Home
Motorpact™ - 7.2 kV - Elektronický katalog Schneider Electric
Contents
1. DE57744 E hee FH FH _ L oe SH o SH X 804 1520 9 1720 Room Motorpact entrance T 2500 28007 N Y Y 1200 Y 1 Minimum dimensions to be defined according to the cable bending radius Note for lined up switchboard with MCset 2 Minimum dimensions to be complied with when installing the MCset switchboard 3 Operating distance 4 Distance needed to extract a functional unit from the switchboard without moving the other units 5 Provide an exhaust tunnel above the switchboard when the room height is less than 4 metres For further information refer to the civil engineering user and instruction manual Schneider D Electric Installation Implementation examples Stand alone switchboard DE55506 ji f amp Sorsan B Sostar j B 2 HHH H AHH cure ou as A v v Civil engin
2. Schneider D Electric El Busbar A LV control cabinet El Withdrawable part El Current sensors H Earthing switch 3 Voltage transformers MV connections El Busbar A LV control cabinet El Withdrawable part El Current sensors H Voltage transformers El Busbar A LV control cabinet El Earthing switch El Voltage transformers El Busbar El Earthing switch EIMV fuses E LV control cabinet PE56474 PE55146 Description Earthing conductor interconnection Enclosures General characteristics Motorpact is composed of modular cubicles single tiers indoor construction Each transformer or motor starter consists in a single or multiple section line up close coupled to the main incomer switchgear Degree of protection m P3X outside the enclosure optional 4X m IP2XC inside the enclosure m IPX1 is optional Tunnel Atunnel of 457 mmis installed m when the rating current of the busbars is higher than 2500 A m when the cubicle is internal arc type and the ceiling is lower than 4 m Anti corrosion protection and finishing To ensure that the equipment performs under severe climatic it is finished as follows 1 all non painted steel parts are zinc plated 2 all painted steel parts are cleaned and a zinc phosphate pre treatment applied prior to paint application 3 paint colour is RAL9002 white frosted TGIC polyester powder applied electrostatically throu
3. Low voltage control cabinet Busbars compartment Operating panel Line disconnector MV fuses Load compartment Vacuum contactor Es Schneider D Electric Motorpact range Presentation Motorpact is composed of modular indoor single tier cubicles Each motor starter or transformer feeder consists of single or multiple section equipment close coupled to the main incoming switchgear Stand alone motor starter equipment can be provided with an incoming cable cubicle Description of the basic cubicle Each motor starter or transformer feeder consists of four parts separated by metal sheets or isolating parts and an operating panel special sections are required for reduced voltage starters El Line disconnector A two position closed or earthed air break disconnector safely isolates the load compartment from the busbars El Busbars compartment A horizontal main bus allows easy extension of the switchboard El Load compartment It includes ma removable vacuum contactor m 1 or 2 fuses per phase ma set of current sensors ma cable earthing switch optional m cable connection facilities top or bottom Optionally the load compartment can contain a control power transformer CPT a voltage transformer VT a voltage presence indication system VPIS and a power factor correction capacitor El Low voltage control cabinet Adequate space is provided for all necessary prote
4. Electrical endurance AC3 250 000 operations Mechanical life Mechanically latched type 250 000 operations Electrically held type 2 500 000 operations Internal arc withstand according to IEC 62271 200 app A Internal arc withstand 4 sides 25 kA 1s 40 kA 0 5s 50 kA 0 25 s Rated operational power Values are given for combination with HRC fuses Network characteristics power factor cos p of 0 92 and efficiency 0 94 Motor characteristics Starting current 6xIn Starting time 5s Number of starts per hour 6 Rated voltage 3 3 5 5 6 6 Rated operational current 200 A Motor power with 315 A single fuse kW 950 1500 1800 Transformer power with 315 A single fuse kVA 1000 1600 2000 Rated operational current 400 A Motor power with 315 A single fuse kW 950 1600 1900 Motor power with 315 A double fuses kW 1900 3000 3800 Transformer power with 315 A double fuses kVA 1800 3000 3500 Schneider D Electric Motorpact range Operating conditions Operating conditions Normal operating conditions according to IEC 60694 for indoor switchgear m Ambient air temperature o less than or equal to 40 C o less than or equal to 35 C on average over 24 hours o greater or equal to 5 C m Altitude o less than or equal to 1000 m o above 1000 m a derating coefficient is applied please consult us m Humidity n average relative humidity over a 24 hour period less t
5. m as a Main contactor in all the motor starters and the transformer feeder m as a Start and Run contactor in the RVAT motor starter W as a By pass contactor in the RVSS motor starter Main fused contactor Use Main contactor controls the motor or the transformer feeder It can be electrically held or mechanically latched optional It is combined with fuses for high level short circuit protection It is controlled m locally m remotely Description The vacuum contactor comply with IEC 60470 standard It comprises m 3 vacuum interrupters breaking an electromagnetic control unit that can be electrically held mechanically latched optional a contactor position indicator a mechanical operation counter option auxiliary contacts m aextraction rail system to remove the contactor BEEBOCG Location It is situated below the power fuses and mounted on rails in order to be easily removable Auxiliary contactors RVAT Start contactor Use an electrically held contactor to connect the auto transformer in Y during the first step of the starting time RVAT Run contactor Use an electrically held contactor to by pass the auto transformer after the motor has reached operating speed For RVAT the Main and the Run contactors are switched automatically by the control logic RVSS By pass contactor Use an electrically held contactor to by pass the SoftStart after the motor has reached operating speed For
6. m designing multifunctional parts to reduce connections and hardware m using non flammable materials used in the cubicle m utilization of concentric compression connections on all flexible bus connections Installation in a room must be in accordance with the ceiling height m Ceiling height between 2 8 and 4 meters it is possible to install a tunnel above the switchboard in order to channel off the hot gas due to the effects of internal arcing and to avoid the gases moving towards any present operators m Ceiling height over 4 meters the tunnel is not compulsory Schneider D Electric DE57730 PE55147 Description Line disconnector Maintenance free line disconnector Use The line disconnector provides isolation between the busbars compartment and the load compartment Location It is situated in the main enclosure at the upper part of the load compartment and is manually operated from the front of the cubicle Description The disconnector has two positions m connected closed m earthed disconnected The disconnector is a non load break device capable of interrupting the magnetizing current of the control power transformer 5000 operations without maintenance The disconnector contacts are readily visible An optional light is available The internal degree of protection is IP2XC The load side terminals are integrated into a single multifunctional unit that also integrates the fuse holders single o
7. m earthing switch key interlock m disconnector operator m disconnector key interlock m disconnector padlock provision m earthing switch padlock provision It comprises also a viewing window and a pushbutton for the disconnector and load compartment back light Schneider D Electric DE57740 PE56475 Description LV control cabinet LV enclosure LV enclosure Use To install all local protection and control LV equipment Structure The low voltage control cabinet is separated from the MV compartment by earthed metal barriers A hinged door is situated at the upper part of the front of the enclosure and above the busbars compartment Relays and local control devices are flush mounted on the door of the cabinet Terminals miniature circuit breaker auxiliary relays are fixed on DIN rails inside the cabinet Under the LV control cabinet in front of the busbars compartment a fix escutcheon gets together pushbutton lamps voltage presence indicator system and a position disconnector mechanical indicator Schneider D Electric PE55170 Description Each Motorpact unit is equipped with a comprehensive protection control and measuring system comprising m instrument transformers to measure the necessary electrical values phase current residual current voltages etc m Sepam protection relay adapted to the application m metering equipment m ow voltage auxiliary relays DE5
8. 2 Underfrequency 81L 4 Temperature monitoring 8 RTDs 38 49T Hn Hn Temperature monitoring 8 or 16 RTDs 38 49T Hn Thermostat Buchholz 26 63 o Metering Phase current I1 12 I3 RMS residual current 10 Demand current l1 12 I3 peak demand current IM1 IM2 IM3 m 1 1 Voltage U21 U32 U13 V1 V2 V3 residual voltage VO a Positive sequence voltage Vd rotation direction Negative sequence voltage Vi Frequency 1 Active reactive and apparent power P Q S Peak demand power PM QM power factor Calculated active and reactive energy W h var h Active and reactive energy by pulse counting W h varh Hn Temperature o oO o Network and machine diagnosis Tripping context Tripping current Tripl1 Tripl2 Tripl3 TriplO 1 Unbalance ratio negative sequence current li Phase displacement 90 o1 92 93 Disturbance recording u Thermal capacity used u L Remaining operating time before overload tripping Waiting time after overload tripping a nu P Running hours counter operating time B n u Starting current and time Start inhibit time number of starts before inhibition Switchgear diagnosis Cumulative breaking current Trip circuit supervision o o o Number of operations operating time charging time m m H CT VT supervision 60FL Control and monitoring ANSI code Circuit breaker contactor control 1 94 69 n n Latching acknowledgement 86 Logic discrimination 68 n H Hn Sw
9. 32Q 1 1 1 Frequency u 7 Phase undercurrent 37 1 1 1 Active power P P1 P2 P3 Excessive starting time locked rotor 48 51LR 1 1 1 Reactive power Q Q1 Q2 Q3 Starts per hour 66 1 1 1 Apparent power S S1 S2 S3 Field loss underimpedance 40 1 1 1 Peak demand power PM QM 2 Pole slip 78PS 1 1 1 Power factor Overspeed 2 set points 2 12 n n r Calculated active and reactive energy Wh VARh Underspeed 2 set points 2 14 o n o Active and reactive energy by pulse counting 2 o o n Positive sequence undercurrent 27D 2 2 2 Wh VARh Remanent undervoltage 27R 2 2 2 Phase current I 1 1 2 l 3 RMS Senne Lt an f j i Calculated residual current O m m vervi Lor L Nunal T ETET 59N 2 2 2 Temperature 16 RTDS H i Negative sequence overvoltage 47 2 2 2 Potation speed nd n n a Overfrequency 81H 2 2 2 Neutral point voltage Vnt Underfrequency 81L 4 4 4 Network and machine diagnosis Thermostat Buchholz 2 26 63 5 Tripping o o m m 8 Temperature monitoring 16 RTDs 3 38 49T n n n Tripping currant TBI Tapes Wipls m m TENET Phase fault and earth fault trip counters Control and monitoring Circuit breaker contactor control 94 69 E Unbalance ratio negative sequence current li Load shedding automatic restart Harmonic distortion THD current and voltage Ithd Uthd m Logic discrimination 2 68 n n n Phase displacement g0 oOo a La
10. Motorpact an innovative range of motor starters up to 3800 kW Designed and manufactured to tackle the toughest power and process control challenges Motorpact MV motor starters provide unmatched performance high reliability low maintenance and exclusive technologies that encourage only the safest operation Motorpact units can be configured as motor starters or as transformer feeders Motorpact motor starters provide a wide range of applications including reduced voltage starting m FVNR full voltage non reversing motor starter m RVAT reduced voltage auto transformer motor starter m RVSS reduced voltage SoftStart motor starter They are suitable for all MV motor applications in markets such as oil amp gas mining water pulp and paper for starting m pumps m fans m compressors m chillers m conveyors Schneider Electric pre designed solutions The Motorpact catalogue provides Schneider Electric solutions for frequently used MV motor starter applications Our solutions are designed to save engineering time and to provide adequate protection and operation of the different systems Optional equipment and applications are available for specific requirements please consult us Schneider Electric certified quality In each of its units Schneider Electric integrates a functional organization whose main mission is to check quality and monitor compliance with IEC and or NEMA standards This procedure is
11. RVSS an integral digital controller controls both the Main and the By pass contactors Location Start Run and By pass contactors are installed on rails in the upper compartment of the auto transformer or SoftStart cubicle All these contactors are interchangeable with each other and with the Main contactor Schneider D Electric PE55151 Description Load compartment Vacuum contactor Vacuum contactor characteristics Electrical characteristics Rated voltage 7 2kV Rated current 200 400A Category of use AC3 AC4 Rated short circuit breaking capacity without fuse 6 3kA Electrical endurance 250000 operations Mechanical life Mechanically latched type 250000 operations Electrically held type 2500000 operations Chopping current Avg RMS 0 5A Rated switching frequency 1200 hour 300 hour for mechanically latched version Maximum closing time 80 ms or less Maximum opening time 30 ms or less 300 ms or less delayed Control Supply voltage Vdc 100 125 240 250 Vac 115 120 230 240 possible variations 10 15 Consumption Closing is achieved via the closing coils The holding coils are inserted in the circuit at the end of the closing Closing Holding 100 110 V 670VA80ms 85VA Auxiliary contacts The auxiliary contacts are of the changeover type with a common point The following are available m 3 NO 3 NC for the electrically held version optional 3 NO amp 3
12. clamp the cable An earth busbar is provided for termination of the cable screen Floor plates are available to prevent the ingress of dust and vermin A dielectric barrier Formex is provided over the cable termination pads When rear access is available removable rear covers provide simple and easy cable termination In addition a removable top entry cover at the rear section of each FVNR cubicle provides a full height cable pull area PE55162 PE55163 PE55164 Front access Rear access Floor cable entry E Schneider D Electric PE55156 PE56477 Description Load compartment Optional equipment Cable earthing switch Use The cable earthing switch earths the outgoing cables and allows to discharge them Location It is situated on the load side of the contactor Description Electrical characteristics Earthing switch making capacity 14 kA peak No load operations according to IEC standard 1000 Direct visual indication of the position of the device on the front face Auxiliary contacts 2 NO and 2 NC auxiliary contacts are available in open and closed position Interlocking The earthing switch is mechanically interlocked with the disconnector and the MV front door As an option a key interlock is available in closed or open position Earthing switch is provided with padlock provision in open and closed positions An optional key interlock blocks access to the operating handle thus locking the earthing sw
13. m uniform throughout all departments m recognized by many customers and approved organizations But above all it is the strict application that has allowed it to obtain recognition from an independent organization The quality system for the design and manufacture of Motorpact range is certified in conformity with requirements in the ISO 9001 2000 quality assurance standards Protected environment As part of the group s environmental policy Schneider Electric Services provides you with an operational subsidiary to recover medium voltage switchgear and thus eliminate any discharge to atmosphere In order to help you protect the environment and to relieve you of any concerns in terms of stock or dismantling Schneider Electric Services offers to take back your equipment at the end of its life Motorpact has been designed with environmental protection in mind m the materials used insulators and conductors are identified easily separable and recyclable m production sites are certified to ISO 14000 Schneider D Electric PE56476 PE55132 Motorpact general presentation Motorpact the value of innovative design Motorpact MV motor starters integrate innovative solutions designed around proven technologies high performance digital protection and control maintenance free disconnector internal arc withstand capability thermal diagnosis system Safety m Fully tested for internal arc resistance in all MV comp
14. of 40kA3s 50kA2s Encapsulated 1250A Rated operational current Degree of protection housing 2500 A 3150 A 200A 400A iesx IPAX IPX1 Maintenance free disconnector Options Internal arc withstand 25 kA 1 s 40 kA 0 5 s 50 kA 0 25 s Ceiling height lt 4m _ gt 4m Thermal diagnosis system Cable earthing switch Voltage presence indicator system VPIS Heating element Back light disconnector contacts amp load compartment Key interlockings Ronis L Profalux Line disconnector Cable earthing switch Power factor correction Voltage kV Power kVA see the list page 38 Main fused contactor Removable vacuum contactor Electrically held Basic equipment Mechanically latched Open release 125 Vac 250 Vac 48 Vdc 125 Vdc 250 Vdc MV fuses Fusarc CF 442 mm 50A 63A 80A 100A 125A 160A 200A 250A 2x250A Cable connection Bottom Top 1 cable phase max 240 mm 2 cables phase max 120 mm Blown fuse indicator Options Mechanical operation counter Surge arrestors line side H Fused control power transformer CPT Basic equipment Fused voltage transformer Basic equipment SoftStart module includes basic protection metering and control 1 SoftStart module 1 by pass vacuum contactor electrically held Voltage measurement 1 set of current sensors Optio
15. or series 80 digital relays and provide the required performance for the protection and measuring functions of transformer and motor applications Due to its linearity a single LPCT covers the entire operating range If the motor changes only the setting of the Sepam protection relay has to be modified see also rule on previous page Characteristics LPCT Rated primary current 100A Rated extended primary current 800A Rated secondary output 22 5 mV Accuracy class for measuring 0 596 Accuracy limit factor 160 Accuracy class for protection 5P Burden 22kQ Rated continuous thermal current 800A Thermal current surge 5kA 10s Rated short time thermal current 16 kA Highest voltage for equipment 0 72kV Rated power frequency withstand voltage 3kV Service conditions 25 C indoor Accuracy template A 10 5 1 5 0 75 7 0 5 5A 20A 100A 5 kA 16 kA Due to its linearity a single LPCT covers the entire operating range Location It is located on the CT and load terminal assembly providing the required support and ensuring dielectric withstand Wiring and cables Each cable is 5 meters long and is embedded in the LPCT enclosure The 3 RJ45 plugs are equipped with color coded terminals that mate up to color coded sockets on the Sepam eliminating possible connection errors Schneider D Electric DE57736EN DE57737 E28678 Description D
16. rise in 2 zones m triggering of the pre alarm m triggering of the alarm m self monitoring of the module m self monitoring of the temperature probes Technical characteristics Optical fibre probes CF0733 Maximum equipment voltage 17 5 kV Rated power frequency voltage 38 kV Impulse voltage 95 kV Maximum fibre sensor temperature 120 C MDT107 module Temperature rise setting To be defined Storage temperature 25 C to 70 C Values of maximum absolute thresholds Pre alarm 115 C Alarm 120 C DIN profile width 10 5cm Module power 24 250 Vdc 110 240 Vac Dry contact voltage Voltage 24 48 127 220 Vdc 110 to 240 Vac Current 5A permanent pre alarm 8A permanent alarm Consumption standby max AC lt 1 2 W standby lt 3 4 W max DC 4 4 VA standby 6 6 VA max Schneider E D Electric PE56476 Description Operating panel Operating panel The operating front panel comprises different control and indicating elements m control Run and Stop pushbuttons m indicating lights Both can be replaced by an optional Sepam 100 MI control and indication device m local remote switch optional m mimic diagram m operating sequence m open closed indicator m running time meter optional as well as voltage presence indication system The operating front panel allows control interlocking and padlocking m earthing switch operator
17. to none priced functions The auto transformer is designed according to the motor requirements Nominal power Service voltage Nominal current RVAT auto transformer asynchronous motor starter Quantity 7 2kv _ 40kA3s 50kA2s Basic unit cubicle Rated voltage 3 6 kV LI Rated short time withstand current 25kA3s 31 5kA3s Busbar Bare Encapsulated Rated current ssoAl_ 1250A 8150A 2500A Rated operational current 200A 400A iesx IPAX IPX1 Options Internal arc withstand 25 kA 1 s 40 kA 0 5 s 50 kA 0 25 s Ceiling height lt 4m gt 4m Thermal diagnosis system Cable earthing switch Voltage presence indicator system VPIS Heating element Back light disconnector contacts amp load compartment Key interlockings Ronis LI Line disconnector Cable earthing switch Power factor correction Degree of protection housing Maintenance free disconnector Profalux 20 1C 1Oor1C Power kVA Voltage kV 1 see the list page 38 Main fused contactor Removable vacuum contactor Electrically held Mechanically latched Basic equipment Open release 125 Vac 250 Vac 48 Vdc 125 Vdc 250 Vdc MV fuses 50A 63A 80A 100A 125A 160A 200A 250A 2x250A Cable connection Bottom Top 1 cable phase max 240 mm 2 cables phase max 120 mm Blown fuse indicator LL T NNI Options Mechanical operation cou
18. 7741 LV control cabinet Sepam protection system Sepam digital protection relay Sepam is at the heart of the protetion chain It carries out all the necessary protection control monitoring and signalling functions and provides an optimal solution for each application m Sepam T transformer feeder m Sepam M motor starter m Sepam B or S for busbars substation and capacitor application Sepam series 20 series 40 and series 80 a modular solution To satisfy increasing numbers of applications and allow the installation to be upgraded W basic advanced or mimic based User Machine Interface The advanced UMI with graphic LCD screen and keypad can be remotely located m functional enhancement by optional modules o 42 logic inputs and 23 relay outputs with 3 optional modules o Modbus communication network connection interface o 8to 16 temperature probes acquisition module O analog output 4 20 mA O Synchro check module Sepam simplicity and performance Easy to install m optional modules common for all Sepam and easy to implement Assisted commissioning m pre defined functions commissioned by a simple parameter setting m user friendly and powerful PC software for parameter and protection setting User friendly m intuitive User Machine Interface with direct data access m local operating data in the user s language Protection in Motorpact units The basic equipment of each Motorpact unit comprise
19. A 3150A Cables Bottom Top or bottom Single core 6 x 400 mm 6 x 400 mm 4x 500 mm 4 x 500 mm Three core 6 x 240 mm 6 x 240 mm Busducts Top Dimensions H 2300 mm 2300 mm W 500 mm 750 mm D 950 mm 950 mm Approximate weight 350 kg 900 kg Transition to MCset functional units Composition Basic equipment m 1 enclosure standard IP3X W 1 set of busbars in separate compartment m 1 removable front panel Characteristics Options m internal arc withstand m IP4X or IPX1 enclosure m encapsulated busbars Transition cubicle to MCset Maximum rated voltage 7 2kV Impulse withstand voltage 1 2 50 us peak value 60 kV Power frequency withstand voltage 1 min 20 kV Busbars ratings 630A 1250A 2500A 3150A Dimensions H 2300 mm Ww 375 mm D 1550 mm Approximate weight Consult us Schneider D Electric Motorpact range Make up a Motorpact MCset switchboard MCset switchboard is made up of several interconnected functional units By using a transition functional unit it s easy to connect a MCset switchboard with a Motorpact switchboard For details see MCset catalogue ref DEAIO2 1 For functional units equipped with circuit breakers or fuse contactors the breaking capacity is equal to the short time withstand current In all cases the device peak making capacity is equal to 2 5 times the short time withstand current 2 With fan 3 Lightning impulse dielectric withst
20. Medium Voltage motor starter Motorpact 7 2 kV Vacuum contactor Catalogue Schneider Electric A new path for achieving your electrical installations A comprehensive offer Motorpact is part of a comprehensive offer of products that are perfectly coordinated to meet all medium and low voltage electrical distribution requirements All of these products have been designed to work together electrical mechanical and communication compatibility The electrical installation is thus both optimised and has improved performance W better service continuity m increased personnel and equipment safety m guaranteed upgradeability m efficient monitoring and control You therefore have all the advantages at hand in terms of know how and creativity for achieving optimised safe upgradeable and compliant installations Tools for facilitating the design and installation With Schneider Electric you have a complete range of tools to help you get to know and install the products whilst complying with current standards and good working practices These tools technical sheets and guides design software training courses etc are regularly updated Schneider Electric is associating itself with your know how and your creativity to produce optimised safe upgradeable and compliant installations For a real partnership with you Auniversal solution doesn t exist because each electrical installation is specific The variety of
21. NC additional auxiliary contacts m 5 NO 6 NC for the mechanically latched version as standard Characteristics Operating voltage Minimum 48V Maximum 480 V Rated current 10A Breaking capacity Vdc 60 W L R 150 ms Vac 700 VA power factor 0 35 Options m Mechanical operation counter m Mechanically latched contactor including open release The open release allows opening of the contactor when mechanically latched It is supplied with o mechanical position indicator o padlock provision closed position o 1 key interlock open or closed position optional o 1 emergency mechanical trip pushbutton Open release characteristics Power supply Vdc 48 125 250 Consumption W 470 680 640 Response time ms 20 40 20 41 20 40 Schneider D Electric DE57733 Description Load compartment MV fuses MV fuses Use MV power fuses are used for short circuit current protection Sepam series 20 40 or 80 digital relay provides fine protection and metering and control of the motor or transformer Characteristics Fuses comply with IEC 60282 1 and DIN 43625 standards with high breaking capacity High fault current limitation reduces electrodynamic stresses on the load side components contactor cables CT s etc A blown fuse indicator is provided to open the three poles of the contactor in case of single phase or two phase fault Maximum service voltage 7 2 kV Maximu
22. able m 750 mm wide for rated current up to 400 A Structure The main busbars goes through the module in a segregated compartment It splits the module in two parts m the upper part with the by pass vacuum contactor m the lower part with the MV SoftStart device The upper medium voltage door has an optional window to see the status of the bypass contactor The medium voltage doors are mechanically interlocked with the disconnector of the main cubicle Alow voltage compartment in the centre of the module contains the logic and control of the SoftStarter Dry cables are used to connect the SoftStart module to the main cubicle Earthing switch voltage presence indication system customer s terminations are in the main cubicle SoftStart modules are designed to ship connected to the main cubicle Keypad interface Motorpact SoftStart offers keypad display programming and serial communications A2 line x 20 character LCD display with backlight provides easy readout of multiple motor data points Motor protection functions W over current m under current m current imbalance m two stage overload W reset m number of starts per hour Metering functions m motor load m phase current average current earth fault current m thermal capacity remaining thermal capacity to start m average start time current capacity to start elapsed time from last start m upto 12 RTD s data m kW kvar power factor kWh Communi
23. acts amp load compartment Profalux Key interlockings Ronis L Line disconnector Cable earthing switch Power factor correction Voltage kV see the list page 38 Power kVA Main fused contactor Removable vacuum contactor Electrically held Basic equipment Mechanically latched Open release 125 Vac 250 Vac 48 Vdc 125 Vdc 250 Vdc MV fuses 50A 63A 80A 100A i25A 160A 200A 250A 2x250A Cable connection Bottom Top 1 cable phase max 240 mm LI 2 cables phase max 120 mm Blown fuse indicator Options Mechanical operation counter OOT Surge arrestors line side Fused control power transformer CPT Fused voltage transformer Protection metering and control Sepam digital relay see Sepam catalogue m2o Other Transparent Ready option 4l e Local control Sepam 100MI Phase current sensors 5ACT LPCT 2 push buttons 2 indication lights L R T 1ACT Zero sequence current sensors ZSCT L CSH 120 CSH 200 E CSH 280 Sepam options Additional logic I O s module MES114 Analog output module MSA141 Temperature sensor acquisition module MET148 Modbus communication interface LITT LETI ACE949 Schneider D Electric Order form Only one ofthe boxes ticked X orfilled Joy the needed value have to be considered between each horizontal line Green box X corresponds
24. and voltage 60 kV peak 4 Limited by fuses 5 With LF circuit breaker with Evolis circuit breaker consult us 6 With Rollarc contactor 7 Limited to 1 s for In circuit breaker 1250 A PE56473 MCset functional unit The MCset cubicle The cubicle is of LSC2B Loss of Service Continuity Category type as defined by IEC standard 62271 200 in other words the medium voltage parts are compartmented using metal partitions PM class which are connected to earth and which separate m the busbars m the withdrawable part circuit breaker fuse contactor disconnector truck or earthing truck m MV connections earthing switch current sensors and voltage transformers as required MCset guarantees a high level of protection of people when a compartment containing a main circuit is open the other compartments and or functional units may remain energised The low voltage auxiliaries and monitoring unit are in a control cabinet separated from the medium voltage section Four basic cubicle layouts are offered m incomer or feeder AD m line up bussection CL GL m busbar metering and earthing TT m switch fuse feeder DI AD and CL cubicles have withdrawable switchgear Electrical characteristics The values below are given for normal operating conditions as defined in IEC 62271 200 and IEC 60694 Rated voltage kV 72 12 Rated insulation level Power frequency withstand voltage 50 Hz 1 min rms kV 20 28 Lightn
25. arc withstand cable earthing switch including mechanical position indicator auxiliary contacts padlock provision blown fuse indicator m mechanically latched vacuum contactor includes release coil m 1 disconnector load compartment back light m key interlocks m encapsulated busbars m 1 fused control power transformer CPT m additional CT s or ZSCT zero sequence current Low voltage control m 1 Sepam T20 transformer protection relay m Start amp Stop pushbuttons m Run amp Stopped pilot lights Control options m fuse protection without protective relay m Sepam series 40 or series 80 protection relay m Transparent Ready option m 1 Sepam 100 MI control and indication m IP4X or IPX1 enclosure transformer m local remote switch not m 1 set of 3 surge arrestors needed in case of Sepam 100MI m voltage presence indicator system VPIS m heating resistor Sepam accessories m mechanical operation counter m additional logic I O module m running time meter m Modbus communication interface m motor temperature sensor acquisition module m analog output module Attype Operation and interlocking z See FVNR cubicle Basic transformer key interlocks A1 type To prevent closing the earthing switch on a transformer feeder unless the LV circuit breaker has been opened first and locked in the open or disconnected position C1 type Ci o To prevent access to the transformer if the earthing sw
26. ardless of the load This starting method lowers the starting current of the motor reduces electrical eb stresses on the network and the motor It reduces peak starting torque stresses on both the motor and mechanical load components thereby providing longer service life and less downtime N1 Nn I andT Torque regulation I starter U start k we leeccccect Resistive torque Resistive torque For synchronous motors please consult us For selection of motor starter type see the Application guide ref AMTED303042EN Es Schneider D Electric DE57701EN DE57704 DE57705 Motorpact range Motorpact range Transformer feeder Transformer feeder is a cost effective solution to include auxiliary transformer feeder in a Motorpact assembly It can be used as a fused contactor feeder with Sepam transformer relay or as a fused switch This solution for a transformer feeder within a motor starter assembly provides the operator consistency in the operation of the equipment as well as providing standardisation of features and controls in the Motorpact range Incoming cubicle for stand alone application An auxiliary cubicle for incoming cable connections for standalone motor control applications Available up to 3150 A Bottom cable entry is available in the 500 mm cubicle Busduct top and bottom cable entry is available in the 750 mm cubicle Optional voltage pres
27. artment It provides an IP2XC protection inside the enclosure It splits the module in two parts m the upper part with the two vacuum contactors start and run The door has two optional windows to see the status of the contactors m the lower part with the auto transformer The medium voltage doors are mechanically interlocked with the disconnector of the main cubicle Dry cables are used to connect the auto transformer and the contactors to the main cubicle Current sensors earthing switch voltage presence indication system customer s terminations are in the main cubicle Provision is supplied in the auto transformer module to install a current transformer for accurate measurement of motor current Auto transformer modules are designed to ship connected to the main cubicle Schneider bg D Electric DE57743 Description Characteristics Voltage 2 8kV 7 2kV Frequency 50 or 60 Hz Unit overload capacity 125 96 Continuous 500 60 seconds 600 30 seconds Power ranges 3 3 kV to 1900 kW 5 5 kV to 3000 kW 7 2 kV to 3800 kW Power circuit 6 SCRs 12 SCRs or 18 SCRs SoftStart compartment SoftStart module Use This module is always erected on the right side of the main cubicle to compose the SoftStart motor starter Selection One width of module is avail
28. artments m Fully safe compartmented design prevents inadvertent access to MV compartments m Viewing window provides visible disconnector earthed position from the front of the equipment indicating safe isolation of the starter from the busbars m Cable earthing switch with making capacity m Closed door operation m Simple interlocks prevent inadvertent operator errors Reliability m Simple architecture with a line disconnector which reduces the number of parts and provides simple and robust interlocks m Multifunctional cast components minimizes parts consequently reduces maintenance and heat loss m Pre engineered solutions with low power current transducer LPCT and Sepam digital relay provide proven designs for the full range of motor applications m Separate LV control cabinet enhances electromagnetic compatibility EMC and wire management m Global design complying with all relevant IEC and NEMA standards Maintainability m All necessary maintainable motor starter components accessible without the need of de energizing the complete switchboard m Maintenance free vacuum contactor m High endurance maintenance free line disconnector m Thermal diagnosis system for predictive maintenance m Few spare parts Compactness and flexibility m Compact footprint of 375 mm width m One design allows front rear top and bottom cable entries m Simple and compact transition cubicles allow extension to other Schneider El
29. cation m protocol Modbus m RS 485 Schneider D Electric Description MV fuses Selection guide Motor application Starting Normal Minimum LPCT Starting time s current A current A CT rating 5 10 30 Id In 6 sec 1 A Number of starts per hour 2400 400 400 valid with 2200 366 400 all fuse 2000 333 300 ratings 1725 288 300 2x 25 2 x 250 1570 262 300 2x 200 X 1415 235 75 1x315 1x315 1x315 1x315 1x315 2 x 200 1256 209 75 1x315 1x315 1x315 1x315 1x315 1x315 1100 183 75 250 250 250 1x315 1x315 1x315 942 157 75 250 250 250 250 250 250 785 131 75 200 200 200 200 200 250 628 105 75 160 160 160 200 200 200 565 94 75 160 160 160 160 160 160 502 84 75 125 160 160 160 160 160 439 73 75 125 125 125 160 160 160 377 63 75 100 125 100 125 125 160 314 52 30 100 100 100 100 100 125 251 42 30 100 100 100 100 100 100 188 31 30 80 100 100 100 100 100 126 21 30 50 50 63 80 80 80 63 10 30 32 32 32 40 40 40 47 8 30 25 32 32 32 32 32 31 5 30 25 25 25 25 25 25 Note o fuses are 442 mm long o fuses are only for short circuit protection Ofor starting currents lower than 170 A we recommend the LPCT mI Itis necessary to delay the tripping of the contactor Transformer application Quantity and rated current for Fusarc fuses These values are approximate Please check with the actual characteristics of the transformer to de
30. combinations on offer allows you to truly customise the technical solutions You are able to express your creativity and put your know how to best advantage when designing manufacturing and exploiting an electrical installation Motorpact 7 2kV Contents Motorpact general presentation Field of application Motorpact the value of innovative design Motorpact a comprehensive solution Motorpact Transparent Ready Motorpact range Presentation Technical characteristics Operating conditions Specific applications Motorpact range o FVNR full voltage non reversing asynchronous motor starter o RVAT auto transformer asynchronous motor starter o RVSS SoftStart asynchronous motor starter n Transformer feeder n Incoming cubicle Transition to MCset functional units o MCset functional unit Description Enclosures Line disconnector Busbars compartment Load compartment o Vacuum contactor n MV fuses o Current sensors o Cable connection o Optional equipment Operating panel LV control cabinet n LV enclosure o Sepam protection system o Local remote control device Auto transformer compartment SoftStart compartment MV fuses selection guide Installation Implementation examples Order form Schneider amp Electric 2 3 4 5 MT20052 PE55175 MT20069EN Motorpact general presentation To comply with the environment rules To protect the environment Field of application
31. core dry cables m Screened and non screened cable m Armoured or non armoured cable Location Cable termination pads are located on the left side of the main contactor FVNR unit for all applications including auto transformers and SoftStarts They are situated 310 mm from the front of the cubicle to allow for easy access during installation and maintenance The cable termination pads are suitable for m 1 cable max 240 mm or m 2cables max 120 mm je d a Nw ree Equipment cable access FVNR Cable termination pads are designed for easy accessible from the front of the cubicle Cables can exit as follows Cable type Utility space Front and rear access Front access only 7 2 kV max Top Bottom Top Bottom Single core u u u Phasing relationship Three core u u a Single core u u u u Three core u a Incoming line Cable termination pads are designed to be easily accessible from the front of the cubicle Cables can exit as follows Incoming cubicle width Front and rear access Front access only Top Bottom Top Bottom 500 mm Li E 750 mm u u u u Load termination pads Load termination pads are provided with a two hole configuration permitting the use of virtually any one or two hole cable connecting lug To prevent single hole cable lugs from rotating provision is provided to
32. ction and control devices such as Sepam protection relay PowerMeter or Circuit Monitor metering unit auxiliary relays etc For access to the main busbars from the front of the switchboard a removable panel at the bottom of the LV control cabinet is provided El Operating panel Contains all necessary devices to operate the line disconnector and the cable earthing switch Pushbuttons control the electrically held contactor and long life LED lights provide contactor status indication Schneider E D Electric PE56472 Motorpact range Technical characteristics Motor starter ratings Installation Indoor type Maximum rated voltage 7 2kV Rated Insulation level Impulse withstand voltage 1 2 50 us peak value 60 kV Power frequency withstand voltage 1 min 20 kV Maximum rated short time withstand current busbars 40kA3s 50 kA2 s Rated frequency 50 60 Hz Maximum busbars rating 2500A 3150 A Degree of protection Enclosure IP3X IPAX IPX1 IPX2 Between compartments IP2XC for stand alone applications or when lined up with LF circuit breaker MCset switchgear Fused contactor ratings Technology Vacuum type Rated operational current 200 400A Rated short circuit breaking capacity HRC fuses 50 kA Rated switching frequency 1200 hour Category of use AC3 amp ACA Type of HRC coordination Class C Mechanism Mechanically latched Electrically held
33. dle has been removed m allows for a test position which meets the following criteria o the front door has been opened for access O the disconnector is open and earthed and can not be closed o the contactor is in the fully connected position and can be operated o the control power transformer has been isolated from the test control power All interlocks do not require adjustments over the life of the equipment Schneider D Electric DE57078 DE57708 Motorpact range RVAT auto transformer Front view Main cubicle asynchronous motor starter Side view Auto transformer module Main cubicle Auto transformer module Auto transformer module 1 T T 4 DE57117 DE57711 H H w2 wi 1 1 Run and start vacuum contactor 2 Busbars 3 Auto transformer Characteristics ATM1 ATM2 Maximum motor power 440 kw 3800 kW Dimensions H 2300 mm 2300 mm W1 1500 mm 1875 mm W2 with capacitor module 1875 mm 2250 mm D 950 mm 950 mm Approximate weight 1200 kg 1360 kg Auto transformer weight to be added The auto transformer is designed according to the motor requirements Nominal power Service voltage Nominal current Frequency Starting current Starting tim
34. e motor Starting time motor auto transformer Number of starts hour Number of consecutive starts Schneider D Electric Motorpact range Composition of RVAT motor starter RVAT auto transformer asynchronous motor starter The RVAT motor starter is composed of a main cubicle similar to FVNR unit and auto transformer module Basic equipment Main cubicle m 1 enclosure standard IP3X 1 line disconnector 1 electrically held vacuum contactor 3 or 6 HRC fuses 1 set of busbars 1 three core LPCT auxiliary contacts provision for padlocks 1 position contactor indicator window Options and accessories Starter options thermal diagnosis system internal arc withstand cable earthing switch including mechanical position indicator auxiliary contacts o padlock provision m blown fuse indicator m P4X or IPX1 enclosure m power factor correction capacitor FVNR3 DO Ba Auto transformer module m 1 enclosure standard IP3X m 1 electrically held vacuum contactor Run contactor W 1 vacuum contactor mechanically interlocked with the Run contactor Start contactor m 1 auto transformer m provision for LPCT true current measurement m mechanically latched vacuum contactor includes release coil m 1 disconnector load compartment back light m key interlocks m encapsulated busbars m 1 fused control power transformer CPT m additional CT s or ZSCT zero sequence current transforme
35. e damage due to water hammer m With DOL motor starters torque is lost instantly when the starter is turned off o fluid flowing through the system and associated kinetic energy immediately reverses To prevent reverse flow a check valve closes trapping kinetic energy in the piping system and creating a shock wave water hammer O gradual reduction in motor torque using decel control dissipates the pump output pressure slowly during the stopping process Check valves close gently and the other system components pipes valves flanges couplings and hangers are not subjected to the shock Seconds 104 Class 30 Class 25 Class 20 1000 Class 15 Class 10 Class 5 100 9 xin o A N gt a o N co Schneider D Electric PE55174 Motorpact range Characteristics Overload capacity RVSS SoftStart asynchronous motor starter Main features 12596 continuous 500 60 seconds 600 30 seconds 850 1 cycle internal electronic shear pin Frequency 50 or 60 Hz 2 Hz hardware selectable Power circuit 6 120r 18 SCRs SCR PIV rating 3 3 kV 13000 6 6 kV 19500 Phase insensitivity User selectable Phase sequence detection Transient voltage protection RC snubber dv dt networks 1 per SCR pair Control power 2 or 3 wire 110 Vac CPTs are supplied on all standard units Auxiliary contacts Motor protection Two stage electronic Overload curv
36. ectric equipment m Ideal for retrofit applications Schneider D Electric PE55170 PE55134 PE55135 PE55136 Motorpact general Motorpact presentation a comprehensive solution Motorpact MV motor starters provide the most efficient means to control and protect a wide range of applications Sepam protection and control units Sepam series 20 series 40 and series 80 digital protection relays take full advantage of Schneider Electric experience in electrical network protection Sepam series 20 series 40 and series 80 provides all the necessary functions m effective protection of people and property m accurate measurements and detailed diagnosis m integral equipment control m local or remote indication and operation Easy evolution Addition of communication digital I O s analog output or temperature acquisition are possible due to its modular design PowerMeter and Circuit Monitor metering units The PowerLogic PowerMeter replaces a full complement of basic analog meters This cost effective high performance meter provides a full complement of accurate true rms metering values The PowerLogic Series 3000 4000 Circuit Monitor is designed for critical s power users and large energy consumers to provide the information A needed to confidently enter the evolving world of deregulation It can be adapted to meter almost any time of use or real time rate HAN RA 3 jm jm m je m Im Monitoring and con
37. eering with utility space for front and rear access a A 804 1520 gt Room Motorpact entrance 2500 2800 N Y Y 1100 Y 1 Minimum dimensions to be defined according to the cable bending radius 2 Can be placed against the wall for single core cable applications or for single and three core applications if utility space provides bottom access for three core preparation and installation For further information refer to the civil engineering user and instruction manual Schneider E D Electric Order form Only one ofthe boxes ticked X orfiled Joy the needed value have to be considered between each horizontal line Green box X corresponds to none priced functions FVNR full voltage non reversing asynchronous motor starter Basic unit cubicle Rated voltage 3 6KV Quantity 7 2kv Rated short time withstand current 25kA3s 315kA3s 40kA3s 50kA2s Busbar Bare Encapsulated Rated current esoA 1250A 2500A 3150A Rated operational current 200A 400A Degree of protection housing IP3X L IP4X IPX1 Maintenance free disconnector Options Internal arc withstand 25 kA 1s 40 kA 0 5 s 50 kA 0 25 s Ceiling height lt 4m _ gt 4m Thermal diagnosis system Cable earthing switch Voltage presence indicator system VPIS Heating element Back light disconnector cont
38. ence indicator system VPIS MCset transition cubicle for lined up application An auxiliary cubicle to allow transition to the MCset switchgear at either end Available up to 4000 A Schneider ES D Electric DE57706 Motorpact range DE57116 FVNR full voltage non reversing asynchronous motor starter Front view FVNH1 FVNR3 Characteristics Maximum rated voltage o E R D w a Side view FVNR1 and FVNR3 MV compartment 1 Line disconnector 2 Busbars 3 Fuses 4 Contactor 5 Earthing switch 6 Current sensors LPCT current transformer and earth fault sensor LV control cabinet 7 LV protection measurement and control devices FVNR1 7 2 kV FVNR3 Maximum power at 6 6 kV p f 0 88 n 0 95 3800 kW Impulse withstand voltage 1 2 50 us peak value 60 kV Power frequency withstand voltage 1 min 20kV Rated short time withstand current busbars 25kA3s 31 5 KA3s 40 kA3s 50 kA 2 s Rated frequency 50 60 Hz Rated operational current 200 400 A Busbars ratings 630A 1250A 2500 A 3150 A Category of use AC3 AC4 Cable connections Single or three core Maximum 1 x 240 mm2 or 2x 120 mm Bottom or top Dimensions H 2300 mm 2300 mm WwW 375 mm 750 mm D 950
39. ent limit 200 600 VR or CR Dual ramp settings 4 options VR1 VR2 VR1 CR2 CR1 CR2 CR1 VR2 Dual ramp control Ramp 1 Default Ramp 2 Selectable via dry contact Deceleration adjustments Begin decel level 0 100 Un Stop level 0 100 less than begin decel level Decel time 1 60 seconds Jog settings Voltage jog 5 75 Kick start settings Kick voltage 10 100 or off Kick time 0 1 2 seconds Fault display Shorted SCR phase loss shunt trip phase imbalance trip overload overtemp overcurrent short circuit load loss undervoltage or any trip Lockout display Coast down time starts per hour time between starts and any lockout Event history Up to 60 events Data includes cause of event time date voltage power factor and current for each phase Metering functions Motor load and ground fault current at time of event Percent of In Current data A B C phase current average current ground fault option Thermal data Remaining thermal register thermal capacity to start Start data Average start time and start current measured capacity to start time since last start Resistance temperature Temperature readings from up to 12 RTDs 6 stators detector data Voltage metering Serial communications Protocol kW kVAR PF kWh Modbus9 RTU Signal RS 485 RS 422 or RS 232 Network Up to 247 devices per node Functionality Full operation status view and pro
40. er including web pages dedicated to power equipment data Easy commissioning Transparent Ready equipment is delivered ready to connect and commission A Quick Start guide packaged with your switchboard provides three easy to follow steps Functionalities provided TRe 1 TRe 2 Instantaneous readings 1 Displays automatically updated meter values Circuit summary Displays the RMS current 3 phase average A the real power KW the power factor the circuit breaker status if applicable etc Load current summary Displays the current RMS value for each phase A for all circuits Demand current summary P Displays the average demand current value for each phase A for all circuits Power summary Displays the present demand kW the peak demand kW and the times and dates ofthe records Energy summary 1 u Displays the energy kWh the reactive energy kvarh and the times and dates ofthe records Instantaneous readings all devices Displays automatically updated meter values for all the communicating devices in the equipment Basic historical data logging energy and trending Displays automatically updated meter values for all the communicating devices in the equipment Log displays Displays data as time curves or tables Export of data tables 1 Allows data tables to be exported in a standard Windows format Schneider D Electric Motorpact range Presentation PE56471
41. es Multiple changeover contacts rated 5 A 250 Vac max 8 fully programmable relays including fail safe operation 5 dedicated relays fault at speed etc Start Run Class 5 to 30 Class 5 to 30 when at speed detected Overload reset Manual Default or automatic Retentive thermal memory Overload circuit retains thermal condition of the motor witout control power Real time clock adjusts for off time Dynamic reset capacity No overload reset until thermal capacity is sufficient to restart motor Starter monitors learns and retains thermal data from successful starts Phase current imbalance protection Imbalance trip level Imbalance trip delay 5 30 current between any 2 phases 1 20 seconds Overcurrent protection Trip level 100 300 In Electronic shear pin Trip delay 1 20 seconds Load loss protection Undercurrent trip level 10 90 In Undercurrent trip delay 1 60 seconds Coast down Back spin Coast down time 1 60 minutes Lockout timer Starts per hour lockout timer Range 1 6 successful starts per hour Time between starts 1 60 minutes Programmable outputs Type Rating Changeover contacts 5A240 Vac Run indication Programmable At speed indication Programmable Acceleration adjustments Programmable ramp types Voltage or current ramp VR or CR Starting torque 0 100 of line voltage VR or 0 600 of motor In CR Ramp time 1 120 seconds Curr
42. gh air Following paint application parts are baked to produce a hard durable finish The average thickness of the paint film is 50 microns Paint film is uniform in color and free from blisters sags flaking and peeling 4 adequacy of paint finish to inhibit the buildup of rust on ferrous metal materials are periodically tested and evaluated Earthing conductor Copper earthing conductor is continuous and extends from one end of the motor starter switchboard to the other through each vertical section Each section is supplied with an internal earthing conductor of 6 x 50 mm The earthing conductor connections are designed for easy future extension Schneider D Electric Description Enclosures Loss of service continuity cubicle classification Loss of service continuity class LSC The design is based on safe compartment access Several classes of service continuity during maintenance are defined LSC2A Safe access to compartment m with power flow in busbars and the other units m MV cables must be earthed LSC 2B Safe access to compartment m with power flow in busbars and the other units m MV cable in separate compartment m cable of unit under maintenance can remain energized LSC 1 Metal enclosed cubicle not of LSC2 class Motorpact complies with the definition of LSC2A and thus provides a fully safe access to the contactor compartment knowing that maintenance operation m the downstream cables t
43. gramming via communications port Schneider D Electric DE57716 Motorpact range DE57119 Transformer feeder Front view o E R D w a Side view MV compartment 1 Line disconnector 2 Busbars 3 Fuses 4 Contactor 5 Earthing switch 6 Current sensors LPCT LV control cabinet 7 LV protection measurement and control devices Characteristics Transformer feeder Maximum rated voltage 7 2kV Impulse withstand voltage 1 2 50 us peak value 60 kV Power frequency withstand voltage 1 min 20 kV Rated short time withstand current busbars 25kA3s 31 5 KA3s 40 kA3s 50 kA2 s Rated frequency 50 60 Hz Rated operational current 200 400 A Busbars rating 630A 1250A 2500A 3150 A Dimensions H 2300 mm Ww 375 mm D 950 mm Approximate weight 475kg For stand alone applications or when lined up with LF circuit breaker MCset switchgear Schneider D Electric Motorpact range Transformer feeder Composition of the transformer feeder Basic equipment Cubicle Options and accessories 1 enclosure standard IP3X 1 line disconnector 1 electrically held vacuum contactor 3 or 6 HRC fuses 1 set of busbars 1 three core LPCT auxiliary contacts provision for padlocks 1 position contactor indicator window Feeder options a a a o o o E thermal diagnosis system internal
44. han or equal to 95 n average relative humidity over a 1 month period less than or equal to 90 o average vapor pressure over a 24 hour period less than or equal to 2 2 kPa o average vapor pressure over a 1 month period less than or equal to 1 8 kPa Specific operating conditions please consult us Motorpact has been developped to meet the following specific conditions m earthquake withstand application spectrum required m temperature m specific atmosphere m marine applications Storage conditions We recommend that the units are stored in their original packaging in dry conditions sheltered from the sun and rain at a temperature between 25 C and 55 C Standards Motorpact meets IEC standards IEC 60694 Common specifications for high voltage switchgear and controlgear standards IEC 62271 200 AC metal enclosed switchgear and controlgear for rated voltages above 1 kV and up to and including 52 kV ex IEC 60298 IEC 60470 High voltage alternating current contactors and contactor based motorstarters IEC 60282 1 High voltage fuses limiting fuses IEC 62271 102 Alternating current disconnectors and earthing switches ex IEC 60056 IEC 60255 Electrical relays IEC 60044 1 Instrument transformers Part 1 current transformers IEC 60044 2 Instrument transformers Part 2 voltage transformers IEC 60044 8 Instrument transformers Part 8 low power current transducers IEC 61958 High vo
45. imensions in mm d Y 120 Single depth 57 Wi Load compartment Current sensors Phase current transformer Use Alternatively Motorpact can be supplied with a three core phase CT This CT is optimised for Sepam digital relays and will provide performance and protection for the system Accuracy ratings Rated current Single depth 57 mm Double depth 114 mm 30A 1A 2 5 VA 10P5 or 2 5 VAcl 3 30 A 5A 5 VA 10P5 or 5 VAcI 3 50AAA 5 VA 10P5 or 5 VAcI 3 50 A 5A 5 VA 10P5 or 5 VAcl 3 100A 1A 2 5 VA5P5 or 2 5 VAcl 1 100A 5A 5 VA5P5 or 5 VAcl 1 150 A 1A 2 5 VA5P5 or 10 VAcl1 or 2 5 VA cl 0 5 150A 5A 5 VA5P5 or 2 5 VA cl 0 5 200 A 1A 2 5 VA 5P5 or 5 VA cl 0 5 200 A 5A 5 VA5P5 or 2 5 VA cl 0 5 250A 1A 2 5 VA5P5 or 10 VAcl 0 5 250 A 5A 5 VA5P5 or 2 5 VA cl 0 5 300 A 1A 2 5 VA5P5 or 15 VA cl 0 5 300 A 5A 5 VA5P5 or 5 VAcl 0 5 400 A 1A 2 5 VA5P5 or 30 VA cl 0 5 400 A 5A 5 VA5P5 or 10 VA cl 0 5 For all other needs please consult us It is essential to verify specially in case of rating change change in motor power for instance that dimensioning rules are satisfied See page 34 All CT s comply with measuring and protection requirements m single depth 57 mm m double depth 114 mm Note for rated currents lower than 75 A the best solution is to use the LPCT see previous page Location It is located on the CT and load termi
46. ing impulse withstand voltage 1 2 50 us kV peak 60 75 Nominal current and maximum short time withstand current 1 Functional unit with circuit breaker Short time withstand current Ith max KA 3 s 25 25 31 5 31 5 40 40 kA 3 s 50 50 Rated current In max busbar A 4000 4000 Rated current In CB A 1250 1250 2500 2500 3150 3150 4000 2 5 4000 2 5 Functional unit with fuse contactor 3 Short time withstand current Ith max kA 50 4 50 4 6 Rated current In max A 250 200 6 Functional unit with switch fuse DI cubicle Short time withstand current Ith max kA 50 4 50 4 Rated current In max A 200 200 Internal arc withstand maximum value Schneider amp Electric MT20081 MT20080 DE56359 MT20078 MT20082 Motorpact range Incomer Feeder EM 1 4 FER m Switch fuse feeder E38180 E28523 DE57080 D o DE57726 DE57727 DE57728 DE57729 MCset functional unit The MCset range includes 13 functional units based on 4 functions
47. irmation of the information given in this publication LAX This document has been printed on ecological paper Publishing Schneider Electric Industries SAS Design Schneider Electric Industries SAS Printing Imprimerie du Pont de Claix JPF Made in France 11 2007 ART 47999 Schneider Electric Industries SAS All rights reserved
48. is LI Profalux Line disconnector 20 1C Cable earthing switch 1Oor 1C Power factor correction Voltage kV 1 Power kVA see the list page 38 Main fused contactor Removable vacuum contactor Electrically held Basic equipment Mechanically latched Open release 125 Vac 250 Vac 48 Vdc 125 Vdc 250 Vdc MV fuses 50A 63A 80A 100A 125A 160A 200A 250A 2x250A Cable connection Bottom Top 1 cable phase max 240 mm 2 cables phase max 120 mm Blown fuse indicator Options Mechanical operation counter Surge arrestors line side Fused control power transformer CPT Fused voltage transformer Protection metering and control Sepam digital relay see Sepam catalogue T20 L Other Transparent Ready option Local control il eda 2 push buttons 2 indication lights L R switch Sepam 100MI Phase current sensors 5ACT 1ACT LPCT Zero sequence current sensors ZSCT L CSH 120 CSH 200 CSH 280 Sepam options Additional logic I O s module MES114 Analog output module MSA141 Temperature sensor acquisition module MET148 LITT Ct Modbus communication interface ACE949 Schneider BI D Electric Notes E Schneider D Electric Schneider Electric Industries SAS 89 boulevard Franklin Roosevelt F 92506 Rueil Malmaison Cedex Tel 33 0 1 41 29 85 00 www schneider electric com AMTED302059EN As standards specifications and designs change from time to time please ask for conf
49. istics The CPT is protected with two MV fuses and the secondary by a miniature circuit breaker Electrical interlocking is provided in the CPT secondary to disconnect the load of the CPT before opening the disconnector This prevents the possibility of backfeeding the CPT Two types of CPT are available m VRCR 200 VA capable of supplying one contactor and associated auxiliaries m CPT 300 VA capable of supplying all contactors and associated auxiliaries in reduced voltage motor starting applications m CPT 750 VA supplied as standard in RVSS Optional for other applications m CPT 2000 VA optional when additional power is required for downstream components Primary CPT MV fuses are connected to the load side of the main fuses Type Ferraz 5 5 kV 20 mm diameter and 127 mm length 5 5 kV 20 mm diameter and 190 mm length Location CPT is placed under the contactor on the floor of the cubicle The CPT fuses and holders are accessible from the front for easy fuse replacement Power factor correction capacitor Three phase capacitors without internal fuses Possible for FVNR3 cubicle 750 mm width Network voltage V 6600 6300 6000 5500 Capacitor voltage V 6600 6300 6000 5500 Power kvar Dimensions mm Weight H L D b H1 kg 300 347 500 347 190 700 347 190 135 810 347 190 135 630 810 347 190 135 630 These capacitors could be available in stock please consult us Option Temperature cla
50. itch in either the open or closed position Voltage presence indicator system VPIS Use This device enables to check the presence or absence of voltage in the cables It is in accordance with IEC 61958 Location The sensors are located on the cable termination box indicators on the front face Heater resistor Use Heaters are required to prevent condensation when the cubicle is installed in a humid atmosphere or is de energized for extended periods of time Description One heater resistor 50 W 230 Vac The heater resistor is controlled by a miniature circuit breaker The heater is switched off when the contactor is energized Schneider D Electric PE55158 DE57739EN Description 120412014 42 Z b Y i A 180 y L A H1 Y Y Three phase Propivar capacitor Load compartment Optional equipment Control Power Transformer CPT Use To supply power to the closing coil of the contactor two solutions can be used m an external DC or AC auxiliary m an internal supply A control power transformer CPT can be provided and installed into the cubicle The CPT is used to close inrush current and to electrically hold the contactor If the contactor is mechanically latched the CPT is used only to close the contactor Generally a reliable auxiliary supply is utilized in the release circuit of the contactor Character
51. itch of the feeder type E has not been closed first C4 Type To prevent closing the earthing switch on a transformer feeder unless the LV circuit breaker has been opened first and locked in the open or disconnected position and to prevent access to the transformer if the earthing switch of the feeder has not been closed first Padlocks and key interlocks C4 type DE57720 DE55491EN Padlocks Key interlocks Disconnector C O OorO amp C Cable earthing switch C O Oorc Legend Be no key free key Schneider D Electric captive key DE55489 DE55490 Motorpact range Side view Side view Incoming cubicle Transition to MCset functional units Incoming cubicle Composition Basic equipment m 1 enclosure standard IP3X m 1 set of busbars m provision for cable connections o single or three core o bottom or top connection Options m internal arc withstand m IP4X or IPX1 enclosure m encapsulated busbars Characteristics Incoming cubicle 500 750 Maximum rated voltage 7 2kV 7 2 kV Impulse withstand voltage 1 2 50 us peak value 60 kV 60 kV Power frequency withstand voltage 1 min 20 kV 20 kV Busbars ratings 630A 630A 1250A 1250A 2500A 2500A 3150
52. itching of groups of settings m 2 m 2 C Annunciation 30 L Logic equation editor Additional modules 8temperature sensor inputs MET148 2 module n o n9 1 low level analog output MSA141 module Hn Hn Hn Logic inputs outputs o o o MES114 MES114E MES114F 101 40 module Communication interface o o o ACE949 2 ACE959 ACE937 ACE969TP or ACE969FO Schneider D Electric Description LV control cabinet Sepam protection system Motor Motor Protection ANSI code M81 M87 M88 Metering M81 M87 M88 Phase overcurrent 1 50 51 8 8 8 Phase current I1 12 I3 RMS m m m Earth fault Sensitive earth fault 1 50N 51N 8 8 8 Measured residual current IO calculated 102 m m z SUIS Demand current 11 12 I3 Breaker failure 50BF 1 1 1 Negative sequence unbalance 46 2 2 2 Peak demand current IM1 IM2 IMS Thermal overload for machines 1 49RMS 2 2 2 Measured residual current l O Two winding transformer differential 87T 1 Voltage U21 U32 U13 V1 V2 V3 Machine differential 87M 1 Residual voltage VO Directional earth fault 1 67N 67NC 2 2 2 Positive sequence voltage Vd rotation direction Directional active overpower 32P 2 2 2 Negative sequence voltage Vi Directional reactive overpower
53. ith optional MET148 2 temperature input modules 4 With optional MCS025 synchro check module 5 With ACE949 2 ACE959 ACE937 ACE969TP or ACE969FO communication interface P Schneider LF Electric Description PE55173 LV control cabinet Sepam protection system Sepam series 20 series 40 and series 80 modularity Sepam base unit Available with 3 User Machine Interface UMI levels m basic UMI with signal lamps m advanced UMI with keypad and graphic LCD display This advanced UMI can be remotely located and its screens can be customised in all languages m mimic based UMI for Sepam series 80 This mimic based UMI offers the local switchgear control H Logic 1 0 module The 4 outputs on the Sepam series 20 and series 40 base unit may be completed by adding an MES114 module with 10 input 4 output on the back of the base unit The 5 output relays included on the Sepam series 80 base unit may be extended by adding 1 2 or 3MES120 modules with 14 DC logic inputs and 6 outputs relays 1 control relay output and 5 indication relay outputs E ACE communication interfaces With Modbus communication Sepam series 20 series 40 or series 80 units can be connected to a monitoring and control system equipped with a master Modbus communication channel To connect Sepam series 20 40 or 80 to a RS485 network an interface module is required m ACE949 2 interface for connection to a 2 wire RS485 network m ACE95S interface fo
54. l options m Sepam series 20 series 40 or series 80 protection relay m Transparent Ready option m 1 Sepam 100 MI control and indication W local remote switch not needed in case of Sepam 100MI Sepam accessories m additional logic I O module m Modbus communication interface m motor temperature sensor acquisition module m analog output module Padlocks and key interlocks Padlocks Key interlocks Disconnector C O OorO amp C Cable earthing switch C O OorC By pass contactor O Operation and interlocking Main cubicle see FVNR cubicle SoftStart module The disconnector mechanism in the main cubicle incorporates the necessary interlocks to prevent access to the load compartment with the contactor energized The disconnector mechanism is key interlocked with the SoftStart module to prevent access to the medium voltage components m SoftStart m by pass contactor m communication board On SoftStart module the doors are interlocked to prevent locking the unit without all of them being closed Power to the SoftStart module comes from the adjacent main cubicle When the motor has started the by pass contactor is closed The by pass contactor can be opened to provide a soft deceleration of the motor Schneider D Electric DE57713EN DE57714EN DE57715EN Motorpact range Closed loop current Torque ramp M Current limit N torque Start Full speed I A Pump running Stop c
55. ltage prefabricated switchgear and controlgear assemblies Voltage presence indicating systems IEC 60076 11 Auxiliary power transformers Other specifications IBC 2000 International Building Code Seismic qualification testing of nonstructural components Schneider s D Electric PE55541 E74225 MT20073 Motorpact range Specific applications Marine application Derived from standard Motorpact a Marine version has been developed to meet specific conditions when used on ships offshore platforms m vibrations shocks W steepness m etc Motorpact is particularly adapted and its characteristics meet Marine requirements m compartmented cubicle LSC2A type m front access m withdrawable circuit breaker m Sepam protection and control chain m internal arc withstand m thermal diagnosis Certifications Motorpact Marine is approved by m Lloyds Register LR m Det Norske Veritas DNV m Bureau Veritas BV m Germanischer Lloyd GL m American Bureau of Shipping ABS Schneider D Electric American Bureau of Shipping DE57075EN DE57076EN Motorpact range Tmax Resistive torque DE57701EN Motorpact range FVNR full voltage non reversing asynchronous motor starter Full Voltage Non Reversing motor starter Asimple and reliable solution that provides the maximum starting torque allowed by the motor suitable for most application
56. m fuse rating 2x315A Breaking capacity 50 kA Motor application Quantity and rated current of the fuses Select from the table page 49 It is essential to verify specially in case of rating change change in motor power for instance that dimensioning rules are satisfied Dimensioning rules Accumulation of starting sequences The check point current 2 x Id must be lower than the minimum clearing current I3 of the fuse Saturation of sensors m in order to be sure that fault currents will be seen by the fuses the accuracy limit current of the sensors must be higher than the minimum clearing current I3 of the fuse m In order to insure the correct functioning of the thermal image protection of the Sepam relay the sensor rating must be lower than 3 times the normal motor current Corollary do not over rate the sensors Transformer application Quantity and rated current of the fuses See table page 49 Schneider Es D Electric DE57734EN PE55152 Description 55 bhd 3 RJ45 plugs a 120 Z Single depth 57 DE57735 Load compartment Current sensors CLV1 low power current transducer LPCT The LPCT is the standard current sensor for Motorpact It consists of a three core voltage current sensor which complies with the IEC 60044 8 standard One sensor covers all the applications Use The LPCT is compatible with Sepam series 20 series 40
57. mm 950 mm Approximate weight 475kg 650 kg For stand alone applications or when lined up with LF circuit breaker MCset switchgear Schneider D Electric Motorpact range Composition of FVNR motor starter Basic equipment Cubicle m 1 enclosure standard IP3X m 1 line disconnector 1 electrically held vacuum contactor 3 or 6 HRC fuses 1 set of busbars 1 three core LPCT auxiliary contacts provision for padlocks 1 position contactor indicator window Options and accessories Starter options m thermal diagnosis system m internal arc withstand m cable earthing switch including o mechanical position indicator o auxiliary contacts O padlock provision m blown fuse indicator m P4X or IPX1 enclosure m one fused 3 phase voltage transformer m power factor correction capacitor FVNR3 FVNR full voltage non reversing asynchronous motor starter m mechanically latched vacuum contactor includes release coil m 1 disconnector load compartment back light m key interlocks m encapsulated busbars m 1 fused control power transformer CPT m additional CT s or ZSCT zero sequence current transformer m 1 set of 3 surge arrestors m voltage presence indicator system VPIS m heating resistor m mechanical operation counter m running time meter Low voltage control m 1 Sepam M20 motor protection relay m Start amp Stop pushbuttons m Run amp Stopped pilot lights Control options m Sepam series 40 or
58. nal assembly providing the required support and ensuring all dielectric withstand Zero sequence cu rrent transformer Three types of zero sequence current transformer ZSCT may be used Internally mounted zero sequence CT Use The internally mounted zero sequence current transformer is used for earth fault protection when the expected value of the fault current is higher than 50 A direct earthing system Location and size The internally mounted zero sequence current transformer is installed with the LPCT or CT Its depth is a single depth 57 mm Internally mounted CSH 280 core balance CT Use CSH core balance CTs provide more sensitive protection by direct measurement of earth fault currents Specifically designed for the Sepam range they can be directly connected to the Sepam residual current input Location and size The internally mounted CSH 280 core balance CT is installed with the LPCT or CT Its depth is a single depth 57 mm Externally mounted CSH 120 and CSH 200 core balance CTs Use Same use as CSH 280 They are installed in the cable tray under the cubicle around the cable m CSH 120 120 mm internal diameter core balance CT m CSH 200 200 mm internal diameter core balance CT A hole would need to be drilled on site to pass the wires Schneider g D Electric DE57738 Description Load compartment Cable connection Cable connection Capability m Upto 2x 120 mm or 1 x 240 mm single or three
59. nder the LV control cabinet Description The busbars is mounted in the horizontal position Barriers are provided to isolate the compartment from the rest of the individual vertical section Busbars rated current When the cubicles are part of a main switchboard the busbars rated current is of the same current rating as the main switchboard When Motorpact is used as stand alone equipment the current rating of the busbars must be greater than the total of the individual currents of each motor starter Rating A Short time withstand current 3s 2s Up to 31 5 kA 40 kA 50 kA 630 u u 1250 u E 2500 u u u 3150 u u E For stand alone applications or when lined up with LF circuit breaker MCset switchgear Design of the busbars The busbars is connected directly on the disconnector terminals The connection to the main circuit breaker switchboard is done through a transition cubicle and solid copper busbars links Option Encapsulated busbars Access Front access only For periodic busbars maintenance access is provided through a removable access cover at the bottom of the LV control cabinet Front and rear access If rear access is available busbars maintenance can also be performed from the rear of the cubicle by removing the enclosure cover and the busbars access barrier Schneider D Electric DE57732 PE55150 Description Load compartment Vacuum contactor The vacuum contactor is used
60. ns Mechanical operation counter Protection metering and control optional Sepam digital relay see Sepam catalogue Transparent Ready option Local control 2 push buttons 2 indication lights L R switch Sepam 100MI Phase current sensors 5ACT 1ACT LPCT Zero sequence current sensors ZSCT L CSH 120 CSH 200 CSH 280 Sepam options Additional logic I O s module Analog output module Temperature sensor acquisition module MET148 Modbus communication interface ACE949 MES114 MSA141 Schneider D Electric Order form Only one ofthe boxes ticked X orfilled Joy the needed value have to be considered between each horizontal line Green box X corresponds to none priced functions Transformer feeder Basic unit cubicle Quantity 1 Rated voltage 3 6KV z2kV Rated short time withstand current 25kA3s B 40kA3s 50kA2s Busbar Bare Encapsulated Rated current esoA 1250A 2500A 3150A Rated operational current 200A 400A Degree of protection housing IP3X L IP4X IPX1 Maintenance free disconnector Options Internal arc withstand 25 kA 1 s 40 kA 0 5 s 50 kA 0 25 s Ceiling height lt 4m gt 4m Thermal diagnosis system Cable earthing switch Voltage presence indicator system VPIS Heating element Back light disconnector contacts amp load compartment Key interlockings Ron
61. nter Surge arrestors line side Fused control power transformer CPT Fused voltage transformer Auto transformer module 1 auto transformer 1 run vacuum contactor electrically held 1 start vacuum contactor electrically held Frequency Starting current Starting time motor Starting time motor auto transformer Number of starts hour Number of consecutive starts Options Mechanical operation counter Contactor position indication windows Protection metering and control Sepam digital relay see Sepam catalogue Transparent Ready option Local control mal Other A co ual LL 2 push buttons 2 indication lights L R switch Sepam 100MI Phase current sensors 5ACT 1ACT LPCT Zero sequence current sensors ZSCT O CSH 120 CSH 200 CSH 280 Sepam options Additional logic I O s module MES114 Analog output module MSA141 Temperature sensor acquisition module MET148 Modbus communication interface ACE949 Schneider D Electric Order form Only one ofthe boxes ticked X orfiled Joy the needed value have to be considered between each horizontal line Green box X corresponds to none priced functions RVSS SoftStart asynchronous motor starter Basic unit cubicle Rated voltage Quantity 3 6KV z2kV Rated short time withstand current Busbar Bare Rated current esoA 25kA3s 31 5
62. o feed motor are not energized and can be earthed m the upstream fuse contacts are earthed and segregated from the busbars through the disconnector Partition Class or M Class defining whether metallic or non metallic material for separation to live parts is used Partition Class PM All partitions and shutters of safe access compartment shall be metallic with some current carrying capacity Partition Class PI m Partitions or shutters may be partially or totally of insulating material m Ashutter can be defined as moving contact of a disconnector to engage fixed contacts to a position where it becomes a part of the enclosure or partition shielding the fixed contacts Motorpact complies with Partition Class PI earthing switches being shutters for the line and load sides of the equipment Internal arc withstand classification IAC AFLR optional Motorpact internal arc withstand is designed to protect operators in the case of an internal arc and is Internal Arc Classified IAC Successfully tested in conformity with IEC 60271 200 standard ex IEC 60298 appendix A Accessibility is Type A permitting access from the Front side Lateral side and Rear side AFLR Motorpact is designed to offer a high level of safety by minimizing the effects of internal arcing by m using metallic flaps on top of the equipment to limit overpressure in the compartments and to direct the hot gases to the outside minimizing operator hazards
63. ocal remote control device Local remote control device Use Local remote control of the contactor Characteristics Two possibilities m integrated Sepam 100MI solution m basic solution Sepam 100 MI Sepam 100 MI is a local breaking device control and signalling module The front of Sepam 100 MI includes the following mimic m red and green indicator units used to make up mimic diagrams representing the cubicle electrical diagram m ared vertical bar representing device closed m a green horizontal bar representing device open m alocal or remote control selector switch CLR m abreaking device open control pushbutton KD2 active in local or remote mode m abreaking device close control pushbutton KD1 active only in local position Sepam 100 MI can be installed either separately or combined Sepam series 20 series 40 or series 80 Location It is mounted on the LV control cabinet door Schneider D Electric DE57742 Description Auto transformer compartment Auto transformer module Use This module is always erected on the right side of the main cubicle to compose the auto transformer starter Selection Two widths of modules are available m 1125 mm wide for motor up to 440 kW m 1500 mm wide for motor lower than 3800 kW Structure The main busbars goes through the module in a segregated comp
64. ommand Pump output affected Pump off Pump flex decel Torque eee o 3selectable curves w 2to 8time torque oint per curve 9 p p Time gt Torque Check valve closes z Process machinery m Jog function can be used to apply just enough voltage torque to rotate the motor shaft without accelerating to full speed m Dual ramps allow for different load conditions and ramping requirements o programmable overload class 5 30 D as an example class 30 for starting and class 10 for running Time DE57114EN RVSS SoftStart asynchronous motor starter Pumps fans blowers and conveyors Closed Loop Torque uses PID proportional integral derivative algorithms ideal for deep well pumps ideal for systems where loads change from start to start Linear Speed Ramping achieved by adding tachometer feedback signal from the motor nmuounNm Custom acceleration curves m Programmed to match pump and hydraulic conditions m Upto eight time and torque points for smooth acceleration of pumps without surges or undue motor thermal stress m Three selectable and programmable custom curves for changing load pump conditions or different processes Pump decel m Gradual reduction in output torque of the pump motor when a stop signal is initiated m When the motor output reaches a point where the check valve can be safely and gently closed the decel circuit automatically turns off m Eliminat
65. otor starter is composed of a main cubicle identical to FVNR unit and SoftStart module Basic equipment Main cubicle m 1 enclosure standard IP3X 1 line disconnector 1 electrically held vacuum contactor 3 or 6 HRC fuses 1 set of busbars auxiliary contacts provision for padlocks 1 position contactor indicator window 1 voltage transformer 1 fused control power transformer 750 VA Options and accessories Module options m thermal diagnosis system m internal arc withstand m cable earthing switch including o mechanical position indicator o auxiliary contacts O padlock provision m 1three core LPCT m blown fuse indicator m P4X or IPX1 enclosure m power factor correction capacitor FVNR3 SoftStart module m 1 enclosure standard IP3X m 1 electrically held vacuum contactor by pass contactor m 1 SCR power module m voltage measurement m 1 set of current sensors m 1 microprocessor based protection and control system m motor temperature sensor inputs option m mechanically latched vacuum contactor includes release coil m 1 disconnector load compartment back light m key interlocks m encapsulated busbars m additional CT s or ZSCT zero sequence current transformer m 1 set of 3 surge arrestors m voltage presence indicator system VPIS m heating resistor m mechanical operation counter m running time meter Low voltage control m Start amp Stop pushbuttons m Run amp Stopped pilot lights Contro
66. r m 1 set of 3 surge arrestors m voltage presence indicator system VPIS m heating resistor m mechanical operation counter m running time meter m contactor position indicator windows for auto transformer cubicle Low voltage control m 1 Sepam M41 protection relay including starting automation m Start amp Stop pushbuttons m Run amp Stopped pilot lights Control options W Sepam series 40 or series 80 protection relay m Transparent Ready option m 1 Sepam 100 MI control and indication W local remote switch not needed in case of Sepam 100MI Sepam accessories m additional logic I O module m Modbus communication interface m motor temperature sensor acquisition module m analog output module Padlocks and key interlocks Padlocks Key interlocks Disconnector C O OorO amp C Cable earthing switch C O Oor C Run contactor O Start contactor C Operation and interlocking Main cubicle see FVNR cubicle Auto transformer module The disconnector mechanism in the main cubicle incorporates the necessary interlocks to prevent access to the load compartment with the contactor energized The disconnector mechanism is key interlocked with the auto transformer module to prevent access to the medium voltage components m auto transformer m start contactor m run contactor The start and run contactors are mechanically and electrically interlocked to prevent simultaneous closure On a
67. r connection to a 4 wire RS485 network m ACE9Q37 interface for connection to a fiber optic network m ACE969 interface for connection to 2 independent communication networks a 2 wire RS485 network or a fiber optic network and a 2 wire RS485 network El MSA141 analog output module The MSA141 module converts one of the Sepam series 20 series 40 and series 80 measurements into a 0 10 mA 4 20 mA or 0 20 mA analog signal H MET148 2 temperature sensor module Temperature measurement e g in transformer or motor windings is used by the following protection functions m thermal overload to take into account the ambient temperature mtemperature monitoring With the MET148 2 module 8 Pt100 Ni100 or Ni120 temperature sensors can be connected Dnm SFT software tools m SFT2841 setting and operating Sepam software The control and monitoring functions can be customised by the use of the SFT2841 software m SFT2826 disturbance recording data display software Synchro check module This optional module available only on Sepam series 80 base unit checks the voltages upstream and downstream of a circuit breaker to ensure safe closing BH Parameter and protection settings saved on removable memory cartridge Sepam series 80 has a removable memory cartridge to simplify maintenance operations in order to fasten return to service following replacement Schneider D Electric PE60116 Description LV control cabinet L
68. r double fuses The disconnector mechanism incorporates the necessary interlocks to prevent access to the multifunctional compartment with the contactor energized Interlocking requires 3 hands to defeat any function The disconnector operating mechanism has a pad lockable feature for both the open and closed positions Rating 400 Amperes Options m Key interlocks Two key interlocks are available D one with a removable key when the disconnector is locked in the open position o one with a removable key when the disconnector is locked in the open position or with a removable key when the disconnector is in closed position m Disconnector position contact back light Auxiliary contacts m 1 set of 4 form C auxiliary contacts is available for external uses n 1 inthe earthed position disconnector open Hn 1 inthe connected position disconnector closed m 1 set of 4 form C auxiliary contacts is available as an option Characteristics Operating voltage Minimum 48 V Maximum 480 V Rated current 10A Breaking capacity Vdc 60 W L R 150 ms Vac 700 VA power factor 0 35 Common point changeover type contacts Schneider A D Electric DE57731 PE55146 Description Phasing relationship Busbars compartment Busbars Location The busbars is mounted directly on the disconnector u
69. s Since it draws high inrush current typically 60096 of full load motor current it can be used when there are no motor machine or network restrictions For the following applications reduced voltage starting should be used m when maximum starting torque can result in a sudden start of the machine and can cause undesirable mechanical constraints m when high inrush current during starting can cause the system line voltage to drop to unacceptable levels and result in potential equipment damage or can cause network instability DE57702EN RVAT auto transformer asynchronous motor starter Reduced Voltage Auto Transformer motor starter Itis used when the network cannot withstand high inrush current An auto transformer motor starter provides reduced voltage to the motor terminals during starting with a three phase auto transformer It reduces the line current and provides the right starting torque For synchronous motors please consult us For selection of motor starter type see the Application guide ref AMTED303042EN Schneider ur D Electric DE57077EN Motorpact range Motorpact range RVSS SoftStart asynchronous motor starter Current limitatic 8 T In DE5770 Tmax UM T varies fas Un 00000000009999 Resistive torque Reduced Voltage SoftStart motor starter SoftStart motor starter provides smooth stepless acceleration and deceleration reg
70. s an adapted protection system Motorpact unit Standard Optional FVNR Sepam M20 Sepam M40 or M80 RVAT Sepam M41 Sepam M40 or M80 RVSS SoftStart relay Sepam M40 or M80 Transformer feeder Sepam T20 Sepam T40 or T80 For any other types of Sepam relay please consult us Schneider D Electric Description Sepam functions The main functions performed by the Sepam units proposed as basic equipment of Motorpact units are summarized in the table opposite For other details please refer to the Sepam catalogue The figures indicate the number of relays available for each protection function LV control cabinet Sepam protection system Transformer Motor Protection ANSI code T20 M20 M41 Phase overcurrent 50 51 4 4 4 Earth fault Sensitive earth fault 50N 51N 4 4 4 50G 51G Breaker failure 50BF 1 Negative sequence unbalance 46 1 1 2 Directional earth fault 67N 67NC 2 Directional active overpower 32P 1 Directional reactive overpower 32Q 40 1 Thermal overload 49RMS 2 2 2 Phase undercurrent 37 1 1 Excessive starting time locked rotor 48 51LR 14 1 1 Starts per hour 66 1 1 Positive sequence undervoltage 27D 2 Remanent undervoltage 27R 1 Undervoltage 4 27 278 2 Overvoltage 59 2 Neutral voltage displacement 59N 2 Negative sequence overvoltage 47 1 Overfrequency 81H
71. series 80 protection relay m Transparent Ready option m 1 Sepam 100 MI control and indication m local remote switch not needed in case of Sepam 100MI Sepam accessories m additional logic I O module m Modbus communication interface m motor temperature sensor acquisition module m analog output module Padlocks and key interlocks Padlocks Key interlocks Disconnector C O OorO amp C Cable earthing switch C O OorC Operation and interlocking The disconnector mechanism incorporates the necessary interlocks mechanical and or electrical to prevent access to the load compartment with the contactor energized All interlocking requires three simultaneous operations to defeat any function without the destruction of parts Interlocking W prevents disconnector closure normal operations if o the contactor is closed O the load compartment door is open o the contactor is not in the fully connected position o the cable earthing switch is closed if so equipped m prevents closure of the contactor if the Blown Fuse Indication system has not been reset m prevents unlatching the load compartment door when the disconnector is closed W prevents access to the contactor cable compartment unless o the contactor is open and the disconnector is earthed o the earthing switch is closed if so equipped Provision to operate the earthing switch with door open for cable testing is provided o the operating han
72. ss 25 55 C Clamping for 1 cable connection Clamping for 2 cables connection Schneider D Electric PE55160 Description Load compartment Optional equipment Thermal diagnosis system Use To reduce maintenance costs in MV substations It continuously monitors temperature rise using optical fibres and sensors installed atthe heart of the sensitive areas The sensors are located on cable connections and on top MV fuse holders Presentation Thermal diagnosis is based on the principle of temperature measurement of energized circuits By using optical fibres the system doesn t introduce any risks in terms of insulation It provides m permanent monitoring of the temperature rise in power circuits at the connections m tripping of a pre alarm then an alarm by activating dry contact outputs m indication of the zone and circuit involved The standard solution is composed of the MDT module and two probes as described hereunder Probes CFO733 The optical fibre probes are factory built assemblies comprising W 3 sensors attached to the power circuit m the optical connections m aconnector linked to the module This connector incorporates the opto electrical conversion unit thus eliminating any optical connections when assembling MDT107 module The MDT107 electronic module is mounted in the low voltage compartment of the cubicle It provides the following functions m monitoring of temperature
73. tching acknowledgement 86 Phase displacement p2 p3 m Annunciation 30 Disturbance recording Switching of groups of settings Thermal capacity used Li a u Adaptation using logic equations Remaining operating time before overload tripping Logipam programming Ladder language 5 5 Waiting time after overload tripping a Running hours counter operating time n Starting current and time Start inhibit time Number of starts before inhibition Unbalance ratio negative sequence current l i Differential current Idiff1 Idiff2 Idiff3 1 Through current It1 It2 It3 Current phase displacement 0 Apparent positive sequence impedance Zd 1 1 Apparent phase to phase impedances Z21 Z32 Z13 Switchgear diagnosis ANSI code CT VT supervision 60 60FL Trip circuit supervision 2 74 n n n Auxiliary power supply monitoring B 1 Cumulative breaking current Number of operations operating time charging time o o n number of racking out operations 2 Modbus communication IEC 60 870 5 103 or DNP3 Measurement readout 5 n n n Remote indication and time tagging of events 9 n Remote control orders 5 The figures indicate the number of relays available for each protection function m standard n options 1 Protection functions with 2 groups of settings 2 According to parameter setting and optional MES120 input output modules 3 W
74. termine the fuse rating Service Transformer rating kVA voltage kV 25 50 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3 125 125 125 125 125 125 125 125 125 125 160 200 250 2x200 2x250 3 3 125 125 125 125 125 125 125 125 125 125 160 200 250 2x200 2x250 5 125 125 125 125 125 125 125 125 125 125 125 125 160 200 250 2x200 2x250 5 5 125 125 125 125 125 125 125 125 125 125 125 125 160 160 250 2x200 2x250 6 125 125 125 125 125 125 125 125 125 125 125 125 125 160 200 250 2x200 6 6 125 125 125 125 125 125 125 125 125 125 125 125 125 160 200 250 2x200 For more information see Fuses catalogue ref AC0479EN ART 72747 Schneider D Electric w n E iB u a Installation Implementation examples Lined up switchboard
75. trol El d Motorpact Motor Control Centre can be easily d m integrated into an existing monitoring and control system communication of Sepam digital relay or PowerMeter Circuit Monitor m metering device through a standard protocol Modbus m integrated into a SMS Powerl ogic electrical installation monitoring system A B 0 a re Thermal diagnosis system Specially designed for Schneider Electric MV equipment this system continuously monitors the temperature rise using optical fibres and sensors installed at the heart of the sensitive areas Thermal diagnosis system reduces the probability of failure and reduces maintenance time Es Schneider D Electric PE55137 DE57492EN PE55138 PE55139 PE55140 Motorpact general presentation HILL im t Ready TCP IP over Ethernet Motorpact Transparent Ready Motorpact Transparent Ready option Motorpact motor control centres integrate Web technologies so that you can find out information about your electrical installation as easy as opening a Web page All you need is a standard Web browser and a PC connected to your local area network Simple choice Asimple choice between TRe 1 and TRe 2 service levels allows you to easily order your Transparent Ready Motorpact switchboard A customised level is also available Transparent Ready Motorpact control centre comes equipped with a web serv
76. uto transformer modules the doors are interlocked to prevent closing the disconnector without all of them being closed Power to the Start and Run contactors comes from the adjacent main cubicle The power from the Run contactor is then routed back to the load terminal box in the main cubicle The auto transformer is of a roll in design such that it can be handled separately making it easier to handle position and install the cubicle The module is available with a main bus compartment to allow easy extension to the switchboard Extension may be an FVNR RVSS or another RVAT unit Schneider D Electric DE57079 DE57709EN Motorpact range Front view Main cubicle SoftStart module BEE 4 w2 DE57118 RVSS SoftStart asynchronous motor starter Main cubicle SoftStart module A DE57712 Characteristics Rated current Dimensions H Side view SoftStart module l 1 By pass vacuum contactor 2 Busbars 3 SoftStart power stack 200 400 A 2300 mm w1 W2 with capacitor module 1125 mm 1500 mm D 950 mm Approximate weight 1095 kg Schneider D Electric Motorpact range Composition of RVSS motor starter RVSS SoftStart asynchronous motor starter The RVSS m
Download Pdf Manuals
Related Search
Related Contents
PT-EP11 - Olympus 取扱説明書・保証書 Instrucciones de uso 050914 7085454 CS+ V3.02.00 Integrated Development Environment User`s Manual MANUAL DEL USUARIO Serie TX200/ TX300/ TX600 Origin Storage 1TB TLC SATA 2.5" Frostair 1500 Installation manual R&S®BTC Broadcast Test Center Copyright © All rights reserved.
Failed to retrieve file