Liebert UD1400R User's Manual
Contents
1. UPStation D Desktop Models UD600 UD900 UD1400 UD2000 Rackmount Models UD600R UD900R UD1400R UD2000R ptible Power System 600 2000 VA 120 VAC 60 50 Hz USER S MANUAL 0 Lieber 9 IMPORTANT SAFETY INSTRUCTIONS WARNING Do not attempt to service this product yourself There are no user serviceable parts inside the unit Opening or removing the cover may expose you to dangerous voltages even when the UPS is unplugged Refer all servicing to qualified Liebert service personnel SAVE THESE IMPORTANT SAFETY INSTRUCTIONS ADHERE TO ALL OPER ATING INSTRUCTIONS AND WARNINGS ON THE UNIT AND IN THIS MANUAL CONSERVER CES INSTRUCTIONS IMPORTANTES CONCERNANT LA SECURITE Liebert Corporation neither recommends nor knowingly sells this product for use with life support or other U S FDA designated critical devices CAUTION A BATTERY PRESENTS A RISK OF ELECTRICAL SHOCK OR BURN FROM HIGH SHORT CIRCUIT CURRENT OBSERVE PROPER PRECAUTIONS ATTENTION UNE BATTERIE PEUT PR SENTER UN RISQUE DE CHOC ELECTRIQUE OU DE BRULURE PAR TRANSFERT D ENERGIE SUIVRE LES PRECATIONS QUI S IMPOSENT WHEN REPLACING BATTERIES SE THE SAME NUMBER AND THE FOLLOW ING TYPE OF BATTERIES CSB 12V 7 AH 600 VA CSB 6 V 10 AH 900 amp 1400 VA CSB 12 V 17 AH 2000 VA DISPOSE OF BATTERIES PROPERLY REFER TO LOCAL CODES FOR DISPO QUIREMENTS POUR LE REMPLACEMENT UT ME NOMBRE DE BATTERIES DU MODELE SU
2. OR THE FITNESS OF THE GOODS FOR ANY INTENDED PURPOSES LIEBERT ASSUMES NO RESPONSIBILITY FOR INCIDENTAL OR CONSEQUEN TIAL DAMAGES INCLUDING WITHOUT LIMITATION LOSS OF USE PROFIT OR INCOME To make a warranty claim call 1 800 222 5877 to obtain the required return authorization number Return trans portation costs to Liebert are the responsibility of the pur chaser 0 Liebert Keeping Business in Business 1050 Dearborn Drive Columbus OH 43229 614 888 0246 France Germany Internet Web Site Technical Support cabin 1 800 222 5877 ae 44 0 1793 553355 33 1 46 87 51 52 49 89 99 19 220 upstech liebert com http www liebert com Peer erereresreury asaznannunapasna While every precaution has been taken to ensure accuracy and completeness in this manual Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or tor any errors or omissions 1996 Liebert Corporation All rights reserved throughout the world Specifications subject to change without notice Liebert and the Liebert logo are registered trademarks of Liebert Corporation All names referred to are trademarks or registered trademarks of their respective owners Printed in U S A SL 23330 4 96 Rev 001
3. a fault in your computer equipment may cause an overload alarm Silence alarms by pressing the ALARM SILENCE button 12 on the front panel Refer to the tables on the following page for alarm indications and recom mended actions when alarms occur Check these tables first before call ing for assistance They diagnose and solve common problems and help prevent potential problems UPSTATION D LED amp ALARM INDICATIONS UPS CONDITION LED INDICATORS AUDIBLE ALARM OPERATOR ACTION FromarOpwaton Povertepsut Were None PECIFICATIONS Boost Circuit Power LED Lit Model Number UD600 UD600R UD900 UDs00R UD1400 UD1400R UD2000 UD2000R Operation Voltage Boost LED Lit Rating VA Watts 1400 1000 2000 1500 On Battery Top Beep every Check for loss of 3 es LED Lit 5 Seconds Utility Power att ly UPS 10 5 x7 x 17 8 peration On Battery 1 Second Beep every Check for High Utility Desktop Dimensions Bx5 3x15 10 57 15 4 10 5x7x178 267 x 178 x 452 LED Flashing 5 Seconds Power 131 VAC WxDxH 206 x 135x381 267x178x391 267x178x452 Battery 9x7x17 8 Low Battery Left most LED of 4 Second Beep Perform an Orderly 229 x 178 x 452 Warning Battery Charge bar every 5 Shutdown of alt Load Rackmount Dimensions 5x 17x21 5x17 x21 7x17 x21 7x17 x21 LEDs Flashing Seconds Equipment WxDxH 127 x 432x534 127x432x534 178x432x534 178x432x534 Replace Replace Batte See Troubleshootin 7 3 cominuous Tone Such U
4. sustains load equipment indefinitely in this condition with both the Power 7 and Voltage Boost 11 LEDs steadily iit If utility voltage falls below 84 VAC or rises above 132 VAC or fails completely the UPS immediately operates on battery power until utility voltage returns to normal levels The On Battery LED 8 lights steadily during unboostable or unavailable utility voltage and flashes during high voltage battery operation Battery operation causes a 1 second alarm to sound every 5 seconds Press the Alarm Silence button 12 to silence the alarm Once on bat tery begin a controlled shutdown of the load equipment The UPS provides battery power for approximately 6 minutes depending on the load it supports Reduced loads increase battery time With approximately two minutes of battery time left the alarm sounds every second instead of every 5 seconds Complete a controlled shutdown of your equipment before the UPS exhausts the battery If the UPS is ON when normal utility power returns it continues to supply power to the load equipment Whether ON or OFF the UPS recharges the battery when connected to normal utility power OVERLOAD CONDITIONS A UPS overload causes all five LEDs along the top of the diplay panel 7 11 to light along with all of the Load bar LEDs 13 The right most Load bar LED changes from green to red and a two tone alarm sounds every 5 seconds until either the user corrects the overload or the UPS sh
5. IVANT CSB 72 V 7 AH 600 VAJ CSB 6 V 10 AH 900 amp 1400 VA CSB 12 V 17 AH 2000 VA L ELIMINATION DES BATERIES EST REGLEMENTEE CONSULTER LES CODES LOCAUX A CET EFFET WARNING TO REDUCE RISK OF FIRE OR ELECTRIC SHOCK INSTALL IN A TEMPERATURE AND HUMIDITY CONTROLLED AREA FREE FROM CONDUC TIVE CONTAMINANTS AVERTISSEMENT POUR R DUIRE LE RISQUE D INCENDLE OU DE CHOC ELECTRIQUE INSTALLE DANS UN SECTEUR AVEC TEMPERATURE CONTROLE ET HUMIDITE CONTROLEE EXAMPT DE POLLUANTS CONDUC TEURS Read all safety and operating instructions before operating UPS Operate UPS indoors only Install it in a clean environment free trom moisture flammable liquids gases or corrosive substances WARNING Do not modify cable Consult dealer if connector does not match equip ment Ground UPS while in use Turn UPS OFF before unplugging or the safety ground from UPS to equipment will be removed CAUTION Output receptacles on the UPS are electrically live if the UPS is ON even if UPS is unplugged The UPS on off switch does not electrically isolate inter nal parts To isolate UPS turn it OFF and unplug it Turn the UPS OFF and unplug it before cleaning Use only dry cloth never liquid or aerosol cleaners 10 Do not plug appliances like hair dryers heaters or surge protectors into UPS 11 Operate UPS only from grounded outlet 2 wire ground 120 VAC 60 50 Hz 12 The UPS is equipped with a grounded NEMA input power p
6. PS OFF Refer Rackmount Wegt ins T1 AER ia e Table Below Four 5R One 58 ED ch Load bar LEDs all lit Two Tone Beep Remove some of the a chang repeated once every load until the condition Voltage nutty tes 120 VAC 10 es from l _5 Seconds Mappen Voltage Boost Maintains outputto 120V 10 15 when input is 120V 10 30 kor auto senses input frequency UPSTATION D TROUBLESHOOTING GUIDE E PTEE PEER ETENE Input Power Cord ipa wi NEMA w NEMA PROBLEM SOLUTION g g 5 20 plug L5 30 plug Overload Warning Right most LE i ig UPS into a receptacle known to be good UPS will not start arab es HE i charge batteries for 5 hours i UPS operates eet De ae iR eet Battery Overad 750 for 1 oye 125 for 5 seconds continuously on battery Faulty wall receptacie Plug UPS into a receptacle known to be good l Sealed Maintenance Free deseo pay LED fit Paray charge low Plug UPS in and charge batteries for 5 hours Qty x Voltage x Rating tylim Batteries exhausted Return UPS to dealer Transfer Time Sas Aan e rid G l i i 6 mi typical Mee ee ao Pa Internal fault Return UPS to dealer puls do vi Fault 10 and Bove h 1 Excessive internal UPS Switch UPS OFF Check for obstructions near etl Ee ha aus alam caol down en rosink ie iy A i oe nae Inverter fault Return UPS to dealer Operating Altitude Up to 10 000 feet at 35 C without derating 8 LEDe it Continuou 8 ffi fit CAE Charger or other UP
7. S Return UPS to dealer Storage Altitude 50 000 feet maximum batteries can be air freighted fault ible Noi audible alarm Audible Noise lt 45 dBA at t meter at full load Load Bar LEDs 13 all lit with right most UPS output overload or Disconnect load equipment switch UPS OFF UL 1778 UL 1449 CSA IEEE 587 Cat A FCC Class A LED changing from faulty load equipment then restart UPS green to red LIEBERT TECHNICAL SUPPORT 800 222 5877 LIMITED WARRANTY We are pleased that you have purchased the UPStation D product to enhance the reliability of utility power to your sensitive electronic equipment Liebert Corporation warrants to the original user that the UPStation D product is and will remain free of defects in materials and workmanship for a period of two years from the date of shipment Extended warranty contracts are available During the warranty period Liebert will repair or replace at Liebert s determination products purchased which fail to meet the above warranty NOTE Warranty is void if the battery is allowed to discharge below the minimum the unit power switch power being supplie source external to the odut n others or which have product serial numbers removed or altered There are no warranties other than that described herein In no event will Liebert be responsible beyond the pur chase price of the product SELLER DISCLAIMS ANY IMPLIED WARRANTY OF MERCHANTABILITY OF THE GOODS
8. UPS to charge the batteries Liebert recommends charging the batteries for at least 5 hours before connecting load equipment After charging batteries shut down load equipment and unplug it Plug load equipment into UPS output receptacles 3 EJ When all equipment is plugged in UPS is ready for normal operation RACKMOUNT INSTALLATION Plug in the UPS to charge the batteries Liebert recommends charging the batteries for at least 5 hours before connecting load equipment Liebert offers kits for UPS rail or slide installation Install the UPS on rack mount rails slides o S Use t with your rackmount kit Check that all power connections to and from the unit are secure and fitted with the correct cables 2 Turn the UPS ON 7 Switch all load equipment ON Check the UPS front panel LED s The Power LED 7 should be lit The Load bar LEDs indicate how much power your equipment con sumes as a percentage of the UPS output capability Each LED repre sents a 20 increment e g 3 LEDs lit equipment using 60 of UPS output capability The Battery Charge bar LEDs 14 indicate the bat tery charge in 20 increments e g 4 LEDs lit 80 battery charge Check the operation of your equipment It should display normal opera tional conditions POWER DIPS SURGES AND OUTAGES When utility voltage dips below 120 VAC the UPS continues to draw power from the utility but automatically boosts the voltage to 120 VAC The UPS
9. er turned ON or OFF For extended storage plug in the UPS and turn it ON every 5 months for 5 hours to recharge the battery STARTING FROM BATTERY Unplug UPS switch it OFF and connect equipment to it Press the hidden button located approximately 1 inch below the ON OFF Switch a high pitched tone sounds After the tone press the ON OFF Switch The UPS provides battery power to the connected equip ment Pay attention to time remaining during battery operation NOTE The UPS is designed to start connected equipment from utility power High inrush current requirements may render a battery start impossible BATTERY LIFE Batteries last up to five years Excessive battery use stor age at high ambient temperatures and lengthy periods in a discharged state greatly reduce battery life Your UPS maximizes battery life by limiting the depth of battery discharge and using a temperature compensated battery charger harges the battery and tests it ent battery replacement Press perform a manual 10 second ion The Replace Battery LED bieshooting Guide ours operation from battery test to verify batt 9 lights if the battery fa NOTE The UPS requires an ini utility to totally recharge baiterie ALARMCONDITIONS The UPStation D sounds alarms and flashes visual indications at the front panel LED s 7 11 whenever it senses a power failure low battery voltage while on battery overload or fault condition Sometimes
10. hout battery drainag The UPS contains a counter which automaticaily initiates a 15 second battery test every 7 days and upon start up The UPS resets the counter after back up operation manual bat tery test or if the UPS is switched OFF The operator may perform a manual battery test by pressing the ALARM SILENCE button A control circuit monitors power input and battery condition and upon sensing a fault sounds an alarm and flashes a visual indication of the UPS status In addition a commu nications port enables the UPS to inform a computer equipped with SiteNet software of the power failure SiteNet automatically saves data and performs an orderly shutdown Cables and software are available as optional computer LAN Interface Kits Consult your dealer for the kit suitable for your application CONDITIONS OF USE Utility receptacle must be within 6 feet of UPS This UPS op erates on 110V to 120V AC 60 50 Hz voltage Models are available for other voltages Your UPS is designed to protect only Communication and Data Processing equipment Maximum load must not exceed that shown on UPS rating label If uncertain consult your dealer or representative wer to its AC outputs but when the ON the battery light and provides e free battery Upon utility restora ility power boosting it if necessary Placing magnetic storage media on top of the UPS may result in data corruption CAUTION This UPS complies with Part 15 Sub
11. l UNIX Unisys Sun Hewlett Packard and DEC computer systems This option provides automatic orderly system shutdown in the event of power failure or low battery power POWER SURVEILLANCE KIT Available for UNIX Novell OS 2 and DOS computer systems This option uses a seral communications link between the UPS and the connected system to pro vide comprehensive UPS monitoring and control Communication with a LAN Interface Shutdown Kit or Power Surveillance Kit requires the RS 232 Option SIMPLE NETWORK MANAGEMENT PROTOCOL SNMP Provides UPS with full bi directional open standard communications on any secure Token Ring or Ethernet network The UPS becomes a network node allowing monitoring communication and control from any other part of the LAN RS 232 OPTION Provides the signals listed below on the UPS DB 25 communications port PIN FUNCTION PIN FUNCTION 1 Reserved 14 Not Used 2 RxD 15 Not Used 3 TxD 16 On Battery 4 Not Used active closed 5 Not Used 17 Common 6 Not Used for pins 16 amp 18 7 Signa Ground 18 On Battery 8 Not Used active open 9 Low Battery Relay 19 UPS Shutdown Contact common active high 10 Low Battery Relay 20 Not Used Contact active open 21 Not Used 11 Low Battery Relay 22 Not Used Contact active closed 23 Not Used 12 Shutdown active low 24 Not Used 13 Not Used 25 Not Used BATTERY CARE AND USE STORAGE When temporarily not in use keep UPS plugged in It maintains battery charge wheth
12. lug Do not defeat the safe ty purpose of this plug with a ground plug adapter If unabie to fully insert plug into out let contact an electrician to replace the outlet 12 Route power supply cords so they are not walked on or pinched 13 Never block or insert objects into ventilation holes or other openings Maintain mini mum clearance of 4 inches all around UPS for proper air flow and cooling 14 CAUTION Do not open or mutilate battery Released electrolyte is harmful to skin and eyes and may be toxic INTRODUCTION amp SYSTEM DESCRIPTION Congratulations on choosing the Liebert UPStation D It provides continuous conditioned power to microcomputers and other data processing equipment Upon generation AC power is clean and stable However during transmission it may be subject to load variations or accidents which cause power problems like low voltage volt age spikes or complete power failure These problems may interrupt computer opera tions cause data loss or even damage equipment The UPS provides protection from many of these disturbances It smooths out voltage variations and in the event of te power failure it supports equipment long enough for an orderly shutdown Thes yand rackmount units are available in four ratings 600 900 1400 and 2000 VA i Normally the UPS connect UPS senses a power failure it 0u AC power to equipment through a tion the UPS powers the e If a brownout occurs and A age wit
13. part B of FCC rules for Class B computing devices Operation in residential areas may interfere with radio and TV reception The user must correct the interference at his own expense DESKTOP 2000 VA MODELS UPStation D Front Display P Optional Communications Pott 1 6 Hidden Battery Start Button 11 Voltage Boost LED 2 Input Circuit Breaker 7 On Off Switch amp LED 12 Alarm Silence and Battery 3 Output Receptacles 8 On Battery LED Test Button 4 Power Input 9 Replace Battery LED 13 Load Indicator Bar 5 Optional Output Receptacle 10 Faut LED 14 Battery Charge Indicator Bar ATTENTION Refer to these drawings when reading this manual This manual references the various parts of your UPS by number UPStation D is also available in rackmount configuration BEFORE INSTALLATION Unpack UPS carefully noting the packing method Retain packaging To return the UPS re pack as originally shipped Inspect UPS for freight damage Contact the carrier and or your distributor concerning freight damage or missing parts Place UPS on a sturdy dry surface in a well ventilated area where it can not be accidently turned OFF Keep it away from moisture flammable liquids gases explosives and direct heat sources Operating tempera ture ranges from 10 to 40 C 50 to 104 F Leave at least 4 inches 100 mm clearance all around the UPS for adequate ventilation 3 DESKTOP INSTALLATION Plug in the
14. uts down The Alarm Silence button 12 cannot silence an overload alarm To avoid losing power to all the load equipment disconnect non critical equipment until alarm ceases An overload outside UPS parameters shuts down the UPS and may trip the Input Circuit Breaker 2 To confirm this condition press the Hidden Battery Start switch 6 the UPS sounds the overload alarm as describ ed above Reset the Input Circuit Breaker 2 if tripped See Resetting the Circuit Breaker next page Press the ON OFF switch 7 If the overload still exists the UPS shuts down again If the overload is gone the UPS starts on battery If the UPS starts on battery turn the UPS OFF 7 After reducing the overload to normal resetting the Input Circuit Breaker 2 and reconnecting the UPS to utility turn the UPS ON 7 It should function normally again See Troubleshooting Guide for all abnormal conditions If problems per sist consult your dealer or contact Technical Support 1 800 222 5877 RESETTING THE CIRCUIT BREAKER If the UPS is overloaded the Input Circuit Breaker 2 may activate to protect the UPS Upon activation its plastic covering pops open To reset the circuit breaker 2 simply push the covering back in place If it activates offen ask your representative to check the UPS sizing COMPUTER INTERFACE OPTIONS Your dealer supplies easily installed computer interface options LAN INTERFACE SHUTDOWN KITS Available for Novel
Download Pdf Manuals
Related Search
Related Contents
Herunterladen Informe del Resultado de la Fiscalización Superior de la Cuenta Il fait Bio dans mon assiette : Mode d`emploi d`un The 'NAVIGATOR' Compass - 'NV-2400 Series' このたびは当商品をお買い上げ頂き誠にありがとうございます。ご使用に AIR COOLED CHILLER (C Series) Manual de Instruções Bedienungsanleitung Manuel d'instructions Copyright © All rights reserved.