Home

APC Symmetra PX

image

Contents

1. Parallel System Summary Qtlaups1 Q5bups1 eee ae Q1bups1 c UPS Mode Normal Operation System Mode On Q3MAINT3 UPS 2 Q4LO0AD44 UPS 3 Las System Redundancy N 1 741 KVA 5 System Load 75 UPS Mode Normal Operation System Mode Symmetra PX 250 500 kW 400 480 V 990 2748E 001 3 Press the Isolate this UPS button on the Operation screen Symmetra PX UPS Mode Normal Operation A P Cc System Mode On by Schneider Electric UPS 1 Operation a E System Start up System Shutdown Static Bypass gt Normal Op Normal Op gt Static Bypass Isolate this UPS lt 4 Follow the steps which appear on the screen Steps will appear in the order in which they need to be completed A step will initially appear in red and then when it is completed the step will change to green The next step to be completed will be highlighted in red text and yellow background Note Grey buttons are touch screen functions Symmetra PX une Moat Operation d em Mode On by Schneider E eceri s UPS 1 Isolate this UPS Please verify that the remaining system can support the load before completing the isolation procedure Number Action Description UPS Off Open breaker Q2aQx UPS output Open breaker O5aQx SSW input Open battery breakers Open Battery Breakers Open breaker 01 aQx UPS input Note The display will switch off after all steps have been completed Note The display wi
2. 400 V 260 A UPS 4 Module Redundancy N 2 183 KVA UPS 4 Load 74 UPS 4 Runtime Available 5m Os 288 V 288 V UPS 4 Ambient Temperature 20 C OA 990 2748E 001 Symmetra PX 250 500 kW 400 480 V 5 Battery operation If the utility mains supply fails the UPS transfers to battery operation During battery operation battery power ensures uninterrupted support to the critical load While the UPS system is in battery operation a single line diagram will appear on the screen The green line indicates the power flow from the batteries through the inverters and then to the load Single System Parallel System UPS Mode Battery Operation Symmetra PX System Mode On ia Samer tower UPS Summary 09 59 Symmetra PX UPS Mode Battery Operation System Mode On by Schneider Elscirie UPS 4 Parallel System Summary Q3 UPS 1 Master Q5aups1 Q2aups1 Bypass Qiaups1 Q5bups1 Output 400 V 257 A Q2bups1 i input 400 V 257 A System Redundancy N 1 UPS Module Redundancy N 2 741 KVA System Load UPS Load n 75 Q2dups4 UPS Runtime Available 5m 0s 288 V 288 V 260 A 260 A Ups ambient Temperature 20 C Qidups4 Or Symmetra PX UPS Mode Battery Operation APC System Mode On ipsa ME EE p Q5d Bypass Output 400 V 260 A UPS 4 Module Redundancy N 2 183 KVA 74 UPS 4 Runtime Available 5m 0s 288 V 288
3. Date format Temperature unit 990 2748E 001 Symmetra PX 250 500 kW 400 480 V Maintenance Access Predictive Maintenance Screen Note Press the home button to go to the UPS Summary or Parallel System Summary screen 1 Press the UPS System button in the bottom left corner to access the UPS System screen Single System Parallel System Symmetra PX UPS Mode Normal Operation Symmetra PX UPS Mode Normal Operation System Mode On System Mode On cema UPS Summary MT Parallel System Summary Q3MAINT3 Q4LOAD44 400 V 260 A UPS Module Redundancy N 2 UPS Load eba 5 UPS Runtime Available s 288 V 288 V OA OA i ae UPS Ambient Temperature 2 System Information Configuration Operation 36 Symmetra PX 250 500 kW 400 480 V 990 2748E 001 3 Press the Predictive Maintenance button to access the Predictive Maintenance screen Symmetra PX UPS Mode Off System Mode Maintenance Bypass by Schneider Electric UPS 1 System Information 00 00 DGO Active in control Intelligence module UPS serial number 0 0 0 0 UPS system firmware version 4 20 0 123 Event Logs System firmware version stored at memory 4 20 0 123 card Firmware Overview Display firmware version 2 0 0 125_ENG APC support phone Enter phone number Predictive Maintenance 7 US 7 456 524 US 7 456 518 US 7 274 112 US 7 126 409 US 7 106 607 US 7 012
4. UPS Mode Off Symmetra PX System Mode Maintenance Bypas Err UPS Summary Symmetra PX UPS Mode de Off System Mode Maintenance A Q5aups1 Q2aups1 Bypass yp Q1aups1 Q5bups1 Output Q2bups1 Q1bups1 OV OA System Redundancy N 1 UPS Module Redundancy 741 KVA 75 Qic System Load UPS Load UPS Runtime Available OV OA UPS Ambient Temperature s Q5dups4 Q2dups4 Q1idups4 Or Symmetra PX UPS Mode Off System Mode Maintenance Bypass by Schneider Electric UPS 4 UPS 4 Summary 09 5 OO Q5d Bypass Output 0v OA OV OA aid Input UPS 4 Module Redundancy N 2 183 KVA 74 UPS 4 Runtime Available 5m 0s 288 V UPS 4 Ambient Temperature 20 C UPS 4 Load 10 Symmetra PX 250 500 kW 400 480 V 990 2748E 001 Autostart Countdown UPS Mode Normal Operation Symmetra PX 3 System Mode Om eee UPS Summary System will autostart in 20 second s Buy D 0 Ambient temperature 0 C Runtime available 10m 00s 120 fir 120 D 500 A 500 A The system can be set up for an automatic start when AC utility power is restored following a low battery voltage shutdown The autostart countdown window is shown over all screens until the countdown period expires or the autostart is manually stopped by pressing the stop button This feature is disabled by default and is not supported in parallel syste
5. UPS Runtime Available 5m 0s 288 V DA Ups ambient Temperature 20 C Parallel System Symmetra PX UPS Mode Normal Operation System Mode On by Schneider Electris 400 V 260 A UPS Module Redundancy N 2 UPS Load TESA 74 UPS Mode Normal Operation System Mode 0 Symmetra PX by Schneider Electric User Configuration lt Service Configuration Configuration Factory Configuration UPS Mode Normal Operation System Mode On ae v 990 2748E 001 Symmetra PX 250 500 kW 400 480 V UPS 4 Parallel System Summary Q3MAINT3 UPS Mode Normal Operation de On System Mode Q2aups1 Q4L0AD44 System Redundancy System Load N 1 25 Perform a Battery Runtime Calibration Recalibrating the batteries keeps measurements like runtime and battery charge accurate 1 Go to the User Configuration screen by following the steps in Access the User Configuration Screen 2 Press the Battery Test Settings button on the User Configuration screen to access the Battery Test Settings screen UPS Mode Normal Operation Symmetra PX System Mode Og Arc by Schneider Electric User Configuration 10 00 Battery Test Settings Display Settings NMC Settings 3 Press Start to begin the battery runtime calibration The batteries must be 100 charged to start a calibration You can press Cancel to stop the
6. Arc by Schneider Electric Symmetra PX 250 500 kW 400 480 V Single and Parallel Operation Table of Contents 352 VIC W Si E RP EE I OE ET POE RPE PRE l SyMDOIS USE cenne a a a e a N 3 Parallel System Summary eeeeeeeeeessssssrrrrssssssrrrresssssrrrrresssserrrersssseerrresssss 3 UPS Summary Screen eeeeeseeessessrrrrrrsssssrrrrssssserrrresssssrrrteesssserrreressserrrresssss 4 Smole SyS CCIM rea E E E E NO OE AO A EOR 4 Parallel Sy Sten yeeseeascharsorasba a E N ENANA E OANE 4 Operation Modes 00 cscscescecsscecscsssecsesssecsessssnsssessesssesseeseeseeess 5 UPS MOdES cna ara ahi ae 5 NOM al OD GratlON ic secsescasscusesce seen sadacsndededeasedeutantsedeusdesedensdcesudossdeecdouadseudondousdsedest 5 Battery ODEFAUOMN ccrasc orcs instaes cassis sat ieassiee lia radecslateane canta menuc oes einen RAEN TEACA 6 Requested static bypass operation forced static bypass operation 7 Battery COS Tenna ages E ton enh ices a pele aad ected nena ees N 8 System MOG CS sisi seiiis eres aioe ieee 9 OR iit Gets aie ee ees 9 O enre E E dels whats ciaae cites svat Sua E AE A E 9 Requested static bypass operation forced static bypass operation 9 Maintenance bypass Operation cccccscccseccesccececcessceescesceescessessseescesseesees 10 Avitostart Countdown E E E E tartare E tien deae tae Rete 11 Operation Procedures ooo cece cscs cecscsscecsssscecsesessesssesses
7. perature 20 C System Mode On UPS Summary Q3 Bypass Output 400 V 260 A UPS Module Redundancy N 2 183 KVA UPS Load 74 UPS Mode Normal Operation System Mode On UPS System pean Parallel System Symmetra PX UPS Mode Normal Operation J System Mode On by Schneider Electric UPS 4 Parallel System Summary Q3MAINT3 Q2aups1 Q4L0AD44 System Redundancy N 1 741 KVA System Load 75 on Symmetra PX 250 500 kW 400 480 V 51 3 Verify that the UPS system firmware version and System firmware version stored at memory card are identical Press the Firmware Overview button P System Information Active in control Intelligence module UPS serial number 0 0 0 0 UPS system firmware version 4 20 0 123 System firmware version stored at memory 4 20 0 123 card Display firmware version 2 0 0 125_ENG APC support phone Enter phone number 4 US 4 112 US 6 409 US 7 106 607 US 7 012 825 US 6 838 925 US 7 104 805 eserved atents S 7 456 524 US 7 456 518 US 7 274 US 7 126 409 atent Pending Copyright 2009 Schneider Electric All Rights Rese 4 To save the firmware version list insert a USB flash drive into the USB port on the display ay Note Do not remove the USB flash drive before a dialog box on the display indicates that it is safe to remove the USB flash drive Note USB flash drives from the following manuf
8. 500 kW 400 480 V 17 o Press the Normal Op Static Bypass button Single System Parallel System UPS Mode Normal Operation Symmetra PX e On Symmetra PX System Mode O APC by Schneider Electric em Operation i UPS 1 Operation Li M System Start up System Start up System Shutdown Static Bypass gt Normal Op Normal Op gt Static Bypass Static Bypass gt Normal Op Normal Op gt Static Bypass Isolate this UPS 4 Press the Initiate Transfer button to go to static bypass operation The Initiate Transfer button gt is greyed out when the transfer is not available Symmetra PX UPS Mode Normal Operation APC rere Transfer to Static Bypass Check that the status has changed to Requested Static Bypass in the upper right corner Transfer from Requested Static Bypass to Normal Operation static bypass to normal operation Q Note Following this procedure will transfer the entire parallel system from requested screen Q Note Press the home button to go to the UPS Summary or Parallel System Summary 18 Symmetra PX 250 500 kW 400 480 V 990 2748E 001 l e Press the UPS System button in the bottom left corner to access the UPS System screen Single System Parallel System UPS Mode Requested Static Bypass Symmetra PX UPS Mode Requested Static Bypass Symmetra PX System Mode Requested Static Bypas by Seber t ere UPS Summary System Mode Requested St
9. 825 US 6 838 925 US 7 104 805 Patent Pending Copyright 2009 Schneider Electric All Rights Reserved Uv a a 4 The Predictive Maintenance screen shows the status and the estimated remaining lifetime of the power modules and their fans The status can be OK Near end or Exceeded Remember to order new spare parts or schedule a maintenance visit when the status is Near end Symmetra PX UPS Mode Normal Operation System Mode On Susann Predictive Maintenance by Sel Estimated Reg Fan Estimated Remaining te Remaining Lifetime Lifetime Lifetime Months Status Months Module Lifetime Status Module Location Power Module 24 00 OK 12 400 Power Module 23 05 OK 11 91 Power Module 5 20 OK 6 G0 Power Module 1 4 OK 9 G5 Power Module 20 83 Exceeded 1 8 Power Module 19 9 Near end 2 06 Power Module 18 75 OK 6 G0 Power Module PANS 17 0 OK 5 41 v Dosar Modula f Power Enclosure 1 1A hie MBBS Fat 5 MWS Determine if you need a Replacement Part To determine if you need a replacement part contact APC Customer Support and follow the procedure below so that the APC Customer Support representative can assist you promptly 1 Inthe event of a module failure the display interface will indicate an alarm condition Scroll through the alarm lists record the information and provide it to the representat
10. controller N Carefully insert the new board into the slot 6 Reconnect the cables removed in step 2 7 Secure the new board with the two four screws 990 2748E 001 Symmetra PX 250 500 kW 400 480 V 43 Replace Boards in the Battery Enclosure the equipment as well as the electrical and mechanical hazards involved may WARNING Only trained persons familiar with the construction and operation of install and remove system components WARNING Replace only one board at a time N nA A W 44 Only applicable to the A Bus communication Carefully pull out the board Carefully insert the new board into the slot Reconnect the cables removed in step 2 Loosen the two four screws in the corners of Battery Enclosure the board a Battery motor breaker PSU b System power supply c Top half battery monitoring board d Bottom half battery monitoring board e A Bus communication board board remove the cables connected to the board Secure the new board with the two four SCrews Symmetra PX 250 500 kW 400 480 V 990 2748E 001 Troubleshooting Alarms The color of the top of the screen switches from blue to red and an alarm button is shown when an alarm situation occurs Alarm Button Press the alarm button to go to the Active Alarms screen that displays all active alarms along with a corrective action for addressing each alarm When you press the alarm button the alarm wi
11. module unlocked 00 00 00 004 A 01 01 2000 1 Switchgear board communication OK 00 00 00 005 2 s 01 01 2000 00 00 00 006 anal ID amp Relay board communication n pini Please contact APC Support 01 01 2000 00 00 00 007 Shni RIM heartbeat signal OK 46 Symmetra PX 250 500 kW 400 480 V 990 2748E 001 View the Event Log Note Press the home button to go to the UPS Summary or Parallel System Summary screen The Event Log screen can be accessed either by pressing the Event Log button on the Active Alarms screen see View the active alarms or by following this procedure 1 Press the UPS system button in the bottom left corner to access the UPS System screen Single System Parallel System UPS Mode Normal Operation Symmetra PX p ode Normal Oneratic sais System Mode On g ode O 3 by Salers UPS Summary UPS 4 Paralle 5 09 5 Za hat Q3MAINT3 Q3 Q2aups1 Bypass Output Q4L0AD44 400 V 260 A em Redundan N 1 UPS Module Redundancy N 2 ii j 183 KVA 74 x UPS Runtime Available 5m 0s 288 V 288 V OA OA a UPS Ambient Temperature 20 C 741 KVA 75 UPS Load System Load UPS Mode Normal Operation System Mode 0 3 Press the Event Logs button on the System Information screen Symmetra PX UPS Mode Off e System Mode Maintenance Bypass System Status Active in control Intelligence modu
12. optimal run time see Example 1 However it may only be necessary to replace three battery units at the same time according to Examples 2 and 3 in the table below Example 1 Directions for Storage Note The battery modules must be stored indoors and with their protective packaging Q still in place Note Stored batteries should be recharged at regular intervals depending on the storage temperature Storage Temperature Recharge Interval Caution Do not store the batteries for more than 12 months 990 2748E 001 Symmetra PX 250 500 kW 400 480 V 39 Replace Batteries m i Use two people to lift components weighing between 18 32 kg 40 70 Ibs 1 Holding the handle gently lift the battery unit Battery Enclosure and pull it halfway out A lock mechanism prevents it from being pulled all the way out 2 Release the lock by pushing the battery unit upwards and pull the battery unit all the way out while you continue to support its weight 3 Carefully guide the new battery unit into the system Haas Replace Power Modules A A i 40 WARNING Only trained persons familiar with the construction and operation of the equipment as well as the electrical and mechanical hazards involved may install and remove system components WARNING Before replacing the power modules ensure that the UPS system firmware version and the System firmware version stored at memory card are identical on t
13. output status of the complete system and not the individual UPS unit On When the system mode is On the UPS system supports the critical load with conditioned power The load is supported by the UPS in both normal and battery operation Off When the system mode is Off the UPS system does not support the connected load with power Requested static bypass operation forced static bypass operation The UPS is in requested static bypass following a command from the graphical user interface And the UPS is in forced bypass when a fault on the system has caused static bypass operation During static bypass operation the critical load is supplied directly by utility mains power While the UPS 1s operating in this mode a single line diagram will appear on the screen The orange line indicates the power flow from the utility mains through the bypass static switch and then to the critical load 990 2748E 001 Symmetra PX 250 500 kW 400 480 V 9 Maintenance bypass operation During maintenance bypass operation the critical load is supplied directly by utility mains power While the UPS system is in maintenance bypass operation a single line diagram will appear on the screen The orange line indicates the power flow from the utility mains and then to the critical load via the Q3 switch Note The batteries are not available as an alternate power source while the UPS system is in maintenance bypass operation Single System Parallel System
14. packaging materials when shipping a module The module may settle in transit and become damaged Enclose a letter in the package with your name RMA number address a copy of the sales receipt description of the problem a phone number and a cheque as payment if necessary User Replaceable Parts understood and followed Failure to do so could result in equipment damage WARNING ALL safety instructions in the Safety Sheet 990 2984 shall be read serious injury or death External connection board ID and relay controller board External switch gear board Battery breaker motor PSU Battery monitoring board A Bus communication board Battery Module Replacement Directions for Replacement WARNING Only trained persons familiar with the construction and operation of the equipment as well as the electrical and mechanical hazards involved may install and remove system components modules in the UPS the time duration from the battery installation until the UPS is powered up should not exceed 72 hours or 3 days Failure to do so can result in a deep discharge of the batteries and cause permanent damage Caution The batteries must only be replaced with APC high performance battery units Caution Wait until the system is ready to be powered up before installing battery 8 3 Symmetra PX 250 500 kW 400 480 V 990 2748E 001 APC recommends that a whole battery module one row of batteries 1s replaced at the same time to ensure
15. 00 5 4 Press Apply to confirm the settings Set the Language and Regional Settings Note Press the home button to go to the UPS Summary or Parallel System Summary screen l Press the UPS system button in the bottom left corner to access the UPS System screen Single System Parallel System Symmetra PX UPS Mode Normal Operation UPS Mode Normal Operation Symmetra PX On System Mode On System Mode O APC by Sehmelder Elec UPS Summary Electric Parallel System Summary Q3MAINT3 Q3 Bypass Ls Qlaups1 Q5bups1 Q2bups1 Q4L0AD44 400 V 260 A em Redundan N 1 UPS Module Redundancy N 2 ii 183 KVA 74 UPS Runtime Available 5m Os 238V Ws 288 V 0A BS 0A ups ambi ient Temperature 20 C 741 KVA 75 UPS Load System Load 2 Press the Language button to access the Language Settings screen Symmetra PX UPS Mode Normal Operation APC System Mode O m UPS System D System Information Configuration Operation PA T 34 Symmetra PX 250 500 kW 400 480 V 990 2748E 001 3 Select the preferred language H UPS Mode Normal Operation Symmetra PX Alarm Warning an Moda ON Language Settings English Pycekn Espa ol German Portugu s Brasil 4 Select your preferred date format and temperature unit and complete with Finish Symmetra PX UPS Mode Normal Operation APC System Mode O EEA Regional Settings
16. MWrite Manual Network settings mode BootP 23 123 123 IP address 146 215 101 137 Disabled Modbus RTU Enabled NMC Level 5 Position G 4 Change the NMC settings The IP address Subnet mask and Gateway can only be edited if the NMC is set to manual See NMC documentation for more information UPS Mode Normal Operation System Mode On Configure NMC Settings iN i Symmetra PX by Schneider Electri NMC Level 4 Position B UPS configuration access the chanaes Network settings mode IP address Subnet mask Gateway a UPS configuration access Set the UPS access level for the specific NMC It can be set to Reaa write aa The Network settings mode must be set to Manual before network address settings can be configured The NMC will reboot to activate O00 Manual 10 216 252 132 p55 255 255 128 u 10 216 252 129 Apply No access Read or Read Write 990 2748E 001 Symmetra PX 250 500 kW 400 480 V 29 b Network settings mode Select to use DHCP BOOTP or manual IP address c IP address Enter a valid IP address for the card Only visible if manual mode has been selected d Subnet mask Enter a valid subnet mask Only visible if manual mode has been selected e Gateway Enter a valid gateway Only visible if manual mode has been selected Press the arrow down button and change the settings UPS Mode N
17. OUTPUT V Limit filter by event timestamp Only show events with timestamps between aA UPS ope f Start date MM dd yyyy 0 05 02 2009 _ Start time hh mm ss Pee 1 ound 15 37 53 m and UPS ope Endate c MM EAI EYYYY E 05 07 2009 End time hh mm ss 99 10 22 00 a UPS ope Reset l OK Cancel Note Do not remove the USB flash drive before a dialog box on the display indicates that it is safe to remove the USB flash drive Note USB flash drives from the following manufacturers have passed our tests Cn Memory SanDisk Integral A Data Pqi PNY OCZ Verbatim Lexar TwinMOS Freecom Toshibia Sony LG and Yifang Digital If you experience problems using your USB flash drive please try a different USB flash drive preferably one from the above list 990 2748E 001 Symmetra PX 250 500 kW 400 480 V 49 10 Press the Save Log button The full event log is saved as a text and an HTML file Associated event capture files are also saved UPS Mode Normal Operation System Mode On Event Log AA 45 Critical a E seeps 2113 Informational Active Controller MIM Y No filters active Symmetra PX v Location ose Severity 3 ww HH mm ss SSS Capture 11 30 2009 RTC Time old value 12 30 07 974 aig 11 30 2009 Power module lifetime error lifetime exceeded enclosure 1 level 42 30 05 997 Power ay 11 30 2009 Power module fan lifetime error co
18. V UPS 4 Ambient Temperature 20 C 260 A 260 A UPS 4 Load 6 Symmetra PX 250 500 kW 400 480 V 990 2748E 001 Requested static bypass operation forced static bypass operation The UPS is in requested static bypass following a command from the graphical user interface And the UPS is in forced bypass when a fault on the system has caused static bypass operation During static bypass operation the critical load is supplied directly by utility mains power While the UPS is operating in this mode a single line diagram will appear on the screen The orange line indicates the power flow from the utility mains through the bypass static switch and then to the critical load Note The batteries are not available as an alternate power source while the system is in forced static bypass operation The batteries are available in requested bypass and it is possible to manually transfer to normal operation If there is an interruption to the utility mains power supply during requested static bypass operation the system will transfer to battery operation This will cause an interruption to the power supplying the load and may result in a load drop Single System Parallel System Symmetra PX Symmetra PX APC a ist UPS Summary 400 V 260 A System Redundancy N 1 UPS Module Redundancy 741 KVA System Load 75 UPS Load UPS Runtime Available 288 V 0A UPS ambient Temperature Symmetra PX by Trsa ME EA 260 A UPS 4 M
19. acturers have passed our tests Cn Memory SanDisk Integral A Data Pqi PNY OCZ Verbatim Lexar TwinMOS Freecom Toshibia Sony LG and Yifang Digital If you experience problems using your USB flash drive please try a different USB flash drive preferably one from the above list Symmetra PX 250 500 kW 400 480 V 990 2748E 001 5 Press the Save FW Versions list button to save the firmware version list as an HTML file Press the button in the location column to open the Module Status Details screen for the particular module Symmetra PX UPS Mode Normal Operation APC System Mode On Eaa Firmware Overview Save FW Versions ay A e Module Locat Firmware Version Fi Install Status Intelligence Module dM No update active Redundant IM No update active Touch Screen Display No update active ID and Relay Card Update succeeded Ext Switchgear Card Update in progress Bypass Static Switch Restoring succeeded NMC Update failed FW Firmware Reboot the Display 1 Press the reboot button at the bottom of the display to reboot the display 990 2748E 001 Symmetra PX 250 500 kW 400 480 V 53 Worldwide Customer Support Customer support for this or any other product is available at no charge e Contact the Customer Support Center by telephone or e mail For local country specific centers go to www apc com support c
20. as changed to Normal Operation in the upper right corner Access a Configured Network Management Card a web interface It is also possible to use the following interfaces Telnet and SSH SNMP FTP and SCP See the Network Management Card Installation Manual for more information Q Note The below procedure shows how to access the Network Management Card from Q Note Ensure that only one NMC in the entire system is set to synchronize time Use Microsoft Internet Explorer IE 7 x or higher on Windows operating systems only or Mozilla Firefox 3 0 6 or higher on all operating systems to access the Web interface of the Network Management Card Other commonly available browsers may work but have not been fully tested by APC You can use either of the following protocols when you use the Web interface e The HTTP protocol enabled by default which provides authentication by user name and password but no encryption e The HTTPS protocol which provides extra security through Secure Socket Layer SSL encrypts user names passwords and data being transmitted and authenticates Network Management Cards by means of digital certificates To access the Web interface and configure the security of your device on the network 1 Address the Network Management Card by its IP address or its DNS name if a DNS name is configured 2 Enter the user name and password by default apc and apc for an Administrator 3 To e
21. atic A Q1aups1 Q5bups1 Output UPS 3 Q1bups1 400 V Q5c 260 A System Redundancy N 1 Q2c Qtc 741 KVA System Load UPS Load 75 Q5dups4 UPS Runtime Available 0A UPS Ambient Temperature UPS Mode Normal Operation System Mode 0 System Information Configuration ooe a Language Press the Static Bypass gt Normal Op button on the Operation screen Single System Parallel System UPS Mode Normal Operation Symmetra PX UPS Mode Normal Operation Symmetra PX System Mode On APCO System Mode On by Schneider Electric A Operation UPS 1 Operation Static Bypass gt Normal Op J Normal Op gt Static Bypass Static Bypass gt Normal Op Normal Op gt Static Bypass Isolate this UPS 4 Press the Initiate Transfer button to go to normal operation The Initiate Transfer button gt is greyed out when transfer is not available Check that the status has changed to Normal Operation in the upper right corner 990 2748E 001 Symmetra PX 250 500 kW 400 480 V 19 Isolate this Single UPS from the Parallel System Note Before you start this procedure ensure that the remaining UPS units can supply the load Note This procedure is only applicable to parallel systems Note Press the home button to go to the Parallel System Summary screen l Press the UPS System button in the bottom left corner to access the UPS System screen Symmetra PX by Schneider Electric UPS 4 20
22. calibration The status of the runtime calibration is Shown under Runtime calibration status UPS Mode Normal Operation System Mode Q Battery runtime calibration Battery self test Start Auto battery self test every n weeks Never disabled x Auto battery self test start time HH mm ss 00 00 00 Auto battery self test day of week Monday Reset battery test alarms Reset ORAY Set the Battery Test Settings The battery self test simulates the battery mode of operation If AC utility mains power fails during the test the test stops and the UPS supplies battery power The test detects any weak or defective battery cells To do this the load must be high enough to draw sufficient current which in turn causes the voltage to drop to a low level The following criteria should be met to ensure your search detects any weak battery cells e The total discharge current to the load from both the positive and negative sides of the batteries needs to be at least half of the rated battery Ah which is determined by the number of installed battery strings For example if you have 18 Ah of batteries more than 9 A must be drawn by the load from each battery side e Both the positive and negative battery voltage must be lower than 280 V for longer than 16 seconds 26 Symmetra PX 250 500 kW 400 480 V 990 2748E 001 The test lasts for approximately 10 of the available runtime 1 Go to the User Confi
23. dible alarms Enable or disable audible alarms 1 Enable APC Q breaker prefix Enable or disable the display of the APC Q breaker prefix before the breaker name e g Q1 for the main input breaker 28 Symmetra PX 250 500 kW 400 480 V 990 2748E 001 Set the Network Management Card NMC Settings 3 Go to the User Configuration screen by following the steps in Access the User Configuration Screen Press the NMC Settings button on the User Configuration screen to access the NMC Settings screen Symmetra PX UPS Mode Normal Operation APC System Mode On cron User Configuration Battery Test Settings Display Settings NMC Settings a System Time Settings A E Password Settings Alarm Settings v The NMC Settings screen displays the configuration for each NMC in the system Press the Configure NMC Settings button to access the Configure NMC Settings screen and to change the settings Arc NMC Level 4 Position B UPS configuration access Network settings mode IP address 123 1 Modbus RTU NMC Level 5 Position B by Schneider Electric NMC Settings 11 33 UPS configuration access Read only UPS configuration access No access Network settings mode DHCP Network settings mode BootP IP address 145 215 101 145 IP address 0 0 0 0 Modbus RTU Enabled Modbus RTU Disabled Symmetra PX Alarm Warning ae 900 NMC Level 4 Position G No access UPS configuration access Readi
24. e On Parallel System System Redundancy N 1 System Load UPS Mode Normal Operation Symmetra PX e On System Mod APC A A Operation System Start up Static Bypass gt Normal Op Symmetra PX 250 500 kW 400 480 V UPS Mode Normal Operation System Mode On System Shutdown Normal Op gt Static Bypass Isolate this UPS 13 14 5 Follow the steps which appear on the screen Steps will appear in the order in which they need to be completed A step will initially appear in red and then when it is completed the step will change to green The next step to be completed will be highlighted in red text and yellow background Note Grey buttons are touch screen functions Single System Parallel System Symmetra PX UPS Mode Off Symmetra PX System Mode Maint Byp APC S Mode Maint Byp ystem Mode Maintenance ass ystem Mode Maintenance as by Setmetder esi System Start up UPS 1 System Start up 08 AA Start System from Maintenance Bypass Start System from Maintenance Bypass A Number Step Action Description 1 Close breaker 01 Ox Apply AC utility power 1 Close breaker 01 aQx Apply AC utility power 2 eebeaaragoe sawn 3 Close battery breakers Close Battery Breakers Close battery breakers Close Battery Breakers Number Step Action Description 4 Switch on UPS UPS On Switch on UPS UPS On Please repeat sequence 1 to 4 for the other parallel UPSs you want to start up before continuing to th
25. e active Power Module 4 20 0 49 No update active Power Module 4 20 0 49 No update active Power Module 4 20 0 49 No update active Power Module 4 20 0 49 No update active Power Module 4 20 0 49 No update active 990 2748E 001 Symmetra PX 250 500 kW 400 480 V Al Activate the power module by turning the locking latch clockwise to the locked position The LED in the top right corner of the power module will start to flash green which indicates that the power module is initializing and doing a self test When the self test is complete the LED will be constant green Replace Intelligence Modules A 42 Identify the faulty intelligence module via the display or red LED indication Loosen the two screws in one of the intelligence modules one in the top and one through the disable button at the bottom of the intelligence module Press down the disable button to loosen and deactivate the intelligence module Carefully insert the new module into the slot Enable the button to close and activate the intelligence module and the LED will flash green When the initialization is complete the LED will be solid green Fasten the two screws to secure the intelligence module WARNING Only trained persons familiar with the construction and operation of the equipment as well as the electrical and mechanical hazards involved may install and remove system components WARNING Before replacing the intel
26. e next step Initiate transfer to static bypass initiate Transfer Initiate transfer to static bypass Initiate Transfer Close breaker Q20x UPS output Glows breniier Auli URS aigput Please repeat step 6 for the other parallel UPSs you want to start up before continuing to the next step Close breaker Q4Qx System output Close breaker Q4Qx System output Open breaker 30x Static bypass Open breaker Q30x Static bypass Transfer load to normal operation Output On Transfer load to normal operation Output On 6 Check that the UPS Mode is Normal Operation in the upper right corner Symmetra PX 250 500 kW 400 480 V 990 2748E 001 Shut Down System from Normal to Maintenance Bypass Operation Note Press the home button to go to the UPS Summary or Parallel System Summary screen 1 Press the UPS System button in the bottom left corner to access the UPS System screen Single System Parallel System UPS Mode Normal Operation Symmetra PX p ode Normal Operatio Symmetra PX On y x System Mode by Setmetder Fieri UPS Summary 54 Paralle d J J Q3MAINT3 Q2aups1 Q3 Bypass yp Qlaups1 Q5bups1 Q4LOAD44 400 V 260 A System Redundancy N 1 UPS Module Redundancy N 2 183 KVA 741 KVA UPS Load 74 System Load 75 UPS Runtime Available 5m Os 288 V 288 V 2 0A OA P UPS Ambient Temperature 20 C Idups4 UPS Mode Normal Operation System Mode 0 System Information Co
27. erity Power enclosure 1 level 3 01 01 2000 Power module input voltage error high voltage 00 00 00 000 Power 3 01 01 2000 Power module input phase sequence OK 1 level 00 00 00 000 01 01 2000 Power module input phase sequence error Power enclosure 1 level 4 00 00 00 000 Power module input contactor and PFC FET are ok Power enclosure 1 level 6 01 01 2000 00 00 00 000 Power module input contactor or PFC FET error Power enclosure 2 level 6 01 01 2000 00 00 00 000 Power module synchronization OK Power enclosure 1 level 01 01 2000 6 Press the Filter button to filter the event log or go directly to step 9 to save the event log UPS Mode Normal Operation System Mode On e Symmetra PX by Schneider Electric UPS 1 Event Log 45 Critical Refresh Save Log Filter amp 375 Warning 2113 Informational Active Controller MIM Y No filters active a Event Location gies Severity WN HH mm ss SSS RTC Time old value Power enclosure 1 level 10 Capture 11 30 2009 12 30 07 974 11 30 2009 12 30 05 997 Power module lifetime error lifetime exceeded 11 30 2009 12 30 05 997 Power enclosure 1 level 10 Power module fan lifetime error corrected 11 30 2009 Synchronization OK to bypass 12 29 54 650 11 30 2009 12 29 52 499 Bonding wire between neutral and ground error sense 10 enclos
28. ettings 990 2748E 001 Symmetra PX 250 500 kW 400 480 V 27 Set the Display Settings l Go to the User Configuration screen by following the steps in Access the User Configuration Screen 2 Press the Display Settings button on the User Configuration screen to access the Display Settings screen UPS Mode Normal Operation System Mode On User Configuration Battery Test Settings Display Settings NMC Settings 3 Set the display settings UPS Mode Normal Operation System Mode On Display Settings Temperature unit Fc x Enable audible buttons Back light time out 5 minutes NA Enable audible alarms Date format MM dd yyyy x Enable APC Q breaker prefix Waveform voltage label Phase to Neutral x Recalibrate touch screen Stan a Brightness Place the finger on the indicator and slide it left or right to the desired setting b Temperature unit Select C for Centigrade or F for Fahrenheit c Back light time out Select the time limit for turning off the screen back light d Date format Select the preferred setting e Waveform voltage label Select phase to phase or phase to neutral f Recalibrate touch screen Press the Start button to initiate the calibration of the screen Press the points that are shown on the screen to calibrate the touch area of the display g Enable audible buttons Enable or disable audible buttons h Enable au
29. gional Settings 0 0 cece ccceeeeeeesseeeeees 34 VV AVENE TAN Cio siete boas ee eds eee aa ne 36 Access Predictive Maintenance Screen cccccccccescceeeseeeeesseeeesteeeeeeeeens 36 Determine if you need a Replacement Part 0 0 0 cc cccceesseeeeeeeeens 37 Return Parts to APC 0 0 00 cccccccccsscccsssesenesseeeesseeeeeseeeeseseecneseeeeesseeseesaesensaees 38 User Replaceable Parts ice coc cictcicncdess aca A ealede ti halter UiirniniieonteieeaheieSods 38 Battery Module Replacement cccccccccccceceeeeeeeeeeeeseeeeeseeseeeeeeeneees 38 Directions for Replacement icsisiseskscdeks estes hectic lcs Siedehudedadehd auobetesedteiascedad 38 Directions for Storage cerea ase aterive salts ene ese aaa sean eal 39 Replace Batenies csi ceneno sa di a E E oa 40 Replace Power MOQUICS iced tiie bwin es ere oe eras 40 Replace Intelligence Modules cccccccccccceeeeeeseeeeeeeeeeseeeeeeeeeeens 42 Replace Boards in Input Output Bypass Enclosure 00 00 cece 43 Replace Boards in the Battery Enclosure 00000 i cccccccseeeessssseseeereees 44 Troubleshooting 0 0 ccccececcscsscscsesscsecscsescsecsssessssesscsesssseeecsesssseesseeeses 45 Ala MS ena ere ee een re rare eee eT om re ee eee or eee eee 45 Alarm BUELON a5 eho hc8 chic oadiccd 08 E gona bus saan a wate E E A 45 Alarm Levels ss csicctanvasiealsecnialeaticeb sarees eens cabs ST ied sons aes oes 45 View the Active Alarms cccccccsssssccce
30. gt Go to the Parallel System Summary screen e Go to the previous screen aoe COnmmy Log out of password protected screens 4 Symmetra PX 250 500 kW 400 480 V 990 2748E 001 Operation Modes UPS Modes The UPS operation mode is indicated in the top right corner of the screen under the heading UPS Mode The UPS mode indicates the current status of the operated UPS Normal Operation During normal operation the UPS supports the critical load with conditioned power While the UPS is operating in normal operation a single line diagram will appear on the screen A green line indicates the power flow from the utility mains through the UPS system and to the load The green line to the batteries indicates that the batteries are connected Single System Parallel System UPS Mode Normal Operation Symmetra PX de On System Mode Arc abana UPS Summary Symmetra PX UPS Mode Normal Operation System Mode On by Sel QSaups1 Q2aups1 Bypass he Q1taups1 QS5bups1 rae Q1ibups1 Q5c UPS 3 Q2c Qic Q4L0AD44 400 V 260 A em Redundan N 1 UPS Module Redundancy N 2 2d 183 KVA 741 KVA UPS Load em Load QS5dups4 UPS 4 ii 75 UPS Runtime Available 5m 0s a Q2dups4 288 V 288 V 7 N 0A OA Ups ambient Tem 1dups4 s perature 20 C Qidups Symmetra PX UPS Mode Normal Operation APC System Mode On Ipsa ME Ea A Bypass
31. guration screen by following the steps in Access the User Configuration Screen 2 Press the Battery Test Settings button on the User Configuration screen to access the Battery Test Settings screen UPS Mode Normal Operation System Mode Op User Configuration Battery Test Settings Display Settings NMC Settings 3 Set the battery test settings UPS Mode Normal Operation System Mode Q Battery Test Settings Battery runtime calibration Start Battery self test Start Auto battery self test every n weeks Never disabled nas Auto battery self test start time HH mm ss 00 00 00 Auto battery self test day of week Monday ani Reset battery test alarms Reset j ix a Battery self test Press Start to begin the battery self test immediately You can press Cancel to stop the self test and continue in normal operation The status of the self test is shown under Self test information b Auto battery self test every n weeks Select the time in weeks between automatic battery self tests APC recommends a battery self test every 12 weeks c Auto battery self test start time HH mm ss Select the time of the day the battery self test must start d Auto battery self test day of week Select the day of the week the battery self test must start e Reset battery test alarms Press the Reset button to reset the battery alarms 4 Press Apply to confirm the s
32. he System Information screen Use three people to lift components weighing between 32 54 kg 70 120 Ibs Symmetra PX 250 500 kW 400 480 V 990 2748E 001 Identify the faulty power module via the display or the red LED indication in the top right corner of the power module Deactivate the power module by turning the locking latch counter clockwise to the unlocked position Unscrew the spring activated knobs on both sides of the power module Pull the power module up and out of the enclosure as far as the lock mechanism allows Release the lock by pressing the black plastic tab on each side of the power module and pull the power module all the way out Carefully guide the new power module completely into the system Secure the spring activated knobs on both sides of the power module Wait until the firmware update is complete and ensure that the new power module has the same firmware version as the other power modules in the UPS system a On the UPS Summary or the Parallel System Summary screen press the UPS System button in the bottom left corner b Press the System Information button on the UPS System screen c Press the Firmware Overview button to open the Firmware Overview screen d Verify that the firmware versions is the same Symmetra PX UPS Mode Normal Operation m Mode On Syste 09 59 UPS4 Firmware Overview Module lk Firmware Version FW Install Status a Power Module 4 20 0 49 No updat
33. ive 2 Write down the serial number of the unit so that you will have it easily accessible when you contact APC Customer Support 3 Ifpossible call APC Customer Support from a telephone that is within reach of the UPS display interface so that you can gather and report additional information to the representative 4 Be prepared to provide a detailed description of the problem A representative will help you solve the problem over the telephone if possible or will assign a return material authorization RMA number to you If a module is returned to APC this RMA number must be clearly printed on the outside of the package 5 Ifthe unit is within the warranty period repairs or replacements will be performed free of charge If it is not within the warranty period there will be a charge 6 Ifthe unit is covered by an APC service contract have the contract available to provide information to the representative 990 2748E 001 Symmetra PX 250 500 kW 400 480 V 37 Return Parts to APC Call APC Customer Support to obtain an RMA number To return a failed module to APC pack the module in the original shipping materials and return it by insured prepaid carrier The APC Customer Support representative will provide the destination address If you no longer have the original shipping materials ask the representative about obtaining a new set Pack the module properly to avoid damage in transit Never use styrofoam beads or other loose
34. l Bypass Summary screens E Go to the Parallel Output Summary screens F Go to the UPS Summary screens 990 2748E 001 Symmetra PX 250 500 kW 400 480 V UPS Summary Screen Single System In single systems the UPS Summary screen is the home screen It provides you with an overview of the UPS system and circuit breakers It shows the system status and the power flow through the system and gives access to the system s summary screens and the UPS System screen A Access further details on the current screen z Go to the UPS System screen Q Go to the System Status screen for the current UPS Go to the Bypass Summary screens Go to the Input Summary screens Go to the Output Summary screens Go to the Battery Summary screens T mmg Log out of password protected screens Parallel System In parallel systems the UPS Summary screen provides you with an overview of the actual UPS and circuit breakers It shows the system status and the power flow through the UPS and gives access to the system s summary screens and the UPS System screen A Access further details on the current D screen A jap Go to the UPS System screen A oo QOO Go to the System Status screen for the current UPS Q W Go to the Bypass Summary screens Go to the Input Summary screens Go to the Output Summary screens Go to the Battery Summary screens o zs
35. le UPS serial number 0 0 0 0 Event Logs system firmware version 4 20 0 123 System firmware version stored at memory 4 20 0 123 by Schneider Electric 7 UPS 1 System Information card ii cin man APC support phone Enter phone number Predictive Maintenance Patents US 7 456 524 US 7 456 518 US 7 274 112 US 7 126 409 US 7 106 607 US 7 012 825 US 6 838 925 US 7 104 805 Patent Pending Copyright 2009 Schneider Electric All Rights Reserved 990 2748E 001 Symmetra PX 250 500 kW 400 480 V 47 4 Active in control indicates which intelligence module is in control of the system Press the Active Event Log button to view the records from the intelligence module in control or press the RIM Event Log to view the records from the intelligence module that is passive UPS Mode Normal Operation Symmetra PX System Mode On Arc by Schneider Electric Event Logs 13 37 O0 Active in control Intelligence module Active Event Log RIM Event Log 5 The Recent Events log contains a detailed record of the 32 latest events Press the Full Log button to see the 10000 latest events and access the Save Log button UPS Mode Normal Operation System Mode On a e Date Time Event Location MM dd HH mm ss SSS Symmetra PX by Schneider E eceris UPS 1 e Active Controller MIM Recent Events 3 Critical 3 Warning 19 Informational Capture Sev
36. ligence modules ensure that the UPS system firmware version and the System firmware version stored at memory card are identical on the System Information screen WARNING Replace only one intelligence module at a time Input Output Bypass Enclosure Symmetra PX 250 500 kW 400 480 V 990 2748E 001 Replace Boards in Input Output Bypass Enclosure WARNING Only trained persons familiar with the construction and operation of the equipment as well as the electrical and mechanical hazards involved may install and remove system components WARNING Before replacing the boards ensure that the UPS system firmware version and the System firmware version stored at memory card are identical on the System Information screen WARNING Replace only one board at a time Note A faulty system power supply can be identified via the display or a flashing red LED indication oO gt e D pd Loosen the two four screws in the corners of Input Output Bypass Enclosure the board a External connection board b External switch gear board c System power supply d ID and relay controller NO Only applicable to the external connection board and the ID and relay controller remove the cables connected to the board 3 Carefully pull out the board aN Only applicable to ID and relay controller take the SD memory card from the old ID and relay controller and install it in the replacement ID and relay
37. ll automatically be silenced Alarm Levels Info Symmetra PX UPS Mode Normal Operation APC System Mode On by Schneider Electric UPS 4 Parallel System Summary iN 54 Q3MAINT3 QS5aups1 Q2aups1 Q1laups1 QS5bups1 UPS 2 pa Q2bups1 ZS bups1 PS 3 Qic Q4LOAD44 Q1 Q5c uU UPS 4 System Redundancy N 1 ra 741 KVA System Load 75 Q5dups4 EH Isr J a KERA Q2dups4 Qidups4 Warning S tra PX 8 a ymmetra PX Alarm Warnin g s TES ae nanes Operation by Schneider Electric UPS 4 Parallel System Summary Q3MAINT3 Q5aups1 Q2aups1 Q1aups1 Q5bups1 a Sa ae Q1bups1 System Redundancy N 1 System Load Q2dups4 Qidups4 Informational alarm No immediate action required Check the cause of the alarm as soon as possible The load remains supported but action must be taken Call APC for instructions 990 2748E 001 Symmetra PX 250 500 kW 400 480 V Critical instructions by Schneider Electr UPS 4 Parallel System Summary Synneva Px s 2 4 Take immediate action Call APC for Q3MAINT3 0A 400 V Q5aups1 Q2aups1 Q1aups1 1037 A 400 V Q2bups1 Q4L0AD44 Q5bups1 1086 A 400 V System Redundancy System Load Q2dups4 Qidups4 View the Active Alarms l Press the Alarm button on the top bar when an alarm situation occurs Symmetra PX UPS Mode Normal Operation Alarm Critical Syste
38. ll turn off when the UPS input breaker Q1 is opened Add UPS to a Running Parallel System 1 Close the UPS input breaker Q1 This will power up the UPS display 2 When the screen becomes active verify that all UPS is set up as a parallel system and that all units are shown on the screen 990 2748E 001 Symmetra PX 250 500 kW 400 480 V 3 Press the UPS System button in the bottom left corner to access the UPS System screen Off UPS Mode System Mode 4 Symmetra PX Qlaups1 Q5bups1 UPS 2 rae ESen Q1bups1 Q5c System Redundancy N 1 Qic System Load Q5dups4 Q2dups4 i 4 Press the Operation button Type in the user password and complete with Enter Symmetra PX UPS Mode Normal Operation APC System Mode 0 UPSI UPS System gt System Information Configuration a Language 5 Press System Start up button Symmetra PX UPS Mode Normal Operation APC System Mode On Operation System Start up System Shutdown Static Bypass gt Normal Op Normal Op gt Static Bypass Isolate this UPS 22 Symmetra PX 250 500 kW 400 480 V 990 2748E 001 6 Follow the steps which appear on the screen Steps will appear in the order in which they need to be completed A step will initially appear in red and then when it is completed the step will change to green The next step to be completed will be highlighted in red text and yellow background 7 Check that the UPS Mode h
39. m Mode On by Schneider cers UPS 4 Parallel System Summary Q3MAINT3 QS5aups1 Q2aups1 1037 A 400 V Q5bups1 Q2bups1 Qibups1 System Redundancy N 1 741 KVA System Load 75 Q5dups4 Q2dups4 Qidups4 2 A list of the active alarms is shown on the screen Press the Location button to see the location of the particular module Press the Graph button to see voltages and currents at the time the alarm was generated The three alarm severity icons display at the top of the screen with numbers indicating how many times each severity type has occurred Press on that icon or number to display the next alarm of that severity type on the screen When you reach the final alarm pressing the icon displays the first one of the same severity UPS Mode Normal Operation System Mode Q Symmetra PX ANE Var Gia later by Sel Active Alarms 08 08 hnelder Elect 0 Critical Refresh Event Log RIM Alarms 21 Warning A 0 Informational q Active Controller IM Alarm Corrective Action Location Taal he Capture aay HH mm ss S55 aa 01 01 2000 Overload on bypass static switch Reduce load on system ARENA 01 01 2000 00 00 00 002 PSU module failed Replace module Please contact APC Support Graph D 01 01 2000 a Power module communication to 00 00 00 003 MIM error n 01 01 2000 Power
40. mark a sixth entry in the event log the following screen will be shown 50 Symmetra PX 250 500 kW 400 480 V 990 2748E 001 Symmetra PX Arc Aa ton Event Log UPS Mode Normal Operation System Mode On 45 Critical Refresh Save Log Filter 375 Warning Active Controller MIM 2113 Informational D Q i a Severity RTC Time old valu existing bookmarks to remove them 1 by 1 The maximum number of bookmarks has been reached Press Remove All to delete all current bookmarks Press Cancel and press twice on Power module lifet Remove All Cancel Power module fan Synchronization OK to bypass 11 30 2009 12 29 54 650 aS Bei A Battery temperature sensor 2 fault BBE enclosure 1153052099 level 1 12 29 52 437 You can choose to remove all existing bookmarks by pressing the Remove All button or click Cancel to remove them one by one Press twice on the log entry to clear a bookmark View and Save Information about Firmware Version Note Press the home button to go to the UPS Summary or Parallel System Summary screen 1 Press the UPS system button in the bottom left corner to access the UPS System screen Single System by Schneider Electric Symmetra PX by Schneider Electric UPS 1 990 2748E 001 Symmetra PX UPS Mode Normal Operation Arc fi I UPS Runtime Available 5m Os 288 V 288 V OA OA ups ambient Tem c
41. ms Contact APC 1f this feature should be enabled 990 2748E 001 Symmetra PX 250 500 kW 400 480 V Operation Procedures Access Screens Protected by User Password 1 When prompted for the user password press the password field to access the keyboard UPS Mode Normal Operation System Mode On 2 Type in the user password and press Enter Enter password Copy Paste Clear Tab 1 2 3 4A 8 8 LZ 8 9 0 _Backspace_ D GED a Ged a SS SE SS ES SS a GE ES o GD GES SE Sts Gs EUs o ES Gis Ep a Se Ss Q Note On installation the user password is set to apc 12 Symmetra PX 250 500 kW 400 480 V 990 2748E 001 Start Up System from Maintenance Bypass Operation Note Start up condition The load is supplied via the Q3 switch from the utility mains and the other breakers are open 1 Close the UPS input breaker Q1 This will power up the UPS display 2 Press the UPS System button in the bottom left corner to access the UPS System screen Single System Symmetra PX Arc ipsamuea Baan UPS Summary Output Parallel System Symmetra PX UPS Module Redundancy N 0 UPS Load UPS Runtime Available vV 0 KVA 0 Os OA UPS Ambient Temperature 0 C 3 System Information Configuration a lt Language 4 Press System Start up button Single System Symmetra PX Arc Saee Operation 990 2748E 001 UPS Mode Normal Operation System Mod
42. nable or disable the HTTP or HTTPS protocol use the Network menu on the Administration tab and select the Access option under the Web heading on the left navigation menu 990 2748E 001 Symmetra PX 250 500 kW 400 480 V 2 See See the Security Handbook available on the APC Network Management Card Utility CD or from the APC Web site www apc com for more information on selecting and configuring network security Operate the APC Battery Breaker Manually j9 il l Turn the selector to Manual position 2 Check the spring status a If CHARGED SPRING go to step 3 b If DISCHARGED charge the spring by pressing the bottom part of the handle to release it and pumping the handle a few times until the spring status says CHARGED SPRING 3 Push the green ON button to turn the breaker on A red ON indication will show the breaker Status 24 Symmetra PX 250 500 kW 400 480 V 990 2748E 001 Configuration Access the User Configuration Screen The UPS system is configured from the password protected user configuration area of the display 1 Press the UPS system button in the bottom left corner to access the UPS System screen Single System Symmetra PX Arc ipeanden eat UPS Summary Q3 Bypass System Information Configuration Language 3 Press the User Configuration button on the Configuration screen
43. nfiguration Cee la Language 3 Press the System Shutdown button on the Operation screen Single System Parallel System UPS Mode Normal Operation Symmetra PX UPS Mode Normal Operation Symmetra PX System Mode On APC System Mode On Schnei Electric System Shutdown Normal Op gt Static Bypass 990 2748E 001 Symmetra PX 250 500 kW 400 480 V 15 4 Follow the steps which appear on the screen Steps will appear in the order in which they need to be completed A step will initially appear in red and then when it is completed the step will change to green The next step to be completed will be highlighted in red text and yellow background Note Grey buttons are touch screen functions Single System Parallel System Symmetra PX Sten Mone _ Operation Symmetra PX ones Mode Normal Operation Arc Ar c iaae ar System Shutdown System Shutdown Shutdown System to Maintenance Bypass Shutdown System to Maintenance Bypass O 2 Number Step Action Description Number Step Action Description 1 Initiate Transfer 1 Initiate Transfer 2 Close breaker Q3Qx Load will be on manual bypass Close breaker Q3Qx Load will be on manual bypass Open breaker 040x System output Switch off UPS UPS Off Switch off UPS UPS Off Open breaker Q20x UPS output Open breaker Q2aQx UPS output Open breaker O5aQx SSW input Open breaker 50x SSW input Open battery breakers Open Battery Breakers Open battery breaker
44. nput Summary Parallel Bypass Summary Parallel Output Summary UPS System UPS Summary UPS Input Summary UPS Bypass Summary UPS Battery Summary System Status Subfeed Summary UPS Output Summary UPS System System Information System Status Event Log Firmware Overview Predictive Maintenance Configuration User Configuration Service Configuration Factory Configuration Operation Start Up Shutdown Transfer to normal operation Transfer to static bypass Isolate this UPS Language Settings Regional Settings 2 Symmetra PX 250 500 kW 400 480 V 990 2748E 001 Symbols used WARNING Indicates an electrical hazard which if not avoided could result in injury or death i Caution Indicates a hazard which if not avoided could result in injury or death Q Note Indicates important information See Indicates that more information is available on this subject Parallel System Summary The Parallel System Summary screen is the home screen in parallel systems It provides you with an overview of the parallel system and circuit breakers It shows the system status and the power flow through the system and gives access to the system s summary screens Q Note The operated UPS is highlighted on the screen and the other UPS units are faded A Access further details on the current screen B Go to the UPS System screen C Go to the Parallel Input Summary screens D Go to the Paralle
45. odule Redundancy N 2 UPS 4 Load UPS 4 Runtime Available 990 2748E 001 Symmetra PX 250 500 kW 400 480 V Battery test The UPS is in battery test mode when the UPS is performing a battery self test During battery test the battery runtime capacity is reduced by 10 Note The battery test will stop if the mains supply fails during the test Single System Symmetra PX by Schneider Electr e UPS Summary Bypass Output 400 V 257 A UPS Module Redundancy UPS Load UPS Runtime Available 288 V 260 A UPS Ambient Temperature 8 Symmetra PX 250 500 kW 400 480 V UPS Mode Battery Test System Mode On N 2 183 KVA 74 5m Os 20 C Parallel System Symmetra PX UPS Mode Battery Test System Mode On ji by Schneider Electric UPS 4 Parallel System Summary Q3MAINT3 OA Q5aups1 Q2aups1 Q1aups1 Q5bups1 UPS 2 2a Q2bups1 Q4L0AD44 Q1bups1 UPS 3 System Redundancy N 1 741 KVA System Load 75 Q5dups4 Q2dups4 Q1dups4 or UPS Mode Battery Test System Mode On l Output Symmetra PX UPS 4 Summary Bypass 400 V 260 A UPS 4 Module Redundancy UPS 4 Load UPS 4 Runtime Available 288 V UPS 4 Ambient Temperature 260 A 990 2748E 001 System Modes The system mode is indicated in the top right corner of the screen under the heading System Mode The system mode indicates the current
46. ontact for contact information APC by Schneider Electric APC and the APC logo are owned by Schneider Electric Industries S A S American Power Conversion Corporation or their affiliated companies All other trademarks are property of their respective owners 990 2748E 001 10 2010
47. ormal Operation Configure NMC Modbus System Mode Settings NMC Level 4 Position B FH enable Modbus RTU Modbus RTU address Baud rate Bits s Parity a Select the Enable Modbus RTU box to enable the use of Modbus RTU b Specify the BMS address of the NMC device Only a BMS Manager should modify this address c Specify the Baud rate of the modbus communication port d Specify the Parity of the modbus communication port Press Apply to confirm the settings Set the User Password Settings 30 l Go to the User Configuration screen by following the steps in Access the User Configuration Screen Press the Password Settings button on the User Configuration screen to access the Password Settings screen UPS Mode Normal Operation System Mode Ox User Configuration Battery Test Settings Display Settings NMC Settings System Time Settings Symmetra PX 250 500 kW 400 480 V 990 2748E 001 3 Change the user password UPS Mode Normal Operation System Mode On Symmetra PX APC Sreara ay Password Settings anne A a Press the Enter current password field and type the current password by using the keyboard on the screen Complete with Enter b Press the Enter new password field and type the new password by using the keyboard on the screen Complete with Enter c Press the Confirm new password field and
48. re present Set the load percentage for each subfeed breaker that should generate a warning alarm UPS Mode Normal Operation Symmetra PX p System Mode On Arc by Schneider Electric Alarm Settings Subfeed Warning Levels SB7 load warning 9 hoo SB6 load warning 9 L B13 load warning 69 100 i B14 load warning 69 NE a l SB15 load warnin SB16 load warnin g 69 100 g 69 Apply Page 3 of 3 8 Press Apply to confirm the settings Set the System Time Note The date and time will be synchronized between the UPS units in a parallel system 1 Go to the User Configuration screen by following the steps in Access the User Configuration Screen 2 Press the System Time Settings button on the User Configuration screen to access the System Time Settings screen The System Time Settings screen can also be accessed by pressing on the time displayed in the top right corner of the screen UPS Mode Normal Operation Symmetra PX E System Mode On User Configuration oaa by Schneider Electric Battery Test Settings Display Settings NMC Settings 990 2748E 001 Symmetra PX 250 500 kW 400 480 V 33 3 Set the system date and the system time Symmetra PX UPS Mode Normal Operation System Mode On 900 System Time Settings System date MM dd yyyy lo1 01 2000 _ System time HH mm ss 10 00
49. re type the new password Confirm with Enter 4 Press Apply to complete the password change procedure Set the Alarm Settings 1 Go to the User Configuration screen by following the steps in Access the User Configuration Screen 2 Press the Alarm Settings button on the User Configuration screen to access the Alarm Settings screen s UPS Mode Normal Operation Symmetra PX s System Mode Op APC by Schneider Electric User Configuration Sin Battery Test Settings Display Settings NMC Settings 990 2748E 001 Symmetra PX 250 500 kW 400 480 V 31 3 Set the threshold values that must trigger the alarms Note For parallel systems shared settings are marked with Single System Parallel System P ode Battery Operatio ra UPS Mode Battery Test Symmetra PX et APC i s System Mode by Schneider E eceri lt Aid gt U 00 00 Neo v UPS module redundancy UPS module redundancy Load alarm threshold 90 Parallel system redundancy Low battery alarm threshold seconds h 80 kais Load alarm threshold Low battery alarm threshold seconds 1800 Anni Settings with a blue asterisk will be Apply PPI applied to all parallel UPSs a UPS module redundancy Set the system threshold for generating alarms in the redundant power modules N 0 indicates that the redundancy alarm is disabled N 1 indicate
50. rrected mane 1 level 12 30 05 997 ae 11 30 2009 Synchronization OK to bypass 42 29 54 650 Bonding wire between neutral and ground error sense 10 enclosure 11 30 2009 cable is unplugged level 2 42 29 52 499 BBE enclosure 11 30 2009 Battery temperature sensor 2 fault 12 29 52 437 All files are saved in a single compressed Zip file to the USB flash drive Bookmark an Entry in the Event Log A maximum of five entries can be bookmarked in the system Symmetra PX UPS Mode Normal Operation APC System Mode On by Schneider Eisctrie UPS 1 Event Log 45 Critical Refresh Save Log Filter amp 375 Warning 2113 Informational Active Controller MIM Y No filters active P Dater ime Location Capture Severity Mady HH mm ss SSS l 11 30 2009 RTC Time old value 12 30 07 974 Power 12 30 05 997 om Ee Power module lifetime error lifetime exceeded enclosure 1 level 11 30 2009 10 Power SEN 11 30 2009 Power module fan lifetime error corrected peis 1 level 12 30 05 997 Ha 11 30 2009 Synchronization OK to bypass 12 29 54 650 BBE enclosure 11 30 2009 Battery temperature sensor 2 fault level 4 12 29 52 437 1 Double press on an event in the event log to bookmark a log entry 2 Bookmarked entries are highlighted in a darker background colour 3 Press the Bookmark symbol to cycle through the bookmarks If you try to book
51. s Open Battery Breakers Open breaker Q1aQx UPS input Open breaker Q10x UPS input Please repeat sequence 4 to 8 for the other parallel UPSs you want to shutdown Note The display will switch off after all steps have been completed Note The display will switch off after all steps have been completed Note The display will turn off when the UPS input breaker Q1 is opened Caution Do not open the Q3 breaker when the system is in maintenance bypass operation as it may result in a load drop 16 Symmetra PX 250 500 kW 400 480 V 990 2748E 001 Transfer from Normal to Requested Static Bypass Operation Note Following this procedure will transfer the entire parallel system to requested static bypass Note Press the home button to go to the UPS Summary or Parallel System Summary screen 1 Press the UPS system button in the bottom left corner to access the UPS System screen Single System Symmetra PX APC by Schneider Electric UPS Summary 238V i 288 V Parallel System UPS Mode Normal Operation Symmetra PX em Mode On by Schneider Electric UPS 4 400 V 260 A UPS Module Redundancy UPS Load UPS Runtime Available UPS Ambient Temperature Parallel System Summary Q3MAINT3 a UPS Mode Normal Operation System Mode On QLOAD H UPS Mode Normal Operation System Mode O 990 2748E 001 Symmetra PX 250
52. s that there must be one redundant power module b Parallel system redundancy Set the number of redundant UPS units in a parallel system If you have a parallel system with UPS redundancy you can use this field to configure an alarm to generate when the load in your parallel system starts using some of the UPS redundant power N 0 indicates that there is no redundant power and N 1 indicates that there is one UPS of redundant power c Load alarm threshold Set the threshold for load percentage of the total UPS capacity for generating an alarm d Low battery alarm threshold seconds Set the remaining battery runtime threshold for generating an alarm 4 Press Apply to confirm the settings and press arrow down to go to the next Alarm Settings screen 5 This screen is only visible if subfeed breakers are present Set the load percentage for each subfeed breaker that should generate a critical alarm UPS Mode Normal Operation System Mode On Alarm Settings Subfeed Critical Levels SB load critical 100 a SB6 load critical 39 B13 load critical 9 100 Ca SB14 load critical 9 B15 load critical 9 100 SB16 load critical 9 Page 2 of 3 6 Press Apply to confirm the settings and press arrow down to go to the next Alarm Settings screen 32 Symmetra PX 250 500 kW 400 480 V 990 2748E 001 7 This screen is only visible if subfeed breakers a
53. ssssnsceecssssceecesscseeeeecessnsseeesesssseeesessanes 46 VIEW ING EVEN LOG aerua a al tener a a 47 Bookmark an Entry in the Event Log 0 00 i cccccccccceeeeeeeeeeeesseeeeeeenens 50 View and Save Information about Firmware Version ccccccccsseeee 51 Reboot the Display siscs onsen ansrtece an are station coectneahteaakeacanntei aces Ytatseaneasdasdansaaavadansengagneee 53 ij Symmetra PX 250 500 kW 400 480 V 990 2748E 001 Overview Display Overview Q Note The screens shown in this manuals are examples only The UPS graphical user interface is located in the Input Output Bypass Enclosure The UPS utilizes the touch screen display to configure and monitor the system and provides the user with visible and audible alarms O The screens are organized hierarchically In parallel systems the Parallel System Summary screen is at the top of the hierarchy In single systems the UPS Summary screen is at the top of the hierarchy Overview of Breakers in the MBwD Option Q Note The MBwD is only applicable for single systems The APC MBwD contains the breakers Q1 Q2 Q3 and Q5 When the associated breaker lamp is lit it is ok to open and close the breaker Bypass Input Mains Input To Distribution Breakers 990 2748E 001 Symmetra PX 250 500 kW 400 480 V 1 Navigation Parallel System Summary Parallel I
54. tssseseseeseeess 12 Access Screens Protected by User Password l 12 Start Up System from Maintenance Bypass Operation 00 000 13 Shut Down System from Normal to Maintenance Bypass Operation 15 Transfer from Normal to Requested Static Bypass Operation 00 17 Transfer from Requested Static Bypass to Normal Operation 18 Isolate this Single UPS from the Parallel System 0000 ee 20 Add UPS to a Running Parallel System 0000 0000o eerren 21 Access a Configured Network Management Card 23 Operate the APC Battery Breaker Manually 24 Configuration parm eaten etree eenatrr tae te ten aren ten kttn ee kee are eee tt Seen ieee len i rete ats ree eye 25 Access the User Configuration Screen ccceccccccccecesssssseeeeeeesesseees 25 Perform a Battery Runtime Calibration 0 0 0000 oc ceccecccccceceeessseeeeeeeeens 26 990 2748E 001 Symmetra PX 250 500 kW 400 480 V i Set the Battery Test Settings 0000 00 00 cccccccessccecceeeessssseeeeeceeessesseeeees 26 Set the Display Settings i iicecsce neotenic ieee elnieeiaueand 28 Set the Network Management Card NMC Settings 0000 29 Set the User Password Settings 0 cece ccccccssssseceececeeessssseeeeeceeessstsneesees 30 Set the Alarm SettiNgS siidicseactsing ra ctavessecheimetacialaaestu ceca aedaanasihabe meaveshoe snanedtadcaancene 31 Set the System TIME ernan AN N T E AO 33 Set the Language and Re
55. ure cable is unplugged level 2 BBE enclosure 11 30 2009 5 Battery temperature sensor 2 fault level 4 12 29 52 437 48 Symmetra PX 250 500 kW 400 480 V 990 2748E 001 7 Select to filter the events by source location and or timestamp and press OK Symmetra PX Filter Options Arc Limit filter by event source Sel sider Electri Press on the event source checkbox Refresh to enable event source filter options Limit filter by event location Capture Severity Press on the location checkbox to enable location filter options ID amp Rel Limit filter by event timestamp ID amp Reli Power m Bypass Press on the timestamp checkbox to enable timestamp filter options Bypass Bypass Bypass Reset OK Cancel a Bynass 4 8 Set your filter parameters and press OK to initiate the filtering Filter Options Normal Operation System Mode O v Limit filter by event source _ Intelligence Module _ External Switchgear __ Power Module ID amp Relay Card Refresh 3 e F T _ Bypass Static Switch _ Battery Monitoring Board _ Aux Monitoring Board B Aux Monitoring Board M v Limit filter by event location Severity 7 Enclosure All Enclosures es ut A Battery i ar TNN