Home

Cisco PWR-950-AC

image

Contents

1. The 8700 W AC input power supply is limited to 6000 W maximum output when it is installed in the Catalyst 6513 switch chassis Catalyst 6500 Series Switches Installation Guide OL 5781 07 Appendix A Power Supply Specifications 950 W AC Input and DC Input Power Supplies W 950 W AC Input and DC Input Power Supplies The 950 W AC input PWR 950 AC and DC input PWR 950 DC power supplies can be installed in the Catalyst 6503 and Catalyst 6503 E switch chassis only Due to form factor differences the 950 W AC input and DC input power supplies cannot be installed in any other Catalyst 6500 series switch chassis The 950 W power supplies see Figure A 1 do not connect directly to source AC or source DC but use Power Entry Modules PEMs located on the front of the Catalyst 6503 and Catalyst 6503 E switch chassis to connect the site power source to the power supply located in the back of the chassis The form factor is the same for the AC input and DC input power supplies The AC input PEM shown in Figure A 2 and DC input PEM shown in Figure A 3 provide an input power connection on the front of the switch chassis to connect the site power source to the power supply You can connect the DC input power supply to the power source with heavy gauge wiring connected to a terminal block The actual wire gauge size is determined by local electrical codes and restrictions amp Note The system NEBS ground serves as the
2. e 16 A 200 VAC 3000 W output e 16A 100 VAC 1400 W output AC input frequency 50 60 Hz nominal 3 for full range Branch circuit requirement Each chassis power supply should have its own dedicated fused branch circuit e For North America 20 A e For International Circuits sized to local and national codes e All AC power supply inputs are fully isolated Source AC can be out of phase between multiple power supplies in the same chassis which means that PS1 can be operating from phase A and PS2 can be operating from phase B For high line operation the power supply operates with the hot conductor wired to a source AC phase and the neutral conductor wired either to ground or to another source AC phase as long as the net input voltage is in the range of 170 to 264 VAC Source AC can be out of phase between AC inputs on power supplies that are equipped with multiple AC inputs which means that power cord 1 can be plugged into phase A and power cord 2 can be plugged into phase B Power supply output capacity e 1400 W maximum 100 120 VAC e 3000 W maximum 200 240 VAC OL 5781 07 Catalyst 6500 Series Switches Installation Guide Appendix A Power Supply Specifications HI 3000W AC Input Power Supply Table A 25 3000 W Power Supply Specifications continued Specification Description Power supply output e 100 120 VAC operation 250A 3 3 V 5A 5V 12A
3. IEC 60320 C20 Switzerland CAB ACS 16 SEV 5934 2 Type 23 16 A 250 VAC Figure A 45 1 The 2500 W power supply operating on 110 VAC delivers 1300 W 2 The PDU power cable is designed for users who power their switch from a PDU The end of the cable that plugs into the Catalyst 6500 series switch chassis has a C19 connector the other end of the cable that plugs into the PDU has a C20 connector Catalyst 6500 Series Switches Installation Guide OL 5781 07 AppendixA Power Supply Specifications 2700 W AC Input and DC Input Power Supplies W 2700 W AC Input and DC Input Power Supplies The 2700 W AC input power supply PWR 2700 AC 4 and 2700 W DC input power supply PWR 2700 DC 4 are supported only in the Catalyst 6504 E switch See Figure A 11 for the 2700 W AC input power supply and Figure A 12 for the 2700 W DC input power supply Note The 2700 W AC input power supply needs 220 VAC to deliver 2700 W of power When powered with 110 VAC it delivers only 1350 W In addition the power supply needs 16 A regardless of whether it is plugged into 110 VAC or 220 VAC Figure A 11 2700 W AC Input Power Supply 1 Power on off switch I O 4 Status LEDs 2 Power supply fan 5 AC In receptacle 3 Captive installation screw 4x Catalyst 6500 Series Switches Installation Guide OL 5781 07 EEE Appendix A Power Supply Specifications W 2700W AC Input and DC Input Power Suppli
4. 3 3 VDC 5A 5 VDC 10A 12 VDC 55 5 A 42 VDC Output holdup time 20 ms minimum kVA rating 3520 W total input power or 3 6 KVA high line operation Heat dissipation 10 939 BTU hour approx Weight 17 0 1b 7 7 kg 1 The kVA rating listed for the power supply should be used as the sizing criteria for both UPS outputs as well as standard circuits and transformers to power a switch Table A 18 lists the specifications for the 2500 W DC input power supply Catalyst 6500 Series Switches Installation Guide OL 5781 07 g A25 Appendix A Power Supply Specifications WE 2500W AC Input and DC Input Power Supplies Table A 18 2500 W DC Input Power Supply Specifications Specification Description DC input voltage 48 VDC to 60 VDC continuous DC input current e 80A 40 5 VDC e 70A 48 VDC e 55 A 60 VDC Power supply output 2500 W maximum 48 to 60 VDC capacity Power supply output e 15A 43 3 VDC e SA 5 VDC e 10A 12 VDC e 55 5 A 42 VDC DC input terminal block Accepts 2 14 AWG copper conductors Actual size of the wire needed is determined by the installer or local electrician Terminal block material rated at 150 C Output holdup time e 20 ms minimum AC input power supply e 4 ms DC input power supply Heat dissipation e 10 939 BTU hour approx AC input power supply e 11 377 BTU hour approx DC input power supply Weight 20 2 Ib 9
5. are supported in the following Catalyst 6500 series switches e Catalyst 6506 e Catalyst 6509 e Catalyst 6509 NEB The 1300 W power supply see Figure A 5 for the 1300 W AC input power supply and Figure A 6 for the 1300 W DC input power supply shares the same form factor as the 1000 W 2500 W 3000 W 4000 W and 6000 W AC input power supplies OL 5781 07 Catalyst 6500 Series Switches Installation Guide Appendix A Power Supply Specifications W 1300W AC Input and DC Input Power Supplies Figure A 5 1300 W AC input Power Supply Figure A 6 1300 W DC Input Power Supply Catalyst 6500 Series Switches Installation Guide mer Appendix A Power Supply Specifications 1300 W AC Input and DC Input Power Supplies Hi 1300 W Power Supply Specifications Table A 11 lists the specifications for the 1300 W AC input power supply Table A 10 1300 W AC Input Power Supply Specifications Specification AC input type Description Autoranging input with power factor correction PFC Note Power factor correction is a standard feature on all Catalyst 6500 series AC input power supplies PFC reduces the reactive component in the source AC current allowing higher power factors typically 99 percent or better and lower harmonic current components AC input voltage e Low line 120 VAC nominal 85 VAC min to 132 VAC max e High line 230 VAC nominal 170 VAC min to 264 VAC max AC input curren
6. supplies must have a minimum configuration of one fan tray one supervisor engine and one additional module Failure to meet these minimum configuration requirements can cause a false power supply output fail signal OL 5781 07 Catalyst 6500 Series Switches Installation Guide Appendix A Power Supply Specifications W 8700W AC Input Power Supply Remote Power Cycling Feature Terminal Block The 8700 W power supply is equipped with a remote power cycling feature that allows you to remotely turn on or turn off the power supply through an external relay controller box Figure A 19 shows a typical remote power on off setup A three position terminal block and a switch located on the lower right quadrant of the power supply faceplate see Figure A 18 provide the interface to the external relay controller box Figure A 19 Remote Power On Off Feature Components The terminal block has three contacts labeled 1 2 and 3 Two control wires from an external relay controller box attach to either positions 1 and 2 or positions 2 and 3 Positions 1 and 2 are used when the relay controller box contains a normally open NO type of relay Positions 2 and 3 are used when the relay controller box contains a normally closed NC type of relay Relay Controller Box Switch Ferrite Bead The relay controller box switch located next to the terminal block allows you to match the power supply power control signal s active state with t
7. 2 kg Table A 19 lists the power supply LEDs and their meanings Catalyst 6500 Series Switches Installation Guide OL 5781 07 Appendix A Power Supply Specifications 2500 W AC Input and DC Input Power Supplies W Table A 19 2500 W AC Input and DC Input Power Supply LEDs LED Meaning INPUT OK AC input power supplies e Green Source AC voltage is OK Input voltage is 85 VAC or greater e Off Source AC voltage falls below 70 VAC is not present or the power supply is turned off DC input power supplies e Green Source DC voltage is OK Input voltage is 40 5 VDC or greater e Off Source DC voltage falls below 33 VDC is not present or the power supply is turned off FAN OK e Green Power supply fan is operating properly e Off Power supply fan failure is detected OUTPUT FAIL e Red Problem with one or more of the DC output voltages of the power supply e Off DC output voltages within acceptable margins Note For proper operation of the OUTPUT FAIL LED systems with single power supplies must be configured with a minimum of one fan tray and one supervisor engine Systems with dual power supplies must have a minimum configuration of one fan tray one supervisor engine and one additional module Failure to meet these minimum configuration requirements can cause a false power supply output fail signal OL 5781 07 Catalyst 6500 Series Switches Installation Guide Appendix
8. A 36 6000 W Power Supply AC Power Cords Locale Power Cord AC Source Plug Type Cordset Rating Power Cord Part Number Reference Illustration Argentina CAB 7513ACR or IRAM 2073 16 A 250 VAC Figure A 31 CAB IR2073 C19 AR Australia New Zealand CAB AC 16A AUS AU20S3 16 A 250 VAC Figure A 46 People s Republic of China CAB AC16A CH GB16C 16 A 250 VAC Figure A 37 Continental Europe CAB AC 2500W EU CEE 7 7 16 A 250 VAC Figure A 41 International CAB AC 2500W INT IEC 309 16 A 250 VAC Figure A 42 Israel CAB AC 2500W ISRL S116S3 16 A 250 VAC Figure A 34 Italy CAB 7513ACI CEI 23 16 7 16 A 250 VAC Figure A 35 Catalyst 6500 Series Switches Installation Guide OL 5781 07 mw ASS Appendix A Power Supply Specifications W 8700W AC Input Power Supply Table A 36 6000 W Power Supply AC Power Cords continued Locale Power Cord AC Source Plug Type Cordset Rating Power Cord Part Number Reference Illustration Japan North America CAB AC 2500W US NEMA 6 20 16 A 250 VAC Figure A 43 nonlocking plug 200 240 VAC operation Japan North America CAB AC C6K TWLK NEMA L6 20 16 A 250 VAC Figure A 44 locking plug 200 240 VAC operation Japan North America CAB 7513AC NEMA 5 20 16 A 125 VAC Figure A 36 100 120 VAC operation Power Distribution Unit CAB C19 CBN IEC 60320 C19 16 A 250 VAC Figure A 47 3 PDU IEC 60320 C20 Switzerland CAB ACS 16 SEV 5934 2 Type 23 16 A 250 VAC Figure A 45 1 T
9. A Power Supply Specifications WE 2500W AC Input and DC Input Power Supplies 2500 W Power Supply AC Power Cords Table A 20 lists the specifications for the AC power cords that are available for the 2500 W AC input power supply The table includes references to power cord illustrations amp Note All 2500 W power supply power cords are 14 feet 4 3 meters in length a Note All 2500 W power supply power cords have an IEC60320 C19 appliance connector at one end Table A 20 2500 W Power Supply AC Power Cords Locale Power Cord AC Source Plug Type Cordset Rating Power Cord Part Number Reference Illustration Argentina CAB 7513ACR or IRAM 2073 16 A 250 VAC Figure A 31 CAB IR2073 C19 AR Australia New Zealand CAB AC 16A AUS AU20S3 16 A 250 VAC Figure A 46 People s Republic of China CAB AC16A CH GB16C 16 A 250 VAC Figure A 37 Continental Europe CAB AC 2500W EU CEE 7 7 16 A 250 VAC Figure A 41 International CAB AC 2500W INT IEC 309 16 A 250 VAC Figure A 42 Israel CAB AC 2500W ISRL SI16S3 16 A 250 VAC Figure A 34 Japan North America CAB AC 2500W US l NEMA 6 20 16 A 250 VAC Figure A 43 200 240 VAC operation nonlocking plug Japan North America CAB AC C6K TWLK NEMA L6 20 16 A 250 VAC Figure A 44 200 240 VAC operation locking plug Japan North America CAB 7513AC NEMA 5 20 20 A 125 VAC Figure A 36 100 120 VAC operation Power Distribution Unit CAB C19 CBN IEC 60320 C19 16 A 250 VAC Figure A 47 PDU
10. DC input e 6000 W AC input and DC input e 8700 W AC input No restrictions Catalyst 6509 NEB e 1000 W AC input e 1300 W AC input and DC input e 2500 W AC input and DC input e 3000 W AC input e 4000 W AC input and DC input e 6000 W AC input and DC input e 8700 W AC input The 6000 W AC input 6000 W DC input and the 8700 W AC input power supplies are limited to 4000 W when they are installed in the Catalyst 6509 NEB switch chassis I OL 5781 07 Catalyst 6500 Series Switches Installation Guide rel Appendix A Power Supply Specifications HI Power Supply Compatibility Matrix Table A 2 Platform Supported Power Supplies Catalyst 6500 Series Switch Supported Power Supply Configurations continued Chassis Power Supply Restrictions Catalyst 6509 NEB A e 2500 W AC input and DC input e 3000 W AC input e 4000 W AC input and DC input e 6000 W AC input and DC input e 8700 W AC input The 6000 W AC input 6000 W DC input and the 8700 W AC input power supplies are limited to 4500 W maximum output when they are installed in the Catalyst 6509 NEB A switch chassis Catalyst 6509 V E e 2500 W AC input and DC input e 3000 W AC input e 4000 W AC input and DC input e 6000 W AC input and DC input e 8700 W AC input No restrictions Catalyst 6513 e 2500 W AC input and DC input e 3000 W AC input e 4000 W AC input and DC input e 6000 W AC input and DC input e 8700 W AC input
11. Figure A 26 CAB 7KACA Australia and New Zealand Figure A 27 CAB 7KACE Continental Europe Catalyst 6500 Series Switches Installation Guide OL 5781 07 oe Appendix A Power Supply Specifications HE AC Power Cord Illustrations Figure A 28 CAB 7KACI Italy Figure A 29 CAB 7KAC 15 Japan and United States Figure A 30 CAB 7KACU United Kingdom Catalyst 6500 Series Switches Installation Guide lt x mer Appendix A Power Supply Specifications AC Power Cord Illustrations i Figure A 31 CAB 7513ACR and CAB IR2073 C19 AR Argentina Figure A 32 CAB 7513ACA Australia and New Zealand Figure A 33 CAB 7513ACE Continental Europe Catalyst 6500 Series Switches Installation Guide OL 5781 07 om Appendix A Power Supply Specifications HE AC Power Cord Illustrations Figure A 34 CAB AC 2500W ISRL Israel Figure A 35 CAB 7513ACI Italy Figure A 36 CAB 7513AC Japan and United States Catalyst 6500 Series Switches Installation Guide OL 5781 07 Appendix A Power Supply Specifications AC Power Cord Illustrations Wi Figure A 37 CAB AC16A CH People s Republic of China Figure A 38 CAB 7513ACSA South Africa Figure A 39 CAB ACS 10 Switzerland Catalyst 6500 Series Switches Installation Guide OL 5781 07 e Appendix A Power Supply Specifications HE AC Power Cord Illustrations Figure A 40 CAB 7513AC
12. Installation Guide PAs E OL 5781 07 Appendix A Power Supply Specifications 950 W AC Input and DC Input Power Supplies W Table A 3 950 W AC Input Power Supply Specifications continued Specification Description Branch circuit requirement Each chassis power supply should have its own dedicated fused branch circuit e For North America 15 A e For International Circuits sized to local and national codes e All Catalyst 6500 series AC input power supplies require single phase source AC e All AC power supply inputs are fully isolated Source AC can be out of phase between multiple power supplies in the same chassis which means that PS1 can be operating from phase A and PS2 can be operating from phase B For high line operation the power supply operates with the hot conductor wired to a source AC phase and the neutral conductor wired either to ground or to another source AC phase as long as the net input voltage is in the range of 170 to 264 VAC Source AC can be out of phase between AC inputs on power supplies that are equipped with multiple AC inputs which means that power cord 1 can be plugged into phase A and power cord 2 can be plugged into phase B Power supply output 950 W maximum 100 240 VAC capacity Power supply output e 15 A 41 5 VDC e 2 5 A 3 3 VDC e 19 15 A 50 VDC Output holdup time 20 ms minimum kVA rating 1 32 kVA Heat dissipation 4441 BTU hour approx W
13. Red Problem with one or more of the DC output voltages of the power supply is detected Off DC output voltages within acceptable margins Note For proper operation of the OUTPUT FAIL LED systems with single power supplies must be configured with a minimum of one fan tray and one supervisor engine Systems with dual power supplies must have a minimum configuration of one fan tray one supervisor engine and one additional module Failure to meet these minimum configuration requirements can cause a false power supply output fail signal Catalyst 6500 Series Switches Installation Guide Ans E OL 5781 07 Appendix A Power Supply Specifications 950 W Power Supply AC Power Cords Table A 6 lists the 950 W AC input power supply AC power cords specifications These power cords plug into the 950 W PEM PEM 15A AC not directly into the power supply The table includes references to power cord illustrations amp 950 W AC Input and DC Input Power Supplies Note All 950 W power supply power cords are 8 feet 2 inches 2 5 meters in length amp Note All 950 W power supply power cords have an IEC60320 C15 appliance connector at one end The appliance connector has a 90 left bend Table A 6 Locale Argentina Australia New Zealand Continental Europe Italy Japan North America United Kingdom Power Cord Part Number CAB 7KACR CAB AC10A 90L AU CAB AC10A 90L EU CAB AC10A 90L IT
14. TWLK NEMA L6 20 16 A 250 VAC Figure A 44 South Africa CAB 7513ACSA IEC 884 1 16 A 250 VAC Figure A 38 Switzerland CAB ACS 10 SEV 1011 10 A 250 VAC Figure A 39 Switzerland CAB ACS 16 SEV 5934 2 Type 23 16 A 250 VAC Figure A 45 United Kingdom CAB 7513ACU BS 1363 13 A 250 VAC Figure A 40 1 For operation in Japan ask your local electrical contractor to prepare the NEMA 5 20 power plug 2 For operation in Japan ask your local electrical contractor to prepare the NEMA 6 20 power plug 3 For operation in Japan ask your local electrical contractor to prepare the NEMA L6 20 power plug 4 Plug contains a 13 A fuse Catalyst 6500 Series Switches Installation Guide AppendixA Power Supply Specifications 2500 W AC Input and DC Input Power Supplies W 2500 W AC Input and DC Input Power Supplies The 2500 W AC input power supply WS CAC 2500W and 2500 W DC input power supply WS CDC 2500W are supported in the following Catalyst 6500 series switches e Catalyst 6506 e Catalyst 6506 E e Catalyst 6509 e Catalyst 6509 E e Catalyst 6509 NEB e Catalyst 6509 NEB A e Catalyst 6509 V E e Catalyst 6513 The 2500 W power supplies shown in Figure A 9 and Figure A 10 share the same form factor as the 1000 W 1300 W 3000 W 4000 W and 6000 W AC input power supplies amp Note With a fully populated Catalyst 6513 switch two 2500 W power supplies are not fully redundant If you operate the 2500 W power supply at
15. W AC input power supply requires a PEM 20A AC Power Entry Module PEM Catalyst 6504 E e 2700 W AC input and DC input No restrictions Catalyst 6500 Series Switches Installation Guide a OL 5781 07 Appendix A Power Supply Specifications Power Supply Compatibility Matrix i Table A 2 Catalyst 6500 Series Switch Supported Power Supply Configurations continued Platform Supported Power Supplies Chassis Power Supply Restrictions Catalyst 6506 e 1000 W AC input The 6000 W AC input 6000 W e 1300 W AC input and DC input e 2500 W AC input and DC input e 3000 W AC input e 4000 W AC input and DC input e 6000 W AC input and DC input e 8700 W AC input DC input and the 8700 W AC input power supplies are limited to 4000 W when they are installed in the Catalyst 6506 switch chassis Catalyst 6506 E e 2500 W AC input and DC input e 3000 W AC input e 4000 W AC input and DC input e 6000 W AC input and DC input e 8700 W AC input No restrictions Catalyst 6509 e 1000 W AC input e 1300 W AC input and DC input e 2500 W AC input and DC input e 3000 W AC input e 4000 W AC input and DC input e 6000 W AC input and DC input e 8700 W AC input The 6000 W AC input 6000 W DC input and the 8700 W AC input power supplies are limited to 4000 W when they are installed in the Catalyst 6509 switch chassis Catalyst 6509 E e 2500 W AC input and DC input e 3000 W AC input e 4000 W AC input and
16. W DC input power supplies cannot be installed in the Catalyst 6503 Catalyst 6503 E and Catalyst 6504 E switch chassis Catalyst 6500 Series Switches Installation Guide OL 5781 07 Appendix A Power Supply Specifications 6000 W AC Input and DC Input Power Supplies W Figure A 16 6000 W AC Input Power Supply Figure A 17 6000 W DC Input Power Supply Catalyst 6500 Series Switches Installation Guide OL 5781 07 EA Appendix A Power Supply Specifications HX 6000W AC Input and DC Input Power Supplies 6000 W Power Supply Specifications Table A 34 lists the specifications for the 6000 W AC input power supply Table A 33 6000 W AC Input Power Supply Specifications Specification Description AC input type 2 AC inputs per power supply High line input with power factor correction PFC included Note Power factor correction is a standard feature on all Catalyst 6500 series AC input power supplies PFC reduces the reactive component in the source AC current allowing higher power factors typically 99 percent or better and lower harmonic current components AC input voltage e Low line 120 VAC nominal 85 VAC min to 132 VAC max e High line 230 VAC nominal 170 VAC min to 264 VAC max AC input current 16 A each input AC input frequency 50 60 Hz nominal 3 for full range Catalyst 6500 Series Switches Installation Guide A 48 OL 5781 07 Appendix A Power Su
17. and you power off or remove power supply 2 the total system power will be 4000 W The system will issue a normal power supply 2 down remove indication warning e If you power down power supply 1 while power supply 2 is operating the system will issue a normal power supply 1 down indication warning with another warning asking the user not to remove power supply 1 If power supply 1 is left in the system even if it is powered off the total system power will be 4000 W e If you remove power supply 1 from the system a major alarm will be issued to warn that the total system power will be reduced to 2940 W and that any modules or PoE devices that cause the system to exceed 2940 W will power down in 180 seconds 3 minutes If you insert a replacement power supply 1 in the 180 second timeframe no action will be taken Catalyst 6500 Series Switches Installation Guide PA76 E OL 5781 07 Appendix A Power Supply Specifications amp Power Supply Redundancy W Note In systems that are equipped with two power supplies if one power supply fails and the other power supply cannot fully power all of the installed modules system power management will shut down devices in the following order e Power over Ethernet PoE devices The system will power down PoE devices in descending order starting with the highest numbered port on the module in the highest numbered slot e Modules If additional power savings are needed the sys
18. criteria for both UPS outputs as well as standard circuits and transformers to power a switch Table A 39 lists the power supply LEDs and their meanings Catalyst 6500 Series Switches Installation Guide Pass E OL 5781 07 Appendix A Power Supply Specifications 8700 W AC Input Power Supply W Table A 39 8700 W AC Input Power Supply LEDs LED INPUT OK 1 INPUT OK 2 and INPUT OK 3 Green Source voltage is OK Input voltage is 85 VAC or greater Off Source AC voltage falls below 70 VAC is not present or the power supply is turned off 220VAC 1 2 and 3 Green High line AC is present on the respective AC inputs Input voltage is 170 VAC or higher Off Source AC voltage falls below 170 VAC is not present or the power supply is turned off FAN OK e Green Power supply fan is operating properly e Off Power supply fan failure is detected OUTPUT FAIL e Red One or more of the power supply DC output voltages is out Note of the normal operating range For 3 3 VDC output 2 7 3 0 VDC min 3 6 3 8 VDC max For 12 VDC output 10 5 11 5 VDC min 12 6 13 0 VDC max For 42 VDC output 38 0 40 0 VDC min 45 0 52 0 VDC max Off All DC output voltages are within normal operating ranges For proper operation of the OUTPUT FAIL LED systems with single power supplies must be configured with a minimum of one fan tray and one supervisor engine Systems with dual power
19. e Green Source AC voltage is OK Input voltage is 85 VAC or greater e Off sSource AC voltage falls below 70 VAC is not present or the power supply turned off DC input power supplies e Green Source DC voltage is OK Input voltage is 40 5 VDC or greater e Off Source DC voltage falls below 33 VDC is not present or the power supply is turned off FAN OK e Green Power supply fan is operating properly e Off Power supply fan failure is detected OUTPUT FAIL e Red Problem with one or more of the DC output voltages of the power supply is detected e Off DC output voltages within acceptable margins Note For proper operation of the OUTPUT FAIL LED systems with single power supplies must be configured with a minimum of one fan tray and one supervisor engine Systems with dual power supplies must have a minimum configuration of one fan tray one supervisor engine and one additional module Failure to meet these minimum configuration requirements can cause a false power supply output fail signal 1300 W Power Supply AC Power Cords Table A 13 lists the specifications for the AC power cords that are available for the 1300 W AC input power supply The table includes references to power cord illustrations amp Note All 1300 W power supply power cords are 14 feet 4 3 meters in length amp Note All 1300 W power supply power cords have an IEC60320 C19 appliance connector at one
20. operating with 100 120 VAC you must use two or three AC power cords and the power supply output is limited to either 2800 W 2 inputs or 4200 W 3 inputs 2 The PDU power cable is designed for users who power their switch from a PDU The end of the cable that plugs into the Catalyst 6500 series switch chassis has a C19 connector the other end of the cable that plugs into the PDU has a C20 connector Catalyst 6500 Series Switches Installation Guide OL 5781 07 Appendix A Power Supply Specifications AC Power Cord Illustrations Wi AC Power Cord Illustrations This section contains the AC power cord illustrations see Figures A 19 through A 48 An AC power cord may be used with several power supplies See the power supply specifications tables for the AC power cord illustrations that are applicable for your power supply Figure A 20 CAB AC10A 90L AU Australia and New Zealand Figure A 21 CAB AC10A 90L EU Continental Europe Catalyst 6500 Series Switches Installation Guide OL 5781 07 I Appendix A Power Supply Specifications HE AC Power Cord Illustrations Figure A 22 CAB AC10A 90L IT Italy Figure A 23 CAB AC15A 90L US Japan and United States Figure A 24 CAB AC10A 90L UK United Kingdom Catalyst 6500 Series Switches Installation Guide ELE TTE Appendix A Power Supply Specifications AC Power Cord Illustrations Wi Figure A 25 CAB 7KACR Argentina
21. power supplies PFC reduces the reactive component in the source AC current allowing higher power factors typically 99 percent or better and lower harmonic current components AC input voltage e Low line 120 VAC nominal 85 VAC min to 132 VAC max e High line 230 VAC nominal 170 VAC min to 264 VAC max AC input current e 12 A 120 VAC e 6A 230 VAC AC input frequency 50 60 Hz nominal Branch circuit requirement Each chassis power supply should have its own dedicated fused branch circuit e For North America 15 A or 20 A e For International Circuits sized to local and national codes e All Catalyst 6500 series AC input power supplies require single phase source AC e All AC power supply inputs are fully isolated Source AC can be out of phase between multiple power supplies in the same chassis which means that PS1 can be operating from phase A and PS2 can be operating from phase B For high line operation the power supply operates with the hot conductor wired to a source AC phase and the neutral conductor wired either to ground or to another source AC phase as long as the net input voltage is in the range of 170 to 264 VAC Source AC can be out of phase between AC inputs on power supplies that are equipped with multiple AC inputs which means that power cord 1 can be plugged into phase A and power cord 2 can be plugged into phase B OL 5781 07 Catalyst 6500 Ser
22. primary safety ground for Catalyst 6503 and Catalyst 6503 E chassis that are equipped with 950 W DC input power supplies and DC input PEMs The DC input power supplies for these chassis do not have a separate ground The PEMs have an illuminated power switch AC input model only current protection surge and EMI suppression and filtering functions Figure A 1 950 W AC and DC Input Power Supplies Figure A 2 950 W AC Input PEM PEM 15A AC Catalyst 6500 Series Switches Installation Guide OL 5781 07 a AS Appendix A Power Supply Specifications WE 950W AC Input and DC Input Power Supplies Figure A 3 DC Power Entry Module PEM 950 W Power Supply Specifications Table A 3 lists the specifications for the 950 W AC input power supply Table A 3 950 W AC Input Power Supply Specifications Specification Description AC input type Autoranging input with power factor correction PFC Note Power factor correction is a standard feature on all Catalyst 6500 series AC input power supplies PFC reduces the reactive component in the source AC current allowing higher power factors typically 99 percent or better and lower harmonic current components AC input voltage e Low line 120 VAC nominal 85 VAC min to 132 VAC max e High line 230 VAC nominal 170 VAC min to 264 VAC max AC input current e 12 A 120 VAC e 6A 230 VAC AC input frequency 50 60 Hz nominal Catalyst 6500 Series Switches
23. the low range input 100 to 120 VAC it is not redundant in a fully populated Catalyst 6509 Catalyst 6509 E Catalyst 6509 NEB Catalyst 6509 NEB A or Catalyst 6509 V E switch Ss Note The 2500 W AC input power supply needs 220 VAC to deliver 2500 W of power When powered with 110 VAC it delivers only 1300 W In addition the power supply needs 16 A regardless of whether it is plugged into 110 VAC or 220 VAC Figure A 9 2500 W AC Input Power Supply I OL 5781 07 Catalyst 6500 Series Switches Installation Guide gy Appendix A Power Supply Specifications WE 2500W AC Input and DC Input Power Supplies Figure A 10 2500 W DC input Power Supply 2500 W Power Supply Specifications Table A 17 lists the specifications for the 2500 W AC input and DC input power supplies Table A 17 2500 W AC Input Power Supply Specifications Specification Description AC input type Autoranging input with power factor correction PFC Note Power factor correction is a standard feature on all Catalyst 6500 series AC input power supplies PFC reduces the reactive component in the source AC current allowing higher power factors typically 99 percent or better and lower harmonic current components AC input voltage e Low line 120 VAC nominal 85 VAC min to 132 VAC max e High line 230 VAC nominal 170 VAC min to 264 VAC max AC input current 16 A maximum at 230 VAC at 2500 W output 16 A maximum at 120 VAC at 1300 W
24. 12V 27 89 A 42 V e 200 240 VAC operation 250A 3 3 V 5A 5V 12A 12V 65 98 A 42 V Front panel power connector A two pin male Molex connector is located in the lower right corner of the power supply front panel The connector provides 42 VDC at a maximum of 17 A This connector provides power to the WS 6509 NEB UPGRD kit fan assembly through a power harness also provided in the kit A hinged protective flap secured by a captive screw covers the connector when it is not in use Output holdup time 20 ms minimum kVA rating 3520 W total input power or 3 6 KVA high line operation Heat dissipation 12 046 BTU hour approx Weight 15 8 lb 7 2 kg 1 The kVA rating listed for the power supply should be used as the sizing criteria for both UPS outputs as well as standard circuits and transformers to power a switch Table A 26 lists the power supply LEDs and their meanings Catalyst 6500 Series Switches Installation Guide OL 5781 07 Appendix A Power Supply Specifications 3000 W AC Input Power Supply W Table A 26 3000 W AC Input Power Supply LEDs LED Meaning INPUT OK e Green Source AC voltage is OK Input voltage is 85 VAC or greater e Off Source AC voltage falls below 70 VAC is not present or the power supply is turned off FAN OK e Green Power supply fan is operating properly e Off Power supply fan failure is detected OUTPUT FAIL e Red Problem wi
25. 500 series switches e Catalyst 6506 e Catalyst 6506 E e Catalyst 6509 e Catalyst 6509 E e Catalyst 6509 NEB e Catalyst 6509 NEB A e Catalyst 6509 V E e Catalyst 6513 The 3000 W power supply see Figure A 13 shares the same form factor as the 1000 W 1300 W 2500 W 4000 W and 6000 W AC input power supplies amp Note The 3000 W AC input power supply needs 220 VAC to deliver 3000 W of power When operating with 110 VAC it delivers only 1400 W In addition the power supply needs 16 A regardless of whether it is plugged into 110 VAC or 220 VAC Figure A 13 3000 W AC Input Power Supply Catalyst 6500 Series Switches Installation Guide EEN TAE Appendix A Power Supply Specifications 3000 W AC Input Power Supply W 3000 W Power Supply Specifications Table A 25 lists the specifications for the 3000 W AC input power supply Table A 25 3000 W Power Supply Specifications Specification Description AC input type Autoranging input with power factor correction PFC Note Power factor correction is a standard feature on all Catalyst 6500 series AC input power supplies PFC reduces the reactive component in the source AC current allowing higher power factors typically 99 percent or better and lower harmonic current components AC input voltage e Low line 120 VAC nominal 85 VAC min to 132 VAC max e High line 230 VAC nominal 170 VAC min to 264 VAC max AC input current
26. AC Input and DC Input Power Supplies Table A 10 1300 W AC Input Power Supply Specifications continued Specification Description kVA rating 1 625 kVA Heat dissipation 5478 BTU hour approx Weight 18 4 1b 8 3 kg 1 The kVA rating listed for the power supply should be used as the sizing criteria for both UPS outputs as well as standard circuits and transformers to power a switch Table A 11 lists the specifications for the 1300 W DC input power supply Table A 11 1300 W DC Input Power Supply Specifications Specification Description DC input voltage 48 VDC to 60 VDC continuous DC input current e 39 A 48 VDC e 31 A 60 VDC Power supply output 1360 W maximum DC input capacity Power supply output e 15 A 43 3 VDC e SA 5 VDC e 6A 12 VDC e 28 9 A 42 VDC DC input terminal block Accepts 3 10 AWG copper conductors Actual size of the wire needed is determined by the installer or local electrician Terminal block material is rated at 120 C Output holdup time 8 ms Heat dissipation 6447 BTU hour approx Weight 21 0 Ib 9 5 kg Table A 12 lists the 1300 W power supply LEDS and their meanings Catalyst 6500 Series Switches Installation Guide Pe i OL 5781 07 Appendix A Power Supply Specifications 1300 W AC Input and DC Input Power Supplies W Table A 12 1300 W AC Input and DC Input Power Supply LEDs LED Meaning INPUT OK AC input power supplies
27. APPENDIX A Power Supply Specifications This appendix describes the Catalyst 6500 series power supplies and provides their specifications This appendix contains the following sections Power Supply Compatibility Matrix page A 2 950 W AC Input and DC Input Power Supplies page A 5 1000 W AC Input Power Supply page A 10 1300 W AC Input and DC Input Power Supplies page A 13 1400 W AC Input Power Supply page A 18 2500 W AC Input and DC Input Power Supplies page A 23 2700 W AC Input and DC Input Power Supplies page A 29 3000 W AC Input Power Supply page A 36 4000 W AC Input and DC Input Power Supplies page A 41 6000 W AC Input and DC Input Power Supplies page A 46 8700 W AC Input Power Supply page A 54 AC Power Cord Illustrations page A 63 Power Supply Redundancy page A 73 Table A 1 lists the currently available Catalyst 6500 series switch power supplies and the power supply description location Table A 1 Catalyst 6500 Series Power Supplies Power Supply AC Input Model DC Input Model Rating Product Number Product Number 950 W PWR 950 AC PWR 950 DC 1000 W WS CAC 1000W Not Available 1300 W WS CAC 1300W WS CDC 1300W 1400 W PWR 1400 AC Not Available 2500 W WS CAC 2500W WS CDC 2500W 2700 W PWR 2700 AC 4 PWR 2700 DC 4 3000 W WS CAC 3000W Not Available I OL 5781 07 Catalyst 6500 Series Switches Installation Guide Appendix A Power Supply Specifications HI Power Supply C
28. C voltage 110 VAC low line or 220 VAC high line applied to the power supply inputs The 8700 W AC input power supply is limited to reduced wattage ratings when it is installed in the following Catalyst 6500 series chassis e 4000 W maximum output when it is installed in a Catalyst 6506 Catalyst 6509 or Catalyst 6509 NEB switch chassis e 4500 W maximum output when it is installed in the Catalyst 6509 NEB A switch chassis e 6000 W maximum output when it is installed in the Catalyst 6513 switch chassis Note The power supply will not power up if you attach only one power cord and the power cord is connected to low line 110 VAC nominal source AC 2800 W maximum with the following combinations of power cords and source AC voltage applied to the power supply inputs e Two AC inputs are connected to low line 110 VAC nominal the third AC input is not connected e One AC input is connected to low line 110 VAC nominal one AC input is connected to high line 220 VAC nominal the third AC input is not connected e One AC input is connected to high line 220 VAC nominal two AC inputs are not connected 4200 W maximum with the following combinations of power cords and source AC voltage applied to the power supply inputs e All three AC inputs are connected to low line 110 VAC nominal e Two AC inputs are connected to low line 110 VAC nominal one AC input is connected to high line 220 VAC nominal 5800 W maximu
29. CAB AC15A 90L US CAB AC10A 90L UK 950 W AC Input Power Supply Power Cords AC Source Plug Type IRAM 2073 SAA AS 3112 CEE 7 7 CEI 23 16 7 NEMA 5 15 BS 1363 Cordset Rating 10 A 250 VAC 10 A 250 VAC 10 A 250 VAC 10 A 250 VAC 15 A 125 VAC 10 A 250 VAC Power Cord Reference Illustration Figure A 25 Figure A 20 Figure A 21 Figure A 22 Figure A 23 Figure A 24 1 Plug contains a 13 A fuse OL 5781 07 Catalyst 6500 Series Switches Installation Guide Appendix A Power Supply Specifications W 1000W AC Input Power Supply 1000 W AC Input Power Supply The 1000 W AC input power supply WS CAC 1000W is supported in the following Catalyst 6500 series switches e Catalyst 6506 e Catalyst 6509 e Catalyst 6509 NEB The 1000 W power supply shown in Figure A 4 shares the same form factor as the 1300 W 2500 W 3000 W 4000 W and 6000 W AC input power supplies Figure A 4 1000 W AC Input Power Supply Catalyst 6500 Series Switches Installation Guide TAE Appendix A Power Supply Specifications 1000 W AC Input Power Supply W 1000 W Power Supply Specifications Table A 7 lists the specifications for the 1000 W AC input power supply Table A 7 1000 W Power Supply Specifications Specification AC input type Description Autoranging input with power factor correction PFC Note Power factor correction is a standard feature on all Catalyst 6500 series AC input
30. One DC input operation 1350 W operation 15A 41 5 VDC 5A 43 3 VDC 27 49 A 50 VDC e Two DC inputs operation 2700 W operation 15A 41 5 VDC 5A 43 3 VDC 55 61 A 50 VDC DC input terminal block Accepts 2 14 AWG copper conductors Actual size of the wire needed is determined by the installer or local electrician Terminal block material rated at 150 C Output holdup time 4 ms kVA rating 3 5 KW Heat dissipation 11 968 BTU hour approx Weight 21 0 Ib 9 5 kg 1 The kVA rating listed for the power supply should be used as the sizing criteria for both UPS outputs as well as standard circuits and transformers to power a switch Table A 23 lists the power supply LEDs and their meanings OL 5781 07 Catalyst 6500 Series Switches Installation Guide Appendix A Power Supply Specifications W 2700W AC Input and DC Input Power Supplies Table A 23 2700 W AC Input and DC Input Power Supply LEDs LED INPUT 1 OK INPUT 2 OK DC input power supply only AC input power supplies e Green Source AC voltage is OK Input voltage is 85 VAC or greater e Off Source AC voltage falls below 70 VAC is not present or the power supply is turned off DC input power supplies e Green Source DC is OK Input voltage is 40 5 VDC or greater e Off Source DC voltage falls below 33 VDC is not present or the power supply is turned off FAN OK e Green Power
31. U United Kingdom Figure A 41 CAB AC 2500W EU Continental Europe Figure A 42 CAB AC 2500W INT International Catalyst 6500 Series Switches Installation Guide 70 mer Appendix A Power Supply Specifications AC Power Cord Illustrations i Figure A 43 CAB AC 2500W US1 Japan and United States Figure A 44 CAB AC C6K TWLK Japan and United States Catalyst 6500 Series Switches Installation Guide OL 5781 07 im Appendix A Power Supply Specifications HE SAC Power Cord Illustrations Figure A 45 CAB ACS 16 Switzerland Figure A 46 CAB AC 16A AUS Australia and New Zealand Figure A 47 CAB C19 CBN PDU Catalyst 6500 Series Switches Installation Guide A72 E TTE Appendix A Power Supply Specifications Figure A 48 Power Supply Redundancy W WS CAC 4000W INT International Figure A 49 WS CAC 4000W US United States Power Supply Redundancy amp Catalyst 6500 series switching modules have different power requirements Depending upon the wattage of the power supply certain switch configurations might require more power than a single power supply can provide Although the power management feature allows you to supply power to all installed modules with two power supplies redundancy is not supported in this configuration Redundant and combined power configurations are summarized in Table A 42 The effects of changing the power supply configuration
32. an tray one supervisor engine and one additional module Failure to meet these minimum configuration requirements can cause a false power supply output fail signal Catalyst 6500 Series Switches Installation Guide n12 E OL 5781 07 Appendix A Power Supply Specifications 1300 W AC Input and DC Input Power Supplies W 1000 W Power Supply AC Power Cords Table A 9 lists the specifications for the AC power cords that are available for the 1000 W AC input power supply The table includes references to power cord illustrations amp Note All 1000 W power supply power cords are 8 feet 2 inches 2 5 meters in length amp Note All 1000 W power supply power cords have an IEC60320 C15 appliance plug at one end Table A 9 1000 W AC Input Power Supply Power Cords Locale Power Cord AC Source Plug Type Cordset Rating Power Cord Part Number Reference Illustration Argentina CAB 7KACR IRAM 2073 10 A 250 VAC Figure A 25 Australia New Zealand CAB 7KACA SAA AS 3112 15 A 250 VAC Figure A 26 Continental Europe CAB 7KACE CEE 7 7 16 A 250 VAC Figure A 27 Italy CAB 7KACI CEI 23 16 7 10 A 250 VAC Figure A 28 Japan North America CAB 7KAC 15 NEMA 5 15 15 A 125 VAC Figure A 29 United Kingdom CAB 7KACU BS 1363 10 A 250 VAC Figure A 30 1 Plug contains a 13 A fuse 1300 W AC Input and DC Input Power Supplies The 1300 W AC input power supply WS CAC 1300W and 1300 W DC input power supply WS CDC 1300W
33. and syslog messages are generated power supply is inserted with tedundancy disabled e System power is increased to the combined power capability of both supplies e The modules marked as power deny in the show module Status field are brought up if there is sufficient power Power supply is removed e System log and syslog messages are generated witiredundarcy en abled e Ifthe power supplies are of equal wattage there is no change in the module status because the power capability is unchanged If the power supplies are of unequal wattage and the lower wattage supply is removed there is no change in the module status If the power supplies are of unequal wattage and the higher wattage supply is removed the lower wattage power supply must be turned on manually The system had previously turned off the lower wattage power supply Power supply is removed e System log and syslog messages are generated with redundancy disabled e System power is decreased to the power capability of one supply e If there is not enough power for all previously powered up modules some modules are powered down and marked as power deny in the show module Status field Catalyst 6500 Series Switches Installation Guide OL 5781 07 a A75 Appendix A Power Supply Specifications W Power Supply Redundancy Table A 43 Effects of Power Supply Configuration Changes continued Configuration Change Effect System is booted wit
34. art number for the power supply The AC power cords are hardwired to the 4000 W power supplies 2 For Japan ask your local electrical contractor to prepare the NEMA L6 30 power plug 6000 W AC Input and DC Input Power Supplies Catalyst 6500 series switch support for the 6000 W AC input WS CAC 6000W and the 6000 W DC input PWR 6000 DC power supplies along with any power supply output restrictions are listed in amp Note Table A 32 Table A 32 Catalyst 6500 Series Chassis 6000 W AC Input Power Supply Restriction Chassis Support for the 6000 W AC Input and DC Input Power Supplies 6000 W DC Input Power Supply Restriction Catalyst 6506 Output limited to 4000 W Output limited to 4000 W Catalyst 6506 E No restrictions No restrictions Catalyst 6509 Output limited to 4000 W Output limited to 4000 W Catalyst 6509 E No restrictions No restrictions Catalyst 6509 NEB Output limited to 4000 W Output limited to 4000 W Catalyst 6509 NEB A Output limited to 4500 W Output limited to 4500 W Catalyst 6509 V E No restrictions No restrictions Catalyst 6513 No restrictions No restrictions The 6000 W AC input power supply shown in Figure A 16 and the 6000 W DC input power supply shown in Figure A 17 share the same form factor as the 1000 W 1300 W 2500 W 3000 W and 4000 W power supplies Because of form factor differences the 6000 W AC input and the 6000
35. ay type the corresponding power supply terminal block positions and a description of the power cycling operation Table A 40 External Relay Controller Box Relay Type Power Supply Relay Controller Switch Setting Power Supply Terminal Block Positions Used 8700 W Power Supply Relay Controller Switch Settings and Operation Remote Power Cycling Operation Normally open NO NO RELAY Control wires from the e Power supply cycled from on to off The relay DEFAULT external relay controller power supply is powered off by energizing box attach to terminal the relay relay contacts go from open to block positions 1 and 2 closed for more than 30 seconds e Power supply cycled from off to on The power supply is powered on by deenergizing the relay relay contacts go from closed to open for more than 10 seconds Normally closed NC NC RELAY Control wires from the e Power supply cycles from on to off The relay external relay controller power supply is powered off by energizing box attach to terminal the relay relay contacts go from closed to block positions 2 and 3 open for more than 30 seconds e Power supply cycles from off to on The power supply is powered on by deenergizing the relay relay contacts go from open to closed for more than 10 seconds No relay attached NO RELAY Remote power cycling DEFAULT feature not installed I OL 5781 07 Catalyst 6500 Series Switches Instal
36. chassis The 1400 W power supplies see Figure A 7 do not connect directly to source AC but use power entry modules PEMs located on the front of the Catalyst 6503 and Catalyst 6503 E switch chassis to connect the site power source to the power supply located in the back of the chassis The AC input PEM PEM 20A AC shown in Figure A 8 provides an input power connection on the front of the router chassis to connect the site power source to the power supply The PEMs have an illuminated power switch current protection surge and EMI suppression and filtering functions Figure A 7 1400 W AC Input Power Supply PWR 1400 AC Catalyst 6500 Series Switches Installation Guide OL 5781 07 Appendix A Power Supply Specifications 1400 W AC Input Power Supply W Figure A 8 1400 W AC Input PEM PEM 20A AC 1400 W Power Supply Specifications Table A 14 lists the specifications for the 1400 W AC input power supply Table A 14 1400 W AC Input Power Supply Specifications Specification Description AC input type Autoranging input with power factor correction PFC Note Power factor correction is a standard feature on all Catalyst 6500 series AC input power supplies PFC reduces the reactive component in the source AC current allowing higher power factors typically 99 percent or better and lower harmonic current components AC input voltage e Low line 120 VAC nominal 85 VAC min to 132 VAC max e Hig
37. cifications continued Specification Description Power supply output capacity e 2900 W operation one 220 VAC source or two 110 VAC sources 25 A 43 3 VDC 12 A 12 VDC 63 6 A 42 VDC e 6000 W operation two 220 VAC sources 25 A 43 3 VDC 12 A 12 VDC 137 4 A 42 VDC Output holdup time 20 ms minimum kVA rating 7 5 kVA Heat dissipation 23 812 BTU hour approx System power dissipation 7034 W Weight 25 4 Ib 11 5 kg 1 The kVA rating listed for the power supply should be used as the sizing criteria for both UPS outputs as well as standard circuits and transformers to power a switch Table A 34 list the specifications for the 6000 W DC input power supply Table A 34 6000 W DC Input Power Supply Specifications Specification Description Input voltage e 48 VDC nominal 37 A in North America operating range 40 5 VDC to 56 VDC e 60 VDC nominal 30 A for international operating range 55 VDC to 72 VDC Input current 40 A per DC input 48 VDC input voltage total of 4 inputs Power supply output The 6000 W DC input power supply can operate at either capacity e 2800 W 2 DC inputs active e 4500 W 3 DC inputs active e 6000 W 4 DC inputs active Catalyst 6500 Series Switches Installation Guide OL 5781 07 LEN Appendix A Power Supply Specifications HX 6000W AC Input and DC Input Power Supplies Table A 34 6000 W DC Input P
38. e Because of the form factor difference when you install an 8700 W power supply in a Catalyst 6506 Catalyst 6509 or Catalyst 6509 NEB chassis you must relocate the system ground connection from the chassis ground pad connection to the two system ground studs located on the 8700 W power supply faceplate Installing an 8700 W power supply in the other Catalyst 6500 series chassis does not require that you move the chassis system ground connection to the power supply The 8700 W power supply cannot be installed in the Catalyst 6503 Catalyst 6503 E and Catalyst 6504 E switch chassis Figure A 18 8700 W AC Input Power Supply 8700 W Power Supply Specifications Table A 38 lists the specifications for the 8700 W AC input power supply Table A 38 8700 W AC Input Power Supply Specifications Specification Description AC input type 3 AC inputs per power supply High line input with power factor correction PFC included Note Power factor correction is a standard feature on all Catalyst 6500 series AC input power supplies PFC reduces the reactive component in the source AC current allowing higher power factors typically 99 percent or better and lower harmonic current components AC input voltage e Low line 120 VAC nominal 85 VAC min to 132 VAC max One phase e High line 230 VAC nominal 170 VAC min to 264 VAC max OL 5781 07 Catalyst 6500 Series Switches Installation Guide gy Appendix A Power Suppl
39. e power supply is disabled For Cisco IOS both power supplies come on The total available wattage is the output wattage of the higher wattage power supply Equal or unequal wattage Disabled The total power available to the system is approximately 167 percent of the lower wattage power supply The system powers up as many modules as the combined capacity allows If the higher wattage power supply fails the lower wattage supply might also shut down due to overcurrent protection to prevent damage to the lower wattage power supply Table A 43 Effects of Power Supply Configuration Changes Configuration Change Effect Redundant to combined System log and syslog messages are generated System power is increased to approximately 167 percent of the lower wattage power supply The modules marked as power deny in the show module Status field are powered up if there is sufficient power Combined to redundant System log and syslog messages are generated System power is the power capability of the higher wattage supply If there is not enough power for all previously powered up modules some modules are powered down and marked as power deny in the show module Status field Equal wattage power supply is inserted with redundancy enabled System log and syslog messages are generated System power equals the power capability of one supply Both supplies provide approximately one half of the total cur
40. eight 8 2 lb 3 7 kg 1 The kVA rating listed for the power supply should be used as the sizing criteria for both UPS outputs as well as standard circuits and transformers to power a switch Catalyst 6500 Series Switches Installation Guide OL 5781 07 E Appendix A Power Supply Specifications Hi 950W AC Input and DC Input Power Supplies Table A 4 lists the specifications for the 950 W DC input power supply Table A 4 950 W DC Input Power Supply Specifications Specification Description DC input voltage 48 VDC to 60 VDC continuous DC input current e 38 A 48 VDC e 30A 60 VDC Power supply output 950 W capacity Power supply output e 15 A 41 5 VDC e 2 5 A 3 3 VDC e 19 15 A 50 VDC Output holdup time 4 ms Heat dissipation 4632 BTU hour approx Weight 8 4 lb 3 8 kg Table A 5 lists the power supply LEDs and their meanings Table A 5 950 W AC Input and DC Input Power Supply LEDs LED Meaning INPUT OK AC input power supplies e Green Source AC voltage is OK Input voltage is 85 VAC or greater e Off sSource AC voltage falls below 70 VAC is not present or the PEM is turned off DC input power supplies e Green Source DC voltage is OK 40 5 VDC or greater e Off Source DC voltage falls below 33 VDC or is not present at the PEM FAN OK Green Power supply fan is operating properly Off Power supply fan failure is detected OUTPUT FAIL
41. ement Each chassis power supply should have its own dedicated fused branch circuit e For North America 20 A e For International Circuits sized to local and national codes e All AC power supply inputs are fully isolated Source AC can be out of phase between multiple power supplies in the same chassis which means that PS1 can be operating from phase A and PS2 can be operating from phase B For high line operation the power supply operates with the hot conductor wired to a source AC phase and the neutral conductor wired either to ground or to another source AC phase as long as the net input voltage is in the range of 170 to 264 VAC Source AC can be out of phase between AC inputs on power supplies that are equipped with multiple AC inputs which means that power cord 1 can be plugged into phase A and power cord 2 can be plugged into phase B Power supply output capacity e 1350 W maximum 100 120 VAC e 2700 W maximum 200 240 VAC OL 5781 07 Catalyst 6500 Series Switches Installation Guide Appendix A Power Supply Specifications WE 2700W AC Input and DC Input Power Supplies Table A 21 2700 W AC Input Power Supply Specifications continued Specification Description Power supply output e 100 120 VAC operation 15A 41 5 VDC 2 5 A 3 3 VDC 27 49 A 50 VDC e 200 240 VAC operation 15A 41 5 VDC 2 5 A 3 3 VDC 55 61 A 50 VDC Output holdup time 20 ms m
42. end Catalyst 6500 Series Switches Installation Guide OL 5781 07 ES Appendix A Power Supply Specifications His 1400 W AC Input Power Supply Table A 13 Locale Power Cord Part Number 1300 W Power Supply AC Power Cords AC Source Plug Type Cordset Rating Power Cord Reference Illustration CAB 7513ACR Argentina Australia New Zealand Continental Europe Israel Italy Japan North America People s Republic of China South Africa Switzerland United Kingdom CAB 7513ACA CAB 7513ACE CAB AC 2500W ISRL CAB 7513ACI CAB 7513AC CAB AC16A CH CAB 7513ACSA CAB ACS 10 CAB 7513ACU IRAM 2073 SAA AS 3112 CEE 7 7 SI1683 CEI 23 16 7 NEMA 5 20 GB16C IEC 884 1 SEV 1011 BS 13637 10 A 250 VAC 15 A 250 VAC 16 A 250 VAC 16 A 250 VAC 16 A 250 VAC 20 A 125 VAC 16 A 250 VAC 16 A 250 VAC 10 A 250 VAC 13 A 250 VAC Figure A 31 Figure A 32 Figure A 33 Figure A 34 Figure A 35 Figure A 36 Figure A 37 Figure A 38 Figure A 39 Figure A 40 1 For Japan ask your local electrical contractor to prepare the NEMA 5 20 power plug 2 Plug contains a 13 A fuse 1400 W AC Input Power Supply The 1400 W AC input power supply PWR 1400 AC can be installed in the Catalyst 6503 switch and Catalyst 6503 E switch chassis only Due to form factor differences the 1400 W AC input power supply cannot be installed in any other Catalyst 6500 series switch
43. es Figure A 12 2700 W DC Input Power Supply Ground terminal block 1 Captive installation screw 4x 7 Fixed cable guide top half 2 Source DC terminal block 8 Detached cable guide bottom half 3 Status LEDs 9 Tie wrap for source DC cables 4 Terminal block cover 10 Fixed cable guide bottom half 5 Detached cable guide top half 11 Tie wrap for ground cable 6 mi Catalyst 6500 Series Switches Installation Guide OL 5781 07 Appendix A Power Supply Specifications 2700 W AC Input and DC Input Power Supplies W 2700 W Power Supply Specifications Table A 22 lists the specifications for the 2700 W AC input power supply Table A 21 2700 W AC Input Power Supply Specifications Specification AC input type Description Autoranging input with power factor correction PFC Note Power factor correction is a standard feature on all Catalyst 6500 series AC input power supplies PFC reduces the reactive component in the source AC current allowing higher power factors typically 99 percent or better and lower harmonic current components AC input voltage e Low line 120 VAC nominal 85 VAC min to 132 VAC max e High line 230 VAC nominal 170 VAC min to 264 VAC max AC input current e 16 A maximum at 230 VAC at 2700 W output e 16 A maximum at 120 VAC at 1350 W output AC input frequency 50 60 Hz nominal 3 for full range Branch circuit requir
44. h e System log and syslog messages are generated power supplies of different wattage installed and redundancy enabled e For Cisco IOS both power supplies come on The total available wattage is the output wattage of the higher wattage power supply e The lower wattage supply is disabled Catalyst operating system System is booted with e System log and syslog messages are generated power supplies of equal or different wattage installed and redundancy disabled e The system powers up as many modules as the combined capacity allows e System power equals the combined power capability of both supplies When running redundant 4000 W 6000 W or 8700 W power supplies in Catalyst 6506 and Catalyst 6509 non E series systems if you remove the power supply in bay 1 the total system power will be reduced to 2940 W 70 A at 42 VDC after 180 seconds 3 minutes You can avoid this reduction in the total system power by leaving the power supply in bay 1 even in a powered down state If the total system power usage is greater than 2940 W the following scenario will apply if a 4000 W 6000 W or a 8700 W power supply is removed from bay 1 these scenarios are specific to only these three power supplies running in redundant mode in either the Catalyst 6506 or Catalyst 6509 non E series systems e Ifthe power supplies in bay 1 and bay 2 are running in redundant mode the total system power will be 4000 W e If power supply 1 is running
45. h line 230 VAC nominal 170 VAC min to 264 VAC max AC input current e 16A 120 VAC e 8A 230 VAC AC input frequency 50 60 Hz nominal 3 Hz for full range Catalyst 6500 Series Switches Installation Guide OL 5781 07 ES Appendix A Power Supply Specifications 1400 W AC Input Power Supply Table A 14 Specification 1400 W AC Input Power Supply Specifications continued Description Branch circuit requirement Each chassis power supply should have its own dedicated fused branch circuit e For North America 20 A e For International Circuits sized to local and national codes e All AC power supply inputs are fully isolated Source AC can be out of phase between multiple power supplies in the same chassis which means that PS1 can be operating from phase A and PS2 can be operating from phase B For high line operation the power supply operates with the hot conductor wired to a source AC phase and the neutral conductor wired either to ground or to another source AC phase as long as the net input voltage is in the range of 170 to 264 VAC Source AC can be out of phase between AC inputs on power supplies that are equipped with multiple AC inputs which means that power cord 1 can be plugged into phase A and power cord 2 can be plugged into phase B Power supply output capacity 1400 W Power supply output e ISA 41 5V e 25A 43 3V e 274A 50V Output holdup time 20 ms min
46. he 6000 W power supply operating on two 110 VAC inputs delivers 2900 W 2 When operating with 100 120 VAC you must use two AC power cords and the power supply output is limited to 2900 W 3 The PDU power cable is designed for users who power their switch from a PDU The end of the cable that plugs into the Catalyst 6500 series switch chassis has a C19 connector the other end of the cable that plugs into the PDU has a C20 connector 8700 W AC Input Power Supply Catalyst 6500 series switch support for the 8700 W AC input WS CAC 8700W E power supply along with any power supply output restrictions are listed in Table A 37 Table A 37 Catalyst 6500 Series Chassis Chassis Support for the 8700 W Power Supply 8700 W Power Supply Restriction Catalyst 6506 Output limited to 4000 W Catalyst 6506 E No restrictions Catalyst 6509 Output limited to 4000 W Catalyst 6509 E No restrictions Catalyst 6509 NEB Output limited to 4000 W Catalyst 6509 NEB A Output limited to 4500 W Catalyst 6509 V E No restrictions Catalyst 6513 Output is limited to 6000 W The 8700 W AC input power supply shown in Figure A 18 shares a similar but not identical form factor as the 1000 W 1300 W 2500 W 3000 W 4000 W and 6000 W power supplies Catalyst 6500 Series Switches Installation Guide OL 5781 07 AppendixA Power Supply Specifications amp 8700 W AC Input Power Supply W Not
47. he type of relay contained in the external relay controller box either a normally open type of relay or a normally closed type of relay A plastic bag containing one ferrite bead and two 4 inch plastic ties is included with the 8700 W power supply AC power cords The ferrite bead is a passive device that limits high frequency interference on interface and control cables and is only required when you install the remote power cycling feature that is supported by the 8700 Watt power supply The ferrite bead is installed on the two control wires that come from the relay controller box to the terminal block on the 8700 W power supply The ferrite bead should be installed as close as possible to the power supply terminal block for the bead to be effective You do not need the ferrite bead for 8700 Watt power supply installations that do not include the remote power cycling feature If you need to install the ferrite bead refer to Installing the Ferrite Bead procedure on page 4 99 Catalyst 6500 Series Switches Installation Guide nco i OL 5781 07 Appendix A Power Supply Specifications 8700 W AC Input Power Supply W Remote Power Cycling Operation This feature allows you to remotely power cycle the Catalyst 6500 series switch using any appropriate third party relay controller This eliminates the need for you to have access to the supervisor engine console or CLI to control power cycling Table A 40 lists the relay controller box rel
48. ies Switches Installation Guide Appendix A Power Supply Specifications W 1000W AC Input Power Supply Table A 7 1000 W Power Supply Specifications continued Specification Description Power supply output 1000 W capacity Power supply output e 15 A 43 3 VDC e SA 5 VDC e 6A 12 VDC e 20 3 A 42 VDC Output holdup time 20 ms minimum kVA rating 1 25 kVA Heat dissipation 4213 BTU hour approx Front panel LEDs Weight 14 8 lb 6 7 kg 1 The kVA rating listed for the power supply should be used as the sizing criteria for both UPS outputs as well as standard circuits and transformers to power a switch Table A 8 list the power supply LEDs and their meanings Table A 8 1000 W Power Supply LEDs LED Meaning INPUT OK e Green Source AC voltage is OK Input voltage is 85 VAC or greater e Off sSource AC voltage falls below 70 VAC is not present or the power supply is turned off FAN OK e Green Power supply fan is operating properly e Off Power supply fan failure is detected OUTPUT FAIL e Red Problem with one or more of the DC output voltages of the power supply is detected e Off DC output voltage with acceptable margins Note For proper operation of the OUTPUT FAIL LED systems with single power supplies must be configured with a minimum of one fan tray and one supervisor engine Systems with dual power supplies must have a minimum configuration of one f
49. imum kVA rating 1 75 kVA Heat dissipation 5976 BTU hour approx Weight 7 8 Ib 3 5 kg 1 The kVA rating listed for the power supply should be used as the sizing criteria for both UPS outputs as well as standard circuits and transformers to power a switch Table A 15 lists the 1400 W AC input power supply LEDs and their meanings Catalyst 6500 Series Switches Installation Guide OL 5781 07 Appendix A Power Supply Specifications 1400 W AC Input Power Supply W Table A 15 1400 W AC Input Power Supply LEDs LED Meaning INPUT OK e Green Source AC voltage is OK Input voltage is 85 VAC or greater e Off Source AC voltage falls below 70 VAC is not present or the power supply is turned off FAN OK e Green Power supply fan is operating properly e Off Power supply fan failure is detected OUTPUT FAIL e Red Problem with one or more of the DC output voltages of the Note power supply is detected DC output voltages within acceptable margins For proper operation of the OUTPUT FAIL LED systems with single power supplies must be configured with a minimum of one fan tray and one supervisor engine Systems with dual power supplies must have a minimum configuration of one fan tray one supervisor engine and one additional module Failure to meet these minimum configuration requirements can cause a false power supply output fail signal 1400 W Power Supply AC Power Cord
50. inimum kVA rating 3 4 KVA high line operation Heat dissipation 11 238 BTU hour approx Weight 18 5 1b 8 4 kg 1 The kVA rating listed for the power supply should be used as the sizing criteria for both UPS outputs as well as standard circuits and transformers to power a switch Table A 22 lists the 2700 W DC input power supply specifications Table A 22 2700 W DC Input Power Supply Specifications Specification Description DC input voltage e 48 VDC 37 A for nominal 48 V battery backup system operating range 40 5 VDC to 56 VDC e 60 VDC 29 A for nominal 60 V battery backup system operating range 55 VDC to 72 VDC DC input current per DC e 43 A 40 5 VDC nyt e 37 A 48 VDC e 29 A 60 VDC Note For multiple DC input power supplies each DC input must be protected by a dedicated circuit breaker or a fuse The circuit breaker or the fuse must be sized according to the power supply input power rating and any local or national electrical code requirements Power supply output e 1350 W maximum 48 to 60 VDC with one DC input capacity e 2700 W maximum 48 to 60 VDC with two DC inputs Catalyst 6500 Series Switches Installation Guide PA32 OL 5781 07 Appendix A Power Supply Specifications 2700 W AC Input and DC Input Power Supplies Table A 22 2700 W DC Input Power Supply Specifications continued Specification Description Power supply output e
51. land CAB AC 16A AUS AU20S3 16 A 250 VAC Figure A 45 People s Republic of China CAB AC16A CH GB16C 16 A 250 VAC Figure A 37 Continental Europe CAB AC 2500W EU CEE 7 7 16 A 250 VAC Figure A 41 International CAB AC 2500W INT IEC 309 16 A 250 VAC Figure A 42 Israel CAB AC 2500W ISRL SI16S3 16 A 250 VAC Figure A 34 Italy CAB 7513ACI CEI 23 16 7 16 A 250 VAC Figure A 35 Japan North America CAB AC 2500W US l NEMA 6 20 16 A 250 VAC Figure A 43 200 240 VAC operation nonlocking plug Japan North America CAB AC C6K TWLK NEMA L6 20 16 A 250 VAC Figure A 44 200 240 VAC operation locking plug Japan North America CAB 7513AC NEMA 5 20 20 A 125 VAC Figure A 36 100 120 VAC operation Power Distribution Unit CAB C19 CBN IEC 60320 C19 16 A 250 VAC Figure A 46 1 PDU IEC 60320 C20 South Africa CAB 7513ACSA IEC 884 1 16 A 250 VAC Figure A 38 Switzerland CAB ACS 16 SEV 5934 2 Type 23 16 A 250 VAC Figure A 45 1 The PDU power cable is designed for users who power their switch from a PDU The end of the cable that plugs into the Catalyst 6500 series switch chassis has a C19 connector the other end of the cable that plugs into the PDU has a C20 connector OL 5781 07 Catalyst 6500 Series Switches Installation Guide Appendix A Power Supply Specifications HI 3000W AC Input Power Supply 3000 W AC Input Power Supply The 3000 W AC input power supply WS CAC 3000W is supported in the following Catalyst 6
52. lation Guide Appendix A Power Supply Specifications W 8700W AC Input Power Supply 8700 W Power Supply AC Power Cords Table A 41 lists the specifications for the AC power cords that are available for the 8700 W AC input power supply Included in the table are references to illustrations of the power cords Table A 41 8700 W Power Supply AC Power Cords Locale Power Cord AC Source Plug Type Cordset Rating Power Cord Part Number Reference Illustration Argentina CAB 7513ACR or IRAM 2073 16 A 250 VAC Figure A 31 CAB IR2073 C19 AR Australia New Zealand CAB AC 16A AUS AU20S3 16 A 250 VAC Figure A 46 People s Republic of China CAB AC16A CH GB16C 16 A 250 VAC Figure A 37 Continental Europe CAB AC 2500W EU CEE 7 7 16 A 250 VAC Figure A 41 International CAB AC 2500W INT IEC 309 16 A 250 VAC Figure A 42 Israel CAB AC 2500W ISRL SI16S3 16 A 250 VAC Figure A 34 Italy CAB 7513ACI CEI 23 16 7 16 A 250 VAC Figure A 35 Japan North America CAB AC 2500W US l NEMA 6 20 16 A 250 VAC Figure A 43 nonlocking plug 200 240 VAC operation Japan North America CAB AC C6K TWLK NEMA L6 20 16 A 250 VAC Figure A 44 locking plug 200 240 VAC operation Japan North America CAB 7513AC NEMA 5 20 16 A 125 VAC Figure A 36 100 120 VAC operation Power Distribution Unit CAB C19 CBN IEC 60320 C19 16 A 250 VAC Figure A 47 2 PDU IEC 60320 C20 Switzerland CAB ACS 16 SEV 5934 2 Type 23 16 A 250 VAC Figure A 45 1 When
53. ld be used as the sizing criteria for both UPS outputs as well as standard circuits and transformers to power a switch Table A 29 list the specification for the 4000 W DC input power supply I OL 5781 07 Catalyst 6500 Series Switches Installation Guide Appendix A Power Supply Specifications Hi 4000W AC Input and DC Input Power Supplies Table A 29 4000 W DC Input Power Supply Specifications Specification Description DC input voltage e 48 VDC 37 A for nominal 48 V battery backup system operating range 40 5 VDC to 56 VDC e 60 VDC 29 A for nominal 60 V battery backup system operating range 55 VDC to 72 VDC Note The 4000 W DC input power supply requires two source DC inputs to be connected it cannot operate with only one positive negative source DC terminal pair installed DC input current 40 A per each DC input three inputs Note For multiple DC input power supplies each DC input must be protected by a dedicated circuit breaker or a fuse The circuit breaker or the fuse must be sized according to the power supply input power rating and any local or national electrical code requirements Power supply output capacity e 4000 W with three inputs active e 2700 W with two inputs active Note The 4000 W power supply cannot operate with only one source DC input connected Power supply output e 15A 3 3 VDC e SA 5 VDC e 12A 12 VDC e 90 63 A three input
54. lies WS CAC 4000W US WS CAC 4000W INT and PWR 4000 DC are supported in the following Catalyst 6500 series switches e Catalyst 6506 e Catalyst 6506 E e Catalyst 6509 e Catalyst 6509 E e Catalyst 6509 NEB e Catalyst 6509 NEB A e Catalyst 6509 V E e Catalyst 6513 The 4000 W AC input and DC input power supplies shown in Figure A 14 and Figure A 15 share the same form factor as the 1000 W 1300 W 2500 W and 3000 W power supplies Figure A 14 4000 W AC Input Power Supply Catalyst 6500 Series Switches Installation Guide OL 5781 07 m Appendix A Power Supply Specifications HI 4000 W AC Input and DC Input Power Supplies Figure A 15 4000 W DC Input Power Supply 4000 W Power Supply Specifications Table A 29 lists the specifications for the 4000 W AC input power supply Table A 28 4000 W AC Input Power Supply Specifications Specification Description AC input type High line input with power factor correction PFC Note Power factor correction is a standard feature on all Catalyst 6500 series AC input power supplies PFC reduces the reactive component in the source AC current allowing higher power factors typically 99 percent or better and lower harmonic current components AC input voltage High line 230 VAC nominal 170 VAC min to 264 VAC max AC input current 23 A AC input frequency 50 60 Hz nominal 3 for full range Catalyst 6500 Series Switches Installation Guide A
55. m with the following combinations of power cords and source AC voltage applied to the power supply inputs e Two AC inputs are connected to high line 220 VAC nominal the third AC input is connected to low line 110 VAC nominal e Two AC inputs are connected to high line 220 VAC nominal the third AC input is not connected 8700 W maximum with the following combinations of power cords and source AC voltage applied to the power supply inputs e All three AC inputs are connected to high line 220 VAC nominal I OL 5781 07 Catalyst 6500 Series Switches Installation Guide r Appendix A Power Supply Specifications W 8700W AC Input Power Supply Table A 38 8700 W AC Input Power Supply Specifications continued Specification Description Power supply output e 2800 W operation 25 0A 3 3 VDC 12 0 A 12 VDC 61 29 A 42 VDC e 4200 W operation 25 0A 3 3 VDC 12 0 A 12 VDC 94 62 A 42 VDC e 5800 W operation 25 0 A 3 3 VDC 12 0 A 12 VDC 132 71 A 42 VDC e 8700 W operation 25 0 A 3 3 VDC 12 0 A 12 VDC 201 75 A 42 VDC Output holdup time 20 ms minimum kVA rating 10 4 KVA Heat dissipation e 11 200 BTU hour 2800 W e 16 800 BTU hour 4200 W e 23 200 BTU hour 5800 W e 34 800 BTU hour 8700 W System power dissipation 10 360 W Weight 39 7 lb 18 kg 1 The kVA rating listed for the power supply should be used as the sizing
56. ompatibility Matrix S Table A 1 Catalyst 6500 Series Power Supplies continued Power Supply AC Input Model DC Input Model Rating Product Number Product Number 4000 W WS CAC 4000W US 1 PWR 4000 DC WS CAC 4000W INT 6000 W WS CAC 6000W PWR 6000 DC 8700 W WS CAC 8700W E Not Available 1 For use with the Catalyst 6503 and Catalyst 6503 E switches only 2 For use with the Catalyst 6504 E switch only Note amp The Catalyst 6500 series switches allow you to mix AC input and DC input power supplies in the same chassis Note Many telco organizations require a 48 VDC power supply to accommodate their power distribution systems From an operational perspective the DC input power supply has the same characteristics as the AC input version Power Supply Compatibility Matrix Table A 2 lists the compatibility of the power supplies with the Catalyst 6500 switch chassis Table A 2 Catalyst 6500 Series Switch Supported Power Supply Configurations Platform Supported Power Supplies Chassis Power Supply Restrictions Catalyst 6503 e 950 W AC input and DC input e The 950 W AC input power e 1400 W AC input supply requires a PEM 15A AC Power Entry Module PEM e The 1400 W AC input power supply requires a PEM 20A AC Power Entry Module PEM Catalyst 6503 E e 950 W AC input and DC input e The 950 W AC input power e 1400 W AC input supply requires a PEM 15A AC Power Entry Module PEM e The 1400
57. output AC input frequency 50 60 Hz nominal 3 for full range Catalyst 6500 Series Switches Installation Guide cmd Appendix A Power Supply Specifications 2500 W AC Input and DC Input Power Supplies W Table A 17 2500 W AC Input Power Supply Specifications continued Specification Description Branch circuit requirement Each chassis power supply should have its own dedicated fused branch circuit e For North America 20 A e For International Circuits sized to local and national codes e All AC power supply inputs are fully isolated Source AC can be out of phase between multiple power supplies in the same chassis which means that PS1 can be operating from phase A and PS2 can be operating from phase B For high line operation the power supply operates with the hot conductor wired to a source AC phase and the neutral conductor wired either to ground or to another source AC phase as long as the net input voltage is in the range of 170 to 264 VAC Source AC can be out of phase between AC inputs on power supplies that are equipped with multiple AC inputs which means that power cord 1 can be plugged into phase A and power cord 2 can be plugged into phase B Power supply output e 1300 W maximum 100 120 VAC cape e 2500 W maximum 200 240 VAC Power supply output e 100 120 VAC operation 15 5 A 3 3 VDC 5A 5 VDC 10A 12 VDC 27 5 A 42 VDC e 200 240 VAC operation 15A
58. ower Supply Specifications continued Specification Description Power supply output The 6000 W DC input power supply can operate at either 2800 W 4500 W or 6000 W depending on the number of source DC power cables attached Note The 6000 W DC input power supply is limited to 4000 W maximum output when it is installed in a Catalyst 6506 Catalyst 6509 or Catalyst 6509 NEB switch chassis The power supply is limited to 4500 W maximum output when it is installed in the Catalyst 6509 NEB A switch chassis e 2800 W operation two DC inputs 25 0 A 3 3 VDC 12 0A 12 VDC 61 2 A 42 VDC e 4500 W operation three DC inputs 25 0A 3 3 VDC 12 0A 12 VDC 101 9A 42 VDC e 6000 W operation four DC inputs 25 0A 3 3 VDC 12 0 A 12 VDC 137 4 A 42 VDC DC input terminal block e Accepts 2 hole copper compression type lugs Note The actual size of the wire needed is determined by the power engineer or local electrician in accordance with national or local electrical codes e Terminal posts accept 1 4 inch 20 hex nuts Output holdup time 20 ms minimum Weight 35 lbs 16 kg Table A 35 list the 6000 W AC input and DC input power supply LEDs and their meanings Catalyst 6500 Series Switches Installation Guide OL 5781 07 Appendix A Power Supply Specifications Table A 35 6000 W AC Input and DC Input Power Supplies W 6000 W AC Input and DC Input Power Suppl
59. pply Specifications 6000 W AC Input and DC Input Power Supplies W Table A 33 6000 W AC Input Power Supply Specifications continued Specification Description Branch circuit requirement Each power supply input should have its own dedicated fused branch circuit e For North America 20 A e For International Circuits should be sized according to local and national codes e All Catalyst 6500 series AC input power supplies require single phase source AC e All AC power supply inputs are fully isolated Source AC can be out of phase between multiple power supplies in the same chassis which means that PS1 can be operating from phase A and PS2 can be operating from phase B For high line operation the power supply operates with the hot conductor wired to a source AC phase and the neutral conductor wired either to ground or to another source AC phase as long as the net input voltage is in the range of 170 to 264 VAC Source AC can be out of phase between AC inputs on power supplies that are equipped with multiple AC inputs which means that power cord 1 can be plugged into phase A and power cord 2 can be plugged into phase B OL 5781 07 Catalyst 6500 Series Switches Installation Guide Appendix A Power Supply Specifications W 6000W AC Input and DC Input Power Supplies Table A 33 6000 W AC Input Power Supply Specifications continued Specification Description Power su
60. pply output capacity The 6000 W power supply can operate at either 2900 W or 6000 W depending on the number of AC power cords attached and the source AC voltage Note The 6000 W AC input power supply is limited to 4000 W maximum output when it is installed in a Catalyst 6506 Catalyst 6509 or Catalyst 6509 NEB switch chassis The power supply is limited to 4500 W maximum output when it is installed in the Catalyst 6509 NEB A switch chassis e 2900 W maximum with the following source AC arrangements INPUT 1 and INPUT 2 both connected to low line 120 VAC nominal INPUT connected to high line 230 VAC nominal INPUT 2 not connected INPUT 1 not connected INPUT 2 connected to high line 230 VAC nominal INPUT connected to high line 230 VAC nominal INPUT 2 connected to low line 120 VAC nominal INPUT 1 connected to low line 120 VAC nominal INPUT 2 connected to high line 230 VAC nominal e 6000 W maximum with the following source AC arrangements INPUT 1 and INPUT 2 both connected to high line 230 VAC nominal Note The 6000 W power supply will not power up if you have only one power cord plugged into either INPUT 1 or INPUT 2 and source AC is low line 120 VAC nominal Catalyst 6500 Series Switches Installation Guide OL 5781 07 Appendix A Power Supply Specifications 6000 W AC Input and DC Input Power Supplies W Table A 33 6000 W AC Input Power Supply Spe
61. ralia New Zealand CAB AC 16A AUS AU20S3 16 A 250 VAC Figure A 46 People s Republic of China CAB AC16A CH GB16C 16 A 250 VAC Figure A 37 Continental Europe CAB AC 2500W EU CEE 7 7 16 A 250 VAC Figure A 41 International CAB AC 2500W INT IEC 309 16 A 250 VAC Figure A 42 Israel CAB AC 2500W ISRL SI16S3 16 A 250 VAC Figure A 34 Italy CAB 7513ACI CEI 23 16 7 16 A 250 VAC Figure A 35 Japan North America CAB AC 2500W US l NEMA 6 20 16 A 250 VAC Figure A 43 nonlocking plug 200 240 VAC operation Japan North America CAB AC C6K TWLK NEMA L6 20 16 A 250 VAC Figure A 44 locking plug 200 240 VAC operation Japan North America CAB 7513AC NEMA 5 20 20 A 125 VAC Figure A 36 100 120 VAC operation Power Distribution Unit CAB C19 CBN IEC 60320 C19 16 A 250 VAC Figure A 47 2 PDU IEC 60320 C20 Switzerland CAB ACS 16 SEV 5934 2 Type 23 16 A 250 VAC Figure A 45 1 The 3000 W power supply operating on 110 VAC delivers 1400 W 2 The PDU power cable is designed for users who power their switch from a PDU The end of the cable that plugs into the Catalyst 6500 series switch chassis has a C19 connector the other end of the cable that plugs into the PDU has a C20 connector Catalyst 6500 Series Switches Installation Guide OL 5781 07 AppendixA Power Supply Specifications 4000 W AC Input and DC Input Power Supplies W 4000 W AC Input and DC Input Power Supplies The 4000 W AC input and DC input power supp
62. re of the DC output voltages of the power supply Off DC output voltages within acceptable margins For proper operation of the OUTPUT FAIL LED systems with single power supplies must be configured with a minimum of one fan tray and one supervisor engine Systems with dual power supplies must have a minimum configuration of one fan tray one supervisor engine and one additional module Failure to meet these minimum configuration requirements can cause a false power supply output fail signal I OL 5781 07 Catalyst 6500 Series Switches Installation Guide A Appendix A Power Supply Specifications HX 6000W AC Input and DC Input Power Supplies 4000 W Power Supply AC Power Cords Table A 31 lists the specifications for the AC power cords that are available for the 4000 W AC input power supply Included in the table are references to illustrations of the power cords Table A 31 Locale International North America Japan amp Note The AC power cords for the 4000 W AC input power supply are hardwired directly to the power supply they do not have an IEC 60320 C19 appliance plug and cannot be removed from the power supply 4000 W Power Supply AC Power Cords Power Cord Part Number WS CAC 4000W INT WS CAC 4000W US AC Source Plug Type Cordset Rating Power Cord Reference Illustration IEC 60309 32 A 250 VAC Figure A 48 NEMA L6 307 30 A 250 VAC Figure A 49 1 This is the p
63. rent No change in the module status because the power capability is unchanged Catalyst 6500 Series Switches Installation Guide Power Supply Specifications OL 5781 07 Appendix A Power Supply Specifications Power Supply Redundancy W Table A 43 Effects of Power Supply Configuration Changes continued Configuration Change Effect Equal wattage power e System log and syslog messages are generated supply is inserted with e System power is the combined power capability of both supplies redundancy disabled e The modules marked as power deny in the show module Status field are brought up if there is sufficient power Higher wattage power e System log and syslog messages are generated supply is inserted with e The system disables the lower wattage power supply the redundancy enabled higher wattage supply powers the system Catalyst operating system e For Cisco IOS both power supplies come on The total available wattage is the output wattage of the higher wattage power supply Lower wattage power e System log and syslog messages are generated supply is inserted with e The system disables the lower wattage power supply the redundancy enabled higher wattage supply powers the system Catalyst operating system e For Cisco IOS both power supplies come on The total available wattage is the output wattage of the higher wattage power supply Higher or lower wattage e System log
64. s Table A 16 lists the specifications for the AC power cords that are available for the 1400 W AC input power supply These power cords plug into the 1400 W PEM PEM 20A AC not directly into the power supply The table includes references to power cord illustrations amp Note amp All 1400 W power supply power cords are 14 feet 4 3 meters in length Note All 1400 W power supply power cords have an IEC60320 C19 appliance plug at one end OL 5781 07 Catalyst 6500 Series Switches Installation Guide E Appendix A Power Supply Specifications His 1400 W AC Input Power Supply Table A 16 1400 W Power Supply AC Power Cords Locale Power Cord AC Source Plug Type Cordset Rating Power Cord Part Number Reference Illustration Argentina CAB 7513ACR IRAM 2073 16 A 250 VAC Figure A 31 CAB IR2073 C19 AR Australia New Zealand CAB 7513ACA SAA AS 3112 15 A 250 VAC Figure A 32 People s Republic of CAB AC16A CH GB16C 16 A 250 VAC Figure A 37 China Continental Europe CAB 7513ACE CEE 7 7 16 A 250 VAC Figure A 33 CAB AC 2500W EU CEE 7 7 16 A 250 VAC Figure A 41 International CAB AC 2500W INT IEC 309 16 A 250 VAC Figure A 42 Israel CAB AC 2500W ISRL S116S3 16 A 250 VAC Figure A 34 Italy CAB 7513ACI CEI 23 16 7 16 A 250 VAC Figure A 35 Japan North America CAB 7513AC NEMA 5 20 20 A 125 VAC Figure A 36 CAB AC 2500W US l NEMA 6 202 16 A 250 VAC Figure A 43 CAB AC C6K
65. s or 59 68 A two inputs 42 VDC Note The 4000 W power supply cannot operate with only one source DC input connected DC input terminal block Accepts 4 AWG copper conductors Actual size of the wire needed is determined by the installer or local electrician Output holdup time 8 ms kVA rating 5 4 kVA maximum Heat dissipation 17 730 BTU hour approx Weight 30 8 Ib 14 0 kg 1 The kVA rating listed for the power supply should be used as the sizing criteria for both UPS outputs as well as standard circuits and transformers to power a switch Table A 30 lists the power supply LEDs and their meanings Catalyst 6500 Series Switches Installation Guide OL 5781 07 Appendix A Power Supply Specifications Table A 30 LED 4000 W AC Input and DC Input Power Supplies 4000 W AC Input and DC Input Power Supplies LEDs INPUT OK DC AC input power supplies Green Source AC voltage is OK Input voltage is 85 VAC or greater Off Source AC voltage falls below 70 VAC is not present or the power supply is turned off input power supplies Green Source DC voltage is OK Input voltage is 40 5 VDC or greater Off Source DC voltage falls below 33 VDC is not present or the power supply is turned off FAN OK Green Power supply fan is operating properly Off Power supply fan failure is detected OUTPUT FAIL Note Red Problem with one or mo
66. s are summarized in Table A 43 Note amp For proper load sharing operation in a redundant power supply configuration you must install two modules in the chassis If you fail to install two modules you might receive spurious OUTPUT FAIL indications on the power supply Note In systems that have two different sized power supplies installed you may not have true redundancy If the larger wattage power supply fails the smaller wattage power supply might not be able to handle the entire load by itself OL 5781 07 Catalyst 6500 Series Switches Installation Guide jg Appendix A W Power Supply Redundancy Table A 42 If you have two Power Supply Redundancy Then and redundancy is power supplies of Equal wattage Enabled The total power drawn from both supplies is never greater than the capability of one supply If one supply malfunctions the other supply can take over the entire system load Each power supply provides approximately half of the required power to the system Load sharing and redundancy are enabled automatically no software configuration is required Unequal wattage Enabled Both power supplies initially come online For the Catalyst operating system if the difference between the two power supply s output wattage is less than 10 percent of the higher output wattage power supply redundancy is enabled If the difference is greater than 10 percent the lesser wattag
67. supply fan is operating properly e Off Power supply fan failure is detected OUTPUT FAIL e Red Problem with one or more of the DC output voltages of the power supply e Off DC output voltages within acceptable margins Note For proper operation of the OUTPUT FAIL LED systems with single power supplies must be configured with a minimum of one fan tray and one supervisor engine Systems with dual power supplies must have a minimum configuration of one fan tray one supervisor engine and one additional module Failure to meet these minimum configuration requirements can cause a false power supply output fail signal Catalyst 6500 Series Switches Installation Guide OL 5781 07 Appendix A Power Supply Specifications 2700 W AC Input and DC Input Power Supplies W 2700 W Power Supply AC Power Cords Table A 24 lists the specifications for the AC power cords that are available for the 2700 W AC input power supply The table includes references to power cord illustrations amp Note All 2700 W power supply power cords are 14 feet 4 3 meters in length amp Note All 2700 W power supply power cords have an IEC60320 C19 appliance connector at one end Table A 24 2700 W Power Supply AC Power Cords Locale Power Cord AC Source Plug Type Cordset Rating Power Cord Part Number Reference Illustration Argentina CAB 7513ACR or IRAM 2073 16 A 250 VAC Figure A 31 CAB IR2073 C19 AR Australia New Zea
68. t e 16A 120 VAC e 8A 230 VAC AC input frequency 50 60 Hz nominal 3 Hz for full range Branch circuit requirement Each chassis power supply should have its own dedicated fused branch circuit e For North America 15 A or 20 A e For International Circuits sized to local and national codes e All Catalyst 6500 series AC input power supplies require single phase source AC e All AC power supply inputs are fully isolated Source AC can be out of phase between multiple power supplies in the same chassis which means that PS1 can be operating from phase A and PS2 can be operating from phase B For high line operation the power supply operates with the hot conductor wired to a source AC phase and the neutral conductor wired either to ground or to another source AC phase as long as the net input voltage is in the range of 170 to 264 VAC Source AC can be out of phase between AC inputs on power supplies that are equipped with multiple AC inputs which means that power cord 1 can be plugged into phase A and power cord 2 can be plugged into phase B Power supply output capacity e 1300 W maximum AC input e 1360 W maximum DC input Power supply output e 15 A 43 3 VDC e SA 5 VDC e 6A 12 VDC e 27 46 A 42 VDC Output holdup time 20 ms minimum OL 5781 07 Catalyst 6500 Series Switches Installation Guide Appendix A Power Supply Specifications W 1300W
69. t TAE Appendix A Power Supply Specifications 4000 W AC Input and DC Input Power Supplies W Table A 28 4000 W AC Input Power Supply Specifications continued Specification Description Branch circuit requirement Each chassis power supply should have its own dedicated fused branch circuit e For North America 30 A e For International Circuits should be sized according to local and national codes e All AC power supply inputs are fully isolated Source AC can be out of phase between multiple power supplies in the same chassis which means that PS1 can be operating from phase A and PS2 can be operating from phase B For high line operation the power supply operates with the hot conductor wired to a source AC phase and the neutral conductor wired either to ground or to another source AC phase as long as the net input voltage is in the range of 170 to 264 VAC Source AC can be out of phase between AC inputs on power supplies that are equipped with multiple AC inputs which means that power cord 1 can be plugged into phase A and power cord 2 can be plugged into phase B Output capacity 4000 W maximum Power supply output e 15 A 43 3 VDC e SA 5 VDC e 10A 12 VDC e 90 36 A 42 VDC Output holdup time 20 ms minimum kVA rating 5 4 kVA maximum Heat dissipation 17 065 BTU hour approx Weight 22 2 Ib 10 1 kg 1 The kVA rating listed for the power supply shou
70. tem will power down modules in descending order starting with the highest numbered slot Slots containing supervisor engines or Switch Fabric Modules are bypassed and are not powered down This shut down order is fixed and cannot be changed You can change the configuration of the power supplies to redundant or combined at any time If you switch from a redundant to a combined configuration both power supplies are enabled even a power supply that was disabled because it was of a lower wattage than the other power supply If you change from a combined to a redundant configuration both power supplies are initially enabled and if they are of the same wattage they remain enabled If they are of different wattage a syslog message displays and the lower wattage supply is disabled For additional information about the power management feature and individual module power consumption refer to your software configuration guide OL 5781 07 Catalyst 6500 Series Switches Installation Guide Hl Appendix A Power Supply Specifications W Power Supply Redundancy Catalyst 6500 Series Switches Installation Guide n78 E OL 5781 07
71. th one or more of the DC output voltages of the power supply e Off DC output voltages within acceptable margins Note For proper operation of the OUTPUT FAIL LED systems with single power supplies must be configured with a minimum of one fan tray and one supervisor engine Systems with dual power supplies must have a minimum configuration of one fan tray one supervisor engine and one additional module Failure to meet these minimum configuration requirements can cause a false power supply output fail signal 42V OK e Green 42 VDC is present at the fan power connector e Off 42 VDC is not present at the fan power connector Catalyst 6500 Series Switches Installation Guide OL 5781 07 EN Appendix A Power Supply Specifications HI 3000W AC Input Power Supply 3000 W Power Supply AC Power Cords Table A 27 lists the specifications for the AC power cords that are available for the 3000 W AC input power supply The table includes references to power cord illustrations amp Note All 3000 W power supply power cords are 14 feet 4 3 meters in length amp Note All 3000 W power supply power cords have an IEC60320 C19 appliance connector at one end Table A 27 3000 W Power Supply AC Power Cords Locale Power Cord AC Source Plug Type Cordset Rating Power Cord Part Number Reference Illustration Argentina CAB 7513ACR or IRAM 2073 16 A 250 VAC Figure A 31 CAB IR2073 C19 AR Aust
72. y LEDs LED INPUT OK 1 and INPUT OK 2 AC input power supply only Green Source voltage is OK Input voltage is 85 VAC or greater Off Source AC voltage falls below 70 VAC is not present or the power supply is turned off INPUT OK 1 INPUT OK 2 INPUT OK 3 and INPUT OK 4 DC input power supply only Green Source DC voltage is greater than or equal to 40 5 VDC Off Source DC voltage is less than or equal to 37 5 VDC Green off or flashing Source DC voltage is between 37 5 and 40 5 VDC FAN OK e Green Power supply fan is operating properly e Off Power supply fan failure is detected OUTPUT FAIL e Red Problem with one or more of the DC output voltages of the Note power supply Off DC output voltages within acceptable margins For proper operation of the OUTPUT FAIL LED systems with single power supplies must be configured with a minimum of one fan tray and one supervisor engine Systems with dual power supplies must have a minimum configuration of one fan tray one supervisor engine and one additional module Failure to meet these minimum configuration requirements can cause a false power supply output fail signal 6000 W Power Supply AC Power Cords Table A 36 lists the specifications for the AC power cords that are available for the 6000 W AC input power supply Included in the table are references to illustrations of the power cords Table
73. y Specifications HI 8700W AC Input Power Supply Table A 38 8700 W AC Input Power Supply Specifications continued Specification Description AC input current 16 A each input AC input frequency 50 60 Hz nominal 3 for full range Branch circuit requirement Each power supply input should have its own dedicated fused branch circuit e For North America 20 A e For International Circuits should be sized according to local and national codes e All Catalyst 6500 series AC input power supplies require single phase source AC e All AC power supply inputs are fully isolated This means that source AC can be out of phase between multiple AC inputs on the same power supply or different AC power supplies that are installed in the same chassis For the 8700 W power supply this means that power cord 1 can be plugged into phases A B power cord 2 can be plugged into phases B C and power cord 3 can be plugged into phases C A A B or B C Catalyst 6500 Series Switches Installation Guide nse E OL 5781 07 Appendix A Power Supply Specifications 8700 W AC Input Power Supply W Table A 38 8700 W AC Input Power Supply Specifications continued Specification Description Power supply output capacity 2800 W operation 4200 W operation 5800 W operation 8700 W operation The power supply output capacity is dependent on the number of AC power cords 1 2 or 3 attached and the source A

Download Pdf Manuals

image

Related Search

Related Contents

IOSERVE - N0GSG - No-IP    RFID-200 : système d`information et numérique    Eminent TV Tuner Card PCI  Operating Instructions - Support  manual de instalación y mantenimiento para controlador  Supporting Early Intervention Programmes for special  Samsung MM-J5 Manual de Usuario  Shure SM48 Microphone User Guide  