diagram can be found on the inside of the outdoor unit top panel 5 4 Functional diagram of outdoor hydraulic 6 SELECTING AN INSTALLATION LOCATION WARNING Be sure to provide for adequate measures in order to prevent that the EBHQ outdoor unit be used as a shelter by small animals Small animals making contact with electrical parts can cause malfunctions smoke or fire Please instruct the customer to keep the area around the EBHQ outdoor unit clean and clear CAUTION Appliance not accessible to the general public install it in a Secured area protected from easy access This unit is suitable for installation in a commercial and light industrial environment General precautions on outdoor installation location Refer to 2 General Safety precautions on page 2 Select an installation site that meets the following requirements and
12. to a drain pan in order to recover the glycol Connecting a drain pipe is not required if no glycol is used The discharged water is then drained via the bottom of the unit 10 5 Protecting the water circuit against freezing Frost can damage the unit As this unit is installed outdoors and thus the hydraulic system is exposed to freezing temperatures care must be taken to prevent freezing of the system All hydraulic parts are insulated to reduce heat loss Insulation must be foreseen on the field piping The unit is already equipped with several features to prevent freezing The software contains special functions using pump and back up heater optionally to protect the complete system against freezing However in case of power failure above mentioned features can This function will only be active when the unit is off not protect the unit from freezing If power failure can happen at times the unit is unattended Daikin recommends adding glycol to the water system Refer to Caution Corrosion of the system due to presence of glycol on page 13 Refer to 4 04 Freeze protection function in the EKCB installation manual Depending on the expected lowest outdoor temperature make sure the water system is filled with a weight concentration of glycol as mentioned in the table below Minimum outdoor temperature Glycol 5 10 10 C 15 15 C 20 20 C 25 25 C 30 CA
13. 18 Installation manual DAIKIN EBHQ006 008BBV3 Unit for air to water heat pump system 4P347825 1A 2013 04 4 ACCESSORIES 5 OVERVIEW OF UNIT 4 1 Location of the accessories 5 1 Opening of the outdoor unit Opening of the outdoor unit To gain access to the unit the service panels need to be opened as shown in the figure below 1 2 3 4 Ale 1 Installation manual 2 Operation manual 3 Shut off valve 2x 4 Wiring diagram sticker inside top unit cover 5 Cable Ties 15x For access to the terminals following panels have to be removed as shown in the figure below EBHQ006 008BBV3 DAIKIN Installation manual Unit for air to water heat pump system 5 4P347825 1A 2013 04 A WARNING Switch off all power supply i e outdoor unit power supply and backup heater and domestic hot water tank power supply if applicable before removing the switch box service panel outdoor unit and indoor unit mM Do not touch the refrigerant pipes during and immediately after operation as the refrigerant pipes may be hot or cold depending on the condition of the refrigerant flowing through the refrigerant piping compressor and other refrigerant cycle parts Your hands may suffer burns or frostbite if you touch the refrigerant pipes To avoid injury give the pipes time to return to normal temperature or if you must touch them be sure to wear proper gloves E Do not touch the internal parts pum
14. 18191981000 60 16900 SESSOU se WOI opio9e wefas enb epsep sjonjeuou s ojueunoop no s euuou s ajuinBas s e epepiuuojuoo 0215980 jezoxye u e e ABoy ueqejepn abassojaja s la CH 9 soupo eAefz eno es nloy eu ep nosouio ofpo wose pod efnfjvez Em S alnyejza luage youd ojo es znuigu y uezijez az soupgaodpo eujd ans alnsejyold CD p JE LUe 104 8 eye ueejnnisen eegiou uolsese yap euuep 1 uos Je 10 Jensue Dipuejsinj Jo aea CND Zh uojese yap euuep 5 wos ye BueAsuepnanu 1 CS LL euuep je 1e Ya klspn ye wos a Gr OL oatmBOL9eH NOdOLOY x ewreaot idogo Olh 4 1019810 01089 End 60 31VLINHO3NO2 30 3l viv 1930 39 I9S0NGO9Z VrOV3V DI30 39 3Q0HS 0 IN3S Y 1HOMd 39 vriovav Diad svaliSTiglv 39 THAC SAILMILILY 39 NOOIS1V3V DI3QShAVIS VA 39 LLSONOVDAS O VAVIZI 39 1VZOXLV TIAN 193801313393W 39 ILSONAGV1SN O WAVEZI 39 VL
15. 8BBV3 DAIKIN Installation manual Unit for air to water heat pump system 4P347825 1A 2013 04 7 DEFINITIONS 1 1 Meaning of warnings and symbols Warnings in this manual are classified according to their severity and probability of occurrence DANGER Indicates an imminently hazardous situation which if not avoided will result in death or serious injury WARNING Indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION Indicates a potentially hazardous situation which if not avoided may result in minor or moderate injury It may also be used to alert against unsafe practices NOTICE Indicates situations that may result equipment or property damage accidents only INFORMATION This symbol identifies useful tips or additional information gt gt a Some types of danger are represented by special symbols Electric current Danger of burning and scalding 1 2 Meaning of used terms Installation manual Instruction manual specified for a certain product or application explaining how to install configure and maintain it Operation manual Instruction manual specified for a certain product or application explaining how to operate it Maintenance instructions Instruction manual specified for a certain product or application which explains if relevant how to install configure operate and or maintain the product or applic
16. BHQ006 008BBV3 16 Unit for air to water heat pump system 4P347825 1A 2013 04 16 3 Service mode operation Refer to the service manual to carry out any service mode operation 17 TROUBLESHOOTING This section provides useful information for diagnosing and correcting certain problems which may occur with the unit This troubleshooting and related corrective actions may only be carried out by the installer or service agent 17 1 General guidelines Before starting the troubleshooting procedure carry out a thorough visual inspection of the unit and look for obvious defects such as loose connections or defective wiring DANGER ELECTRICAL SHOCK See 2 General Safety precautions on page 2 DANGER DO NOT TOUCH PIPING AND INTERNAL PARTS See 2 General Safety precautions on page 2 When a safety device was activated stop the unit and find out why the safety was activated before resetting it Under no circumstances safety devices may be bridged or changed to a value other than the factory setting If the cause of the problem can not be found call your local dealer DANGER When carrying out an inspection on the control box of the unit always make sure that the main switch of the unit is switched off If the pressure relief valve is not working correctly and is to be replaced always reconnect the flexible hose attached to the pressure relief valve to avoid water dripping out of the unit I
17. Gation rooted E et eoe skint CAREFULLY READ THESE INSTRUCTIONS BEFORE 4 ACCESSES ciim leeren INSTALLATION THEY WILL TELL YOU HOW TO INSTALL AAs Location of the accessories een AND HOW TO CONFIGURE THE UNIT PROPERLY 4 2 Accessories supplied with the outdoor KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE 5 OvervieWiOl ltda REFERENCE 51 Opening Te UO UN scd Lecce ehe 5 2 Main components of the outdoor 5 8 Main components of the outdoor unit switch box 5 5 4 Functional diagram of outdoor hydraulic compartment 7 6 Selecting an installation 7 General precautions on outdoor installation location 7 Wheater dependent Selecting an outdoor location in cold climates ne Place of installation co 7 Dimensions and service 7 1 Dimensions of the outdoor unit B 7 2 Service space of the outdoor unit me 8 Typical application examples iD 9 Inspecting handling and unpacking the 9 Bei pee en 9 9 2 Handling 9 9 3 Unpacking 10 9 4 Installing the unit wil Heater kit installation optional esses 10 9 5 Drain wor
18. NFORMATION For problems related to the optional solar kit for domestic water heating refer to the troubleshooting in the installation manual of that kit DANGER Do not touch water pipes during and immediately after operation as the pipes may be hot Your hand may suffer burns To avoid injury give the piping time to return to normal temperature or be sure to wear proper gloves WARNING Do not touch the refrigerant pipes during and immediately after operation as the refrigerant pipes may be hot or cold depending on the condition of the refrigerant flowing through the refrigerant piping compressor and other refrigerant cycle parts Your hands may suffer burns or frostbite if you touch the refrigerant pipes To avoid injury give the pipes time to return to normal temperature or if you must touch them be sure to wear proper gloves E not touch the internal parts pump backup heater etc during and immediately after operation Your hands may suffer burns if you touch the internal parts To avoid injury give the internal parts time to return to normal temperature or if you must touch them be sure to wear proper gloves 17 2 General symptoms heating or cooling as expected Symptom 1 The unit is turned on ss LED is lit but the unit is not POSSIBLE CAUSES CORRECTIVE ACTION The temperature setting is not correct Check the controller set point The water flow is too low C
19. SACGNNSIVANWNAGHA SNLIOWTI 39 UVASWVS WO 9NIH3 DIU3 39 3S TAWWYLSNAY3A0 WO NVENYSHOS 39 NIu3 83535 T3 1A4dO 39 lt g gt Je jeuep na y joue uos 01 uoo ep lt g gt Jod ajuawengisod lt 9 gt Aetoquatetine sa y ua eoo qejse as 0 02 PION 90 lt g gt WIAHALIBLWKOLIOL 2 Onsuoyueaieno lt g gt 2812198100 8 y 8 OHEELY 60 100p 9500 lt y gt sjeoz p lt Q gt O opJo9e lt g gt ap 2 JE9 J11199 ne lt g gt 180a1ed 0 W09 9 y OWO Je 80 Jed uewenysod anjeng lt y gt suep iuyap anbieway 0 lt 2 gt OL 311 lt g gt OL oun lt gt yeyyiuez geueb yanaq DYIL3Q IDISAIGY 10 y 010 10137100090 So 0 lt g gt uoa pun y ap uram 20 gt opuooes lt g gt lt g gt oj Duipioooe ejueurenisod ojeapni6 lt y gt au ojeeuijap EION 90 lt g gt Aq Ajenn sod pabpn pue y ui o jas se ON 10 Sepyre ou sey seqiseJd Jolosane 27 ul gh Iwelusimouejsod z alupobz Hanoy 9 WNEMHOXOUOLI 2 8121
20. UTION Corrosion of the system due to presence of glycol Uninhibited glycol will turn acidic under the influence of oxygen This process is accelerated by presence of copper and at higher temperatures The acidic uninhibited glycol attacks metal surfaces and forms galvanic corrosion cells that cause severe damage to the system It is therefore of extreme importance W that the water treatment is correctly executed by a qualified water specialist that a glycol with corrosion inhibitors is selected to counteract acids formed by the oxidation of glycols W that in case of an installation with a domestic hot water tank only the use of propylene glycol including necessary inhibitors classified as Category 3 according to EN1717 or equivalent based on the applicable legislations is allowed In other installations the use of ethylene glycol is permitted as well that no automotive glycol is used because their corrosion inhibitors have a limited lifetime and contain silicates which can foul or plug the system W that galvanized piping is not used in glycol systems since its presence may lead to the precipitation of certain components in the glycol s corrosion inhibitor that it has to be made sure the glycol is compatible with the used materials in the system CAUTION Units without backup heater kit installed are obligatory always to use glycol NOTICE Be aware of the hygroscopic property of glycol it absorbs
21. aborted 5 the unit properly earthed m Is the wiring between units connected in DANGER series correct 2 Never leave the unit unattended with an open front panel Are any of the wiring attachment screws during test run loose 5 the insulation resistance at least 1 MQ CAUTION Use 500 V mega tester when measuring ingulation To protect the compressor make sure to turn on the power supply 6 hours before starting operation Do not use a mega tester for low voltage circuits 14 3 Underfloor heating screed dry out program Refer to the EKCB indoor unit installation manual EBHQ006 008BBV3 DAIKIN Installation manual Unit for air to water heat pump system 4P347825 1A 2013 04 15 75 OPERATION OF THE UNIT Once the unit is installed and test operation of outdoor unit and indoor units is finished the operation of the unit can start For operating the indoor unit the user interface of the indoor unit should be switched ON Refer to the indoor unit operation manual for more details 76 MAINTENANCE AND SERVICE 16 1 Maintenance introduction In order to ensure optimal operation of the unit a number of checks and inspections should be carried out on the unit at regular intervals preferably yearly This maintenance must be carried out by your local Daikin technician To execute the maintenance activities as mentioned below it is WARNING W Do not touch the refrigerant pip
22. age 11 EBHQ006 008BBV3 Unit for air to water heat pump system 4P347825 1A 2013 04 DAIKIN Installation manual 17 Symptom 5 The water pressure relief valve leaks POSSIBLE CAUSES CORRECTIVE ACTION Dirt is blocking the water pressure relief valve outlet Check for correct operation of the pressure relief valve by turning the red knob on the valve counter clockwise 19 UNIT SPECIFICATIONS Technical specifications EBHQ006BBV3 EBHQOO08BBV3 If you do not hear a clacking sound Nominal capacity emend your local nn Cooling Refer to the Technical Data In case the water keeps running out of the unit close both the water inlet eating and outlet shut off valves first and Dimensions x W x D mm 805 x 1190 x 360 then contact your local dealer Weight Machine weight kg 95 Symptom 6 The user interface displays AVAILABLE when pressing Operation weight 99 certain buttons Connections i b POSSIBLE CAUSES CORRECTIVE ACTION a Ip _ Field installed waterpiping The current permission level is setto Change the user permission level Minimum pressure a level that prevents using the field setting 0 00 refer to the SETS bar 4 pressed button chapter Field settings in the EKCB xa installation manual Minimim temperature
23. aks fire or other damage to the equipment Be sure only to use accessories and optional equipment made by Daikin which are specially designed for use with the products as of subject in this manual and have them installed by an installer The precautions listed here are divided into the following four types They all cover very important topics so be sure to follow them carefully A DANGER ELECTRICAL SHOCK Switch off all power supply before removing the switch box service panel or before making any connections or touching electrical parts Do not touch any switch with wet fingers Touching a switch with wet fingers can cause electrical shock Before touching electrical parts turn off all applicable power supply To avoid electric shock be sure to disconnect the power supply 1 minute or more before servicing the electrical parts Even after 1 minute always measure the voltage at the terminals of main circuit capacitors or electrical parts and before touching be sure that those voltages are 50 V DC or less When service panels are removed live parts can easily be touched by accident Never leave the unit unattended during installation or servicing when the service panel is removed IN DANGER DO NOT TOUCH PIPING AND INTERNAL 3 PARTS Do not touch the refrigerant piping water piping or internal parts during and immediately after operation The piping and internal parts may be hot or cold depending on the working cond
24. al water volume in the installation is below the maximum allowed water volume Water volume lt 170 with unit installed 150 no EKMBUH unit installed gt 170 I with EKMBUH unit installed Actions required pre pressure must be decreased calculate according to Calculating the pre pressure of the Installation height difference zm No pre pressure adjustment required expansion vessel check if the water volume is lower than maximum allowed water volume use graph below Actions required pre pressure must be increased calculate according to Calculating the gt 7 m pre pressure of the Expansion vessel of the unit expansion vessel too small for the installation check if the water volume is lower than maximum allowed water volume use graph below a Installation height difference height difference m between the highest point of the water circuit and the unit If the unit is located at the highest point of the installation the installation height is considered 0 m EBHQ006 008BBV3 Unit for air to water heat pump system 4P347825 1A 2013 04 DAIKIN Installation manual 11 Calculating the pre pressure of the expansion vessel The pre pressure Pg to be set depends on the maximum installation height difference H and is calculated as below 10 0 3 bar Checking the maximum allowed water volume To determine the maximum a
25. an installation site where the snow will not affect the unit If lateral snowfall is possible make sure that the heat exchanger coil is not affected by the snow if necessary construct a lateral canopy Construct a large canopy Construct a pedestal Install the unit high enough off the ground to prevent burying in snow Place of installation Prepare a water drainage channel around the outdoor unit to drain waste water from around the unit Ifthe water drainage of the unit is not easy please build up the unit on a foundation of concrete blocks etc the height of the foundation should be maximum 150 mm If you install the unit on a frame please install a waterproof plate within 150 mm of the underside of the unit in order to prevent the invasion of water from the lower direction Wi f you install the unit on a building frame please install a waterproof plate field supply within 150 mm of the underside of the unit in order to avoid the drainwater dripping See figure NOTICE Units cannot be installed hanging from the ceiling or stacked Installing near a wall or obstacle Where a wall or other obstacle is in the path of the unit s air intake or exhaust airflow the distances as indicated on the figures below need to be respected The wall height on the exhaust side should be 1200 mm or less E not sit or stand on top of the unit E Do not place any objects or equipment on
26. ated power circuit Never use a power circuit shared by another appliance For wiring use a cable long enough to cover the entire distance with no connection Do not use an extension cord Do not put other loads on the power supply use a dedicated power circuit Failure to do so may cause abnormal heat electric shock or fire Do not touch the refrigerant pipes during and immediately after operation as the refrigerant pipes may be hot or cold depending on the condition of the refrigerant flowing through the refrigerant piping compressor and other refrigerant cycle parts Your hands may suffer burns or frostbite if you touch the refrigerant pipes To avoid injury give the pipes time to return to normal temperature or if you must touch them be sure to wear proper gloves CAUTION For use of units in applications with temperature alarm settings it is advised to foresee a delay of 10 minutes for signalling the alarm in case the alarm temperature is exceeded The unit may stop for several minutes during normal operation for defrosting of the unit or when in thermostat stop operation E Earth the unit Earth resistance should be according to the applicable legislations Do not connect the earth wire to gas or water pipes lightning conductor or telephone earth wire Incomplete earthing may cause electric shocks Gas pipe Ignition or explosion may occur if the gas leaks Water pipe Hard vinyl tubes are not effect
27. ation Dealer Sales distributor for products as per the subject of this manual Installer Technical skilled person who is qualified to install products as per the subject of this manual User Person who is owner of the product and or operates the product Service company Qualified company which can perform or coordinate the required Service to the unit Applicable legislation All international European national and local directives laws regulations and or codes which are relevant and applicable for a certain product or domain Accessories Equipment which is delivered with the unit and which needs to be installed according to instructions in the documentation Optional equipment Equipment which can optionally be combined to the products as per the subject of this manual Field supply Equipment which needs to be installed according to instructions in this manual but which are not supplied by Daikin 2 GENERAL SAFETY PRECAUTIONS All activities described in this manual shall be carried out by an installer Be sure to wear adequate personal protection equipment protection gloves safety glasses when performing installation maintenance or service to the unit If not sure of installation procedures or operation of the unit always contact your local dealer for advice and information Improper installation or attachment of equipment or accessories could result in electric shock short circuit le
28. by the unit during operation is low avoid installation near to places where even low noise levels can be disturbing e g bedroom windows terraces next door neighbours not install the unit in places often used as workplace In case of construction works e g grinding works where a lot of dust is created the unit must be covered Be sure that sufficient precautions are taken in accordance with the applicable legislations in case of refrigerant leakage Wheater dependent precautions Select a place where the rain can be avoided as much as possible W In heavy snowfall areas it is very important to select an installation site where the snow will not affect the unit If lateral snowfall is possible Be sure that the heat exchanger coil is not affected by the snow if necessary construct a lateral canopy Ensure that water cannot cause any damage to the location by adding water drains to the foundation and prevent water traps in the construction W Do not install the unit in areas where the air contains high levels of salt such as that near the ocean corrosion may shorten the life of the unit Wi Prevent direct exposure to winds coming from the sea Be sure that the air inlet and outlet of the unit are not positioned towards the main wind direction frontal wind will disturb the operation of the unit If necessary use a screen to block the wind W When installing the unit in a place exposed to s
29. e power supply settings and electrical connections do not match If d 01 1 or 2 the wiring requires specific installation like illustrated in the chapter Connection to a benefit kWh rate power supply in the EKCB installation manual Other correctly installed configurations are possible but are to be specific for the type of benefit KWh rate power supply type at this specific site The benefit KWh rate signal was sent by the electricity company Wait for the power to return Symptom 3 Pump is making noise cavitation POSSIBLE CAUSES CORRECTIVE ACTION There is air in the system Purge air Water pressure at pump inlet is too low Check on the manometer that there is sufficient water pressure The water pressure must be gt 1 bar water is cold Check that the manometer is not broken Check that the expansion vessel is not broken Check that the setting of the pre pressure of the expansion vessel is correct refer to 10 3 Setting the pre pressure of the expansion vessel on page 12 Symptom 4 The water pressure relief valve opens POSSIBLE CAUSES CORRECTIVE ACTION The expansion vessel is broken Replace the expansion vessel The water volume in the installation is too high Make sure that the water volume in the installation is under the maximum allowed value refer to 10 2 Checking the water volume and expansion vessel pre pressure on p
30. ecting the water circuit Inappropriate tooling will cause damage to the pipes Wi Increasing the distance between shut off valves is necessary for ease of installation Installation example To secure the piping of the unit To connect the shut off valve Water outlet Water intlet Round socket 2x 1 FBSP field supply 1 MBSP pipe end field supply ONADN Installation manual 12 DAIKIN EBHQ006 008BBV3 Unit for air to water heat pump system 4P347825 1A 2013 04 NOTICE The unit is only to be used in a closed water system Application in an open water circuit can lead to excessive corrosion of the water piping Never use Zn coated parts in the water circuit Excessive corrosion of these parts may occur as copper piping is used in the unit s internal water circuit When using a 3 way valve in the water circuit Preferably choose a ball type 3 way valve to guarantee full separation between domestic hot water and floor heating water circuit When using a 3 way valve or a 2 way valve in the water circuit The recommended maximum changeover time of the valve should be less than 60 seconds CAUTION For installations with a domestic hot water tank the use of propylene glycol including necessary inhibitors is only allowed if classified as Category 3 according to EN1717 or the applicable legislations In case of over pressure when using glycol be sure to connect the safety valve
31. es during and immediately after operation as the refrigerant pipes may be hot or cold depending on the condition of the refrigerant flowing through the refrigerant piping compressor and other refrigerant cycle parts Your hands may suffer burns or frostbite if you touch the refrigerant pipes To avoid injury give the pipes time to return to normal temperature or if you must touch them be sure to wear proper gloves E Do not touch the internal parts pump backup heater etc during and immediately after operation Your hands may suffer burns if you touch the internal parts To avoid injury give the internal parts time to return to normal temperature or if you must touch them be sure to wear proper gloves Checks The described checks must be executed at least once a year required to open the outdoor unit covers See Opening the outdoor 1 Water pressure unit on page 9 as well as the indoor unit front panel See Opening Check if the water pressure is above 1 bar If necessary add the indoor unit on page 9 water 2 Water filter 16 2 Maintenance activities 3 Water pressure relief valve Check for correct operation of the pressure relief valve by Service precautions turning the red knob on the valve counter clockwise lf you do not hear a clacking sound contact your local dealer DANGER ELECTRICAL SHOCK Incase the water keeps running out of the unit close both See 2 General Safety precau
32. eu uo lt gt s A g lt gt al 10y 9 MILIY no eyejruuojuoo lt g gt Nyizod jeroaude 6 lt gt U 11119 ejse tuno ese lt gt WaNyoapeIMs lt 8 gt Biuido eum jkzod lt y gt tloejueunyop z alupoBz guuezs 2 2 e e eyozebi lt g gt z e ueldeje v z e WWexaeduou 09 aubredip 60 Wa 80 AMAUQO LO ep ameg 90 o pisepuaweab sjeoz ueufluoiy pO anb g0 Buruepuy gewab 20 pepuauie se L0 203010 BON ebemn sezAbalban 02 102 Ae jo pueiso 2 nexa 0 lt g gt sueys po ouefualioo oungizod lt y gt n ouezojzi al oyey lt gt s npejnos A lt g gt 00945112 e y ouapann ojfq yel NSOSIeyn 2 ureeyyruag Ju syendy uo lt g gt eyjol el y esseluyerse Apasa uo eol 2 JM Lag ala lt g gt 5 wouuel y Jap wos euawoden Gl ByUpUZod p Wony EL Men CL 477 129 11 lt q Opedag
33. formed the user interface will return to normal mode after 10 seconds or by pressing the button once To test the heating operation push the button so the icon is displayed To start the test run operation press the button To test the cooling operation push the button so the icon is displayed To start the test run operation press the button To test the domestic water heating operation push the AI 5 button The test run operation will start without pressing the button 3 The test run operation will end automatically after 30 minutes or when reaching the set temperature The test run operation can be stopped manually by pressing the button once If there are misconnections or malfunctions an error code will be displayed on the user interface Otherwise the user interface will return to normal operation 4 Toresolve the error codes see 17 3 Error codes on page 18 INFORMATION To display the last resolved error code push the Electrical wiring Is the wiring as mentioned on the wiring eae time button again 4 times to nter unit wirin H return to normal mode Earth wire 2 diagram Make sure no wiring has been forgotten and W itis not possible to perform a test run if a forced that there are no missing phases or reverse operation from the outdoor unit is in progress Should phases forced operation be started during a test run the test a run will be
34. heck that all shut off valves of the water circuit are completely open Check if the water filter needs cleaning Make sure there is no air in the System purge air heck on the manometer that there is sufficient water pressure The water pressure must be gt 1 bar water is cold Checkthat the pump speed setting is on the highest speed Make sure that the expansion vessel is not broken Check that the resistance in the water circuit is not too high for the pump refer to the chapter Setting the pump speed in the EKCB installation manual The water volume the installation is too low Make sure that the water volume in the installation is above the minimum required value refer to 10 2 Checking the water volume and expansion vessel pre pressure on page 11 Symptom 2 The unit is turned on but the compressor is not starting space heating or domestic water heating POSSIBLE CAUSES CORRECTIVE ACTION The unit must start up out of its operation range the water temperature is too low In case of low water temperature the system utilizes the backup heater to reach the minimum water temperature first 15 Check that the backup heater power supply is correct Check that the backup heater thermal fuse is closed Check that the backup heater thermal protector is not activated Check that the backup heater contactors are not broken The benefit kWh rat
35. ion of the outside water piping during winter time The backup heater factory set capacity is 6 kW however depending on the installation the installer can limit the backup heater capacity to 3 kW The backup heater capacity decision is a mode based on the equilibrium temperature see scheme below 4 Ta Heat pump capacity Required heating capacity site dependent Additional heating capacity provided by the backup heater Aa O N Equilibrium temperature can be set through the user interface refer to the chapter Equilibrium temperature and space heating priority temperature in the EKCB installation manual Ambient outdoor temperature Pu Heating capacity Datacable obligatory option The EKCOMCAB1 thermistor interconnection cable must be connected to allow communication between the indoor unit and the outdoor unit Domestic hot water tank option An optional EKHW domestic hot water tank with integrated 3 kW electrical booster heater can be connected to the indoor unit The domestic hot water tank is available in three sizes 150 200 and 300 litre Refer to the domestic hot water tank installation manual for further details Solar kit for domestic hot water tank option For information concerning the EKSOLHW solar kit refer to the installation manual of that kit Digital O PCB kit option An optional EKRP1HB digital I O PCB can be connected to the indoor unit and allows W remote alarm out
36. ir to water heat pump system 4P347825 1A 2013 04 10 PIPING CONNECTION WORK 10 1 Checking the water circuit The units have a water inlet and water outlet for connection to a water circuit This circuit must be provided by a licensed technician and must comply with all applicable legislations NOTICE The unit is only to be used in a closed water system Application in an open water circuit can lead to excessive corrosion of the water piping Before continuing the installation of the unit beware of the following points W Two shut off valves are delivered with the unit To facilitate Service and maintenance install one at the water inlet and one at the water outlet of the unit W Drain taps must be provided at all low points of the system to permit complete drainage of the circuit Two drain valves are provided inside the unit Air vents must be provided at all high points of the system The vents should be located at points which are easily accessible for servicing An automatic air purge is provided inside the outdoor unit Check that this air purge valve is not tightened too much so that automatic release of air in the water circuit remains possible care that the components installed in the field piping can withstand the water pressure maximum 3 bar static pressure of the pump The maximum waterpiping temperature is 65 C according to safety device setting Always use materials which
37. ition of the unit Your hand may suffer burns or frostbite if you touch the piping or internal parts To avoid injury give the piping and internal parts time to return to normal temperature or if you must touch them be sure to wear protective gloves WARNING W Tear apart and throw away plastic packaging bags so that children will not play with them Children playing with plastic bags face danger of death by suffocation Safely dispose of packing materials Packing materials such as nails and other metal or wooden parts may cause stabs or other injuries Installation manual DAIKIN EBHQ006 008BBV3 Unit for air to water heat pump system 4P347825 1A 2013 04 Ask your dealer or qualified personnel to carry out installation work Do not install the machine by yourself Improper installation may result in water leakage electric shocks or fire Perform installation work in accordance with this installation manual Improper installation may lead to water leakage electric shocks or fire Be sure to use only the specified accessories and parts for installation work Failure to use the specified parts may result in water leakage electric shocks fire or the unit falling Install the unit on a foundation that can withstand its weight Insufficient strength may result in the fall of equipment and causing injury Carry out the specified installation work in consideration of strong winds hurricanes o
38. ive earths Lightning conductor or telephone earth wire Electric potential may rise abnormally if struck by a lightning bolt Install the indoor and outdoor units power wire and connecting wire at least 1 meter away from televisions or radios to prevent image interference or noise Depending on the radio waves a distance of 1 meter may not be sufficient to eliminate the noise Do not rinse the unit This may cause electric shocks or fire Do not install the unit in places such as the following Where there is mist of mineral oil oil spray or vapour Plastic parts may deteriorate and cause them to fall out or water to leak Where corrosive gas such as sulphurous acid gas is produced Corrosion of copper pipes or soldered parts may cause the refrigerant to leak Where there is machinery which emits electromagnetic waves Electromagnetic waves may disturb the control System and cause malfunction of the equipment Where flammable gases may leak where carbon fibre or ignitable dust is suspended in the air or where volatile flammables such as thinner or gasoline are handled Such gases may cause a fire Where the air contains high levels of salt such as that near the ocean Where voltage fluctuates a lot such as that in factories n vehicles or vessels Where acidic or alkaline vapour is present EBHQ006 008BBV3 Unit for air to water heat pump system 4P347825 1A 2013 04 DAIKIN In
39. k Of the outdoot Urt cii cnet 10 10 Piping connection work 10 1 Checking the water circuit 10 2 Checking the water volume and expansion vessel Prespressufe S 10 3 Setting the pre pressure of the expansion vessel 3 10 4 Connecting the waler circuit aenneren 10 5 Protecting the water circuit against freezing 10 6 Initial start up at low ambient temperatures 8 10 7 CHANGING Water a Piping C Water piping freezing prevention is 11 Important information regarding the refrigerant used 14 12 Electrical WIRING WORK croire atti rp erret h pne 14 13 Start up and configuration esee 14 14 Test rum and tinal CHECK t ee etes 15 14 1 Final check s15 Pre run checks 15 14 2 Test operation manual 15 Procedure 18 14 3 Underfloor heating screed dry out program 15 Operation Of the UN coe me tree N 16 16 Maintenance and service iain eti centes 16 16 1 Maintenance imtrOGuctiom 16 16 2 Maintenance activities Service NO CAUTIONS auna ide amp MM 16 3 Service mode operation nass seen 17 17 Troubleshooting 17 17 1 General guidelines e rd 17 2 General symptoms 17 17 3 IEMORCODOS ceveustes esconsedescats 18 EBHQ006 00
40. k for correct operation of contactors K1M K2M K3M K5M applications with domestic hot water tank only and When service panels are removed live parts can be by use of an ohmmeter All contacts of these contactors easily touched by accident must be in open position Never leave the unit unattended during installation or servicing when service panel is removed 7 In case of use of glycol RD Refer to the caution at 10 5 Protecting the water circuit against freezing on page 13 CAUTION Play it safe Document the glycol concentration and the pH value in the Touch a metal part by hand such as the stop valve in system at least once a year Ris deed nn 11 W pH value below 8 0 indicates that a significant portion of P 9 the inhibitor has been depleted and that more inhibitor needs to be added DANGER DO NOT TOUCH PIPING AND INTERNAL m PARTS W When the pH value is below 7 0 then oxidation of the glycol occurred the system should be drained and flushed See 2 General Safety precautions on page 2 thoroughly before severe damage occurs Do not touch water pipes during and immediately after Make sure that the disposal of the glycol solution is done in operation as the pipes may be hot Your hand may suffer accordance with all applicable legislations burns To avoid injury give the piping time to return to normal temperature or be sure to wear proper gloves Installation manual DAIKIN E
41. l have a satisfying result In critical processes or in rooms with a high heat load though extra water volume might be required NOTICE When circulation in each space heating loop is controlled by remotely controlled valves it is important that this minimum water volume is kept even if all the valves are closed See example below The maximum allowed water volume is 2501 if no glycol is used This is reduced to 1751 if 25 of propyleen glycol is used In case no EKMBUHBA6V3 backup heater kit is installed the maximum allowed water volume is restricted to 1501 In such case we recommend the use of a thermostatic by pass valve see example below As soon as the water circuit with the outdoor unit is in normal operation range this by pass valve will gradually open so the entire circuit is than gradually heated Example AA 1 Outdoor unit 2 Indoor unit 3 Heat exchanger 4 Backup heater 5 Pump 6 Shut off valve 7 Motorised thermostatic by pass valve 8 Collector field supply 9 By pass valve field supply FHL1 3 Floor heating loop T1 3 Individual room thermostat optional M1 3 Individual motorised valve to control the floor heating loop field supply 2 Using the table below determine if the expansion vessel prepressure requires adjustment 3 Using the table and instructions below determine if the tot
42. llowed water volume in the entire circuit proceed as follows 1 Determine for the calculated pre pressure Pg the corresponding maximum water volume using the graph below 2 Check that the total water volume in the entire water circuit is lower than this value If this is not the case the expansion vessel inside the unit is too small for the installation a pre pressure bar D 010 50 100 150 200 250 300 350 400 450 maximum water volume I pre pressure Pre pressure maximum water volume Maximum water volume A System without glycol B System with 25 propyleen glycol C With EKMBUH unit only Example 1 The outdoor unit is installed 5 m below the highest point in the water circuit The total water volume in the water circuit is 100 In this example no action or adjustment is required Example 2 The outdoor unit is installed 4 m below the highest point in the water circuit The total water volume in the water circuit is 190 I Result B Since 1901 is higher than 1701 the pre pressure must be decreased see table above The required pre pressure is Pg H 10 0 3 bar 4 10 0 3 bar 0 7 bar The corresponding maximum water volume can be read from the graph approximately 200 I Since the total water volume 190 1 is below the maximum water volume 200 1 the expansion vessel suffices for the installation
43. lt temperature display is in 17 3 Error codes When a safety device is activated the user interface LED will be flashing and an error code will be displayed A list of all errors and corrective actions can be found in the installation manual of the EKCB indoor manual 18 DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done in accordance with the applicable legislations a Only if connected to EKCBX008BCV3 b MBSP Male British Standard Pipe Electrical specifications EBHQ006BBV3 EBHQOO08BBV3 Power circuit Phase 15 Frequency Hz 50 Voltage V 230 10 Maximum running current Cooling A 16 25 Heating A 18 a Equipment complying with EN IEC 61000 3 12 b Only if connected to EKCBX008BCV3 European International Technical Standard setting the limits for harmonic currents by equipment connected to public low voltage systems with input current gt 16 A and lt 75 A per phase Installation manual 18 DAIKIN EBHQ006 008BBV3 Unit for air to water heat pump system 4P347825 1A 2013 04 4P347825 1 0000000 Copyright 2013 Daikin DAIKIN EUROPE N V Zandvoordestraat 300 B 8400 Oostende Belgium 4P347825 1A 2013 04
44. moisture from its environment Leaving the cap off the glycol container causes the concentration of water to increase The glycol concen tration is then lower than assumed And in consequence freezing can happen after all Preventive actions must be taken to ensure minimal exposure of the glycol to air WARNING a ETHYLENE GLYCOL IS TOXIC b The concentrations mentioned in the table above will not prevent the medium from freezing but prevent the hydraulics from bursting c The maximum allowed water volume is then reduced according to the figure Checking the maximum allowed water volume on page 12 Also refer to Pre run checks on page 15 EBHQ006 008BBV3 Unit for air to water heat pump system 4P347825 1A 2013 04 DAIKIN Installation manual 13 10 6 Initial start up at low ambient temperatures NOTICE To ensure that the unit operates within its operating range as soon as possible water temperature gt 30 C the load during start up must be reduced as much as possible For example you can do this by putting off fans of the fan coil unit until the water temperature has increased to 30 C If no backup heater EKMBUHBA6C3 is installed within the unit we recommend to start up the unit with a minimum water temperature of 5 C For floor heating applications without a backup heater installed start up circuit by circuit by using an thermo static bypass valve make sure that the tempe
45. mperatures The expansion vessel stabilises the pressure changes with changing water temperatures by giving free space to the changing water volume Expansion vessel service point The service point allows connection of a dry nitrogen cylinder to adjust the expansion vessel pre pressure if necessary Drain and fill valve 2x Air purge valve Remaining air in the water circuit will be automatically removed via the air purge valve Water filter The water filter removes dirt from the water to prevent damage to the pump or blockage of the heat exchanger The water filter should be cleaned on a regular base See 16 Maintenance and service on page 16 Temperature sensors thermistors Two temperature sensors determine the water inlet temperature 12a and water outlet temperature 12b A third thermistor 12c measures the refrigerant temperature Power supply intake Thermistor interconnection cable intake Shut off valves accessory The shut off valves on the water inlet connection and water outlet connection allow isolation of the outdoor unit water circuit side from the residential water circuit side This facilitates draining and filter replacement of the outdoor unit Flow switch The flow switch checks the flow in the water circuit and protects the heat exchanger against freezing and the pump against damage In case the minimum required flow is not achieved the unit will be shut down Pressure relief valve The pressure
46. oAoelnd jseu bleiujads Z4 Yelleuzsey juuezs Jeyoze eu yeu yo uunyuauunyop yeu yo KueAqezs qgeje ze g ay es eajseoe efjipuoo s jueunoop nes piepueys uekaq iqi6 n6npjo nq asazn yewjo epun ninjun os ipuey GL 62 eiueseju A 0 0 alnyejza es a10 y eu ejuepeuez az jsoupenodpoz eu e nseju A GAS yz Is seosipe weny zn seyeyal yeje ey nud je AD z elioesejyap Is ewoyle reuny eBuejl pey erqjeys egfuoyesye ones exslsi 17 ZZ Weel BOBHLO 0190 ee oLemeati dogo h 100 10 eH edudenmat 68 0 snjsnueA Anjny eAejoseey jasnjnjseA nyjere qejuuy Cs 07 egeueu enelzi es oJgjey eu aesdeu ewaudo ef ep eljnelz osa 2 69 6 eijejepop gjseeoe as aes e ajeyuawediyos eo auapundse eudojd ed exejoap Ow 81 Azofyop efoejepyep ej uo uopy eluezpzin ez osoujerzpewodpo usen eu e nueyep Cia INVAJ9ANINN9AN 39 AGOHZ3IN3SYTHAA 39 3M89138 09 9 VE BUHNVAVLM3 39 60 lt gt ejpeexpnues Biel lt g gt syeay el y sipuawnyop pnjepi
47. p backup heater etc during and immediately after operation Your hands may suffer burns if you touch the internal parts To avoid injury give the internal parts time to return to normal temperature or if you must touch them be sure to wear proper gloves A DANGER E not touch water pipes during and immediately after operation as the pipes may be hot Your hand may suffer burns To avoid injury give the piping time to return to normal temperature or be sure to wear proper gloves When service panels are removed live parts can be easily touched by accident Never leave the unit unattended during installation or servicing when the service panel is removed A DANGER ELECTRICAL SHOCK See 2 General Safety precautions on page 2 A DANGER DO NOT TOUCH PIPING AND INTERNAL A PARTS See 2 General Safety precautions on page 2 5 2 Main components of the outdoor unit gt 11 12 13 14 15 16 17 Switch box The switch box contains connection terminals for the power supply and a connection point for the thermistor interconnection cable Heat exchanger Water inlet connection 1 MBSP Water outlet connection 1 MBSP Pump The pump circulates the water in the water circuit Manometer The manometer allows readout of the water pressure in the system Expansion vessel 6 litre The water in the water circuit expands with rising te
48. piayylyapsoomuesan anaisnjoxa uabie do 1reepuie GN p uonesejogp ejuesgud e Jed asia Juewed nba anb syjiqesuodsei anas es snos GD 0 je autas jne epua Ca 20 ase p 1nj Bunjsrusny ssep BunuowqueJeA Sejejo1 uonerejoep siu o jueuidinbe ayy Ayj gsuodsau ajos sy apun seepep 89 NN DIB3ASLISLIWHO3NOO 39 3LINHO3NO2 3Q NOIL VV 1930 39 ONNYVTHYASLYLINYOANOM 39 ALINYOANOD JO NOILVYV 1930 39 ZHZUGdONWAZ HZUVHV 39 VLINYOANOD I0 SNOIZVYVIHOIG 39 OVAINEOANO9 30 NOIOVEV 1930 39 DAIKIN Unit for air to water heat pump system Installation manual CONTENTS Page 18 DisposaliregulfermBuls teet ia eet serere iret tn 18 na 19 Unit 5 namen 18 1 Definitions conocen cerraron 2 SECCION an 18 2 General Safety precautions errore retur 2 El amp ctrical Specifications mia 18 o TE ERN 4 Roc ICD sa ari 4 Thank you for purchasing this product Heating cooling units and heating only 4 3b Combination and rtm teet 4 The original instructions are written in English All other languages Connection to a benefit KWh rate power supply i are translations of the original instructions 3 39 Scope of the mean al u 94 Modelidertifi
49. put E heating cooling ON OFF output W bivalent operation permission signal for the auxiliary boiler Refer to the operation manual and to the installation manual of the digital I O PCB for more information Refer to the wiring diagram or connection diagram for connecting this PCB to the unit Bottom plate heater EKBPHTO8BA option Remote thermostat kit option An optional room thermostat EKRTWA EKRTR or EKRTETS can be connected to the indoor unit Refer to the installation manual of the room thermostat for more information To obtain more information concerning these option kits please refer to dedicated installation manuals of the kits Connection to a benefit kWh rate power supply Refer to the EKCB installation manual 3 3 Scope of the manual This manual describes the procedures for handling installing and connecting the EBHQ units This manual has been prepared to ensure adequate maintenance of the unit and it will provide help if problems occur INFORMATION Refer to the installation manual of the indoor unit for items not described in this manual The operation of the outdoor unit is described in the outdoor unit operation manual 3 4 Mlodel identification Voltage 1P 230 V Series Indication of heating cooling capacity KW 9 Refrigerant R410A Low water temperature ambient zone 3 Monoblock oudoor heat pump a For exact values refer to Technical specifications on page
50. r earthquakes Improper installation work may result in accidents due to fall of equipment Make certain that all electrical work is carried out by qualified personnel according to the applicable legislations and this installation manual using a separate circuit Insufficient capacity of the power supply circuit or improper electrical construction may lead to electric shocks or fire Be sure to install an earth leakage circuit breaker in accordance with the applicable legislations Failure to do so may cause electrical shock and fire Make sure that all wiring is secure using the specified wires and ensuring that external forces do not act on the terminal connections or wires Incomplete connection or fixing may cause a fire When wiring between the indoor and the outdoor units and wiring the power supply form the wires so that the panels can be securely fastened If the panels are not in place overheat of the terminals electric shocks or a fire may be caused After completing the installation work check to make sure that there is no leakage of refrigerant gas Never directly touch any accidental leaking refrigerant This could result in severe wounds caused by frostbite Electrical work must be carried out in accordance with the installation manual and the national electrical wiring rules or code of practice Insufficient capacity or incomplete electrical work may cause electrical shock or fire Be sure to use a dedic
51. rature of the water returning to the unit is more than 20 C 10 7 Charging water 1 Connectthe water supply to a drain and fill valve see 5 2 Main components of the outdoor unit on page 6 2 Make sure the automatic air purge valve is open at least 2 turns 3 Fill with water until the manometer indicates a pressure of approximately 2 0 bar Remove air in the circuit as much as possible using the air purge valves Air present in the water circuit might cause malfunctioning of the backup heater if applicable 4 Checkthat the backup heater vessel EKMBUH if applicable is filled with water by opening the pressure relief valve Water must flow out of the valve NOTICE E During filling it might not be possible to remove all air in the system Remaining air will be removed through the automatic air purge valves during first operating hours of the system Additional filling with water afterwards might be required The water pressure indicated on the manometer will vary depending on the water temperature higher pressure at higher water temperature However at all times water pressure should remain above 1 bar to avoid air entering the circuit W Theunit might dispose some excessive water through the pressure relief valve Water quality must be according EN directive 98 83 EC If no glycol is in the system in case of a power supply failure or pump operating failure drain the system When water
52. relief valve for location of the reset button raa aedi 3 The backup heater equilibrium Raise the equilibrium temperature Operation range water side temperature has not been field setting 5 01 to activate backup Heating 415 450 configured correctly heater operation at a higher outdoor a 16 temperature Cooling C 4157422 Domestic hot water by heat Too much heat pump capacity is Check that the space heating priority pump 25 80 used for heating domestic hot water temperature field settings are mem applies only to installations with a configured appropriately Operation range air side domestic hot water tank Make sure that the space heating Heating 15 25 priority status field setting 5 02 is Cooling C 4107443 Raise the space heating priority Domestic hot water by heat C 45 435 temperature field setting 5 03 to pump activate booster heater operation at a higher outdoor temperature Symptom 8 Temperature values displayed on the remote controller user interface are displayed in F instead of C POSSIBLE CAUSES CORRECTIVE ACTIONS You accidentally changed the setting to view the temperature values in F by pushing the and Cv J buttons simultaneously To change the display back to push 8 and buttons simultaneously for 5 seconds Execute same procedure to change back to the F display The defau
53. stallation manual 3 3 INTRODUCTION 3 1 General information This installation manual concerns the outdoor EBHQOO6BBV3 and EBHQOO8BBV3 of the Monoblock units of the GBS Altherma series The Monoblock units exist out of an outdoor installed unit EBHQ this manual and an indoor installed wall mounted unit EKCB These units are used for both heating and cooling applications The units can be combined with Daikin fan coil units floor heating applications low temperature radiators domestic hot water tank option and solar kit option A user interface is standard supplied with the unit to control your installation Heating cooling units and heating only units The monoblock unit range consists of two main versions a heating cooling version uses EKCBX indoor unit and a heating only version uses EKCBH indoor unit both available in 2 capacity sizes 6 kW EBHQOO6 or 8 kW EBHQ008 The indoor unit and outdoor unit must be connected with the obligatory optional datacable 3 2 Combination and options Possible combinations Outdoo EKCBX008BCV3 EKCBHO08BCV3 EBHQO06BBV3 Possible Possible EBHQ008BBV3 Possible Possible Both versions heating only and heating cooling are optionally delivered with a backup heater kit EKMBUH for additional heating capacity during cold outdoor temperatures The backup heater also serves as a backup in case of malfunctioning of the unit and for freeze protect
54. supplied with the domestic hot water tank is 12min length to be connected to the 13 Manometer indoor unit EKCB be en S at Maximum allowable distance between the 10m 3 way valve and the outdoor unit only for try to keep as close to 16 Flow switch installations with a domestic hot water tank the outdoor unit as 17 Water filter installed possible R11T Water outlet temperature sensor R12T Backup heater temperature sensor Since drain flows out of the unit do not place anything under the Ri3T Refrigerant temperature thermistor unit which must be kept away from moisture R14T Water inlet temperature sensor Waterflow direction Take care that in the event of a water leak water cannot cause Refrigerant flow direction in cooling mode any damage to the installation space and surroundings e g in Refrigerant flow direction in heating mode case of a blocked drain pipe Wi Install the unit and power cords at least 3 m away from television and radio sets This is to prevent interference to images and Sounds Depending radio wave conditions electromagnetic interference may still occur even if installed more than 3 m away EBHQ006 008BBV3 DAIKIN Installation manual Unit for air to water heat pump system 4P347825 1A 2013 04 7 Select the location of the unit in such a way that the sound generated by the unit does not disturb anyone and the location is selected according the applicable legislation Although the noise produced
55. system 4P347825 1A 2013 04 14 TEST RUN AND FINAL CHECK The installer is obliged to verify correct operation of the indoor and outdoor unit after installation 14 1 Final check Before switching on the unit read following recommendations W When the complete installation and all necessary settings have been carried out close all panels of the outdoor unit and the indoor unit The service panel of the outdoor unit switch box and front panel of the indoor unit may only be opened by a licensed electrician for maintenance purposes DANGER Never leave the unit unattended during installation or servicing When the service panel is removed live parts can be easily touched by accident NOTICE Note that during the first running period of the unit required power input may be higher than stated on the nameplate of the unit This phenomenon originates from the compressor that needs elapse of a 50 hours run in period before reaching smooth operation and stable power consumption Pre run checks 14 2 Test run operation manual If required the installer can perform a manual test run operation at any time to check correct operation of cooling heating and domestic water heating Procedure 1 Push the button 4 times so the TEST icon will be displayed 2 Depending on the indoor unit model heating operation cooling operation or both must be tested as follows when no action is per
56. t use stands to only support the corners N A NN N SN 777777777 07777722 577 7 85077777777 15772277 6777777777 VY y gt 100 gt 100 X Not allowed Allowed units mm The height of the foundation must at least be 150 mm from the floor In heavy snowfall areas this height should be increased dependant on the installation place and condition Refer to the installation manual of the EKMBUH heater kit for more details 9 5 Drain work of the outdoor unit In case drain work on your outdoor unit is neccessary follow the guidelines below Two drain outlets are provided in the bottom plate of unit drain plug and drain hose are field supply In cold areas do not use a drain hose with the unit Otherwise drain water may freeze and block the drain In case the use of a drain hose is unavoidable for one reason or another it is recommended to install a heater tape in order to protect drain from freezing Make sure the drain works properly NOTICE If drain holes of the outdoor unit are covered by a mounting base or by floor surface raise the unit in order to provide a free space of more than 100 mm under the outdoor unit 913 199 5 1225 27 N A e te LL 1 Drain water holes 2 Bottom frame Installation manual 10 DAIKIN EBHQ006 008BBV3 Unit for a
57. the unit must be checked and any damage must be reported immediately to the carrier s claims agent 9 2 Handling The unit is packed in a cardboard box fixed by straps W When handling the unit take into account the following 1 Fragile handle the unit with care Keep the unit upright in order to avoid compressor damage 2 Choose on before hand the path along which the unit is to be brought in 3 Bring the unit as close as possible to its final installation position in its original package to prevent damage during transport 4 After unpacking the unit can be positioned correctly using the handles provided at both ends of the unit As shown in the figure below slowly move the unit by grabbing the left and right grips Position your hands on the corner instead of grabbing the suction grill otherwise the casing could be deformed CAUTION To avoid injury do not touch the air inlet or aluminium fins of the unit EBHQ006 008BBV3 Unit for air to water heat pump system 4P347825 1A 2013 04 DAIKIN Installation manual 9 9 3 Unpacking CAUTION To avoid injury do not touch the air inlet or aluminium fins of the unit Relief the unit from its packing material Unpack the unit completely according to the instructions mentioned Prepare 4 sets of M8 or M10 foundation bolts nuts and washers each field supply Fasten the unit in place using four fo
58. tions on page 2 the water inlet and outlet shut off valves first and then contact Before carrying out any maintenance or repair activity your local dealer always switch off the circuit breaker on the supply 4 Domestic hot water tank pressure relief valve field supply panel remove the fuses or open the protection Applies only to installations with a domestic hot water tank devices of the unit Check for correct operation of the pressure relief valve on the Make sure that before starting any maintenance or domestic hot water tank repair activity also the power supply to the outdoor 5 Domestic hot water tank booster heater unit is switched off Applies only to installations with a domestic hot water tank W not touch live parts for 10 minutes after the power Sn ah on AUDI SAL off because tisk So drain the domestic hot water tank remove the booster heater W The heater of the compressor may operate even in from the domestic hot water tank and immerse in a bucket or stop mode similar with lime removing product for 24 hours mM Please note that some sections of the electric 6 Outdoor unit and indoor unit switch box component box are hot Carry out a thorough visual inspection of the switch box sure you do not touch a conductive section in and outdoor unit and look for obvious defects such as Do not rinse the indoor unit This may cause electric loose connections or defective wiring shocks or fire Chec
59. top of the unit Installation manual DAIKIN EBHQ006 008BBV3 Unit for air to water heat pump system 4P347825 1A 2013 04 7 DIMENSIONS AND SERVICE SPACE 7 1 Dimensions of the outdoor unit Unit of measurement mm 7 2 Service space of the outdoor unit The space around the unit is adequate for servicing and the minimum space for air inlet and air outlet is available Refer to the figure below Unit of measurement mm NOTICE The wall height on the air outlet side marked with grey arrow in the figure above must be less than 1200 mm The installation space required on this drawing is for full load heating operation without considering possible ice accumulation If the location of the installation is in a cold climate then all dimensions above should be 2500 mm to avoid accumulation of ice in between the outdoor unit and the nearest walls The connection piping outlet direction in the installation shown in the figure is frontward or downward When routing the piping backward secure space of 2250 mm on the right side of the unit NOTICE If shut off valves are directly installed on the water inlet and outlet increase installation space at the rear of the unit to a minimum of 300 mm 8 TYPICAL APPLICATION EXAMPLES Refer to the installation manual of the EKCB X H indoor unit 9 INSPECTING HANDLING AND UNPACKING THE UNIT 9 1 Inspection At delivery
60. trong wind pay special attention to the following Strong winds of 5 m sec or more blowing against the unit s air outlet cause short circuit suction of discharge air and this may have the following consequences deterioration of the operational capacity frequent frost acceleration in heating operation disruption of operation due to rise of high pressure when a strong wind blows continuously on the face of the unit the fan can start rotating very fast until it breaks Refer to the figures for installation of this unit in a place where the wind direction can be foreseen Turn the air outlet side toward the building s wall fence Screen Make sure there is enough room to do the installation Set the outlet side at a right angle to the direction of the wind Strong wind Selecting an outdoor location in cold climates NOTICE When operating the unit in a low outdoor ambient temperature be sure to follow the instructions described below prevent exposure to wind install the unit with its suction side facing the wall Never install the unit at a site where the suction side may be exposed directly to wind prevent exposure to wind install a baffle plate on the air discharge side of the outdoor unit W When installing the unit in a place frequently exposed to snow pay special attention to the following Elevate the foundation as high as possible Select
61. undation bolts M8 or M10 in accordance with the installation drawing It is best to screw in the foundation bolts until their length remains 20mm above the foundation surface 20mm E NOTICE Prepare a water drainage channel to drain waste water from around the unit During heating operation and when the outdoor temperatures are negative the drained water from the outdoor unit will freeze up If the water drainage is not taken care of the area around the unit might be very slippery W When installed in a corrosive environment use a nut with plastic washer 1 to protect the nut tightening part from rust 99 Heater kit installation optional WARNING Tear apart and throw away plastic packaging bags so that children will not play with them Children playing with plastic bags face danger of death by suffocation Make sure that all accessories as mentioned 4 2 Accessories supplied with the outdoor unit on page 5 are available in the unit 9 4 Installing the unit W When installing the outdoor unit please refer to 6 Selecting an installation location on page 7 to select an appropriate location Check the strength and level of the installation ground so that the unit will not cause any operating vibration or noise after installation W Make sure that the unit is installed level NOTICE When the installation height of the unit needs to be increased do no

Download Pdf Manuals

image

Related Search

Related Contents

CD9180 / Deutsche Bedienungsanleitung DE 1  Baxi Solo 2 RS Quick Start Manual  Etudes supérieures et handicap : mode d`emploi  dans la revue thomiste, 1964, p  Bedienungsanleitung (Grundfunktionen: )  Samsung 400PX manual de utilizador  Baixar  Mode d`emploi  DeLOCK Adapter HDMI male > HDMI male 90° up  

Copyright © All rights reserved.
Failed to retrieve file