1. Base Tabs Bottom Slots Smart UPS VT Maintenance Bypass Panel w Power Distribution 10 30kVA 208V 990 4199B 13 Installation Front panel removal 1 Use a T30 Torx screwdriver to loosen the two 2 M6 Torx screws under the top lip of the front panel see graphic below for location of screws 2 Pull the top section of the panel away from the MBP enclosure 3 Holding the panel at an angle away from the enclosure lift the panel s two 2 base tabs out of the two 2 slots at the bottom of the enclosure 4 Set the panel on its side to disconnect the internal ground cable from the panel s ground stud Use an M10 nut driver to remove the M6 flange nut securing the cable to the stud 5 Store the panel and the M6 flange nut in a safe location for later re attachment M6 Torx Screws FRONT PANEL Ground Stud on inside of front panel ZA Bottom Slots Base Tabs 14 Smart UPS VT Maintenance Bypass Panel w Power Distribution 10 208V 990 4199B Installation Rear panel removal 0 The TOP and the BOTTOM rear panels are removed in exactly the same way Use the following procedure to remove each of the rear panels in its turn Note 1 Use a T30 Torx screwdriver to loosen the two 2 M6 Torx screws under the top lip of the panel see graphic below for location of screws
2. Smart UPS VT Maintenance Bypass Panel w Power Distribution 10 30kVA 208V 990 4199B 29 Operation Bypass operation Bypass operation allows the UPS to be serviced while the load is still being supported by the utility The heavier line in the graphic shows the flow of utility power when the UPS is in bypass operation To achieve bypass operation from normal operation 1 Transfer the UPS into static bypass mode using the UPS user interface Follow the procedure described in the Smart UPS VT 10 Operation Manual p n 990 1599 WARNING A Be sure to address the MBP switches steps 2 4 below in the EXACT order Warning specified in this procedure Q3 MUST be switched ON before Q2 is switched OFF Addressing the MBP switches in the wrong order will cause the load to drop 2 Switch Q3 ON 3 Switch Q2 OFF 4 Switch Q1 OFF Q1 UPS Input WARNING The UPS may still have power Electrical after being switched to bypass operation Before performing maintenance on the UPS follow the Total Power Off procedure described in the UPS Operation Manual UPS power MUST be turned OFF Q3 Bypass Q2 UPS Output 30 Smart UPS VT Maintenance Bypass Panel w Power Distribution 10 208V 990 4199B Operation Returning to normal operation To return to normal operation from bypass operation If power to the UPS was previously turned OFF for maintenance purposes it must
3. 33 APC product covered 33 Terms of warranty hn 33 Non transferable warranty extends to first purchaser for use 33 Assignment of warranties 33 Drawings 5 34 Warranty claims procedure 34 34 li Smart UPS VT Maintenance Bypass Panel w Power Distribution 10 208V 990 4199B Safety SAVE THESE INSTRUCTIONS This manual contains important instructions for the SUVT series that should be followed when handling the Maintenance Bypass Panel with Power Distribution floor Safety warnings A Warning Electrical Hazard WARNING Only APC trained personnel who are familiar with the construction and operation of this equipment as well as the mechanical and electrical hazards involved may perform this installation WARNING This installation must comply with the requirements of ANSI NFPA 75 and NEC NFPA 79 Art 645 WARNING All safety codes safety standards and other regulations must be strictly observed during installation and ongoing maintenance of this equipment WARNING Prior to installing the Smart UPS VT Maintenance Bypass Panel de energize all external power being supplied to the UPS WARNING Ensure that no electrical power is connected to the Maintenance Bypass Panel and that all switches are in the OFF position before installing
4. 208V 990 4199B 6 Product Overview Schematic without panel board _ God ooejelu 5 5 5 1 N v00X ayol 2 5 c 15281 104 sJojonpuoo 1eddoo Ajuo ap gt D LAdNI Sdn 9 21 N 200 9 1 21 100 4 4 P 7 Smart UPS VT Maintenance Bypass Panel w Power Distribution 10 208V 990 4199B Shipping Receiving and Unloading Shipping The floor versions of the Smart UPS VT MBP with Power Distribution are shipped bolted to a pallet and wrapped in packaging material A 13 14mm wrench is attached to the pallet A wooden ramp is also included Door keys and documentation are stored in a plastic sleeve inside the unit Wrench 13 14 Receiving 1 Upon receipt inspect the MBP for obvious signs of rough handling and or external damage DO NOT remove the packaging material until the MBP is off its pallet and ready for installation DO NOT remove the MBP enclosure from the pallet until all movement is completed A thorough internal inspection should be conducted only after the enclosure has been positioned for installation and prior to making electrical connections 8 Smart UPS VT Maintenance Bypass Panel w Power Distribution 10 208V 99
5. du Ns 9 Considerations 44 cs ee VEN VIRES I RE 11 Environmental 4 232 dex reet 11 inoa a ku Ree DR E E RU OR 11 InistallatlOD s x RE xd xdg 12 OvervieW 5 295443 12 LOOMS ms ha ee exe T ear ii e 12 Panel board breakers 12 Removing the front and rear panels 13 Mechanically connecting the MBP to the UPS 16 Anchoring the MBP optional 21 Internal cable connections 22 Making external cable connections 23 Re attaching the front and rear panels 25 Installing Panel Board 5 27 Smart UPS VT Maintenance Bypass Panel w Power Distribution 10 208V 990 4199B Operation oz oes UPS RESO E 28 Normal operating mode 28 Battery back up operation 29 Static bypass mode 29 Bypass operation 30 Returning to normal operation 31 Appendix A Changing 565 32 Removing fuses 32 Replacing 565 32 Limited Factory Warranty
6. 2 Pull the top section of the panel away from the MBP enclosure 3 Holding the panel at an angle away from the enclosure lift the panel s two 2 base tabs out of the two 2 slots at the bottom of that section of the enclosure middle or bottom 4 Disconnect the internal ground cable from the panel s ground stud Use an M10 nut driver to remove the M6 flange nut securing the cable to the stud 5 Store the panel and the M6 flange nut in a safe location for later re attachment M6 Torx Screws Base Tabs Bottom Slots TOP REAR PANEL M6 Torx Screws BOTTOM REAR PANEL Smart UPS VT Maintenance Bypass Panel w Power Distribution 10 30kVA 208V 990 4199B 15 Installation Mechanically connecting the MBP to the UPS The MBP can be mechanically connected to either the left or the right side of the UPS The UPS and the MBP can also be anchored in tandem using stabilizing brackets shipped with the UPS 1 If a stabilizing bracket was previously attached to the side of the UPS where the MBP will be mechanically connected remove the bracket Use an M10 nut driver to remove the four 4 M6 side screws and an appropriate tool to remove the floor anchors Set the bracket and all of its assembly hardware aside for later use If there is no stabilizing bracket proceed to step 2 Stabilizing brackets are used for floor anchoring or for the general stability not anchored of the UPS and all of its mecha
7. Decorative front re attachment n The instructions for re attaching the decorative front are the reverse of the instructions for removing the dead front Refer to the graphic on page 13 Note 1 Holding the decorative front at an angle away from the enclosure lower its two 2 base tabs into the OUTER two 2 slots at the bottom of the enclosure 2 Push the top of the decorative front forward until it snaps into position Smart UPS VT Maintenance Bypass Panel w Power Distribution 10 30kVA 208V 990 4199B 25 Installation Rear panel re attachment The TOP and BOTTOM rear panels are re attached in exactly the same way Use the following procedure to re attach each of the rear panels in its turn Note Theinstructions for re attaching the rear panels are the reverse of the instructions for removing rear panels Refer to the graphic on page 15 1 Re connect the internal ground cable to the panel s ground stud Secure the ground cable lug to the stud with an M6 flange nut Use an M10 nut driver and torque to 120in Ibs 14 Nm 2 Holding the panel at an angle away from the enclosure lower the panel s two 2 base tabs into the two 2 slots at the bottom of that section of the enclosure middle or bottom 3 Push the top of the panel forward until it is properly set in position 4 Use a T30 Torx screwdriver to tighten the two 2 M6 Torx screws under the top lip of the panel 0 After installation the rear pane
8. Neutral Terminal Block N Load Power Terminal Block N L1 L2 L3 to Input Bus N L3 L2 L1 Output Bus L3 L2 L1 to Input Fuse Block L1 L2 L3 Output Bus to Neutral Bars N Bars located behind Panel Board Power Terminal Block n N L1 L2 L3 to Input e Bus N L3 L2 L1 Output Fuse Block L3 L2 L1 to Panel o o Board L1 L2 L3 LJ Output Bus to Input Fuse Block L3 L2 L1 These connections are completed for the MBP WITH panel board version ONLY For MBP WITHOUT panel board external cables are NOT supplied for output to load connections 22 Smart UPS VT Maintenance Bypass Panel w Power Distribution 10 208V 990 4199B Installation Making external cable connections External cables can enter the MBP a through any of the available 3 A inch 19 mm knockouts in the top or bottom plate b by making larger cutouts in the top or bottom plate c by removing one of the five 5 horizontal plates in the bottom rear panel or d through the open side adjacent to the UPS Prior to making any of the following external cable connections establish an appropriate point of access for the cable The top or bottom plate can be removed using a T30 Torx screwdriver to detach the four 4 M6 Torx screws securing it to the enclosure The cables are typically color coded L1 black L2 red L3 blue N whit
9. UPS VT Maintenance Bypass Panel w Power Distribution 10 30kVA 208V 990 4199B 17 Installation 6 Remove the two 2 baying adapters from the side of the MBP Each baying adapter is secured to the MBP enclosure with three 3 M6 bolts and flange nuts Use an M10 nut driver and appropriate size wrench to remove the six 6 bolts and flange nuts Baying Adapters 2 M6 Bolts and Flange Nuts 3 M6 Bolts and Flange Nuts 3 gt gt gt gt ex MU we g se oe e coe BM d 1 1 d ers aa gt 7 Attach the baying adapters to the side of the UPS where the MBP will be connected Note the front and rear positioning of the baying adapters graphic on left and how each adapter s two 2 dual sided tabs fit into one of the large open slots at the top of the UPS inset on right Baying Adapter rear Open Slot on UPS x me gt c aay Co CT Dual sided Tabs on Baying Adapters gt Baying Adapter front 18 Smart UPS VT Maintenance Bypass Panel w Power Distribution 10 208V 990 4199B Installation 8 Roll the MBP into position alongside the UPS and flush against the baying adapters The open dual sided OUTER tab in each baying adapter those closest to the front and the rear of the UPS must be inserted into the two 2 ho
10. access to the rear of the panel board if included There should be a minimum of 20 inches 508mm clearance ABOVE the MBP to accommodate ventilation Smart UPS VT Maintenance Bypass Panel w Power Distribution 10 30kVA 208V 990 4199B 11 Installation Overview WARNING Review Safety on page 1 before starting this installation Pay strict attention to all Warning Safety warning and caution notices The MBP must be mechanically connected to the UPS on site using supplied baying adapters and assembly hardware Floor anchoring of both units UPS and MBP in tandem is optional ALL INTERNAL cable connections were made prior to shipment EXTERNAL cable connections between the UPS and the MBP were made prior to shipment on the MBP side only These two 2 sets input and output of supplied cables are bundled inside the MBP The connections on the UPS side need to be made on site EXTERNAL cable connections from the utility to the MBP also need to be made on site These cables are not supplied Control wire connections between the UPS and the MBP additionally need to be made on site Control wires are not supplied Panel board breakers if applicable must be ordered separately Tie wraps are not supplied Tools The following tools are required for this installation Forklift pallet jack Drill for floor anchoring Phillips screwdriver Tape measure 13 14mm wrench supplied e
11. attach the four 4 M6 side screws and an appropriate tool to attach the floor anchors Make side screws hand tight Torque the floor anchors in accordance with their size o Side Panel M6 Side Screw total of 4 Floor Anchors minimum of 4 Stabilizing Bracket Smart UPS VT Maintenance Bypass Panel w Power Distribution 10 30kVA 208V 990 4199B 21 Installation Internal cable connections For the convenience of the installer ALL internal MBP cable connections were made prior to shipment Check to make certain the following internal cable connections were completed Power Terminal Block N L1 L2 L3 left to right to Input Bus N L3 L2 L1 left to right e Output Bus L3 L2 L1 left to right to Input Fuse Block L3 L2 L1 left to right for MBP with Panel Board L1 L2 L3 left to right for MBP without Panel Board Output Bus N to Neutral Bars Block N e Output Fuse Block L3 L2 L1 left to right to Panel Board L1 L2 L3 left to right Control Terminal Block to optional customer contacts 1 2 3 4 5 6 and UPS connections for Q3 7 8 Note The control wires from the UPS MUST be connected to the Normally Closed Auxiliary Contacts on Q3 7 8 DO NOT use terminals 5 and 6 for these connections Refer to Schematics on pages 6 and 7 and to the appropriate wiring diagram in the UPS Install Manual MBP w Panel Board MBP w o Panel Board Output Bus to
12. dispatched to the Product location to repair or replace the Product at the discretion of APC Exclusions 34 APC shall not be liable under the Warranty if its testing and examination discloses that the alleged defect in the product does not exist or was caused by your or any third person s misuse negligence improper installation or testing unauthorized attempts to repair or modify or any other cause beyond the range of the intended use or by accident fire lightning or other hazard THERE ARE NO WARRANTIES EXPRESSED OR IMPLIED BY OPERATION OF LAW OR OTHERWISE OF PRODUCTS SOLD SERVICED OR FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH APC DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE THE APC EXPRESS WARRANTIES WILL NOT BE ENLARGED DIMINISHED OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF APC RENDERING TECHNICAL OR OTHER ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES THE WARRANTIES SET FORTH ABOVE CONSTITUTE SOLE LIABILITY OF APC AND YOUR EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES THE WARRANTIES EXTEND ONLY TO YOU AND ARE NOT EXTENDED TO ANY THIRD PARTIES Smart UPS VT Maintenance Bypass Panel w Power Distribution 10 208V 990 4199B Limited Factory Warranty IN NO EVENT SHALL APC ITS OFFICERS DIRECTORS AFFILIAT
13. or servicing this unit WARNING All wiring instructions must be followed precisely Failure to comply could result in permanent damage to the equipment Smart UPS VT Maintenance Bypass Panel w Power Distribution 10 30kVA 208V 990 4199B Safety Live maintenance precautions 2 APC does NOT recommend performing live maintenance to the Maintenance Bypass Panel with Power Distribution However APC is aware that due to the critical nature of data center loads live maintenance may occur If providing live maintenance observe the following precautions to reduce the risk of electrical shock A Caution Never work alone Only a certified electrician who is trained in the hazards of live electrical installation should perform the maintenance Know the procedure for disconnecting electricity to the Maintenance Bypass Panel and to the data center in the event of an emergency Wear appropriate protective clothing and other body equipment Be sure to use rubber insulated gloves and rubber insulated boots Use double insulated tools If double insulated tools are not available insulate all tools with electrical tape Use electrical tape to insulate any non insulated conductive parts Always follow local codes and site regulations when working on the Maintenance Bypass Panel Smart UPS VT Maintenance Bypass Panel w Power Distribution 10 30kVA 208V 990 4199B Introduction This manual pro
14. the MBP 3 Connect the two 2 UPS control wires to Pins 7 and 8 in the MBP Control Terminal Block Use a standard flathead screwdriver and make the screws hand tight MBP w Panel Board MBP w o Panel Board UPS Inputs at O1 Switch N L3 L2 L1 UPS Outputs at Q2 Switch N L3 L2 L1 UPS Inputs at O1 Control Wires 7 8 Switch N L3 L2 L1 UPS Outputs at O2 Switch N L3 L2 L1 control Wires 7 8 24 Smart UPS VT Maintenance Bypass Panel w Power Distribution 10 208V 990 4199B Installation Re attaching the front and rear panels Front panel re attachment 0 The instructions for re attaching the front panel are the reverse of the instructions for removing the front panel Refer to the graphics on page 14 Note 1 Set the panel on its side and re connect the internal ground cable to the panel s ground stud Secure the ground cable lug to the stud with an M6 flange nut Use an M10 nut driver and torque to 120in Ibs 14 Nm 2 Holding the panel at an angle away from the enclosure lower the panel s two 2 base tabs into the INNER two 2 slots at the bottom of the enclosure 3 Push the top of the panel forward until it is properly set in position 4 Use a T30 Torx screwdriver to tighten the two 2 M6 Torx screws under the top lip of the panel
15. 0 4199B Shipping Receiving and Unloading 2 Record any damages observed and call the carrier immediately to allow their personnel to conduct an equipment inspection if necessary Do NOT contact APC first notify the carrier instead Otherwise APC may be unable to assist in recovering the realized amount of the claim All damage claims should be as specific as possible Information pertaining to the shipment should appear on the shipping label and related paperwork BE SURE to request a copy of the carrier 5 inspection report Unloading 1 Use a forklift or pallet jack to transport the MBP to the installation site Make certain the route to the installation site can accommodate the size and weight of the unit plus the lifting device 2 Atthe installation site remove a the packaging material b the wooden ramp and c the plastic sleeve located inside the unit containing the door keys and documentation Also detach the 13 14 mm wrench from the shipping pallet 3 Use the 13 14 mm wrench to remove the M8 bolt and an M10 nut driver to remove the M6 bolt from each of the four 4 angle brackets securing the MBP to its pallet Be aware that the MBP is shipped on its casters and may begin to roll once the bolts have been removed Take steps to prevent this from happening Caution Angle Bracket M8 Bolt M6 Bolt Smart UPS VT Maintenance Bypass Panel w Power Distribution 10
16. 208V 990 4199B 9 Shipping Receiving and Unloading 4 Attach the wooden ramp to the side of the pallet that contains a velcro strip The top of the ramp also contains velcro strips on its underside Securely mate the two 2 sets of velcro strips A At least two 2 people should be involved in unloading the MBP from its pallet Caution Velcro Strips underside of Ramp Velcro Strip on Pallet 5 Carefully roll the MBP off its pallet and down the ramp The unit should be brought to rest on a smooth and level surface 10 Smart UPS VT Maintenance Bypass Panel w Power Distribution 10 30kVA 208V 990 4199B Considerations Environmental The MBP should be kept in a climate controlled environment having a temperature range of 0 to 40 C 32 to 104 F and a relative humidity of 0 to 95 non condensing The MBP must be protected at all times from excessive moisture construction dirt corrosive elements and other contaminants The floor surface on which the MBP rests must be firm and level and the total weight of the installed unit s must not exceed limitations for floor loading Spacing There should be a minimum of 36 inches 914mm clearance directly in FRONT of the MBP to accommodate installation servicing and access to the panel board if included There should be a minimum of 36 inches 914mm clearance directly BEHIND the MBP to accommodate installation servicing and
17. A www apc com Smart UPS VT Maintenance Bypass Panel with Power Distribution floor units 10 30 kVA 208V Installation and Operation Smart UPS VT Maintenance Bypass Panel with Power Distribution floor units Installation and Operation Manual IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions for the SUVT series that should be followed during installation and operation of the Maintenance Bypass Panel with Power Distribution Smart UPS VT Maintenance Bypass Panel w Power Distribution 10 30kVA 208V 990 4199B Contents Safety Geor PPP Ro ee 1 SAVE THESE INSTRUCTIONS 1 Safety warnings 1 Live maintenance precautions 2 3 Product OVervIeW x ax exui UR GA e Sees RC t ACA 4 Features cuu oye Hota tend ah ate ere a ras 4 Internal components 5 About the graphics 5 Schematic with panel board 6 Schematic without panel board 7 Shipping Receiving and Unloading 8 Shipping 45 rm imm IRURE inm elt 8 Receiving eee li cz velim ee ee a 8 sg des
18. ES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT SPECIAL CONSEQUENTIAL OR PUNITIVE DAMAGES ARISING OUT OF THE USE SERVICE OR INSTALLATION OF THE PRODUCTS WHETHER SUCH DAMAGES ARISE IN CONTRACT OR TORT IRRESPECTIVE OF FAULT NEGLIGENCE OR STRICT LIABILITY OR WHETHER APC HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH DAMAGE Smart UPS VT Maintenance Bypass Panel w Power Distribution 10 30kVA 208V 990 4199B 35 36 Smart UPS VT Maintenance Bypass Panel w Power Distribution 10 208V 990 4199B www apc com APC Worldwide Customer Support Customer support for this or any other APC product is available at no charge in any of the following ways Visit the APC Web site to access documents in the APC Knowledge Base and to submit customer support requests www apc com Corporate Headquarters Connect to localized APC Web sites for specific countries each of which provides customer support information www apc com support Global support searching APC Knowledge Base and using e support Contact an APC Customer Support center by telephone or e mail Regional centers Direct InfraStruXure Customer Support Line 1 877 537 0607 toll free APC headquarters U S Canada 1 800 800 4272 toll free Latin America 1 401 789 5735 USA Europe Middle East Africa 353 91 702000 Ireland Japan 0 35434 2021 Australia New Zealand South Pacific area 61 2 9955 9366 Austr
19. T30 Torx screwdriver Level Wrenches various sizes T20 Torx screwdriver Marker Standard flathead screwdriver e MIO nut driver Panel board breakers The 42 position panel board supports the following Square D 1 2 and 3 pole bolt on circuit breakers of the circuit breakers listed below have been pre tested and approved by APC Breaker Type APC Parti Breaker Type APC Part 1 pole 20 Amp PD1P20ABBSD 3 pole 20 Amp PD3P20ABBSD 2 pole 20 Amp PD2P20ABBSD 3 pole 80 Amp PD1P80ABBSD 2 pole 30 Amp PD2P30ABBSD 3 pole 100 Amp PD3P100ABBSD 12 Smart UPS VT Maintenance Bypass Panel w Power Distribution 10 30kVA 208V 990 4199B Installation Removing the front and rear panels The front panel and the two 2 rear panels of the MBP should be removed prior to installation to permit total access to the interior of the unit 0 The plastic decorative front must first be removed to expose the front panel Note Decorative front removal 1 Place the fingertips of one hand into the grab handle at the top of the decorative front and pull toward you This will disengage the top of the decorative front from the enclosure 2 Holding the decorative front at an angle away from the enclosure lift its two 2 base tabs out of the two 2 slots at the bottom of the enclosure 3 Store the decorative front in a safe location for later re attachment Grab Handle DECORATIVE FRONT
20. alia Local country specific centers go to www apc com support contact for contact information Contact the APC representative or other distributor from whom you purchased your APC product for information on how to obtain local customer support Entire contents copyright 2006 American Power Conversion Corporation All rights reserved Reproduction in whole or in part without permission is prohibited APC the APC logo and Smart UPS VT are registered trademarks of American Power Conversion Corporation All other trademarks are the property of their respective owners
21. be turned ON again before proceeding with the following steps Follow the UPS Note power on procedure described in the UPS Operation Manual 1 Switch Q1 ON 2 The UPS will now autostart Follow the UPS start up procedure described in the UPS Operation Manual and apply load when prompted 3 Transfer the UPS into the requested bypass mode following the procedure described in the UPS Operation Manual Q1 4 Switch Q2 ON UPS Input 5 Switch Q3 OFF 6 Transfer the UPS into normal ssedhg operation following the procedure described in the UPS Operation Manual Q2 UPS Output Smart UPS VT Maintenance Bypass Panel w Power Distribution 10 30kVA 208V 990 4199B 31 Appendix A Changing Fuses WARNING Before changing fuses make sure ALL MBP switches are in the OFF position From Electrical normal operation first switch Q2 OFF and then switch Q1 OFF replaced with either Bussmann Class J 90 Amp fuses p n JKS 90 or Bussmann Note Class J 50 Amp fuses p n JKS 50 O Depending on your MBP version refer to Features on page 4 blown fuses are Removing fuses 1 Remove the decorative front and the front panel from the MBP to access the fuse block 2 Using a plastic or insulated fuse puller tightly grasp the center section of the blown fuse 3 Pull the fuse toward you forcing its release from the two 2 sets of spring clasps Replacing fuses 1 Usi
22. e and G green Utility connections 1 Connect the four 4 inputs N L1 L2 L3 left to right from the Utility to the Power Terminal Block Use a standard flathead screwdriver and torque to 60in Ibs 7Nm 2 Connect the one 1 ground input G from the Utility to the Ground Terminal Compression Lug Place the cable end in the bottom section of the compression lug and then use a standard flathead screwdriver and torque to 120in Ibs 14 Nm MBP w Panel Board MBP w o Panel Board Utility to Ground G Utility to Power Terminal Block N L1 L2 L3 Utility to Power Terminal Block N L1 L2 L3 Utility to Ground G Smart UPS VT Maintenance Bypass Panel w Power Distribution 10 208V 990 4199B 23 Installation UPS connections UPS cables have been appropriately pre connected to the MBP Refer to the Smart UPS VT 10 30kVA 208V UPS Installation Manual p n 990 1598 for MBP cable connections at the UPS of these cables should be run through the adjacent sides of the two enclosures MBP and UPS and out the rear of the UPS for connection 1 The four 4 UPS inputs N L3 L2 L1 left to right have been pre connected to the Q1 Switch in the 2 The four 4 UPS outputs N L3 L2 L1 left to right have been pre connected to the Q2 Switch in
23. easures 58 75 H x 13 75 W x 31 75 D dimensions in mm below Product SKU SBPSUIOK30FCIMI FP Key Features Three 10 w panel board 3 90A fuses Input 81 3A 208 120 V 3 phase 50 60Hz Output 83 3 A 208 120 V 3 phase 50 60Hz Weight 2641b 120kg per unit 3161b 143kg shipping SBPSUIOKISFCIMI 10 15 w o panel board Three 3 50A fuses 40 6 A 208 120 V 3 phase 50 60Hz 41 64 208 120 V 3 phase 50 60Hz 2301b 104kg per unit 2821b 129kg shipping SBPSU2OK30FCIMI 20 30kVA w o panel board Three 3 90A fuses 81 3A 208 120 V 3 phase 50 60Hz 83 3A 208 120V 3 phase 50 60Hz 2361b 107kg per unit 2881b 131kg shipping The MBP enclosure supports both top and bottom cable entry There are twenty five 25 3 4 inch 19mm knockouts in the top and bottom plates 50 knockouts total Space has additionally been provided at the front of these plates to accommodate larger cutouts Each unit also contains three 3 fuses that provide over current and short circuit protection 13 75 lt 349 58 75 1492 31 73 806 Ti 58 75 1492 SIDE Smart UPS VT Maintenance Bypass Panel w Power Distribution 10 30kVA 208V 990 4199B Internal components MBP w Panel Board MBP w o Panel Board Product Overview Ne
24. heavier line shows the flow of utility power through Q1 the UPS and Q2 Q1 Q1 UPS Input UPS Input Q3 Bypass Q2 Q2 UPS Output UPS Output 28 Smart UPS VT Maintenance Bypass Panel w Power Distribution 10 208V 990 4199B Operation Battery back up operation The UPS will automatically transfer from normal operation to battery back up operation in instances when utility power is lost or becomes degraded The heavier line in below graphic C shows the flow of battery supplied power through the UPS and Q2 Be aware that this transfer of power CANNOT take place when the UPS is operating in either static bypass mode or bypass mode Q After transferring from normal operation to battery back up operation the MBP switch settings are unchanged Q1 and Q2 are ON Q3 is OFF Note Static bypass mode Static bypass is a temporary operating mode that becomes active during the process of transferring from normal operation to bypass operation or from bypass operation to normal operation The below graphic D shows static bypass mode during the transfer from normal to bypass operation Q The user interface on the UPS is the instrument used to initiate static bypass mode Note C Q1 UPS Input Q1 UPS Input Sdn Asayeg Q2 UPS Output UPS Output
25. hed by sliding it down into the grooves at the base of the MBP 12 Re attach the top cover to the MBP Place the top cover onto the MBP enclosure and then use a Phillips screwdriver to tighten the four 4 M4 Phillips screws Refer to Step 5 graphic 20 Smart UPS VT Maintenance Bypass Panel w Power Distribution 10 208V 990 4199B Installation Anchoring the MBP optional The MBP along with the UPS can be anchored to the floor using the same stabilizing bracket and hardware that was previously removed from the side of the UPS refer to step 1 Mechanically connecting the MBP to the UPS on page 16 1 Panel Board Hinged Door Place the stabilizing bracket against the open side of the MBP aligning the bracket s four 4 side holes with the four 4 holes at the bottom of the MBP Mark desired anchor locations in the stabilizing bracket s holes A minimum of four 4 MS or larger anchors are recommended for each bracket Consult APC Technical Support for guidance concerning the use of anchor bolts in Smart UPS VT configurations Remove stabilizing bracket and drill appropriate size holes in marked locations on the floor Install anchor bolts in drilled holes Place the stabilizing bracket onto the anchor bolts while again aligning the bracket s four 4 side holes with the four 4 holes at the bottom of the MBP Secure the stabilizing bracket to the MBP Use an M10 nut driver to
26. l MUST be removed whenever the ground and neutral bars at the back of the panel board if included need to be accessed Note 26 Smart UPS VT Maintenance Bypass Panel w Power Distribution 10 208V 990 4199B Installing Panel Board Breakers This section describes how to install breakers to the MBP s 42 position panel board if included WARNING Before installing breakers make sure ALL MBP switches are in the OFF position Electric From normal operation first switch Q2 OFF and then switch Q1 OFF 1 Remove the top rear panel from the MBP enclosure Refer to Rear panel removal on page 15 2 Remove the decorative front and the front panel from the MBP enclosure Refer to Decorative front removal on page 13 and Front panel removal on page 14 3 Select the next available breaker position s on the panel board and then snap the new 1 2 or 3 pole breaker into the appropriate guard rail The panel board supports Square D bolt on circuit breakers For a listing of 0 recommended breakers refer to Panel board breakers on page 12 Note top pole of a 3 pole breaker must always be placed in an L1 position on the panel board Counting down from the top these are positions 1 7 13 19 etc on the left side of the board and positions 2 8 14 20 etc on the right side of the board 4 Make the bolt on connections those nearer the center of the panel board Use a standard flathead
27. ng a plastic or insulated fuse puller tightly grasp the center portion of the replacement fuse 2 Align the fuse s metallic ends with the two 2 sets of spring clasps that will hold it in place 3 Push the fuse into the two 2 sets of clasps until the clasps snap around the metallic ends 4 Re attach the front panel and the decorative front to the MBP Spring Clasps top and bottom Metallic End top and bottom 90A Fuse or 50A Fuse Fuse Puller Fuse Block Q After changing fuses the MBP can be returned to normal operation by first switching Q2 ON and then switching Q1 ON Q3 remains OFF Note 32 Smart UPS VT Maintenance Bypass Panel w Power Distribution 10 208V 990 4199B Limited Factory Warranty The limited warranty provided by American Power Conversion Corporation in this Statement of Limited Factory Warranty applies only to Products you purchase for your commercial or industrial use in the ordinary course of your business APC product covered Smart UPS VT Maintenance Bypass Panel MBP with Power Distribution floor Terms of warranty APC warrants that the Product shall be free from defects in materials and workmanship for a period of one 1 year from the date of start up when APC authorized service personnel performed the start up of the Product or a maximum of 18 months from the date of Product shipment from APC when A PC authorized service personnel have not
28. nically connected ancillary enclosures Note 2 Remove the top cover from the UPS The top cover is removed by loosening the four 4 M4 Torx screws one at each corner securing it to the UPS enclosure Use a T20 Torx screwdriver to loosen the screws and then pull the top cover up and away from the UPS Top Cover M4 Torx Screws front and back 5 Side Panel M6 Side Screw total of 4 Floor Anchors minimum of 4 Stabilizing Bracket 16 Smart UPS VT Maintenance Bypass Panel w Power Distribution 10 208V 990 4199B Installation 3 Remove the side panel from the UPS on the side where the MBP will be connected The side panel is removed by pulling it up and away from the base of the UPS enclosure Set this panel aside for later installation on the open side of the MBP Side Panel UPS 4 Re attach the top cover to the UPS Place the top cover onto the UPS enclosure and then use a T20 Torx screwdriver to tighten the four 4 M4 Torx screws Refer to Step 2 graphic 5 Remove the top cover from the MBP The top cover is removed by loosening the four 4 M4 Phillips screws one at each corner securing it to the MBP enclosure Use a Phillips screwdriver to loosen the screws and then pull the top cover up and away from the MBP M4 Phillips Screws Top Cover M4 Phillips Screws MBP Smart
29. performed the start up of the Product Warranty Period In the event that the Product fails to meet the foregoing warranty APC shall repair or replace any defective parts such repair or replacement to be without charge for on site labor and travel if APC authorized personnel have conducted start up of the Product An APC Start Up Service must be performed completed by APC authorized service personnel or replacement of defective parts only will be covered APC shall have no liability and no obligation to repair the installed Product if non authorized personnel performed the start up and such start up caused the Product to be defective Any parts furnished under this warranty may be new or factory remanufactured Repair or replacement of a defective product or part thereof does not extend the original warranty period Non transferable warranty extends to first purchaser for use This Warranty is extended to the first person firm association or corporation herein referred to by You or Your for whom the APC Product specified herein has been purchased This Warranty is not transferable or assignable without the prior written permission of APC Assignment of warranties APC will assign to you any warranties which are made by manufacturers and suppliers of components of the APC Product and which are assignable Any such warranties are assigned AS IS and APC makes no representations as to the effectiveness or extent of such warranties ass
30. rizontal slots near the top of the MBP Horizontal Slot top of Dual sided Inner Tab Dual sided Outer Tab Baying Adapter front Baying Adapters UPS not shown ee a 9 Use the 13 14mm wrench to lower the four 4 leveling feet located in the corner positions beneath the MBP Lower all four 4 leveling feet simultaneously working front to back and left to right until all four 4 foot pads make solid contact with the floor Q Leveling feet are lowered by turning their leveling nut clockwise Leveling feet are raised by turning their leveling nut counter clockwise Note Leveling Nut Foot Pad Smart UPS VT Maintenance Bypass Panel w Power Distribution 10 30kVA 208V 990 4199B 19 Installation 10 Insert the six 6 previously removed M6 bolts through the designated assembly holes see graphic in the MBP the baying adapter and the UPS Attach an M6 flange nut to the other end of each bolt Use an M10 nut driver with an appropriate size wrench and bind until rigid Baying Adapter rear UPS Baying Adapter 1 front M6 Bolts 3 M6 Bolts 3 t 0 The following steps in this process 11 and 12 can either take place now after making the electrical connections Note 11 Attach the side panel that was previously removed from the UPS to the open side of the MBP The side panel is attac
31. screwdriver and torque to 24in Ibs 3 Nm 5 Remove the corresponding plastic blanking plate s located directly in front of the newly installed breaker 3 pole Breaker 3 pole Breaker positions 1 3 5 positions 2 4 6 Bolt on Connections 0 After installation panel board breakers can be accessed by simply opening the panel board hinged door Use the front door key to open this door Note Smart UPS VT Maintenance Bypass Panel w Power Distribution 10 30kVA 208V 990 4199B 27 Operation The MBP with Power Distribution supports four 4 modes of UPS operation 1 Normal 2 Battery Back up 3 Static Bypass and 4 Bypass The process of changing from one operational mode to another requires a series of automated and manual tasks Automated tasks are initiated from the user interface at the front of the UPS and may require switches on the MBP to be turned ON or OFF depending on the operational mode T Refer to the Smart UPS VT 10 30kVA Operation Manual p n 990 1599 for an overview of the functionality of the user interface See also A switch can be locked in place by pressing down on its red lever and then applying a locking device to the exposed holes The MPP is shipped with its switches in the OFF position graphic A Normal operating mode To enter normal operating mode graphic B first switch Q2 ON and then switch Q1 ON Q3 remains OFF The
32. umes NO RESPONSIBILITY for any matters which may be warranted by such manufacturers or suppliers and extends no coverage under this Warranty to such components Smart UPS VT Maintenance Bypass Panel w Power Distribution 10 30kVA 208V 990 4199B 33 Limited Factory Warranty Drawings descriptions APC warrants for the Warranty Period and on the terms of the Warranty set forth herein that the APC Product will substantially conform to the descriptions contained in the APC Official Published Specifications or any of the drawings certified and agreed to by an authorized APC representative if applicable thereto Specifications It is understood that the Specifications are not warranties of performance and not warranties of fitness for a particular purpose Warranty claims procedure To obtain service under Warranty contact APC Customer Support see rear cover You will need the model number of the Product the serial number and the date purchased A technician will ask you to describe the problem If it is determined that the Product will need to be returned to APC you must obtain a returned material authorization RMA number from APC Customer Support Products that must be returned must have the RMA number marked on the outside of the package and be returned with transportation charges prepaid If it is determined by APC Customer Support that on site repair of the Product is allowed APC will arrange to have APC authorized service personnel
33. utral Terminal Inputs Ground Terminal UPS Block Compression Lug Power Terminal Block Fuse Block Ground Bar and O1 Switch 3 50A Fuses or Neutral Bar located 3 90A Fuses behind Panel Board Q3 Switch Panel Board 42 position Q2 Switch Outputs Control Inputs from UPS Terminal to UPS Block Power Terminal O1 Switch Block Ground Terminal Compression Lug Switch Fuse Block 3 90A Fuses Q2 Switch Outputs Control from UPS Terminal About the graphics Block The MBP version WITH the panel board above left is used as the primary graphic example throughout this manual The versions WITHOUT the panel board above right are shown as well in instances when such graphics might help to clarify the instruction The MBPs DO NOT come with side panels though there may appear to be side panels in many of the graphic examples Smart UPS VT Maintenance Bypass Panel w Power Distribution 10 208V 990 4199B 5 Product Overview Schematic with panel board nano san d Mii itat Andino Sdn 5 Jewoysng Sdn L1 N 200 010 ZI N 200 c 15281 20 ajqeyns sJojonpuoo esn P d SED See N LAdNI W31SAS Smart UPS VT Maintenance Bypass Panel w Power Distribution 10
34. vides step by step instruction on how to install and operate the floor versions of the Smart UPS VT Maintenance Bypass Panel MBP with Power Distribution These UL listed units were designed to operate in conjunction with the Smart UPS VT 10 30kVA 208 V UPS Each of these MBPs contains switches that facilitate the transfer of power from the UPS to bypass operation to allow maintenance to be performed on the UPS One version also houses a 42 position panel board for distributing power to load Read these instructions carefully and observe all safety warnings and other precautions Should you require any installation operation supervision service parts accessories or maintenance call the appropriate APC phone number refer to the back cover of this manual Refer to the Smart UPS VT 10 30kVA 208 V Installation Manual p n 990 1598 for Ss INSTALLATION specific information relating to the SUVT series UPS See also Refer to the Smart UPS VT 10 30kVA 208V Operation Manual p n 990 1599 for OPERATION specific information relating to the SUVT series UPS Smart UPS VT Maintenance Bypass Panel w Power Distribution 10 30kVA 208V 990 4199B 3 Product Overview Features three floor versions of the Smart UPS VT Maintenance Bypass Panel MBP with Power Distribution were designed for installation in lineup and match configurations with the Smart UPS VT 10 30kVA UPS Each unit m
Download Pdf Manuals
Related Search
Related Contents
ST Motor User Manual NextBase SDV97-AC DVD Player User Manual Garmin 190-00864-01 User's Manual personne morale D\namic Model User Guide 9ersion 3.0 Video Projector Samsung Soundbar J355 User Manual BANDIT 240 DB v206 installation manual Acer TravelMate P4 TMP453-M-33124G50Makk 9710 Library Storage Module Hardware Operator`s Guide Copyright © All rights reserved.