Ever Sinline XL, 2 x 4 x 9Ah
Contents
1. PARAMETERS SINLINE XL SINLINE XL SINLINE XL UPS TYPE 1800 2200 3000 Output power 1800VA 2200VA 3000VA 1260W 1540W 2100W Working environment Office or industrial rooms with low level of pollution Operating temperature 10 gt 35 Storage temperature 0 45 Relative humidity for operation 20 80 without condensation Relative humidity for storage 20 95 without condensation Altitude above sea level up to 1000 m Maximum length of outgoing cables lt 10m MAINS OPERATION MODE Input voltage 7150 280 V 160 265 V 2 Frequency of input voltage 45 55 Hz 1 Hz Range of output voltage A 7172 280 V 7184 265 V 2 Switching thresholds Mains UPS 150 170 V 160 V 255 280 V 265 V 2 Shape of output voltage Same as input Filtering of output voltage Noise filter RFI EMI varistor damper 100 80 50 P max Time to switch to UPS lt 3 ms BACK UP BATTERY OPERATION MODE Output voltage effective value 230 V15 Shape of output voltage Sinus Switching thresholds UPS mains 7 155 175 V 165 V 250 275 V 260 V 12 Frequency of output voltage 50Hz 1 Hz Filtering of output voltage LC Shorting safeguard Electronic Overload safeguard Electronic Time to switch back to mains operation 0 ms Support time with internal batter
2. N be turned off with the power switch located on the front panel WARNING During the first charging of batteries the UPS must not Turning the UPS off may lead to incorrect display of its parameters later on Disconnecting the module 1 Turn the UPS off with the power switch located on the front panel and disconnect it from the mains by removing the power cord plug from the mains socket Disconnect the battery module from the UPS 3 Secure the connector by replacing the protective stopper 4 Connect the UPS to the mains and then turn it on with the power switch on the front panel Configure the number of battery modules in the PowerSoft programme in the case of no modules set the parameter to 0 After the batteries are charged the UPS is ready for operation 2010 01 27 www ever eu 13 SINLINE XL series UPS Instruction Manual EVER MANAGEMENT CARD The Ever management card is an optional component that may be installed by the user Installing the card renders the communication via RS232 and USB impossible Installing themanagement card Tower and Rack Models 1 Turn the UPS off with the power switch on the front panel and disconnect it from the mains by removing the power cord plug from the mains socket 2 Remove the screws holding the cover of the card slot and remove the cover Fig 6a 3 Connect the cable located in the opening to the card Fig 6b c 4 Slide the car
3. 2010 01 27 www ever eu For normal operation of the UPS the load connected to its output should not exceed 80 of value indicated in the table Reserve power is essential to ensure 30 SINLINE XL series UPS Instruction Manual TECHNICAL PARAMETERS Rack Model PARAMETERS SINLINE XL SINLINE XL SINLINE XL UPS TYPE 1800 19 Rack 3U 2200 19 Rack 3U 3000 19 Rack 3U Output power 1800VA 2200VA 3000VA 1260W 1540W 2100W Working environment Office or industrial rooms with low level of pollution Operating temperature 10 35 Storage temperature 0 45 Relative humidity for operation 20 80 without condensation Relative humidity for storage 20 95 without condensation Altitude above sea level up to 1000 m Maximum length of outgoing cables lt 10m MAINS OPERATION MODE Input voltage 150 280 V 160 265 V 2 Frequency of input voltage 45 55 Hz 1 Hz Range of output voltage 3 172 280 V 184 265 V 42 Switching thresholds Mains UPS 150 170 V 160 V 255 280 V 265 V 2 Shape of output voltage Same as input Filtering of output voltage Noise filter RFI EMI varistor damper Time to switch to UPS lt 3 ms BACK UP BATTERY OPERATION MODE Output voltage effective value 230 V 5 Shape of output voltage Sinus
4. SN NI R A z HE 2 2 pe oE P TN S CORRECT PE LOAD POWER SUPPLY INCORRECT Fig 10 Output installation of the UPS The arrangement of terminals of output sockets of the UPS is presented on Fig 11 Fig 11 Arrangement of terminals of output sockets 2010 01 27 www ever eu 17 SINLINE XL series UPS Instruction Manual FIRST START WARNING The UPS may only be connected to a 230V mains N socket eduipped with a grounding bolt Electric installation of the building to which the back up is connected must be protected against overloads and shorting After unpacking place the device in the chosen location and connect it to the mains in order to charge the internal batteries Charging time of batteries can be found in the technical parameters table Afterwards the user may continue with the installation procedure Take the following steps e Turn the UPS off with the power switch on the front panel only if it was turned on e connect the devices that require buffer power supply e g computer and monitor to the outlet sockets on the UPS e connect the UPS to the computer if using RS232 e turn on the UPS with the switch on the front panel e turn on the devices connected to the UPS e install the monitoring software on the control computer see chapter Installation of the PowerSoft softw
5. the equipment will cause the UPS to shut down This happens because the powered equipment temporarily draws power that significantly exceeds the nominal power 2010 01 27 www ever eu 27 SINLINE XL series UPS Instruction Manual of the UPS which causes an overload detection and consequently a shutdown This situation may occur in the case of Television sets and monitors as they are switched on the picture tube is degaussed which temporarily requires a lot of power Laser printers drum warming cycle Other products with similar operating features Therefore if a UPS is to be used with equipment other than computers its compatibility with equipment used must be verified In order to do this all devices should be connected to the UPS and its operation should be observed in all modes i e start up shutdown stand by etc UPS AND POWER GENERATORS SINLINE XL UPSs are LINE INTERACTIVE VI class devices synchronising with the mains voltage By design the UPS tolerates mains voltage variations in the range of 160 264V basic range or 150 280V enhanced range as well as frequency variations of 5Hz with relation to the nominal frequency of 50Hz When connected to a power generator the frequency variations change over time and are strictly dependent on changes of load levels If the frequency variations of a power generator s voltage exceed the allowed tolerance range the UPS will consider such frequen
6. ydele ON APE EE EE EN N EE RE N 22 COMMUNICATION BETWEEN THE UPS AND THE COMPUTER esse sees se ee se ee se ee se ee se ee se ese ee ee ee ee 23 COMMUNICATION VIA RS232 OR USB ou ee see eee ee eee se ee ee ee Ge aaa Re Ge RA Re ee ee Ge ee ee ee ee 23 INSTALLATION AND CONFIGURATION OF THE POWERSOFT PERSONAL SOFTWARE 23 EVER SNMP HTTP NETWORK management card sees se esse esse ese ee ee see ee ee ee ee eke Gee Gee be ee ee ee ee 26 CONFIGURING THE UPS S PARAMETERS ees esse esse esse ese ese see ee ese see see ee ee ee ee ese ee se ese ee ee ee ee 27 ADDITIONAL REMARKS Ge e EE EE N EE AE EE 27 UPS ANDPOWER GENERATOR eertse saa Gresse ge See ee svete eens doi Gegee onesie LP gebede Ee 28 USING THE TELECOMMUNICATIONS FILTER esse esse esse esse ese see ee ke ee i ee ee ee ee ee ee ee ee be ee se ee ee ee see ee 28 USING THE LAN FILTER e OR EE EO EE N OE ER pau evens N 28 STORAGE MAINTENANCE AND TRANSPORT ese ee see ee ee ee ee se ee se ee se ese ee ee ee ke Se ke ee eed Gee ee ee 29 DISPOSAE pzd ER NO EE OE EA EE EE EEEREN 29 TECHNICAL PARAMETERS Tower Model sees sees se esse esse ese ee se esse ee se ese ee ee ke ee ee EE ee ee ee ee ee ee S 30 TECHNICAL PARAMETERS Rack Model see see see e ee se esse esse ee se ee ee ee Re Ge Re E Gee bee se ee ee ee ee 31 INFORMATION REGARDING REGULATIONS AND WARRANTY 00 sees sees se ee se ee se ee se esse ee ese ee ee 32 DECLARATION OF CONFORMITY eee ee ee ee
7. KANE Z AM Y Fixed handle y Fixed handle Fig 5 SINLINE RACK 19 Top Wiew 1 WARNING The device must not be installed in the proxmity of flammable materials THE BATTERY MODULE SINLINE XL UPSs have the option of connecting an additional battery module For this the special connector located on the rear panel is used Connecting a battery module extends the time of battery operation mode The battery module is protected by an additional cut out located inside the module Replacement of cut outs should be conducted only by a qualified representative of the technical support WARNING The given model of UPS may only be enhanced with N battery modules recommended by the manufacturer see Technical parameters 2010 01 27 www ever eu 12 SINLINE XL series UPS Instruction Manual Connecting the module 1 Turn the UPS off with the power switch located on the front panel and disconnect it from the mains by removing the power cord plug from the mains socket Remove the stopper covering the connector rear panel Connect the battery module to the UPS 4 Connect the UPS to the mains and then turn it on with the power switch on the front panel Configure the number of battery modules in the PowerSoft programme for SINLINE XL the maximum number is 1 After the batteries are charged the UPS is ready for operation
8. Switching thresholds UPS mains 79 155 175 V 165 V 250 275 V 260 V 2 Frequency of output voltage 50Hz 1 Hz Filtering of output voltage LC Shorting safeguard Electronic Overload safeguard Electronic Time to switch back to mains operation 0 ms Support time with internal batteries only 7185119 min 547 15min 4 5 9min 100 80 50 P max Support time with battery module installed 100 80 50 P max 28 48 81 min 25 34 65 min 17 24 46 min Battery 4x VRLA 12V 9 Ah Additional modules 2x 4x VRLA 12V 9 Ah Maximum charging time of internal batteries 3h Maximum charging time of internal batteries battery module 12h MECHANICAL PARAMETERS Dimensions h x w x d 3U x 19 x 400 mm UPS weight 39 kg Battery module weight 38 kg EQUIPMENT Outlet sockets 6 x IEC320 C13 Signalling Acoustic and visual Cut out Circuit breaker 15 A Telecommunications filter Available LAN filter Available Communication interface RS232 USB SNMP HTTP networkmanagement card optional Note The manufacturer reserves the right to change the abovementioned parameters without prior notice Notes 1 N S R o ME 2 For normal operation of the UPS the load connected to its output should not exceed 80 of value indicated in the table Reserve power is essential to ensure continuous operation of connected devices in case of mome
9. and following the instructions onscreen As the driver s location you should indicate the PowerSoft installation folder usually C Program Files PowerSoft To uninstall PowerSoft select the Uninstall PowerSoft option in Start Menu You can also uninstall PowerSoft from the Add and remove programs menu in the control panel Installation on computers with Linux Unix The binary version of the application for Linux Unix systems is provided in the following formats CentOS RedHat Suse Linux Fedora Core For the CentOS RedHat Suse Linux and Fedora Core systems the software is provided in the form of a RPM package The software can be installed by using any package manage available for the system installed If you are using the command line the software will be installed by entering the following command rpm ivh PowerSoftpersonal x x x i386 rom Users working with the PowerSoft must have root privileges to install the software and use it After installation the application may be found in the usr local PowerSoft directory To uninstall the application enter the following command rpm ev PowerSoftpersonal x x x 2010 01 27 www ever eu 24 SINLINE XL series UPS Instruction Manual Debian For Debian systems the software is provided in the form of a DEB package The software is installed via the following command dpkg install PowerSoftpersonal x x x deb To uninstall the application enter the followin
10. ee ee 11 INSTALLATION OF THE UPS Rack Model sees sees se esse ee se ese ee ee see ee ke ee See Gee Gee Ge ee ee ee ee see ee 11 THE BATTERY MODULE NE i CO AAAA es Rodin aah See ea aed 12 Connecting the module st ae ROER RE See EL eden ee eae A een aude Soe ae aa eee 13 Disconnecting the mod le sege Boece eek vet ecu heel eects essa ee OTOP es eas tans tes ee gastos es oes 13 EVER MANAGEMENT CARD 2 se z R Ee A ease O Z EAT 14 Installing themanagement card Tower and Rack Models e2 e ee aaa oaza Ge ee ee 14 Installing themanagement Card oo sees ee ee ee Se Se Ge Ge GRA GR Ge aan ee ee 15 CONNECTING THE UPS EE BESEER Ail eee Ee Ge Ge RE De Ds WE VER ee ek ees au Rae ea 15 Input installato ss EN EE EE Dee De W be Se Ee eens tes date nents ee Ee De RE WE eee a Ro DEER 16 Output inst lla oi ss ss Sei Ee A el cokes A se WE ER Gee te DE EER eee Gee EIA 17 FIRST START sp a EE EE ER EE OE SENEN S TEESE ETE CEE ESE EErEE sy 18 DESCRIPTION OF THE BACK UP S OPERATION esse ese esse ese ese ee see ee ee ee ee ee ee ene ee ee ee ee ese ee se ee ee ee ke ee 19 GENERAL INFORMATION ER EE N OR RE EE ER IE OE E Trs 19 MAINS OPERATION MODE eise use sa oe Ge OO Gee Ge ee Bee oe Ge ee noe apts se gee ee oe ee Vee Gee ene ek gebed A 20 BACK UP BATTERY OPERATION MODE ees sees sees se es se esse ee se ese ee ee ee ee ge ee ee ee ee eke Gee Gee be ee ee ee ee 20 STAND BY MODE EEN ER EE N N RE OE N 21 EMERGENCY MODE ME OE EE N 21
11. installation of the UPS it is crucial to familiarise yourself with the health amp safety measures provided in gt gt gt gt the previous chapter UNPACKING Please inspect the UPS upon receipt Although the product is packed very carefully it could have sustained damage from shock during transport Should you find any damages please inform the carrier or seller immediately A N WARNING The device is delivered with its battery connected 2010 01 27 www ever eu 10 SINLINE XL series UPS Instruction Manual Check the contents of the packaging The packaging should contain e the UPS e a CD ROM with the PowerSoft software and complete instruction manual e quick reference guide e communication cable to connect the back up to a computer via RS232 e communication cable to connect the back up to a computer via USB e 2 outlet power cords e warranty card e 2 moving handles for cabinet installation Rack Model only INSTALLATION OF THE UPS Tower Model When choosing the installation location you must take the device s weight into account The back up should only be used in rooms whose dustiness temperature and moisture levels conform with the device s specification To ensure correct operation of the back up appropriate cooling conditions for the device must be provided For this reason the ventilation openings on the back up s case must be uncovered and the distan
12. into the alternating current to power the protected devices MAINS OPERATION MODE Connecting the UPS to the mains does not cause current to appear at the back up s output UPS batteries are not charged either The UPS is turned on upon pressing the power switch on the front panel Switching on is accompanied by the operation mode LED lighting in red and then after approximately 3 seconds a sound signal Subsequently all LEDs on the front panel light up so their correct operation can be verified autotest Next the UPS will attempt synchronisation with the mains If the mains voltage of the socket to which the back up s power cord is connected is appropriate then after approximately 5 seconds the UPS switches to the mains operation mode and lights the green operation mode LED If the mains voltage is incorrect too low or too high voltage or frequency exceeding the operation range the UPS switches to the back up operation mode and lights the red operation mode LED In the mains operation mode the UPS s outlet provides mains voltage that was filtered and optionally raised by the AVR system BACK UP BATTERY OPERATION MODE In the back up operation mode the true sine wave voltage output is generated by the battery until the mains voltage returns the battery is discharged or an emergency situation takes place When operating in the back up mode if the batteries are discharged or the appropriate command from the control software is
13. mains voltage to remove the noise and distortions that may be dangerous for the receivers The dedicated DPC system monitors the operation of the UPS it has a precise and very quick reacting system of detecting overloads and outlet shorting in the back up operation mode In mains operation mode the shorting safeguard is provided by a cut out and overloads are signalled both visually and acoustically When the UPS is started in the back up operation mode a special soft start mode is used in order to launch with high loads that draw high starting current e g laser printers Moreover the DPC system enables long operation in battery mode by allowing connection of an additional battery module and control of internal temperature by means of an active cooling system which is activated as necessary This manner of switching on the cooling reduces the amount of noise generated by the UPS The DPC system offers various modes of communication between the UPS and the computer via a communication port or a special slot for the Ever management card HTTP telnet SNMP 2010 01 27 www ever eu 19 SINLINE XL series UPS Instruction Manual This UPS utilises an innovative charging method reserved only for the most advanced UPSs CBC COOL BATTERY CHARGING which utilises the elements of an internal inverter During the mains operation mode it charges the batteries and in the back up operation mode it converts the internal energy of the battery
14. systems compatible with the application is available at www ever eu just run the software installer and follow the instructions onscreen During the installation you will be asked to select the model of the UPS connected to the computer on which the software is being installed This setting may also be changed when the application is running 2010 01 27 www ever eu 23 SINLINE XL series UPS Instruction Manual In the case of a UPS connected to the computer via a USB cable when the software installation is complete the PowerSoft Personal installer will ask the user to connect the USB cable to the computer The system will announce that a new device has been found and will propose to install the drivers Select the option to install the drivers from a chosen location and on the next screen indicate the installation folder of the PowerSoft programme usually C Program Files PowerSoft to be searched Next the operating system will locate and install the appropriate driver In the case of Windows Vista the operating system will not initiate automatic installation of the drivers from the hard drive After connecting the USB cable to the computer you will need to open the control panel from the Start Menu and select system properties On the device tree displayed find the USB bus branch in most cases it will be already expanded and select the UPS Update the device s driver from it s Properties window by right clicking it in the list
15. 0 01 27 www ever eu SINLINE XL series UPS Instruction Manual ELEMENTS OF THE SINLINE XL UPS Rack Model FRONT PANEL Fig 3 Front panel 1 Circuit breaker After the circuit breaker is triggered the reason for shorting should be removed and the breaker pressed back in to be activated 2 Power switch 3 Two colour LED indicating the operating mode a Mains operation mode constant green light b Battery operation mode constant red light blinking red LED indicates that a flat battery must be changed 4 LED indicating whether the AVR Automatic Voltage Regulation system is active 5 LEDs indicating the available battery capacity O O O OQ Available battery capacity maximum battery capacity obtainable at the current gt 20 gt 45 gt 80 gt 95 UPS load The upper line of green LEDs indicates the charge level of batteries 6 LEDs indicating the load level The lower line of green LEDs indicates the O O O LI percentage load level of the UPS in both the E gt 5 gt 30 gt 60 gt 85 mains and battery operation mode If the last 2010 01 27 www ever eu SINLINE XL series UPS Instruction Manual LED is lit in red and the UPS is emitting a continous sound signal this indicates that the UPS has overloaded However if the red LED is blinking and the UPS is emitting a quick intermittent signal this indic
16. ains power factor value of the active power and apparent power connected to the back up s output output power factor presence of the battery module connected to the UPS e AVR Automatic Voltage Regulation automatic mains voltage regulation system e Filtering of the mains voltage e Telecommunications and LAN filter e RS232 serial port and a USB port for communication with a PC e Upgrade card slot e g management card e he possibility of connecting an additional battery module e Archiving and storage of data pertaining to the UPS S OPERATION e Calculation of currently available time of battery operation mode e PowerSoft software to monitor the operating parameters of the back up and shut down the system automatically 2010 01 27 www ever eu SINLINE XL series UPS Instruction Manual ELEMENTS OF THE SINLINE XL UPS Tower Model FRONT PANEL IN N w i ln Fig 1 Front panel 1 LEDs indicating the available battery capacity 2 Power switch 3 LED indicating whether the AVR Automatic Voltage Regulation system is active 4 Two colour LED indicating the operating mode a Mains operation mode constant green light b Battery operation mode constant red light blinking red LED indicates that a flat battery must be changed 5 LEDs indicating the load level Available battery capacity maximum battery capacity obtainable at the cur
17. any modifications made by the user Apart from the arrangements included in the warranty card EVER Sp z o o shall not grant any guarantee or warranty including warranty of merchantability or fitness for particular purpose Apart from the arrangements included in the warranty card EVER Sp z o o shall not be liable for direct indirect specific incidental or consequential losses incurred in the course of using the UPS even in cases when the buyer was warned about such losses being a possibility The company shall not be liable for any costs such as loss of profit or revenue cost of equipment costs of equipment use costs of software data replacement products claims of third parties or other costs 2010 01 27 www ever eu 32
18. are e connect the UPS to the computer if using USB With all of the above actions complete the UPS is ready for operation 1 WARNING Back up s batteries reach their full capacity after approximately a month of mains operating mode 2010 01 27 www ever eu 18 SINLINE XL series UPS Instruction Manual DESCRIPTION OF THE BACK UP S OPERATION GENERAL INFORMATION The SINLINE XL UPS is a state of the art electronic device constituting an autonomous source of true sine wave voltage of 230V This device belongs to the group of LINE INTERACTIVE VI class UPSs which includes UPSs that synchronise with the mains The UPS is equipped with the CLEAR DIGITAL SINUS CDS system which generates a precisely stabilised output voltage in the shape of sinusoid which enables supplying power to a wide range of equipment that does not tolerate quasi sine wave voltages This system increases the reliability of the device and guarantees stable operation of the UPS With the help of the Automatic Voltage Regulation AVR system the UPS instantly corrects slight drops in the mains voltage to provide the receivers with appropriate power supply conditions without tapping into the energy reserves stored in the batteries The back up also uses the system of advanced DIGITAL POWER CONTROL DPC which precisely shapes the oscillation of the output voltage to obtain a clear sinus In the mains operating mode the system filters the
19. ates a shorting at the back up s output If the UPS malfunctions it switches off automatically The reason for shutdown is indicated by the combination of LEDs lit see Description of the UPSS OPERATION REAR PANEL Fig 4 Rear panel Telecommunications filter LAN filter USB port for communication with a PC RS232 serial port for communication with a PC 5 Stopper for the upgrade card opening internal upgrade card slot Outlet sockets Stopper for the external battery module socket Fan Mains power cord 2010 01 27 www ever eu SINLINE XL series UPS Instruction Manual HEALTH AND SAFETY INSTRUCTIONS HANDLING exercise utmost caution when handling the device do not handle heavy equipment by yourself lt 18 kg 18 32 kg E storage and operation of the device should take place in conditions conforming to its specification ELECTRIC SAFETY Never work alone in conditions that may be hazardous to health and or life Even a momentary shorting of a strong current may lead to severe burns Prior to connecting the device to the mains inspect the condition of power cords plugs and sockets as well as the condition of the device itself To minimise the risk of electric shock in cases when there is no way of verifying the earthing the device should be disconnected from the mains before installation or connection of other equipment to the back up reconnect the powe
20. automatically even when there are no devices connected to the outlet sockets so they may even power devices with extremely low power consumption Load power of this UPS is limited only at the upper extreme and the overload status is communicated visually acoustically and via the PC software monitoring the device Unlike quasi sine wave UPSs the SINLINE XL series back ups may power devices with induction motors WARNING SINLINE XL UPSs were not designed to work with N medical equipment in particular life and or health support devices It is not recommended to use this UPS to power TVs laser printers and other similar devices that draw greater impulse power than the back up is capable of providing 2010 01 27 www ever eu SINLINE XL series UPS Instruction Manual GENERAL FEATURES OF THE UPS e Output true sine wave also generated in battery operating mode e DPC digital control of operating parameters of the back up such as shape of the output voltage frequency of the output voltage charge level of batteries voltage and current of batteries measurement of battery set capacity displayed on the front panel battery life temperature of essential parts of the UPS e Digital monitoring of external parameters such as value of the mains voltage value of the mains current frequency of the mains voltage value of active power and apparent power drawn from the mains m
21. ce between the back up and other objects should be at least 10 cm INSTALLATION OF THE UPS Rack Model When choosing the installation location you must take the device s weight into account The strength of the supporting cabinet rack is essential The back up should only be used in rooms whose dustiness temperature and moisture levels conform with the device s specification To ensure correct operation of the back up appropriate cooling conditions for the device must be provided For this reason the ventilation openings on the back up s case must be uncovered and the distance between the back up and other objects should be at least 10 cm The back up is designed for installation in a cabinet rack In order to facilitate installation in cabinets racks of various depth the device is equipped with moving handles which enable installation in racks with depth of up to 700 mm If the back up is to be installed in a rack of 900 mm or 1000 mm depth it is possible to order longer handles to adjust the product for installation in such a rack To install the UPS take the following steps 2010 01 27 www ever eu 11 SINLINE XL series UPS Instruction Manual 1 Install the moving handles in the back section of the cabinet 2 Supporting the back up s base with hand slide UPS onto the previously installed handles 3 Screw the front fixed handles of the UPS to the rack s frame Moving handles max 700mm a SX KONNA
22. cy to be incorect and switch to battery operation mode USING THE TELECOMMUNICATIONS FILTER In order to protect the telephone line and connected devices such as modems or telephones the SINLINE XL UPSs are equipped with an anti overvoltage filter which safeguards the devices connected against overvoltages in the telephone line If the filter is to safeguard the devices correctly they must be connected with a cable with RJ11 or RJ12 terminators The existing telephone line should be connected to the other outlet socket of the filter The filter is symmetrical so it does not matter to which of the two sockets the telephone line is connected USING THE LAN FILTER In order to protect the ETHERNET UTP line and connected devices the SINLINE XL UPSs are equipped with an anti overvoltage filter which safeguards the devices connected against overvoltages If the filter is to safeguard the devices correctly they 2010 01 27 www ever eu 28 SINLINE XL series UPS Instruction Manual must be connected with a cable with RJ45 terminators The existing ETHERNET UTP line should be connected to the other outlet socket of the filter The filter is symmetrical so it does not matter to which of the two sockets the ETHERNET UTP line is connected STORAGE MAINTENANCE AND TRANSPORT The UPS should be stored in a cool and dry place in operating position with batteries fully charged e n temperatures between OC and 30 the batter
23. d into the slot Fig 6d 5 Replace the screws fixing the card to the rear panel Fig 6e Fig 6 Installation of the management card Tower Model 2010 01 27 www ever eu 14 SINLINE XL series UPS Instruction Manual Installing themanagement card 1 Turn the UPS off with the power switch on the front panel and disconnect it from the mains by removing the power cord plug from the mains socket 2 Remove the screws holding the cover of the card slot and remove the cover Fig 7a 3 Connect the cable located in the opening to the card Fig 7b 4 Slide the card into the slot Fig 7c 5 Replace the screws fixing the card to the rear panel Fig 7d a gt BE Fig 7 Installation of themanagement card Rack Model CONNECTING THE UPS The mains socket the UPS is to be connected to should be located near the back up maximum distance 1 5 m and should be easily accessible Do not use additional extension cords to connect the device to the mains WARNING The UPS is disconnected from the mains only when the power cord is removed from its socket 2010 01 27 www ever eu 15 SINLINE XL series UPS Instruction Manual Due to the type and placement of cut outs present in the UPS the safety circuits of the building function as one of the protection measures This is essential to provide the UPS with shorting protection Prot
24. ection parameters of the buildings installations should be adjusted according to the type and size of load connected to the installation Differing characteristics of protections of installations in the building and the UPS may in extreme cases lead to quicker responses of the former Input installation To connect the UPS in accordance with the instruction manual the layout of terminals of the mains socket is important see Fig 8 PE Fig 8 Layout of terminals of a mains socket Fig 9 presents the ways of correctly connecting the UPS to different types of mains TN S or TN C S that vary with regard to the manner of earthing Lg bl urs L 5 z z L z INPUT OUTPUT z e S z POWER SUPPLY siea a LURS JE L a a N 5 SN 5 eed z z s N a z z o a gE PE o PE 6 7 TN C S LOAD Fig 9 Input installation of the UPS 2010 01 27 www ever eu 16 SINLINE XL series UPS Instruction Manual mains configuration WARNING The output side of the back up only allows the TN S Output installation Even though the input side allows both types of terminals the output installation arranged inconsistently with this instruction may damage the UPS The scheme of correctly arranged output connections is presented in Fig 10 PE si gl UPS a E E
25. g command dpkg remove PowerSoft FreeBSD For FreeBSD systems the software is provided in the form of the default package format designed for FreeBSD systems The software is installed via the following command pkg_add PowerSoftpersonal x x x tbz To uninstall the application enter the following command pkg_delete PowerSoft WARNING FreeBSD systems do not support communication with N the UPS via the USB cable Starting the software When the installation is complete the system service is started automatically while the control panel application can be found at usr local PowerSoft Please note that for the Polish diacritics to be correctly displayed the system locale should be Polish Software Updates Windows systems The software installer for Windows systems has a buil in automatic updater PowerSoft can regularly check for new software versions and notify the user when updates are available By default the software checks for updates after the user logs in This setting can be changed under the Update configuration tab in the system s program menu 2010 01 27 www ever eu 25 SINLINE XL series UPS Instruction Manual Linux Unix systems In the case of Linux Unix systems PowerSoft can be updated by downloading the new package from www ever eu In the case of CentOS RedHat Suse Linux and Fedora Core PowerSoft can be updated by entering the following command rom Uv PowerSoftli
26. given the UPS may switch to the battery stand by mode 2010 01 27 www ever eu 20 SINLINE XL series UPS Instruction Manual STAND BY MODE The UPS switches to STAND BY mode when the batteries are completely discharged or when it receives an appopriate command from the control software The UPS will wait for the mains voltage of correct parameters to come back in order to return to the mains operation mode EMERGENCY MODE In this mode the UPS cuts the power from its outlets and signals all malfunctions and their origins The emergency mode is signalled with a sound and blinking of the red LED in the load column as well as appropriate combinations of lit LEDs in the battery charge column see Table 1 The UPS remains in emergency mode until switched off by the user or until the batteries are completely discharged Table 1 Error table ERROR TABLE Signalling Type of error Tower Rack OOO UPS connected incorrectly 9 5 0 O 00 Internal errors a combination of lit LEDs Q Q ES A 1 indicates various errors tz bed 1 Information for the tech support 2010 01 27 www ever eu 21 SINLINE XL series UPS Instruction Manual SAFEGUARDS Against overloads An overload is signalled by constant shining of the top LED red in the load indication column and a continuous sound signal If the UPS
27. ies only 7 18 5 19 min 547 115 min 4 15 9min Support time with battery module installed 100 80 50 Pmax 28 48 81 min 25 34 65 min 17 24 46 min Battery 4x VRLA 12V 9 Ah Additional modules 2x 4x VRLA 12V 9 Ah Maximum charging time of internal batteries 3h Maximum charging time of internal batteries battery module 12h MECHANICAL PARAMETERS Dimensions h x w x d 190 x 165 x 570 mm UPS weight 28 kg Battery module weight 27 kg EQUIPMENT Outlet sockets 6 x IEC320 C13 Signalling Acoustic and visual Cut out Circuit breaker 15 A Telecommunications filter Available LAN filter Available Communication interface RS232 USB SNMP HTTP networkmanagement card optional Note The manufacturer reserves the right to change the abovementioned parameters without prior notice Notes 1 continuous operation of connected devices in case of momentary rushes in load current N The User may modify the switching thresholds de RD ME ER SER Factory setting is provided in parentheses 2 Continued exposure of the UPS to the temperature of the surrounding exceeding 25 will shorten the life of batteries If the altitude above sea level increases beyond the provided limit the permitted load power of the batter back up decreases After discharging the UPS with power 80 Pmax charging the battery to 90 capacity
28. is operating in back up mode and the overload lasts longer than 10 seconds the UPS will switch to emergency operation mode Outlet sockets are disconnected from the power supply Against shorting In the mains operation mode the safeguard against shorting is provided by the cut outs located in the rear section of the UPS In the battery operation mode the electronic shorting safeguard reduces the short circuit current to a safe level by lowering the output voltage This is signalled by by the UPS by rapid blinking of the last LED red in the load indication column and a quick intermittent sound signal If the shorting lasts longer than 1 second the UPS will switch to the emergency operation mode Aqainst overvoltage The UPS is equipped with anti overvoltage safeguard at the input which protects the circuits of receivers and the internal circuits of the UPS against high energy current rushes caused by atmospheric phenomena and power grid disruptions Aqainst incorrect connection Incorrect connection of the UPS causes it to switch to emergency operation mode the moment it is switched on This is signalled by slow blinking of the last LED red in the load indication column and an intermittent sound signal mirroring the rate of blinking In addition the layout of lit LEDs in the battery charge level column indicates the type of error see the Error Table 2010 01 27 www ever eu 22 SINLINE XL series UPS Instruction Ma
29. ntary rushes in load current Continued exposure of the UPS to the temperature of the surrounding exceeding 25 will shorten the life of batteries If the altitude above sea level increases beyond the provided limit the permitted load power of the batter back up decreases The User may modify the switching thresholds Factory setting is provided in parentheses After discharging the UPS with power 80 Pmax charging the battery to 90 capacity 2010 01 27 www ever eu 31 SINLINE XL series UPS Instruction Manual INFORMATION REGARDING REGULATIONS AND WARRANTY DECLARATION OF CONFORMITY The UPS was manufactured in Poland and its structure conforms to appropriate subject matter standards WARRANTY A separate document attached to the product constitutes the warranty The document must meet all formal requirements e g the following fields must be populated serial number model type date of sale and dealer stamp The manufacturer made all efforts to ensure that products offered are free of material and workmanship defects throughout the term specified in the warranty document The company s liability under the warranty shall be limited to repairs or replacement of products with such defects The manufacturer shall make the decision as to how the defect is removed The warranty shall not cover devices with mechanical damages that occurred as a result of negligence of incorrect use nor devices subjected to
30. nual COMMUNICATION BETWEEN THE UPS AND THE COMPUTER COMMUNICATION VIA RS232 OR USB SINLINE XL series UPSs come with enhanced control features The UPS is delivered with a built in RS232 and USB communication port and the PowerSoft software package To ensure correct cooperation the UPS must be connected to the computer with the provided cable WARNING The communication connection between the UPS and the computer should be made only if the user intends to use the control software If the software is not installed while the connection is made then the RS232 or USB port may receive random conditions PNP or others which may lead to incorrect operation of the UPS WARNING Only one type of connection may be used at any given N time For Linux Unix and Novell systems only the RS232 communication is available INSTALLATION AND CONFIGURATION OF THE POWERSOFT PERSONAL SOFTWARE Installation on computers with Windows Prior to beginning the installation of PowerSoft e Uninstall the current version of PowerSoft or any other control software in situations where the user is changing the UPS protecting the computer e If the installed UPS communicates with the PC via a USB cable this cable should be initially disconnected from the computer The software installer will prompt the user to connect the communication cable at the appropriate time To install PowerSoft on a computer with Windows the list of operating
31. pa T INS EVER POWER SYSTEMS INSTRUCTION MANUAL SINLINE XL SINLINE XL RACK 3U EVER Sp z 0 0 ul Grudzi skiego 30 62 020 Swarz dz Poland www ever eu upsQever com pl tel 0048 61 6500 400 fax 0048 61 6510 927 SINLINE XL series UPS Instruction Manual TABLE OF CONTENTS INTRODUCTION EE EE EE A SE RE ES N 3 GENERAT INFORMA O N s i OOBE oo ves Res Re bana S Ee ee ee Sonesta GE Ee EE LO 3 PURPOSE OFTHE POWER SUPPLY SE Ee es Ge RE ge ees ER ste Ge eed O gee eg ees Bee ee Eb see ee ROSE 3 GENERAL EEATURES OF THE UPS EE eb Es SE ERGE A Ge Ee EEEE Eg ee boat estan ER Ese OO ini 4 ELEMENTS OF THE SINLINE XL UPS Tower Model esse sees sees se ee se ee se ee se ese ese aaa aaa ee ee ee ee ee ee ee ee se ee 3 FRONF PANE o a a OE Wi OO OT OC BOO T W 5 REAR PANELA ao n e ER E E EE OO E E TEE 6 ELEMENTS OF THE SINLINE XL UPS Rack Model iese esse esse esse ese see ee ee ee ee ee ee ee ee ee ee ee ee see ese ee ee ee ke ee ke ee 7 ld OASE RE RE N EE EE OE WE 7 REARPANEL VRAE EE EE EE EE OR EE 8 HEALTH AND SAFETY INSTRUCTIONS lt a ERGER ees eksegese es eg Ge Ee Tee EER EDE aves eg Ge EE Dek RD OE E O ee see see eg 9 HAND IN G RE EE EE EE EE OE EE RE 9 BEE CTRIC SA FED AE EE EE RE EE RR Soseteaees 9 INSTALLATION EER EE RE KERE DE 10 UNPACKING a RE ER OE EE OR EE EE EE EE 10 INSTALLATION OF THE UPS Tower Model ees sees sees se esse esse ese ese ee se see ee ke eed eke Gee Gee Ge ee ee
32. r cord only after all connections are made To avoid the risk of electric shock when connecting and disconnecting signal cables and touching two surfaces with differing electric potential if possible use only one hand The device must be plugged in to a three lead sockets two poles and earthing connecting the device to any other socket may result in electric shock The device receiving the current must be connected with an appropriate circuit protection manual cut out or circuit breaker 2010 01 27 www ever eu SINLINE XL series UPS Instruction Manual e A device powered via a cord with a plug has an earthing lead that carries away the leakage current from the receivers e g computer equipment the total leakage current must not exceed 3 5mA Users are forbidden to carry out any maintenance activities as they may lead to injury or death Any repairs and replacement of batteries should be conducted only by a qualified representative of the technical support WARNING The UPS is disconnected from the mains only when the power cord is removed from its socket WARNING The device is equipped with an internal power source batteries Hazadrous voltage may be present at the output even though the device is not connected to the mains WARNING SINLINE XL UPSs were not designed to work with medical equipment in particular life support devices INSTALLATION WARNING Prior to the
33. rent UPS load pants The left column of green LEDs indicates the charge level of O gt 80 batteries 45 gt 20 cs 2010 01 27 www ever eu SINLINE XL series UPS Instruction Manual O gt 85 O 230 O gt o a REAR PANEL The right column of green LEDs indicates the percentage load level of the UPS in both the mains and battery operation mode If the top LED is lit in red and the UPS is emitting a continous sound signal this indicates that the UPS has overloaded However if the red LED is blinking and the UPS is emitting a quick intermittent signal this indicates a shorting at the back up s output lf the UPS malfunctions it switches off automatically The reason for shutdown is indicated by the combination of LEDs lit see Description of the UPSS OPERATION w ON O OI A 9 Joo Fig 2 Rear panel USB port for communication with a PC RS232 serial port for communication with a PC Internal slot for an upgrade card the figure above presents a UPS with a card installed it is an optional component Outlet sockets Telecommunications filter LAN filter Socket for connecting an external battery module Mains circuit breaker After the circuit breaker is triggered the reason for shorting should be removed and the breaker pressed back in to be activated Mains power cord 10 Stopper for the external battery module socket 201
34. sege AO ee Se RE dei Gegee vonage pak ee ees EES ese SE 32 WARRANTY eee RE EE RE RE i OE EE HOE OE 32 2010 01 12 www ever eu 2 SINLINE XL series UPS Instruction Manual INTRODUCTION Thank you for purchasing the EVER SINLINE XL UPS UPS It belongs to the latest series of state of the art power supply devices designed to work with servers small computer networks as well as workstations When operating in the battery mode the UPSs of this series generate sinusoidal current at their output thanks to the Clear Digital Sinus CDS system and offer the feature of remote control of operating parameters via RS232 serial port or USB and optionally via the Ever management card Telnet SNMP HTTP SINLINE XL series EVER UPS was designed so as to meet all your expectations for protection against power loss The UPS was manufactured in Poland and its structure conforms with requirements of the CE symbol GENERAL INFORMATION PURPOSE OF THE POWER SUPPLY SINLINE XL series UPSs are LINE INTERACTIVE VI class devices designed for work with equipment powered by monophase 230V mains In back up operation mode they generate true sine wave voltage at their output This enables a much wider range of tolerated loads when compared with power supply devices using approximation of the sinusoid UPSs belonging to this group may power virtually any device whose power does not exceed the nominal power of the UPS SINLINE XL UPSs do not switch off
35. te x x x In the case of Debian and FreeBSD systems we recommend uninstalling the old version and then installing the new version of the software Commands which enable these operations are described in the instruction manual available at www ever eu EVER SNMP HTTP NETWORK management card Optionally the UPS can be upgraded with the EVER SNMP HTTP networkmanagement card It is a device that integrates the UPS with an Ethernet network The network adapter is located in a special slot located on the rear panel of the UPS With the network adapter installed the user can control the UPS from any computer connected to the network This solution is most frequently used in cases of central power supply or when the power supply system needs to be controlled remotely The network adapter has the following services implemented e SNMP agent enables control of the power supply system via a SNMP manager software e HTTP server enables inspection and modification of the UPS s parameters via an Internet browser e Telnet server control via a Telnet network terminal More information on the network adapter can be found in its instruction manual 2010 01 27 www ever eu 26 SINLINE XL series UPS Instruction Manual CONFIGURING THE UPS S PARAMETERS PowerSoft Plus allows the user to change certain parameters of the UPS To enable this the UPS must be connected to the computer with the cable provided by the man
36. ufacturer A list of these parameters together with available settings is presented in the tables below Table 2 PARAMETER FUNCTION SEAN CUSTOM SETTINGS DESCRIPTION Acoustic signalling On On off Only for the battery operation mode Delay before standby mode 90 sec 0 1000 sec MA a ek EE ine Table 3 UPS STATUS SWITCHING VOLTAGE z BAT MAINS AVR 155 175 V 165 V MAINS AVR BAT 150 170 V 160 V MAINS AVR MAINS 200 210 V 205 V MAINS MAINS AVR 195 205 V 200 V MAINS BAT 250 280 V 265 V BAT MAINS 245 275 V 260 V BAT battery operation mode MAINS mains operation mode MAINS AVR mains operation mode with AVR system engaged ADDITIONAL REMARKS CAUTION This is a C2 category UPS In domestic environment the product may interfere with reception of radio waves so the user may be required to implement additional preventive measures AN WARNING No service elements located inside the UPS are to be modified by the end user e Damaging the warranty seal shall void the warranty for the given device e Any repairs should be conducted only by gualified technical support staff e The UPS may not perform as expected if the powered equipment draws high impulse power In practice this means that even though mean power of the protected equipment does not exceed the power range accepted by the UPS
37. y should be charged every 6 months e In temperatures between 30 and 45 the batter y should be charged every 3 months The UPS should be transported in the original packaging and in conditions conforming to the product s specification see Technical parameters If the packaging is missing or a non original or incomplete packaging is used EVER Sp z o o shall not be liable for any mechanical damages that occur in transport DISPOSAL Appropriate disposal of used up electric and electronic equipment helps to avoid consequences resulting from the presence of dangerous materials as well as inappropriate disposal and processing of such equipment which may be hazardous to human life and the environment Act dated 29 July 2005 on used up electric and electronic equipment Article 22 1 items 1 and 2 According to the applicable EU regulations a crossed rubbish bin A symbol means that when a product is no longer used it should be disposed of at a special waste pickup site This concerns the device itself as well as other accessories marked with this symbol Do not dispose of those products together with unsorted household waste Method of safe removal of the batteries from the appliance The batteries should be removed from the appliance by an authorised service outlet or by a duly authorised electrician 2010 01 27 www ever eu 29 SINLINE XL series UPS Instruction Manual TECHNICAL PARAMETERS Tower Model
Download Pdf Manuals
Related Search
Related Contents
Omron B3F User's Manual DeLOCK MR16 L`ACTU DES TRAVAUX GARE CRÉTEIL L`ÉCHAT YOUR ULTIMATE - PCE UPS Systems 0147A Ford DTC Reader Manual & Codes cette-grenade-dossie.. Bibliographie complète en PDF - Genre, travail, mobilités RAVE Water Sports Equipment User Manual Sharp LC32LE450U 32" Black Copyright © All rights reserved.