1. ASCO 5310 User s Guide User s Guide ATS Remote Annunciator Catalog 5310 The ASCO Catalog 5310 ATS Remote Annunciator provides remote visual status reporting and push button testing of one ASCO automatic transfer switch sd EMERSON ASCO poweRQuesT Network Power Power Monitoring and Control This User s Guide provides operation information after the ATS Remote Annunciator has been installed and configured It also includes basic troubleshooting Refer to Installation Manual 381333 317 for mounting wiring and configuration TABLE OF CONTENTS page Operation 2 3 Control key switch Alarm silence button Transfer test Flashing light Reset button Troubleshooting Figure 1 shows the status lights and Transfer button BRWOWNMNM PND The Normal source acceptable light upper left is on when the ATS controller accepts the utility source This light 1s off C P when the utility has failed The Emergency source acceptable light upper right is on when the ATS controller accepts the generator source This light is off when the generator is unacceptable low or high voltage low or high frequency or generator is off Utility Generator Emergency The ATS connected to Normal light center left is on when the Normal source source load is being fed by the utility It is off when it is disconnected acceptable i A acceptable from the utility The ATS connected to Emergency light center righ
2. follow this procedure 1 Turn the Control key right to the unlocked position 2 Press and release Transfer button do not hold the button 3 Observe that the generator light comes on generator acceptable 4 Observe that the light in the corner of the button blinks transfer time delay active if used 5 Observe that the ATS connected lights change position transfer from normal to emergency 6 To retransfer the load back to Normal go to section 3 2 381333 316 A ASCO 5310 Note If Feature 2B transfer to emergency time delay is used the transfer may not occur for up to 61 minutes depending upon the ATS and the setting in the controller To bypass cancel this time delay press the Transfer button again and hold it for more than 5 seconds until you hear a beep 3 2 Load Retransfer to Normal source To retransfer the load from the emergency source back to the normal source follow this procedure 1 Turn the Control key right to the unlocked position 2 Press and release the Transfer button do not hold the button 3 Observe that the utility light comes on utility acceptable 4 Observe that the light in the corner of the button blinks retransfer time delay active if used 5 Observe that the ATS connected lights change position transfer from emergency to normal 6 Turn the Control key left to the locked position then remove it Note If Feature 3A retransfer to normal
3. ncelled A lights in the button indicates if the ATS is in the test mode and if a time delay is active See Figures 1 and 2 Power ON Transfer button light Utility Y Generator hidden reset button Alarm silence button Control key switch Figure 2 Control buttons 1 Control key switch The Control key switch prevents unauthorized operation of the ATS Remote Annunciator The key can be removed in either the locked or unlocked positions In the locked position left the buttons do not operate In the unlocked position right all buttons function Page 2 ASCO Power Technologies EMERSON ASCO 5310 Es Press and release the alarm silence button to turn off the audible alarm sound Do not hold the button These are the possible alarm conditions Alarm Condition Product communication error oa 4000 7000 locked out 4000 amp 7000 ATS position error 4000 amp 7000 2 Alarm silence button Alarms can be specific to the ATS or a general common communications error or any configured alarm via the Power Manager NOTICE Before using the transfer button be sure conditons are safe for running the generator and for load transfer O 3 Transfer test Mansi The following operation starts the generator and transfers the load Be sure that conditions are safe to do this operation 3 1 Load Transfer to Emergency source To transfer the load from the normal source to the emergency source
4. t is on when the load is being fed by the generator It is off when it is disconnected from the generator ATS and Pe Transfer time The ATS amp common alarm light lower left is on when an common delay active ATS or common alarm is received It is off when the alarm is alarm cleared See Alarm silence button page 2 Troubleshooting page 4 ATS connected to Normal ATS connected to Emergency The Transfer light lower right is blinking when a load Figure 1 Status lights and Transfer button transfer time delay is active It is off when there is not a load transfer time delay active See Flashing light time delay page 3 381333 316 A 381333 316 A EMERSON ASCO Power Technologies Page 1 User s Guide Operation The ASCO 5310 ATS Remote Annunciator communicates with an ASCO automatic transfer switch ATS to report its status The ATS Annunciator polls the ATS and obtains its status Lights indicate if the ATS is connected to the normal source or the emergency source Source acceptability status for the ATS is also shown In addition the ATS Remote Annunciator can send commands to the ATS to control its operation A control key switch prevents unauthorized operation A transfer test button simulates a normal source outage and transfers the load to the emergency source if acceptable The same button is used to retransfer the load back to the normal source When the button is held any active time delay is ca
5. time delay is used the transfer may not occur for up to 61 minutes depending upon the ATS and the setting in the ATS controller To bypass cancel this time delay press the Transfer button again and hold it for more than 5 seconds ye Transfer 4 Flashing light time delay The light in the Transfer button flashes when a transfer time delay is active The faster the blinking the shorter the delay 1 10 sec blink 0 to 5 second transfer delay 5 to 15 second transfer delay 1 4 sec blink 1 2 sec blink 15 to 60 second transfer delay 1 sec blink over 1 minute transfer delay S 381333 316 A EMERSON ASCO Power Technologies User s Guide A hidden reset button is located just below the Alarm Silence button see Figure 1 The Control key switch must be unlocked The reset button and alarm silence button work together as follows 5 Reset button 5 1 Soft reboot reset keeps user s configurations The soft reboot retains the configurations that you have made To perform a soft reboot press and hold the hidden reset button and the alarm silence button together for less than 3 seconds The configuration parameters remain unchanged 5 2 Hard reboot reset factory default configuration The hard reboot resets all user configuration parameters to factory default settings The configurations that you have made will be erased To perform a hard reboot press and hold the hidden reset but
6. tion Manual 381333 317 Use the configuration details entered on page 2 reconfigure the ATS Annunciator Refer to Installation Manual 381333 317 Check the Ethernet connections ATS Annunciator to the LAN and Power Manager to the LAN Refer to Installation Manual 381333 317 Verify that the protocol on both devices is the same Contact ASCO Services for replacement 800 800 ASCO or customercare asco com EMERSON 381333 316 A
7. ton and the alarm silence button together for more than 15 seconds The default configuration parameters are IP Address 169 254 1 200 Subnet 255 255 255 0 Gateway Other factory default parameters could be checked through Ethernet interface with computer Page 3 User s Guide Troubleshooting Symptom Probable Cause The DC or AC power source is Power ON light is off inadequate or off The unit keeps on resetting due to watchdog reset possibly due to corruption of software The power ON light is blinking Button not held long enough Transfer button does not work load transfer does not occur ATS Annunciator could have changed to default settings Communication with the Power Buzzer is beeping continuously Manager may have stopped Communication protocol may not the same as that of the Power Manager if present Communication alarm occurs but all configurations are correct ATS Annunciator is not functioning properly A light does not come on when a corresponding button is pressed Page 4 ASCO Power Technologies ASCO 5310 Recommended Action Restore the DC or AC power supply Check the terminals fuse circuit breaker Refer to Installation Manual 381333 317 Try to reprogram the unit with the latest software Contact ASCO Services for replacement 800 800 ASCO or customercare asco com Hold the button for at least 5 seconds until you hear a beep Refer to Installa
Download Pdf Manuals
Related Search
Related Contents
Digitus 19" console PerkinElmer Perkin Elmer - lambda 20 - Perkin Elmer Uvvis-spectrophotometer Lam KOHLER K-702202-G54-MX Installation Guide 1. Monter un projet artistique et culturel - CRDP Basse Agilent VISA User`s Guide Mode d`emploi - r. stahl home Minka Lavery 4404-581 Instructions / Assembly Atoll AM100SE audio amplifier Epson 455Wi Installation Guide Copyright © All rights reserved.