Tripp Lite SmartOnline SU1000RT2UHV User's Manual
Contents
1. Equipment Connection Warning e Do not use Tripp Lite UPS Systems for life support applications in which a malfunction or failure of a Tripp Lite UPS System could cause failure or significantly alter the performance of a life support device Battery Warnings e Your UPS does not require routine maintenance Do not open your UPS except to replace batteries There are no user serviceable parts inside e Battery replacement should be performed by qualified service personnel Because the batteries present a risk of electrical shock and burn from high short circuit current service personnel should observe proper precautions Use tools with insulated handles remove all metal hand jewelry and when possible work with only one hand to reduce the danger of shock Replace the existing batteries with an equal number of new batteries of the same type Do not open the sealed lead acid batteries Do not short or bridge the battery ter minals with any object e The UPS batteries are recyclable Refer to local codes for disposal require ments or in the USA only call 1 800 SAV LEAD 1 800 728 5323 for com plete recycling information Do not dispose of the batteries in a fire The UPS contains its own energy source battery The output terminals may be live even when the UPS is not connected to an AC supply Only connect Tripp Lite battery packs of the correct voltage to your UPS s external battery connectors e Do not connect or disconnect external
2. an electrical outlet If your model features a detachable line cord first plug the female end into your UPS s AC Input Receptacle Your UPS must be connected to a dedicated circuit of sufficient amperage check the Recommended Utility Amps rating of your model in the specifications Note however SU2200RT2U Plug NEMA 5 20 Shown that the select models may be fitted with differ ent plug types Refer to the OP Rating Plug Rating chart printed on the top of your UPS Once your UPS is plugged in the fan and all Indicator Lights will turn ON The LINE and LOAD ACTIVE METER LEDs will illuminate and the UPS will emit a beep to indicate nor mal operation However power is not supplied to your UPS s AC outlets until the UPS is turned on 2 Plug your equipment into your UPS Your UPS is designed to support computer equipment only You will overload your UPS if you connect household appliances or laser printers to the UPS s outlets SU2200RT2U Shown 3 Turn your UPS ON e Press the ON TEST Switch e Hold it for several seconds until you hear a beep e Release it Your UPS will begin providing AC power to its outlets The ON LINE LED will illuminate Optional Connections Your UPS will function properly without these connections Serial Port Connection Using the serial cable provided connect a seri al port on your computer to the s
3. battery packs while the UPS is operat ing from battery e Do not operate your UPS without batteries METET Rackmount 1 Loosen the wingnuts on each of the two UPS Side Supports adjust the length of the supports to match the depth of your rack tighten wingnuts 2 Mount both UPS Side Supports in your rack on the inside surfaces of the rack rails Note Both support ledges should face inward The side supports front and back holes are threaded and do not require nuts to secure rack bolts 3 Attach mounting ears to the front end of the UPS s sides using the screws provided 4 Lift UPS and slide it onto the UPS Side Supports within your rack Mount the UPS by screwing rack bolts through the UPS mounting ears through the rack rails and through the UPS Side Supports Note The side supports front holes are threaded and do not require nuts to secure rack bolts SU2200RT2U Shown OOprA A ApoOo Vertical Tower Mount 1 Cover the rackmount screw holes on the UPS s sides with supplied snap in hole cover caps 2 Place the UPS upright in a flat sta ble location with its control panel on the high corner facing forward Position stabilizer feet 4 in from each end of the UPS Connection amp Start Up D Plug your UPS s Line Cord into
4. EDs will illuminate for ten seconds Alarm Silence To silence the UPS on battery alarm press this switch and hold it until you hear a beep UPS Cold Start To use your UPS as a stand alone power source when AC power is unavailable i e during a blackout press this switch and hold it until you hear a beep The UPS will then provide battery power to its out lets The ON BATT Indicator Light will be illuminated since your UPS will be operating from battery power OFF Switch This switch turns power OFF at the UPS receptacles Press this switch hold it until you hear a beep then release it The UPS will continue charging and the fan will continue to cool internal com ponents even after you turn the UPS receptacles off To turn the UPS OFF completely including the charger disconnect the UPS s power cord after pressing the OFF switch Front Panel Indicator Lights ON LINE LINE ON LINE LED This green light will illuminate constantly to indicate the UPS is performing normal on line operation filtering and resyn thesizing incoming AC line voltage to provide pure sine wave output When this light is illuminated you can monitor the load level of your UPS on the LOAD ACTIVE METER LEDs LINE LED This green light will illuminate constantly to indicate the utility supplied AC line voltage at your wall outlet is nominal It will flash if the line voltage is outside the nominal r
5. TRIPP LITE Owner s Manual POWER PROTECTION S M A RTO N LI N E 1111 W 35th Street n a A Rack Tower Mount ustomer Support 77 n www tripplite com Online UPS Systems ESPA OL p 13 FRAN AIS p 25 DEUTSCH p 37 Important Safety Instructions p 2 Installation p 3 5 Basic Operation p 6 9 Battery Replacement p 10 Storage amp Service p 11 Specifications p 11 12 Copyright 2001 Tripp Lite All rights reserved SmartOnline is a trademark of Tripp Lite Important Safety Instructions SAVE THESE INSTRUCTIONS This manual contains important instructions and warnings that should be followed while installing operating amp storing all Tripp Lite UPS Systems UPS Location Warnings e Install your UPS indoors away from excess moisture or heat conductive contaminants dust or direct sunlight e For best performance keep the indoor temperature between 32 F and 104 F between 0 C and 40 C e Leave adequate space around all sides of the UPS for proper ventilation UPS Connection Warnings e Connect your UPS to a properly grounded AC power outlet Do not remove or modify the ground connector of your UPS s plug Do not use two prong adapters with the UPS s plug Do not plug your UPS into itself this will damage the UPS and void your war ranty If you are connecting your UPS to a motor powered AC generator the genera tor must provide clean filtered computer grade output
6. ange either too low or two high No action is required on your part when the LED flashes the UPS continuously and automatically filters AC line power to provide your equipment with pure sine wave AC power regardless of brownout or overvoltage conditions If this light is off then AC line voltage is not present blackout or is at an extremely high voltage and the UPS will provide connected equipment with power from battery Front Panel Indicator Lights Continued BYPASS FAULT i gt S amp gt 4 OVERLOAD BATT LOW gt ie e BATT REPLACE BATT BYPASS LED This yellow light will illuminate to indicate that the UPS s DC AC inverter is deactivated and the UPS is in the Bypass mode During normal operation this LED will light briefly when the unit is plugged in but if an internal fault occurs this light will illumi nate constantly to show that connected equipment will receive filtered AC mains power but will not receive battery power during a blackout In this case contact Tripp Lite for service FAULT LED Select Models Only This red light will flash when your UPS detects an internal fault overheating overvoltages etc or when it detects a wiring fault in your wall outlet reversed phases missing ground etc If the light persists after restarting the UPS con tact an electrician to check the AC line Your UPS will identify the presence of most but not all wiring
7. erial port of your UPS Install Tripp Lite s PowerAlert soft ware provided on CD on the computer E SU2200RT2U Shown External Battery Pack Connection Ce Check to ensure that the external batteries you Ja Rod are connecting match the voltage listed on your BREAKER EATERY DC 72V 26A UPS s battery connector Plug either end of the battery connection cable supplied with the bat tery pack into the UPS s External Battery F7 z we Connector and the other end into the Battery I A Output Connector on the rear panel of the Ee external battery pack SU2200RT2U Shown Since your UPS has internal batteries external batteries are only needed to extend runtime Adding external batteries will increase recharge time as well as runtime Make sure that each end of the cable is fully inserted into its con nector Several small sparks may result during battery connection this is normal Basic Operation Front Panel Switches ON TEST Switch This switch controls four separate UPS functions UPS Power ON To turn the UPS on press this switch hold it for several seconds until you hear a beep then release it The ON LINE LED will illuminate UPS Self Test During normal on line operation press this switch and hold it until you hear a beep This initiates a 10 second self test of the battery The UPS will shift to battery power the ON BATT and BATT ACTIVE METER L
8. extend ed period of time fully recharge the UPS batteries once every three months by plugging the UPS into a live AC outlet and letting the UPS charge for 4 6 hours If you leave your UPS batteries discharged for an extended period of time they may suffer permanent loss of capacity Service If returning your UPS to Tripp Lite please carefully pack the UPS using the ORIG INAL PACKING MATERIAL that came with the unit Enclose a letter describing the symptoms of the problem If the UPS is within the 2 year warranty period enclose a copy of your sales receipt Specifications All Models Input Frequency 50 60 Hz Auto Selecting Output Waveform in Line and Battery Modes Pure Sine Wave Transfer Time 0 ns Maximum Harmonic Distortion with Linear Load lt 3 Maximum Harmonic Distortion with Nonlinear Load lt 6 Battery Recharge Time to 80 Capacity 2 4 hours Model SU1000RT2U SU1000RT2UHV Input Voltage 120V 200 208 240V Input Breaker Rating 15A 8A Input Plug Type 5 15P 6 15P Recommended Utility Amps 15A 15A Output Capacity VA Watts 1000 800 1000 800 Battery Runtime Half Load Full Load Min 18 6 18 6 System Battery Voltage 36 VDC 36 VDC Approvals UL cUL FCC NOM UL cUL FCC NOM Model SUINT1000RT2U SU2200RT2U Input Voltage 220 230 240V 120V Input Breaker Rating 8A 30A Input Plug Type IEC 320 014 5 20P Recommended Utility Amps 10A 20A Output Capacity VA Watts 1000 800 2200 1600 Batter
9. faults LOAD ACTIVE METER LED This green light will illuminate when your UPS is receiving AC power to indicate that the set of four dual function LEDs is displaying the load level of your UPS BATT ACTIVE METER LED This green light will illuminate when your UPS is operating from battery power to indicate that the set of four dual function LEDs is displaying the battery charge level of your UPS Note the ON BATT LED will also be illuminated OVERLOAD LED This red light will illuminate constantly to indi cate that your UPS s capacity has been exceeded while it is in on line operation The UPS alarm will beep continuously Immediately remove overload until light and alarm goes off If you do not immedi ately remove the overload the UPS will transfer from on line to bypass operation BATT LOW LED This yellow light will illuminate when your UPS s battery charge level is low The UPS alarm will beep until either the battery charge is depleted or the batteries are adequately recharged ON BATT LED This green light will illuminate constantly to indicate that AC line voltage is not present and your UPS is providing your equipment with battery power The UPS will also beep every two sec onds unless silenced by the ON TEST Switch When this light is illuminated you can monitor the battery charge level of your UPS on the BATT ACTIVE METER LEDs REPLACE BATT LED This red light will i
10. ired operation This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radi ate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause 12
11. lluminate constantly and the UPS alarm will sound three beeps if your UPS s microprocessor detects a battery fault or if your UPS fails the automatic self test after you turn your UPS ON and the UPS battery is less than fully charged Turn the UPS OFF and let it charge for 12 hours and turn it back ON to perform a second self test If the light continues to stay on contact Tripp Lite for service After the initial alarm the UPS will beep once every hour until the problem is corrected Rear Panel Accessory Slot Remove the small cover panel from this slot to use optional accessories to remotely monitor and control your UPS Contact Tripp Lite Customer Support at 773 869 1234 for more information including a list of available SNMP network management and connectivity products SMART Serial Port This serial port connects your UPS to any work station or server Use with Tripp Lite software and cabling to monitor and manage network power and automatically save open files and shut down equipment during a blackout The port uses RS 232 communi cations to transmit UPS and power conditions Contact Tripp Lite Customer Support at 773 869 1234 for more information including a list of available SNMP network management and connectivity prod ucts External Battery Pack Connector Use to connect optional Tripp Lite Battery Packs for additional runtime Contact Tripp Lite Customer Support at 773 869 1234 fo
12. nnected equipment with pure sine wave AC output from the AC line during normal operation and from battery power during blackouts and severe brownouts Power provided at these outlets is filtered to pro tect connected equipment against damaging surges and line noise The receptacles are divided into numbered load banks as labelled on the unit Using PowerAlert software and cabling load banks one NEMA 5 150R ANd two may be individually turned off and on from a remote loca tion allowing users to reset or reboot connected equipment See Serial Port Connection under Optional Connections Battery Replacement Under normal conditions the original battery in your UPS will last several years Contact Tripp Lite for information about replacement batteries Battery replacement should be performed only by qualified service personnel The batteries are hot swappable it is not necessary to turn off or disconnect the UPS and its connected load to replace the UPS s batteries However when it is convenient to do so service personnel may simplify the replacement procedure by pressing the OFF switch to turn power off at the UPS outlets and disconnect ing the UPS s power cord from the wall outlet When replacing the batteries qualified service personnel should refer to Battery Warnings in the Safety section and follow this procedure 1 Place the UPS horizontal with the Control Panel on the right side 2 Remove both snap on cover
13. panels A 3 Unscrew and remove rack handle plates B on either side of the UPS 4 Disconnect the microprocessor circuit board plug C located on the right side of the UPS 5 Disconnect battery connectors D Note while batteries are disconnected the UPS will not provide battery backup 6 Unscrew and remove the battery retaining bracket E 7 Grasp pull tab and pull out sliding battery tray F WARNING On the SU2200RT2U the batteries are arranged in an L shape on the tray Since the tray is heaviest on the front and on the left provide adequate support to keep the tray from tipping 8 Make a detailed sketch of the batteries and the polarity color and connec tion of all cables Disconnect used batteries and dispose of them properly Connect replacement batteries in exactly the way original batteries were connected Reassemble the UPS by reversing steps 1 7 Note you may not receive full runtime until your replacement batteries have fully charged Small sparks arcing between battery connectors during battery replacement are normal SU2200RT2U SHOWN Storage amp Service Storage First turn your UPS OFF press the OFF switch to turn power off at the UPS out lets then disconnect the power cord from the wall outlet Next disconnect all equipment to avoid battery drain If you plan on storing your UPS for an
14. r the appropriate Tripp Lite battery pack to connect Refer to instructions available with the Battery Pack for complete connection information and safety warnings Fan The fan cools the UPS s internal components It is always on when line power is present TVSS Cover Plate Reserved for future use Optional modem network surge protection modules may be available for purchase by special arrangement with Tripp Lite Input Circuit Breaker Switch This resettable breaker prevents high input current from damaging the UPS or the attached load If this breaker trips make sure your UPS is connected to AC power of the proper voltage before resetting the circuit breaker by pushing the breaker switch in Input Receptacle Select Models Only Connect one end of the detach able line cord into this receptacle and the other into your wall outlet Rear Panel Continued S ERD A ao 83 To KE NEMA 5 15R OUTPUT Output Circuit Breakers Switches Select Models Only These reset table circuit breakers protect your UPS from output overload If one or both breakers trip remove some of the load on the circuit s and allow the UPS to cool before pressing the breaker switch es in to reset Input Cord Select Models Only This permanently attached power cord connects your UPS to a power outlet AC Receptacles NEMA 5 15R Varied by Model These 15 20 and 30 amp receptacles provide your co
15. y Runtime Half Load Full Load Min 18 6 18 6 System Battery Voltage 36 VDC 72 VDC Approvals CE UL cUL FCC NOM Model SU2200RT2UHV SUINT2200RT2U Input Voltage 200 208 240V 220 230 240V Input Breaker Rating 15A 15A Input Plug Type 6 20P IEC 320 C20 Recommended Utility Amps 20A 20A Output Capacity VA Watts 2200 1600 2200 1600 Battery Runtime Half Load Full Load Min 18 6 18 6 System Battery Voltage 48 VDC 48 VDC Approvals UL cUL FCC NOM CE 11 Specifications Continued Model SU3000RT3U SU3000RT3UHV Input Voltage 120V 200 208 240V Input Breaker Rating 40A 25A Input Plug Type L5 30P L6 20P Recommended Utility Amps 30A 20A Output Capacity VA Watts 3000 2400 3000 2400 Battery Runtime Half Load Full Load Min 14 6 14 6 System Battery Voltage 72 VDC 72 VDC Approvals Model UL cUL FCC NOM SUINT3000RT3U UL cUL FCC NOM Input Voltage Input Breaker Rating Input Plug Type Recommended Utility Amps Output Capacity VA Watts Battery Runtime Half Load Full Load Min System Battery Voltage Approvals 220 230 240V 25A IEC 320 C20 20A 3000 2400 14 6 72 VDC CE FCC Specifications for Models with FCC Approval This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undes
Download Pdf Manuals
Related Search
Related Contents
bq Aquaris E4.5 8GB Black Warranty HW, HWQS, RadioRA, RadioRA2, Clear Connect TM AudioLink Pro Chapitre 3 : L`impact de sponsoring sportif sur l`image de marque de Visual Land ME-107-L-8GB SUSE Linux Riferimento Manuale - Hanna Instruments Service & Installation Manual Copyright © All rights reserved.