JB-QBC-BS10 OPERATING INSTRUCTIONS

image

Contents

1. 33 4 3 STARTUP 33 4 4 FIRE ALARM 33 JD UU 35 4 6 OTHER ALA RM 35 4 7 RESET 35 4 3 35 4 9 SETUP DIMMER 36 5 INTERNAL CODE TABLE 37 6 VDR PROTOCOL u uwa esa ie apos ke pev ka JB QBC BS10 Fire Alarm System 3 BSKY JB QBC BS10 Operating Instructions 1 DESCRIPTION In order to protect the life and assurance on board Brightsky company develop JB QBC BS10 fire alarm system Addressable detector and modules are used in this system If the detector find fire the fire place can be easy to confirm from the fire alarm panel The fire alarm system is designed to meet all major marine and industrial requirements The fire alarm system is designed to meet MSC 1 Circ 1387 revised guidelines for the approval of fixed water based local application fire fighting systems for use in category a machinery spaces and can be used to au
2. 3 Line Fault Check Communication Line 1 9068 Repeater 3 Line Fault Check Communication Line 2 9069 System Fault Repeater 4 Fault 9070 Repeater 4 Line Fault Check Communication Line 1 9071 Repeater 4 Line Fault Check Communication Line 2 9072 System Fault Wrong device type 9073 System Fault Device not included in the configuration 9074 System Fault Flash checksum error 9075 System Fault EEPROM checksum error 9076 System Fault Interface board fault 9077 Interface board lineCheck Communication Line 1 Fault 9078 Interface board lineCheck Communication Line 2 Fault 9079 System Fault Loop board 1 9080 System Fault Loop board 2 9081 Repeater 1 Line Fault Check 24V GND line 9082 Repeater 1 Line Fault Check 24V GND linel 9083 Repeater 1 Line Fault Check 24V GND line2 9084 Repeater 2 Line Fault Check 24V GND line 9085 Repeater 2 Line Fault Check 24V GND linel 9086 Repeater 2 Line Fault Check 24V GND line2 9087 Repeater 3 Line Fault Check 24V GND line 9088 Repeater 3 Line Fault Check 24V GND linel 9089 Repeater 3 Line Fault Check 24V GND line2 9090 Repeater 4 Line Fault Check 24V GND line 9091 Repeater 4 Line Fault Check 24V GND linel 9092 Repeater 4 Line Fault Check 24V GND line2 9093 Control Panel Line Fault Check 24V GND line 9094 Control Panel Line Fault Check 24V GND linel 9095 Control Panel Line Fault Check 24V GND line2 9096 Power Off Power Off 9097 Loop board
3. s 666 INS 9 1 Fire indicator flashing or steady in red color the fire indicator is flashing to indicate that the current fire alarm is not confirmed It turn to steady if the current alarm is confirmed by pressing OK key 2 wm Fault indicator flashing or steady in yellow color the fault lamp is flashing to indicate that the current fault alarm is not confirmed It turn to steady if the current alarm is confirmed by pressing OK key 3 Disabled Condition indicator steady in yellow color When the system is in disabled condition this indicator will be lit 4 Test Condition indicator steady in yellow color When some zones in the system is set to test condition this indicator will be lit 5 Supervisory indicator flashing or steady in red color When the input module activated or input output module received feedback signal this indicator is flashing It turn to steady if the current alarm is confirmed by pressing OK key 6 MSBD Fault indicator flashing or steady in yellow color Indicator is lit when the main power missing 7 ESBD Fault indicator flashing or steady in yellow color Indicator is lit when the emergency power missing 6 JB QBC BS10 Fire Alarm System BSKY JB QBC BS10 Operating Instructions 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 2
4. BSKY JB QBC BS10 Fire alarm system Fixed water based local application fire fighting system OPERATING INSTRUCTIONS WUXI BRIGHTSKY ELECTRONIC CO LTD Bskv JB QBC BS10 Operating Instructions Z ERU c d Content 3 FIRE ALARM CONTROLLER 6 3 1 FRONT PANEL OF FIRE ALARM CONTROLLE 6 32 OPERATIONAL FUNCTION LIST AND ACCESS LEVEL 8 3 3 STARTUP M 9 3 4 FIRE ALA RM 9 3 5 FAULT u 3 6 SUPERVISORY 12 3 7 13 REDIRI D D TO A 14 3 9 16 3 10 RESET 17 3 11 MUTE SILENCE 17 3 12 LOCK UNLOCK 18 3 13 18 3 13 1 ADJUST TIME eer eee tt eerie 19 3 13 2 HISTORY RECORD enne er rep eR 19 3 13 3 VERSION INFORMATION u 20 34134 5
5. JB QBC BS10 Fire Alarm System 39 BSKY JB QBC BS10 Operating Instructions S SSS ANNEX Example for the alarm system used in fixed water based local application fire fighting system JB QBC BS10 fire alarm system can be used in fixed water based local application fire fighting system water mist control function Fire Protection Control Board can be used to control water mist zone s valve and the control signal can be used as input signal for pump controller The pump is controlled by pump controller This system have auto and manual control mode in water mist control function Auto control mode Auto control mode can only send out starting signal in 3 13 6 3 logic setting set the relative detector s address to the source place Set the control module s address to the Activate place Several items that the contents in the source place is the same and the targets are different in activate place can be set that used to control other devices such as AV sounder in the water mist zone if the fire alarm occurred in this zone when the system is in auto state the detector in water mist zone send out fire alarm then the module in fire protection control board will be started start the relative valve and send out starting signal to pump In order to stop the module in fire protection control board press the reset key to reset system or press the activate key to stop the module i
6. DOWNLOAD CONFIGURATION FROM USB Please select USB port 1 or 2 Initialization USB1 Look BSKYBS10 CFG Read data Write data Download to board 1 yes 2 no below Remarks The name of configuration document is fixed as BSKYBS10 CFG Configuration document content is all the content of service menu 28 JB QBC BSI0 Fire Alarm System BSKY JB QBC BS10 Operating Instructions uM Fr Upload configuration to USD is to upload the configuration document to USD memory see the below UPLOAD CONFIGURATION TO USB Please select USB port 1 or 2 Initialization USB1 Read data from FLASH Write file BSKYBS10 CFG to USB Remarks The configuration data document name is fixed as BSKYBS10 CFG The content of configuration data document is all the content of service menu Download configuration to board is used to download the configuration data from panel to interface DOWNLOAD CONFIGURATION To BOARD Download configuration data to board please waitting 1 board see the below SUCCESS 3 14 SAVE CONFIGURATION If you have change the information of the service menu when you exit the service menu the controller will prompt whether you will save the correction see the below SAVE CONFIGURATION Configuration Data have changed Please chose 1 Save amp Download to board 2 Save 3 Cancel Select a menu with 1 3 In general if you want to save the inform
7. Mese steeds 20 3 13 5 DETECTOR TEST eee em ra der 20 3 13 6 SERVICE cette c e Ete e a Ee ER tet 21 3 13 6 1 DETECTOR 22 3 13 6 2 ZONE 23 3 13 6 3 LOGIC hee 24 3 13 64 WORKSPAQCB ite eret eie Rep e P erts 24 3 13 65 SETTINGS 24 3 13 6 54 FIRE PROTECTION ioter nn ene rho 25 3 13 6 5 2 ALARM TYPE enit be Mel e EMEN ER E 26 3 13 6 5 3 DELAY wes 26 9 13 6 9 4 SHORT KREY ebd 26 3 13 6 5 5 OTHER SETTINGS oerte 27 3 13 6 6 EXCHANGE soisissa 28 3 14 SAVE CONFIGURATION 29 3 15 USER PERMISSIONS SETTINGS 30 3 16 FACTORY 5 30 4 FIRE ALARM REPEATERU 32 2 JB QBC BS10 Fire Alarm System BSKY JB QBC BS10 Operating Instructions LO RR 4 1 FRONT PANEL OF FIRE ALARM REPEATER 32 4 2 ADDRESS SET TING
8. 1 line fault Check interface board Loop board 1 line 9098 Loop board 2 line fault Check interface board Loop board 2 line 9099 FPE fault Check FPE fire protection equipment 38 JB QBC BS10 Fire Alarm System Bskv 6 VDR PROTOCOL JB QBC BS10 Operating Instructions SSS SSS Data direction from controller to VDR it is single way transmission Electrical signals RS485 Communication parameter 9600 n8 lor 4800 n 8 1 can be set on the controller Data format Data unit name Length Byte Description Remark Header 6 SFRFIR fixed format Spacer 1 Alarm type S fire supervisory E association 1 F Fault D Disable R reset C communication Spacer 1 Device type FS smoke detector Reset and communication IFH heat detector signals is fixed as OT 2 FD combined detector manual call point others Spacer 1 Loop number 2 decimal system ASCII code Reset and communication signals is fixed as 00 Spacer 1 Device number 3 decimal system ASCII code Reset and communication signals is fixed as 000 Spacer 1 Division number 3 decimal system ASCII code Reset and communication signals is fixed as 000 Spacer 1 Action type A fire association supervisory The action type for reset and disable communication is blank 1 V cancel association fault supervisory restore cancel disable X device fault terminator 2 nn Start a new line
9. 2001 002 ZONE 2 smoke detector 2002 periodic 15 00 18 20 003 ZONE 2 smoke detector 2003 clock 18 20 LEFT RIGHT page 2 del Note this interface only shows the disable equipment that you have set we have some disable which are not come into effect immediately for periodic disable as well you can inquire the effective disable by pressing status key in disable menu see below picture DISABLE 1 1 1 ZONE 2 smoke detector 2001 Accommodation floor 2 OK Confirm alarm RIGHT Details MUTE Buzz off SILENCE Alarm device off JB QBC BS10 Fire Alarm System 15 BSKY JB QBC BS10 Operating Instructions GLEE La For the effective Disable information beside it is shown on LCD the controller can also act as below D Illuminate the disable indicator on the panel Put the time when disable happens and the address to the history record 3 If the system has a fire repeater it will send disable information to fire repeater D If the system has a VDR it will send disable information to VDR On disable interface you can also to the below operation D Press right arrow to check the detailed disable information 2 Press up page key down page to check previous or next disable information 8 Press Status key to check other status information 3 9 TEST If you just want to test the alarm function of detectors and do not want to start the alarm bell output fire relay and the logic operation you can
10. be lit 5 Supervisory indicator flashing or steady in red color When the input module activated or input output module received feedback signal this indicator is flashing It turn to steady if the current alarm is confirmed by pressing OK key 6 MSBD Fault indicator flashing or steady in yellow color Indicator is lit when the main power missing 7 ESBD Fault indicator flashing or steady in yellow color Indicator is lit when the emergency power missing 8 System Fault indicator flashing in yellow color This indicator is lit when the system fault 32 JB QBC BSI0 Fire Alarm System BSKY JB QBC BS10 Operating Instructions Z Z gt UU UNE EEPROM checksum error CPU fault and so on occur 9 Alarm delay indicator flashing in yellow color When the system is in alarm delay status the indicator is flashing and it will be shut down if the alarm delay count down to zero 10 Alarm device indicator flashing or steady in yellow color If the line connected to the BELL is broken this indicator is flashing If the BELL is disabled it is steady 11 FPE Running indicator flashing or steady in red color This indicator is used to Indicate the running state of fire protection equipment when some fire extinguishing zones are started it is flashing and it is changed to steady when the controller receive the starting feedback signal 12 FPE Fault indicator flashing or steady in yell
11. controller will act as below D Put the time address and other information of activate to history record 2 When the system has a fire repeater it will send activate information to fire repeater 3 When the system has a VDR it will send Activate information to VDR On activate interface you can do the below operation D Press right arrow to check detailed activate information 2 Press up page and down page to check previous or next Activate information Press Status key to check other status information Press Reset key to turn of all the started equipment Output modules fire extinguishing protection zone bells and other equipment can be started automatically when fire alarm happens besides this they can also be started by using the menu on the board manually ACTIVATE 1 Module 2 Fire protection zone 3 Bell Select a menu with 1 3 Choose the activate type for example if you choose module the interface will show the present registered modules list JB QBC BS10 Fire Alarm System 13 BSKY JB QBC BS10 Operating Instructions Ca S E MODULE LEFT RIGHT page 1 open 2 close After activate the activated module information will be shown on the activate interface if you turn off the module information will be cleared from the activate interface 3 8 DISABLE The controller has disable function press Disable key to enter the disable function the interface is DISABLE 1 Disable list 0
12. d In fault status it will give a interrupted buzzing The sound of fire and supervisory is prior to fault sound Even if a fault happens once the fire or supervisory comes the sound will change to fire supervisory sound immediately If controller is in mute status it will the give the sounds that comes to it It the inside sound is open press Mute key you will turn off the inside sound if you press the Mute key again if there is unconfirmed fire alarm in the system the inside sound will be restarted if you have set the Mute restart delay Delay gt Mute restart delay and you have turn off the inside sound after the delay time the controller will give alarm sound if the system has unconfirmed fire alarm If the bell is in Activate status press S ence key to turn off the bell if it is under countdown stage then the countdown will be stopped after you press 5 key again the bell will be restarted again if the system has unconfirmed fire alarm Besides this if you have set Silence restart delay Delay gt Silence restart delay after the delay time the bell will be restarted again if unconfirmed fire alarm is existing 3 12 LOCK UNLOCK The control panel can be locked automatically to avoid unauthorized operation under the below two kind of situations D There is no any operation within 30 seconds 2 Press lock key After locked you can only clear inside sound or check fire alarm information and the lock
13. it is used to exit the current menu and back to upper menu Disable key press it when you want to disable some device in the system Test key press it to set some zone to test condition Alpha numbering key it is used to input confirm or delete letters and numbers ARROW key it is used for page turning over or change the cursor s position Lock key it is used to lock or unlock the keyboard Down page key press it to check next alarm message Status key use to change the alarm status display fire alarm activities activate fault disable or test Up page key press it to check last alarm message Reset key use to reset the system disabled condition is not affected by this operation Activate key press it to activate or close some device Silence key press it to turn off the bell when the bell is started press again to restart the bell Lamp test key use to test all indicators on the fire alarm control panel all the indicator will be lit if this key pressed Mute key it is used to stop or restart the internal buzz in the fire alarm control panel when the internal buzz is started LCD display all messages are displayed in this area JB QBC BS10 Fire Alarm System 7 BSKY JB QBC BS10 Operating Instructions 3 2 OPERATIONAL FUNCTION LIST AND ACCESS LEVEL Ment tree of fire alarm control panel Lock 2 Silence 2 Reset 2 Activate 2B Disable 2B Disable list New disable Remove a
14. modules address press the key to start or stop the fire modules at the same time 3 13 6 5 5 OTHER SETTINGS Other settings is used to control some important parameters that on running such as association status power test fire repeater quantities and so on see the below OTHER SETTINGS 1 18 Association auto status yes MSBD fault check ESBD fault check Ship s DC24V fault check Battery fault check MAG Door hold fault check Bell fault check Repeater panel sum LEFT RIGHT page Status yes no OTHER SETTINGS 9 18 Repeater panel fault check Water mist using Water mist panel fault check PA close Earth fault check Earth grade VDR using VDR baudrate LEFT RIGHT page Status yes no OTHER SETTINGS 17 18 Ext power fault output all Language ENG Remarks Association auto status is the association status of fire controller if it is in automatic status it will carry our logic in Logic when in fire alarm or supervisory MSBD fault check is to check whether the main power supply has fault not ESBD fault check is to check whether the emergency power supply has fault or not JB QBC BS10 Fire Alarm System 27 BSKY JB QBC BS10 Operating Instructions uM Fr e Ship s DC24V fault check is to check whether the ship s DC24V has fault or not Battery fault check is to check whether the battery has charging fault or low voltage fault MAGDoor hol
15. of all detectors in one loop See the below DETECTOR TEST 1 Write detector address 2 Read detector address 3 Test detector analogy 4 Test loop detector Select a menu with 1 4 20 JB QBC BS10 Fire Alarm System BSKY JB QBC BS10 Operating Instructions The Write detector address Read detector address Test detector analogy of the Detector test function is only for the detectors that connected to the BUS terminals of fire alarm control panel you can connect one detector for one time The interface to write the address function of detectors is as below WRITE DETECTOR ADDRESS Input detector address 1 160 001 Detector type smoke detector Detector analogy 026 Ok confirm Detector analogy is a non dimensional value and the range of the value is 15 35 in normal status If the value is more than 50 it will alarm if it is less than 15 it is fault Test loop detector is to test loop that connected to loop board please see the below TEST LOOP DETECTOR input detector address 1 160 001 Loop zc 2 3 4 RegBase 000 000 000 030 Analogy 003 003 003 030 LEFT RIGHT switch loop Remarks Is the analog value of the registered detectors please reference Detector information Is the analog value of the present detector Press eft arrow right arrow to switch the loop press down arroW up arrow to increase or decrease the present address of det
16. some fire alarm have not confirmed the bell will be restart Press right arrow to check the detailed fire alarm information as below FIRE ALARM 2 3 Zone 2 smoke detector 2001 Accommodation floor 2 O Room No 201 2011 06 25 17 50 OK Confirm alarm RIGHT Details Alarm device off The place where the fire alarm happens that is the place of the detector the above picture is Room No 201 Time when fire alarm happens the time shown on the above picture is 17 50 June 25 2011 Press eft arrow key to back to the main fire alarm interface Press up page dow n pa ge to check the previous or next fire alarm information Press Status key to check other status information event activate fault disable test and so on see the below illustration JB QBC BS10 Fire Alarm System BSKY JB QBC BS10 Operating Instructions Ca E STATUS 1 Fire alarm 2 Event 3 Activate 4 Fault 5 Disable 6 Test Select a menu with 1 6 Note if fire alarm messages are suppressed to display another type s alarm message the controller will automatically back to the fire alarm display status without any operating in 30 seconds 3 5 FAULT When in the below situation the controller will enter fault status 1 When the wire that connect the controller and detectors is open circuit or short circuit or the disconnect between the detector and bases or the detector was damaged s
17. supervisory sound if the repeater is in mute status the sound is in accordance with the signals JB QBC BS10 Fire Alarm System 35 BSKY JB QBC BS10 Operating Instructions Z ue If the inside sound is open press Mute key you will turn off the inside sound of repeater if you press mute key again if there is unconfirmed fire alarm in the system the inside sound will be restarted When in mute the mute indicator will be illuminated 4 9 SETUP DIMMER Press STATUS UP PAGE or STATUS DOWN PAGE to adjust the lightness of indicator and the brightness of LCD backlight there are four grade of lightness totally 0 is the darkest and 3 is the brightest 36 JB QBC BS10 Fire Alarm System Bskv 5 INTERNAL CODE TABLE JB QBC BS10 Operating Instructions code implication prompt remark 9001 Loop fault 9002 Loop2 fault 9003 Loop3 fault 9004 Loop4 fault 9005 Loop5 fault 9006 Loop6 fault 9007 Loop7 fault 9008 Loop8 fault 9009 Reserved 9010 IReserved 9011 Reserved 9012 Reserved 9013 IReserved 9014 Reserved 9015 IReserved 9016 GA input 9017 IPA input 9018 Backup input 1 9019 Backup input 2 9020 MSBD Fault Check MSBD fuse or switch 9021 ESBD Fault Check ESBD fuse or switch 9022 Ship s DC24V Fault Check Ship s DC24V fuse or switch 9
18. 01 2 New disable 3 Remove all disable shown as below Select a menu with 1 3 Choose New disable to set the new disable firstly you should choose the equipment type please see below picture DISABLE NEW 1 Zone 2 Detector MCP module etc 3 Bell Select a menu with 1 3 There are three kinds of equipment type zone bell and detectors after you have chosen the equipment type the controller will give the equipment list of this type of equipment if you choose disable zone the interface will show the below information DISABLE NEW zone 002 LEFT RIGHT page Ok select 14 JB QBC BS10 Fire Alarm System BSKY JB QBC BS10 Operating Instructions RR After you chose the zone that you want to disable then you chose the time attribute please see the DISABLE NEW below picture 1 permanent 2 periodic 3 clock Select a menu with 1 3 Permanent means this equipment will be disabled forever and will be disabled immediately Periodic means this equipment is disabled periodically you can choose a period in a day when the equipment is disables after this period it will be normal please see the below From time 15 00 Totime 16 00 Clock means from now on to the time that you have set the equipment is disable and the effect is only for one time after the disable function is set they will be shown on disable list DISABLE LIST 001 ZONE 2 smoke detector
19. 023 Charger Fault Connect Vendor 9024 Battery Fault Charge the battery 9025 Battery Disconnect Check the BATTERY fuse and switch 9026 Earth Fault 9027 MAG Door hold line disconnect 9028 Fire 1 Relay 9029 Fire 2 Relay 9030 Fire 3 Relay 9031 Fire 4 Relay 9032 Fire 5 Relay 9033 Fire 6 Relay 9034 Bell 1 9035 Bell 2 9036 PA output 9037 Fault 1 Relay 9038 Fault 2 Relay 9039 Fault 3 Relay 9040 Fault 4 Relay 9041 System Fault Output 9042 Power Fault Output 9043 Alarm delay 9044 PlusFog ZONE 1 9045 PlusFog ZONE 2 9046 PlusFog ZONE 3 9047 PlusFog ZONE 4 9048 PlusFog ZONE 5 9049 PlusFog ZONE 6 9050 PlusFog ZONE 7 JB QBC BS10 Fire Alarm System Z Z uU 37 Bskv JB QBC BS10 Operating Instructions 7 gt aS 9051 PlusFog ZONE 8 9052 PlusFog ZONE 9 9053 PlusFog ZONE 10 9054 PlusFog ZONE 11 9055 PlusFog ZONE 12 9056 PlusFog ZONE 13 9057 PlusFog ZONE 14 9058 PlusFog ZONE 15 9059 PlusFog ZONE 16 9060 System Fault Repeater 1 Fault 9061 Repeater 1 Line Fault Check Communication Line 1 9062 Repeater 1 Line Fault Check Communication Line 2 9063 System Fault Repeater 2 Fault 9064 Repeater 2 Line Fault Check Communication Line 1 9065 Repeater 2 Line Fault Check Communication Line 2 9066 System Fault Repeater 3 Fault 9067
20. 7 28 29 30 Oe System Fault indicator flashing in yellow color This indicator is lit when the system fault EEPROM checksum error CPU fault and so on occur Alarm delay indicator flashing in yellow color When the system is in alarm delay status the indicator is flashing and it will be shut down if the alarm delay count down to zero Alarm device indicator flashing or steady in yellow color If the line connected to the BELLI is broken this indicator is flashing If the BELL is disabled it is steady FPE Running indicator flashing or steady in red color This indicator is used to Indicate the running state of fire protection equipment when some fire extinguishing zones are started it is flashing and it is changed to steady when the controller receive the starting feedback signal FPE Fault indicator flashing or steady in yellow color This indicator is used to Indicate the fault state of fire protection equipment when the fire protection equipment is in fault state and send fault signal to this system the indicator is flashing pressing OK key to confirm it Power indicator steady in green color when the system power on it is lit F1 F4 keys and indicator when press the key the equipment that controlled by these keys will be started and the related indicators will be lit steady in yellow color Menu key press it when you want to test or configure the system or check the history records Exit key
21. Source has supervisory the zone of zone will be isolated please see the above If module 1007 input modules has supervisory alarm then zone 1 is isolated You can set maximally 20 pieces of WORKSPACE 3 13 6 5 SETTINGS This item is used to configure the system running parameter 24 JB QBC BS10 Fire Alarm System BSKY JB QBC BS10 Operating Instructions SS SSS 3 13 6 5 1 FIRE PROTECTION Fire protection is used to set the parameter of protection zone please see the below FIRE PROTECTION 1 Fire protection localbox 2 Fire protection monitor Select a menu with 1 2 Fire protection localbox is used to protect the localbox of the fire extinguishing protection area 01 3005 3006 3007 3007 5001 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 07 0000 0000 0000 0000 LEFT RIGHT page OK detail Remarks Several local operating boxes can be in one zone the places of start and stop are address range e Module is fire sounder for example the above picture means the fire sounder address of first fire protection area is 5001 module2 is the output module that connected to Solenoid valve the above picture means the address of output module that connected to solenoid valve of first protection area is 1008 You can set localbox information for maximally 16 fire protection zones 10 fire protection output zones are in one fire
22. ate the supervisory indicator on the panel If the association is in automatic status it will carry out the associate logic of the logic settings Put the time address and other information of supervisory to history record If the system has a fire repeater it will send supervisory information to fire repeater If the system has a VDR it will send the supervisory information to VDR On supervisory interface you can do the below operations D Press OK key to confirm the supervisory after supervisory is confirmed when focus frame moves to this piece of supervisory information and the supervisory indicator will be 12 JB QBC BS10 Fire Alarm System BSKY JB QBC BS10 Operating Instructions Cau uU CR illuminated or else it is flashing Press right arrow to check detailed supervisory information 3 Press up page or down page to check previous or next supervisory information Press Status key to check other status information After supervisory signals are cleared the supervisory will automatically reset 3 7 ACTIVATE When module is in action or fire extinguishing zone is started or the bell is started the controller will display below information and the interface is as below ACTIVATE 1 1 1 ZONE 2 module 2079 Accommodation floor 2 OK Confirm alarm RIGHT Details MUTE Buzz off SILENCE Alarm device off When an activate information happens beside the displaying on LCD the
23. ation you should chose Save amp Download to board so that the controller will save the configuration information to the panel and download to interface board as well if you chose Save the information will keep to panel this may cause the data difference between the panel and the interface board which may cause mistake as well of course users can choose Download configuration to board in EXCHAGE to synchronize and update the data between the panel and interface board JB QBC BS10 Fire Alarm System 29 BSKY JB QBC BS10 Operating Instructions Z Z uU SSS Remarks You can not do the function to the controller unless one minute later than you have download data to interface board 3 15 USER PERMISSIONS SETTINGS The controller has four levels of permission that is 2 2B 3 4 each function has the lowest permission requirements only the level is the same or higher than the required level then you can do the operation The fourth level is for the service company the permission password od 2 2B and 3 can be changed in user password see the below for the level 4 operation you have to connect the short jumper to of the printed board to 4 LEVEL then start the machine then input the password of level 4 to enter USER PASSWORD User level 2 Password 2 User level 2B Password 2 User level 3 Password 3 3 16 FACTORY SETUP Factory setup is used to restore the factory settings it need
24. d fault check is to check whether Magnetic door hold has disconnection fault Bell fault check is to check whether the bell has disconnection fault Repeater panel sum is the quantity of the repeaters that can be connected to this system it is maximally 4 repeaters Repeater panel fault check is to check whether the fire repeater has connection fault Water mist using is for backup usage Water mist panel fault check is for backup usage PA Close means when there is a PA input do you want to close the PA output if yes it PA output will be closed Earth fault check to check whether the controller has earth fault Earth grade is the sensitivity grade of earth grade 1 10 grade the smaller number the higher sensitivity e using means whether VDR is connected VDR baudrate is the baudrate that communicate with VDR it has 4800 and 9600 types e Ext power fault output means when any of MSBD ESBD Ships DC24V has fault POW FAUI POW FAU2 output or all of ESBD Ship s DC24V have fault the POW FAUI POW FAUZ2 will output 3 13 6 6 EXCHANGE Exchange is used to download upload the configuration data see the below EXCHANGE 1 Download configuration from USB 2 Upload configuration to USB 3 Download configuration to board Select a menu with 1 3 Download configuration from USB is to download the configuration data from USB memory see the
25. e The total alarm message the above means 3 fire alarm message in this system First fire alarm information display zone It is remain although the up page or down page key pressed Zone in which first fire alarm happens For example the above zone is zone 1 The device type that send out first fire alarm for example the above picture is smoke detector Address of the first fire alarm device the above address is 004 in loop 1 The first fire alarm zone s description for example the above is bridge Fire alarm information display zone for example the above picture shows the second piece of fire alarm information and the message is the similar with first fire alarm information press up page or down page key to check last or next fire alarm message Operation help message display zone Alarm delay count down display zone After fire alarm happens besides the above fire alarm information was shown on LCD the controller will act as below JB QBC BS10 Fire Alarm System 9 BSKY JB QBC BS10 Operating Instructions up RU M SSS Give fire alarm sound and illuminate the fire indicator on the panel Fire alarm output relay FIRE1 FIRE6 output OOO When bell begins count down the Alarm Delay indicator is flashing after count down is finished the Alarm Delay will be illuminated and the bell is started if the fire alarm is from the manual call point it is started without delay If Associat
26. ection and fire alarm systems Part 10 Flame detectors Point detectors gt EN54 11 2001 A1 2005 Fire detection and fire alarm systems Part 11 Manual call points IEC60092 504 2001 Electrical installation in ships Part 504 Special features control and instrumentation gt 1 60533 1999 Electrical and electronic installations in ships Electromagnetic compatibility gt MSC 1 1387 2010 replace MSC CIRC 913 DNV SfC 2 4 ENVIRONMENTAL TEST SPECIFICATION FOR INSTRUMENTATION AND AUTOMATION EQUIPMENT JB QBC BS10 Fire Alarm System Bskv 3 FIRE ALARM CONTROLLER JB QBC BS10 Operating Instructions Z S SSS SSS 3 1 FRONT PANEL OF FIRE ALARM CONTROLLE 4 99998 3 FIRE 1 gt CO i 5 J BSK Y CO BH Disabled Condition BT Wisk Test Condition Sane 23 LL CO Fault eee j Le 63 9 CO Alarm Delay o FXR Alarm Device gt TCO enm FPE Running 22 10 FPE Fault 7 Power 12 ae i end ipe l iud aet atu eU 13 FY XP Men E 20 3 Exit 4 5x 6mo 14 9 F3 Bii Disable 7 pars 8 wv 9 wwz Sa
27. ectors 3 13 6 SERVICE This item is used to configure the parameter for the system following is the picture for it SERVICE 1 Detector information 2 Zone information 3 Logic 4 Workspace 5 Settings 6 Exchange 7 User password Select a menu with 1 7 JB QBC BS10 Fire Alarm System 21 BSKY JB QBC BS10 Operating Instructions S SSS 3 13 6 1 DETECTOR INFORMATION Detector information function is to inquire register or edit the equipment information you can also register the equipment manually or automatically please see the below picture DETECTOR INFORMATION 1002 1003 1004 1005 1006 2001 2002 2003 2004 2005 2006 5001 5002 5003 5004 5005 OK detail 1 new 2 del 3 register Press OK key to inquire and edit the equipment information please see the below DETECTOR INFORMATION Device number 1001 Type somke detector Alarm grade 000 Zone 001 Description bridge left OK confirm LEFT RIGHT change type Remarks Device number is the equipment number for example the above is number 1 of loop 1 is equipment type for example the above is smoke detector Zone is the zone number if the equipment for example the above No 1001 detector belongs to zone 1 Description is the description to the place where the equipment is installed for example the above means that No 1001 detector is installed in bridge left There are 40 characters
28. four grades of permission for this operation FACTORY SETUP 1 Clear history 2 Clear configuration data 3 User password 4 Controller or Repeater see the below Select a menu with 1 4 e Clear history is used to clear fire alarm history Clear configuration data is used to clear configuration data User password is used to change different grades of permission password except the forth permission 30 JB QBC BS10 Fire Alarm System BSKY JB QBC BS10 Operating Instructions This panel be used both as controller and repeater From Factory setup gt Controller or Repeater you can set the working type see the below FANEL TYPE 1 2 Panel type controller Panel address Status change type If the panel type is repeater you have to set the address of the repeater The Silence Reset key of the panel in repeater type has the same function with the keys on controller you can through the repeater to make the bell silence and also reset the controller the function is similar to repeater and it keeps all the functions of the first grade permission of controller meanwhile it adds the silence and reset function of grade two permission but it does not have the activate disable and test functions of grade two permission and also all the functions of grade 3 permission JB QBC BS10 Fire Alarm System 31 BSKY JB QBC BS10 Operating Instr
29. he changed descriptions directly in description of detector information for example the above picture shows that module 4012 has detected that the pump is in fault then it can be described as pump fault when module 4012 alarms pump fault Ext In will be shown on the description place of fault if module 4012 itself has a problem for example disconnection then pump fault will be shown on the fault 3 13 6 5 3 DELAY Delay is used to set delay functions see the below DELAY 1 3 Bell delay S Mute restart delay s Silence restart delay s OK confirm Remarks Bell delay is the delayed time of bell started after fire alarm usually it is 120 seconds Mute restart delay is after the mute of the controller if there is unconfirmed fire alarm and the inside sound will be restarted after some time the above is 900 seconds Silence restart delay is after the silence of the bell if there is some unconfirmed fire alarm the bell will be restarted after some time the above is 900 seconds 3 13 6 5 4 SHORT KEY Short key is used to set the output modules that corresponding to F1 F4 on the panel 26 JB QBC BS10 Fire Alarm System BSKY JB QBC BS10 Operating Instructions C C SHORT KEY Key F1 5001 0000 0000 0000 0000 Key F2 0000 0000 0000 0000 0000 Key F3 0000 0000 0000 0000 0000 Key F4 0000 0000 0000 0000 0000 XRemarks Each key corresponds to the five
30. he fire alarm status and the LCD will display as below JB QBC BS10 Fire Alarm System 33 BSKY JB QBC BS10 Operating Instructions Zone 2 smoke detector 2001 Accommodation floor 2 2011 06 25 17 50 MUTE Buzz off Remarks Is the interface type for example the above is the fire alarm interface Shows the present focus frame is on which piece of fire alarm information For example the above shows that the focus frame is on the second piece of fire alarm information s the present total quantity of fire alarm information the above picture shows that the present total quantity of fire alarm information is 3 The zone that the first fire alarm information displays in this system the first fire alarm information is shown on the fixed zone no matter how to turn over the page the first fire alarm information is always shown in this place The zone where first fire alarm happens the above is zone 1 The device type of the first fire alarm happens the above is smoke detector The address of the first fire alarm the above is number 4 of loopl The description to the zone of the first fire alarm the above is bridge The time when the first fire alarm happens the above is 17 50 of June 25 2011 The display zone of fire alarm information the above is the second piece of fire alarm information the format is the same as the first fire alarm information Prompt information display zone When recei
31. heck previous or next fire alarm information 2 Press Mute key to clear the inside sound of fire repeater 3 Press Status key to check other type of alarm information 4 6 OTHER ALARM Repeater can receive SUPERVISORY ACTIVATE DISABLE TEST and other information the display format and the operation way is the same as that in fault status STATUS PRIORITY The repeater follows the turn of Fire Supervisory Activate Fault Disable Test to show grade from high to low arrangement information high grade status display takes precedence That is to say when in low grade interface if there is high grading information coming then the interface will be immediately switched to high grade display status Press status key to switch the interface board from the high to low grade If the interface of the repeater is not showing the latest fire alarm information and the system has a fire alarm the repeater will switch to the latest fire alarm interface automatically if there is no any operation after 30 seconds 4 7 RESET The repeater can be reset only after it get the instruction from fire controller 4 8 MUTE The repeater can give two kind of sound from inside In fire alarm and supervisory it will give a continuous buzzing In fault status it will give a interrupted buzzing The sound of fire and supervisory is prior to the sound of fault even if a fault happens when a fire or supervisory signals come the repeater will come to fire
32. indicator is illuminated in this situation Press Lock key and enter the password then you can unlock the controller 3 13 MENU Press menu key to enter the main menu see the below picture 1 Date amp Time 2 History 3 Service 3 Level 4 System version 5 Detector test 6 Setup dimmer Select a menu with 1 6 When the interface is on any grade of the menu D When there is a fire if there is no any operation on the controller after 30 seconds the interface will switch to the latest fire interface automatically When detect the fire the controller will immediately enter the fire status and the interface will immediately come to fire alarm interface as well 3 When there is no any fire alarm happens if there is no any operation on the controller after 30 seconds it will exit from Menu automatically 18 JB QBC BS10 Fire Alarm System BSKY JB QBC BS10 Operating Instructions 75 S _ 1 3 13 1 ADJUST TIME From Menu gt Date amp Time you can adjust the time of the controller and the format of the time is year month day hour minute second DATE amp TIME 2011 06 27 10 17 52 OK confirm 3 13 2 HISTORY RECORD From Menu gt history you can inquire more fire alarm history the recorded type of controller is Fire Supervisory Activate Fault Disable Test The controller can record 999 pieces of fire information and 999 pieces of other information The i
33. ion Other settings gt Association auto status is in automatic status and the association logic of logic setting will be carried out Put the time and place and other information of fire alarm to history record If a fire repeater Other settings gt Repeater panel sum is connected it will send fire alarm information directly to the fire repeater If a VDR Other settings gt VDR using is connected it will send fire alarm information to VDR In fire alarm status the below operations can be achieved 10 Press OK key to confirm fire alarm after confirmation when focus frame moves to this piece of fire alarm information the fire indicator is illuminated or else it is flashing Press Mute key to turn off the inside sound of the controller press mute key again if there are some fire alarm have not been confirmed yet the inside sound will be restart If you set delay restart Delay gt Mute restart delay after you turn off the inside sound if there are fire alarm that have not been confirmed the controller will give alarm sound after the delay time 8 Press Silence key if the bell is in start status then the bell is turned off if it is in count down status the counting down is stopped if you press silence key again if there are some fire alarm has not been confirmed the bell will be restart Beside this if you set the silence delay restart Delay gt Silence restart delay if after the delay time there are
34. k previous or next alarm information 3 Press Status key to check other status information Test alarm can automatically reset for example after all smokes scattered to the air the test alarm status of smoke detector can automatically reset STATUS PRIORITY The control panel follows the turn of Fire Supervisory Activate Fault Disable Test to show grade from high to low arrangement information high grade status display takes precedence That is to say when in low grade interface if there is high grading information coming then the interface will be immediately switched to high grade display status 3 10 RESET If there is a fire fault supervisory happens press Reset key to reset this status if the elements that caused this status still existing this status will happens again after reset for example if a smoke detector alarms if you press the reset when the smoke still existing in the smoke detector the controller will alarm again When Activate happens press reset key to turn off all the started equipment Disable is not affected by reset When the controller is reset the test zone that you set will be cleared 3 11 MUTE SILENCE The controller can send out two type sounds continuous sound or fire alarm or supervisory alarm When in fire alarm and supervisory status it will give a continuous buzzing JB QBC BS10 Fire Alarm System 17 BSKY JB QBC BS10 Operating Instructions Z up ERU UU c
35. ll disable Test 2B Test zone list New test zone Remove all test zone Menu 2 Date amp Time 2 History 2 Service 3 Detector information Zone information Logic Workspace Settings Fire protection Alarm type Delay Short key Other settings Exchange Download configuration from USB Upload configuration to USB Download configuration to board User password System version 2 Detector test 2 Write detector address Read detector address Test detector analogy Test loop detector Setup dimmer 2 Remark The number in the bracket after the item is access level 8 JB QBC BSI0 Fire Alarm System BSKY JB QBC BS10 Operating Instructions SSS 3 3 STARTUP Turn on the power and the controller will be power on and enter standby status see the below display of the LCD 2011 06 25 18 36 JB QBC BS10 Fire Alarm Control Panel System Normal 3 4 FIRE ALARM When the thickness of smoke or temperature are larger than the alarm limit or press the manual call point manually the control panel will be in fire alarm status and the LCD display will show as the below 5 Zone 1 smoke detector 1004 8 bridge Zone 2 smoke detector 2001 Accommodation floor 2 OK Confirm alarm RIGHT Details 11 a E Alarm device off Is the type of the alarm status for example the above is the fire alarm The fire alarm information s number For example the above is the second fire alarm messag
36. maximally Press numbering key 7 to register the new equipment manually DETECTOR INFORMATION 1002 1003 1004 1005 1006 2001 2002 2003 2004 2005 2006 5001 5002 5003 5004 5005 input device number 0000 OK confirm Press numbering key 2 to delete the equipment that you have chosen from the registered equipment Press numbering key 3 to register the equipment manually please see the below 22 JB QBC BS10 Fire Alarm System BSKY JB QBC BS10 Operating Instructions Z Z CC C REGISTER Register Please waitting 1 The controller will automatically scan the equipment that connected to the bus and record the equipment type when in automatic register status when the system is installed for the first time you can inquire the quantity of devices address and type of the installed devices throng checking automatic register function which make it more simple 3 13 6 2 ZONE INFORMATION Zone information function is used to inquire and edit the present zone information of the system please see the below ZONE INFORMATION m 6 zone 001 zone 002 LEFT RIGHT page OK detail Remarks The zone list here is the zone number you set for the detectors in detector information you can not add new zone here Press OK key to inquire and edit the zone information that you have chosen please see the below ZONE INFORMATION Zone 001 Desc
37. n fire protection control board Manual control mode The function is the same with fire protection function in 3 13 6 5 1 For example 2 detectors in one water mist zone the addressed are 1001 and 1002 the address of AV sounder in relative zone is 1005 Fire protection control board is connected to loop 4 the address of the modules in fire protection control board is from 4001 to 4010 the 4001 module is used to control the zone s valve One local operating box is installed in this zone the start key s address is 1006 and the stop key s address is 1007 For auto start mode refer to the following logic setting figure in this case the 1001 and 1002 detectors send out fire alarm at the same time the 1005 and 4001 module will be started LOGIC Sum 002 Logic Source Activate 001 AND 1001 1002 1005 1005 002 AND 1001 1002 4001 4001 LEFT RIGHT page OK detail 1 new 2 del For manual start mode refer to the following fire protection local box setting figure In this case press the start button address 1006 to start the modules 1005 and 4001 press the stop button address 1007 to stop the 1005 and 4001 module 01 1006 1006 1007 1007 1005 4001 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 7 LEFT RIGHT page OK detail 40 JB QBC BS10 Fire Alarm System ZrEnES ABS ARS WUXI BRIGHTSKY ELECTRONIC CO LTD Luoshe Town Wuxi Cit
38. nterface of history record is shown as below HISTORY 1 Fire alarm history 010 2 Other alarm history 119 Select a menu with 1 2 FIRE ALARM HISTORY 010 FIRE ZONE 2 smoke detector 2001 Accommodation floor 2 2011 06 25 17 50 FIRE ZONE 1 smoke detector 1004 bridge 2011 06 25 17 49 LEFT RIGHT page Remarks The type of history record the above is fire The zones in which the fire alarm happens the above is zone2 The time when the alarm happens the above is 17 50 June 25 2011 JB QBC BS10 Fire Alarm System 19 BSKY JB QBC BS10 Operating Instructions OO uU OTHER ALARM HISTORY 119 DISABLE ZONE 2 smoke detector 2001 Accommodation floor 2 2011 06 26 13 50 FAULT ZONE 1 smoke detector 1004 bridge 2011 06 26 12 49 LEFT RIGHT page 3 13 3 VERSION INFORMATION From Menu gt System version you can inquire the software version of the controller and the update date of the accessory equipment See the below picture SYSTEM VERSION Software ver 1 001 Configuration data update data 2011 06 20 08 04 3 13 4 SETUP DIMMER From Menu gt Setup dimmer you can set the lightness of indicator and the LCD backlight there are 4 grades of lightness 0 is the darkest 3 is the brightest SETUP DIMMER 3 13 5 DETECTOR TEST You can write the address Programming read the address or read the Analog value through Menu gt Detector Test you can also test the running status
39. o that the monitoring between the detector and controller is abnormal 2 The wire connect the controller and fire repeater is open circuit or short circuit which cause the abnormal communication 3 Line broken between the controller and the bell 4 Main power supply emergency power supply DC24V charging fault battery low voltage or disconnection earth fault 5 MAG Door hold line disconnect 6 Wrong device type 7 Device not included in the configuration 8 Flash checksum error 9 EEPROM checksum error 10 The communication fault that caused by the open circuit short circuit between Control panel and interface board 11 Abnormal communication that caused by the open circuit or short circuit between Interface board and Loop board 12 DC24V fault for fire alarm control panel or fire alarm repeater In fault status the LCD displays as below FAULT 1 1 1 ZONE 2 smoke detector 2001 Accommodation floor 2 OK Confirm alarm RIGHT Details MUTE Buzz off SILENCE Alarm device off After fault happens besides the fault information in LCD the controller will carry out below actions JB QBC BS10 Fire Alarm System 11 BSKY JB QBC BS10 Operating Instructions Cau up ERU UU _ _ D Give fault sound and the fault indicator on the panel is illuminated FAULTI FAULTA of the fault output relay will output for some fault system faultl system fault2 will output as well please see the detailed fault description list 3 Put
40. ow color This indicator is used to Indicate the fault state of fire protection equipment when the fire protection equipment is in fault state and send fault signal to this system the indicator is flashing pressing OK key to confirm it 13 Power indicator steady in green color when the system power on it is lit 14 Down page key press it to check next alarm message 15 Status key use to change the alarm status display fire alarm activities activate fault disable or test 16 Up page key press it to check last alarm message 17 Mute key it is used to stop or restart the internal buzz in the fire alarm control panel when the internal buzz is started 18 Lamp test key use to test all indicators on the fire alarm control panel all the indicator will be lit if this key pressed 19 LCD display all messages are displayed in this area 4 2 ADDRESS SETTING You can use the repeater only after you have set the address press the back cover switch SW1 to the address that you want to set according to the capacity of BS10 the system can connect four repeaters maximally so the address should be from 1 to 4 4 3 STARTUP Turn on the power and the repeater will be power on and enter to the standby status and the LCD will display as the below JB QBC BS10R Fire Alarm Repeater Panel System Normal 4 4 FIRE ALARM When repeater receive the fire alarm information that sent from the fire controller it will enter t
41. protection control board If the fire protection zone number is larger than 10 please add input output module Fire protection monitor is used to set the address f input modules which is used to monitor pump status see the below FIRE PROTECTION MONITOR 1 2 CPE input module 4008 FPE input module OK confirm Remarks e CPE input module is the input module that used to detect the running status of protection area input module is the input module that used to detect the fault status of pump JB QBC BS10 Fire Alarm System 25 BSKY JB QBC BS10 Operating Instructions Cau ERU UU UR 3 13 6 5 2 ALARM TYPE Alarm type is used to change the alarm type of input modules in general the input module alarm is supervisory but in some cases the alarm of input module should be fault as well for example we use the input module to monitor the fault status of pump if this input module alarms it is better to show the alarm as fault because it is indicate that the pump is in fault The interface of alarm type is shown as below ALARM TYPE Sum 001 Address New Alarm Type 001 4012 Fault LEFT RIGHT page OK detail 1 new 2 del Remarks For the above picture when there is there is signals input to number 4012 signal input modules the alarm signals will be taken as fault You can set maximally 100 pieces of alarm type For the equipment that needs to change the alarm type you can input t
42. ription Bridge Device list 1001 1002 gt lt Remarks Zone description can has maximally 40 characters Device list is an format that the controller generated automatically according to the zone number of the detector information JB QBC BS10 Fire Alarm System 23 BSKY JB QBC BS10 Operating Instructions 3 13 6 3 LOGIC Logic function is used to set the controlling functions that the controller has to carry out after the fire alarm or supervisory happens LOGIC Sum 001 001 OR1 1001 1002 5001 5002 LEFT RIGHT page OK detail 1 new 2 del XRemarks There are three types if logic ORI OR2 AND ORI means if any detector give alarm in source range then all the equipment in Activate will start OR2 means if any two of the detector give alarm then all the equipment of Activate will be started AND means if all the detectors of source range give alarms then all the equipment of Activate will be started The equipment of Activate are usually input or output modules You can set maximally 150 pieces of LOGIC In Menu gt Service gt Settings gt Other gt Association auto status only it is automatic status the logic setting can be carried out 3 13 6 4 WORKSPACE WORKSPACE function is used to isolate one zone quickly please see the below WORKSPACE Sum 001 001 1007 001 LEFT RIGHT page OK detail 1 new 2 del XRemarks If the equipment of
43. the time address and other information of the fault to the history record 4 If the system has a fire repeater it will send fault information to fire repeater Ifthe system has a VDR it will send fault information to VDR as well You can do the below operation on fault interface Press OK key to confirm the fault after the fault information is confirmed when the focus frame moves to this piece of fault information the fault indicator will be illuminated or else it is flashing 9 Press Mute key to turn off the inside sound of the controller Press right arrow key to check the detailed fault information D Press up page or dow n page key to check previous or next fault information 2 Press Status key to check other status information Except system fault all other fault can be reset automatically after fault signals is cleared you can only reset manually for system fault 3 6 SUPERVISORY Supervisory signal is the input signals except fire signals and fault signals such as the alarm of input modules feedback of input output modules and so on when controller receives this signals it will enter the supervisory status and the LCD displays as below SUPERVISORY 1 1 1 ZONE 2 module 2078 Accommodation floor 2 OK Confirm alarm RIGHT Details MUTE Buzz off SILENCE Alarm device off After enter supervisory status except the supervisory information shown on the LCD the controller will act as below Illumin
44. tomatically control the fixed water based local application fire fighting system This system can be easy to be operated The fire alarm system is composed with the following parts fire alarm controller fire alarm repeater addressable smoke detector addressable heat detector IR flame detector manual call point disable input device isolator input module and input output module Max two loop boards can be used in the controller each loop board supports 4 loop maximum 160 points can be connected to each loop 4 JB QBC BS10 Fire Alarm System BSKY JB QBC BS10 Operating Instructions Z uU CR 2 STANDARDS gt MSC 311 88 AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS FSS CODE CCS Guidelines for Type Approval Test of Electric and Electronic Products 2006 gt CCSGD01 Guidelines for Type Approval Test of Electric and Electronic Products 2006 gt EN54 2 1998 A1 2006 Fire detection and fire alarm systems Part 2 Control and indicating equipment gt 54 4 1997 1 2002 A2 2006 Fire detection and fire alarm systems Part 4 Power supply equipment gt EN54 5 2000 A1 2002 Fire detection and fire alarm systems Part 5 Heat detectors Point detectors gt EN54 7 2000 A1 2002 42 2006 Fire detection and fire alarm systems Part 7 Smoke detectors Point detectors using scattered light transmitted light or ionization gt EN54 10 2001 A1 2005 Fire det
45. uctions Cau ERU UR d 4 FIRE ALARM REPEATERU Fire alarm repeater is used to display all alarm messages occurred in the fire alarm system 4 1 FRONT PANEL OF FIRE ALARM REPEATER e M ON JB QBC BS10R FIRE N BSKY 5 FIRE gt CO Fault ON in Disabled LN Test Condition 7 CO Supervisory c Fault he c ALAR ESBD Fault 8 115 SEHD System Fault 19 9 FREER Alarm Del ay V _ FOR 888 Alarm Device 0 77 T ER AHR Rumi ng MU LAP BRHRERE FPE Fault D We PAN 3 ea Ie we grim Status Mute Lamp Test 1 1 Fire indicator flashing or steady in red color the fire indicator is flashing to indicate that the current fire alarm is not confirmed It turn to steady if the current alarm is confirmed by pressing OK key 2 Fault indicator flashing or steady in yellow color the fault lamp is flashing to indicate that the current fault alarm is not confirmed It turn to steady if the current alarm is confirmed by pressing OK key 3 Disabled Condition indicator steady in yellow color When the system is in disabled condition this indicator will be lit 4 Test Condition indicator steady in yellow color When some zones in the system is set to test condition this indicator will
46. use test function set the zone in Test function press Test key to set the set please see the below picture 1 Test zone list 001 2 New test zone 3 Remove all test zone Select a menu with 1 3 Choose New Test Zone to set the zone that you want to test for example ZONE LIST zone 002 LEFT RIGHT page Ok select For the test zone that you have chosen you can see them from test zone list please see below TEST ZONE LIST a zone 002 LEFT RIGHT page 1 remove test zone For the zone that is set test the Test indicator is illuminated if there is a detector in this zone the controller will enter test alarm status the display is shown as below 16 JB QBC BS10 Fire Alarm System BSKY JB QBC BS10 Operating Instructions Cau up S M TEST 1 1 1 ZONE 2 smoke detector 2001 Accommodation floor 2 OK Confirm alarm RIGHT Details MUTE Buzz off SILENCE Alarm device off Besides the alarm information of the test zone the controller will act as below D Put the time address and other information of test to the history record It the system is connected with a fire repeater it will send the test alarm information to fire repeater Ifthe system has a VDR it will send test alarm information to VDR On test interface you can do the below operation D Press right arrow to check the detailed test information Press up page dow n page to chec
47. ve the fire alarm information the repeater will illuminate the indicator on its panel and give continuous buzzing The confirmation status of the control panel is the same as the repeater if you have confirmed certain piece of fire alarm when the focus frame moves to this piece of confirmed information of the repeater the fire alarm indicator will be illuminated or else it is flashing this function is the same for supervisory and fault as well You can do the below operation on fire alarm interface D Press up page or dow n page to check previous or next fire alarm information Press Mute key to clear the inside sound of fire repeater if there still unconfirmed fire alarm after mute the inside sound will be restarted after you press Mute key again 3 Press Status key to check other type of fire alarm information such as supervisory Activate Fault Disable Test and so on 34 JB QBC BS10 Fire Alarm System BSKY JB QBC BS10 Operating Instructions 75 S SSS 4 5 FAULT When the fire repeater receive the fault information that sent from the fire controller it will enter fault status see the below FAULT 1 1 1 ZONE 2 smoke detector 2001 Accommodation floor 2 2011 06 25 18 10 MUTE Buzz off When receive the fault information the repeater will illuminate the fault indicator on its panel and give a interval buzzing You can do the below operation on the fault interface Press up page down page to c
48. y Jiangsu Province China PC 214187 Tel 86 510 8331 1597 Fax 86 510 8330 7870 E mail brightsky bsky cn Http www bsky cn