1. CAUTION The intra building ports of the equipment are suitable for connection to intra building or unexposed wiring or cabling only The intra building ports of the equipment must not be metallically connected to interfaces that connect to the Outside Plant OSP or its wiring These interfaces are designed for use as intra building interfaces only Type 2 or Type 4 ports as described in GR 1089 CORE Issue 4 and require isolation from the exposed OSP cabling The addition of primary protectors is not sufficient protection to connect these interfaces metallically to OSP wiring Cabling 3 Power supplies specifications and cable information HP 1200W PSU 48VDC Input Part Number 437573 B21 Input Voltage Range DCV 36 72 Frequency Range Nominal Hz DC Nominal Input Voltage VDC 36 48 72 Maximum Rated Output Wattage 1200 1200 1200 Nominal Input Current ACD 38 28 19 Maximum Rated Input Wattage Rating Watts 1380 1350 1365 Maximum Rated VA Volt Amp 1380 1350 1365 Efficiency of Maximum Rated Output Wattage 87 89 88 Power Factor N A N A N A Leakage Current mA N A N A N A Maximum Inrush Current A peak 20 25 35 Maximum Inrush Current duration mS 1 3 Maximum British Thermal Unit Rating Btu Hr 4713 4610 4662 NOTE Battery return terminals are isolated DC returns DCI Power cable color codes Each DC power cable is shipped with a label that
2. Carrier Grade Server only This kit includes all the parts you need to convert the server to the NEBS compliant version NEBS certified configuration details are available from your HP sales representative Conversion kit contents Table 1 Carrier grade conversion kit parts list Preventing electrostatic discharge Description Part Number Quantity ASSY FAN DL380G6 463172 001 2 BAG ZIP LOCK 108344 001 1 TERM RING VIN 12 10 AWG 10 545155 001 1 LOCK WASHER T10127 A00 2 HP ProLiant DL380 G6 Carrier Grade Server RBI Carrier Grade Conversion Instructions AM275 9001A BOX TT 9 5 X 7 5 X 2 25 111158 002 1 BAG BUBBLE WRAP 6 X 8 5 100473 001 1 Screw 6 32 taptite struck slot T15 Torx 192308 002 1 To prevent damage to the system you must take precautions when setting up the system or handling parts A discharge of static electricity from a finger or other conductor might damage system boards or other staticsensitive devices This type of damage can reduce the life expectancy of the device To prevent electrostatic damage take the following precautions e Avoid hand contact by transporting and storing parts in staticsafe containers e Keep electrostaticsensitive parts in containers until they arrive at staticfree workstations e Before removing parts from containers place parts on a grounded surface e Avoid touching pins leads or circuitry e Make sure you are grounded properly when touching a st
3. HP ProLiant DL380 G6 Carrier Grade Server Read Before Install Carrier Grade Instructions HP Part Number AM275 9001A Published July 2012 Edition 3 Copyright 2009 2012 Hewlett Packard Development Company L P The information contained herein is subject to change without notice The only warranties for HP products and services are set forth in the express warranty statements accompanying such products and services Nothing herein should be construed as constituting an additional warranty HP shall not be liable for technical or editorial errors or omissions contained herein NEBS is a trademark of Telecordia Technologies Incorporated Audience assumptions This document is for the person who installs administers and troubleshoots servers and storage systems HP assumes you are qualified in the servicing of computer equipment and trained in recognizing hazards in products with hazardous energy levels 1 Converting to carrier grade This document provides information for the carrier grade version of the commercial HP ProLiant DL380 G6 Server This chapter provides the steps required to convert the commercial HP ProLiant DL380 G6 Server to its carrier grade version The conversion to carrier grade consists of the following actions e Installing fans e Changing the system maintenance switch e Installing the ground lug Before you start The conversion kit 581031 B21 is intended for the DL380 G E5540
4. NOTE The following instructions use iLO 2 For complete information and instructions on using iLO 2 see the HP Integrated Lights Out 2 User Guide on the HP website at http www hp com bizsupport TechSupport 1 Log in to iLO 2 For instruction see the HP Integrated Lights Out 2 User Guide 2 Select System Information on the left navigation bar Installing the fans 3 Select the Temperatures tab If the temperature thresholds appear as shown below the switch is set correctly O Integrated Lights Out 2 System Status Remote Console Virtual Media Power Management Administration Temperature Health Summary System Information Data is not updated while server is off iLO 2 Log System health information current as of last power off IML Diagnostics iLO 2 User Temp 1 Tips Temp 2 Insight Agent Temp 3 Temp 4 Temp 5 Temp 6 Temp 7 Incorrect thresholds Location Ambient Zone CPU 1 CPU 2 Memory Zone Memory Zone Memory Zone Memory Zone oan Status Reading Thresholds 25C 40C 40C 37C 34C 40C 36C LLLNRLNVL Caution Caution Caution Caution Caution Cauton Caution 59C Critical 65C 82C Cntical 83C 82C Critical 83C 87C Cntical 92C 87C Cntical 92C 87C Cntical 92C 87C Cntical 92C If the thresholds don t show up correctly you might have switched the wrong switch Ensure the switch is reset to the factory defaults as described in the HP Proliant DL380 G6 M
5. aintenance and Service Guide on the HP website at http h20000 www2 hp com bizsu ort TechSupport After you reset the switch settings to the factory defaults repeat the above process for verifying the system maintenance switch setting Changing the system maintenance switch settings T 5 Installing the DL380 server into a seismic rack For information on the installation of the DL380 using the commercial rack mount kit see the HP website at htto www hp com support manuals Under Servers click ProLiant ml dl and tc series servers and select your product While not specifically designed for use in seismic rack solutions the commercial kit was successtully evaluated in the AH343A HP Seismic Rack to the NEBS Zone 4 criteria as part of the DL380 Server NEBS certification IMPORTANT Perform all the steps in the kit with the exception of the steps specified here in this procedure which pertains only to installing a DL380 into a seismic rack Hardware kit contents In addition to the supplied items you might need e Screws that fit the rack e The appropriate screwdriver for the screws Installing the rack mount kit 12 A CAUTION Plan the rack installation so that the heaviest item is on the bottom of the rack Install the heaviest item first and then continue to populate the rack from the bottom to the top NOTE The following procedure was performed by HP personnel to install the rack moun
6. atic sensitive component or assembly Overview The following graphic provides an overview of the carrier grade conversion process Before you start 3 4 Toggle DIP switch to invoke BIOS for Telco fan and temperature threshold table Converting to carrier grade Two 48VDC power supplies 2x 437573 B21 Add grounding hardware Add two supplemental fans 2x 463172 001 Single 8 SFF drive bay only 1x 516914 B21 2 Cabling Installing the ground lug To meet the bonding and grounding criteria for NEBS compliance a dedicated ground lug is required To install the ground lug see the steps illustrated in the following figure Star washers Grounding lug 545155 001 T15 Torx screw 192308 002 The following figure illustrates the finished assembly of the ground lug Installing the ground lug 5 Cable information This section provides cabling information for installing the HP ProLiant DL380 G6 Carrier Grade Server NEBS chassis ground This carrier grade product is intended for use in both common bonding networks and isolated bonding networks The product is equipped with a NEBS compliant chassis ground lug located on the rear of the product The ground lug included with the product accepts wire gauges between 10 and 12 AWG Network cabling 6 Intra building connections of the HP Proliant DL Series Carrier Grade Servers require the use of shielded cables grounded at both ends
7. ce and Service Guide on the HP website at htt www hp com su Under Servers click ProLiant ml dl and tc series servers and select your product Power supplies specifications and cable information ort manuals A Installing the tans A WARNING To prevent personal injury from hazardous energy remove watches rings or other metal objects 1 Power off the server 2 Remove power to the server 3 Remove the top cover 4 Locate the fan blanks 5 Remove and discard the fan blanks 6 Install the fans into the board Make sure the power connector on the fan lines up with the power connector on the board 7 Replace the top cover Changing the system maintenance switch settings A WARNING To prevent personal injury from hazardous energy remove watches rings or other metal objects Power off the server Remove power to the server Remove the top cover Locate the system maintenance switches which are visible through the opening in the PCI riser cage RwOWN gt Changing the system maintenance switch settings 9 5 Change the 10 system maintenance switch setting to the On position You can use a plastic ball point pen to flip the system maintenance switch 6 Replace the top cover Verifying the system maintenance switch setting 10 After you switch the setting verity that the 10 system maintenance switch is in the On position
8. describes each lead The label is located near the pigtail leads The three leads are described in the following table Cable color Description Black Positive return Blue Negative input voltage Green Yellow Safety ground HP 1200W 500172 B21 Power Supply Part Number AC Operational 100 to 240 Input Voltage Range Vrms Frequency 50 60 Range Nominal Hz Nominal Input 100 120 208 200 220 230 240 Voltage VDC Maximum Rated Output Wattage 800 900 1200 1200 1200 1200 1200 Power cable color codes 7 Replacing the fans and power supplies 8 Nominal Input Current A rms 9 7 9 0 7 0 6 8 6 4 91 5 9 Maximum Rated Input Wattage Rating Watts 930 1034 1348 1348 1348 1348 1348 Maximum Rated VA Volt Amp 970 1079 1406 1406 1406 1406 1406 Efficiency of Maximum Rated Output Wattage 86 87 89 89 89 89 89 Power Factor 0 97 0 97 0 97 0 97 0 97 0 97 0 97 Leakage Current mA 0 42 0 50 0 83 0 87 0 92 0 96 1 00 Maximum Inrush Current A peak 30 30 30 30 30 30 30 Maximum Inrush Current duration mS 20 20 20 20 20 20 20 Maximum British Thermal Unit Rating BTU Hr 3174 3530 4600 4600 4600 4600 4600 If a cooling fan or power supply fails you must replace it Replacement usually takes no longer than 5 minutes For instructions on replacing these components see the HP ProLiant DL380 G6 Server Maintenan
9. ing rails and into the rack 14 Installing the DL380 server into a seismic rack 8 Snap the server into place 9 Fasten the server to the rack using the screws included in the rack kit as described in the rack kit instructions for preparing a server for shipment a Pull down the plastic retention lever on each side of the server b Insert the screws into each side 10 Install the cable arm using the instructions in the rack kit Hardware kit contents 15 x AM 275 9 OO 17 A Printed in the US
10. t kit This information is provided as an example and a reference to assist in the installation of a DL380 Server into a seismic rack 1 Unscrew the eight snap in screws from the mounting rails and discard the screws 2 Obtain eight round hole M5 cage nuts that are intended for use with the seismic rack Installing the DL380 server into a seismic rack NOTE The square hole cage nuts that are provided in the rack kit do not fit in the round holes in the seismic rack 3 Install the round hole M5 cage nuts in the appropriate rack hole positions where you want to install the DL380 Server e Two cage nuts on the front of each rail e Two cage nuts on the back of each rail 4 Line up the mounting rail with the cage nuts and fasten the mounting rail to the rack with M5 screws IMPORTANT You must provide the screws to secure the slide mounting bracket assemblies Hardware kit contents 13 NOTE Apply some pressure when fastening the screws to the mounting rail 5 Repeat steps 1 through 3 for the other mounting rail A WARNING To reduce the risk of personal injury or equipment damage be sure that the rack is adequately stabilized before sliding the inner slides into the slide mounting bracket assemblies 6 To install the side rails on each side of the server align each side rail to the server and snap it into place 7 Slide the server onto the mount