Contents
1. 3 Unscrew and remove the battery retaining battery bracket 5 Slide the new battery into Battery module 6 Reconnect the battery cable and screw up the battery retaining bracket 7 Close and reinstall the front panel back to Battery module 3000VA model 1 Remove the battery case front panel by pulling on both ends 2 Disconnect the battery cable from UPS 3 Unscrew the battery bracket from the Battery module 4 Remove the battery bracket from EBM by pulling on both ends 5 Pull the battery out from right side onto flat area 7 Slide the new batteries into Battery module 8 Reconnect the battery cable and screw up the battery bracket 9 Close and reinstall the front panel back to Battery module 8 COMMUNICATION PORT 81 RP Qtaapes D Ferde R2 adicoauders PIN 1 0 Function Explanation Low Battery Output normally open pull to Pin 5 when battery low alarm in battery ode D D m AC Fail Output normally open pull to Pin 5 when UPS is in battery mode 8 2 USB port HID protocol The USB and RS232 are unable to operate at the same time Either only USB or DB9 can connect with RS 232 at one time usually connecting with USB function is priority 8 3 AS400 interface Optional Not available for models lower than 1500 VA This UPS has the AS400 communications as an option through a female DB9 connector which allows to
2. 2 4 Add up the front panels for both sides The load can be connected 1500 2000VA models optional e UPS and Battery integrate into a rack form 1 Place the UPS on a flat and in a clean place that the front side of the UPS is facing to you 2 Disconnect the cable from the UPS and Battery modules UPS and Battery are disconnected 3 Loosen the screws and remove the UPS and Battery modules cover from the unit 4 Pull two covers toward the direction shown as below 5 Align the mounting bracket with the screw holes onthe each side of UPS and Battery modules and secure with the supplied screws 8 Align two small mounting brackets at the rear of UPS and Battery modules and secure with the supplied screws Install Output receptacles at the rear panel of the UPS z EH y A i H WV J a reis da El s os A The rackmount kit for connecting the UPS to Battery amp Battery to Battery modules is different Please contact your dealer for further details 3000VA model optional Install the 3000VA series into 19 rack as shown below AnA L 2 Turn on the UPS and connect the load After installing the UPS into rack the load may be connected Make sure the load equipment is turned off th
3. 30 50ER The figure indicates that the input voltage is 230V and the input frequency is 50Hz 6 Auto Voltage Regulation The LCD symbol ESIE indicates that the UPS is in AVR Auto Voltage Regulation mode 7 Line M ode The LCD symbol EEA illuminates when UPS is on and the AC source is available 8 Battery The LCD symbol MBMA indicates that the battery is in charging mode second when Fer is low The battery symbol also could show battery level There are four segments to indicate the amount of battery capacity remaining The higher the battery capacity the more indicators that will be illuminated Each indicator designates a 25 capacity level Please see the follow ing capacity level respectively This is 100 to 76 HU all or tne rour indicators illuminate ll 50 al 26 HN two indicators limits El 25 al11 Hi only one indicator illuminates l 10 al 0 fc i none of the indicator illuminates ll l Output paremeters voltage amp frequency This part gives the information of the output including output voltage and output frequency OUTPUT c30 5 UGH The figure indicates that the output voltage is 230V and the output frequency is 50Hz 10 Capacity of Load The LCD gives the load information by displaying the load percentage Normally the symbol a will not illuminate but wh
4. 50 Battery capacity 11 25 Battery capacity 0 10 Flashing UPS is overload UPS is overload and the time is out FAULT OVER LOAD UPS is overload and the time is out i UPS is plugged into an improperly polarity SITE FAULT only for LV models BAD BAT pf cone 4 apavora is onora 4 3 Audible alarm introduction Backup Mode Power Failure Sounding every four seconds UPS Fault Continuously Sounding Sounding every second Battery Replacement Sounding every second 4 4 Back panel 750 1000VA Models 1000 LV 750 LV 1000 HV 750 HV Rear panel description for LV and HV models table a ae En Modem Network Surge Protection ES RS232 Dry Contact Communication Port ES USB Communication Port A AC Input Power cord AC Input amp Protection ICE DE IT TT 1500 2000VA Models e UPS module The host rear panel pictures for HV and LV models are shown as below O s r Es INPUT 10A MAX t ha 4 oni r i amp it L 4 J W l Lj Lt J J di J r n 3 1 I 1 EA t t od I DS P g n x E mn 5 J J si I gE AT amr Ll 4 SE 4 l rA l b d j a Rear panel for HV model I EE I Est O ee A OIL o SNMP IN OUT mmoOooon Ni E Rear panel for LV model Rear panel description for LV and HV models table E RR
5. El hp e800 i s r 3 oa AC LINE ara ad UPS dm hon IE i Voltage 132 V BATTERY Standard 120 V HE Cepscty 100 0 0401 20 144433 Agent Start Li Installation procedure 1 Insert CD The installation assistant runs up automatically Follow the steps 2 When the system requires tape the serial number 511C1 01220 0100 478DF2A When your computer restarts the WinPower software will appear as a green plug icon located in the system tray near the clock Salicru com saLIcr U 08460 Palautordera Tel 34 93 848 24 00 sat salicru com
6. RANGE e Normal The UPS accepts a input voltage range of 20 Generator The low frequence transfer point changes at 40Hz and there is not limit for the high frecuence transfer point Extended margin The UPS accepts a input voltage margin of 30 to 20 14 Output voltage margin The UPS output voltage selection 110Vac 120Vac 127Vac o 220Vac 230Vac 240Vac RATED VOLTAGE oe eee eee eee ee eee esse pees eee eee ee eee eee e 110 VAGie 220 VAC O lt e 120 VAGie 230 VAC gt je 127 VAC e 240 VAC ee en ee eee nr D 110Vac 120Vac 127Vac are LV mode low voltage 220Vac 230Vac 240Vac are HV mode high voltage Example To a HV UPS after selection the 230Vac mode default selection by the switchs CNFG and ENTER the output voltage will be approximately 230V and the LCD display will be how the next figure shows RATED VOLTAGE 220 VAC e 230 VAC 240 VAC Examples to the LCD display If the mains supply exist c LV ac c 30 n iA INPUT TYPE RATED VOLTAGE NORMAL 220 VAG GENERATOR e 230 VAC WIDE RAWGE 240 VAG If the mains supply do not exist HHV ac nn Ei Hz INPUT TYPE RATED VOLTAGE NORMAL 220 VAC GENERATOR e 230 VAC WIDE RANGE 240 VAC 4 2 Introducing the LCD display EET ES EE ES EE EE TEA oy o mama Auto Voltage Regulation Mode a Pre P anam O eee Battery capacity 76 100 Battery capacity 51 5 Battery capacity 26
7. of contamination Locate it in a clean and indoor environment free from moisture flammable liquids and direct sunlight M aintain a minimum clearance of 4 inches 100mm an ambient temperature range must be 0 C to 40 C 32 F to 104 F and operating humidity range must be 20 to 80 relative humidity non condensing A The long term uses at ambient temperature in higher than 25 C which should reduce battery life In addition place the UPS unit away from the monitor at least 20cm to avoid interference 5 3 Charging This UPS is shipped from the factory with its internal battery fully charged however some charge may be lost during shipping The battery should be recharged prior to use Plug the UPS into an appropriate power supply and allow the UPS to charge at least 4 hours 5 3 1 Load connection Connect one load related device to each of the power receptacles supplied at the rear of the UPS 5 4 Modem Phoneline Connection Plug incoming telephone line into the In socket at the back of the UPS Use on telephone line cable and plug one end of the telephone line cable to the Out socket at the back of the UPS Plug the other end to the modem input socket 5 5 DC Start function DC Start Function enables UPS to be started up when AC utility power is not available and battery is full charged ust simply press the On Off switch to turn on the UPS 5 6 Turn On Off To turn on off the UPS you should p
8. C ean ae ae Pt _ AS232 Dn ContactCommurcaion Pot a SP EE I EE S LC at Suge P DS DT I a ow DT I S Pa feral ater corer OOO e Battery module Rear panel for HV model f OVERLOAD V 1 PROTECTOR Rear panel for LV model Rear panel description for LV and HV models table co LV model 110 120 127Vac ENS Battery Output Povver Cord CT I Output ES a Eternal BatoryComector CS OutputBreaker NA se ouput Brealer DT 6 Output hecepiaoes Output Receptas 3000VA model Te fJ fo FNS c REN i A 3 Rear panel for HV model Rear panel for LV model Rear panel description for LV and HV models table Es LV model 110 120 127Vac HV model 220 230 240Vac ak 4 Output thermic protection EH AC Output AC Input Modem Network Surge Protection EA CA ES N A 6 7 7 RS232 Dry Contact Communication Port 5 INSTALLATION 5 1 Inspecting the Equipment Inspect the UPS upon receipt If the UPS has been damaged during shipment keep the box and packing material for the carrier Notify the carrier and dealer immediately 5 2 Placement This UPS should be installed indoors with adequate airflow and free
9. OUTPUT requency 90Hz or 60Hz requency Regulation Batt Mode 110 0 8 shutdown after 3 minutes 150 0 10 shutdown after 10 cycles 110 6 shutdown after 30 seconds 120 6 Shutdown after 5 cycles TRANSFER Tvpical 2 4ms Typical 6 ms max TIME yee 13ms max in Generator mode OVERLOAD RATING 5 minutes min 3 hours to 90 after discharged Display LCD ack up mode Sounding every 4 seconds ow Battery sounding every second INDICATORS 235 86 2 383 438 86 2 582 PHYSICAL es INTERFACE Yes es ackup Time at full load echarge Time ojojoj co T oe Pe p s isol QS J m o 2 lt is o S 13 am CD attery Type 12V 7AH 12V 9Ah 12V SAh BATTERY Betten Number 8 pcs d n lt amp K D ow D Oj Optional EPO N pes Pes w Yes Yes N A A 11 SOFTWARE INSTALLATION WinPower is a brand new UPS monitoring software which provides user friendly interface to monitor and control your UPS This unique software provides safely auto shutdown for multi computer systems while power failure With this software users can monitor and control any UPS on the same LAN no matter how far from the UPSs EE min Power Manager ver 2 0 El mi xj Sysiem Logs UPS Tools Monitor Preference Language Help 0 33 el 2 Root LB Ser UPS Hornet 146 D pp LAN Ep c9 2000 Voltage 2170 V g com OFF L waa ae mites i o 3 aa ist C backup j O
10. UNINTERRUPTIBLE POWER SUPPLY ADVANCE series User s manual installation and start up EK459B01 General contents 1 INTRODUCTION 1 1 Gratefulness letter 1 2 Using this manual 1 2 1 Used symbols and conventions 1 2 2 For further information and or help 2 QUALITY AND STANDARD GUARANTEING 2 1 Management declaration 2 2 Standard 2 3 Safety and first aid 2 4 Environment 3 DESCRIPTION 4 PRESENTATION OF SYSTEM 4 1 Front Panel 4 2 Introducing the LCD display 4 3 Audible alarm introduction 4 4 Back panel 5 INSTALLATION 5 1 Inspecting the Equipment 5 2 Placement 5 3 Charging 5 3 1 Load connection 5 4 Modem Phoneline Connection 5 5 DC Start function 5 6 Turn On Off 5 7 UPS Setup 5 7 1 Tower Setup 5 7 2 Rack M ount Setup 5 8 Emergency Power Off E P 0 set up 6 ADDITIONAL BATTERY INSTALLATION SETUP 7 BATTERY REPLACEM ENT 8 COMMUNICATION PORT 8 1 RS232 Optocouplers 8 2 USB port HID protocol 8 3 AS400 interface Optional Not available for models lower than 1500 VA 9 TROUBLE SHOOTING 9 1 Audible Alarm Trouble Shooting 9 2 General Trouble Shooting 10 SPECIFICATION 11 SOFTWARE INSTALLATION 1 INTRODUCTION 1 1 Gratefulness letter We would like to thank you in advance for the trust you have placed in us by purchasing this product Read this instruction manual carefully bef
11. communicate with other equipments like the standard RS232 optocouplers simultaneously but the AS400 provides dry contacts from relays instead of optocouplers and it has a higher quantity of alarms Its installation is very easy and not complicated 1 Loosen and remove the screws from cover 2 for models up to 2000 VA or 7 for higher models This cover is located inthe rear Side of the equipment 2 Remove the cover and keep it in safe place 3 Insert the AS400 card into the guides that are visible and enter it until is set with the connector of the bottom 4 Put back the screws that fix the cover integrated with the AS400 card The following table and diagram shows the pin out of female DB9 connector and its function Do not apply values higher than 24 V DC and 1 A to the pins of the AS400 connector UPS failure ___ Pin 2 General alarm 1 io P7 Low battery 3 o Pin 8 UPS On 5 ESA UPS On Pin9 Mains failure 9 Mainsfailure o Pin1 UPS failure 1 2 5 1 EEES 2 Generalalam Output S Se Pin 5 Common 9 TROUBLE SHOOTING 9 1 Audible Alarm Trouble Shooting Probie eae Solution Sounding every 4 seconds The UPS is on battery Check the input voltage Sounding every second The battery is running low save your work and turn off your equipment Continuously sounding The UPS fails Please contact your local dealer Sounding every second Output overload Check load level indicator and re
12. en plug all loads into the output receptacle properly protected by a circuit breaker of fuse in accordance with national and local electrical codes 5 8 Emergency Power Off E P O set up 1500 2000VA and 3000VA include E P 0 port that allows power to be shut down the protected equipment immediately and does not follow the shutdown procedure from any power management software Follow the procedure to install the E P O switch as below L 2 3 COMM UI A Check the UPS is turned off Remove the E P O connector from the E P O port on the rear panel of UPS Connect isolated normally open dry contacts rated to handle 60Vdc maximum 30Vac RMS maximum and 20mA maximum across the EPO device to Pin 1 and Pin 2 Reconnect the E P 0 connector to the E PO port Verify that the externally connected E PO switch is not activated to enable power to the UPS output receptacles Plug in the UPS then pressing power switch ON OFF button to turn on the UPS Activate the external E PO switch to test the E P O function De activate the external E P O switch and restart the UPS 6 ADDITIONAL BATTERY INSTALLATION SETUP 1500 2000VA and 3000VA include external battery port that allow to provide additional battery runtime 1500 2000VA model has no internal battery and 3000VA has designed an internal battery inside the UPS A Connecting battery cable to external battery port may occur sparkle if adding up additional bat
13. en the load percentage is more than 110 overload it will flicker every second If over load is time out it will illuminate constantly 11 Site Fault The Site Fault indicator BEIMA will light when UPS is plugged into an improperly utility This function is only available for 120Vac models 12 Fault code When UPS fails the corresponding LCD symbol will illuminate to show the type of failure Battery bad When the battery of the UPS is bad the symbol ma FAULT E will be displayed constantly Over load time out When UPS is Over load time out the symbol will be displayed constantly At the same time the symbol e will be displayed constantly and the output voltage is QVac 0Hz Battery missing If the battery connection is not good the LCD will display FAULT CODE 1 Fan fail If the fan is locked The symbol FAULT CODE 2 will flicker every second if the time is out The symbol will be displayed constantly Over temperature If the temperature of the UPS is too high The LCD will display FAULT CODE 3 constantly Output invalid If output voltage is out of range the LCD will display FAULT CODE 4 constantly Battery overcharged The LCD will display FAULT CODE 5 constantly Output short circuit The LCD will display FAULT CODE 6 constantly Other fault type The LCD will display FAULT CODE 8 constantly 13 Input type Operation mode INPUT TYPE e NORMAL GENERATOR WIDE
14. eplacement kit is damaged in anyway or shows signs of leakage contact your dealer immediately Properly recycle or dispose of used battery Do not dispose of batteries in a fire The batteries may explode A If you are not qualified service personnel to replace the battery do not attempt to open the battery door Please call local dealer or distributor immediately Recycle the used battery e Never dispose the batteries in a fire It may explode e Do not open or mutilate the batteries Released electrolyte is harmful to the skins and eyes It may be toxic A battery can present a risk of electrical shock and high short circuit current To recycle properly the used battery please do not discard the UPS battery pack and batteries into the trashbin Please follow your local laws and regulations you may contact your local recycling waste center for further information to dispose properly of the used UPS battery pack and batteries Follow the steps and Charts below to replace batteries 750 1000VA models 1 Unscrew and remove the front panel on both ends 2 Disconnect the battery cable from the UPS and remove the battery retaining battery bracket 4 Slide the new battery into UPS 5 Reconnect the battery cable and screw up the battery retaining battery bracket 6 Close and reinstall the front panel 1500 2000VA models 1 Remove the battery case front panel by pulling on both ends
15. for the serial ports shall conform to true RS232 interface e Features Microprocessor control guarantees high reliability High frequency design Built in boost and buck AVR Userreplaceable design for 1500VA or above Selectable output range and line sensitive Cold startup capability Optocouplers RS 232 USB communication port SNMP allows for web based remote or monitoring management Enable to extend runtime with scalable external battery pack for 1500VA or above Overload Short circuit and overheat protection e Rack Tower 2 in 1 Design e 19 rack mount available for all models 4 PRESENTATION OF SYSTEM 4 1 Front Panel The total view of the LCD in front panel r RR MM 3 fa i5885 tre e 110 VAC e 220 VAG 120 VAG 230 VACI m i 3 ff INPUT f E OUTPUT 888m 888m on orr Darrrnararamann TEST CC CNFG CD een LTE FAULT INPUT TYPE CET NORMAL ZUR TEER GENERATOR re 90 ENTER T The primary introduction to above figure No Function Description 10 1 Power Switch e To turn on the UPS press the ON OFF button more than three seconds e To turn off the UPS press and hold this button until you hear the UPS beep ceases 2 UPS Test Alarm Silence Switch e When AC utility power is available and battery is full charged it is possib
16. his product can cause radioelectric disturbs and in this case the user must take additional measures e This UPS is designed for Commercial Industrial use only It is not intended for use with life support application and other designated life critical devices e Do not remove the input power cord when this UPS is turned on This removes the safety ground from this UPS and the equipment connected to UPS e When replacing the batteries use the appropriate replacement battery kits same number and type of battery are M UST Turn off this UPS and disconnect input power cord before battery replacement During the installation of this equipment it should be assured that the sum of the leakage currents of the UPS and the connected loads does not exceed 3 5mA 2 4 Environment This product has been designed to respect the environment and has been manufactured in accordance with the standard ISO 14001 Recycling the UPS ADVANCE series at the end of its useful life SALICRU commits to use the services of authorised societies and according to the regulations in order to treat the recovered product at the end of its useful life contact your distributor Packing To recycle the packing follow the legal regulations in force Batteries The batteries mean a Serious danger for health and environment The disposal of them must be done in accordance with the standards in force 3 DESCRIPTION This series is a compact and fully pure
17. le to perform self test function by pressing and holding the TEST button for five seconds e To disable alarm buzzer press this button for a second that will turn off the alarm buzzer Each time a new alarm event is encountered the alarm that will sound and press this button to turn off the alarm Note Unable to disable alarm buzzer as below conditions Low Battery Overload Fan Failed Fan Fault Time Out Over Temperature 3 Configure switch To reconfigure the internal UPS setup options follow the procedure as below Step 1 By entering the CNFG button more than three seconds UPS will transfer to Rated voltage configure mode Step 2 Pressing the CNFG button more than one second the UPS allows you to select the Rated voltage one by one Step 3 After selecting the mode press the ENTER button more than three seconds the Rated voltage is configured Step 4 UPS will automatically transfer to Input type configure mode Step 5 Pressing the CNFG button more than one second the UPS will allow you to select the Input type one by one Step 6 After selecting the mode press the ENTER button more than three seconds the Input type is configured 4 Enter switch Press the ENTER button after you choose the mode 5 Input parameters voltage amp frequency This part gives the information of the AC utility power including input voltage and input frequency INPUT c
18. move some load Continuously sounding Battery may need to charge or service Replace the battery 9 2 General Trouble Shooting Coben ease CE The UPS is not on when The power cord is not connected correctly Check the power cord connection power switch is pressed The wall outlet may be faulty Please contact your local qualified electrician The UPS output may short circuit or overload 1 Disconnect all loads and ensure nothing is lodged in output receptacles 2 Ensure loads are not detective or shorted internally UPS could not provide power to the load No output from any output receptacle 1 Check the connected cable 2 Ensure the load does not exceed the maximum rating of UPS Battery has reduced backup Battery is not charged Re charge the battery at least 24 hours to age 2 Replace Battery lights on Please contact your local dealer Connected equipment s lose the UPS continuously 1 The UPS is in green mode 1 Wait for a while and try again 2 Button is Broken 2 Please contact your local dealer 10 SPECIFICATION MODEL CST oA 1500 2000VA__ 3000VA__ 110 120 127VAC or 220 230 240VAC Line Low Transfer Wide mode 77 84 89VAC 4 or 154 161 168VAC 4 Line High Transfer AVR mode Boost lf the input voltage drops further 10 the Voutput Increases 12 Buck requency Range urge Rating LV HV oltage 110 120 127VAC or 220 230 240VAC oltage Regulation Batt Mode 5 RMS for entire battery voltage range
19. nnexes it contents the specification table and the appendices 1 2 1 Used symbols and conventions A W arning symbol Carefully read the indicated paragraph and take the stated prevention measures AN Danger of electrical discharge symbol Pay special attention to it both in the indication on the equipment and in the paragraph referred to this user s manual DG M ain protective earthing terminal symbol Connect the earth cable coming from the installation to this terminal Gi Notes of information symbol X Preservation of the environment The presence of this symbol in the product or in their associated documentation States that when its useful life is expired it will not be disposed together with the domestic residuals In order to Ps avoid possible damages to the environment separate this product from other residuals and recycle it suitably The users can contact with their provider or with the pertinent local authorities to be informed on how and where they can take the product to be recycled and or disposed correctly 1 2 2 For further information and or help e For further information and or help on the version of your specific unit request it to our Service and Technical Support department S T S 2 QUALITY AND STANDARD GUARANTEING 2 1 Management declaration Our target is the client s satisfaction therefore this Management has decided to establish a Quality and Environmental policy by means
20. ntal System of SALICRU PROCESS MANAGEMENT PROCESS PROCESS PROCESS TRAINING PROCESS 2 2 Standard The UPS product ADVANCE series is designed manufactured and commercialized in accordance with the standard EN ISO 9001 of Quality Assurance The lt lt marking shows the conformity to the EEC Directive quoted between brackets by means of the application of the following standards e 2006 95 EC of Security of Low Tension e 2004 108 EC of Electromagnetic Compatibility CEM according to the specifications of the harmonious standards Reference of standards e IN 60950 1 Equipments of technology of the information Security Part report 1 General Requirements e IN 61000 6 3 Electromagnetic Compatibility General emission standard Residential commercial and light industry environments e IN 61000 6 2 Electromagnetic Compatibility Generic standard of immunity Industrial environment When a UPS of ADVANCE series is used as part or component of a complex system or installation the Generic or Product standards of that installation or specific system must be applied It is possible that when adding parts or being under the requirements of a specific standard all the parts have to be under corrections to assure the conformity with the European Directives and the corresponding national regulations It is responsi bility of the project Manager and or Fitter the compliance of the standard providing t
21. o the installation all the needed parts to comply the standard Furthermore the interference phenomena due to input harmonic currents exists and although it is not regulated by these standards it is necessary to correct them in some installations Depending on the installation conditions of UPS ADVANCE series the corrections described in the Electromagnetic Compat ibility have or do not have to be done For all the versions and regarding the Safety standard EN 60950 1 has to be kept in mind the aspects of the Product detailed in the INSTALLATION section 2 3 Safety and first aid e Together with the equipment and this User and installation manual it is provided the information relating to Safety instructions See document EK266 08 Before proceeding to the installation or commissioning check that both infor mation are available otherwise request them It is compulsory the compliance of the Safety instructions being the user the legal responsible regarding to its observance Once read keep them for future consults that can arise 0 AN Do not attempt to repair and service this UPS This UPS contains high voltages which could cause the risk of electrical shock Even this UPS is disconnected from the electrical outlet the dangerous voltage still may be present through the battery All maintenance and battery replacement should be performed by qualified service personnel only 0 AN this is a class A product In domestic use t
22. of installation a Quality and Environmental Management System that becomes us capable to comply the require ments demanded by both the standards ISO 9001 2000 and ISO 14001 2004 and our Clients and concerned parts too Likewise the SALICRU M anagement is committed with the development and improvement of the Quality and Environmental Management System through e The communication to all the company about the importance of satisfaction both in the client s requirements and in the legal and regulations e The Quality and Environmental Policy diffusion and the fixation of the Quality and Environment targets e To carry out revisions by the M anagement e To provide the needed resources Management agent The Management has designated as management agent the person in charge about the Quality and Environment depart ment who with independence of other responsibilities has the responsibility and authority to assure that the processes of the quality and environmental management system are established and maintained to inform to the Management about the operating of the quality and environmental management system including the necessities for the improvement and to promote the knowledge of the client s requirements and environmental requirements at all levels of the organization CONTINUOUS IMPROVEMENT PROCEDURE MANAGEMENT REVISION In the next PROCESS MAP is represented the interaction among all the processes of the Quality and Environme
23. ore starting up the equipment and keep it for any possible future consult that can arise We remain at you entire disposal for any further information or any query you should wish to make Yours sincerely SALICRU LY The equipment here described can cause important physical damages due to wrong handling Due to this the maintenance and or fixing of the here described equipment must be done by SALICRU staff or specifically authorised ua According to our policy of constant evolution we reserve the right to modify the specifications in part or in whole without forew arning a Al reproduction or third party concession of this manual is prohibited without the previous written authorization of our firm 1 2 Using this manual The purpose of this manual is to provides explanations and procedures for the installation commissioning maintenance and troubleshooting of UPS from ADVANCE series This manual has to be read carefully before installing and operating it Keep this manual for future consults This manual consists into four main chapters e Introduction it contents the information of the general description features and specifications of UPS ADVANCE series e Installation and Operating it provides the information of the commissioning and operating of UPS ADVANCE series as well as its connection e Maintenance and Troubleshooting it contents the information to maintain and solve wrong operating and parts faults of UPS ADVANCE series e A
24. ress the on off switch three seconds at least 5 UPS Setup All models series are designed for tow er and rack purpose They can be installed as a 19 inch equipment rack and 3000VA can be placed in a tower with optional stand as well Please follow the instruction for Tower Setup or Rack M ount Setup 5 7 1 Tower Setup This series can be placed in horizontally and vertically 3000VA model is designed in a rack itself As a tower it is provided with the optional UPS stand to stabilize the UPS when the UPS is positioned in vertically The UPS stand must be attached to the bottom of the tower 750 1000VA models e Tower form 1500 2000VA models e UPS and Battery modules integrate into three types of tower forms a Tower form 1 b Tower form 2 c Tower form 3 3000VA model e Tower form setup 1 Slide down the UPS vertically and put two UPS stands at the end of the tower 2 Place the UPS into two stands carefully 5 7 2 Rack M ount Setup 750 1000 1500 2000VA optional and 3000VA can be installed in 19 racks And the UPS and external battery enclosure need 2U of valuable rack space Use the following procedure to install UPS in a rack 750 1000VA models optional 1 Align the mounting ears with screw holes on the side of the UPS Ga hd E bd 4
25. sinew ave line interactive UPS and it designs for application and environment such as desktops servers workstations and other networking equipments This model is available in the output ratings of 750 1000 1500 2000 and 3000VA This series protects your sensitive electronic equipments against power problems including power sags spike brownouts line noise and blackouts This series designs from two in one form factor it can be placed either in Rack 2U or Tower The front panel of the UPS includes LED indicators and four push buttons Power Switch UPS Test Silence Configure and Enter that allow to monitor easily configuration and control AC line in notification of site wiring fault and output load status of the UPS It also includes four LCD bar graphic Load Battery Level Indication two status indications On AC On Battery five alarm indications Overload Over Temperature Site Wiring Fault Battery Fault Self Test Failure A push button from the front panel allows silencing of the AC fail alarm and the initiation of the UPS self test sequence as well The UPS case for 750 2000VA is made of plastic as well as 3000VA is made of metal This series is powered from the AC mains and supply AC outputs via receptacles on the rear panel Communication and control to the unit is available through serial or USB ports located on the rear panel The serial port will support communications directly with a server The communications protocol
26. tery Follow the procedure to install additional battery as below 1500 2000VA models There are two external battery ports for each side of UPS itself and battery pack 1 Connect the battery cable to the external battery port of the rear of UPS 2 Then connect the supplied battery cable from extended battery module to the external battery port of the rear of previous UPS 3 If continuing to add up extended battery pack repeat above steps e Additional battery connection in rack form ei eccorresse 1 ms or ce Bi po 1 tob li porccn Ea npese I econo esse screse af 3000VA model There is one external battery port for the UPS itself 1 Connect the supplied battery module cable from extended battery module to the external battery port of the rear of UPS 2 If continuing to add up extended battery module repeat above steps 7 BATTERY REPLACEM ENT When the Bad Battery icon ma PPRESE lights and there is a continuous sounding the battery may need to be replaced FAULT Please check the battery connection or contact your local dealer to order new battery A A battery can present a risk of electrical shock and high short circuit current The following precautions should be observed before replacing the batteries Turn off the UPS and disconnect the utility power cord from the wall outlet Remove rings watches and other metal objects If the battery r