Bradford-White Corp EF Series User's Manual

image

Contents

1. CAUTION The vent shall terminate a minimum of 12 inches dove expected snowfall level to prevent blockage of vent termination The horizontal centerline of the exhaust vent terminal if applicable must not be located lower than the horizontal centerline of the air intake terminal if vented through the same wall A service drain loop must be installed in the drain tubing to serve as a condensate trap to prevent flue gases from escaping in the room DO NOT position the air intake above the exhaust terminal NEVER locate the air intake where exhaust gases can be introduced 18 NOTICE Before beginning installation of any vent pipe read the vent pipe manufacturer s installation instructions Water heater must be protected from freezing downdrafts during shutdown periods Provide protection of the building materials from degradation by flue gases from the exhaust vent terminal VENTING The venting instructions must be followed to avoid restricted combustion or recirculation of flue gases Such conditions cause sooting or risks of fire and asphyxiation This water heater can be installed as either a direct vent system or power vent air from inside system If it is installed as a direct vent system then the air intake and the exhaust vent are piped to the outside If a power vented system is used then air is drawn from inside and only the exhaust is piped to the outside Determine which system is best for your applicatio
2. LOCATE WATER HEATER in front of final position before removing crate 1 LOCATE so that venting connections will be short and direct 2 THIS WATER HEATER IS SUITABLE FOR INSTALLATION ON COMBUSTIBLE FLOOR Do not install this water heater on carpeting 3 FOR BASEMENT INSTALLATION provide a solid level elevated base such as concrete 4 Minimum clearance to combustible material is 0 for the Top Sides and Rear of this water heater However it is recommended that at least 18 from the Top 24 from the Front and 4 for the Sides and Rear of the water heater be provided for servicing Clearance for servicing may be reduced down to minimum clearance to combustible material but service time and effort may be greatly increased Figure 3 Minimum Clearance To Combustible 10 REMOVE CRATE 1 Remove all banding and pry off crate sides carefully so as not to damage the water heater 2 Carefully roll lift the water heater from the crate base Z N CAUTION Do not drop water heater Do not bump water heater jacket against floor Do not bump exhaust vent pipe against crate or other objects This will damage the heater and cause it to be inoperable or create nuisance problems MOVE WATER HEATER TO PERMANENT POSITION by sliding or walking Place drain pan underneath water heater INSTALL TEMPERATURE AND PRESSURE RELIEF VALVE if not already installed A 4 WARNING Temperature and pressure relief valve discharge
3. ULTRA HIGH EFFICIENCY COMMERCIAL GAS WATER HEATER EF Series Models A WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the N gas supplier s instructions If you cannot reach your gas supplier call the fire department BRADFORD WHITE Installation and service must be performed by a qualified installer service agency or gas supplier ities PA 19002 Tech Service 800 334 3393 Service Parts 800 538 2020 Warranty Service 800 531 2111 Part No 238 44445 00B 03 04 INSTALLATION OPERATING MANUAL WITH TROUBLESHOOTING GUIDE PLACE THESE INSTRUCTIONS ADJACENT TO WATER HEATER AND NOTIFY OWNER TO KEEP FOR FUTURE REFERENCE SECTION I IMPORTANT INFORMATION This gas fired water heater is design certified by CSA International under the American National Standard Z21 10 3 as indicated on the rating plate and CAN CGA 4 3 M as indicated on the rating plate available from CSA Standards Association 178 Rexdale Blvd Etobicoke Ontario Canada MOW IR3 This water heater must be in
4. 12 inches of the enclosure bottom e Each opening shall have a free area of at least one square inch per 1000 Btu h of the total input of all appliances in the enclosure but not less than 100 square inches 2 Ifthe confined space is within a building of tight construction air for combustion and ventilation must be obtained from outdoors This may be accomplished by piping air directly to the water heater from outside or providing opening or ducts in the wall When directly communicating with the outdoors through vertical ducts two permanent openings located in the above manner shall be provided e Each opening shall have a free area of not less than one square inch per 4000 Btu h of the total input of all appliances in the enclosure e If horizontal ducts are used each opening shall have a free area of not less than one square inch per 2000 Btu h of the total input of all appliances in the enclosure 3 If the water heater is installed as a direct vent outside air piped directly to the water heater then additional opening other than the opening for the air intake are not required However adequate ventilation air must be provided in all cases to prevent increased room temperature CHEMICAL VAPOR CORROSION Corrosion of the flue ways and vent system will occur if air for combustion contains certain chemical vapors Such corrosion may result in poor combustion and create a risk of asphyxiation Spray can propellants cleaning solvents
5. 3 5 kPa The supply line must be capped when not connected to the water heater If copper supply lines are used they must be internally tinned and certified for gas service 31 COMBUSTION SURROUND WATER HEATER Figure 24 Drip Leg The gas supply lines must meet all requirements of the National Fuel Gas Code ANSI Z223 1 Latest Edition or in Canada CAN CGA B149 1 Natural Gas Installation Code Latest Edition or CAN CGA B149 2 Propane Installation Code Latest Edition GAS METER SIZE NATURAL GASES ONLY Be sure that the gas meter has sufficient capacity to supply the full rated gas input of the water heater as well as the requirements of all other gas fired equipment supplied by the meter If the gas meter is too small ask the gas company to install a larger meter having adequate capacity GAS PRESSURE REGULATION Main line gas pressure to the water heater should be between a maximum 14 0 inch W C and a minimum supply pressure as shown on the rating plate The inlet gas pressure must not exceed the maximum value BEFORE PLACING THE WATER HEATER IN OPERATION CHECK FOR GAS LEAKAGE USE SOAP AND WATER SOLUTION OR OTHER MATERIAL ACCEPTABLE FOR THE PURPOSE OF LOCATING GAS LEAKS Z WARNING DO NOT USE MATCHES CANDLES FLAME OR OTHER SOURCES OF IGNITION FOR THIS PURPOSE 32 SECTION VIII ELECTRICAL CONNECTIONS Z N WARNING Turn off or disconnect the electrical power supply to the water heater before se
6. Such valves are available from the local plumbing DANGER 0 HOT II BURN Water temperatures aver 1257 52 C can cause severe bums instantly or death from scalds Children disabled and elderly are at highest risk of being scalded See Temperature Adjustment section of this manual before setting thermastat at water heater Feel water before bathing or showering Temperature limiting valves are available consult lacal plumbing supplier Figure 9 Scald Warning The following chart details the relationship of water temperature and time with regard to scald injury and may be used as a guide in determining the safest water temperature for your applications Approximate Time Temperature Scald Chart APPROXIMATE TIME TEMPERATURE RELATIONSHIPS IN SCALDS More than 5 minutes 1 to 2 minutes About 30 seconds 1 Less than 5 seconds Less than 3 seconds About 1 seconds About 1 second Table 2 2 About 10 seconds 5 16 ALTERNATE SPACE HEATING WATER CONNECTIONS AN Z DANGER Toxic chemical such as those used for boiler treatment shall not be introduced into potable water used for space heating This water heater shall not be connected to an existing heating system or component s previously used with a non potable water heating appliance All piping components connected to this water heater for space heating applications must be suitable for use with potable water WW CL WA
7. maximum set pressure not to exceed the maximum working pressure of the water heater The combination temperature and pressure relief valve rating must not be less than the hourly rating of the water heater Install the combination temperature and pressure relief valve into the opening provided and marked for this purpose on the water heater Note Some models may already be equipped or supplied with an installed combination temperature and pressure relief valve Verify that the combination temperature and pressure relief valve complies with local codes If the combination temperature and pressure relief valve does not comply with local codes replace it with one that does Follow the installation instructions above on this page Install a discharge line so that water discharged from the combination temperature and pressure relief valve will exit within six 6 inches 15 2 cm above or any distance below the structural floor and cannot contact any live electrical part The discharge line is to be installed to allow for complete drainage of both the combination temperature and pressure relief valve and the discharge line The discharge opening must not be subjected to blockage or freezing DO NOT thread plug or cap the discharge line It is recommended that a minimum clearance of four 4 inches 10 0 cm be provided on the side of the water heater for servicing and maintenance of the combination temperature and pressure relief valve Do not place a
8. Add 2 feet of venting for every 45 elbow 4 Total vent length can not exceed Max Vent Length in Table 4 NOTICE Do not include the 3 exhaust elbow or vent terminals in determining maximum vent length COAXIAL VENTING INSTALLATION PROCEDURE WARNING Improper installation adjustment service or maintenance can cause property damage personal injury or death Consult a qualified installer service agency or the gas supplier for information or assistance This kit must be used only for terminating this water heater Do not use this termination kit for any other appliance Using this kit on other appliances and or water heaters can result in property damage personal injury or death DO NOT operate this water heater until the installation and assembly of this kit is complete and the piping completed Failure to wmplete installation before operation can result in property damage personal injury or death Before beginning any installation be sure the main electrical disconnect switch is in the OFF position Electrical 27 shock can cause personal injury or death DO NOT operate this water heater with the rain cap removed or recirculation of combustion products may occur Water may also collect inside larger combustion air pipe and flow to the burner assembly Failure to follow this warning could result in product damage or improper operation personal injury or death Z N CAUTION DO NOT use field supplied
9. NOT ATTEMPT TO REPAIR THERMOSTAT BOARD DO NOT ATTEMPT TO REPAIR TRANSFORMER DO NOT ATTEMPT TO REPAIR PRESSURE SWITCH GENERAL KEEP APPLIANCE AREA CLEAR AND FREE FROM COMBUSTIBLE MATERIALS GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQUIDS Water heater maintenance includes periodic tank flushing and cleaning and removal of lime scale The unit should be inspected and adjusted to maintain proper combustion Refer to Table 5 Suggested Maintenance Schedule A periodic inspection of the venting system should be made MAINTENANCE SCHEDULE Following are the instructions for performing some of the recommended maintenance Unit inspection and adjustment should be performed by a competent technician Suggested Maintenance Schedule COMPONENT OPERATION INTERVAL REQUIRED Sediment Removal Monthly Flushing Required Relief Valve Check Operation Semi Annually Operation Clean Inlet Screen Soft Brush Vent amp Air Joints should S y P y and dirt Remove object Vent Terminal Piao Shrubs i Monthly that caused Debris ai restriction System Month Line restriction Table 5 37 FLUSHING WATER HEATER 1 Turn OFF the water heater electrical disconnect switch 2 Open the drain valve and allow water to flow until it runs clean 3 Close the drain valve when finished flushing 4 Turn ON the water heater electrical disconnect switch DRAINING WATER HEATER The water heater must be drained if it is to be shut down and exposed to
10. PRESSURE RELIEF VALVE IS INSTALLED IN THE RELIEF VALVE OPENING OF THE WATER HEATER GENERAL INSTRUCTIONS TO FILL THE WATER HEATER 1 Close the water heater drain valve by turning the knob or valve stem clockwise If alternative water connections are provided but not used make certain they are plugged i e rear connections 2 Open the cold water supply shut off valve 3 Open several hot water faucets to allow air to escape from the system 4 When a steady stream of water flows from the faucets the water heater is filled Close the faucets and check for water leaks at the water heater drain valve combination temperature and pressure relief valve and the hot and cold water connections SEQUENCE OF OPERATION 1 A call for heat from thermostat 2 Blower ON 3 Pressure switch proves blower operation 4 Blower pre purge 5 Igniter warm up 6 Main burner ON 7 Flame signal confirmed 8 Thermostat satisfied 9 Main burner OFF 10 Blower post purge 34 LIGHTING INSTRUCTIONS FOR YOUR SAFETY READ BEFORE LIGHTING WARNING If yu do not follow these instructions exactly a fre of explosion may result cousing property damoge personol injury or loss of fife A This appliance does nol have o piki pei cannot reach your gas suppher H ts equipped with an ignition device the fire department which automatically lights the bumer Tum off moin power to the water Do not try to light the burner by homad heater B BEFOR
11. be directly stressed or high thermal stresses may be formed when the pipe heats up and expands Install accordingly to minimize such stresses Follow the following procedure to vent through the wall 1 Cut two 3 1 2 in 8 9 cm diameter holes for 3 7 6 cm diameter pipe or 4 1 2 11 4 cm diameter holes for 4 10 2 cm diameter pipe in the wall with the centerline hole distances at least 18 45 72 cm apart in the location where the exhaust vent and air intake terminals will exit the outside wall if vented on the same wall Use the proper PVC cement to secure the 90 exhaust vent and air intake terminals provided with the water heater to the plastic pipes The distance between the back edge of the 90 exhaust vent terminal and the exterior wall see Figure 13 must be 6 inches 12 7 cm more for the exhaust vent terminal than the air intake terminal Use the proper cement or sealant and assembly procedures to secure the vent connector joints between the terminal and the blower outlet Provide support brackets for every 3 feet 91 m of horizontal vent 21 EVERY 3 MN SUPPORT BRACKET 90 EXHAUST Figure 13 Typical Horizontal Direct Vent System Vertical Installation Vertical venting system must_be supported every 5 feet of vertical run and every 3 feet of horizontal run of vent pipe length Stress levels in the pipe and fittings can be significantly increased by improper installation If rigid pipe
12. clamps are used to hold the pipe in place or if the pipe cannot move freely through a wall penetration the pipe may be directly stressed or high thermal stresses may be formed when the pipe heats up and expands Install accordingly to minimize such stresses Follow the following procedure to vent through the roof 1 Cut the necessary holes through the roof and ceiling 2 Install the exhaust vent and air intake plastic pipes as shown in Figure 14 Make sure that the installation meets the local codes and or The National Fuel Gas Code ANSI Z223 1 Latest Edition or CGA CAN B149 Installation Code 22 90 EXHAUST TERMINAL 90 INTAKE TERMINAL SUPPORT BRACKET ELEVATED BASE Figure 14 Typical Vertical Direct Vent System Installation Through The Wall Venting With Low Ground Clearance When venting cannot exit through the wall at a height greater than or equal to 12 30 5 cm and above expected snow level from the ground then the installation must be modified as shown below see Figure 15 AT 7 5 cm OR 4 10 2 cm PVC 90 INTAKE OR EXHAUST TERMINAL 1 2 54 em FOR INTAKE TERMINAL 6 15 2 om FOR EXHAUST TERMINAL Figure 15 Vent Terminal Low Ground Clearance 23 Maximum Vent Length Direct Vent Maximum Vent Length Model Max Vent Length feet Max Vent Length feet Number 3 PVC CPVC or ABS 4 PVC CPVC or ABS EF60T125 EF100T150 120 170 EF60T150 EF100T199 100 150 EF60T199 EF10
13. energy efficiency both to heat the water and to maintain the storage temperature during standby periods Lower water temperatures also extend tank life Remember no water heating system will provide exact temperatures at all times Allow a few days of operation at this setting to determine the correct temperature setting consistent with the requirements for the installation 1 CAUTION This water heater when set at a lower temperature setting is not capable of producing hot water of sufficient temperature for sanitizing purposes 35 During the winter season or any cold period you may desire a higher temperature setting to adjust for the colder incoming water This adjustment however may cause additional condensation to form on the colder tank surface This does not mean the tank is leaking During summer months the warmer incoming water temperatures will benefit the performance of your water heater and reduce the amount of condensation developed Condensation does not mean your tank is leaking Most of reported tank leaks on installation are proven to be condensation To avoid unnecessary inconvenience and expense make sure the tank is leaking before calling an independent servicing contractor or qualified service professional DANGER Hotter water increases the risk of scald injury Scalding may occur within 5 seconds at a temperature setting of 135 F 57 C To protect against hot water injury install an ASSE approved mixing
14. freezing temperatures Maintenance and service procedures may also require draining the water heater 1 Turn off the water heater electrical disconnect switch 2 Connect a hose to the drain valve 3 Locate hose s discharge in an area where hot water will not cause any damage or injury 4 Close the cold water inlet valve to water heater 5 Open a nearby hot water faucet to vent the system 6 Open the heater drain valve 7 If the water heater is being drained for an extended shutdown it is suggested the drain valve be left open during this period FILLING WATER HEATER 1 Close the water heater drain valve by turning the knob or valve stem clockwise If alternative water connections are provided but not used make certain they are plugged i e rear connections 2 Open the cold water supply shut off valve Open several hot water faucets to allow air to escape from the system 4 When a steady stream of water flows from the faucets the water heater is filled Close the faucets and check for water leaks at the water heater drain valve combination temperature and pressure relief valve and the hot and cold water connections w SEDIMENT AND LIME SCALE REMOVAL Waterborne impurities consist of the particles of soil and sand which settle out and form a layer of sediment on the bottom of the tank The amount of calcium carbonate lime released from water is in direct proportion to water temperature and usage The higher the water tempe
15. kg m The manufacturer of this water heater will not be liable for any damage or injury caused as a result of a cracked gas inlet as a result of excessive torque This water heater and its gas connection must be leak tested before placing the water heater in operation Check for gas leaks with a soap and water solution and a brush or a commercial leak detector fluid NEVER USE A MATCH OR OPEN FLAME FOR TESTING The water heater is not intended for operation at higher than 14 0 inch water column psi supply gas pressure Higher gas supply pressures require supplemental reducing service regulation Exposure to higher gas supply pressure may cause damage to the gas controls which could result in fire or explosion If overpressure has occurred such as through improper testing of gas lines or emergency malfunction of the supply system the gas valve must be checked for safe operation Make sure that the outside vents on the supply regulators and the safety vent valves are protected against blockage These are parts of the gas supply system not the water heater The water heater and individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of the system at test pressures in excess of 1 2 psi 3 5 kPa The water heater must be isolated from the gas supply piping system by closing its manual shutoff valve during any pressure testing of the gas supply system at test pressures equal to or less than 1 2 psi
16. must terminate so that proper clearances are maintained as cited in local codes or the latest edition of the National Fuel Gas Code ANSI Z223 1 73 4e and 7 8a b as follows 1 Do not terminate the exhaust vent terminal over public area where condensate or vapor can cause nuisance or hazard 2 For direct vent the venting system shall terminate at least 1 foot below 1 foot horizontally from or 1 foot above any door window or gravity air inlet into building 3 For horizontal the venting system shall terminate 4 foot below 4 foot horizontally from or 1 foot above any door window or gravity air inlet into building 4 The manufacturer also recommends the vent system terminations not be installed closer than 3 feet from an inside corner of an L shaped structure 3 The vent termination shall not be mounted directly above or within 3 feet horizontally from an oil tank vent or gas meter to avoid potential freeze up from condensation 6 The vent shall terminate a minimum of 12 inches above expected snowfall level to prevent blockage of vent termination Vent pipes serving power vented appliances are classified by building codes as vent connectors Required clearances from combustible materials must be provided in accordance with information in this manual under LOCATION OF WATER HEATER and CLEARANCES and with National Fuel Gas Code and local codes 20 NOTICE This unit can be vented using only PVC Class 160 ASTM D2241 Schedule 40 A
17. overall dimension by more than 60 in See Fig 19 CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL ROOF BOOT FLASHING FIELD SUPPLIED FIELD SUPPLIED COMBUSTION AR Figure 22 Concentric Vent Roof Top Attachment Install rain cap and small diameter pipe assembly in roof penetration assembly Ensure small diameter pipe is cemented and bottomed in Y concentric fitting Cement heater combustion air and vent pipes to concentric y fitting assembly Figure 20 See Figure 22 for proper pipe attachment Operate heater through one cycle to ensure combustion air and vent pipes are properly connected to concentric vent termination connections Horizontal Installation 1 2 3 4 Become familiar with coaxial vent kit part no 239 44069 01 As shown in Figures 19 through 21 Determine the best location for the termination kit NOTICE Position termination where vent vapors will not damage plants shrubs or air conditioning equipment Position termination where vent vapors will not be adversely effected by wind condition Position termination where it will not be damaged or be subjected to foreign objects Position termination where vapors will not be objectionable Cut the recommended 5 diameter hole Partially assemble vent kit a Cement Y concentric fitting to larger diameter kit pipe See Figure 20 29 b Cement rain cap to smaller diameter kit pipe See Figure 21 Install concentric Y fitting and p
18. replace vacuum switch If filled empty hose Is the Pressure Switch exhaust pressure switch N O If no then check the hose and see if it is filled with condensate If the hose is not filled with condensate then replace pressure switch If filled empty hose Is the Collector Limit Switch N C If no then reset switch If this switch trips more than 3 times call service If all items above are ok then replace the blower Ignitor does not glow Is there voltage to the Hot Surface Ignitor Check for 120VAC to the ignitor from the ignition module 41 Is there continuity across the Hot Surface Ignitor If no then replace hot surface ignitor If yes then replace the ignition module Main valve does not turn on Put your hand on the gas valve When the Valve LED lights on the ignition module can you feel it energize If not then check the voltages at the ignition module across pins 2 and 7 on the plug CONTROL If there is 24 VAC across these pins then check to see if the Rectifier Harness is secure If it is secure then replace the Gas Valve If you can feel the gas valve energize check the main gas supply is not in the off position Burner Flame keeps going out Is there minimum gas supplied to water heater as stated on the rating plate If not then increase the supply pressure to the water heater Measure the microAmps through the flame sensor using a multimeter Is there a
19. the tank head to extend tank life The anode rods should be inspected periodically for corrosion and replaced when necessary to prolong tank life Water conditions in your area will influence the time interval for inspection and replacement of the anode rods The use of a water softener may increase the speed of anode consumption More frequent inspection of the anodes is needed when using softened or phosphate treated water Contact the installing contractor or service provider that installed the water heater or the manufacturer listed on the rating plate for anode replacement information DISHWASHING MACHINE REQUIREMENTS All dishwashing machines meeting the National Sanitation Foundation requirements are designed to operate with water flow pressures between 15 and 25 pounds per square inch Flow pressures above 25 pounds per square inch or below 15 pounds per square inch will result in improperly sanitized dishes The National Sanitation Foundation also recommends circulation of 180 F water Where this is done the circulation should be very gentle so that it does not cause any unnecessary turbulence inside the water heater The circulation should be just enough to provide 180 F water at the point of take off to the dishwashing machine Adjust flow by means of the valve in the circulation line SECTION IV INSTALLATION INSTRUCTIONS VA Z WARNING INSTALLATION OF THIS WATER HEATER REQUIRES ABILITY EQUIVALENT TO THAT OF A LICENSED TR
20. 0T250 80 130 EF100T300 60 120 Table 3 Determining required vent length Determine the total length of straight vent pipe in feet required for both the intake and the exhaust Add 5 feet of venting for every 90 elbow Add 2 feet of venting for every 45 elbow Total vent length can not exceed Max Vent Length in Table 3 Air intake can not exceed exhaust by more than 30 feet in any venting situation NOTICE Do not include the 3 exhaust elbow or vent terminals in determining maximum vent leng Oe aoe POWER VENT INSTALLATION Power venting is where the indoor air is used and the exhaust is vented to the outside Venting may be run horizontally through an outside wall or vertically through a roof through using either 3 inch 7 6 cm or 4 inch 10 2 cm diameter PVC ABS or CPVC This water heater is supplied with a screened intake and exhaust 90 elbow referred to as the exhaust vent terminal and the air intake terminal Power Vent Terminal Location Refer to the Direct Vent Terminal Location section previously mention to determine the proper exhaust vent location Plan the vent system layout so that proper clearances are maintained from plumbing and wiring Vent pipes serving power vented appliances are classified by building codes as vent connectors Required clearances from combustible materials must be provided in accordance with information in this manual under LOCATION OF WATER HEATER and CLEARANCES a
21. ADESMAN IN THE FIELD INVOLVED PLUMBING AIR SUPPLY VENTING GAS SUPPLY AND ELECTRICAL WORK ARE REQUIRED DO NOT ATTEMPT TO LIGHT ANY GAS APPLIANCE IF YOU ARE NOT CERTAIN OF THE FOLLOWING Liquefied petroleum gases propane gas and natural gas have an odorant added by the gas supplier that aids in detection of the gas Most people recognize this odor as a sulfur or rotten egg smell Other conditions such as odorant fade can cause the odorant to diminish in intensity or fade and not be as readily detectable If you have a diminished sense of smell or are in any way unsure of the presence of gas immediately contact your gas supplier from a telephone in another building Gas detectors are available Contact your gas supplier or plumbing professional for more information Liquefied petroleum gases propane gas is heavier than air and will remain at floor level if there is a leak Basements crawl spaces closets and areas below ground level will serve as pockets for accumulation of leaking gas Before lighting smell all around the appliance area for gas Be sure to smell next to the floor IF YOU SMELL GAS Do not try to light any appliance Do not touch any electric switch do not use any telephone in your building Immediately call your gas supplier from a telephone in another building Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department DO NOT OPERATE THE APPLIANCE UNT
22. E OPERATING smell ad around D Do not use this appliance any part the opplonce far gas Be sure to han been under water Immediately smell next to the floor because some cal a qualified service technician 10 gos is heavier than air and vil cattle inspect the appliance and io replace on the floor any pari of the control system and WHAT TO DO IF YDU SMELL GAS any gas control which has been Da not try ta Kght om appliance under water Da not touch any electric switch do not use any phone in your building LIGHTING INSTRUCTIONS STOP read the safety information above 6 Walt 5 minutes to clear ot any gas on this Kiel i yu safety Ta gos SE Falow Zu Sel ihe thermostat to lowest setti n the safety infarmatian above an this Turn ofi dl claetrleed power ta the aal E you don t smal gas go to next appliance This appliance does not hove o pilot 7 Set the thermostat to desired setting H ts equipped with an ignition device 8 Tum on main power which automaticaly ight the burner Do nat try do light the burner by hand Turn off the moin power switch UGHTED MAIN POWER SWITCH TO TURN OFF GAS TO APPL ANCE 1 Set the thermapiat to lowest setting 2 Tum off moin the mom power switch Figure 26 Lighting Instruction Label TEMPERATURE ADJUSTMENT The temperature selector knob of the thermostat has been adjusted to 120 F when shipped from the factory NOTICE The lower the temperature setting the greater the
23. IL THE LEAKAGE IS CORRECTED Z N WARNING This water heater must be located in an area where leakage of the tank water line connections or the combination temperature and pressure relief valve will not result in damage to the area adjacent to the water heater or to lower floors of the structure When such locations cannot be avoided a suitable drain pan must be installed under the water heater The drain pan depth must be suitable for draining and collecting water and have a minimum length and width of at least four 4 inches 10 0 cm measured from the jacket of the water heater The drain pan as described above can be purchased from your plumbing professional The drain pan must be piped to an adequate drain The piping must be at least 4 inch 2 0 cm in diameter and pitched for proper drainage UNPACKING INSPECT SHIPMENT carefully for any signs of damage 1 All equipment is carefully manufactured inspected and packed 2 Any claims for damage or shortage in shipment must be filed immediately with Bradford White Corporation and noted on the Bill of Lading 3 Remove all venting components from the combustion assembly compartment by removing the latches NOTICE The vent terminals and the condensate elbow that is supplied with this water heater are stored at the top in the Combustion Assembly Compartment To access the vent terminals and condensate elbow unlatch the top lid and remove parts Be sure to replace the top and relatch
24. M Examine the vent and air intake system every 3 months Points of inspection are as follows 1 Check for obstructions and or deterioration of vent piping and vent terminal Replace immediately where needed 2 Vent pipe and vent hood screen should be cleaned of any foreign material The screen is located inside the vent hood outlet and is accessible from the outside of the hood Do not reach inside the vent hood when the water heater is in operation 3 Check all vent system connections for leakage and reseal as required COMBUSTION SYSTEM INSPECTION Inspect the operation of the combustion system monthly Use the following procedure to inspect the combustion system 1 Turn off the main power switch of the water heater Adjust the thermostat to the Min setting Remove the top of the combustion surround by unlatching it While observing the ignition module turn on the main power switch Adjust thermostat to the Max setting Watch the LED s light as the controller goes through the S OP as previously described Upon ignition observe the main burner flame Readjust thermostat to previous setting Replace combustion surround top and latch it securely in place cb Alle 40 SECTION XI TROUBLESHOOTING GUIDE Main power light is not lit Make sure that water heater is plugged in When the switch is on is there 120 VAC between L1 and N on the terminal block If not then check for loose wire connections on the Power Switch Wire Ha
25. RNING When the system requires water for space heating at temperatures higher than required for other means a tempering valve shall be installed to temper the water for those uses in order to reduce the scald hazard potential Failure to properly pipe this water heater may result in improper operation and damage to the water heater or structure Oxygen contamination of this water heater will cause corrosion of iron and steel components and can lead to water heater failure Connect the system supply and return piping to the water heater Refer to Figure 10 and Figure 11 for installation examples Maintain a minimum 2 clearance from hot water piping to combustible materials T amp P RELIEF VALVE COLD WATER INLET RETURN FRON SYSTEN HEAT EXCHANGER Figure 10 Alternate Space Heating Connections 17 18 MIN IF CONVENTIONAL UNEN AR SEPARATOR RE TEE BALL VALVE PRESSURE GAUGE EF SERIES WATER HEATER BALL VALVE PRESSURE RELIEF VALVE TO HYORONK HEATING ZDNE S lt COLD WATER SUPPLY x POTABLE WATER f BALL VALVE EXPANSION TANK PRESSURE 4S REDO REDUCING VALVE SPACE HEATING HEATING ZONE S BALL VALVE DENOTES THAT THE SPECIFIC COMPONENT NEEDS TO BE PROPERLY SIZED FOR THE SYSTEM THAT S BEING DESIGNED Figure 11 Typical Plumbing Schematic for Zoned Heating SECTION VI VENTING WARNING The vent system must be properly installed Failure to properly install the vent system
26. STM D 1785 or Cellular Core Schedule 40 DWV ASTM F891 Schedule 40 CPVC ASTM F411 or ABS ASTM D 2661 pipe The fittings other than the TERMINATIONS should be equivalent to PVC DWV fittings meeting ASTM F2665 Use CPVC fittings ASTM F438 for CPVC pipe and ABS fittings ASTM D 266 3311 for ABS pipe If CPVC or ABS pipe and fittings are used then the proper cement must be used for all joints including joining the pipe to the Termination PVC material PVC materials should use ASTM D2564 grade cement CPVC materials should use ASTM F 493 grade cement and ABS materials should use ASTM D 2235 grade cement For water heaters in locations with high ambient temperatures above 100 F and or insufficient dilution air it is recommended that CPVC or ABS pipe and fittings MUST USE SUPPLIED VENT TERMINAL be used Horizontal Installation In a horizontal application it is important that condensate not be allowed to buildup in the exhaust vent pipe To prevent this from happening the pipe should be installed with an slight upward slope so the condensate will run back toward the water heater The vent system should be supported every 5 feet of vertical run and every 3 feet of horizontal run of vent pipe length Stress levels n the pipe and fittings can be significantly increased by improper installation If rigid pipe clamps are used to hold the pipe in place or if the pipe cannot move freely through a wall penetration the pipe may
27. ands Install accordingly to minimize such stresses 25 Follow the following procedure to vent through the roof 1 Cut the necessary holes through the roof and ceiling 2 Install the exhaust vent and air intake plastic pipes as shown in Figure 17 Make sure that the installation meets the local codes and or The National Fuel Gas Code ANSI Z223 1 Latest Edition or CGA CAN B149 Installation Code 90 EXHAUST TERMINAL SUPPORT BRACKET 90 INTAKE TERMINAL SUPPORT BRACKET ELEVATED BASE Figure 17 Typical Vertical Power Vent System Installation Through The Wall Venting With Low Ground Clearance When venting cannot exit through the wall at a height greater than or equal to 12 30 5 cm and above expected snow level from the ground then the installation must be modified as shown below see Figure 18 Refer to Tables 3 or 4 for maximum venting lengths using 3 7 6 cm or 4 10 2 cm diameter plastic pipe 26 AT 7 5 cm OR 4 10 2 cm PVC 90 INTAKE OR EXHAUST TERMINAL 1 2 84 em FOR INTAKE TERMINAL 6 15 2 cm FOR EXHAUST TERMINAL Figure 18 Vent Terminal Low Ground Clearance Maximum Vent Length Determination Power Vent Maximum Vent paver EF60T125 EF100T150 EF60T150 EF100T199 EF60T199 EF100T250 EF100T300 Table 4 Determining required vent length 1 Determine the total length of straight vent pipe in feet required 2 Add 5 feet of venting for every 90 elbow 3
28. ations of the PVC PVC cellular core ABS or CPVC piping materials that you are about to use Know the reputation of your pipe and cement manufacturer and their products Know your own qualifications or those of your contractor The solvent welding technique of joining PVC PVC cellular core ABS or CPVC pipe is a specialized skill just as any other pipe fitting technique Closely supervise the installation and inspect the finished job before start up Contact the manufacturer supplier or competent consulting agency if you have any questions about the application or installation of PVC PVC cellular core ABS or CPVC pipe Take the time and effort to do a professional job Shortcuts will only cause you problems and delays in start up The majority of failures in these systems are the result of shortcuts and or improper joining techniques 30 SELECTION OF MATERIALS PRIMER It is recommended that Tetrahydrofuran THF be used to prepare the surfaces of pipe and fittings for solvent welding Do not use water rags gasoline or any other substitutes for cleaning PVC cellular core ABS or CPVC surfaces A chemical cleaner such as MEK may be used CEMENT The cement should be a bodied cement of approximately 500 to 1600 centipoises viscosity containing 10 20 by weight virgin PVC material solvated with tetrahydrofuran THF Small quantities of dimethylformamide DMF may be included to act as a retarding agent to extend curing time Select the pr
29. correct part number 6 Install gasket and cleanout plate Be sure to draw plate up tight by tightening screws securely 7 Close the drain valve Open a hot water fixture to allow air to escape Open the cold water supply to water heater and allow the tank to fill Follow the lighting instructions 8 Check for water leakage 9 Install outer jacket cover plate ANODE INSPECTION AND REPLACEMENT This water heater is equipped with multiple sacrificial anodes Anodes protect the glass lined tank from corrosion by sacrificing themselves through electrolysis When the anode material is consumed there is no more protection and corrosion of the tank accelerates Inspection of the anode every 6 months allows you to identify the rate of anode degradation The anode should be replaced when its diameter is 3 8 of an inch or annually which ever is first Aggressive very hot and softened water causes rapid consumption of the anode requiring frequent inspections The replacement anodes rods are available from your Bradford White distributor To inspect or replace an anode The anodes on this water heater are easily accessible from the top of the water heater making replacement simple and quick Use the following procedure to remove and inspect the anodes Drain the heater Refer to DRAINING THE WATER HEATER instructions in this section Flush the heater Refer to FLUSHING THE WATER HEATER instructions in this section Remove the combustion surroun
30. could result in property damage personal injury or death DO NOT install damaged venting system components If damage is evident then please contact the supplier where the water heater was purchased or the manufacturer listed on the rating plate for replacement parts Use only the vent terminals provided or factory authorized terminals for venting this water heater The water heater requires its own separate venting system Do not connect the exhaust vent into an existing vent pipe or chimney All of the exhaust venting connections must be leak checked with a soap solution upon initial start up of the water heater Any leaks must be repaired before continuing operation of the water heater Do not terminate the venting where noise from the exhaust or intake will be objectionable This includes locations close to or across from windows and doors Avoid anchoring the vent and intake pipes directly to framed walls floors or ceilings unless rubber isolation pipe hangers are used This prevents any vibrations from being transmitted into the living spaces Do not exceed the venting distances or the number of elbows listed in this manual Exceeding the maximum venting distances may cause the water heater to malfunction or cause an unsafe condition DO NOT operate this water heater until the venting installation is complete and the piping completed Failure to complete installation before operation can result in property damage personal injury or death
31. couplings to extend pipes Airflow restriction will occur and the water heater pressure switches may cause intermittent problems Vertical Installation Recommended 1 Become familiar with coaxial vent kit part no 239 44069 01 PVC INTAKE CDMBUSTION AIR 4 NONINAL 45 3 4 2 1 2 DA PIPE 4 DIA PIPE CONCENTRIC Y FITTING Figure 20 Concentric Vent Kit Part Identification 2 Determine the best location for the termination kit 3 Cut the recommended 5 diameter hole 4 Partially assemble vent kit by performing the following a Cement concentric Y fitting to larger diameter pipe See Figure 20 b Cement rain cap to smaller diameter pipe See Figure 21 DRILL CLEARANCE HOLE IN RAIN CAP AND PILOT HOLE IN VENT CAP STAINLESS STEEL SCREW FIELD SUPPLIED Figure 21 Rain Cap to Small Vent Pipe Ass y 28 5 Install concentric Y fitting and pipe assembly through the structure s hole and field supplied roof boot flashing Do not allow insulation or other materials to accumulate inside pipe assembly when installing through the hole Secure assembly to roof structure as shown in Figure 22 using field supplied metal strapping or equivalent support material NOTICE Ensure termination height is above the roof surface or anticipated snow level Figure 22 If assembly is too short to meet height requirements the 2 pipe supplied in the kit may be replaced by using the same diameter pipe DO NOT extend the
32. d top by unlatching Remove the second pass access cover If equipped Remove the second pass insulation Remove the second pass collector cover Remove the anode using a socket of the appropriate size Sometimes a breaker bar will need to be used Do not use an impact wrench Inspect and replace the anode as required Use pipe tape or sealant when reinstalling the anode 9 Close the drain valve Open a hot water fixture to allow air to escape Open the cold water supply to water heater and allow the tank to fill Follow the lighting instructions 10 Check your anode and drain valve for leaks 11 Replace second pass collector cover Make sure to clean off any sealant and reseal before fastening 12 Replace second pass insulation 13 Replace second pass access cover 14 Replace combustion surround top and latch it securely in place ADM RWN YE Ee DRAIN VALVE AND TANK ACCESS PANEL The water heaters are equipped with a inch drain valve An access panel covers the cleanout opening in the tank which is sealed by a gasket and cover RELIEF VALVE 39 At least twice a year the temperature and pressure relief valve should be checked to ensure that it is in operating condition To check the relief valve lift the lever at the end of the valve several times The valve should seat properly and operate freely If water does not flow remove and inspect for obstructions or corrosion Replace with a new valve of the recommended s
33. e condition with this water heater for reference by owner and service technician This water heater requires regular maintenance and service to operate safely Follow the instructions contained in this manual Installation maintenance and service must be performed only by an qualified skilled and knowledgeable installer or service provider Installation is not complete unless a temperature and pressure relief valve is installed into the proper location at the top of this water heater It is the responsibility of the installing contractor to see that all controls are correctly installed and are properly operating when the installation is complete This water heater is suitable for installation on combustible flooring Do not install water heater on carpeting DO NOT operate this water heater without first being certain it is filled with water DO NOT tamper with or alter the water heater and or controls DO NOT operate water heater with jumpered or absent controls or safety devices DO NOT operate water heater if any external part has been under water Immediately call a qualified service agency to inspect the appliance and to replace any part of the control system including gas controls which has been under water DO NOT attempt to use this water heater with any gas other than the type listed on the rating plate Do not attempt to convert this water heater for use with a gas other than the type for which it is equipped Failure to use the prop
34. e or other flammable combustible or corrosive vapors and or liquids in the vicinity of this or any other appliance DO NOT install any damaged venting system components If damage is evident then please contact the supplier where the water heater was purchased or the manufacturer listed on the rating plate for replacement parts This water heater is equipped with an adjustable thermostat to control water temperature Hot water temperatures required for automatic dishwasher and laundry use can cause scald burns resulting in serious personal injury and or death The temperature at which injury occurs varies with the person s age and the time of exposure The slower response time of disabled persons increases the hazards to them NEVER allow small children to use a hot water tap or to draw their own bath water NEVER leave a child or disabled person unattended in a bathtub or shower Failure to properly install the vent and air intake if applicable system could result in property damage personal injury or death Z N WARNING Improper installation adjustments alteration service or maintenance can cause property damage personal injury or loss of life Failure to follow all instructions in the proper order can cause personal injury or death Read and understand all instructions including all those provided with the appliance before installing starting up operating maintaining or servicing this appliance Keep this manual and literature in legibl
35. ecommend the hot water faucet to be open for several minutes at the kitchen sink before you use any electrical appliance which is connected to the hot water system If hydrogen is present there will be an unusual sound such as air escaping through the pipes as hot water begins to flow Do not smoke or have open flame near the faucet at the time it is open Keep clear of the combination temperature and pressure relief valve discharge line outlet The discharge may be hot enough to cause scald injury The water is under pressure and may splash Z N CAUTION If sweat fittings are to be used DO NOT apply heat to the nipples in front or side of the water heater Sweat the tubing to the adapter before fitting the adapter to the water connections It is imperative that heat is not applied to the nipples containing a plastic liner INSTRUCTIONS FOR CONNECTIONS 1 BEFORE PROCEEDING WITH THE INSTALLATION CLOSE THE MAIN WATER SUPPLY VALVE After shutting off the main water supply open a faucet to relieve the water line pressure to prevent any water from leaking out of the pipes while making the water connections to the water heater The COLD water inlet and HOT water outlet are identified on the water heater Make the proper plumbing connections between the water heater and the plumbing system to the house Install a shut off valve in the cold water supply line 2 If this water heater is installed in a closed water supply system such as the one havi
36. er gas can create an unsafe condition resulting in property damage bodily injury or death Consult your local gas supplier or gas company if there are any questions This water heater contains very hot water under high pressure Do not unscrew any pipe fittings nor attempt to disconnect any components of this water heater without positively assuring the water is cool and is not under pressure Always wear protective clothing and equipment when installing starting up or servicing this water heater to prevent scald injuries Do not rely on the temperature gauges to determine the temperature Do not touch any components unless they are cool This water heater must be properly vented and connected to an approved vent system in good condition DO NOT operate water heater with the absence of an approved vent system A clean and unobstructed vent system is necessary to allow noxious fumes that could cause injury or loss of life to vent safely and will contribute toward maintaining the water heater s efficiency Z N WARNING This water heater needs fresh air for safe operation and must be installed so there are provisions for adequate combustion and ventilation air Insufficient air supply will cause a recirculation of combustion products resulting in contamination that may be hazardous to life This will result in carboning or sooting of the combustion chamber burners and flue tubes and creates a risk of asphyxiation This water heater requires its
37. ipe assembly through the structure s hole and field supplied roof boot flashing Do not allow insulation or other materials to accumulate inside pipe assembly when installing through the hole Install rain cap and small diameter pipe assembly in concentric Y fitting and large pipe assembly Ensure small diameter pipe is cemented and bottomed in concentric Y fitting Secure assembly to structure as shown in Figure 23 Ensure clearances as shown in Figure 23 STRAP FIELD SUPPLIED ELBOW FIELD RDOF OVERHANG SUPPLIED CONBUSTKIN AIR 12 MININUM CONBUSTION AIR NOTE MAINTAIN 12 IN CLEARANCE STRAP MUST BE FIELD INSTALLED ABOVE HIGHEST ANTICIPATED TO PREVENT MOVEMENT OF VENT SNOW LEVEL GR GRADE TERMINAL IN WALL WHICHEVER IS GREATER Figure 23 Concentric Vent Side Wall Attachment Cement heater combustion air and vent pipes to concentric Y fitting termination assembly See Figure 23 for proper pipe attachment Operate heater through one cycle to ensure combustion air and vent pipes are properly connected to concentric vent termination connections VENT PIPE PREPARATION VAN WA WARNING DO NOT attempt to start this water heater until vent pipe solvent fumes completely clear from the room and inside the vent piping INITIAL PREPARATION 1 Make sure the solvent cement you are planning to use is designed for the specific application you are attempting Know the physical and chemical characteristics and limit
38. ity before connecting the water heater WIRING DIAGRAM AND SCHEMATIC LADDER DWGRAN Figure 25 Wiring Diagram and Schematic 33 SECTION IX OPERATING INSTRUCTIONS Z N WARNING Water heaters are heat producing appliances To avoid damage or injury there must be no materials stored against the water heater or direct vent system and proper care must be taken to avoid unnecessary contact especially by children with the water heater and direct vent system UNDER NO CIRCUMSTANCES SHOULD FLAMMABLE MATERIALS SUCH AS GASOLINE OR PAINT THINNER BE USED OR STORED IN THE VICINITY OF THIS WATER HEATER OR IN ANY LOCATION FROM WHICH FUMES COULD REACH THE WATER HEATER Installation or service of this water heater requires ability equivalent to that of a licensed tradesman in the field involved Plumbing air supply venting gas supply and electrical work are required Light the unit in accordance with the operating instructions label attached to the water heater firing could result in damage or sooting of the water heater If the unit is exposed to the following do not operate water heater until all corrective steps have been made by a factory authorized independent service contractor or qualified service professional Flooding to or above the level of the burner or controls External firing Damage Firing without water 5 Sooting NEVER OPERATE THE WATER HEATER WITHOUT FIRST BEING CERTAIN IT IS FILLED WITH WATER AND A TEMPERATURE AND
39. ize as necessary A thorough inspection of the valve should be performed at least every three years by removing the temperature and relief valve from the tank Do not attempt to repair the valve as this could result in improper operation and a tank explosion In areas with poor water conditions it may be necessary to inspect the T amp P valve more often than the recommended maintenance schedule CAUTION Before manually operating the valve make sure that a drain line has been attached to the valve to direct the discharge to an open drain Failure to take this precaution could mean contact with extremely hot water passing out the valve during this checking operation If the temperature and pressure relief valve on the water heater discharges periodically or continuously it may be due to thermal expansion of water in a closed water supply system or it may be due to a faulty relief valve Thermal expansion is the normal response of water when it is heated In a closed system thermal expansion will cause the system pressure to build until the relief valve actuation pressure is equaled Then the relief valve will open allowing some water to escape slightly lowering the pressure Contact your water supplier or local plumbing inspector on how to control this situation Z wWApNING Above all do not plug the temperature and pressure relief valve This is not a solution and can create a hazardous situation VENT AND AIR INTAKE SYSTE
40. lace or if the pipe cannot move freely through a wall penetration the pipe may be directly stressed or high thermal stresses may be formed when the pipe heats up and expands Install accordingly to minimize such stresses Follow the following procedure to vent through the wall 1 Cutone 3 1 2 in 8 9 cm diameter hole for 3 7 6 cm diameter pipe or 4 2 11 5 cm diameter hole for 4 10 2 cm diameter pipe 2 Use the proper PVC cement or sealant to secure the 90 exhaust vent terminal provided with the water heater to the plastic pipes The distance between the back edge of the 90 exhaust vent terminal and the exterior wall see Figure 16 must be 6 inches 13 0 cm Use the proper cement and assembly procedures to secure the vent connector joints between the terminal and the blower outlet Provide support brackets for every 3 feet 1 0 m of horizontal vent 90 INTAKE TERMINAL SUPPORT BRACKET 90 EXHAUST Figure 16 Typical Horizontal Power Vent System Vertical Installation Vertical venting must be supported every 5 feet of vertical run and every 3 feet of horizontal run of vent pipe length Stress levels in the pipe and fittings can be significantly increased by improper installation If rigid pipe clamps are used to hold the pipe in place or if the pipe cannot move freely through a wall penetration the pipe may be directly stressed or high thermal stresses may be formed when the pipe heats up and exp
41. m with this water heater and combustion air is drawn from inside the room sufficient openings for air must be provided in the walls UNDERSIZED OPENINGS WILL CAUSE AIR TO BE DRAWN INTO THE ROOM THROUGH THE WATER HEATER S VENTING SYSTEM CAUSING POOR COMBUSTION THAT MAY BE HAZARDOUS TO LIFE SOOTING MAY RESULT IN SERIOUS DAMAGE TO THE WATER HEATER AND RISK OF FIRE OR EXPLOSION WHICH CAN ALSO CREATE A RISK OF ASPHYXIATION Refer to local codes and or National Fuel Gas Code for proper air opening sizing UNCONFINED SPACE 1 In buildings of conventional frame brick or stone construction unconfined spaces may provide adequate air for combustion and ventilation 2 If the unconfined space is within a building of tight construction buildings using the following construction weather stripping heavy insulation caulking vapor barrier etc air for combustion and ventilation must be obtained from outdoors This may be accomplished by piping air directly to the water heater from outside or providing opening or ducts in the wall The installation instructions for confined spaces in tightly constructed buildings must be followed to ensure adequate air supply CONFINED SPACE 1 When drawing combustion air from inside a conventionally constructed building to a confined space such a space shall be provided with two permanent openings e The top opening is to be located within twelve 12 inches of the enclosure top and the bottom opening within twelve
42. n and install as described in the following sections DIRECT VENT INSTALLATION Venting may be run horizontally through an outside wall or vertically through a roof through using either 3 inch 7 6 cm or 4 inch 10 2 cm diameter PVC ABS or CPVC pipe This water heater is supplied with a screened intake and exhaust 90 elbow referred to as the exhaust vent terminal and the air intake terminal Direct Vent Terminal Location Plan the vent system layout so that proper clearances are maintained from plumbing and wiring Before the vent is installed determine the vent pipe termination location as shown below in Figure 12 ROOF AIR INTAKE ROOF EXHAUST TERMINAL INTAKE AIR TERMINAL EXHAUST VENT TERMINAL GAS METE U 30 5 cm 12 IN MIN EXHAUST VENT FORCED AIR INLET TERMINAL Figure 12 Vent Terminal Location 19 Vent terminals must terminate at least 3 feet 0 9 m above any forced air inlet located within 10 feet 3 1 m This provision does not apply to 1 The combustion air intake of a direct vent appliance or the circulating air inlet and flue gas discharge of listed outdoor appliances 2 The exhaust vent terminal must be installed with at least 12 inches 30 cm clearance from any air opening into a building 3 The bottom of the exhaust vent and combustion air intake terminals must be located at least 12 inches 30 cm above grade and above the anticipated snow level 4 Must be installed at least 3 feet 0 9 m from an
43. nd with National Fuel Gas Code and local codes NOTICE This unit can be vented using only PVC Class 160 ASTM D2241 Schedule 40 ASTM D 1785 or Cellular Core Schedule 40 DWV ASTM F891 Schedule 40 CPVC ASTM F411 or ABS ASTM D 2661 pipe The fittings other than the TERMINATIONS should be equivalent to PVC DWV fittings meeting ASTM E2665 Use CPVC fittings ASTM F438 for CPVC pipe and ABS fittings ASTM D 266 3311 for ABS pipe If CPVC or ABS pipe and fittings are used then the proper cement must be used for all joints including joining the pipe to the Termination PVC material PVC materials should use ASTM D2564 grade cement CPVC materials should use ASTM F 493 grade cement and ABS materials should use ASTM D 2235 grade cement For water heaters in locations with high ambient temperatures above 100 F and or insufficient dilution air it is recommended that CPVC or ABS pipe and fittings MUST USE SUPPLIED VENT TERMINAL be used 24 Horizontal Installation In a horizontal application it is important that condensate not be allowed to buildup in the exhaust vent pipe To prevent this from happening the pipe should be installed with an slight upward slope The vent system should be supported every 5 feet of vertical run and every 3 feet of horizontal run of vent pipe length Stress levels in the pipe and fittings can be significantly increased by improper installation If rigid pipe clamps are used to hold the pipe in p
44. ng a back flow preventer in the cold water supply provisions must be made to control thermal expansion DO NOT operate this water heater in a closed system without provisions for controlling thermal expansion Warranties do not cover damages from thermal expansion such as pressure bulges and or deformities Your water supplier or local plumbing inspector should be contacted on how to control this situation 3 After installation of the water lines open the main water supply valve and fill the water heater While the water heater is filling open several hot water faucets to allow air to escape from the water system When a steady stream of water flows through the faucets close them and check all water connections for possible leaks 4 Never operate the water heater without first being certain it is filled with water 15 SCALDING This water heater can deliver scalding temperature water at any faucet in the system Be careful whenever using hot water to avoid scalding injury Certain appliances such as dishwashers and automatic clothes washers may require increased temperature water By setting the thermostat on this water heater to obtain the increased temperature water required by these appliances you may create the potential for scald injury To protect against injury you should install an ASSE approved mixing valve in the water system This valve will reduce point of discharge temperature by mixing cold and hot water in branch supply lines
45. oper cement Schedule 40 cement should be used for Schedule 40 pipe Never use all purpose cements commercial glues and adhesives or ABS cement to join PVC or CPVC pipe and fittings SAFETY PRECAUTION PRIMERS AND CEMENTS ARE EXTREMELY FLAMMABLE AND MUST NOT BE STORED OR USED NEAR HEAT OR OPEN FLAME ALSO USE ONLY IN A WELL VENTILATED AREA SECTION VII GAS CONNECTIONS WARNING Connect this water heater only to the type of gas as shown on the rating plate Use clean black iron pipe or equivalent material approved by local codes and ordinances Dirt and scale from the pipe can enter the gas valve and cause it to malfunction The inlet gas line must have at least a 3 inch 7 62 cm drip leg sediment trap installed as close to the water heater s gas valve as possible A ground joint union must be installed in the gas supply line as close to the water heater as possible to permit servicing of the water heater Compounds used on the threaded joints of the gas piping must be resistant to the action of liquefied petroleum gases propane gas DO NOT apply pipe dope to the gas valve inlet and make certain that no pipe dope has become lodged in the inlet screen of the gas valve Extreme care must be taken to ensure no pipe dope enters the gas valve and to avoid excessive torque when tightening the gas supply line to the gas valve Excessive torque may result in cracking of the gas valve housing The suggested maximum torque is 31 5 foot Ibs 4 4
46. own separate venting system DO NOT connect the exhaust vent into an existing vent pipe or chimney Water heater materials of construction products of combustion and the fuel contain carbon monoxide nitrogen oxides aldehydes and or other toxic or harmful substances which can cause death or serious injury and which are known to the state of California to cause cancer birth defects and other reproductive harm Always use proper safety clothing respirators and equipment when servicing or working nearby this water heater Flammable items pressurized containers or any other potential fire hazardous articles must never be placed on or adjacent to the water heater Open containers of flammable material should not be stored or used in the same room with this water heater Insulation blankets are not required for this water heater This water heater meets or exceeds the ASHRAE IES 90 1b latest edition standards with respect to insulation and standby loss requirements Hydrogen gas can be produced in an operating water heater that has not had water drawn from the tank for a long period of time generally two weeks or more Hydrogen gas is extremely flammable To prevent the possibility of injury under these conditions we recommend the hot water faucet to be open for several minutes at the kitchen sink before you use any electrical appliance which is connect to the hot water system If hydrogen is present there will be an unusual sounds such as air esca
47. ping through the pipes as hot water begins to flow Do not smoke or have open flame near the faucet at the time it is open WARNING Liquefied petroleum gases propane gas is heavier than air and will remain at floor level if there is a leak Basements crawl spaces closets and areas below ground level will serve as pockets for accumulation of leaking gas Before lighting smell all around the appliance area for gas Be sure to smell next to the floor IF YOU SMELL GAS DO NOT try to light any appliance DO NOT touch any electric switch do not use any telephone in your building Immediately call your gas supplier from a telephone in another building Follow the gas supplier s instructions If you cannot reach vour gas supplier call the fire department DO NOT OPERATE THE APPLIANCE UNTIL THE LEAKAGE IS CORRECTED SECTION II SPECIFICATIONS 3 PVG CONBUSTION AIR INLET THERNOSTAT KNOB S 3 4 NPT ON OFF SWITCH CAS CONNECTION T amp P REUEF VALVE 1 Des NPT HOT TER OUTLET 1 1 2 NPT COLD WATER INLET 3 4 ORAN DIMENSIONS INCHES Gas Relief Shpg Conn Conn Valve Wt Dia Open LBS 34 34 34 34 34 34 34 Recovery GPH At Degree Rise 40 F 100 F 140 F Gal Dia Intake Table 1 Specifications SECTION II GENERAL INFORMATION FEATURES This water heater contains the following features MAIN POWER ON OFF SWITCH The front panel of this wate
48. piping must be piped near floor to eliminate potential of severe burns Do not pipe in any area where freezing could occur Do not install any shut off valves plugs or caps to the temperature and pressure relief valve or piping d A CAUTION If building cold water supply has a back flow preventer check valve or water meter with check valve provisions for thermal expansion of water in the hot water system must be provided Temperature setting should not exceed safe temperature at fixtures See water temperature control warning on page 16 If higher preheat temperatures are necessary to obtain adequate booster output add an anti scald valve for hot water supplied to fixtures LOCATION KEEP APPLIANCE AREA CLEAR AND FREE OF COMBUSTIBLE MATERIALS GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQUIDS This water heater must be located in an area where the general public does not have access to set temperatures AIR REQUIREMENTS 1 Do not obstruct the flow of combustion and ventilating air 2 For safe operation adequate air is needed for combustion and ventilation Sooting may result in serious damage to the water heater and risk of fire or explosion It can also create a risk of asphyxiation Such a condition often will result in a yellow luminous burner flame causing carboning or sooting of the combustion chamber burner and flue tubes 11 MECHANICAL EXHAUSTING OF ROOM AIR 1 Where an exhaust fan is installed in the same roo
49. r heater has a lighted ON OFF switch which is illuminated when the main power is turned on to indicate power to the water heater COMBUSTION SYSTEM This water heater is equipped with a self compensating negative pressure pre mix combustion system As the blower operates air is drawn in through the air intake and into a venturi which pulls gas from the gas valve The gas and air is then mixed in the combustion blower and sent through the transition tube into the burner The Hot Surface Ignition System HSI then ignites the gas air fuel mixture to produce flue products combustion The flame sensor signals the ignition module described below that a flame is present IGNITION MODULE The ignition module provides the timing for the combustion system A sequence of operation S OP is described in Section IX Operating Instruction As the combustion system progresses through the S OP LED s illuminate allowing accurate trouble shooting should the need arise If a failure occurs the system will blink the LED that corresponds to the failure as described in the Section XI Troubleshooting Guide ADJUSTABLE THERMOSTAT This water heater is equipped with an adjustable thermostat to control water temperature Hot water temperatures required for automatic dishwasher and laundry use can cause scald burns resulting in serious personal injury and or death The temperature may be adjusted from about 80 F to about 180 F The thermo
50. rature or water usage the more lime deposits are dropped out of the water This is the lime scale which forms in pipes water heaters and on cooking utensils Lime accumulation not only reduces the life of the equipment but also reduces efficiency of the water heater and increases fuel consumption The usage of water softening equipment greatly reduces the hardness of the water However this equipment does not always remove all of the hardness lime For this reason it is recommended that a regular schedule of deliming be maintained The depth of the buildup should be measured periodically Water heaters will have about 3 inches of lime buildup when the level of lime has reached the bottom of the cleanout opening or about 1 inch of lime buildup if it has reached the drain valve opening A schedule for deliming should be set up based on the amount of time it would take for a 1 2 inch buildup of lime Example 1 Initial inspection shows L an inch of lime accumulation Therefore the water heater can be delimed once a year 38 To remove sediment and lime scale 1 Drain the heater Refer to DRAINING THE WATER instructions in this section 2 Remove outer cover plate from lower side of water heater jacket 3 Remove cover and gasket from cleanout opening 4 Remove lime scale or sediment using care not to damage the glass lining 5 Inspect cleanout plate gasket Replace gasket if necessary Contact Bradford White Local Distributor for
51. refrigerator and air conditioning refrigerants swimming pool chemicals calcium and sodium chloride waxes and process chemicals are corrosive Products of this sort should not be stored near the water heater or outside by the air intake if applicable 12 TYPICAL INSTALLATION ILLUSTRATION If building cold water supply has a back flow preventer check valve or water meter with check valve provisions for thermal expansion of water in the hot water system must be provided T amp P RELIEF VALVE SUPPORT BRACKET HOT WATER OUTLET EXHAUST VENT EXHAUST VENT POTABLE WATER CIRCULATOR Figure 5 Typical Front Inlet Connect with Storage Heater 13 HOT WATER OUTLET VACUUM BREAKER COLD WATER SUPPLY Figure 6 Typical Two Water Heater Connection H 5 St VACUUM BREAKER COLD WATER SUPPLY Figure 7 Typical Three Water Heater Connection gt a S g 8 Figure 8 Typical Four Water Heater Connection 14 SECTION V WATER CONNECTIONS Z N WARNING Failure to install and maintain a new listed temperature and pressure relief valve will release the manufacturer from any claim which might result from excessive temperature and pressures Hydrogen gas can be produced in an operating water heater that has not had water drawn from the tank for a long period of time generally two weeks or more HYDROGEN GAS IS EXTREMELY FLAMMABLE To prevent the possibility of injury under these conditions we r
52. rness If connections are ok then replace the switch If there is voltage between L1 and N then the light on the switch is burnt out Replace switch Thermostat does not call for heat Make sure that the temperature of the tank is cool If the thermostat does not call for heat then check the PRIMARY voltage across the Transformer If there is voltage across the PRIMARY then check the voltage across the SECONDARY leads of the Transformer Install a jumper wire from N O terminal to the COM terminal on the Thermostat PC Board If the thermostat calls for heat after installing a jumper wire then check the Thermostat Sensor Probe leads for proper resistance with an OHM meter See appendix A If sensor reading are not correct replace Thermostat Sensor Probe If the sensor readings are correct then check Potentiometer for the proper resistance If the readings are correct then replace the Thermostat PC Board otherwise replace the Potentiometer Ignition module Power LED is not lit Check for 120 VAC at the ignition module on 120 VAC IN If there is voltage then replace the ignition module If there is not any voltage check the voltage across the transformer as previously described Blower does not energize Is the Vacuum Switch air intake switch N C If no then check the hose and see if it is filled with condensate If the hose is not filled with condensate then
53. rvicing Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation Verify proper operation after servicing All electrical wiring must be installed and grounded in accordance with local codes or in the absence of local codes the National Electrical Code ANSI NFPA 70 and or CSA C22 2 Electrical Code The water heater must be wired to a 120 VAC 60 Hz 15A power supply The water heater should be connected to a GFI outlet and wired on a separate circuit and breaker If a flexible line cord and plug is permitted by local code then provide a three wire GFI grounding type receptacle within reach of the line cord provided on the control box Do not plug the line cord into a receptacle that can have the power supply interrupted by a switch that is used to control lights or another appliance If wiring in conduit is required remove the line cord and strain relief bushing in the control panel and install an electrical conduit connector Connect the hot neutral and ground leads to the terminal block using quick connect terminals Refer to the wiring diagram for the correct terminal locations for each wire lead CAUTION Do not energize the electric circuit before the water heater tank is filled with water This controller is Polarity sensitive If the Hot and Neutral Supply voltage is reversed the controller will not sense flame and the water heater will not operate Verify polar
54. sert Gasket 44 CC Ignition Control Ass y Transformer 120VAC Power Cord Flame Sensor Wire Harness 45 NOTES 46
55. stalled in accordance with local codes In the absence of local codes it must be installed in compliance with the National Fuel Gas Code ANSI Z223 1 Latest Edition or in Canada CAN CGA B149 1 Natural Gas Installation Code Latest Edition or CAN CGA B149 2 Propane Installation Code Latest Edition The following terms are used throughout this manual to bring attention to the presence of hazards at various risk levels or to important information concerning product life Z N DANGER Z N CAUTION dicates an imminently hazardous situation which if not situation which if not avoided avoided will result in death may result in moderate or minor serious injury or substantial injury or property damage property damage A NOTICE Z WApMING ndicates a potentially hazard ndicates special instructions on situation which if not avoided installation operation or could result in death serious maintenance which are injury or substantial property important but not related to damage personal injury hazards NOTICE This water heater has a limited warranty The warranty for this water heater is valid only if the water heater has been installed maintained and operated in accordance with these instructions TABLE OF CONTENTS IMPORTANT INFORMATION GAS CONNECTIONS SPECIFICATIONS ia ELECTRICAL CONNECTIONS GENERAL INFORMATION OPERATING INSTRUCTIONS MAINTENANCE TROUBLE SHOOTING GUIDE PARTS LIST Z N DANGER DO NOT store or use gasolin
56. stat was adjusted to 120 F before the water heater was shipped from the factory It is recommended that lower temperatures be used to avoid the risk of scalding Refer to the Warnings and the section on SCALDING in Section V Water Connections It is further recommended in all cases that the water temperature be set for the lowest temperature which satisfies your hot water needs This will also provide the most energy efficient operation of the water heater and minimizes scale formation Setting the water heater temperature at 120 F will reduce the risk of scalds Some states require setting the specific lower temperatures The top immersion well of the single bulb controller also contains the high limit energy cutoff sensor The high limit switch interrupts the main burner gas flow should the water temperature reach approximately 200 F Should the high limit switch activate it must be manually reset This can be accomplished by turning the main power on off switch to the off position and then back to the on position and allowing the water temperature of the tank to drop below 160 F Contact your qualified installing contractor service provider or manufacturer listed on the rating plate if continued high limit switch operation occurs SERVICE PANEL The service panel is located behind the service panel access cover which is located by the exhaust collector near the bottom of the water heater This panel contains a differen
57. t least 4 microAmps If not then replace the Flame Sensor or flame sensor wire Thermostat does not satisfy Is the tank temperature above the temperature set point Does the T amp P relief valve leak If yes then replace Thermostat PC Board Blower did not post purge Check Vacuum Switch air intake switch as previously mentioned Check Pressure Switch exhaust pressure switch as previously mentioned Check Collector Limit Switch as previously mentioned If above switches are all ok then replace Ignition Module 42 SECTION XI PARTS LIST EF Series Water Heater 5 Vent Termination Elbow 3 4 5 7 10 11 Plastisert Nipple 1 2 NPT 12 14 15 12 Plug 13 Nipple L 14 T amp P Relief Valve 15 Exhaust Pipe PVC w Barb Tap 17 Silicone hose 20 NSF Escutcheon a a ul 23 EXHAUST SERVICE AREA DETAIL ASSEMBLED 43 1 Combustion Surround Ass y w DD Jacket Head 28 1 4 Grey 2 Combustion Ass y lower Gas Valve Ass y 1A Q gt D urner Ass y lower EB DIE ilicone Hose ee Hose Connector gla let PVC asket Blower Transition 2 dia Flex Reducer G Gasket Flame Sensor rew 8 32 x 1 4 RHCR Sc G G N N In Sc N 7A 8A 9A 10A 11A 12A 13A 14A 15A 16A 17A 18A 19A 20A 21A 22 23 24A 25A 26A S olules wlnb e gt gt gt P gt S gt M Burner Mounting In
58. tial pressure switch that monitors the pressure across the exhaust orifice A collector high limit switch is used to monitor the ambient temperature between the first pass collector and the exhaust collector This is a manually re settable switch If this switch continues to trip please contact an authorized service agency LATCHES The latches allow easy access for servicing the water heater from the top Simply remove the two latches for servicing and re latch upon completion No tools are required to obtain access to the top of the water heater TEMPERATURE AND PRESSURE RELIEF VALVE Z WARNING Keep clear of the combination temperature and pressure relief valve discharge line outlet The discharge may be hot enough to cause scald injury The water is under pressure and may splash For protection against excessive temperatures and pressure install temperature and pressure protective equipment required by local codes but not less than a combination temperature and pressure relief valve certified by a nationally recognized testing laboratory that maintains periodic inspection of production of listed equipment or materials as meeting the requirements of the Standard for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems ANSI Z21 22 and the Standard CAN1 4 4 Temperature Pressure Temperature and Pressure Relief Valves and Vacuum Relief Valves The combination temperature and pressure relief valve must be marked with a
59. valve between the combination temperature and pressure relief valve and the tank CONDENSATE DRAIN This water heater is a condensing type unit and requires a drain to be located in close proximity to allow the condensate to drain safely The condensate drains from the unit at the exhaust elbow located near the bottom of the unit It is important that the condensate hose not be elevated above the exhaust elbow The condensate build up will block the exhaust outlet which will cause improper operation Refer to Figure 2 for an example of a service loop WATER HEATER SERVICE LOOP Figure 2 Condensate Elbow With Loop CLEANOUT All models are equipped with a cleanout opening to aid in removal of hard water deposits from the tank bottom If this water heater operates under hard water conditions the following should be performed at least every 3 months Turn off water supply and drain the water heater Remove the cleanout jacket cover and tank cover When cleaning the tank care must be taken to avoid trying to break deposits loose as this could damage the glass lining and shorten the life of the water heater After cleaning re install the cleanout tank cover and jacket cover and refill with water Refer to the section Section X Maintenance in this Installation and Operating Instruction manual for the procedures for filling and draining the water heater SACRIFICIAL ANODES Four sacrificial anode rods have been installed in
60. valve in the water system This valve will reduce point of discharge temperature by mixing cold and hot water in branch water lines A licensed plumbing professional or local plumbing authority should be consulted This water heater is equipped with an energy cut out device to prevent overheating Should overheating occur or the gas supply fail to shut off turn off the manual gas control valve to the appliance and call a qualified service agency If the water heater is to remain idle for 30 days or more or is subjected to freezing temperatures while shut off the water heater and piping should be fully drained and the drain valve should be left fully open Refer to the General Operation section of this Installation and Operating Instructions Manual for the procedure on draining the water heater BURNER FLAME CHECK At the time of installation and at monthly intervals a visual check of the burner flames should be made to determine if they are burning properly The main burner may be seen through the sight glass window on the front of the combustion insert mounting bracket Figure 27 The burner flames should be a blue flame near the burner surface in a uniform flame pattern Occasional yellow or white streaks are normal SIGHT GLASS Figure 27 Sight Glass Location 36 SECTION X MAINTENANCE DANGER DO NOT ATTEMPT TO REPAIR GAS VALVE DO NOT ATTEMPT TO REPAIR IGNITION MODULE DO NOT ATTEMPT TO REPAIR VENTURI DO
61. y gas meter gas valve or other gas regulating equipment 5 Must be installed in a location where it will not be blocked by snow 6 The exhaust vent and combustion air intake terminals must be installed so that the centerline distances are at least 18 inches 45 7cm apart and the exhaust vent terminal elbow extends 6 inches 15 2 cm past the combustion air intake terminal EXCEPTIONS FOR INSTALLATIONS The vent terminal must not terminate 1 Directly above a paved sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings 2 Less than 7 feet 2 1 m above a paved sidewalk or a paved driveway located on public property 3 Within 6 feet 1 8 m of a mechanical air supply inlet to any building 4 Above a gas meter regulator assembly within 3 feet 0 9 m horizontally of the vertical centerline of the regulator Within 6 feet 1 8m of any gas service regulator vent outlet Less than 1 foot 30 5 cm above grade level 7 Within 12 inches 30 5 cm of a window or door which can be opened in any building any non mechanical air supply inlet to any building or the combustion air inlet of any other appliance 8 Underneath a veranda porch or deck unless e The veranda porch or deck is fully open on a minimum of two sides beneath the floor and e The distance between the top of the vent termination and the underside of the veranda porch or deck is greater than 1 foot 30 5 cm nm The vent system