Emerson MR105 Installation Guide
Contents
1. If the regulator vents fluid or a leak develops in the system it indicates that service is required Failure to take the regulator out of service immediately may create a hazardous condition Personal injury equipment damage or leakage due to escaping fluid or bursting of pressure containing parts may result if this regulator is overpressured or is installed where service conditions could exceed the limits given in the Specifications section or where conditions exceed any ratings of the adjacent piping or piping connections To avoid such injury or damage provide pressure relieving or pressure limiting devices as required by the appropriate code regulation or standard to prevent service conditions from exceeding limits Additionally physical damage to the regulator could result in personal injury and property damage due to escaping fluid To avoid such injury and damage install the regulator in a safe location Clean out all pipelines before installation of the regulator and check to be sure the regulator has not been damaged or has collected foreign material during shipping For NPT bodies apply pipe compound to the external pipe threads For flanged bodies use suitable line gaskets and approved piping and bolting practices Vertical installation with the actuator oriented up or down is recommended The unit will operate in horizontal installation with actuator on the side however this could result in premature wear o
2. Low Pressure Actuator 70 psig 4 8 bar High Pressure Actuator 400 psig 27 6 bar Type MR105 Maximum Emergency Casing Pressures Low Pressure Actuator 70 psig 4 8 bar High Pressure Actuator 400 psig 27 6 bar Maximum Setpoint Low Pressure Actuator 43 psig 3 0 bar High Pressure Actuator Nitrile NBR and Ethylene Propylene EPDM Diaphragm 300 psig 20 7 bar Fluorocarbon FKM Diaphragm 150 psig 10 3 bar Outlet Pressure Ranges NPS 1 and 2 DN 25 and 50 Low Pressure Actuator 5 to 12 psig 0 35 to 0 83 bar 10 to 24 psig 0 69 to 1 6 bar 14 to 32 psig 0 96 to 2 2 bar 18 to 43 psig 1 2 to 3 0 bar High Pressure Actuator 25 to 60 psig 1 7 to 4 1 bar 43 to 100 psig 3 0 to 6 9 bar 75 to 175 psig 5 2 to 12 1 bar 110 to 300 psig 7 6 to 20 7 bar NPS 3 and 4 DN 80 and 100 Low Pressure Actuator 5 to 8 psig 0 35 to 0 55 bar 8 to 20 psig 0 55 to 1 4 bar 12 to 30 psig 0 83 to 2 1 bar 18 to 39 psig 1 2 to 2 7 bar High Pressure Actuator 39 to 72 psig 2 7 to 5 0 bar 71 to 175 psig 4 9 to 12 1 bar 110 to 250 psig 7 6 to 17 2 bar Temperature Capabilities Nitrile NBR 20 to 180 F 29 to 82 C Fluorocarbon FKM 20 to 250 F 7 to 121 C Ethylene Propylene EPDM 20 to 225 F 29 to 107 C Maximum Differential Pressures Liquid Application Low Pressure Actuator NPS 1 and 2 DN 25 and 50 200 psig 13 8 bar NPS 3 and 4 DN 80 and 100 225 psig
3. 15 5 bar High Pressure Actuator NPS 1 DN 25 250 psig 17 2 bar NPS 2 DN 50 200 psig 13 8 bar NPS 3 DN 80 225 psig 15 5 bar NPS 4 DN 100 250 psig 17 2 bar Other Applications Low Pressure Actuator 400 psig 27 6 bar High Pressure Actuator 400 psig 27 6 bar Maximum Pressures over Set Pressure to Avoid Internal Parts Damage Low Pressure Actuator 20 psig 1 4 bar High Pressure Actuator 120 psig 8 3 bar 1 The pressure temperature limits in this Installation Guide or any applicable limitation should not be exceeded 2 Maximum Outlet and Emergency Casing Pressures for constructions with Fluorocarbon FKM diaphragm are limited to 230 psig 15 8 bar or the body rating limit whichever is lower 3 NPS 2 DN 50 body size spring range is limited up to 45 psig 3 1 bar only 4 Maximum setpoint is limited to 150 psig 10 3 bar for constructions with Fluorocarbon FKM diaphragm 5 Fluorocarbon FKM is limited to 200 F 93 C hot water 6 Ethylene Propylene EPDM is limited to 20 to 250 F 7 to 121 C when used with Low Pressure Actuator www fisherregulators com i gt wa aL EMERSON D103246XUS2 Type MR105 Installation Only qualified personnel should install or service a regulator Regulators should be installed operated and maintained in accordance with international and applicable codes and regulations and Emerson Process Management Regulator Technologies Inc instructions
4. 30 Pipe Plug 33 NACE Tag not shown 34 Seal Wire not shown 35 Indicator Fitting 36 Back O ring 37 Indicator Fitting O ring 38 Pipe Plug 40 Actuator Stem 43 Nameplate 44 Lube Fitting 45 Wiper Ring 46 Bearing 47 Valve Stem O ring 48 Jam Nut 49 Spring Washer 51 Lower Diaphragm Head O ring 52 Lower Spring Guide 53 Lower Diaphragm Head 54 Lower Spring Seat 55 Diaphragm Plate 56 Diaphragm 57 Cap Screw or Stud Bolt 58 Hex Nut 60 Bonnet O ring 61 Bonnet 62 Lower Diaphragm Casing 63 Upper Diaphragm Casing 64 Spring Case Spacer O ring 64 Upper Diaphragm Casing O ring 65 Cap Screw 66 Spring Case Spacer 67 Cap Screw 68 Control Spring 69 Upper Spring Seat 70 Spring Case 71 Seal Washer not shown 72 Jam Nut 73 Adjusting Screw 75 Restrictor not shown 76 Pipe Bushing 81 Pipe Nipple not shown 82 Drain Valve not shown 84 Internal Stiffener Plate 85 Bleed Valve not shown 87 Upper Casing Welding Assembly not shown Type MR105 ISSS ASS AS ASS 7 LA ZILLA LLLLLLLL XZ GE38435 Figure 1 Type MR105 Assembly Drawings Type MR105 a SN A N Ss Lt DETAIL Z GE38435 Industrial Regulators Emerson Process Management Regulator Technologies Inc USA Headquarters McKinney Texas 75070 USA Tel 1 800 558 5853 Outside U S 1 972 548 3574 Asia Pacific
5. Shanghai 201206 China Tel 86 21 2892 9000 Europe Bologna 40013 Italy Tel 39 051 419 0611 Middle East and Africa Dubai United Arab Emirates Tel 011 971 4811 8100 NO TRAVEL INDICATOR Figure 1 Type MR105 Assembly Drawings continued Natural Gas Technologies Emerson Process Management Regulator Technologies Inc USA Headquarters McKinney Texas 75070 USA Tel 1 800 558 5853 Outside U S 1 972 548 3574 Asia Pacific Singapore 128461 Singapore Tel 65 6770 8337 Europe Bologna 40013 Italy Tel 39 051 419 0611 Chartres 28008 France Tel 33 2 37 33 47 00 Middle East and Africa Dubai United Arab Emirates Tel 011 971 4811 8100 DETAIL V Sos gt pet Ya HY Coe eS TESCOM Emerson Process Management Tescom Corporation USA Headquarters Elk River Minnesota 55330 2445 USA Tels 1 763 241 3238 1 800 447 1250 Europe Selmsdorf 23923 Germany Tel 49 38823 31 287 Asia Pacific Shanghai 201206 China Tel 86 21 2892 9499 For further information visit www fisherregulators com The Emerson logo is a trademark and service mark of Emerson Electric Co All other marks are the property of their prospective owners Fisher is a mark owned by Fisher Controls International LLC a business of Emerson Process Management The contents of this publication are presented for informational purposes only and while every effort has been made to ensure their acc
6. Installation Guide English June 2014 Introduction This installation guide provides instructions for installation startup and adjustment To receive a copy of the instruction manual contact your local Sales Office or view a copy at www fisherregulators com For further information refer to Type MR105 Instruction Manual Form 5874 D103246X012 P E D Category This product may be used as a pressure accessory with pressure equipment in the following Pressure Equipment Directive 97 23 EC categories It may also be used outside of the Pressure Equipment Directive using sound engineering practice SEP per table below PRODUCT SIZE CATEGORIES NPS 1 DN 25 SEP NPS 2 DN 50 Il NPS 3 DN 80 Il NPS 4 7 DN 100 Il Specifications Available Constructions Type MR105 with low pressure actuator Direct operated large multi purpose regulator with 5 to 43 psig 0 35 to 3 0 bar pressure range Type MR105 with high pressure actuator Direct operated large multi purpose regulator with 25 to 300 psig 1 7 to 20 7 bar pressure range Body Sizes and End Connection Styles DN 25 and 50 NPS 1 and 2 NPT CL125 FF CL250 RF CL150 RF CL300 RF CL600 RF and EN PN 16 25 40 RF DN 80 and 100 NPS 3 and 4 CL125 FF CL250 RF CL150 RF CL300 RF CL600 RF and EN PN 16 RF Maximum Inlet Pressures Low Pressure Actuator 400 psig 27 6 bar High Pressure Actuator 400 psig 27 6 bar Maximum Outlet Pressures
7. f parts Make sure that flow will be in the same direction as that indicated by the body arrow Orientation of the two vents should always be down Vents may be rotated after regulator installation so that the vent screens are down A control line must be installed to allow outlet pressure to register on the actuator s diaphragm It should be installed four to eight pipe diameters downstream of the regulator and in an area of pipe that is free of turbulence Note It is important that the regulator be installed so that the vent hole in the spring case is unobstructed at all times For outdoor installations the regulator should be located away from vehicular traffic and positioned so that water ice and other foreign materials cannot enter the spring case through the vent Avoid placing the regulator beneath eaves or downspouts and be sure it is above the probable snow level Overpressure Protection The recommended pressure limitations are stamped on the regulator nameplate Some type of overpressure protection is needed if the actual inlet pressure exceeds the maximum operating outlet pressure rating Overpressure protection should also be provided if the regulator inlet pressure is greater than the safe working pressure of the downstream equipment Regulator operation below the maximum pressure limitations does not preclude the possibility of damage from external sources or debris in the line The regulator should be inspected f
8. or damage after any overpressure condition Startup The regulator is set at the factory for the setpoint specified on the order or at the midpoint of the spring range The allowable spring range is stamped on the nameplate Ifa pressure setting other than specified is desired be sure to change the pressure setting by following the Adjustment section With proper installation completed and relief valves properly adjusted slowly open the upstream and downstream shutoff valves if applicable Adjustment To change the outlet pressure loosen the locknut and turn the adjusting screw clockwise to increase pressure or counterclockwise to decrease pressure Monitor the outlet pressure with a test gauge during the adjustment Tighten the locknut to maintain the desired setting Taking Out of Service Shutdown To avoid personal injury resulting from sudden release of pressure isolate the regulator from all pressure before attempting disassembly Parts List Key Description 1 Valve Body 2 Body Flange 3 Stud Bolt 4 Gasket 5 Lower Indicator Fitting 6 O ring Retainer 7 Indicator O ring 8 Hex Nut 9 Valve Spring 10 Indicator Stem 11 Cage 12 Port Seal 13 Seat Ring 14 Piston Ring 15 Upper Seal 16 Valve Plug 17 Cage O ring 18 Travel Indicator Scale 19 Travel Indicator Protector 20 Valve Plug O ring 21 Lower Indicator Fitting O ring 22 Flange Nut 23 E Ring 24 Drive Screw 25 Flow Arrow 26 Vent 27 Plug 28 Spring Seat 29 Hex Nut
9. uracy they are not to be construed as warranties or guarantees express or implied regarding the products or services described herein or their use or applicability We reserve the right to modify or improve the designs or specifications of such products at any time without notice Emerson Process Management Regulator Technologies Inc does not assume responsibility for the selection use or maintenance of any product Responsibility for proper selection use and maintenance of any Emerson Process Management Regulator Technologies Inc product remains solely with the purchaser A a EMERSON Emerson Process Management Regulator Technologies Inc 2010 2014 All Rights Reserved
Download Pdf Manuals
Related Search
Related Contents
ENDA EPA741 PROGRAMMABLE AC/DC AMMETER Pyle PDH7 Source Technologies Bulletins Microsoft Windows Server for Small Bus CAL 2003 for PC Land based Aquaculture 2014 - 2015 Catalogue La composition des recueils de La Fontaine : esquisse d`un Biostar A760GE Owner's Manual Samsung جالاكسي 4 ACE Mouse IGFBP1 ELISA Kit User Manual Catalog # D Copyright © All rights reserved.