1. 1 Power On Off Switch Press the power switch to turn the UPS ON or OFF 2 LCD Function Selected Switch Press the LCD function selected switch to know the UPS status 3 LCD Display The LCD will display the UPS status including input voltage output voltage runtime percentage of load and battery etc 4 Communication Protection Ports RJ11 RJ45 Communication protection ports will protect any standard modem fax telephone line or network cable from surge and spikes 5 Battery Charger port Charge external AA AAA battery via battery charger port with battery charger 6 AC outlet The UPS provides 3 outlets for connected equipment to insure temporary uninterrupted operation during a power failure and against surges and spikes and another 3 outlets against surges and spikes only 7 USB Port to PC 7 This port allows connection and communication c from the USB port on the computer to the UPS unit The UPS communicates its status to the PowerPanel Personal Edition software This interface is also compatible with the UPS service aras provided by Windows NT Windows 2000 od Windows XP Windows Vista Mac OSX Linux gt EE PLUGIN PC UPS 8 Input Circuit Breaker The Circuit Breaker provides optimal overload protection 9 Power on LED The power on LED lights up when the UPS is ON 10 Cable Collector Collect the cables connected from the AC outlets in the cabl
2. BR450ELCD BR650ELCD BR850ELCD User s Manual K0O1 0000056 00 SAFETY WARNINGS SAVE THESE INSTRUCTIONS This manual contains important safety instructions Please read and follow all instructions carefully during installation and operation of the unit Read this manual thoroughly before attempting to unpack install or operate your UPS This equipment can be operated by any individuals with no previous training The socket outlet shall be installed near the equipment and easily accessible During the installation of this equipment it should be assured that the sum of the leakage currents of the UPS and the connected loads does not exceed 3 5mA Attention hazardous through electric shock Also with disconnection of this unit from the mains hazardous voltage still may be accessible through supply from battery The battery supply should be therefore disconnected in the plus and minus pole at the quick connectors of the battery when maintenance or service work inside the UPS is necessary Do not dispose of batteries in a fire the battery may explode Do not open or mutilate the battery or batteries released electrolyte is harmful to the skin and eyes INSTALLING YOUR UPS SYSTEM UNPACKING Inspect the UPS upon receipt The box should contain the following 1 UPS Unit x 1 1 Phone Line x 1 3 USB Cable x 1 4 User Manual x 1 5 Management software Disk x 1 6 Green Power Technology description x 1 7 Battery Charger x 1 8 Cab
3. at least 4 The unit has been damaged Contact CyberPower Systems at by a surge or spike service cyberpower eu com Connect the USB cable to the UPS unit The USB cable is not and an open serial port on the back of connected the computer You must use the cable that came with the unit Try another USB port of your computer Shutdown your computer and turn the yah pales providing UPS off Wait 10 seconds and turn the yp UPS back on This should reset the unit The serial cable is not the You must use the cable included with the a was provided with unit for the software TECHNICAL SPECIFICATIONS Model BRA450ELCD BR 650ELCD BR 850ELCD Capacity VA 450VA 650VA 850VA Capacity Watts 270W 390W 510W Mechanical problem The circuit breaker is tripped due to overload Outlets do not provide power to equipment The USB cable is PowerPanel connected to the wrong Personal Edition port is inactive all icons are gray Input Voltage Range 165 270Vac Frequency Range 50 60 Hz 3Hz Auto Sensing On Battery Output Simulated Sine Wave at 230Vac 10 Voltage On Battery Output 50 60 Hz 1 Frequency Overload Protection Physical Total of UPS Schuko 6 3 for battery backup and surge 3 for surge 271 L x160 7 W x113 6 H Weight kg 12V 7Ah x1 8 Hours Battery Sealed Maintenance Free Lead Acid Battery Typical Recharge Time Warning Diagnost
4. e collector 11 Battery Charger Put external AA AAA batteries into the battery charger for charge Functional Test AC Mode The UPS delivers power to the loads derived from the utility and maintains proper battery charge It also regulates the output voltage to within a narrow range On Battery Mode The UPS operates on battery when the line voltage or frequency has fallen outside the limits Local users are alerted to this mode of operation by visual and audible indicators The UPS provides power to the load from the battery and through its inverter and the output voltage and frequency of the UPS are regulated within a narrow range 1 Switch On Press the power switch on the top panel then the power on LED will light up 2 Switch Off Press again the power switch the power on LED on the top panel will go off 3 Cold Start Start on Battery This UPS can be turned on even when AC is not present Press the power switch on the top panel then the power on LED will light up ROUTINE MAINTENANCE AND STORAGE ROUTINE MAINTENANCE 1 Use dry soft clothes to clean the top panel and plastic parts Do not use any detergent that contains alcoholic ingredient N The expected lifetime of the battery is around 3 years Improper operation and harsh environment will reduce the actual lifetime 3 Unplug the UPS from power inlet if the UPS will not operate for long period of time STORAGE 1 First turn off yo
5. ics Indicators Audible Alarms Environmental Operating Temperature Operating Relative Humidity Communication PowerPanel Personal Edition Software Management Auto Charger Auto Restart USB Interface 12V 4 5Ah x1 12V 9Ah x1 Power On On Battery Low Battery Overload 32 F to 104 F 0 C to 40 C 0 to 85 NON CONDENSING Windows2000 NT XP Server 2003 Vista Mac OSX Linux DEFINITIONS FOR ILLUMINATED LCD INDICATORS LCD Indication EDM usted peel cm 4 Ls mE IK OR bt bf LA Line mode UPS Status Display Capacity Display a s Load Battery Input Output Run CLECE ee ee i tie an Px to ve ft xX fo tT ve to ee x o o f x Digital Value Display Select SW Po xX vit x Fo ft vi if ft S y Press gt 3sec y y Sound Disable Press gt 3sec again V X X X Sound Enable ead vy Sx ge e S A a ee ee H X Not Illuminated V Illuminated Either Battery mode UPS Status Display Capacity Display Digital Value Display Select SW Be Load Batter Input Output Run x a S T ovy S S i V V x lt o miia ee ee ee x X ist ie wN i 4th 5th Return Xx Oe x x Oooo So ovi i i Oooo S Press gt 3sec y Sound Disable Press gt 3sec again X V X X Sound Enable Ovaa O Xe eee H d a l X Not Illuminated k Ke k x x lt lt V Illuminated Either For more information visit e
6. le Collector x 1 HOW TO DETERMINE THE POWER REQUIREMENTS OF YOUR EQUIPMENT 1 Insure that the equipment plugged into the battery power supplied outlets does not exceed the UPS unit s rated capacity 450VA 270W for BR450ELCD 650VA 390W for BR650ELCD 850VA 510W for BR850ELCD If rated unit capacities are exceeded an overload condition may occur and cause the UPS unit to shut down or the fuse blow 2 If the power requirements of your equipment are listed in units other than Volt Amps VA convert Watts W or Amps A into VA by doing the calculations below Note The below equation only calculates the maximum amount of VA that the equipment can use not what is typically used by the equipment at any one time Users should expect usage requirements to be approximately 60 of below value TO ESTIMATE POWER REQUIREMENTS 1 Watts W x 1 67 VA or Amps A x 230 VA 2 Add the totals up for all pieces of equipment and multiply this total by 0 6 to calculate actual requirements There are many factors that can affect the amount of power that your computer system will require Suggest the total load to be placed on the battery powered outlets should not exceed 80 of the unit s capacity HARDWARE INSTALLATION GUIDE Before installation please read and understand the following instructions 1 Placement The UPS must be installed in a protected environment away from heat emitting appliances such as a radiator or heat register Do not in
7. stall this product where excessive moisture is present 2 Ventilation The location should provide adequate air flow around the UPS with one inch minimum clearance on all sides for proper ventilation 3 Charge the Battery Your new UPS may be used immediately upon receipt However charge loss may occur during shipping and storage So charging the battery for at least 8 hours is recommended to insure that the battery is fully charged To recharge the battery simply leave the unit plugged into an AC outlet This UPS can be charged even when UPS is not turn on 4 Connect to AC Use power cord to connect the UPS to a wall outlet Please avoid a PLUGIN using extension cords and adapter HOLY Ge plugs To maintain optimal battery ll charge leave the UPS plugged in at l all times D L E J ao oio o 5 Connect the Load Connect the equipment to your UPS a outlets The IEC power cord coming om with the unit are used to connect your a i computer and monitor to the UPS PC UPS Items such as copiers laser printers vacuums space heaters or other large electrical devices SHOULD NOT be connected to the UPS Please make sure that the total loads of your equipments are less than the maximum total power load of your UPS 6 Connect to Computer Install your software and accessories To use the software simply use the USB cable to connect the UPS unit and your computer BASIC OPERATION
8. u cyberpowersystems com or contact CyberPower Systems B V Flight Forum 3545 5657DW Eindhoven The Netherlands Tel 31 40 2348170 E MAIL sales cyberpower eu com CyberPower Systems Inc USA 4241 12th Avenue East Suite 400 Shakopee MN 55379 U S A Tel 1 952 4039500 Fax 1 952 4030009 E MAIL sales cyberpowersystems com Entire contents copyright 2008 CyberPower Systems B V All rights reserved Reproduction in whole or in part without permission is prohibited PowerPanel Personal Edition is the trademark of CyberPower Systems Inc k i as d X l J l CE O g CyberPower warrants to you the original purchaser that CyberPower UPS will be free from defects in design assembly materials and workmanship for two years battery is only one year from the date of original purchase Any warranty services please contact your local dealers or distributors
9. ur UPS and disconnect its power cord from the wall outlet Disconnect all cables connected the UPS to avoid battery drain 2 The UPS should be stored in a cool dry location 3 Make sure the battery is fully charged before the UPS is stored 4 For extended storage in moderate climates the battery should be charged for 12 hours every 3 months by plugging the power cord into the wall receptacle Repeat it every 2 months in high temperature locations TROUBLE SHOOTING The battery is not fully Recharge the battery by leaving the UPS The UPS does not perform plugged in The battery is slightly worn Contact CyberPower Systems at out service cyberpower eu com expected runtime The on off switch is designed to prevent Turn the UPS off Wait 10 seconds and damage by rapidly turning it then turn the UPS on off and on The UPS will not The unit is not connected to The unit must be connected to a turn on an AC outlet 220 240V 50 60Hz outlet i Contact CyberPower Systems at Contact CyberPower Systems at service cyberpower eu com Turn the UPS off and unplug at least one piece connected equipment Unplug the power cord of the UPS then remove the fuse compartment beneath the power inlet of the UPS and replace the blown fuse with a spare one Lock the compartment back to the UPS Connect power cord then turn the UPS on Make sure that your spare fuse meets the specification The battery is discharged flee unit to recharge for

Download Pdf Manuals

image

Related Search

Related Contents

5350_Electrocardiografo 3 Canales Mod BTL-08 SD3  Fiche de données de sécurité  Proceedings of the 4th International Modelica Conference, Hamburg  Canon SELPHY DS810 Printing Guide  メニューマップ  Samsung WW60J4260HS/MF Manuel de l'utilisateur  WIZ108SR User Manual  Merkur 2 - Bircher  1116 00 05 Rev1 UM Condicionador de Ar PH9000FM (unificado)  BB2 Consumer Manual Version 2.2 © 2012 Blofield, The  