Home
SCF 050 CORN FURNACE Installation & Operations Manual
Contents
1. A closer look at the Control Board to the right in figure 14 will explain how the board ON OFF works There are five buttons labeled 1 through 5 a slide switch labeled 6 and a LED Light bar with 5 Heat Settings The LED Light bar is also used during the Diagnostic process see page 28 for more details The buttons on the board function as follows Refer to Figure 14 The touch pad buttons are labeled with the white numbers 1 through 5 1 The Heat Level button 1 will advance the setting between level 1 and 5 Once you reach level 5 it will drop back to level 1 Each level has a LED light to indicate where Figure 14 the board is set SCF 050 Manual 25 Sold and serviced by www PelletKing com 603 424 1183 2 The On Off button 2 turns the Furnace On and Off It will also reset the board after the board has sensed a problem and is flashing a Diagnostic code 3 The auger button 3 will allow the customer to manually auger corn into the burn pot on start up when needed This is particularly helpful in priming the Auger Tube when it is empty 4 The Draft Trim button 4 allows for adjusting the Exhaust fan voltage on Heat Level 1 only Push the button and the all of the LED Lights in the light bar will flash once This decreases the voltage approximately 5 volts below the default setting Push the button a second time and all of the LED Lights in the light bar will flash twice This increases the voltage approximately 5 vol
2. pe POT BOTTOM TWO TURNS Es we d H ACCESS COVER CAUTION CLEAN OUT RODS WILL BE HOT USE HANDLE TOOL SLIDE END OF HANDLE TOOL INTOSLOT _ e PULL COAL RAKE A FORWARD UNTIL A IT STOPS The area shown above is located inside the Furnace Firebox and must be accessed through the Firebox door Figure 21 Burnpot amp Slide out Bottom Removal To remove the Burnpot from the Furnace the Coal Rake must be pulled back so the pot will clear it Open the Firebox door of the Furnace and you will see 2 Hex head screws Follow steps 1 through 4 in the diagram to the left to remove the Burnpot from the Furnace To remove the Slide out Bottom follow steps 1 through 3 in the diagram to the right SCF 050 Manual 40 Sold and serviced by www PelletKing com 603 424 1183 3 Clean Out Ports The Furnace has 3 Exhaust Cleanout Ports located in the LEFT AND RIGHT lower corners of the firebox and behind the Ashpan Remove covers and clean regularly CLEAN OUT PORT LEFT SIDE SHOWN CLEAN OUT PORT BEHIND REMOVE COVERS ASH PAN REGULARLY AND CLEAN AS DESCRIBED Figure 22 Frequency of cleaning depends on the amount of fuel being burnt and the quality of the Corn Pellets Failure to clean the ash traps will cause the Furnace to become plugged with Fly Ash 4 Heat Exchange Baffle Remove the baffle and clean the ashes that acc
3. Also make sure you are using clean corn Otherwise this is mainly caused by improper combustion See Damper Adjustment section of the Operations Manual Besides the damper adjustment there are several areas that can have an effect on the combustion process Solution Check all Gaskets Doors and door Latching Systems for air leaks Any leaks in these areas will negatively affect the burn process and cause the pot to overload Also make sure the slide out bottom is closed all the way If this is left open combustion air will leak out the bottom of the pot area instead of being used in the combustion process 3 My Furnace runs for approximately 6 to 10 hours and then overloads the Burnpot What s wrong Solution This most likely means the combustion process is taking place on top of the Coal Rake During normal burning of corn the Coal Rake must be pulled out of the burnpot This causes the pot to fill up prematurely and overload The coal rake will be damaged if left in the pot for long periods of time 4 My Furnace isn t burning and the number 2 LED light is blinking This diagnostic light indicates the vacuum switch no longer senses negative pressure in the firebox area of the Furnace What caused the Furnace to go out The door of the unit was left open longer than 60 seconds See solution The ash pan door was left open for longer than 60 seconds See solution The combustion fan is not running Defective fan or control bo
4. In this manual approved venting will be referred to a PL vent or Single wall vent All single wall vent adaptors must be stainless steel NOTE TYPE B GAS VENT MUST NOT BE USED IN THE INSTALLATION OF THIS FURNACE Examples of venting system components follow High temperature ceramic roping reduces potential fly ash escaping through joints Stainless steel inner liners resist corrosive flue gas damage to the system Flex pipe should be stainless steel 4 ply construction with a total thickness of approx 07 inches AN SCF 050 Manual 10 Sold and serviced by www PelletKing com 603 424 1183 TYPICAL PL VENT COMPONENTS A RAIN CAP VERTICAL OR WALL THIMBLE CHIMNEY HORIZONTAL ADAPTER ADJUSTABLE LENGTH SINGLE TEE SINGLE REDUCTION DOUBLE TEE PIPE w TEE CAP TEE w TEE CAP w TEE CAP SUPPORT BRACKET iS t 5 PIPE ADAPTER INCREASER 45 ELBOW 90 ELBOW SCF 050 Manual 11 Sold and serviced by www PelletKing com 603 424 1183 VENTING DETERMINING MATERIALS TYPE OF MATERIALS 1 PL Vent must be used 2 Exception Single wall stainless steel may be used inside an existing chimney No clearances to combustibles are needed on single wall stainless steel adaptors rigid or flex pipe installed within a chimney 3 A clean out tee PL Vent or Quick Connect Exhaust must be installed directly to the furnace and at the bottom of each vertical run of the ex
5. Proper installation is essential for safety effective Operation Warranty Coverage Insurance requirements and to meet Local Building Codes Installation Requirements are described in the first section of this manual Verify the installation is correct before firing up the furnace for the first time When burning corn care should be taken in how the venting system is installed To burn corn the moisture content should be 15 or less This is much higher that the moisture content of wood pellets and can result in condensation forming in the venting system in certain installations The chimney system should stay within the warm envelope of the house as much as possible Only penetrate the exterior of the home where the exhaust system will terminate REMEMBER Condensation from a corn furnace is detrimental to the venting system Only buy venting systems that are warranted with burning corn PREVENTING CHIMNEY FIRES Chimney fires can be prevented by properly operating the Furnace and by periodic inspection and cleaning of the chimney When wood is burned it produces tar and other organic vapors which combine with expelled moisture to form creosote The creosote vapors condense in the relatively cool chimney flue associated with a slow burning fire As a result creosote residue accumulates on the flue lining When ignited this creosote can result in an extremely hot chimney fire The chimney and chimney connector should be inspected at least once ev
6. Cycle Time on the Control Board The 10 second Cycle is the factory setting PINS swe When the jumper cap is on the left hand pins the Cycle time is 10 seconds This cycle may be used with Corn and Pellets LEFT When the jumper cap is on the right hand pins the Cycle time is 10 seconds This cycle may only be used with Pellets Before calling your dealer for assistance please read your Operations Manual and perform all the maintenance issues covered in the Daily and Periodic Maintenance section of the Manual If the Furnace still does not operate correctly call your Dealer for Assistance SCF 050 Manual 53 Sold and serviced by www PelletKing com 603 424 1183 SCF 050 WARRANTY The Furnace manufactured by Even Temp Inc is warranted for five 5 years to the original owner against defects and workmanship on all steel parts excluding the burn grate and two 2 year on electrical components from the date of sale to the original owner There specifically is no warranty on the paint glass burn grate and all gaskets There is no written or implied performance warranty on the Furnace as the manufacturer has no control over the installation daily operations maintenance or the type of fuel burned This warranty will not apply if the Furnace has not been installed operated and maintained in strict accordance with the manufacturer s instructions Burning other than quality corn may cause Furnace damage and could void th
7. Heat Pump furnace with a minimum rating of 45 000 BTU The duct work of the furnaces may not be hooked in series with each other This means the Warm Supply Air of the SCF 050 may not be hooked the Cold Air Return of the existing furnace See example in figure 8 above The Cold Air return of the SCF 050 is connected to the Return Air Duct of the existing furnace The Warm Air Supply of the SCF 050 connects to the Supply Plenum of the existing furnace Back Draft Dampers must be used in the SCF 050 Warm Air duct and in the Warm Air Plenum of the existing furnace to prevent the air flow from reversing It is recommended to enter the Supply plenum of the existing furnace above the Air Conditioning A coil The materials used for the Warm Air supply duct must have a minimum temperature rating of 250 degrees F The Plenum of the SCF 050 must be constructed of metal Once installed as an Add On furnace check the Static pressures in the ductwork to make sure they do not exceed the limits on the existing Central furnace or of the SCF 050 Running both furnaces at the same time should not cause any nuisance tripping of the High Limits in either unit Follow all instructions when connecting to existing ductwork Connecting the Warm Air Supply to the Cold Air return may cause harm to the existing furnace and may void the warranty of both the existing furnace and the SCF 050 CAUTION Do not connect an air conditioning system to this unit SCF 050 Manual 16 Sold
8. and serviced by www PelletKing com 603 424 1183 Blower Specs The Blower is a 2 Speed blower 600 800 CFM When connecting this unit to a duct system the high speed should be used If the Furnace is to be used as a stand alone shop heater the option is available to select the 600 CFM setting or the 800 CFM setting The slower speed will produce higher air temperatures because the air moves slower through the heat exchange system allowing it to become hotter Minimum Duct Size 2 SPEED BLOWER Round 10 SWITCH Rectangular 6 x 15 Intake Air Duct should be 10 larger Maximum Static Pressure 4 Velocity 1400 FPM at the above mentioned duct sizes A larger duct size will produce less Air Flow noise the above mentioned sizes are the minimum allowed Fan Limit Control The Furnace uses a Fan Limit Control built into the furnace centered below the 10 plenum opening The High Limit function of this control is set at a maximum setting of 200 degrees F CAUTION DO NOT TAMPER WITH THE HIGH LIMIT SETTING There are two adjustable Fan Control Settings They control when the Convection Blower turns on and when the Blower turns off This will help control the temperature of the air coming out of the registers These settings may be adjusted to accommodate customer preference If the air seems too o cool simply adjust the Fan Off setting higher to shut the AWAY blower down sooner Factory settings are
9. difficulty adjusting the Furnace contact your dealer or the Technical Support Department for St Croix at Even Temp Inc SCF 050 Manual 23 Sold and serviced by www PelletKing com 603 424 1183 OPERATING INSTRUCTIONS A different type of heater The SCF 050 is a furnace FOLLOW THESE OPERATING INSTRUCTIONS EXACTLY AS STATED TO ENSURE SAFE AND RELIABLE OPERATION 1 Carefully read this Operation and Maintenance manual in its entirety BEFORE lighting your Furnace for the first time 2 Obtain final inspection and approval of installation from local building officials 3 Have your dealer demonstrate all the operational and maintenance steps necessary for proper use of the furnace Sign and return the warranty card to the address listed on the back page 4 Some odors may be given off during the first few hours of burning during initial break in These odors are normal and not harmful However ventilating the room until the odors disappear is recommended 5 The furnace will become HOT while in operation Keep children clothing and furniture away from all hot surfaces WARNING Direct contact with the furnace firebox during operation may cause skin burns 6 To avoid the possibility of smoke and or sparks entering the room always keep firebox and ash pan doors closed whenever the furnace is operating 7 A certain amount of carbon monoxide may be produced within the Furnace as a by product of combustion All exhaust vent con
10. of the burn pot The burning fuel on top and the clinker on the bottom 2 The slide out bottom This allows the bottom to be pulled out so the clinker can drop out of the bottom of the burn pot 3 The program on the control board To drop the clinker you set the board on the 1 setting for a couple of seconds and then return the Furnace to the desired setting This starts a timed delay in the program allowing the clinker to be removed the coals to be dropped to the bottom of the pot and the Burn pot to become balanced again before the board resumes on the setting of you choice NOTE WHEN YOU FIRST OPERATE YOUR FURNACE CHECK TO DETERMINE THE NEEDED CLEANING FREQUENCY THE FURNACE REQUIRES A MINIMUM AMOUNT OF DAILY MAINTENANCE REQUIRED MAINTENANCE DEPENDS LARGELY UPON THE QUALITY OF CORN PELLETS BURNED AND THE RATE OF BURN THE AMOUNT OF DAILY MAINTENANCE WILL INCREASE IF FUEL QUALITY DECREASES AND OR THE BURNING RATE OF CORN PELLETS INCREASES NOTE FAILURE TO KEEP YOUR FURNACE CLEAN AS DESCRIBED IN THIS MANUAL COULD RESULT IN POOR OPERATION INEFFICIENT FUEL USAGE AND A POSSIBLE SAFETY HAZARD IT IS THE RESPONSIBILITY OF THE OWNER USER TO DETERMINE THE NEEDED MAINTENANCE FREQUENCY CAUTION THE DOOR AND FRONT PART OF THE FURNACE WILL BE HOT DO NOT TOUCH ANY PART OF THE FURNACE THAT IS HOT SCF 050 Manual 36 Sold and serviced by www PelletKing com 603 424 1183 Daily Maintenance Example of Schedule for dropping Clinkers
11. shown in figure 9 HIGH LIMIT SETPOINT The Fan limit has a Break Away Tab that has been removed When replacing a Fan Limit Control be sure to remove the tab as shown in figure 9 Figure 9 SCF 050 Manual 17 Sold and serviced by www PelletKing com 603 424 1183 Mobile Home Installation Unit must be installed in accordance with the Manufactured Home and Safety Standard HUD CFR 3280 Part 24 The Furnace has been tested and listed for mobile home installations In addition to all previously detailed requirements mobile home installations must observe the following 1 WARNING DO NOT INSTALL IN A SLEEPING ROOM 2 WARNING COMBUSTION AIR MUST COME FROM THE OUTSIDE OF THE MOBILE HOME FAILURE TO DO SO MAY CREATE NEGATIVE PRESSURE WITHIN THE MOBILE HOME AND COULD DISRUPT PROPER VENTING AND OPERATION OF THE PELLET FURNACE 3 CAUTION THE STRUCTURAL INTEGRITY OF THE FLOORS WALLS CEILING AND ROOF MUST BE MAINTAINED FLOOR PROTECTION METAL CHASSIS GROUND STRAP Figure 10 SCF 050 Manual 18 Sold and serviced by www PelletKing com 603 424 1183 4 Permanently bolt the Furnace to the floor 5 Electrically ground the Furnace and pedestal to the metal chassis of the home Use a number eight 8 gauge or larger copper wire 6 Maintain an effective vapor barrier at location where PL vent exits the structure Check any other local building codes or other codes that may apply
12. the Furnace down Adjust the damper See Damper Adjustment in the Operations Manual The Burnpot being empty will mean the auger quit feeding fuel while there was still a fire in the burnpot Check to see if there is fuel in the hopper If the hopper is empty fill the hopper and re light the Furnace d If there is fuel in the hopper check to see if there is an obstruction in the auger system or if the auger set screw is loose Solution Remove obstruction and re light the Furnace or tighten the setscrew on the auger shaft My Furnace isn t burning and the 2 and 3 LED lights are blinking This means the high Limit has shut the Furnace down The Convection Blower could be defective or may need cleaning The high limit switch may be also defective It is best to call your dealer for support when trying to troubleshoot the High Limit Switch Do not use your Furnace if the High Limit switch frequently trips I lit the Furnace and the 2 light started blinking and smoke spills out of the Furnace How do I get the Furnace to quit smoking SCF 050 Manual 50 10 11 Sold and serviced by www PelletKing com 603 424 1183 Cause The Furnace did not establish a vacuum and shut down With the fuel in the pot burning the smoke finds the path of least resistance and leaks out into the house See Installation Manual Minimum vertical height needed to establish some natural draft and prevent smoke spillage Solution Pull the Slid
13. the burn pot rapidly turns into glowing coals If you see a lot of unburned corn in the pot an adjustment may be needed In an unbalanced pot the corn will quickly stick together and prevent the proper flow of combustion air The pot will overload and the fire will go out When burning pellets make sure to check for the formation of creosote in the unit and venting system Constantly running the Furnace on a low setting with too much combustion air may cause creosote to form Burn pot temperatures can be too cool when burning on low with too much draft Once the damper is adjusted for your installation it should not be necessary to make any further adjustments to the damper The combustion air is automatically increased every time the feed rate is advanced on the control board If you notice a difference in the operation of the Furnace first check to see if the Furnace needs cleaning Then check to see if there is a change in the fuel you are burning The moisture content of your corn may be too high or the quality of the pellets you are burning may have changed Break in requires the burning of 15 bushel of corn or 15 bags of pellets or a continuous burn for two weeks 0 D E The setscrew is a useful tool in Sms making adjustments to the Air Intake damper Adjust the damper by turning the screw one half turn clockwise and place the damper blade against the screw Wait 10 minutes to allow the burn to adjust to the new setting Making to
14. there weren t enough coals in the pot when the corn started feeding into the pot during start up the Furnace should be burning fine and an adjustment is most likely not needed b Advance the heat setting to 2 and let the Furnace burn at this setting for Ya an hour Check the burn pot to see if it is balanced Most likely the Furnace will be burning fine at this point because the damper was preset at the factory c Advance the heat setting to 3 and let the Furnace burn at this setting for an hour Check the burn pot to see if it is balanced Remember Look at the coals in the pot not at what the flame looks like Most likely the damper will not need to be adjusted d Advance the heat setting to 4 and let the Furnace burn at this setting for Y an hour Check to see if the pot is balanced This is where a damper adjustment might need to be made As the heat setting reaches the higher settings the Lag time can become too long if the air isn t adjusted correctly If you notice that the coals are being covered up with unburned corn adjust the damper to give it more air Remember Only turn the setscrew one Y turn clockwise to open the damper You might need to use a screwdriver to break up the clump of corn in the burn pot to allow for proper airflow Wait 15 minutes to see if the burn pot becomes balanced Repeat this step as many times as needed until the burn pot becomes balanced SCF 050 Manual 33 Sold and serviced by www P
15. 03 424 1183 STEP ONE COAL RAKE Figure 19 IS PUSHED IN Y AS 8 POT BOTTOM SS amp IS PUSHED IN 2 The ash pan Make sure the Ashpan is not too full to receive a clinker If the Ashpan is too full the clinker may not drop all the way through This will not allow the pot bottom to be closed If this happens empty the Ashpan and restart the Furnace 3 The slide out bottom See figure 20 Now you are ready to drop the clinker from the burn pot Pull the bottom out in one quick motion and let the clinker drop into the ash pan Quickly push the bottom in again To pull out the slide bottom use the Rod Handle tool shown in figure 21 on page 40 THE COAL RAKE WILL BE PUSHED IN amp THE POT BOTTOM WILL BE PULLED OUT Figure 20 4 The control board Set the heat setting to 1 for a few seconds and return to the setting it was on This initiates the time delay for dropping the clinker SCF 050 Manual 38 Sold and serviced by www PelletKing com 603 424 1183 5 Dropping the coals back into the burn pot At this time pull the coal rake back out of the burn pot to drop the coals in the pot See position of Coal Rake amp Pot Bottom in figure 18 on page 37 for normal operation The time delay in the program will allow a smooth transition back to where the Furnace was burning before the clinker was dropped 6 Cleaning the Heat exchange tubes Now you can pull the tube scraper back and forth a couple of t
16. 2 If the Furnace has been running for an extended period of time on the 5 setting the clinker will sometimes stick to the burn pot If that happens pull the coal rake back out Open the door and use a long screwdriver and give the clinker a couple nudges in the pot Make sure the burnpot bottom is closed when you do this or you will lose the coals with the clinker Then repeat the steps for dropping the clinker Remember The coal rake must be pulled out and the slide bottom pushed in during normal operation of the Furnace See Furnace layout on page 6 Remember The fire door and ash pan doors must be in the latched position during normal operation of the Furnace See Furnace layout on page 6 SCF 050 Manual 39 Sold and serviced by www PelletKing com 603 424 1183 Periodic Maintenance CAUTION Periodic maintenance should only be done while the Furnace is shut off and cold 1 Ashpan Empty the ash pan when it appears full approximately once a week The frequency of cleaning the ash pan will depend on the quality and amount of Corn Pellets being used Carefully check to make sure the ash pan door is tightly closed after each opening 2 Burnpot and Slide Out Bottom Clean burn grate holes whenever needed Remove the Burnpot and use a small metal object Nail Drill Bit etc to clean out plugged holes See Figure 21 below STEP 4 LIFT POT UP g TO REMOVE 5 FROM FURNACE STEP 2 oe La STEP 2 LOOSEN SCREW gt
17. 8 Do no use components other than those specified for use with this unit 9 Floor protection requirement must be followed precisely 10 PL Vent must be used for exhaust venting Single wall vent is not allowed Follow PL Vent manufacturer s installation directions and observe all listed clearances to combustibles DO NOT CONNECT THE SCF 050 FURNACE TO A DOWN FLOW FURNACE SYSTEM Thermostat Hook Up NOTE Installers must determine a neutral location of where to mount the Thermostat in order for accurate room temperature measurements Wiring Connections To hook up a thermostat connect the wires from the thermostat to the external Wire Terminal on the left side of the Furnace The external Terminal has been pre wired to the thermostat connections on the back of the control board For Information on how the Thermostat operates please read the section covering thermostat operations THERMOSTAT WIRE TERMINAL Figure 11 SCF 050 Manual 19 Sold and serviced by www PelletKing com 603 424 1183 SCF 050 OPERATION CAUTION Operate this unit only with the fuel hopper lid closed Failure to do so may result in emission of products of combustion from the hopper under certain conditions Maintain hopper seal in good condition This unit requires 120 volt AC power to operate In the event on a power failure the unit will shut down DO NOT ATTEMPT TO RUN THE UNIT DURING A POWER FAILURE INSTALLATION CHECK
18. BLOWER OR TO A CHIMNEY OR VENT SERVING A GAS FURNACE OR APPLIANCE This furnace should only be installed on a furnace duct system and chimney that are in good operating condition This furnace is equipped with a direct drive blower motor This motor should not be changed with one of lesser speed A motor with a faster speed may be used The size of the blower should not be changed This equipment should be installed acceptable to regulatory authority by experienced licensed personnel The installation of this furnace should comply with the requirements of CAN CSA b365 and changes to the installation should comply with CSA B139 for oil fired C22 1 for electric or CAN CGA B149 2 for gas fired SCF 050 Manual 48 Sold and serviced by www PelletKing com 603 424 1183 TROUBLESHOOTING FRQUENTLY ASKED QUESTIONS The Furnace is very trouble free in operation when properly maintained and quality pellets are used When the Furnace fails to operate properly troubleshooting by the operator of the Furnace is limited Please read the following guide for answers to frequently asked questions 1 When first starting the Furnace remember the auger tube is empty which will delay feeding fuel to the burn pot This will in some cases prevent the Furnace from starting Solution Prime the burn pot if the auger tube is empty 2 My Furnace keeps overloading the burnpot First check the moisture content of your corn It should be 15 or less
19. D ASH Do Not Use Chemicals or Fluids to Start The Fire Do Not Burn Garbage Gasoline Naphtha Engine Oil or Other Inappropriate Materials The Furnace will not operate during a power failure unless a Battery Back up system is used during brief power outages Prolonged Power Outages will require the use of a Generator to operate the Furnace SCF 050 Manual 47 Sold and serviced by www PelletKing com 603 424 1183 Additional Canadian Requirements for Supplementary Add On Furnaces See label on the inside front panel of the furnace for additional information 1 2 3 10 11 DO NOT USE DUCT ELBOWS HAVING AN INSIDE RADIUS OF LESS THAN 6 150mm ON THE FURNACES DO NOT CONNECT DUCTWORKSO THAT A REVERSE FLOW IS POSSIBLE OPERATE THE GAS OIL OR ELECTRIC FURNACE PERIODICALLY TO ENSURE THAT IT WILL OPERATE SATISFACTORILY WHEN NEEDED CERTIFIED FOR INSTALLATIOS WITH DUCT WORK CONFIGURATIONS SIMILAR TO THAT SHOWN IN FIGURE 8 ON PAGE 16 DO NOT RELOCATE OR BYPASS ANY OF THE SAFETY CONTROLS IN THE ORIGINAL GAS OIL OR ELECTRIC FURNACE INSTALLATION DO NOT CONNECT WITH ANY GAS FURNACE THAT HAS NOT BEEN CERTIFIED INITIALLY AS COMPLYING WITH CAN CGA 2 3 THE OPERATION OF THE GAS FURNACE MUST BE VERIFIED FOR ACCEPTABLE OPERATION BEFORE AND AFTER INSTALLATION OF THIS ADD ON FURNACE BY A GAS FITTER WHO IS RECOGNIZED BY THE REGULATORY AUTHORITY DO NOT CONNECT TO ANY GAS FURNACE THAT IS NOT EQUIPPED WITH A AN AIR CIRCULATING
20. E DAMPER IN THE EXHAUST SYSTEM OF UNIT DO NOT CONNECT THIS FURNACE TO A CHIMNEY SYSTEM THAT IS CONNECTED TO ANOTHER APPLIANCE DO NOT INSTALL THIS UNIT IN A SLEEPING ROOM ATTENTION CONDENSATION When planning the installation of your Furnace keep in mind that condensation is detrimental to exhaust systems Corn has higher moisture content than pellets and can be more susceptible to condensation forming in certain types of installations Install the Furnace with a minimum of the system exposed to the cold temperatures outside the envelope of the house Check with the manufacturer of your venting system that they honor the warranty of their PL Vent with the use of corn ATTENTION BATTERY BACKUP We strongly recommend using a battery backup system if the furnace is installed using horizontal venting only This prevents any smoke from entering your home in the event of a power failure SCF 050 Manual 9 Sold and serviced by www PelletKing com 603 424 1183 VENTING APPROVED MATERIALS The Furnace requires a venting system approved for pellet Furnaces by a certified testing lab Approved pellet Furnace venting materials are 1 PL vent a double wall vent with a stainless steel liner and 2 Single wall rigid or flexible stainless steel pipe PL Vent and Single wall vent is available through manufacturers such as Energy Vent LTD James A Ryder Simpson DuraVent and Selkirk Metalbestos and is carried by many local pellet Furnace dealers
21. E STRICTLY PROHIBITED DAMPER Figure 7 2 Outside air may be drawn from a semi enclosed attic or crawl space or any semi enclosed space Take care not to draw cold air past water pipes that may freeze 3 Increase the outside air pipe diameter to 3 for runs over ten 10 feet and elevation over 4 000 feet Note Long runs should be avoided 4 Terminate the outside air pipe below the exhaust vent outlet 5 5 An open mesh screen should be placed over the outside air pipe opening to prevent birds or rodents from nesting in the opening Use an elbow or shield to prevent prevailing winds from blowing directly into the outside air intake pipe NOTE Mesh screen should be no smaller than one fourth inch 1 4 by one fourth inch 1 4 WARNING OUTSIDE COMBUSTION AIR IS REQUIRED FOR ALL MOBILE HOME INSTALLATIONS SCF 050 Manual 15 Sold and serviced by www PelletKing com 603 424 1183 Connecting To Existing Duct Work amp Furnaces Before installing the furnace check the Static Pressure in the duct system Static Pressure must not exceed A IWC in the duct system BACK DRAFT DAMPER EXISTING After Installation check the FURNACE Static Pressure in the duct system If Pressure is more than 4 IWC the duct system must be changed to reduce the pressure below the maximum rating of 4 IWC RETURN AIR Figure 8 The SCF 050 may be connected to the existing ductwork of a Gas Oil or Electric
22. ENT REQUIRES A 3 CLEARANCE TO COMBUSTIBLES USE UL LISTED WALL THIMBLES AND FIRESTOPS I FLOOR JOISTS VJ NMS S DS 4 Q VU CLEARANCE TO PUBLIC WALKWAY CLEARANCES TO COMBUSTIBLES 247 CLEARANCE 47 TO GROUND O HA Figure 5 THE EXHAUST TERMINATION LOCATION MUST BE AT LEAST 1 305 mm T 2 1 m 1 305 mm 2 610 mm ABOVE the ground level FROM a public walkway FROM The wall penetration point FROM any adjacent combustibles such as Adjacent buildings fences protruding parts of the structure roof eaves or overhangs plants shrubs etc SCF 050 Manual 13 Sold and serviced by www PelletKing com 603 424 1183 Venting into an Existing Chimney CAP STORM COLLAR 24 ALWAYS FOLLOW PL VENT MANUFACTURERS CLEARANCES TO COMBUSTIBLES FLASHING CEILING LE OR x T WALL THIMBLE MASONARY THIMBLE 3 EARANCE TO OMBUSTIBLE 3 HHH ll PL VENT TEE WITH CLEANOUT E E mi E Figure 6 The Furnace may be connected to an existing Class A chimney or a masonry chimney which meets the minimum requirements of NFPA 211 1 If the Furnace s exhaust is connected to a masonry chimney the masonry chimney must be free of cracks that could leak exhaust gases or fly ash A relining of the chimney with either PL vent or single wall stainless steel pipe may be necessary to bring the chimney into compliance 2 When chimneys are relined
23. ESULT IN POPERTY DAMAGE BODILY INJURY OR EVEN DEATH INSTALLATION CHECK LIST FOR USE IN THE U S AND CANADA MOBILE HOME APPROVED CHECK WITH LOCAL AUTHORITIES AND OBTAIN NEEDED PERMITS WE RECOMMEND INSTALLATION BY A QUALIFIED PROFESSIONAL BEFORE STARTING THE FURNACE FOR THE FIRST TIME 1 Under certain conditions outside combustion air is recommended Use only approved parts When using out side air for combustion check that the outside air inlet is connected to draw fresh air from outside the building 2 All joints of PL vent and single wall stainless steel pipe should be fastened by at least 3 screws and correctly installed Follow vent manufacturer s instructions Seal all joints with high temperature silicone to create an airtight seal 3 WARNING The high temperature paint on this Furnace may take several hours of burning at a high fuel setting to cure fully During this time an odor that is not harmful may be evident When odors are present the area around the Furnace should be well ventilated 4 Caution The high temperature paint can be easily scratched prior to burning the Furnace CAUTION FAILURE TO FOLLOW THE INSTRUCTIONS IN THE INSTALLATIONS MANUAL MAY RESULT IN A HOUSE FIRE PLEASE FOLLOW INSTALLATION AND MAINTENANCE INSTRUCTIONS SCF 050 Manual 5 Sold and serviced by www PelletKing com 603 424 1183 SCF 050 Furnace Layout 200 LBS HOPPER PLENUM AUGER ACCESS OPENING PANEL FIREBOX CO
24. MPONENT DOOR ACCESS COVER FAN LIMIT i CONTROL VIEWING DIGITAL GLASS CONTROLS e 2 SPEED 2 BLOWER SWITCH THERMOSTAT TERMINAL AIR FILTER CONVECTION ASHIPAN DOOR SLIDE OUT FRONT PANEL BLOWER BOTTOM ROD ACCESS COVER HANDLE Figure 1 The SCF 050 has a large Heat Exchange system allowing for more heat to be exchanged The burn system used in the furnace is the St Croix Patent Pending Clinker Removal System This burn pot allows the clinker to be removed without loosing the fire in the pot This eliminates the need of having to constantly re light the furnace after removing the clinker SCF 050 Manual 6 Sold and serviced by www PelletKing com 603 424 1183 Furnace Dimensions 25 25 wel j 33 75 wel Figure 2 Furnace location When finding a location to install the furnace several things need to be kept in mind Consider the following things Service Access Venting Return air Duct Supply air Duct and Electrical Service Access The front panel is removable to allow access to the ash pan and the firebox for regular maintenance The Control Board is mounted on the left side There are also 2 access panels on the left side The smaller cover gives access to the following components Combustion Fan Vacuum Switch and Proof of Fire Switch The larger cover allows access to the Convection Blower for maintenance
25. NCE SECTION Using a thermostat will cause variations in the maintenance Check the burnpot frequently in the beginning to establish a maintenance schedule based on use of furnace Contact your dealer for more information on where to get high quality corn to burn in your new corn furnace Store corn in a tight container or use other methods to ensure they do not become rain soaked or absorb moisture from damp or wet floors This will also prevent rodents from becoming a problem Do not store corn within Furnace installation clearances or within the space required for clinker removal The Furnace is not warranted against damage caused by poor quality corn incorrect operation poor maintenance or incorrect installation PELLETS Clinkers and Ash are by products of pellet combustion and are not caused solely by your Furnace Furnace performance can be quickly and severely reduced if poor quality pellets are used Contact your dealer for more information on APFI approved wood pellet fuels NOTE Pellets with excessive sawdust should be screened by sifting with 1 4 mesh screening Store Pellets under cover on a wooden pallet or other methods to ensure they do not become rain soaked or absorb moisture from damp or wet floors Do not store pellets within Furnace installation clearances or within the space required for ash removal There are 2 ways to burn pellets in the SCF 050 furnace If the furnace is used with a thermostat and the burn rate is moder
26. QUENTIAL OR OTHER DAMAGES OF ANY NATURE WHATSOEVER IN EXCESS OF THE ORIGINAL PURCHASE PRICE OF THIS PRODUCT ALL WARRANTIES BY MANUFACTURER ARE SET FORTH HEREIN AND NO CLAIM SHALL BE MADE AGAINST MANUFACTURER ON ANY ORAL WARRANTY OR REPRESENTATION Some states do not allow the exclusion or limitation of incidental or consequential damages or limitations of implied warranties therefore the limitations of exclusions set forth in this warranty may not apply to you This warranty gives you specific legal rights and you may have other rights which vary from state to state SCF 050 Manual 54 Sold and serviced by www PelletKing com 603 424 1183 Notes After the break in period please note any adjustments that were made to the Feed Trim and Draft Trim on the control board in the area below In the event of a power failure or 1f the units gets unplugged the trim settings will be lost Draft Trim Circle one See point 4 on page 24 Default Draft Low Draft High Draft Feed Trim Circle one See point 5 on page 24 Default Pilot Medium Pilot Low Pilot Serial Number Date of Purchase Dealer Information Even Temp Inc P O Box 127 Waco NE 68460 PHONE 402 728 5255 FAX 402 728 5379 EMAIL SUPPORTEEVENTEMPINC COM WEB ADDRESS www eventempinc com SCF 050 Manual 55
27. Sold and serviced by www PelletKing com 603 424 1183 Installation amp Operations Manual PELLET CORN SIOVEs SCF 050 CORN FURNACE SCF 050 Manual 1 Sold and serviced by www PelletKing com 603 424 1183 TABLE OF CONTENTS re mre reall Orn Att pax cpr a EE 4 Installation Check Mast 0 oe e ng e dl Ge 5 Furnace Layout Diagram mitin ias 6 Furnace Dimensions Location amp Clearances ccccccccnnncncnnnononononononinoninoninininininnononos 7 8 HAUS EV CICS dl re sd onde ae o 10 Venting Approved Materials vascas add 10 Venting Typical PL Vent Components ccooccnoccnonnconancnnncnoncnnnnnonn nono ncnnncnnnnnnnn no 11 Venting Determining Materials sii A dt 12 Venting Termination Requirements ads 13 Venting Termination Clearance Requirements cococccnnccnnnnononncnoncnannninnnonnncnnns 14 Venting Into an existing Chmnen E 15 COMPUSO AA ds 16 Connecting to Existing Duct Work tie eege eegen ege eegen 17 Mobile Hom Installation odo apasia 18 Thermostat Hook Up ins 19 SCE 050 Operation A E a ASA a E E A eee ee 20 Installation EE 20 Preyenting Chimney e A 20 Burning Corn Pellets cun a 21 23 Control Board Features iii ts 25 Pre Lighting amp Lighting mstructons cnn ncnnnnos 26 28 Sh ttns OM the jura uns li 28 Diagnostic amp Safety Features cuca ir dd 28 30 SCF 050 Manual 2 Sold and serviced by www PelletKing com 603 424 1183 Combustion Air Damper Location and Adjustments oooocnnocnnononon
28. a chimney chase cap that reduces the outlet of the chimney to the size of the liner is required Extend the exhaust vent above the chimney chase cap and finish it off with a rain cap A single wall liner may need to be wrapped with insulation to maintain adequate exhaust temperatures when outside temperatures drop below freezing causing the flue temperatures to become too low 3 Venting into the side of an existing masonry chimney must be done through a masonry thimble When wall penetration is necessary to access a masonry chimney use a listed PL vent wall thimble Figure 6 4 When venting into a Class A steel chimney use an appropriate PL Vent adapter SCF 050 Manual 14 Sold and serviced by www PelletKing com 603 424 1183 COMBUSTION AIR 1 Under certain conditions it is recommended that the Furnace be connected to an outside source of combustion air to improve Furnace performance Flexible metal hose such as ClevFlex or rigid metal pipe conduit must be connected around NOT INSIDE the combustion air inlet tube Figure 11A Be careful not to pinch or bend the outside air pipe with too small a radius which may e terminated flush with the outside wall but should be protected from wind and weather by a hood Note The outside air pipe must terminate above the maximum snow line WARNING USE THE AIR INTAKE DAMPER FOR ADJUSTING COMBUSTION INLET AIR ONLY OTHER METHODS OF RESTRICTING OR BLOCKING COMBUSTION INLET AIR AR
29. and Ash from burn pot This may be required more than once a day depending on the burn rate of the Furnace and the quality of Corn Pellets used Check the furnace frequently at first to establish a Schedule for cleaning the burnpot If Clinker Ash is not removed the burnpot will overload and fuel will spill into the Ashpan 1 Continuous burning of the furnace on the Low burn setting Pilot Approximately every 30 hours This may vary depending on the quality of Corn Pellets used 2 Continuous burning of the furnace at the High burn setting 5 Approximately every 12 hours This may vary depending on the quality of Corn Pellets used The daily maintenance will mainly focus on 4 areas in the Furnace removing the clinkers from the ash pan 1f needed dropping the clinker from the burnpot cleaning the heat exchange tubes and cleaning the glass A break down of this process consists of these steps POSITION OF COAL RAKE amp POT BOTTOM DURING NORMAL OPERATION Normal Operation gt Figure 18 PULLED OUT gt _ POT BOTTOM As de IS SS PUSHED IN Sony 1 The coal Rake The first step is to push the coal rake in and shave the coals off the top of the clinker Once this is done open the door and add a 4 cup of pellets on top of the coals See figure 19 on page 38 To push in the Coal rake use the Rod Handle tool shown in figure 21 on page 40 SCF 050 Manual 37 Sold and serviced by www PelletKing com 6
30. ard The vacuum switch is defective The vacuum hose is disconnected The vent system is plugged with fly ash S CH E Solution If the fire is out re light the Furnace If the fire is still burning make sure all doors are securely latched and hold down the On Off button approximately 5 SCF 050 Manual 49 Sold and serviced by www PelletKing com 603 424 1183 seconds until Furnace starts up again This will re start the Furnace in the start up program Occasionally use the auger button to manually feed fuel until the auto feed takes over Auto feed will start 5 minutes after the Furnace has been restarted My Furnace isn t burning and the number 3 LED light is blinking This diagnostic light indicates that the Proof of Fire Switch no longer senses a fire in the Furnace First check to see 1f there are pellets in the hopper If there are pellets in the hopper why did the Furnace go out a Unburned fuel in the burnpot means the fire went out before the auger quit feeding b A power Failure could also cause this If the furnace is still hot when the power comes back on the feed system will resume If the fire had gone out in the pot the feed would continue to run until the Proof of Fire switch dropped out and shut the Furnace down Solution Too much Combustion Air on the pilot setting Adjust the air damper See section covering an Unbalanced Burnpot Corn Pellets would still feed until the P O F switch eventually shuts
31. ate not constantly running on the higher settings simply remove the side shields as shown in figure 12 on page 22 To burn pellets in the standard burn pot in the furnace the side shields of the pot must be removed A maintenance schedule must be established for removing the ash from this pot The frequency of removal of ash from the pot should be determined by the owner user of the furnace It will vary depending on fuel consumption of the unit See section covering the Clinker Removal on page 35 for more information A CONTINUOUS BURN MAINTENANCE SHEDULE IS PROVIDED AS AN EXAMPLE ON PAGE 36 IN THE DAILY MAINTENANCE SECTION Using a thermostat will cause variations in the maintenance Check the burnpot frequently in the beginning to establish a maintenance schedule based on use of furnace SCF 050 Manual 21 Sold and serviced by www PelletKing com 603 424 1183 The Furnace is not warranted against damage caused by using poor pellets incorrect operation improper maintenance or incorrect installation E LIFT UP TO REMOVE SIDE SHIELDS Es Ns BURNPOT SHOWN OUTSIDE OF FURNACE TO REMOVE SHIELDS POT DOES NOT NEED TO BE REMOVED FROM FURNACE Figure 12 To burn Pellets detach the side shields by removing the 2 screws holding the shield in place Do not discard this part but save it for future use in the event you switch back to burning corn The shields must be removed when burning pellets A Retrofit pellet pot is a
32. away from the building 4 For termination above the building roofline a rain cap is required 5 The exhaust pipe on all Furnaces is 4 O D to accommodate a pipe adaptor SCF 050 Manual 12 Sold and serviced by www PelletKing com 603 424 1183 VENTING TERMINATION REQUIREMENTS In determining optimum vent termination carefully evaluate external conditions especially when venting directly through a wall Since you must deal with odors gases and fly ash consider aesthetics prevailing winds distances from air inlets and combustibles location of adjacent structures and any code requirements 1 Exhaust must terminate above combustion air inlet elevation 2 Do not terminate vent in any enclosed or semi enclosed area i e Carports garage attic crawl space etc or any location that can build up a concentration of fumes 3 Vent surfaces can get hot enough to cause burns if touched by children Non combustible shielding or guards may be required EXHAUST TERMINAL EXHAUST TERMINAL Figure 4 4 1 2 m BELOW a door window cavity or air vent 4 1 2 m HORIZONTALLY FROM a door window cavity or air vent 1 305 mm ABOVE a door window cavity or air vent SCF 050 Manual 13 Sold and serviced by www PelletKing com 603 424 1183 VENTING TERMINATION CLEARANCE REQUIREMENTS PUBLIC WALKWAY CLEARANCE TO WALL PENETRATION POINT 12 PL V
33. cnannninnnonancnnnncnnno 30 34 Thermostat Control amp Pilot SEM iia A eae 35 SCF 050 Maintenance ii ection 35 St Croix Clinker E ii 35 Clinker Ash Removal cocinan ata is 36 Daily Ma eo tte aa EE be Oa T 37 39 Periodic Mani ed tial go ck nel Bees ote ate ae 40 42 Vary VES AICS os cite ec daps pace ects ec once n e a 43 44 Safe Opera EE 44 Wiring Sc A Gee tute 45 Electrical Layos aio aida 46 Canadian Requirements station ti a 47 LB Ye EEN 47 gt Upplementary Furnace dessai dee Eed aeons 48 Troubleshooting amp Frequently Asked Questions ooooooonnccnnnconnncnncccincnconnccnos 49 53 KE LEE 54 Furnace tos a lia 55 SCF 050 Manual 3 Sold and serviced by www PelletKing com 603 424 1183 Save This Installation amp Operations Manual GENERAL INFORMATION SAFETY PRECAUTIONS SAFETY NOTICE The furnace must be properly installed in order to prevent the possibility of a house fire These installation instructions must be strictly observed The Maintenance schedule must be followed as described in this manual Failure to follow instructions may result in property damage bodily injury or even death The furnace s exhaust system works with negative combustion chamber pressure and a slightly positive chimney pressure Therefore it is imperative that the air intake and exhaust system be airtight and installed correctly Do not install a flue damper in the exhaust vent of this unit Do not connect this unit to a chim
34. e Out Bottom out and drop the fuel into the ash pan This will minimize the amount of smoke that can spill into the room I turned the Furnace on with the On Off switch and nothing happens First check to see if the Furnace is plugged in and the receptacle has power to it Solution Check the fuses on the back of the control board F2 is the fuse for power in to the board Replace with a 250 Volt 5 Amp fuse I turned the Furnace on with the On Off switch and the board lights up and the fans come on but the auger doesn t feed any fuel Solution Check the F1 fuse on the back of the control board This fuse runs the Auger circuit only Replace with a 250 Volt 5 Amp fuse Why is my glass dirty Normal operation of your St Croix Corn Pellet Furnace will produce a white build up on the glass that wipes off with a dry paper towel However extended burning on the low setting only will produce a light tan color These types of build up on the glass are normal A heavy black build up on the glass could indicate a problem Solution Adjust the combustion air setting to the proper setting If this doesn t seem to help make sure the clean out cover plates are installed in the Furnace It also could be an indication that the Furnace is getting plugged and needs a good cleaning Refer to the section in the manual that covers the Daily Periodic and Yearly Maintenance of the Furnace How do I adjust my Pilot feed rate settings 1 setting Not all
35. e warranty The warranty does not cover damage or breakage due to misuse improper handling or modifications A warranty registration card is provided The card is to be checked and signed and returned to factory by the owner Appropriate information is to be noted on the card All claims under this warranty must be made through the dealer where the Furnace was purchased If an inspection by the dealer indicates that a warranty claim is justified and that all conditions of this warranty have been met the manufacturer s total responsibilities and liabilities shall be to repair or replace at the manufacturer s option the defective part s All costs of removal shipment to and from the dealer or manufacturer any losses during shipment and reinstallation and any other losses due to the Furnace being removed shall be covered by the owner of the Furnace NEITHER THE MANUFACTURER NOR THE SUPPLIERS TO THE PURCHASER ACCEPT RESPONSIBILITY LEGAL OR OTHERWISE FOR THE INCIDENTAL OR CONSEQUENTIAL DAMAGE TO PROPERTY OR PERSONS RESULTING FROM THE USE OF THIS PRODUCT ANY WARRANTY IMPLIED BY LAW INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS SHALL BE LIMITED TO ONE 1 YEAR FROM THE DATE OF ORIGINAL PURCHASE WHEN A CLAIM IS MADE AGAINST THE MANUFACTURER BASED ON THE BREACH OF THIS WARRANTY OR ANY OTHER TYPE OF WARRANTY EXPRESSED OR IMPLIED BY LAW MANUFACTURER SHALL IN NO EVENT BE LIABLE FOR ANY SPECIAL INDIRECT CONSE
36. ed by opening a window slightly on a calm day The house is sealed with a well sealed vapor barrier and tight fitting windows and doors and or has any powered devices which exhaust house air d There is excessive condensation on the windows during the winter e A ventilation system is installed in the house Additional Canadian Operation Requirements 1 2 Store Corn Pellets in sealed containers in a dry environment to prevent the fuel from absorbing moisture and becoming damaged Creosote formation and Cleaning a b Establish a routine for the storage of fuel care of the Furnace and Firing Techniques Check Daily for Creosote build up until experience shows how often cleaning is necessary Be aware that the hotter the fire the less creosote is deposited and that weekly cleaning may be necessary in mild weather even though monthly cleaning may be enough in the coldest months Run the furnace on the hottest setting once a day for 30 45 minutes to prevent excessive build up in the furnace Keep the doors closed and all seals in good condition while operating the furnace INSPECT THE FLUE PIPES JOINTS AND SEALS REGULARLY TO ENSURE THAT SMOKE AND FLUE GASES ARE NOT DRAWN INTO AND CIRCULATED BY THE AIR CIRCULATION SYSTEM CLEANING OF THE HEAT EXCHANGER FLUE PIPE CHIMNEY AND DRAFT INDUCER IS ESPECIALLY IMPORTANT AT THE END OF THE HEATING SEASON TO MINIMIZE CORROSION DURING THE SUMMER MONTHS CAUSED BY ACCUMULATE
37. elletKing com 603 424 1183 e Advance the heat setting to 5 and let the Furnace burn at this setting for Ya an hour Check the burn pot to see if it is balanced A small damper adjustment might need to be made at this time to make sure the Lag time isn t too long Remember Only turn the setscrew one 1 2 turn clockwise to open the damper Wait 15 minutes to see if the burn pot becomes balanced Repeat this step as many times as needed until the burn pot becomes balanced If the Furnace has been connected to an existing Chimney system that has good natural draft the procedure mentioned in the last 2 points above may actually require that the damper gets closed slightly instead of opened to compensate for the additional draft in the chimney system The process of adjusting the damper when burning Corn will take about 3 hours but it only needs to be done once at the initial burn This will adjust the Furnace to the unique circumstances of your home Procedure for adjusting the damper when burning Pellets When burning pellets in the Furnace the adjustment to the damper will most likely need to be made when the Furnace is running in the pilot mode a If a heavy black shiny build difficult to wipe off up is noticed on the glass and inner surfaces after the furnace runs on the low pilot setting for extended periods of time the damper must be closed some This may require the Furnace to run in pilot mode for a while to beco
38. ems too warm and the Thermostat is never calling for heat a lower pilot setting may be a better fit for the home Remember Choosing a lower Pilot setting may require the damper to be fine tuned to match the lower feed rate Monitor how the furnace is operating after a change is made and adjust the damper if needed SCF 050 MAINTENANCE The St Croix corn clinker theory And why we do what we do Some manufacturers of corn Furnaces use complicated stirring mechanisms to break up the clinker in the burn pot We feel that is a mistake We believe that corn doesn t burn as well when it is disturbed during the burn process Corn needs high temperatures and proper airflow in the burn pot to burn properly That energy is stored in the clinker that is being formed in the burn pot It glows red hot and provides the heat needed to ignite the corn that is being fed into the burn pot When the clinker is broken up that constant source of energy is lost and now it becomes more difficult to burn corn When corn is not burning properly it tends to stick together and form a clump in the burn pot It is impossible for air to flow through this clump and soon the pot will overload and the fire goes out This is where some manufacturers use the stirring mechanism to break up the clump of corn to maintain proper airflow and others use large burn pots to handle this problem Smaller burn pots are better The truth is neither is needed The St Croix corn burning
39. enerous amount of starter gel to the pellets 3 This next item is optional but it will give an immediate boost to the start up procedure Crumple up half of a newspaper page with some pellets light the gel and toss the paper and pellets on top of the Coal rake in the burn pot 4 Close the door and push the On Off button on the control board Button 2 If the optional method described in point 3 was used allow the pellets to ignite on top of the Coal Rake for several minutes and then pull the Coal rake out of the burn pot and drop the top layer of pellets on top of the burning pellets in the bottom of the pot At this point all that needs to be done is to monitor the burn pot to make sure the Furnace starts up properly Once the On Off button has been pushed the Start Up program takes over The Start up Program works as follows a The Combustion Fan comes on at high speed and the control board checks to make sure the Vacuum switch locks in See section on Diagnostic features on page 27 SCF 050 Manual 27 Sold and serviced by www PelletKing com 603 424 1183 b When the board senses the Vacuum switch the exhaust fan speed drops to the 1 setting and runs for 5 minutes c After 5 minutes the board checks for Proof of Fire and starts feeding corn or pellets on the 1 setting See section on Diagnostic Features on page27 If the board senses P O F then the Furnace has started successfully d If the board fails to se
40. ers have thoroughly cooled 2 Never use Gasoline gasoline type lantern fluid Kerosene charcoal lighter fluid or similar liquids to start or freshen up a fire in this heater Keep all such liquids well away from the heater while it is in use 3 Creosote Soot and Fly Ash Formation and Need for Removal The products of combustion will contain small particles of Fly Ash The fly ash will collect in the venting system and restrict the flow of flue gases Incomplete combustion such as occurs during start up and shut down or incorrect operation of the room heater will lead to some soot or creosote formation which will collect in the venting system The exhaust system should be inspected regurlarly during the heating season to determine if creosote buildup has occurred Check more frequently at first to determine a schedule for cleaning the venting system based on individual use of this Corn Pellet burning heater If creosote has accumulated it should be removed to reduce the risk of a chimney fire 4 Do not Overfire this unit Follow all instructions regarding the proper use of this heater SCF 050 Manual 44 Sold and serviced by www PelletKing com 603 424 1183 Wiring Schematic Black 120 Volt AC White Common Convection Blower Proof of Fire Switch Wire Colors 1 Orange 2 Gray 3 Open 4 Blue 5 Yellow 6 Open 7 Orange 8 Gray 9 Brown 10 Brown 11 White 12 Black Normally Open Combustion Fan B
41. ery two months during the heating season to determine if a creosote build up has occurred If a significant layer of creosote has accumulated 3 mm or more it should be removed to reduce the risk of a chimney fire Use of an appropriately sized chimney brush or the services of a professional chimney sweep are recommended The chimney and chimney connector should be inspected at least once every two months during the heating season to prevent the system from getting plugged with Fly ash Clean the exhaust system 1f needed Use of an appropriately sized chimney brush or the Services of a Professional chimney sweep are recommended SCF 050 Manual 20 Sold and serviced by www PelletKing com 603 424 1183 SHELLED CORN SATISFACTORY PERFORMANCE Shelled corn must be 15 or less moisture content The keys to satisfactory performance are proper operation of the Furnace diligent maintenance and burning only dry clean quality corn Corn dust must be screened prior to using NOTE Corn with excessive grain dust must be screened by sifting with 3 16 mesh screening Large pieces of cob may plug the auger Clinkers and Ash are a by product of burning corn and are not caused by your Furnace Furnace performance can be quickly and severely reduced if poor quality corn is used See section covering the Clinker Removal on page 35 for more information A CONTINUOUS BURN MAINTENANCE SHEDULE IS PROVIDED AS AN EXAMPLE ON PAGE 36 IN THE DAILY MAINTENA
42. fuel burns at the same rate The moisture content of corn greatly influences how it burns Burning Pellets requires adjustments to the low burn to prevent Creosote from forming Following is a description of the function of the Feed Trim button Solution The Feed Trim button on the control board allows the feed rate on 1 Pilot setting to be increased or decreased Different types of fuel and the way the Furnace is installed will affect the low burn and needs attention during the break in period of the Furnace SCF 050 Manual 51 Sold and serviced by www PelletKing com 603 424 1183 ALWAYS DISCONNECT APPLIANCE POWER BEFORE SERVICING THERMOSTAT MANUAL a The default Pilot setting has an On Time of 2 5 seconds The 1 LED light indicates the default pilot setting This setting requires little fine tuning b Pressing the Feed Trim button once will turn the 1 and 4 LED lights on at the same time This reduces the On Time to 2 0 seconds reducing the fuel on the pilot setting Less Fuel may require more adjusting of the draft See the figure to the right for details ALWAYS DISCONNECT APPLIANCE POWER BEFORE SERVICING THERMOSTAT MANUAL Figure 27 c Pressing the Feed Trim button again will turn on the 1 and 5 light at the same time This reduces the On Time to 1 5 seconds Again less Fuel may require more adjusting of the draft See figure to the left for more details Using the auger trim button is also helpful when t
43. haust system These tees are to assist in periodically cleaning the pipe Single or double clean out tees may be used The exhaust system must be installed so the entire system can be cleaned without disassembly NOTE ADHERE TO THE PL VENT CLEARANCES TO COMBUSTIBLES AS REQUIRED STRICTLY OBSERVE THE PL VENT MANUFACTURER S SAFETY SPECIFICATIONS QUANTITY OF MATERIALS 1 It is recommended that the vent system be installed with a minimum of three feet 3 of vertical rise above the exhaust port on the back of the furnace FAILURE TO PROVIDE THE NATURAL DRAFT THAT RESULTS FROM A VERTICAL RISE MAY RESULT IN SMOKE BEING RELEASED INTO THE HOUSE WHEN ELECTRICITY TO THE UNIT IS INTERRUPTED WHILE BURNING OR SMOLDERING CORN REMAINS IN THE BURN GRATE See Battery Backup on page 9 2 It is not recommended to run vertical venting outside the heated environment where the furnace is installed Running a venting system in a cold environment may cause the flue temperatures to cool down too much for adequate drafting See figures 5 amp 6 on pages 13 amp 14 Additional vertical exhaust venting should be provided when using a More than one 1 elbow or tee and or b Horizontal runs of over three 3 feet Horizontal runs over 10 feet not recommended 3 For a venting system ending in a horizontal run the exhaust pipe must be terminated by a listed end cap or a PL vent elbow 45 or 90 degrees Note End caps or elbows must vent exhaust gases
44. he control board again Many times the cause of this is a change in the vacuum inside the Furnace This may be caused by excessive wind opening the Firebox door or opening the Ash Pan door The control board will monitor the vacuum switch and resume normal operation if the vacuum returns to normal Safety Features WARNING These safety features are designed to protect life and property Bypassing these features voids all warranties and the safety listing of the Furnace 1 High Limit switch an overheat safety switch will shut off the fuel feed if the Furnace reaches temperatures above normal operating temperature This is a Normally Closed switch and is part of the Fan limit control If the High limit switch trips several times the problem in the Furnace must be diagnosed before SCF 050 Manual 29 Sold and serviced by www PelletKing com 603 424 1183 the Furnace is put back in service Defective Room Fan dirty Room Fan dirty Return Air Filter defective Fan Limit Control or possibly a bad Control Board 2 Proof of Fire switch also called the P O F This senses the temperature rise in the exhaust system The switch is Normally Open and closes the circuit at 110 degrees The Furnace will shut down if temperatures above 110 degrees F are not sensed during start up or if the temperature drops below 110 degrees during normal operation 3 Vacuum switch also called the Negative pressure switch When the Furnace
45. he firebox and under the hopper should be vacuumed annually NOTE UNPLUG THE FURNACE Remove the access panels of the Furnace Carefully clean or vacuum any dust cobwebs and household dust Carefully vacuum around the fan motors If electrical wires become disconnected call your dealer for service REMOVE FAN AND CLEAN EXHAUST DUCT REMOVE CONVECTION BLOWER AND CLEAN AND OIL YEARLY CLEAN OR REPLACE FILTER REGULARLY Figure 24 SCF 050 Manual 43 Sold and serviced by www PelletKing com 603 424 1183 4 The exhaust fan should be removed may require a new gasket and cleaned with compressed air annually Call dealer for this service Annual oiling of the motors is not needed 5 The Convection Blower should be removed and cleaned with compressed air annually There are 2 oil ports on the motor Fall Startup Prior to lighting the first fire check the outside area around the exhaust and air intake systems for obstructions Try all controls to see that they are working prior to lighting a fire SAFE OPERATION 1 Disposal of Ashes Ashes should be placed in a metal container with a tight fitting lid The closed container of ashes should be placed on a non combustible floor or on the ground well away from all combustible materials pending final disposal If the ashes are disposed of burial in soil or otherwise locally dispersed they should be retained in the container until all cind
46. imes to keep the tubes clean If the Tube Scraper feels sticky and difficult to move check for the presence of creosote on the tubes If creosote is present a damper adjustment may be needed or the Furnace has become plugged and needs a thorough cleaning Call Dealer for assistance To pull the tube scraper back and forth use the Rod Handle tool shown in Fig 21 on page 40 7 Use a dry paper towel to clean the glass Quickly open the door and wipe the glass The rate of burn will determine how often the window needs cleaning Prolonged burning at a slow burn rate will result in the need for more frequent window cleaning Cooling the Furnace and wiping the window daily with a cloth or paper towel will normally keep the window from accumulating difficult to clean residue Use of a glass cleaner ONLY permitted when the Furnace is cold CAUTION Do not slam the door Do not operate the Furnace with a broken or cracked glass Replace only with heat resistant ceramic glass supplied by the manufacturer There are 2 things to keep an eye on during the cleaning process 1 If the ash pan door or firebox door were left open for more than 90 seconds the Furnace will go into safety shutdown You will notice that the Furnace quits augering corn into the burn pot Toggle the On Off switch off and back on This will reset the board You will need to use the auger button 3 to manually feed corn into the pot for a couple of minutes until the program resumes
47. ing start up If the Exhaust temperature does not reach 110 degrees F or if during use the temperature drops below 110 degrees F the Furnace will go into Internal Alarm and the Auger will quit feeding fuel Once the Furnace completes the safety shutdown the 3 LED will start blinking See Figure 14 on Page 25 2 The High Limit switch This sensor will sense if the unit reaches temperatures that are too high for normal operation If this happens the Auger will quit feeding and the 2 and 3 LED lights will flash simultaneously See Figure 14 on Page 25 3 The Vacuum switch For the Furnace to operate correctly the firebox needs to be sealed During the first 30 seconds after the Furnace has been turned on the control board will check to see if the switch senses negative pressure Vacuum in the firebox of the Furnace If there is no negative pressure the Furnace will go into Safety shutdown and the 2 LED will start blinking See Figure 14 on Page 25 Power Reset If all the lights on the control board are lit up and the board is unresponsive you must unplug the Furnace wait 10 seconds and plug the Furnace back in to reset the board Internal Alarm When the control board becomes unresponsive the control board is in Internal Alarm The control board has sensed one of the Safety sensors This may cause the furnace to go out In some cases after waiting approximately 45 seconds the furnace will start responding to t
48. is turned on the Exhaust fan will create a negative pressure in the firebox The control board continually checks to see if Negative Pressure vacuum is present during operation of the Furnace If the exhaust venting system becomes clogged or obstructed the firebox door or ash pan door are left open or the exhaust fan quits working the control board will go into Safety shutdown There is a 60 second window to allow for cleaning the glass and removing the clinker before then Furnace shuts down This is sufficient for the Daily Maintenance The St Croix corn Furnace has been Safety Tested by an accredited independent laboratory Combustion Air Damper Do not neglect to adjust the Combustion Air damper during the break in period of your new Furnace See Figure 15 to the left Your Furnace is equipped with an air inlet damper The purpose of this damper is to adjust combustion airflow to match the characteristic of each specific air inlet and chimney configuration The damper is preset at the factory with a setscrew The damper will most likely only need a small adjustment during the break in period To know if the damper needs to be adjusted you should learn to recognize how Corn or Pellets burn in this furnace system AIR DAMPER Figure 15 SCF 050 Manual 30 Sold and serviced by www PelletKing com 603 424 1183 When burning corn the burn pot should be BALANCED This means the corn that is being augered into
49. k for 90 of the most common installations Long horizontal runs might need the damper opened Tall vertical runs might need the damper to be closed a little etc To adjust the damper use the setscrew to make the adjustments To make an adjustment turn the screw 1 2 turn clockwise to open the damper or 2 turn counter clockwise to close the damper Turning the setscrew counterclockwise will not move the damper so remember to use the damper handle to bring the damper up to the screw After making an adjustment wait at least 15 minutes to see how the burn pot reacts to the change SCF 050 Manual 32 Sold and serviced by www PelletKing com 603 424 1183 Terminology used when burning Corn 1 Balanced burn pot This means the corn rapidly turns into red hot coals once it is in the burn pot 2 Lag time This is the time it takes for the corn to start burning and the burn pot to become balanced Corn will tend to stick together in a clump in the burn pot if the corn feeds in faster than it s burning 3 Overloaded burn pot Once the corn has formed a clump in the burn pot the pot will overload and slowly the fire will die out Procedure for adjusting the damper when burning Corn a Once the Furnace is burning leave the control board on the 1 setting for Lo an hour This will allow the Furnace to warm up before any adjustments to the damper are made After 1 2 an hour look in the burn pot to see if the burn pot is balanced Unless
50. me noticeable If this build up is noticed close the damper 50 to start out with and place the setscrew against the damper blade Use this as the starting point to make additional adjustments with the setscrew Some build up is normal and may be removed during the maintenance schedule Once the adjustment has been made for the pilot setting slowly advance the Furnace to the 5 Heat Level and observe the flame If black soot wipes off easily builds up on the glass and black smoke is visible at the tips of the flames turn the setscrew one Y turn counterclockwise and bring the damper blade up against the screw Wait 5 10 minutes before attempting another adjustment An occasional wisp of black smoke is normal every now and then SCF 050 Manual 34 Sold and serviced by www PelletKing com 603 424 1183 Thermostat Control Pilot Settings The Furnace may be controlled with a thermostat to help maintain a more constant temperature A Corn or Pellet furnace will be a little slower in reacting to a thermostat than the typical Gas Electric or Oil fired furnace With this in mind we have incorporated 3 Pilot settings on the control board See Point 5 on Page 26 This will allow the heat output during the pilot stage to be matched to the size of the home A larger home will require more heat than a small one Keep in mind that the furnace is constantly producing some heat that helps heat the home while the furnace is in pilot mode If the home se
51. nections must be sealed with RTV silicone to assure a gas tight seal Any leaks into a confined area caused by faulty installation or improper operation of the furnace could produce dizziness nausea and in extreme cases death 8 Under certain circumstances an outside source of combustion air may be needed and is required on all mobile home installations If room air is used to supply combustion air room air starvation operation of exhaust fans and icing of air vents can adversely affect proper furnace operation 9 Smoke detectors installed in the same general area as the Furnace may be activated if the Furnace door is left open and smoke is allowed to enter the area CAUTION NEVER ADD FIRE STARTER TO A HOT FURNACE CAUTION Hot Surfaces Keep Children away Do not touch during Operation SCF 050 Manual 24 Sold and serviced by www PelletKing com 603 424 1183 Control Board Features The Control Board controls all functions of the furnace by monitoring sensors that are in the system These sensors serve 2 purposes ALWAYS DISCONNECT APPLIANCE POWER BEFORE SERVICING a General Operation of the Furnace THERMOSTAT MANUAL b Safety Features to shut the unit down in the event the sensors detect a problem in the unit The Control Board also has Diagnostic Capabilities to help in diagnosing 3 areas in the furnace These areas are 1 High Temperature Limit 2 Proof of Fire Sensor 3 Vacuum in the Firebox
52. ney flue serving another appliance BUILDING PERMIT Contact the local building officials to obtain a permit and information on any local installation restrictions and inspection requirements DEFINITION OF FURNACE The word Furnace as used in this manual is interpreted to mean a corn or wood pellet burning Add On Furnace This model is not intended as the sole source of heat SAFETY TESTING The furnace has been independently tested and listed by Warnock Hersey Laboratories in accordance with the proposed ASTM Standards and the applicable portions of UL 1482 and ULC 5627 B366 2 and Oregon Administrative Rules 814 23 901 through 814 23 909 stating requirements for installation as a shop heater or Add On Furnace and for mobile home installations The safety listing label is located on the inside of the removable front panel of the unit Please refer to label for pertinent information DISCLAIMER OF WARRANTY Since Even Temp Company has no control over the installation of the furnace Even Temp Company grants no warranty implied or stated for the installation of the furnace and assumes no responsibility for any special incidental or consequential damages MANUFACTURED BY Even Temp Inc Hwy 34 Waco NE 68467 SCF 050 Manual 4 BEFORE INSTALLATION THOROUGHLY READ AND UNDERSTAND THIS MANUAL SAFETY NOTICE PLEASE READ THE ENTIRE MANUAL BEFORE INSTALLING AND USING YOUR NEW FURNACE FAILURE TO FOLLOW INSTRUCTIONS MAY R
53. nse P O F it will repeat the last step and continue feeding corn or pellets on the 1 setting for 5 minutes e The board will check for P O F again If the board still fails to sense the Proof of Fire switch the Furnace will go into Safety shutdown See section on Diagnostic Features on page 27 If this happens repeat steps 1 through 4 from the section on Lighting Your Furnace Shutting The Furnace Off Refer to Figure 14 1 Press the On Off switch 2 once the lights will go off and the fire will go out in a few minutes The board essentially goes into Safety shutdown 2 As long as the temperature within the Furnace remains above 110 F the Combustion Exhaust Fan will continue to run When the P O F switch drops out the Combustion fan will run for another 10 minutes and finally shut down completely 4 NEVER unplug the Furnace to shut it off Doing so may cause a significant amount of smoke to enter the room Diagnostic Features of the Control Board The 2 LED and the 3 LED lights on the LED Light bar as show in figure14 will flash to give a diagnostic code to help in diagnosing problems that may occur These conditions fall into 2 categories a Heat related issues b Vacuum related issues SCF 050 Manual 28 Sold and serviced by www PelletKing com 603 424 1183 The Diagnostic Lights flash as follows 1 The Proof of Fire switch This switch will sense the temperature of the Exhaust rising dur
54. o many changes in a short period of time will not Y A d allow for an accurate adjustment EXAMPLES OF DAMPER SETTINGS Figure 16 SCF 050 Manual 31 Sold and serviced by www PelletKing com 603 424 1183 If you experience problems adjusting the Furnace during the Break In Period contact your dealer The figure below may be used to gage the approximate damper setting when making an adjustment Some chimney systems will fall outside the norm for example a chimney with excessive draft or one with a long horizontal run In dealing with technical support the terminology listed in figure 17 may be used to clarify where your damper needs to be set 5 mmm 3 O Clock Position lt p Fully Open 4 O Clock Position Approximately 50 closed O Clock Position Approximately 6 O Clock Position 80 Closed Fully Closed Figure 17 Damper Adjustment Procedure Once the Furnace has been lit for the first time the damper will need to be adjusted The process is different for Corn than Pellets This may take some time so please be patient during this process This Damper Adjustment process only needs to be done once After the damper has been adjusted to the unique installation in your home the control board will do the rest As was Stated earlier there is a setscrew in the damper and the damper has been preset at the factory This setting will most likely wor
55. rown Pin Out on Not Used Molex Connector 80P301 38 Figure 25 The Electrical Rating of this furnace is 120 Volt 60 Hz 4 AMP The minimum recommended circuit is 15 Amp A dedicated circuit for the furnace is recommended SCF 050 Manual 45 Sold and serviced by www PelletKing com 603 424 1183 CAUTION The electrical components of the Furnace are not owner serviceable Call your dealer for proper diagnosis of electrical problems and service to those components Electrical Layout Figure 26 l Fan Limit Control 6 Control Board Ze Convection Blower Ta Thermostat Wiring Terminal 3 Combustion Blower 8 Wiring Terminal Block Inside Cabinet 4 Proof of Fire Switch 9 2 Speed Blower Rocker Switch 5 Vacuum Switch 10 Auger Motor SCF 050 Manual 46 Sold and serviced by www PelletKing com 603 424 1183 Additional Canadian Installation requirements 1 The fans of this Furnace may cause a negative pressure area in the room where this Furnace is installed If the Furnace is not connected to a Return Air duct system in the house provision should be made to provide make up air to the unit It is recommended to provide opening equal to 120 Square inches for Return Air to the Furnace room Outside Combustion Air may be needed if a b The unit does not vent steadily smell experiences smoke rollout burns poorly or back drafts whether or not there is combustion present Any of the symptoms listed above are alleviat
56. rticles of fly ash The fly ash will collect in the exhaust vent and restrict the flow of the flue gases Judge the frequency of cleaning by checking the amount of ash that accumulates in the elbows or tee s of the exhaust system Ask the dealer for suggested frequency of cleaning equipment needed and procedures for cleaning Check the Exhaust system and Ash Traps at least once every two months during the heating season 6 Gaskets Periodically inspect the condition of the rope gasket around the door window and ash door Replace as needed 7 Air Filter Check the Return Air Filters at least once a month and replace when needed The size of the filter is 1 X 12 X 25 SCF 050 Manual 42 Sold and serviced by www PelletKing com 603 424 1183 Many dealers offer a Service Contract that will cover Yearly Maintenance Contact your St Croix Dealer for assistance in maintaining your Furnace in top condition Yearly Maintenance Yearly maintenance is designed to assure safe operation prolong the life of the Furnace and help preserve its aesthetic appeal 1 Spring Shutdown After the last burn in the spring cool the Furnace Remove all corn from the hopper and the auger Thoroughly clean the burn pot burn pot box ash pan and ash traps behind the ash pan To locate the ash traps see figure 4 2 The exhaust system should be thoroughly cleaned at least annually Call your dealer for this service 3 The motor fan area behind t
57. rying to keep the glass cleaner when burning on the 1 setting The more fuel on low will usually mean less build up on the glass Figure 28 SCF 050 Manual 52 Sold and serviced by www PelletKing com 603 424 1183 12 How do I adjust the draft for the Pilot settings 1 setting Not all fuel burns at the same rate The moisture content of corn greatly influences how it burns Burning Pellets requires adjustments to the low burn to prevent Creosote from forming Following is a description of the function of the Fan Trim button ALWAYS DISCONNECT APPLIANCE POWER BEFORE SERVICING THERMOSTAT MANUAL z ZS The Draft Trim button will adjust the combustion fan voltages on the 1 pilot setting There are 2 adjustments that can be made To adjust the Combustion fan voltages push the Draft Trim button and you will notice all of the LED lights on the light bar flash once The first adjustment Lights flash once will lower the combustion fan voltages approximately 5 volts Using this draft adjustment will be common when burning Pellets The second adjustment Lights flash twice will raise the voltage approximately 5 volts This may be used in a venting situation that is restrictive a long horizontal run or a venting system with excessive elbows for instance Figure 29 13 Is there a Cycle Time adjustment on the Control Board for Pellets and Corn Located on the back of the control board are 4 Jumper Pins that control the
58. system allows the corn to be burned efficiently and completely in a relatively small burn pot Very little residue ends up in the ash pan When burning Pellets in the standard pot in the furnace ash will build up in a similar manner as the clinker does when burning corn The pot is maintained the same way as described in the following section covering the removal of the clinker The time it takes the pot to fill up with ash depends on the quality of the pellets and on the quantity of pellets burned The interval of dumping the ash is directly related to the rate of burn A Furnace running on a thermostat cycling at a moderate rate will generally last approximately 24 hours However if SCF 050 Manual 35 Sold and serviced by www PelletKing com 603 424 1183 the Furnace is running continuously on the highest setting the Ash will need dumping every 10 to 12 hours It is the responsibility of the Owner User of the furnace to determine the frequency of dumping the Ash based on the rate of burn and the quality of pellets ash content Clinker Ash Removal Once a clinker ash has formed in the burn pot it must be removed or the Furnace will go out The St Croix Burn system is designed to remove the clinker ash without loosing the fire in the burn pot It is a 3 part system 1 The coal rake This is a fork shaped device that will allow the Furnace operator to shave the burning coals off the top of the clinker separating the 2 areas
59. ts above the default setting Pushing the button a 3 time will reset the voltage to the default setting This adjustment is available to fine tune the 1 Heat Level draft setting This would only be used in the case the furnace was hooked up to a tall Vertical Chimney to decrease the draft if needed or if it was connected to a Chimney with a long Horizontal run to increase the draft if needed 5 The Feed Trim button 5 will allow the Fuel feed rate to be adjusted on Heat Level 1 only Heat Level 1 should be seen as the Pilot setting of the furnace when operating on a Thermostat Pushing the Feed Trim button 5 will switch between the different adjustments Heat Level one can be adjusted in the following ways a The first LED only indicates the Normal 1 setting 2 5 second on time This is the highest Pilot setting and may be used when heating a larger size home b The first and fourth LED lights indicate the 1 Low setting 2 0 second on time This is the medium Pilot setting and may be used when heating a medium size home where less heat is needed when the unit is running in pilot mode c The first and fifth LED lights indicate the 1 High setting 1 50 second on time This is the lowest Pilot setting and may be used when heating a small size home where minimal heat is needed when the unit is running in pilot mode The adjustments described in points 4 and 5 remain in effect as long as the unit is plugged in If the unit gets unpl
60. ugged or if there is a power failure the settings are lost and the adjustments would need to be reset Pre Lighting Instructions When lighting your Furnace for the first time or any time you have run out of corn or pellets fill the hopper The auger tube will be empty and it helps to hold the Auger Button in until you hear corn or pellets drop into the burn pot Corn is fed from the hopper to the burn pot by a high torque motor that is capable of doing SERIOUS harm to fingers Keep fingers and other objects away from the auger SCF 050 Manual 26 Sold and serviced by www PelletKing com 603 424 1183 WARNING Risk of Fire Do not operate with the Firebox door or Ash Removal doors open Do not store Fuel or other Combustible material within marked Installation Clearances Inspect and Clean Flues and Chimneys regularly Danger Risk Of Fire or Explosion Do not burn Garbage Gasoline Drain Oil or other Flammable Liquids WARNING The auger can start at any time while the Furnace is running CAUTION The Coal Rake must be pulled out and the Slide Out Bottom pushed in to Operate the Furnace See Furnace layout on page 1 REMEMBER If burning pellets in the standard Burn pot be sure to remove the side shields of the burn pot first Lighting Your Furnace 1 Make sure there is Corn or Pellets in the hopper 2 Add one cup of Pellets to the burn pot not more and not less Do not try to start your Furnace with corn Add a g
61. umulate on a regular basis Once a month or sooner depending on the quality of fuel being used See Figure 23 on Page 42 Figure 23 shows how the baffle is removed from the Furnace Clean the baffle on a regular basis Frequency of cleaning depends on amount of fuel being burnt and the quality of the pellets Fuel with low ash content is recommended Failure to clean the baffle can cause the Furnace to become plugged with fly ash SCF 050 Manual 41 Sold and serviced by www PelletKing com 603 424 1183 Baffle Removal STEP 2 ALLOW THE 2 SCREWS TO DROP OUT OF THE KEYHOLE SLOTS To remove the baffle lift the back of the baffle up to clear the inner back of the Furnace and slide towards the front of the Furnace The baffle will slide out of the STEP 1 keyhole slots and drop down When SIDE VIEW putting the baffle back in the Furnace OF BAFFLE make sure the screws are in the keyhole slots and the back of the baffle is lifted up over the inner back to keep the LIFT UP THE Baffle locked in place BACK SIDE OF BAFFLE amp SLIDE TOWARDS FRONT OF FURNACE Figure 23 5 Exhaust System Periodic cleaning of the exhaust system is required Under certain conditions chimneys may plug up rapidly Dirty High moisture content Corn and poor installations require more frequent chimney cleanings See Page 20 Preventing Chimney Fires The products of combustion will also contain small pa
62. vailable that offers less maintenance If the furnace is used primarily as a pellet furnace it is recommended to replace the standard burn pot with this Retro Fit Pellet pot See figure 13 on page 23 for details SCF 050 Manual 22 Sold and serviced by www PelletKing com 603 424 1183 STEP4 LIFT POT UP STEP 1 _ os TO REMOVE ek nl ON neg FURNACE REMOVE STEP LOOSEN SCREW TWO TURNS _ STEP 3 PULL COAL RAKE POD AA OZ TOWARDS THE FRONT Se ae OF THE STOVE UNTIL IT STOPS Le s x h THE SLIDE OUT BOTTOM STEP 5 REMAINS IN THE STOVE AFTER REMOVING THE BURN POT AND SHOULD BE CLOSED UNSCREW THE COAL RAKE ROD WHILE USING THE NEW FROM THE COAL RAKE AND REMOVE RETRO FIT PELLET POT IT FROM THE FURNACE REACH INSIDE THE POT WRAP AREA AND REMOVE THE COAL RAKE RETRO FIT POT INSTALLATION PART 80P53831R INSERT THE NEW POT INTO THE BURN POT AREA OF THE FURNACE PLACE THE POT SCRAPER INTO THE POT AS SHOWN SLIDE THE SCRAPER ROD THROUGH THE HOLE IN THE FRONT OF THE FURNACE AND SCREW INTO POT SCRAPER Figure 13 The Maintenance of this pot consists of using the pot scraper to clean the grate in the bottom of the pot when needed The pot clinkering shut over a short period of time would be considered unusual and an adjustment will need to be made to the draft or the cycle time of the board may need to be lengthened For information on adjusting the Cycle Time see point 13 on page 53 If you have
63. when needed The Fan Limit Control is also located on the left side Supply Air The SC 050 Furnace may be connected to a gas oil or Electric Heat pump system with existing duct work Return Air The furnace does not need to be connected directly to the existing cold air return system but it is recommended Venting The location should be as close as possible to an outside wall for venting purposes The furnace requires 4 PL Vent pipe The shortest vent system with minimal elbows is the best SCF 050 Manual 7 Sold and serviced by www PelletKing com 603 424 1183 Clearances amp Access for Service amp Maintenance LE MOSSY E i A 1 j f j LIL Figure 3 FLOOR PROTECTION The furnace should be installed on a non combustible surface extending 16 in front of the unit LEFT SIDE Minimum clearance to combustibles on the right side of the furnace is 2 ACCESS FOR SERVICE AND MAINTENANCE The remaining clearances shown above are required to allow access to components during service and maintenance SCF 050 Manual 8 Sold and serviced by www PelletKing com 603 424 1183 Caution INSTALLATION IS TO BE PERFORMED BY A QUALIFIED INSTALLER OR DEALER ADHERE TO ALL CLEARANCES SPECIFIED BY THE MANUFACTURER OF THE VENTING SYSTEM USED ADHERE TO ALL CLEARANCES SPECIFIED IN THE INSTALLATION INSTRUCTIONS OF THIS FURNACE THIS FURNACE USES A POSITIVE PRESSURE VENTING SYSTEM DO NOT INSTALL A FLU
Download Pdf Manuals
Related Search
Related Contents
QP019 Manual GXV670 Suplemento PROGRAMME - Théâtre de Grasse DROIT SOCIAL Sony PCWA-C100 User's Manual Consulter le document en PDF - Bureau de la sécurité des INFORMATION, INSTRUCTION & USER MANUAL HoMedics HHP-250-CA Downloadable Instruction Book catalogo_residenziale Copyright © All rights reserved.
Failed to retrieve file