Home
FSP/Fortron Knight KN-1103TS Tower
Contents
1. Parameter 1 It s for program alternatives There are 8 programs to set up Refer to below table Parameter 2 and parameter 3 are the setting options or values for each program Parameter 2 Parameter 3 01 Output voltage setting Parameter 3 Output voltage For 200 208 220 230 240 VAC models you may choose the following output voltage 200 presents output voltage is 200Vac 208 presents output voltage is 208Vac 220 presents output voltage is 220Vac 230 presents output voltage is 230Vac 240 presents output voltage is 240Vac For 100 110 115 120 127 VAC models you may choose the following output voltage 100 presents output voltage is 100Vac 110 presents output voltage is 110Vac 115 presents output voltage is 115Vac 120 presents output voltage is 120Vac 127 presents output voltage is 127Vac 02 Frequency Converter enable disable Parameter 2 amp 3 Enable or disable converter mode You may choose the following two options CF ENA converter mode enable CF DIS converter mode disable Parameter 2 amp 3 Output frequency setting You may set the initial frequency on battery mode BAT 50 presents output frequency is 50Hz BAT 60 presents output frequency is 60Hz If converter mode is enabled you may choose the following output frequency CF 50 presents output frequency is 50Hz CF 60 presents output frequency is 60Hz Parameter 3 Enable or disable ECO function You may choo
2. 1K 2K 3K Online UPS Uninterruptible Power Supply System Table of Contents i Important sate War EE 1 tek eeler del E 1 1 2 PREDATION WT 1 SAIAS ll UI EE 1 ee O DEV ALION eege ege 1 1 5 Maintenance Service and faults ccceceseseseseceeeceeeceueeeeeeeuueeuauauaeavavavavavavavavavaravars 2 2 Installation and SCLUD ET 3 e REAL DAN ENEE 3 EE d ODEON EE 6 3 1 fl gelubeile EC el NEE 6 Be CCB PING E 6 325 AUCIDIC Alani aano naan namie Mansi anrr onai 8 Ee ECD dS y WOrGINGS ln el EE 8 JD UPS SEINO EE 8 3 6 Operating Mode Description kk NNN KN KKNKNENKRN NK KRN NEEN KREE N REN KN KNK NENNEN ENNEN EN 11 3 7 Faults Reference Code c scssssccessecessececereeceusecarseeauseeuneeauseeeesuusesaueesaueesausesarsess 11 3 38 ig te bie e te EEN 12 4 FOUDIGSNOOUING WT 13 De DLO age aC Malte aN G O sassictioosvesdaaaeisidsnesvesataanasadinnseuatusansuainensteniaaae E 15 O SPCCINICAL OMS EE E 16 1 Important Safety Warning Please comply with all warnings and operating instructions in this manual strictly Save this manual properly and read carefully the following instructions before installing the unit Do not operate this unit before reading through all safety information and operating instructions carefully 1 1 Transportation Please transport the UPS system only in the original package to protect against shock and impact 1 2 Preparation Condensation may occur if the UPS system is moved directly from cold to wa
3. 5 section Mute operation Indicates that the UPS alarm is disabled Output amp Battery voltage information COOC vac Indicates the output voltage frequency or battery voltage A ds LC Vac output voltage Vdc battery voltage Hz frequency Indicates the load level by 0 25 26 50 51 75 and 76 100 WU AD Indicates overload SHORT Indicates the load or the UPS output is short circuit Mode operation information Indicates the UPS connects to the mains Indicates the battery is working Indicates the bypass circuit is working Indicates the ECO mode is enabled Indicates the Inverter circuit is working Indicates the output is working Battery information Indicates the Battery level by 0 25 26 50 51 75 and 76 100 mam ou Indicates the battery is fault LOW BATT Indicates low battery level and low battery voltage Input amp Battery voltage information ei Li H Vde Indicates the input voltage or frequency or battery voltage a PS Vac Input voltage Vdc battery voltage Hz input frequency 3 3 Audible Alarm Battery Mode Low Battery Bypass Mode 3 4 LCD display wordings index Abbreviation Display content Meaning mr J ia E mr Ai EZE ren Im FAT Enable Disable Escape High loss Low loss re e OF Dim ee o Battery Converter TP CH 3 5 UPS Setting Temperature m X Charger There are three parameters to set up the Parameter 1 UPS
4. sounding every 10 second Standby mode UPS is powered off and no output supply o power but still can charge batteries 3 7 Faults Reference Code Fault event Battery voltage too high Over temperature Inverter soft start fail Inverter voltage high 12 x 11 3 8 Warning indicator Sounding every second Over Charge Over temperature Sounding every second Charger failure Loi Sounding every second Out of bypass voltage range Sounding every second 12 4 Troubleshooting If the UPS system does not operate EE please solve the problem by T e the table below Symptom No indication and alarm even though the mains is normal The icon Aand flashing on LCD display and alarm is sounding every second Fault code is shown as 27 and the icon is lighting on LCD display and alarm is continuously sounding Fault code is shown as 28 and the icon is lighting on LCD display and alarm is continuously sounding The icon A and over LOAD flashing on LCD display and alarm is sounding twice every second Fault code is shown as 43 and The icon is lighting on LCD display and alarm is continuously sounding Fault code is shown as 14 and the icon is lighting on LCD display and alarm is continuously sounding Fault code is shown as 01 02 03 04 11 12 13 and 41 on LCD display and alarm is continuously sounding Possible cause cause The external or internal battery is incorre
5. 0 300 VAC 5 290 VAC 5 OUTPUT 200 208 220 230 240VAC 1 Batt Mode 47 53 Hz or 57 63 Hz 50 Hz 0 25 Hz or 60Hz 0 3 Hz 3 1 2 THD Linear Load lt 4 THD Non linear Load Output voltage C Voltage Regulation Frequency Range Synchronized Range requency Range Batt Mode urrent Crest Ratio Harmonic Distortion IA Zero Time 4 ms Typical EFFICIENCY BATTERY Numbers J 3 6 8 6 Sg 1 0 A max Amex i O 82 1 VDC 109 4VDC 82 1 VDC 109 4VDC 0 Charging Voltage 41 0VDC 1 S 1 1 1 Depending on the capacity of external batteries Battery Type amp ben a Numbers Mo Ge EE Current 1 0A 2 0A 4 0A 6 0 A 82 1 VDC 109 4VDC 82 1 VDC 109 4VDC o PHYSICAL Model 419 X 190 X 318 mm Model ENVIRONMENT Less than 45dBA 1 Meter MANAGEMENT Derate capacity to 80 of capacity in Frequency converter mode or when the output voltage is adjusted to 208VAC 200VAC Product specifications are subject to change without further notice
6. If the problem still persists consult your dealer Batteries defect Contact your dealer to replace the battery Fault code is shown as 05 on LCD A UPS internal fault has Consult your dealer If the display At the same time alarm is occurred and BUS is short UPS power is on again continuously sounding and output circuit before repair the DC DC is cut off mosfet will damage 14 5 Storage and Maintenance Operation The UPS system contains no user serviceable parts If the battery service life 3 5 years at 25 C ambient temperature has been exceeded the batteries must be replaced In this case please contact your dealer Be sure to deliver the spent battery to a recycling facility or ship it to your dealer in the replacement battery packing material Storage Before storing charge the UPS 5 hours Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance with the following table Storage Temperature Recharge Frequency Charging Duration 25 C 40 C Every 3 months 40 C 45 C Every 2 months 15 6 Specifications CAPACITY 1000 VA 800 W 2000 VA 1600 W 3000 VA 2400 W INPUT 160VAC 140VAC 120VAC 110VAC45 based on load percentage 100 80 80 70 70 60 60 0 Low Line Transfer Voltage 168VAC 148VAC 128VAC 118VAC 5 Range based on load percentage 100 80 80 70 70 60 60
7. ctly connected Battery voltage is too high or the charger is fault Battery voltage is too low or the charger is fault UPS is overloaded Devices connected to the UPS are fed directly by the electrical network via the Bypass After repetitive overloads the UPS is locked in the Bypass mode Connected devices are fed directly by the mains The UPS shut down automatically because of overload at the UPS output The UPS shut down automatically because Short circuit occurs on the UPS output A UPS internal fault has occurred There are two possible results 1 The load is still supplied but directly from AC power via bypass 2 The load is no longer supplied by power 13 Remedy connected well firmly connected to the mains The AC input is connected Plug AC input power cord to to the UPS output AC input correctly Check if all batteries are connected well Contact your dealer Contact your dealer UPS is overload Remove excess loads from UPS output Remove excess loads from UPS output Remove excess loads from UPS output first Then shut down the UPS and restart it Remove excess loads from UPS output and restart it Check output wiring and if connected devices are in short circuit status Contact your dealer Symptom Battery backup time is shorter Batteries are not fully Charge the batteries for at than nominal value charged least 5 hours and then check capacity
8. into a two pole three wire grounded receptacle only Avoid using extension cords The power cord is supplied in the UPS package Step 2 UPS output connection For socket type outputs simply connect devices to the outlets For terminal type input or outputs please follow below steps for the wiring configuration a Remove the small cover of the terminal block b Suggest using AWG14 or 2 1mm power cords c Upon completion of the wiring configuration please check whether the wires are securely affixed d Put the small cover back to the rear panel Step 3 Communication connection Communication port USB port RS 232 port Intelligent slot ofze To allow for unattended UPS shutdown start up and status monitoring connect the communication cable one end to the USB RS 232 port and the other to the communication port of your PC With the monitoring software installed you can schedule UPS shutdown start up and monitor UPS status through PC The UPS is equipped with intelligent slot perfect for either SNMP or AS400 card When installing either SNMP or AS400 card in the UPS it will provide advanced communication and monitoring options PS USB port and RS 232 port can t work at the same time Step 4 Turn on the UPS Press the ON Mute button on the front panel for two seconds to power on the UPS Note The battery charges fully during the first five hours of normal operation Do not expect full battery run capability during thi
9. ode UPS will be in standby mode under power normal or transfer to Bypass mode if the Bypass enable setting by pressing this button Confirm selection key Press this button to confirm selection in UPS setting mode Switch LCD message Press this button to change the LCD message for input voltage input frequency battery voltage output voltage and output frequency It will return back to default display when pausing for 10 seconds Setting mode Press and hold this button for 5 seconds to enter UPS setting mode when UPS is in standby mode or bypass mode Down key Press this button to display next selection in UPS setting mode Switch to bypass mode When the main power is normal press ON Mute Select ON Mute and Select buttons simultaneously for 5 seconds Then UPS Button will enter to bypass mode This action will be ineffective when the input voltage is out of acceptable range ON Mute Button OFF Enter Button Select Button 3 2 LCD Panel Remaining Backup Time Info Fault Info Input amp Battery Mute Operation Doacti 7 BATT ol Battery Info a Ga BEN E v Mode Operation Info Display Remaining backup time information Indicates the remaining backup time in pie chart a LI CI Indicates the remaining backup time in numbers sl EAE j H hours M minute S second Fault information Indicates that the warning and fault occurs Indicates the warning and fault codes and the codes are listed in details in 3
10. rm environment The UPS system must be absolutely dry before being installed Please allow at least two hours for the UPS system to acclimate the environment Do not install the UPS system near water or in moist environments Do not install the UPS system where it would be exposed to direct sunlight or near heater Do not block ventilation holes in the UPS housing 1 3 Installation Do not connect appliances or devices which would overload the UPS system e g laser printers to the UPS output sockets Place cables in such a way that no one can step on or trip over them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to the UPS system Please use only VDE tested CE marked mains cable e g the mains cable of your computer to connect the UPS system to the building wiring outlet shockproof outlet Please use only VDE tested CE marked power cables to connect the loads to the UPS system When installing the equipment it should ensure that the sum of the leakage current of the UPS and the connected devices does not exceed 3 5mA 1 4 Operation Do not disconnect the mains cable on the UPS system or the building wiring outlet shockproof socket outlet during operations since this would cancel the protective earthing of the UPS sy
11. s initial charge period Step 5 Install software For optimal computer system protection install UPS monitoring software to fully configure UPS shutdown You may insert provided CD into CD ROM to install the monitoring software If not please follow steps below to download and install monitoring software from the internet 1 Go to the website http www power software download com 2 Click ViewPower software icon and then choose your required OS to download the software 3 Follow the on screen instructions to install the software 4 When your computer restarts the monitoring software will appear as an orange plug icon located in the system tray near the clock Step 6 External battery connection for long run models only Follow the right chart to make external battery connection 3 Operations 3 1 Button operation gt Turn on the UPS Press and hold ON Mute button for at least 2 seconds to turn on the UPS Mute the alarm When the UPS is on battery mode press and hold this button for at least 5 seconds to disable or enable the alarm system But its not applied to the situations when warnings or errors occur Up key Press this button to display previous selection in UPS setting mode Switch to UPS self test mode Press and hold ON Mute button for 5 seconds to enter UPS self testing while in AC mode ECO mode or converter mode Turn off the UPS Press and hold this button at least 2 seconds to turn off the UPS in battery m
12. se the following two options ENA ECO mode enable DIS ECO mode disable Parameter 2 amp 3 Set the acceptable high voltage point and low voltage point for ECO mode by pressing Down key or Up key HLS High loss voltage in ECO mode in parameter 2 For 200 208 220 230 240 VAC models the setting range in parameter 3 is from 7V to 24V of the nominal voltage For 100 110 115 120 127 VAC models the setting range in parameter 3 is from 3V to 12V of the nominal voltage LLS Low loss voltage in ECO mode in parameter 2 For 200 208 220 230 240 VAC models the setting range in parameter 3 is from 7V to 24V of the nominal voltage For 100 110 115 120 127 VAC models the setting voltage in parameter 3 is from 3V to 12V of the nominal voltage 06 Bypass enable disable when UPS is off Parameter 3 Enable or disable Bypass function You may choose the following two options ENA Bypass enable DIS Bypass disable Parameter 2 amp 3 Set the acceptable high voltage point and acceptable low voltage point for Bypass mode by pressing the Down key or Up key HLS Bypass high voltage point For 200 208 220 230 240 VAC models 230 264 setting the high voltage point in parameter 3 from 230Vac to 264Vac For 100 110 115 120 127 VAC models 120 132 setting the high voltage point in parameter 3 from 120Vac to 132Vac LLS Bypass low voltage point For 200 208 220 230 240 VAC models 170 220 setting the low voltage poin
13. stem and of all connected loads The UPS system features its own internal current source batteries The UPS output sockets or output terminals block may be electrically live even if the UPS system is not connected to the building wiring outlet In order to fully disconnect the UPS system first press the OFF Enter button to disconnect the mains Prevent no fluids or other foreign objects from inside of the UPS system 1 5 Maintenance service and faults The UPS system operates with hazardous voltages Repairs may be carried out only by qualified maintenance personnel Caution risk of electric shock Even after the unit is disconnected from the mains building wiring outlet components inside the UPS system are still connected to the battery and electrically live and dangerous Before carrying out any kind of service and or maintenance disconnect the batteries and verify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS capacitors Only persons are adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the ground Before touching please verify that no voltage is present Ba
14. t in parameter 3 from 170Vac to 220Vac For 100 110 115 120 127 VAC models 85 115 setting the low voltage point in parameter 3 from 85Vac to 115Vac 8 Backup time setting for outlets Parameter 3 Set up backup time on battery mode for o e OO z general outlets l OP 0 999 setting the backup time in minutes from 0 999 for 999 general outlets on battery mode m 0 When setting as 0 the backup time will be only 10 seconds 999 When setting as 999 the backup time setting will be disabled 00 Exit setting 10 3 6 Operating Mode Description Operating mode LCD display Online mode When the input voltage is within acceptable range UPS will provide pure and stable AC power to output The UPS will also charge the battery at online mode ECO mode Energy saving mode When the input voltage is within voltage regulation range UPS will bypass voltage to output for energy saving Frequency When input frequency is within 40 Hz to Converter mode 70 Hz the UPS can be set at a constant output frequency 50 Hz or 60 Hz The UPS will still charge battery under this mode Battery mode When the input voltage is beyond the acceptable range or power failure and alarm is sounding every 4 second UPS will backup power from battery Bypass mode When input voltage is within acceptable range but UPS is overload UPS will enter bypass mode or bypass mode can be set by front panel Alarm is
15. tteries may cause electric shock and have a high short circuit current Please take the precautionary measures specified below and any other measures necessary when working with batteries remove wristwatches rings and other metal objects use only tools with insulated grips and handles When changing batteries install the same number and same type of batteries Do not attempt to dispose of batteries by burning them This could cause battery explosion Do not open or destroy batteries Escaping electrolyte can cause injury to the skin and eyes It may be toxic Please replace the fuse only with the same type and amperage in order to avoid fire hazards Do not dismantle the UPS system 2 Installation and setup NOTE Before installation please inspect the unit Be sure that nothing inside the package is damaged Please keep the original package in a safe place for future use NOTE There are two different types of online UPS standard and long run models Please refer to the following model table ik Standard Long run 3KL 2 1 Rear panel view 1K L IEC 2K L IEC 3K L IEC AC input Input circuit breaker USB communication port RS 232 communication port SNMP intelligent slot External battery connection only available for L model Output receptacles NN OF OFF BR W RN e 8 Output circuit breaker 9 Output terminal 2 2 Setup the UPS Step 1 UPS input connection Plug the UPS
Download Pdf Manuals
Related Search
Related Contents
FINEPIX XP150/XP160, FINEPIX XP100/XP110 vestax_spin2_bedienungsanleitung (link is - Dj SureTemp Plus ÿþM icrosoft W ord - @wP0‰0 0¸„úQW0†›±}. doc mdsp resolution enhancement software user`s manual 1 Robic M417 User's Manual Sony BW-RU101 Computer Drive User Manual Spin Master Twin Thunder Motorized Toy Car User Manual Manuale installazione AVEbus この商品は海外では使用できません。 Copyright © All rights reserved.
Failed to retrieve file