Home

Phoenix TRIO-PS/1AC/24DC/2.5

image

Contents

1. 24DC 5 Output characteristic curve The device functions following the U I characteristic curve Under load the working point follows this curve The output current is limited in the event of a short circuit or overload Thereby the device does not switch off but rather supplies a continuous output current The secondary voltage is reduced until the short circuit or overload on the secondary side has been remedied The U I characteristic curve ensures that both heavily capacitive loads and loads with DC DC converters in the primary circuit can be supplied Downstream fuses are triggered Selectivity in the design of your system is guaranteed at all times Uy 24 V IN 5A Py 120 W Thermal behavior With an ambient temperature of up to 55 C the device sup plies the continuous output current of Iy In the case of ambi ent temperatures above 55 C the output current must be reduced by 2 5 per Kelvin increase in temperature The de vice does not switch off at ambient temperatures of 70 C or thermal overload The output capacity is reduced as far as necessary to provide device protection After it has cooled down the output capacity is increased again PHOENIX CONTACT 12 TRIO PS 1AC 24DC 5 Parallel operation Devices of the same type can be connected in parallel to en able both redundancy and an increase in efficiency No other alignment is necessary when in the state of delivery If the output voltage is adjusted
2. following minimum distance to other modules 5 cm in a vertical di rection and 0 cm in a horizontal direction The power supply unit can be snapped onto all DIN rails in acc with EN 60715 They must be N 2 mounted horizontally connecting terminal blocks top and bottom TRIO POWER Mounting position Installation depth 115 mm DIN rail 102777_02_en PHOENIX CONTACT 8 Connection to various network forms TN S TN C The connection for 100 V AC 240 V AC is made using the L N and PE screw connections The device can be connected to 1 phase AC networks or to two of the phase conductors of 3 phase networks TN TT or IT networks in acc with VDE 0100 300 IEC 60364 3 with nominal voltages of 100 V AC 240 V AC In the case of input voltages gt 300 V AC the device switches off for its own safety After the overvoltage has ceased the device starts automatically within a few seconds For operation on two of the phase conductors of a three phase system an isolating facility for all poles must be pro vided 102777_02_en TRIO PS 1AC 24DC 5 Assembly Position the module with the DIN rail guide on the upper edge of the DIN rail and snap it in with a downward motion Removing Pull the snap lever open with the aid of a screwdriver and slide the
3. module out at the lower edge of the DIN rail In order to comply with the UL certification use copper cables that are designed for operating temperatures of gt 75 C In order to comply with EN 60950 UL 60950 flexible cables require ferrules To safely con nect a device the ferrules should have a length of at least 10 mm To achieve a reliable and shockproof connection strip the connect ing ends according to section Structure PHOENIX CONTACT 9 TRIO PS 1AC 24DC 5 Input Protection of the primary side The device must be installed in acc with the regulations as in EN 60950 It must be possible to disconnect the device using a Suitable isolating facility outside the power supply The primary side line protection for example is suitable For device protection there is an internal fuse Additional device protection is not necessary Recommended backup fuse for mains protection Power circuit breaker 6 A 10 A or 16 A characteristic B or identical function 8 SS S If an internal fuse is triggered there is most probably a malfunction in the device In this case the device must be inspected in the factory 102777_02_en PHOENIX CONTACT 10 TRIO PS 1AC 24DC 5 Make sure that all output lines are dimen sioned according to the maximum output cur rent or are separately protected The cables on the secondary side must have sufficiently large cross sections in order to keep the voltage drops on th
4. A characteristic B lt 3 5 mA 24 V DC 1 22 5V DC 29 5 V DC 5 A 0 C 55 C Above 55 C 2 5 per Kelvin Approx 10 A for short circuit Unlimited lt 1 change in load static 10 90 lt 2 change in load dynamic 10 90 lt 0 1 change in input voltage 10 18 W 1 1 W gt 89 lt 2 ms Ugyt 10 90 lt 20 mVpp lt 30 mVpp Yes for redundancy and increased capacity No Yes lt 35 V DC 35 V DC DC OK LED green Uour gt 21 5 V LED lights up PHOENIX CONTACT 3 102777_02_en General data Insulation voltage input output Insulation voltage input PE Insulation voltage output PE Degree of protection Class of protection MTBF Housing version Side element version Dimensions W H D state of delivery Weight Ambient conditions Ambient temperature operation Ambient temperature storage transport Max permissible relative humidity operation Vibration operation Shock Pollution degree in acc with EN 50178 Climatic class Standards Electrical Equipment for Machinery Safety transformers for power supply units Electrical safety of information technology equipment Electronic equipment for use in electrical power installations SELV Safe isolation Protection against electric shock Protection against electric shock basic requirements for safe isolation in electrical equipment Limitation of mains harmonic currents A
5. TRIO PS 1AC 24DC 5 Primary switched power supply 1 phase output current 5A INTERFACE Data Sheet 102 777 02 en PHOENIX CONTACT 06 2007 Description TRIO POWER is the rail mountable 24 V power supply unit Reliable power supply unit even at high ambient temper with basic functions With an output voltage of 24 V DC and atures 1 phase and 3 phase versions with 60 W or 960 W itis par No load and short circuiting resistance ticularly suited for use in series production in mechanical en _ gineering The wide range input and international certifica tion package allows worldwide implementation The high MTBF of 500 000 h stands for high supply reliability The devices can be connected in parallel to increase the ca pacity and redundancy The clear LED signaling and the device connection with dou ble terminal block for plus and minus for fast potential distri bution are further advantages of this device series A third terminal block for minus simplifies the grounding on the sec ondary side All power supply units are idle proof and short circuit proof and provide a regulated and settable output volt age of 22 5 V DC to 29 5 V DC with output currents of 2 5 A 5 A 10 A 20 Aor 40 A High dielectric strength Can be used worldwide in all industrial sectors due to a wide range input and an international approval package DANGER OF EXPLOSION Remove an item only when it is not connected to power or if it is loca
6. a uniform distribution of power is guaranteed by setting all parallel operated power supply units to exactly the same output voltage To ensure symmetrical distribution of power we recommend designing all cable connections from the power supply unit to a busbar of the same length and with the same conductor cross section The system makes it advisable to install a pro tective circuit at the output of each device when more than two power supply units are connected in parallel e g decou pling diode or DC fuse This prevents high reverse feed cur rents in the event of a secondary device fault Redundant operation Redundant circuits are suitable for the supply of systems which make especially high requirements on the operational safety If a fault occurs in the primary circuit of the first power supply unit the second device automatically takes over the entire power supply without interruption and vice versa For this reason the power supply units to be connected in paral lel are dimensioned in such a way that the total current re quirement of all consumers can be completely covered by one power supply unit 100 redundancy makes external decoupling diodes necessary QUINT DIODE 40 Order No 2938963 Increased performance For n parallel connected devices the output current can be increased to n x Iy Parallel connection to increase efficiency is used for the expansion of existing systems It is advisable to use parallel connecti
7. acteristic B Screw connection 9mm 24 V DC 1 22 5 V DC 29 5 V DC 5 A 0 C 55 C Screw connection 9mm Nm Torque 0 4 0 5 0 4 0 5 PHOENIX CONTACT 6 TRIO PS 1AC 24DC 5 Block diagram The power supply units are built in devices The device may only be installed and put into operation by qual IRs ified personnel The corresponding national regulations must be observed DANGER OF EXPLOSION Remove an item only when it is not connected to power or if it is located in the non explosive area DANGER Components with dangerously high voltage and high stored energy are located in the device Never carry out work on live parts Depending on the ambient temperature and the load the housing can become very hot Before startup please ensure The mains connection has been carried out by a competent person and protection against electric shock is guaranteed The device can be disconnected outside the power supply unit in accordance with the regulations as in EN 60950 e g through primary side line protection The ground conductor is connected All feed lines are sufficiently protected and dimensioned All output lines are dimensioned according to the maximum output current of the device or separately protected Sufficient convection is guaranteed 102777_02_en PHOENIX CONTACT 7 TRIO PS 1AC 24DC 5 Installation In order to guarantee sufficient convection we recommend observing the
8. d radio interference in acc with EN 55011 102777_02_en TRIO PS 1AC 24DC 5 Level 3 6 kV 8 kV Criterion B Level 3 80 MHz 3 GHz 10 V m Criterion A 4 kV level 4 asymmetrical conductor to ground 2 kV level 3 asymmetrical conductor to ground Criterion A 4 kV level 4 asymmetrical conductor to ground 2 kV level 4 symmetrical conductor to conductor Criterion A Level 3 asymmetrical 0 1 MHz 80 MHz 10 V Criterion A mains buffering gt 10 ms Criterion B EN 55011 EN 55022 Class B area of application Industry and residential EN 55011 EN 55022 Class B area of application Industry and residential PHOENIX CONTACT 5 TRIO PS 1AC 24DC 5 Structure S 2 Y S Q SS E Input data Input nominal voltage range AC input voltage range AC frequency range Input fuse integrated Recommended backup fuse for mains protection Type of connection Stripping length Output data Nominal output voltage Setting range of the output voltage Output current Type of connection Stripping length 102777_02_en 1 AC input 2 DC output 3 Potentiometer 22 5 V DC 29 5 V DC 4 DC OK LED 5 DIN rail adapter 6 Take up for cable binders mmz AWG solid stranded Input 0 2 2 5 0 2 2 5 24 14 Output 0 2 2 5 02 25 24 14 100 VAC 240 V AC 85 V AC 264 V AC derating lt 90 V AC 2 5 per Kelvin 45 Hz 65 Hz 3 15 A slow blow internal 6A 10A 16 A char
9. e lines as low as possible You can fasten the connection cables to the housing using cable binders Ensure that the cable binders and the connec tion cables are designed for the surface tem peratures that occur in operation Make sure that the insulation of the connection cables is not damaged when tightening the ca ble binders TRIO POWER The connection is made using the and screw connec tions on the screw connection of the DC output At the time of delivery the output voltage is 24 V DC The output voltage can be set on the potentiometer Protection of the secondary side The device is electronically protected against short circuit and idling In the event of a malfunction the output voltage is limited to 35 V DC Signaling The DC OK LED enables evaluation of the function of the power supply directly on site Output voltage gt 21 5 V Output voltage lt 21 5 V or no voltage at the output Meaning Output voltage and output TRIO POWER is in operation but there is a fault on the side current OK of the consumer the current consumption is greater than ly or the output is short circuited TRIO POWER is out of operation because there is no mains voltage the fuse on the primary side has been triggered or the device is faulty 102777_02_en PHOENIX CONTACT 11 Function Your V Output current A 102777_02_en 40 lour A 60 Ambient temperature C TRIO PS 1AC
10. i eo ec cata sera ace acetic gcc et tee vac roca cen orcas 12 OQuiput enge s STE CUNY TT 12 BK Z venr 1 He Ue ToT 12 STH Rea ee DT 13 102777_02_en PHOENIX CONTACT 2 TRIO PS 1AC 24DC 5 Order data Description Primary switched power supply 1 phase output current 5 A Technical data Input data Input nominal voltage range AC input voltage range AC frequency range Current consumption Inrush current limitation It Power failure bypass Typical response time Power factor cos phi Protective circuitry Input fuse integrated Recommended backup fuse for mains protection Discharge current to PE Output data Nominal output voltage Setting range of the output voltage Output current Derating Current limitation Max capacitive load Control deviation Power loss nominal load max Maximum power dissipation idling Efficiency Ascent time Residual ripple Peak switching voltages Connection in parallel Connection in series Surge protection against internal surge voltages Resistance to reverse feed Signal output DC OK active Status display Type Order No Pcs Pkt TRIO PS 1AC 24DC 5 2866310 1 100 V AC 240 V AC 85 V AC 264 V AC derating lt 90 V AC 2 5 per Kelvin 45 Hz 65 Hz 1 65 A 120 V AC 0 9 A 230 V AC lt 15A 1 1 A2s gt 20 ms 120 V AC gt 110 ms 230 V AC lt 1s 0 72 Transient surge protection Varistor 3 15 A slow blow internal 6A 10A 16
11. on if the power supply unit does not cover the current requirement of the most powerful con sumer Otherwise the consumers should be spread among individual devices independent of one another A maximum of five devices can be connected in parallel 102777_02 en PHOENIX CONTACT GmbH amp Co KG 32823 Blomberg Germany 13 Phone 49 0 5235 3 00 Fax 49 0 5235 3 4 12 00 www phoenixcontact com
12. pprovals UL rating 102777_02_en TRIO PS 1AC 24DC 5 4 kV AC Type test 2 kV AC routine test 2 kV AC type test 2 kV AC routine test 500 V DC type test IP20 I with PE connection gt 500 000 h in acc with IEC 61709 SN 29500 Steel sheet zinc plated Aluminum 40 mm 130 mm 115 mm 0 6 kg 25 C 70 C gt 55 C derating 40 C 85 C 95 at 25 C no condensation lt 15 Hz amplitude 2 5 mm in acc with IEC 60068 2 6 15 Hz 150 Hz 2 3g 90 min 15g in all directions in acc with IEC 60068 2 27 2 3K3 in acc with EN 60721 EN 60204 EN 61558 2 17 EN 60950 VDE 0805 SELV EN 61558 2 17 EN 50178 VDE 0160 PELV EN 60950 SELV EN 60204 PELV DIN VDE 0100 410 DIN VDE 0106 1010 DIN 57100 410 DIN VDE 0106 101 EN 61000 3 2 UL C UL Listed UL 508 UL C UL Recognized UL 60950 PHOENIX CONTACT 4 Conformance with EMC directive 89 336 EEC Immunity to interference in acc with EN 61000 6 2 Discharge of static electricity Housing Contact discharge Discharge in air Comments Electromagnetic HF field Housing Frequency range Field intensity Comments Fast transients burst Input Output Comments Surge current loads Surge Input Output Comments Conducted interference Input output Frequency range Voltage Comments Voltage dips Input Comments Emitted interference in acc with EN 61000 6 3 Radio interference voltage in acc with EN 55011 Emitte
13. ted in the non explosive area DANGER Components with dangerously high voltage and high stored energy are located in the device Never carry out work on live parts Depending on the ambient temperature and the load the housing can become very hot Make sure you always use the the latest documentation It can be downloaded at www download phoenixcontact com A conversion table is available on the Internet at www download phoenixcontact com general 7000 en OO pdf DOG 0OC DMO0Meleo gt Lionna 0D E INSPIRING INNOVATIONS TRIO PS 1AC 24DC 5 Table of contents HESS SUMO TTT 1 Tape Or CO tS TTT 2 0 2 i Fz rc ere eee arene Rinne tie emote Nee Pon renee REN eee nea NEUE OU nT ra nn ae en ee ee ere ee eee ae 3 NG Il Mik TTT 3 ee heH 6 BOCKA TTT 7 sale mand T aT g NOl HT 7 HENS VANEAU Eseries A uae ean cee E eee 8 ates Fei feta e e le a ie me eer neers OT yee ee PEP Er aE OS SRE OER ELE Perr ee Tee 8 LT ne UT 9 KENO II ee L O dasebeaes aaceda sadeenanee 9 Connection to various network fFOPMS 2 0 eee cece cee cesceseceecceeseneceeseseceeseeeceeseuseauseaeseeseeeseseseeseesvarseeesneenesnresseeeneds 9 Ise EN PEE PE E N E E LE EET A EET P EE T EE CEC EAE PE A A E EE E EEA A E E A 10 Protection orthe PRIMARY Side iee a ee a eeraa a Sawaal 10 Recommended backup fuse for mains protection eee eee eee e 10 9700 ee eE A eae a E A T E a eer ee ee ere 11 Protection of the secondary Side sse eee 11 0 312 a 6 TTT 11 S