Home

Addenda No. 2-- 13WG02 Equipment Building

image

Contents

1. Figure 1 Approximate Project Site Location At the time of the subsurface exploration the project site was fairly level with an estimated grade differential on the order of 1 to 2 feet across the proposed project area Structural loads were not provided however we assumed that the proposed building will be lightly loaded with maximum column loads and bearing wall loads in the range of 20 to 40 kips and 2 to 3 kips per linear foot klf respectively Proposed grading plans were not provided to us at the time of preparing this proposal however for the purpose of this proposal we assumed that maximum cut and fill depths of less than 2 feet will be required to achieve design grades within the proposed building area 2 0 SCOPE OF SERVICES The purpose of the geotechnical exploration was to determine general subsurface conditions at specific boring locations and to gather data on which to base a geotechnical evaluation with respect to the proposed construction The information gathered from the exploration was evaluated to determine suitable foundation alternatives for the proposed building The information was also evaluated to help determine if any special building pad preparation procedures will be required during the earthwork phase of the project The work included soil test borings laboratory analysis and geotechnical evaluation appropriate to address the geotechnical aspects of the proposed construction The results of our exploration
2. Sites for stock piles shall be graded and cleaned prior to storing materials Aggregate from different sources shall be stored in separate stock piles Care shall be taken to prevent segregation material which becomes segregated to the extent that it no longer satisfies the grading requirements shall be combined to satisfy such requirements before being used in concrete C Water 1 Water used in mixing concrete shall be clean clear and free from deleterious amounts of acids alkalis oil salt organic materials or any other substances injurious to the finished concrete Water from City water system may be accepted without being tested Water from other sourses shall not be used until tested and approved Testing of water shall be in accordance with AASHTO Method T 26 D Admixtures 1 2 Air entraining admixtures shall conform to ASTM Specifications C 260 Set control admixture Set controlling agents shall conform to ASTM C 494 as follows Adopted 2 21 2013 2200 2 of 16 Construction Standards Concrete CONSTRUCTION STANDARDS 2200 CONCRETE a Type A Water Reducing b Type B Retarding c Type C Accelerating d Type D Water Reducing and Retarding e Type E Water Reducing and Accelerating 3 Other admixtures Other admixtures unless specifically called for shall be used only with the written approval of the City of Stillwater and shall be used in accordance with the manufacturer s instructions and recommend
3. The west bays will be used to store large pieces of equipment The list of equipment not all inclusive that shall be stored in the west 3 bays are as follows Description of Large Equipment Weight LBS Track Loader 34 000 Tractor 10 373 Backhoe 16 000 Project Scope 2 1 Bidder shall be fully responsible for the turnkey project that requires the provision of all 2 2 2 3 engineering services needed for the field investigation including field survey and geotechnical investigation needed for the proper design of the reinforced concrete slab and required foundation for the metal storage building geotechnical report provided by City of Stillwater see addenda Bidder is responsible for designing supplying and installation of all electrical power supply and cabling for the needed lighting interior and exterior operation of the motor operated roll up doors gas fired heaters ventilation and exhaust fans with louvers and 110 220V outlet receptacles All electrical design supply and installation shall comply with current electrical codes to include NEC2011 and City of Stillwater Standards Bidder is responsible for designing and installation of steel piping te supph natural eas froman adjacent faciity te for the proposed metal building The City of Stillwater will provide gas piping to the building site Natural gas radiant heater will be Dayton brand The three equipment bays will use two 2 each model 7D841
4. not splatter forms and reinforcing steel 22 Finish of concrete surfaces All surfaces exposed to view shall be free from conspicuous lines affects or other irregularities caused by defects in the forms If for any reason this requirement is not met or if there are any conspicuous honeycombs the City of Stillwater may require a correction of the defects by rubbing with carborundum bricks and water until a satisfactory finish is obtained Immediately after removing the forms all wires or other exposed metal shall be cut back of the concrete surface and the depressions thus made and all honeycomb and other defects shall be painted with mortar and then rubbed smooth If the City of Stillwater deems any honey comb or other defect to require such treatment the defective concrete shall be cut out to a depth sufficient to expose the reinforcement and to afford a key for the concrete replacing the cut out 23 Curing concrete a Exposed surfaces of concrete shall be protected by accepted methods from premature drying for a period of at least seven 7 days Curing compounds when accepted by the City of Stillwater shall be applied according to the manufacturer s recommendations and shall not be used on any surface against which additional concrete is to be bonded nor on surfaces which will be painted In dry hot weather forms shall be removed as early as practicable and curing started immediately The City of Stillwater may require the frequent wettin
5. square intersections d The Contractor shall use extra studs walers and bracing to prevent bowing of forms between studs and to avoid bowed appearance in concrete The Contractor shall not use narrow strips of form material which will produce a bow e The Contractor shall assemble forms to be readily removed without damage to exposed concrete surfaces f The Contractor shall form molding shapes recesses and projections with smooth finish materials and install forms with sealed joints to prevent displacement 5 Corner treatment a The Contractor shall form exposed corners to produce square smooth solid unbroken lines except as other wise shown b The Contractor shall form chamfers with 3 4 x 3 4 strips unless otherwise shown accurately formed and surfaced to produce uniformly straight lines and tight edge joints The Contractor shall extend terminal edges to required limit and miter chamfer strips at changes in direction c Unexposed corners may be formed either square or chamfered 6 Control joints a Concrete shall be placed continuously so that the unit will be monolithic in construction Fresh concrete may be placed against adjoining units provided the set concrete is sufficiently hard not to be injured thereby Joints not indicated shall be made and located to least impair strength and appearance of the structure Concrete for walls shall be in place at least 2 hours before concreting beams girders or slabs thereon
6. 2 5 9 A non insulated Aninsulated full height floor to ceiling deck roof interior wall shall be constructed to separate the parts storage area from the equipment storage area The wall will be built with 20 gauge or better cold rolled steel framing and sheathed on both sides with 24 gauge or better steel siding The interior wall aad ceitng of the parts storage area shall be insulatedand lined with A B grade plywood eight 8 feet high 2 5 10 All exterior walls to the facility Fre interiorwattand ceiting of the equipment bay areas andthe cleanroom shall be insulated using closed cell rigid polyurethane spray foam insulation applied to the inside of the walls te previde aminimum insulation factor of R 49 Foam will be Gaco Western WallFoam System 183 or approved equal applied at two 2 inches thick Ceiling will be insulated using 3 rigid R 10 reinforced backing insulation 2 5 11 As shown in Attachment 1 the bidder shall construct a twenty 20 twelve 42 feet wide reinforced concrete approach slab for the full length of the south side of the building and further narrows to 4 feet wide at the two entrance doors east and west doors The slab shall be designed and constructed to support the load imposed by heavy equipment being moved in out of the building Bidders shall ensure as part of the site preparation and grading all roof run off snow melt and storm water runoff will be directed away from the new building 2 5 12 Bi
7. a qualified representative should observe the proofrolling operations Considering that the onsite materials encountered in the borings are mostly comprised of fine grained silty clayey sand and depending on the moisture contents at the time of construction proofrolling may reduce the stability of the subgrade soils If this occurs the general procedures should be modified such as deleting or reducing the proofrolling or stabilizing the soils Any soft very loose unstable or otherwise unsuitable soils identified during the proofrolling or subgrade evaluation process should be moisture conditioned undercut to suitable material or stabilized in place prior to fill placement or new construction Information regarding suitable stabilization methods can be provided during construction based on actual conditions encountered 7 4 STRUCTURAL FILL We recommend that the structural fill at the site be composed of material with a maximum dry density in excess of 100 pounds per cubic foot pef Plasticity Index PI less than 20 and Liquid Limit LL less than 45 All structural fill materials should be free of any organics should not contain rock fragments greater than 3 inches in any dimension and should be properly moisture conditioned prior to placement Any fill to be placed at the site should be approved by the geotechnical engineer Based upon the soils encountered in the borings the onsite materials appear suitable for use as structur
8. and our knowledge of the geologic conditions of the site we recommend that the site be classified as Site Class C Our subsurface exploration extended to a maximum depth of about 14 feet hence the seismic site classification should be re evaluated in the event subsurface information is made available to a depth of 100 feet 15 11 0 CONSTRUCTION MONITORING The recommendations presented in this report are based on information obtained from two 2 soil test boring locations Field verification of site conditions is an essential part of the services provided by the geotechnical consultant In order to confirm our recommendations it will be necessary for Building amp Earth personnel to make periodic visits to the site during site grading We can prepare a proposal for construction monitoring services based on the construction schedule and your risk management preferences Typical construction monitoring services are listed below e Periodic observations and consultations by a member of our engineering staff during site grading e Field density tests during structural fill placement e Observation and verification of the bearing surfaces exposed after foundation excavation e Molding and testing of concrete cylinders e Structural steel inspections 16 12 0 CLOSING This report was prepared for use by City of Stillwater Water Utilities for specific application to the subject project The information in this report is not transfer
9. clean cut corners with edge grain of plywood not exposed as form for concrete Provide openings in forms to accommodate other work including mechanical and electrical work Accurately place and securely support items required to be built into the form 3 Falsework a The Contractor shall erect falsework and support brace and maintain it to safely support vertical lateral and asymmetrical loads applied until such loads can be supported by in place concrete structures and construct falsework so that adjustments can be made for take up and settlement The Contractor shall provide wedges jacks or camber strips to facilitate vertical adjustments carefully inspect falsework and form work during and after concrete placement operations to determine abnormal deflection or signs of failure and make necessary adjustments to produce work of required dimensions 4 Forms for exposed concrete Adopted 2 21 2013 2200 7 of 16 Construction Standards Concrete CONSTRUCTION STANDARDS 2200 CONCRETE A The Contractor shall drill forms to suit ties used and to prevent leakage of concrete mortar around tie holes and not splinter forms by driving ties through improperly prepared holes b The Contractor shall not use metal cover plates for patching holes or defects in forms c The Contractor shall provide sharp clean corners at intersecting planes without visible edges or offsets and back joints with extra studs or girts to maintain true
10. during concrete placement operations e Welded steel wire fabric Fabric shall conform to the requirements of ASTM A185 and shall be of the size and space opening as designated on the plans 3 3 Fabrication a General Reinforcing bars shall be fabricated conforming to required shapes and dimensions with fabrication tolerances complying with CRSI Manual of Standard Practice In case of fabricating errors the Contractor shall not rebend or straighten reinforcement in a manner that will injure or weaken the material b Unacceptable materials Reinforcement with any of the following defects will not be permitted in the work 1 Bar lengths depths and bends exceeding specified fabrication tolerances 2 Bend or kinds not indicated on drawings or final shop drawings 3 Bars with reduced cross section due to excessive rusting or other cause c Identification Reinforcing bars shall be tied in bundles and tag with weatherproof tags showing shop drawing numbers 4 Splicing Provide a minimum of 35 bar diameters of lap length G Forms 1 1 Forms for exposed concrete Form work for exposed concrete surfaces shall be high density overlay plyform Class or Il Panels shall be APA grade trade marked and meet requirements of the latest edition of U S Product Standard PSI Overlay shall not stain the surface of the architectural concrete Full sheet sizes shall be used to minimize number of joints and to conform to joint system shown on drawin
11. exploration we anticipate that the overburden soils and Interlayered sandstone and lean clay units can be excavated using a backhoe in good working condition Excavation in the moderately hard mudstone unit will likely require large track hoe in good working condition equipped with rock teeth below depth of about 14 feet The ability to excavate weathered rock or hard rock is a function of the material the equipment used the skill of the operator the desired rate of removal and other factors The contractor should review the borings logs and should use his own method to evaluate excavation difficulty 7 7 DRAINAGE CONSIDERATIONS The potential for soil moisture fluctuations within building area subgrades should be reduced to lessen the potential of subgrade movement Site grading should include positive drainage away from the proposed building addition 7 8 WET WEATHER CONSTRUCTION Cooler temperatures and shorter days during the winter season significantly reduce the capacity to dry out wet soils Additionally excessive movement of construction equipment across the site during wet weather will result in ruts which will collect rainwater prolonging the time required to dry the subgrade soils During rainy periods additional effort will be required to properly prepare the site and establish maintain an acceptable subgrade The difficulty will increase in areas where silty soils are exposed at the subgrade elevation Grading contractors
12. including load stresses heavy shock excessive vibration and from damage caused by rain or flowing water Protect all finished concrete surfaces from damage by subsequent construction operations Do not allow any traffic except for curing purposes on the concrete surfaces until the concrete has attained 60 of its 28 day strength 2 Removal of forms Forms shall be removed in such manner as to ensure the complete safety of the structure No forms shall be removed except with the express permission of the City of Stillwater In general acceptance will be based on the following A Forms on ornamental work railings parapets and vertical surfaces which do not carry loads and which will be exposed in the finished work shall be removed within twenty four 24 hours to forty eight 48 hours after placing as long as the temperature has been above 50 F the entire duration and the concrete hardness is such that the form removal will not damage the surface B Form work supporting weight of concrete such as beam soffits joists and slabs and other structural elements shall not be removed in less than fourteen 14 days and not until concrete has attained the design minimum twenty eight 28 day compressive strength Determine potential compressive strength of in place concrete location or members under the least favorable conditions prevailing for any portion of the concrete C Girder beam and joint soffit forms shall remain in place with adequate
13. light without contributing heat loss these can be incorporated into the plans 2 5 6 All roll up door corners shall be adequately protected using bollards Bollards shall be 4 foot high Six inch diameter pipe and filled with concrete Bollards shall be painted with 2 coats of high quality safety yellow paint Sixteen total bollards are required 2 5 7 A total of Three 3 Three 3 feet wide x Seven 7 feet high service type access doors with stainless steel hinges and locksets shall be installed as shown Doors will be FIB R DOR Lightweight Fiberglass Reinforced Door and Frame Systems or approved equal These doors shall be commercial grade insulated and suitable for outdoor installation and fitted with spring mechanical door closures to protect the door from wind gusts Doors shall have a panic bar per OSHA PEOSH requirements 2 5 8 A total of Four 4 electric motor operated roll up doors shall be installed as shown Door dimensions are as follows 14 feet wide x 16 feet high Doors will be Overhead Door Technical Specifications As Revised by Addendum No 2 dated May 31 2013 F 3 Company model Stormtite 625 heavy duty with brush seals RHX 220v single phase bench operator and electric safety edge bottom Fre deers shall betecked ontheinside ope ad omn dec ncdHncoroo Q hareg ad Q Q a A bekeyedto match the Water Treatment Plant keys In case of power failure roll up doors shall have a manual override hand crank
14. mold from growing in or on the structure involved Rely on Your ASFE Member Geotechncial Engineer for Additional Assistance Membership in ASFE The Best People on Earth exposes geotechnical engineers to a wide array of risk management techniques that can be of genuine benefit for everyone involved with a construction project Confer with you ASFE member geotechnical engineer for more information TRE BEST PEOPLE GN EARTH 8811 Colesville Road Suite G106 Silver Spring MD 20910 Telephone 301 565 2733 e mail info asfe org Facsimile 301 589 2017 www asfe org Copyright 2004 by ASFE inc Duplication reproduction or copying of this document in whole ot in part by any means whatsoever is strictly prohibited except with ASFE s specific written permission Excerpting quoting ar otherwise extracting wording trom this document is permitted only with the express written permission of ASFE and only for purposes of scholarly research or book review Only members of ASFE may use this document as a complement to or as an element of a geotechnical engineering report Any other firm individual or other entity that so uses this document without being an ASFE member could be commiting negligent or intentional fraudulent misrepresentation NHGER0G075 SMRP
15. or project except the one originally contemplated Read the Full Report Serious problems have occurred because those relying on a geotechnical engineering report did not read it all Do not rely on an executive summary Do not read selected elements only A Geotechnical Engineering Report Is Based on A Unique Set of Project Specific Factors Geotechnical engineers consider a number of unique project specific tac fors when establishing the scope of a study Typical factors include the client s goals objectives and risk management preferences the general nature of the structure involved its size and configuration the location of the structure on the site and other planned or existing site improvements Such as access roads parking lots and underground utilities Uniess the geotechnical engineer who conducted the study specifically indicates oth erwise do not rely on a geotechnical engineering report that was e not prepared for you e not prepared for your project not prepared for the specific site explored or e completed before important project changes were made Typical changes that can erode the reliability of an existing geotechnical engineering report include those that affect e the function of the proposed structure as when it s changed from a parking garage to an office building or from a light industria plant to a refrigerated warehouse Important Information about Your Geotechnical Engineering R
16. top of cracks and cut out holes to sound concrete and clean of dust dirt and loose particles Dampen all cleaned concrete surfaces and brush with a neat cement grout coating Place drypack before the cement grout takes its intial set Mix drypack consisting of one part Portland cement to 2 1 2 parts fine aggregate passing a No 16 mesh sieve using only enough water as required for handling and placing Compact drypack mixture in place and finish to match adjacent concrete Keep patch areas continuously moist for not less than 72 hours Repair methods not specified above may be used subject to the acceptance of the City of Stillwater END OF SECTION 2200 16 of 16 Construction Standards Concrete LIST OF DOCUMENTS REQUIRED FOR THIS BID Project Numbers SUA Project No 13WG02 SUA Bid No 25 12 13 Description Equipment Building at the Stillwater Water Treatment Plant The Bidder is responsible for reviewing this list of required documents and any requirements contained within the Project Manual and assuring that each and every required document is properly completed signed and submitted with the Bid Forms and Affidavits should be completed and submitted in accordance with provisions of the Signature Requirements for Bidding Documents DOCUMENTS REQUIRED FOR THIS BID Submit one original and two copies of the following documents Detailed Bid Form Bid Bond Bid Security Business Relationship Affidavit Non Collusi
17. will eliminate all air or stone pockets which may cause honeycombing pitting or planes of weakness Where internal vibrators are used provide mechanical vibrators with a minimum frequency of 7000 revolutions per minute Do not use vibrators to transport concrete Insert and withdraw vibrators at points from 18 to 30 inches apart for 5 to 15 seconds duration Keep a spare vibrator on the job site during all concrete operations g Reinforcing steel position shall be held continuously during concrete placement h The placing of concrete under water where permitted must be done by special accepted methods i Formed elements Use internal vibrators not form vibrators When a surface mortar is to be the basis of the finish work coarse aggregate back from the forms with a suitable tool to bring a full surface of mortar against the form j Supported elements Use internal vibrators in elevated beams girders and brackets and along construction joints Consolidate elevated slabs with vibrating bridge screeds roller pipe screens or other means approved by the City of Stillwater Tamp slabs to force aggregates away from surface and screen level to comply with ACI 347 After screeding do not manipulate concrete prior to commencing finishing operations k Bring slab surfaces to the correct level with a straight edge and strike off Use bull floats or darbies to smooth the surface leaving it free of humps or hollows Do not sprinkle water on the plas
18. 2200 CONCRETE Part 1 General A Scope 1 This section shall govern the performance of all work necessary for construction of cast in place concrete structures for inlets manholes junction boxes head walls and incidental structures Construction of concrete street pavements shall conform to Oklahoma Department of Transportation 2009 Standard Specifications and Associated American Concrete Institute Standards a 2 The Contractor shall guarantee that concrete of the specified compressive strength is incorporated in the structures and that the responsibility for producing the required grades of concrete is assumed by the Contractor Should the average strengths shown by test cylinders fall below the strengths required the City of Stillwater may require any or all of the following changes amount of cement grading of aggregate or ratio of the water to the cement used If the tests disclose that the strength of the concrete is insufficient for the structure as built the City of Stillwater may condemn the part of any structure in which concrete of insufficient strength has been placed and the Contractor shall replace all in place concrete whose representative cylinder fails a strength test b Concrete shall conform to the applicable requirements of 2009 ODOT Standard Specifications Section 700 Materials or most current edition and appropriate ACI Standard Specifications most current edition B Quality Assurance 1 Submittals a The C
19. 30 tube heaters or approved equal The parts storage Technical Specifications As Revised by Addendum No 2 dated May 31 2013 F 1 2 4 2 5 bay will have no heater The contractor will provide a gas regulator as required All plumbing and heating system including the location of heaters thermostats required ventilation fans cut off valves etc shall be designed to comply with current plumbing and HVAC codes to include IMC 2009 as adopted by the City of Stillwater Bidders shall be responsible for submitting a design that meets all current city county state and federal standards for metal storage buildings within a potable water treatment facility The bidder is responsible for complying with the prevailing standards codes and requirements including IBC 2009 Bidder is strongly advised to consult with City of Stillwater Building Official Mike Roberts at 405 742 8218 for further clarification as needed The building will be used primarily for storage but can be used by Water Plant personnel to perform maintenance on all types of plant equipment Bidder shall provide the following design information with calculations as part of the submittal review and approval process Failure to provide the required information shall require resubmittal of the missing or incomplete items of the submittal All submittals where an Oklahoma Registered Professional Engineer s stamp and signature on the drawing is required shall be
20. 4 W x 16 H l Roll up Door 14 W x 16 H Roll up Door 14 W x 16 H o 1 Baw EEn M FE a EEn EM Ei wf EEn EM E m EEn EM ii m E a ees EEn EM E m E a ws mee eee i I LT ET ET E Bollards i l a Concrete Approach 88 x 20 z l l E E E E l l E E Notes 1 All T 5 Flourscent Lights and 110V Outlets shall be on separate circuits 2 Provide long eaves to keep rain water from splashing and deteriorating metal siding 3 Provide 3 way switches at service entrances and thru doors Provide single switches to each outdoor overhead light 4 Outdoor Recepticles between bays shall be waterproof 5 Open Bays with vertical clear span of 18 feet REPORT OF SUBSURFACE EXPLORATION AND GEOTECHNICAL EVALUATION PROPOSED METAL BUILDING WATER TREATMENT PLANT STILLWATER OKLAHOMA BUILDING amp EARTH PROJECT NO OK13092 PREPARED FOR CITY OF STILLWATER PREPARED BY BUILDING amp EARTH Geotechnical Environmental and Materials Engineers DATE May 30 2013 es BUILDING amp EARTH Geotechnical Guilvoninestal and Materials Engineers 10828 East Newton Suite 11 Tulsa OK 74116 5662 Ph 918 439 9005 Fax 918 439 9255 www BuildingAndEarth com May 30 2013 Mr Anthony Daniel City of Stillwater Water Utilities 723 S Lewis Street Stillwater OK 74074 Subject Report of Subsurface Exploration and Geotechnical Evaluation Proposed Metal Building Water Treatment Plant Stillwater Oklahoma Bui
21. Beams brackets and haunches shall be considered as part of the floor system and shall be placed monolithically therewith Placement of concrete shall be at such rate that surfaces of concrete not carried to joint levels will not have attained initial set before additional concrete is placed thereon Girders beams and slabs shall be placed in one operation In walls having door and window openings individual lifts shall terminate at top and bottom of opening Other lifts shall terminate at such levels as are indicated or as to conform to structural requirements or architectural details or both as directed 7 Water stops The Contractor shall provide water stops in construction joints as shown on the drawings Install water stops to form a continuous diaphragm in each joint make provisions to support and protect water stops during the progress of the work fabricate field joints in water stops in accordance with manufacturer s print instructions and protect water stop material from damage where it protrudes from any point No wood device of any kind used to separate forms shall be permitted to remain in the finished work 8 Provision for other trades The Contractor shall provide openings in concrete form work to accommodate work of other trades including those under separate prime contracts if any Size and location of openings recesses and chases are the responsibility of the trade requiring such items The Contractor shall accurately place a
22. CITY OF Stillwater Water Utilities ADDENDUM NO 2 Equipment Building at the Stillwater Water Treatment Plant Project 13WG02 SUA Bid No 25 12 13 To All Prospective Bidders From Anthony Daniel Director of Water Utilities Issue Date May 31 2013 The Contract Documents for the above described project are hereby modified by this Addendum No 2 Each Bidder must acknowledge receipt of the Addendum in the place provided in the Bid Form CLARIFICATION TO CONTRACT DOCUMENTS The following clarifications and or additional requirements are made to the Specifications and Contract Documents for the project 1 Technical Specifications Section F pages F 1 through F 3 as originally issued are hereby deleted and replaced with Technical Specifications Section F As Revised by Addendum No 2 dated May 31 2013 pages F 1 through F 4 Attached hereto This new revised document includes strikethreughs for deleted portions and underlined additions 2 Construction Standards Section 2200 Concrete as referenced in the revised Technical Specifications Pages 1 through 16 are hereby included attached hereto 3 List of Documents Required Section H pages H 1 through H 2 as originally issued are hereby deleted and replaced with List of Documents Required As Revised by Addendum No 2 dated May 31 2013 page H 1 through H 2 Attached hereto 4 Bid Form Section J page J 5 only is hereby deleted and replaced with the Bid Form As Revised by Add
23. MOISIURE SENSITIVE SOILS senene enr eierne E aE A Eara 9 7 3 SUBGRADE PREPARATION AND EVALUATION ccc ceeeeeeeeeeeeeneceeeeeeees 10 TA STRUCTURAL FID Diseno a aE E asia tated E EE ES A a E te 10 7 0 UTILITY TRENCH BACKED D sscrauiciscaeanscsiatacsidactarssetdeonsansts Sanaa AN EIE 11 7 6 EXCAVATION CONSIDERATIONS yivovesvsssatoscwisda saxeotndeauonnden deuvtwaceuestundeecbibess 11 7 7 DRAINAGE CONSIDERA TIONS wie icv venaipciisnvel soon bus syanieriudartantiatdatabteoniseas 11 7 8 WET WEATHER CONSTRUCTION vsti civernsevnacnsewieuraepiacehedaesunavesmnavbunserewines 11 8 0 FOUNDATION RECOMMENDATIONS cceeccseccsseaseceeeeeseeceeceveseeseseeseess 12 9 0 FLOOR SLABS isienstivenia identi Vni Oa T EEEE i aE ER Paap ENE aNG 14 10 0 SEISMIC SITE CLASSIFICATION sav vvisevemiavsGasevveieaie dedeci ses tlehtes cgacagensands 15 11 0 CONSTRUCTION MONITORING owisusin s caawtivesinaitsinwcis ds Dpaweeveantsaates sal vecebtanees 16 BZ AY CVAD SING A crac het bois ian E ReValacee coe AGL Pa E EU Se 17 APPENDIX 1 0 SITE AND PROJECT DESCRIPTION The project site is located at 1022 West Yost Street in Stillwater Oklahoma The project site is located on the northwest corner of North Washington Street and Yost Road Based on the information provided to our office we understand that an 80 x 40 metal building is planned on the northeast corner of the water treatment plant property Figure 1 shows the approximate location of the project site
24. ORATION The authorized subsurface exploration was performed on May 20 and 21 2013 The subsurface exploration presented in this report consisted of two 2 soil test borings drilled within the proposed building area Borings B l and B 2 were drilled to a depth of approximately 14 5 feet below existing ground surface within the proposed building area on the east and west ends respectively The soil boring locations were determined in the field by a representative of City of Stillwater The approximate boring locations are indicated on the Boring Location Plan included in the Appendix of this report The borings were drilled with by Data Testing with a truck mounted drill rig equipped with solid stem augers and automatic hammer At each boring location soil samples were retrieved at standard sampling intervals by driving a split tube sampler The borehole was first advanced to the sample depth by augering and the sampling tools were placed in the open hole The sampler was then driven into the ground 18 inches by blows from a 140 pound hammer falling 30 inches The number of blows required to drive the sampler each 6 inch increment was recorded The initial increment is considered the seating blows where the sampler penetrates any loose or disturbed soil in the bottom of the borehole The blows required to penetrate the final two increments are added together and referred to as the Standard Penetration Test SPT N Value The N Value whe
25. Stee Wire Fabric for Concrete Reinforcement d Formwork Unless otherwise shown or specified design construct erect maintain and remove forms and related structures for cast in place concrete work in compliance with the following 1 ACI 347 Recommended Practice for Concrete Form work Adopted 2 21 2013 Page 1 of 16 Construction Standards Section 2200 Concrete Part 2 CONSTRUCTION STANDARDS 2200 CONCRETE 2 USPS PSI Product Standard for Softwood Plywood Construction and Industrial e Allowable tolerances 1 Construct form work to provide completed cast in place concrete surfaces complying with the tolerances specified in ACI 374 2 Before concrete placement check the lines and levels of erected formwork Make corrections and adjustments to ensure proper size and location of concrete members and stability of forming systems 3 During concrete placement check formwork and related supports to ensure that forms are not displaced and that completed work will be within specified tolerances Materials A Cement 1 All cement used in the work shall be a standard brand of portland cement and shall comply with the cement ASTM C150 Standard Specifications for Air Entraining Portland Cement The cement shall be Type I All cement hauled to the job shall be in original unopened containers bags or sacks showing the brand name of the manufacturer Only one brand of cement shall be used in any individual structure Ce
26. able This report should not be used for a different development on the same property without first being evaluated by the engineer The recommendations in this report were based on the information obtained during the field exploration laboratory analysis and engineering judgment regarding conditions between borings The anticipated subsurface conditions should be confirmed during site grading and foundation installation This report is intended for use during design and preparation of specifications and may not address all conditions at the site at the time of construction Contractors reviewing this information should acknowledge that this document is for design information only An article published by the Association of Engineering Firms Practicing in the Geosciences ASFE titled Important Information About Your Geotechnical Report has been included in the Appendix We encourage all individuals to become familiar with the article to help managing risk 17 APPENDIX s4 au uz sjeiazep pue yeIuaWUOJAUy jeI1UYyIe10a5 HLYVa 8 ONIGTING SIN HTVOS 10Z 62 S ULVA BUIOYE YO JLMNNS COOC THO Ued JUIWZJLIL 197M Surprmg e79IN posodorg NVId NOILVOOT ONIXO R ILOS Ue puys SATY MODMY saako JOOS 7 14By fanaysann JOOPIRO LEME CN SOUMI R S WAAG FOOR AAP RE SEMPUS IAIO p ABIA KUL OCA Paufas epia Guneataiayige pane Fugi Lite Lapa n Ws AN IY SEARA Hei Id MAO AHIS LD 99 AUS ANO AD i DUC SAAI DINN B J AY 4 ZK gG yowaldd
27. al fill The site soils consist mostly of fine grained silty clayey sands SC SM which are prone to losing stability with slight increases in soil moisture levels The contractor should use care during fill placement to prevent over wetting of the soils and to limit repeat construction traffic as this will increase the risk of these soils losing stability We recommend that bulk samples of the onsite soils be collected during initial site preparation for further laboratory testing to evaluate their suitability for use as structural fill Any fill to be placed at the site should be approved by the geotechnical engineer The structural fill should be compacted to a minimum of 95 of the standard Proctor maximum dry density and within 2 of the optimum moisture as determined by ASTM D698 The specifications should state that both density and moisture requirements should be met The lifts should not exceed 8 to 12 inches thick depending on the compaction equipment used Density and moisture tests should be performed on each lift prior to placement of subsequent lifts 10 7 5 UTILITY TRENCH BACKFILL All utility trenches in the proposed building addition area must be backfilled and compacted in the manner specified above for structural fill It may be necessary to reduce the lift thickness to 4 to 6 inches to achieve compaction using hand operated equipment 7 6 EXCAVATION CONSIDERATIONS Based on the information gathered during our subsurface
28. assification System USCS 5 2 NATURAL MOISTURE CONTENT ASTM D 2216 Natural moisture contents were determined on selected samples The natural moisture content is the ratio expressed as a percentage of the weight of water in a given amount of soil to the weight of solid particles 5 3 ATTERBERG LIMITS ASTM D 4318 Atterberg Limits tests were performed to evaluate the soils plasticity characteristics The Plasticity Index PI is representative of this characteristic and is bracketed by the Liquid Limit LL and the Plastic Limit PL The LL is the moisture content at which the soil will flow as a heavy viscous fluid The PL is the moisture content at which the soil is between plastic and the semi solid stage The Plasticity Index PI LL PL is a frequently used indicator for a soil s potential for volume change Typically a soil s potential for volume change increases with higher plasticity indices 5 4 PARICLE SIZE ANALYSIS ASTM D 422 A particle size test was performed to determine the soil particle size distribution The grain size distribution of the soil retained on the No 200 sieve was determined by passing the retained portion through a standard set of nested sieves The results are shown on the table below 5 5 SUMMARY OF LABORATORY TEST RESULTS Atterberg limits and wash 200 test was performed on a sample The results of the laboratory testing are presented in the following table Summary of Laborat
29. ations E Fly Ash Use of fly ash or other cement subsitutes shall conform to ODOT Standard Specification Section 702 Supplementary Cementitious Materials F Reinforcing Steel 1 Reinforcing bars rebar All reinforcing bars shall be rolled from new billets and shall conform to the ASTM A615 Specifications for Billet Steel Bars for Concrete Reinforcement and shall be of the Grade 60 unless otherwise specified Unless otherwise shown all reinforcing bars shall be deformed and shall conform to the requirements of the ASTM A615 specifications for minimum reinforcement The deformed bars used shall have a net sectional area at all points equivalent to that of plain bars of equal nominal size Twisted steel bars shall not be used 2 Supports for reinforcement Reinforcement supports shall be bolsters chairs spacers and other devices for spacing supporting and fastening reinforcements in place a Wire bar type supports shall comply with CRSI recommendations unless otherwise indicated Do not use wood brick or concrete block b Sand plates or horizontal runners shall be used where base material will not support chair legs for slabs on grade c Either hot dip galvanized plastic protected or stainless steel protected legs shall be used for exposed to view concrete surfaces where legs of supports are in contact with forms d Tie wire Tire wire sixteen 16 gauge minimum and in sufficient quantity to hold reinforcement accurately in place
30. by the manufacturer accurately measure all admixtures to within plus or minus 5 percent and shall provide suitable agitating equipment to insure uniform distribution of ingredients c Mixing The Contractor shall charge batch into the mixer so that some water will enter in advance of the cement and aggregates allow water to flow into the mixer until the end of the first 25 percent of the specified mixing time provide controls to insure that the batch cannot be discharged until the specified mixing time has elapsed provide controls to insure that no additional water may be added during mixing and discharge the entire batch before recharging d Mixing time The Contractor shall mix each batch of 2 cubic yards or less for not less than 1 1 2 minutes and not more than 5 minutes after all ingredients are in the mixer before any part of the batch is released increase mixing time by 15 seconds for each additional cubic yard or fraction thereof and not exceed 30 minutes total elapsed time between intermingling of damp aggregates and cement to the discharge of the completed mix into the forms e Maintenance The Contractor shall keep mixer clean and replace mixer pick up and throw over blades when they have lost 10 percent of their original depth f Identification The Contractor shall provide a batch ticket for each batch discharged and used in the work indicating the project identification name and number date mix type mix time quantity and a
31. dders shall ensure that the metal building is adequately sealed to minimize heat loss by providing weather proofing at the base eaves rakes and at all openings and penetrations Building will be completely architecturally trimmed at all openings and feature transitions 2 5 13 As part of the submittal approval process the contractor and their subcontractors shall be required to obtain all required permits from the City of Stillwater Development Services Building Safety Division All permit fees will be waived All license and registration fees are to be paid by the Contractor 2 5 14 Owner will hire a testing company to perform compaction testing on the subgrade and collect test concrete cylinders to ensure specifications are met 2 5 15 Facility will be designed with three 3 wall mounted propeller type exhaust fans for the equipment bays Fans will be Loren Cook Company model XPHD or approved equal with manufacturer provided assembled_ wall collars exterior galvanized steel weather hood and bird screen motorized damper and interior OSHA wire blade guard cover 2 5 16 Provide survey for site design to ensure maximum equipment approach slope of 1 12 with final site perimeter grading and restoration to provide water run off away from the building slab with a maximum slope of 4 12 and a minimum slope of 1 12 End of Section Technical Specifications As Revised by Addendum No 2 dated May 31 2013 F 4 CONSTRUCTION STANDARDS SECTION
32. eakage of cement paste during concrete placement solidly butt joints and provide backup material at joints as required to prevent leakage and fins seal form joints with foam tape or other demonstrated effective means and provide a means to seal the bottom of forms at construction joints such as foam tape or other gasket devices 2 Placing forms a j k Concrete forming shall conform to ACI Code 347 to the exact sizes shapes lines and dimensions shown and as required to obtain accurate alignment location grades level and plumb work in finished structures provide for openings offsets sinkages keyways recesses moldings rustications reglets chamfers blocking screeds bulkheads anchorages and inserts and other features required and use select materials to obtain required finishes Forms shall be installed so removal without hammering or prying against concrete surfaces Crush plates or wrecking plates shall be installed where stripping may damage cast concrete surfaces Top forms for inclined surfaces shall be installed where the slope is too steep or place concrete with bottom forms only Kerf wood inserts for forming keyways reglets recesses and the like to prevent swelling and assure ease of removal The Contractor shall provide temporary openings where interior area of form work is inaccessible for clean out for inspection before concrete placement and for placement of concrete The Contractor shall brace temporary c
33. endum No 2 dated May 31 2013 Page J 5 only Attached hereto 5 ATTACHMENT 1 is replaced by ATTACHMENT 1 Revised Per Addendum No 2 dated May 31 2013 attached hereto 6 The Report of Subsurface Exploration and Geotechnical Evaluation is hereby included Attached hereto End of Addendum No 2 Technical Specifications for the Design Supply and Construction of a Metal Equipment Storage Building at the City of Stillwater Water Treatment Plant 1 Project Description 2 1 1 1 2 1 3 1 4 The successful bidder is required to undertake all necessary engineering design for the supply and construction of an industrial type equipment storage metal building at the designated site within the Stillwater Water Treatment complex The sketch plan of the proposed building is shown on the Attachment 1 1 2 1 The minimum dimensions of the building are Forty 40 feet wide Eighty 80 feet long and Eighteen 18 feet full wall height with a clear structural span each way and vertically to roof system 1 2 2 The building will have four 4 bay roll up doors 1 2 3 The building will have two 2 three 43 side entry service doors and one interior passage door within the separation wall between the parts storage area and equipment bays The east bay of the building will be used primarily as a parts storage area for storing and servicing light equipment primarily water pumps motors gasoline engine powered equipment etc
34. ent to render an opinion about subsurface conditions throughout the Site Actual subsurface conditions may differ sometimes significantly from those indicated in your report Retaining the geotechnical engineer who developed your report to provide construction observation is the most effective method of managing the risks associated with unanticipated conditions A Report s Recommendations Are Not Final Do not oversely on the construction recommendations included in your report Those recommendations are not final because geotechnical engi neers develop them principally from judgment and opinion Geotechnical engineers can finalize their recommendations only by observing actual The following information is provided to help oe ee ee ES SE On TRE IE AIIN R E as pe subsuriace conditions revealed during construction The geotechnical engineer who developed your report cannot assume responsibility or fabilily for the report s recommendations if that engineer does not perform construction observation A Geotechnical Engineering Report Is Subject te Misinterpretation Other design team members misinterpretation of geotechnical engineering reports has resulted in costly problems Lower that risk by having your geo i fechnical engineer confer with appropriate members of the design teami after submitting the report Also retain your geotechnicat engineer to review perti nent elements of the design team
35. eport Subsurface problems are a principal cause of construction delays cost overruns claims and disputes gt e elevation configuration location orientation or weight of the proposed structure composition of the design team or e project ownership AS a general rule always inform your geotechnical engineer of project changes even minor ones and request an assessment of their impact Geotechnical engineers cannot accept responsibility or liability for problems that occur because their reports do not consider developments of which they were not informed Subsurface Conditions Can Change A geotechnical engineering report is based on conditions that existed at the time the study was performed Do not rely on a geotechnical engineer ing report whose adequacy may have been affected by the passage of time by man made events such as construction on or adjacent to the site or by natural events such as floods earthquakes or groundwater fluctua tions Always contact the geotechnical engineer before applying the repor to determine if it is still reliable A minor amount of additional testing or analysis could prevent major problems Most Geotechnical Findings Are Professional Opinions Site exploration identifies subsurface conditions only at those points where subsurface tests are conducted or samples are taken Geotechnical engi neers review field and laboratory data and then apply their professional judgm
36. ference can also be valuable Be sure contrac tors have sufficient time to perform additional study Only then might you be in a position to give contractors the best information available to you while requiring them to at least share some of the financial responsibilities stemming from unanticipated conditions Read Responsibility Provisions Closely Some clients design professionals and contractors do not recognize thal geotechnical engineering is far less exact than other engineering disci plines This lack of understanding has created unrealistic expectations that Ne have ied to disappointments claims and disputes To help reduce the risk of such outcomes geotechnical engineers commonly include a variety ot explanatory provisions in their reports Sometimes labeled limitations many of these provisions indicate where geotechnical engineers responsi bilities begin and end to help others recognize their own responsibilities and risks Read these provisions closely Ask questions Your geotechnica engineer should respond fully and frankly fecenvironmental Concerns Are Not Covered The equipment techniques and personnei used to perform a geoenviron mental Study differ significantly from those used lo perform a geotechnical Study For that reason a geotechnical engineering report does not usually relate any geoenvironmental findings conclusions or recommendations g about the likelihood of encountering underg
37. g of the concrete and the use of means to protect it from the direct rays of the sun 1 The Contractor shall protect freshly placed concrete from premature drying and excessive cold or hot temperature and maintain without drying at a relatively constant temperature for the period of time necessary for hydration of the cement and proper hardening of the concrete 2 The Contractor shall start initial curing as soon as free moisture has disappeared from the concrete surface after placing and finishing and weather permitting keep continuously moist for not less than 72 hours 3 The Contractor shall begin final curing procedures immediately following initial curing and before the concrete has dried continue final curing for at least 7 days and in accordance with ACI 301 procedures and avoid rapid drying at the end of the final curing period Adopted 2 21 2013 2200 12 of 16 Construction Standards Concrete CONSTRUCTION STANDARDS 2200 CONCRETE b Water curing The Contractor shall moist cure the concrete using only water that is free of impurities which could etch or discolor exposed natural concrete surface The methods are as follows 1 Keeping the surface of the concrete continuously wet by covering with water 2 Continuous water fog spray 3 Covering the concrete surface with the specified absorptive cover thoroughly saturating the cover with water and keeping the absorptive cover continuously wet Place absorptive cover so as t
38. grayish tan i ae lean clay layers reddish brown and grayish tan medium 3 10 21 15 een HIGHLY WEATHERED MUDSTONE red 4 and teddish brown medium plasticity moist soft 11 18 24 e 104 l Ge E E E er or reddish brown and grayish tan 35 50 3 K gt gt 0143 moderately hard i ae Boring Terminated at 14 3 feet Is Boring Backfilled on 5 20 13 Groundwater seepage not f encountered while drilling al ea E a and boring dry upon s completion g in z 5 fo 5 d Q z S d 9 n SAMPLE TYPE lt Split Spoon oO Z N VALUE STANDARD PENETRATION RESISTANCE AASHTO T 206 REC RECOVERY 2 MOISTURE PERCENT NATURAL MOISTURE CONTENT RQD ROCK QUALITY DESIGNATION 5 g GROUNDWATER LEVEL IN THE BOREHOLE U UNDISTURBED 3 Qu UNCONFINED COMPRESSIVE STRENGTH ESTIMATE FROM POCKET PENETROMETER TEST m Birmingham Ala Huntsville AL Auburn AL Columbus GAE Savannah GAs Raleigh NG Tulsa OK Springdale ARs Shreveport LAM Louisvitle KYS Niceville FL LOG OF BORING 2 0K13092 GP5 BESI GDT 5 30 13 a e LOG OF BORING 10828 E Newton St Suite 111 BUILD A gabe Tulsa OK 74116 gt DING amp H Designation B 2 Office 918 439 9005 Cree i Sheet 1 of 1 Fax 918 439 9255 Geotechnical Environmental and Materials Engineers www BuildingAndEarth com Project Na
39. gs Form material shall be of sufficient thickness to withstand pressure of newly placed concrete without bow or deflection minimum 3 4 inch 2 2 Forms for unexposed concrete Concrete surfaces which will be unexposed in the finished structure shall be formed with plywood lumber metal or other acceptable material Lumber shall be dressed on at least 2 edges and 1 side for tight fit tongue and grooved free from loose knots and of such moisture content as to prevent free absorption of moisture Adopted 2 21 2013 2200 3 of 16 Construction Standards Concrete 3 ap 6 7 CONSTRUCTION STANDARDS 2200 CONCRETE 3 Form coatings Commercial formulation form coating compounds shall be provided will not bond with stain nor adversely affect concrete surfaces and will not impair subsequent treatment of concrete surfaces requiring bond or adhesion nor impede the wetting of surfaces to be cured with water or curing compounds Release agent shall be used in strict accordance with manufacturer s recommendations 4 Vinyl foam tape Vinyl foam tape shall be 3 4 x 1 8 adhesive backed closed cell tape 5 Form accessories Only form ties anchors and hangers of sufficient strength to completely resist displacement of forms due to construction loads and the depositing of concrete shall be used Tie and spreader type form ties designed so that no metal will be within one inch of any surface when forms are removed shall be used Where concre
40. he water level can occur due to seasonal rainfall Water levels as observed during drilling are accurate for only the time and date that the boring was drilled Short term groundwater level readings may not accurately reflect the actual groundwater levels at the borings 7 0 SITE GRADING CONSIDERATIONS Proposed grading plans were not provided to us at the time of preparing this report however for the purpose of this report we assumed that maximum cut and fill depths of 2 feet or less will be required to achieve design grades within proposed building area The primary geotechnical considerations for development of the project site include e The moisture sensitivity of the silty clayey sand encountered across the project site e The presence of Interlayered sandstone and lean clay unit below the clayey sand at depth of 1 to 2 feet below the existing ground surface e The presence of moderately hard mudstone unit at a depth of about 14 feet below existing ground surface 7 1 INITIAL SITE PREPARATION All vegetation topsoil or any other deleterious materials should be removed from the proposed construction areas prior to placing fill or constructing the foundations or slab on grade Existing utility lines are anticipated within the proposed building area We recommend that existing underground utility lines be rerouted to areas outside the proposed building footprint and the utility line trenches backfilled with properly compacted st
41. hen Standard Split Spoon sampling is used the blows required to drive the sampler each 6 inch increment are recorded and shown in column 4 When rock core is obtained the recovery ration REC and Rock Quality Designation RQD is recorded Soil Data Column 5 is a graphic representation of 4 different soil parameters Each of the parameters use the same graph however the values of the graph subdivisions vary with each parameter Each parameter presented on column 5 is summarized below e N Value The Standard Penetration Test N Value obtained by adding number of blows required to drive the sampler the final 12 inches is recorded The graph labels range from 0 to 50 e Qu Unconfined Compressive Strength estimate from the Pocket Penetrometer test in tons per square foot tsf The graph labels range from 0 to 5 tsf Atterberg Limits The Atterberg Limits are plotted with the plastic limit to the left and liquid limit to the right connected by a horizontal line The difference in the plastic and liquid limits is referred to as the Plasticity Index The Atterberg Limits test results are also included in the Notes column on the far right column of the boring log The Atterberg Limits graph labels range from 0 to 100 e Moisture The Natural Moisture Content of the soil sample as determined in our laboratory Soil Description The soil description prepared in accordance with ASTM D 2488 Visual Description of Soil Samples The Mu
42. in the finished slab surface and provide and secure units to support types of screen required 12 Shores and supports a The Contractor shall comply with ACI 347 for shoring and reshoring and as herein specified b Remove shores and reshore in a planned sequence to avoid damage to partially cured concrete c Locate and provide adequate reshoring to safely support the work without excessive stress or deflection 13 Placing reinforcement a All reinforcement when placed shall be free from mill scale loose or thick rust dirt paint oil or grease and shall present a clean surface Storage of material shall be on pallets with tarpaulin coverings to prevent rust and scale b Bends and splices shall be accurately and neatly performed and shall conform to the ACI Manual of Standard Practice for Detailing Reinforced Concrete Structures and the CRSI Handbook c All reinforcing shall be placed in the exact position shown on the plans and shall be held firmly in position by means of metal chairs bolsters spacers hangers or other accepted supports such as wiring the bars together at intersections with accepted wire ties in order that the reinforcement will not be displaced during the depositing and compacting of the concrete Tie wires ends shall be turned away from the exposed surfaces d When the concrete surface will be exposed to the weather in the finished structure or where rust would impair the appearance the portions of all acces
43. ks in excess of 0 01 wide or which penetrate to the reinforcement or completely through non reinforced sections regardless of width spalling popouts honeycomb rock pockets and other objectionable conditions Correct high areas in unformed surfaces by grinding after the concrete has cured sufficiently so that repairs can be made without damage to adjacent areas Correct low areas in formed surfaces during or immediately after completion of surface finishing operations by cutting out low areas and replacing with fresh concrete Finish repaired areas to blend into adjacent concrete Repair defective areas except random cracks and single holes not exceeding 1 inch diameter but cutting out and replacing with fresh concrete Remove defective areas to sound concrete with clean square cuts and expose reinforcing steel with at least 3 4 clearance all around Dampen all concrete surfaces in contact with patching concrete and brush with a neat cement grout coating or use concrete bonding agent Place patching concrete before grout takes its initial set Mix patching concrete of the same materials to provide compact and finish as required to blend with adjacent finished concrete Cure in the same manner as adjacent concrete 2200 15 of 16 Construction Standards Concrete G Adopted 2 21 2013 CONSTRUCTION STANDARDS 2200 CONCRETE Repair isolated random cracks and single holes not over 1 inch in diameter by the dry pack method Groove the
44. lding amp Earth Project No OK13092 Dear Mr Daniel Building amp Earth Sciences Inc has completed the authorized subsurface exploration and geotechnical engineering evaluation for the proposed metal building at the Water Treatment Plant in Stillwater Oklahoma Our services were performed in general accordance with our proposal number OK15114 dated May 22 2013 The purpose of this exploration and evaluation was to assess the general subsurface conditions at the site and to provide recommendations for site grading and foundation design for the proposed building The recommendations in this report are based on a geotechnical reconnaissance of the site and observation and classification of samples obtained from two 2 soil test borings drilled at the site Confirmation of the anticipated subsurface conditions during construction is an essential part of geotechnical services We appreciate the opportunity to provide consultation services for the subject project If you have any questions regarding the information in this report or need any additional information please contact the undersigned Respectfully Submitted BUILDING amp EARTH SCIENCES INC Certificate of Authorization 3975 Expires 6 30 2014 M EJarma yt z 3 7 DL en Dharmateja Maganti Mark Nolen P E Project Engineer Regional Vice President OK22170 Birmingham AL Columbus GA Huntsville AL Louisville KY Raleigh NC Savannah GA Shreveport LA S
45. losures and set tightly to forms to prevent loss of concrete mortar and locate temporary openings on forms in as inconspicuous location as possible consistent with project requirements The Contractor shall form intersecting planes to provide true clean cut corners with edge grain of plywood not exposed as form for concrete The Contractor shall provide openings in forms to accommodate other work including mechanical and electrical work and accurately place and securely support items required to be built into the form The material to be used in the forms for exposed surfaces shall be sized and dressed lumber or metal in which all bolt and rivet heads are countersunk In either case a plain smooth surface of the desired contour shall be obtained Undressed lumber may be used for backing or other unexposed surfaces except inside faces of conduits Dimensions affecting the construction of subsequent portions of the work shall be carefully checked after the forms are erected and before any concrete is placed Temporary openings where interior area of form work is inaccessible shall be used for clean out for inspection before concrete placement and for placement of concrete Temporary closures shall be braced and set tightly to forms to prevent loss of concrete mortar Temporary openings shall be located on forms in as inconspicuous location as possible consistent with project requirements Intersecting planes shall be formed to provide true
46. mb and rock pockets down to concrete but in no case to a depth of less than 1 inch In no case shall reinforcing metal be cut into Adopted 2 21 2013 2200 14 of 16 Construction Standards Concrete D CONSTRUCTION STANDARDS 2200 CONCRETE Make edges of cuts perpendicular to the concrete surface Before placing the cement mortar thoroughly clean dampen with water and brush coat the area to be patched with neat cement grout Proprietary patching compounds may be used when acceptable to the City of Stillwater For exposed to view surfaces the Contractor shall blend white portland cement and standard portland cement so that when dry the patching mortar will match the color of the surrounding concrete Provide test areas at inconspicuous location to verify mixture and color match before proceeding with the patching Compact mortar in place and strike off slightly higher than the surrounding surface The Contractor shall fill holes extending through concrete by means of a plunger type gun or other suitable device from the least exposed face using a flush stop held at the exposed face to insure complete filling 2 Repair of formed surfaces A The Contractor shall repair of exposed to view formed concrete surfaces where possible that contain defects which adversely affect the appearance of the finish Remove and replace the concrete having defective surfaces if the defects cannot be repaired to the satisfaction of the City of Still
47. me Proposed Metal Building Water Treatment Plant Project Location Stillwater Oklahoma Project Number OK13092 Date Drilled 5 21 13 Drilling Method Solid Stem Auger Weather Conditions Equipment Used Giddings Surface Elevation Hammer Type Automatic Drill Crew Data Testing Inc Boring Location West Hole Logged By Teja Maganti E LT op ob O N Value 1 a m SiS a 10 20 30 40 i Zz Z A Quitsf a l H gx2 1 2 3 4 gt Ie eE EE SOIL DESCRIPTION 3 REMARKS ajz 7 2 20 40 6 830 oI Tit lt G i mial A Moisture Pr pie 20 40 60 80 Phe SILTY CLAYEY SAND SC SM pd gray brown orange brown and orange DER 4 2 eH pockets with sandstone fragments trace to 41 Sample 1 0 5 2 ft 1 12 21 11 Hi low plasticity moist dense 7 4 1 Atterberg Limits J arne 2 La ZAY LL 22 PL 16 PI 6 INETERLAYERED SANDSTONE AND Jt fines 36 3 a LEAN CLAY tan yellow grayish tan and Dy ide some reddish brown low plasticity moist Ps 2 9 10 19 oe poorly cemented Ax ft i reddish brown and some tan medium oe 3 17 28 27 plasticity A os J 7 0 B A HIGHLY WEATHERED MUDSTONE red Aa X and reddish brown medium plasticity moist lt a sofi Ka A f K X 10 19 28 0 2 RE 104 FA 7 1 Ks EA ee BE oe reddish brown and grayish tan Ks i 5 37 503 ee S31p143 moderately hard es n ae Boring Terminated at 14 3 feet Ss ae ar Boring Backfilled on 5 20 13 Groundwater
48. ment reclaimed by cleaning bags or cement that has leaked from containers shall not be used Cement shall be used in the sequence of shipments received unless otherwise directed Different brands grades or types of cement shall be stored separately All cement shall be stored in such a manner as to permit easy access for proper inspection and identification of each shipment in a suitable weather tight building that will protect it from dampness and deterioration Packages of cement which have become partially set or contain any lumps or caked cement shall be rejected and in no instance will any portion of a bag of damaged or faulty cement be used B Aggregates 1 All aggregates used shall conform to the requirements of ASTM C33 Specifications for Concrete Aggregate unless otherwise indicated on the drawings or directed by the City of Stillwater 2 Sampling and testing Sampling and testing shall be in accordance with the latest revision of the AASHTO Methods SAMPNING a rinena ea eee es T 2 Sieve Analysis nirisan nario aiana T 27 Material Passing No 200 T 11 Organic Impurities 0 0 eceeeeee eect eeeteeeeeeeeeeeaeeteneeees T 21 Clay Lumps and Friable Particles T 112 modified Coal and Lignite 2 2 00 aeaniee aieeaa iania T 113 Mortar and Tensile Strength s es T 35 3 Storage Aggregate shall be stored in a manner that will allow good drainage and will insure that the aggregate is kept free of foreign matter
49. moisture contents of the sandy soils were 7 and 8 percent Atterberg limits tests performed on a sample of silty clayey sand indicated Liquid Limit LL value of 22 plastic limit PL value of 16 and plasticity index PI value of 6 About 36 percent of the sand material passed the No 200 sieve 6 3 INETERLAYERED SANDSTONE AND LEAN CLAY Interlayered sandstone and lean clay was encountered in Borings B 1 and B 2 below the clayey sands and continued to depths of about 6 2 to 7 feet below the existing ground surface The Interlayered sandstone and lean clay were orange brown tan yellow grayish tan and reddish brown in color The SPT N values in this zone typically ranged from 29 to 61 blows per foot bpf The moisture contents in this unit ranged from 7 to 12 percent 6 4 HIGHLY WEATHERED MUDSTONE UNIT Highly weathered mudstone was encountered below the inlerlayered sandstone and lean clay layer in both the borings The highly weathered mudstone unit continued to a boring termination depth of 14 3 feet The mudstone unit was red reddish brown and grayish tan in color The SPT N values in the mudstone unit typically ranged from 42 blows per foot bpf to 50 blows per 3 inches of 7 penetration The moisture contents in the mudtone unit ranged from 10 to 14 percent 6 5 GROUNDWATER Groundwater was not encountered in the borings while drilling and the borings were dry upon completion of drilling and prior to backfilling Fluctuations in t
50. mount of water introduced Adopted 2 21 2013 2200 5 of 16 Construction Standards Concrete CONSTRUCTION STANDARDS 2200 CONCRETE g Retempering The Contractor shall mix concrete only in quantities for immediate use Discard concrete which has set do not retemper Adding water to the mix at the job site shall not be permitted 3 Ready mix concrete The Contractor shall comply with the requirements of ASTM C94 and as herein specified provided quantity and rate of delivery will permit unrestricted progress of the work in accordance with the placement schedule During hot weather or under conditions contributing to rapid setting of concrete a shorter mixing time than specified in ASTM C 94 may be required Proposed changes in mixing procedures shall be accepted by the City of Stillwater before implementation All mixer trucks shall be equipped with water meters Plant equipment and facilities should conform to National Ready Mix Concrete Association Check list for Certification of Ready Mixed Concrete Production Facilities a Consistency 1 All reinforced concrete which is required to be spaded or puddled in forms or around reinforcing steel shall be of such consistency that A All aggregates will float uniformly throughout the mass without settling or segregating B When dropped directly from the discharge chute of the mixer the concrete will flatten out at the center of the pile but will stand up at the edges the piling spreadi
51. n properly evaluated gives an indication of the soil s strength and ability to support structural loads Many factors can affect the SPT N Value so this result should not be used exclusively to evaluate soil conditions Samples retrieved from the boring locations were labeled and stored in plastic bags at the jobsite before being transported to our laboratory for analysis The project engineer prepared Boring Logs summarizing the subsurface conditions at the boring locations The Boring Logs are included in the Appendix of this report 5 0 LABORATORY ANALYSIS After the soil samples were visually classified specific samples were selected by the project engineer for laboratory analysis The laboratory analysis consisted of ten 10 natural moisture content tests one 1 Atterberg limits test and one 1 Wash 200 tests The results of the laboratory analysis are presented on the boring logs in the Appendix of this report A brief description of the laboratory tests performed is provided in the following sections 5 1 DESCRIPTION OF SOILS VISUAL MANUAL PROCEDURE ASTM D 2488 The soil samples were visually examined by the project geotechnical engineer who provided soil descriptions Representative samples were then selected and tested in accordance with the aforementioned laboratory testing program to determine soil classifications and engineering properties This data was used to correlate the visual descriptions with the Unified Soil Cl
52. n joints between the proposed building addition and existing structures Exterior and perimeter footings should be extended to a minimum depth of 24 inches below finished exterior grades Even though computed footing dimensions may be less column footings should be at least 24 inches wide and strip footings should be at least 16 inches wide These dimensions facilitate hand cleaning of footing subgrades disturbed by the excavation process and the placement of reinforcing steel They also reduce the potential for localized punching shear failure The following items should be considered during the preparation of construction documents and foundation installation e The geotechnical engineer of record should observe the exposed foundation bearing surfaces prior to concrete placement to verify that the conditions anticipated during the subsurface exploration are encountered e All bearing surfaces must be free of soft or loose soil prior to placing concrete e The bottom surface of all footings should be level e Concrete should be placed the same day the excavations are completed and bearing materials verified by the engineer If the excavations are left open for an extended period or if the bearing surfaces are disturbed after the initial observation then the bearing surfaces should be re evaluated prior to concrete placement 12 Water should not be allowed to pond in foundation excavations prior to concrete placement or above the conc
53. nchors and inserts during forming operations Prior to actual placement of concrete all insert and anchor locations shall be rechecked to assure proper vertical and horizontal alignment e Care shall be taken during placement operations so as not to alter the location of any anchors or inserts Adopted 2 21 2013 2200 9 of 16 Construction Standards Concrete CONSTRUCTION STANDARDS 2200 CONCRETE f After screening operations are complete the vertical and horizontal alignment shall be rechecked to assure the proper location of anchors and inserts g Inthe event the alignment is improper the Contractor shall revise repair modify or replace any anchor or insert which is improperly embedded The cost of such work shall be borne by the Contractor 15 Pre placement inspection a Before placing concrete inspect and complete the form work installation reinforcing steel preformed joint fillers vapor barriers water stops and items to be embedded or cast in Notify other crafts involved in ample time to permit the installation of their work cooperate with other trades in setting such work as required b Thoroughly wet the forms immediately before placing concrete as required where form coatings are not used Where coating is used the Contractor shall with a brush or spray coating covering the form evenly without excess drip Form oil which causes softening or permanent staining of the concrete shall not be used c Soil at bottom
54. nd securely support items to be built into forms 9 Cleaning and tightening The Contractor shall thoroughly clean forms and adjacent surfaces to receive concrete remove chips wood sawdust dirt or other debris just before concrete is to be placed and retighten forms immediately after concrete placement as required to eliminate mortar leaks 10 Form coatings a The Contractor shall coat form contact surfaces with form coating compound before reinforcement is placed keep excess form coating from accumulating in forms or to come into contact with surface which will be bonded to fresh concrete and apply in compliance with manufacturer s instructions Adopted 2 21 2013 2200 8 of 16 Construction Standards Concrete CONSTRUCTION STANDARDS 2200 CONCRETE b The Contractor shall coat steel forms with a non staining rust preventive form oil or otherwise protect against rusting Rust stained steel form work is not acceptable 11 Installation of embedded items a General The Contractor shall set and build into the wood anchorage devices and other embedded items required for other work that is attached to or supported by cast in place concrete and use setting drawings diagrams instructions and directions provided by suppliers of the items to be attached thereto b Edge forms and screen strips for slabs The Contractor shall set edge forms or bulkheads and intermediate screen strips for slabs to obtain required elevations and contours
55. ng from internal expansion and not by flowing C The concrete will flow sluggishly when tamped or spaded D The concrete can be readily puddled into corners and angles of forms and around reinforcing steel E The concrete can be readily spaded to the bottom of the placement or to a depth of several feet at any time within thirty 30 minutes after placing 2 Adesirable consistency is one which results in a very slight accumulation of water at the top of a layer several feet in thickness but without segregation or accumulation of laitance If through accident intention or error in mixing any concrete shall vary materially from the consistency specified such concrete shall not be incorporated in the work but shall be discharged as waste material B Cast in place concrete 1 Form work design a The Contractor shall design erect support brace and maintain form work so that it will safely support vertical and lateral loads that might be applied until such loads can be supported by the concrete structure The Contractor shall carry vertical and lateral loads to ground by a form work system and in place construction that has attained adequate strength for that purpose The Contractor shall construct form work so that concrete members and structures are of correct size shape alignment elevation and position b The Contractor shall design forms and falsework to include assumed values of live load dead load weight of moving equipment
56. nsel Color chart is used to determine the soil color Strata changes are indicated by a solid line with the depth of the change indicated on the left side of the line If subtle changes within a soil type occur a broken line is used The Boring Termination or Auger Refusal depth is shown as a solid line at the bottom of the boring Graphic The graphic representation of the soil type is shown The graphic used for each soil type is related to the Unified Soil Classification chart A chart showing the graphic associated with each soil classification is included Remarks Remarks regarding borehole observations and additional information regarding the laboratory results and groundwater observations a While you cannot eliminate all such risks you can manage them Geotechnical Services Are Performed for Specific Purposes Persons and Projects Geotechnical engineers structure their services to meet the specific needs of their clients A geotechnical engineering study conducted for a civil engi neer may not fulfill the needs of a construction contractor or even another civil engineer Because each geotechnical engineering study is unique each geotechnical engineering report is unique prepared solely for the client No one excep you should rely on your geotechnical engineering report without first conferring with the geotechnical engineer who prepared it And no one not even you should apply the report for any purpose
57. o provide coverage of the concrete surfaces and edges with a 4 inch lap over adjacent absorptive covers c Moisture Retaining Cover The Contractor shall provide moisture retaining cover curing as follows Cover the concrete surfaces with the specified moisture retaining cover for curing concrete placed in the widest practicable width with sides and ends lapped at least 3 and sealed by waterproof tape or adhesive Immediately repair any holes or tears during the curing period using cover material and waterproof tape d Liquid membrane cover The Contractor shall provide liquid membrane curing as follows 1 Apply the specified membrane forming curing compound to damp concrete surfaces as soon as the water film has disappeared Apply uniformly in a 2 coat continuous operation by power spray equipment in accordance with the manufacturer s directions Re coat areas which are subjected to heavy rainfall within 3 hours after initial application Maintain the continuity of the coating and repair damage to the coat during the entire curing period 2 Do not use membrane curing compounds on surfaces which are to be covered with a coating material applied directly to the concrete or with a covering material bonded to the concrete such as other concrete liquid floor hardener waterproofing dampproofing membrane roofing flooring painting and other coatings and finish materials unless otherwise acceptable to the City of Stillwater e Curing formed su
58. of Stillwater or such other office noted in the Notice to Bidders Forms to be Used Bidder shall use the forms in this Bid Package or shall photocopy the forms and complete them No alterations can be made to the forms except to add additional signature lines as required Bids submitted with any other alteration or amendment of these forms may be considered non responsive This space intentionally left blank List of Documents Required As Revised by Addendum No 2 dated May 31 2013 H 2 ARTICLE 6 TIME OF COMPLETION 6 01 BIDDER agrees that the Work will be substantially complete in accordance with the Special Provisions and paragraph 2 03 of the General Conditions and completed and ready for final payment in accordance with the Special Provisions and paragraph 14 07 B of the General Conditions 6 02 BIDDER agrees to pay Liquidated Damages as provided for in the Special Provisions ARTICLE 7 ATTACHMENTS TO THIS BID 7 01 The following documents are attached to and made a condition of this Bid reference Section H List of Documents Required for This Bid A Required Bid security in the form of cashier s check or bond for 5 of bid amount Non Collusion Affidavit Business Relationships Affidavit Certificate of Non Discrimination List of three 3 references qualifications statement Manufacturer of pre engineered steel building or design engineer qualifications SAMPLE project submittals as described in the List of Documents Req
59. of foundation systems is subject to testing for soil bearing value by the testing laboratory Place concrete immediately after approval of foundation excavations Excavate and backfill as necessary to complete the concrete work Place concrete on subgrades that are well compacted to level and true grade Before concrete is placed in areas between slabs on grade previously placed recheck compaction of subgrade and if necessary re compact to avoid settlement of slabs at joints Seal extremely porous subgrades in a manner approved by the City of Stillwater Remove all ice debris and excess water from subgrades d Coordinate the installation of joint materials and moisture barriers with placement of forms and reinforcing steel e The installation of anchors inserts and sleeves for electrical mechanical plumbing heating ventilating and air conditioning work is subject to the inspection and approval of the supervisors of the particular trades involved Finish voids in sleeves and inserts temporarily with readily removable material f Notify the City of Stillwater 24 hours before placing concrete 16 Concrete conveying a General Handle concrete from the mixer to the place of final deposit as rapidly as practicable and in a manner which will assure that the specified quality of the concrete is obtained b Equipment Provide conveying equipment of proper size and design to insure a continuous flow of concrete to a delivery end Conveying equi
60. on Affidavit Certificate of Non Discrimination List of three 3 references Manufacturer of pre engineered steel building or design engineer qualifications Submit plan specification of one 1 EXAMPLE project with similar complexity and quality including the following Ee ee a structural specifications b foundation plan c floor plan d structural framing plan e electrical one line and panel plan f electrical outlet and lighting plan g architectural isometric rending 9 Submittal packages for specific equipment proposed for THIS BUILDING J J d ol up doors andpersomnekdoors a Pre engineered building manufacturer s conceptual design and specifications to include at a minimum e Load Parameters wind snow live etc e Architectural isometric rendering e Structural isometric sketch or framing plan and elevation views to include roof system e Material description to include structural steel wall sheathing and roof decking gt For the purpose of determining that a Bid is properly submitted Bidder should submit the properly completed and executed documents listed on this page Failure to submit a required document may be cause for rejection of the Bid List of Documents Required As Revised by Addendum No 2 dated May 31 2013 H 1 Forms Not in Packet If an item is listed on this page and the form is not included in this packet it is the Bidder s responsibility to obtain the form from the City
61. ontractor shall furnish to the City of Stillwater the certificates and test results described below The City of Stillwater may require additional tests and or verifications to insure the quality of concrete produced is as specified b Concrete 1 Mix design Provide mix design formula for the materials proposed for use in making concrete using the absolute volume method The design shall include material sources specific gravities and other pertinent data 2 Strength Prior to placing any concrete the compressive strength shall be verified by making three test cylinders using the proposed mix designs The cylinders shall be tested and the results provided with the mix design submittal c Reinforcing steel 1 Comply with requirements of the latest edition of the following codes and standards except as herein modified A American Welding Society AWS D1 4 1979 Standard Welding Code Reinforcing Steel B Concrete Reinforcing Steel Institute Recommended Practice for Placing Reinforcing Bars C Concrete Reinforcing Steel Institute Manual of Standard Practice for Reinforced Concrete Construction D American Concrete Institute ACI 318 Building Code Requirements for Reinforced Concrete E ASTM A615 Specifications for Deformed and Plain Billet Stee Bars for concrete Reinforcement F ACI315 Manual of Standard Practice for Detailing Reinforced Concrete Structures G ASTM A185 Specifications for Welded
62. operated on Form work concrete mix height of concrete drop vibrator frequency ambient temperature foundation pressures stresses lateral stability and other factors pertinent to safety of structure during construction c The Contractor shall provide shores and struts with positive means of adjustment capable of taking up form work settlement during concrete placing operations using wedges or jacks or a combination thereof and provide trussed supports when adequate foundations for shores and struts cannot be secured d The Contractor shall support form facing materials by structural members spaced sufficiently close to prevent deflection fit forms placed in successive units for continuous surfaces to accurate alignment free from irregularities and within allowable tolerances and provide camber in form work as required for anticipated deflections due to weight and pressures of fresh concrete and construction loads for long span members without intermediate supports e The Contractor shall provide temporary openings in wall forms column forms and at other locations necessary to permit inspection and clean out f The Contractor shall design form work to be readily removable without impact shock or damage to cast in place concrete surfaces and adjacent materials Adopted 2 21 2013 2200 6 of 16 Construction Standards Concrete CONSTRUCTION STANDARDS 2200 CONCRETE The Contractor shall provide form work sufficiently tight to prevent l
63. or approved equal The method of fastening the roof panels using screws washers and caps should be clearly shown on the submittal The components shall be fabricated and supplied by one manufacturer and shall be assembled by an approved assembler construction company Commercial grade 26 guage guttering and downspouts will be provided to match roof profile Following building erection and prior to covering of walls or roof with insulation the Contractor will provide for an inspection by the building manufacturer to certify construction craftsmanship for warranty Technical Specifications As Revised by Addendum No 2 dated May 31 2013 F 2 2 5 3 Design of the heating system utilizing ceiling mounted natural gas fueled heaters with separate thermostats and controls shall be provided to regulate the temperature in the equipment storage area and the parts storage area The intent is to keep the temperature in the equipment area near 50 degrees F and be set not to exceed 55 degrees F The temperature in the large bay area should stay well above freezing during freezing conditions in the winter 2 5 4 Design of the electrical system that is required to provide adequate lighting and convenience outlets for maintenance personnel to work on the equipment 220v Single phase power will be provided to the building site by the City 2 5 4 1 120v Receptacles with proper grounding shall be provided to power hand tools etc At selected locations 220V
64. ory Test Results Sede ao ous Atterberg l Boring Limits Passing Moisture Soil Description No No 200 po USCS Classification LL PL Sieve o B 2 0 5 2 0 22 16 6 36 3 7 8 Silty Clayey Sand SC 6 0 GEOTECHNICAL SITE CHARACTERIZATION The subsurface conditions at the site were evaluated by observation and classification of soil samples obtained from two 2 soil test borings drilled within proposed building area The conditions between the borings are assumed to be similar to the conditions encountered at the boring locations The following conditions and subsequent recommendations are based on the presumption that no significant changes in subsurface conditions occur between boreholes However anomalous conditions can occur due to the geologic conditions at the site and it will be necessary to verify the assumed conditions during site grading and foundation installation 6 1 SURFACE CONDITIONS At the time of the subsurface exploration the site was fairly level with an estimated grade differential on the order of 1 to 2 feet across the proposed project area 6 2 TERRACE DEPOSITS Terrace deposits were encountered in Borings B 1 and B 2 at the surface and continued to depths of about 1 to 2 feet The terrace deposits consisted of dense silty clayey sand SC SM The Standard Penetration Test SPT N values in the sandy soils were 22 and 33 bpf The sands were gray brown orange brown and orange in color The
65. outlets shall be provided to test electric motors etc All electric cables will be installed using conduits Provide and install three LUMAPRO 3 outlet 12 3 conductor 40 foot retractable cord reels or approved equals 2 5 4 2 All interior lights shall be turned on off using 3 way switches located at each of the two exterior service doors and both the bay side and storage area side of the parts storage area door The intent is that personnel can turn on off the lights from any door opening as they enter exit Interior lights will be Lithonia SPEC BEAM FGB26 T5HO Flourescent High Bay T5 s at 24 x 48 with 6 bulbs or approved equal Provide and install three 3 LUMAPRO 5w LED 40 foot cord hand lamp cord reel Grainger 2YKP9 or approved equal 2 5 4 3 Exterior area lighting will be provided above each bay door Lights will be Hubbell Perimaliter LED Wallpacks model PGM3 LED rated at 69 watts with glass refractors or approved equal Exterior bay door lights will be single pole switch controlled from inside of building adjacent to each door Exterior lighting for two side entrance personnel doors will be Hubbell Laredo LED LNC wallpacks model LNC 5LU 5K 5 LEDS with glass refractor and photo cell operation or approved equal 2 5 5 The submittal for the metal building proposed shall as a minimum show three or more views of the building as installed with gutters and downspouts If insulated windows are recommend to admit natural
66. pment will be subject to the City of Stillwater s approval c Truck mixers agitators and non agitating units and their manner of operation shall conform to the applicable requirements of ASTM C 94 d Belt conveyors Provide conveyors and discharge apparatus of a type which will not cause segregation Discharge long runs into a hopper e Chutes Provide metal or metal lined chutes and install to a slope not exceeding 1 vertical to 3 horizontal and not less than 1 vertical to 20 horizontal Chutes more than 20 feet long and chutes not meeting the slope requirements may be used provided they discharge into a proper hopper f Runways Provide runways or other means for wheeled equipment to convey concrete to placement points Do not support runways on reinforcement or wheel equipment over reinforcement g Pumps Do not pump concrete without the City of Stillwater s approval Any change in concrete mix necessitated by pumping must be approved by the City of Stillwater prior to placing concrete by this method 17 Placing concrete a Place concrete in compliance with the practices and recommendations of ACI 304 and as specified herein Do not place any concrete until the City of Stillwater has reviewed the results of the design mix 28 day test breaks and approval is given to proceed Adopted 2 21 2013 2200 10 of 16 Construction Standards Concrete CONSTRUCTION STANDARDS 2200 CONCRETE b Concrete shall be deposited so that the aggrega
67. presented in this report address the following e General site geology e Summary of existing surface conditions e A description of the subsurface conditions encountered at the soil test boring locations including a description of the groundwater conditions observed in the boreholes during drilling Long term monitoring was not included in our scope e Presentation of laboratory test results e Site preparation considerations including material types to be expected at the site treatment of unsuitable soils if encountered excavation considerations and surface drainage e Recommendations to be used for foundation design including appropriate foundation types bearing pressures and depths e Recommendations to be used for design of slabs on grade including modulus of subgrade reaction e Seismic Site Classification according to 2009 International Building Code e Presentation of expected total and differential settlements and recommendations to reduce the expected movements if appropriate e Compaction requirements and recommended criteria to establish suitable material for structural backfill 3 0 GENERAL SITE GEOLOGY According to the Reconnaissance of the Water Resources of the Enid Quadrangle North Central Oklahoma second printing 1991 the general geology at the site is underlain by Permian Age Wellington Formation This group is described as mainly fine grained sandstone and mudstone conglomerate 4 0 FIELD EXPL
68. pringdale AR Tulsa OK TABLE OF CONTENTS 1 0 SITE AND PROJECT DESCRIPTION s ci sccoeiet nese ottds are eeieteeitecvev tid ecuaxeeade 1 2 0 SCOPE OF SERVICES rror ier iepr ati Drean Sense dele uvbdse coieea docs DANAEA EES Eaa 2 2 0 GENERAL SITE GEOLOGY mce ea e i E E EEEE ESE Eiaa 3 AO FIELD EXPLORATION oireina ariaa dan Aa EEE EE Hes OR ESA TNE O EEN ALa aA laea 4 XO LABORATORY ANALY SIS ee eadun cients e iea A eaa eves es 5 5 1 DESCRIPTION OF SOILS VISUAL MANUAL PROCEDURE ASTM D 2488 5 5 2 NATURAL MOISTURE CONTENT ASTM D 2216 ssessssessssrsrssrrsrssesrssrsr gt 5 5 3 ATTERBERG LIMITS ASTM D 4318 siicsscvva iceaaivectuchiestemiresdethecevecieeateare 5 5 4 PARICLE SIZE ANALYSIS ASTM D 422 002 cevicsocsvedesssaestenvenbeassastaaonsesteactins 5 5 5 SUMMARY OF LABORATORY TEST RESULTS 0 eee eeccneeeeceeeeeeeeeecueeaees 6 6 0 GEOTECHNICAL SITE CHARACTERIZATION cc ssscsessesesecseveversesereeeaeees 7 6 1 SURFACE CONDITIONS eiere aoaaa ee EE AETA REEE EARE EELEE auntie tenes EES 7 6 2 TERRACE DEPOSITS enci er E a a aa neue a aE RDE EESE 7 6 3 INETERLAYERED SANDSTONE AND LEAN CLAY eeesreseresrirerersesresen 7 6 4 HIGHLY WEATHERED MUDSTONE UNIT ec eeeeecee nec neceeeeeeecncnseaeeaeeaeens 7 BS GROUNDWATER rerea eaa ee a a a a n Ea eaaa 8 7 0 SITE GRADING CONSIDERATIONS assssssseesrsrersrsssenrensinarsnrranosessrersrresrerss 9 Roh INIHAC SITE PREPARA NON Gasiscuncastotacattaastun daca cakine E EE EARE EER 9 1 2
69. provided with the drawings as part of the submittal process As a minimum the following items shall be submitted 2 5 1 Design of the concrete slab and the foundation to support the columns of the proposed metal building Concrete will be per city Construction Standards Section 2200 Concrete adopted 2 21 13 Building slab foundation will have a monolithic perimeter stem wall above slab elevation to keep the metal siding off of the grade and minimize steel deterioration Engineer approved structural earth fill material will be used to backfill any earthwork on site to bring the facility to needed elevation Recommendations from the geotechnical evaluation prepared by Building amp Earth dated May 30 2013 will be used for the basis of design 2 5 2 Design of the industrial type building using commercial grade ASTM A36 channels angles plates bars ASTM A992 W shapes ASTM A500 structural tubing and ASTM A53 tubing red iron structural frame and roof system The wall sheeting will be 24 auge aluminum zinc alloy coated steel sheet siding ASTM A792 A792M Class AZ50 coating grade 40 structural quality or approved equal with two coat fluoropolymer finish in addition to the manufacturer s prime adhesive The design should take into consideration the wind and snow loadings Roof pitch will be a minimum of 1 12 anda maximum of 3 12 The roof decking will be VULCRAFT Type B 24 gauge or better mechanically seamed wide rib decking
70. rete after the foundation is completed Wherever possible the foundation concrete should be placed neat using the sides of the excavations as forms Where this is not possible the excavations created by forming the foundations must be backfilled with suitable structural fill and properly compacted The building pad should be sloped to drain away from the building foundations Roof drains should be routed away from the foundation soils 13 9 0 FLOOR SLABS Site grading recommendations presented in Section 7 of this report should be followed to provide for subgrade conditions suitable for support of grade supported slabs All slabs must be supported on a properly prepared subgrade that was evaluated by the geotechnical engineer prior to base stone placement At a minimum the floor slabs should be supported on a four inch thick compacted layer of free draining granular material such as ASTM No 57 stone The purpose of this layer is to serve as a leveling course and act as a capillary break for moisture migration through the subgrade soil An effective modulus of subgrade reaction of 130 pci can be used in the design of grade supported building floor slabs Depending on the proposed floor covering consideration should be given to the use of a polyethylene vapor barrier 14 10 0 SEISMIC SITE CLASSIFICATION Based on the 2009 Edition of the International Building Code the subsurface conditions encountered in the borings
71. rfaces The Contractor shall cure formed concrete surfaces including the undersides of girders beams supported slabs and other similar surfaces by moist curing with the forms in place for the full curing period or until forms are removed If forms are removed prior to specified curing period continue curing by one of the methods specified in Curing Unformed Surfaces f Curing unformed surfaces The Contractor shall immediately after finishing operation is complete commence curing unformed surfaces by one of the following methods 1 Continuously sprinkle or pond surface with water Use this method for footings only 2 Cover surface with 2 inches of moist sand Keep sand moist throughout the curing period Use this method for footings only 3 Cover surface with moist fabric Keep fabric moist and in direct contact with surface so that a film of water remains on the surface throughout the curing period This method may be used on all concrete surfaces 4 Cover surface with curing paper Lap sides and ends at least 3 inches and seal with tape This method may be used on all concrete surfaces 5 Apply a uniform coat of liquid curing compound in accordance with manufacturer s recommendations This method may be used on all concrete surfaces except those scheduled to receive bonded materials Do not use this method in hot weather g Temperature of concrete during curing 1 When the atmospheric temperature is 40 F and below the Contractor
72. round storage tanks or regulated contaminants Unanticipated environmental problems have ied to numerous project failures 1 you have not yet obtained your own geoen vironmental information ask your geotechnical consultant for risk man agement guidance Do not rely on an environmental report prepared far someone else Obtain Professional Assistance To Deal with Meld Diverse strategies can be applied during building design construction operation and maintenance to prevent significant amounts of mold from growing on indoor surfaces To be effective all such strategies should be devised for the express purpose of mold prevention integrated into a com prehensive plan and executed with diligent oversight by a professional mold prevention consultant Because just a smait amount of water or moisture can lead fo the development of severe mold infestations a num ber of mold prevention strategies focus on keeping building surfaces dry While groundwater water infiltration and similar issues may have been addressed as part of the geotechnical engineering study whose findings are conveyed in this report the geotechnical engineer in charge of this project is not a moid prevention consultant none of the services per formed in connection with the geotechnical engineer s study were designed or conducted for the purpose of mold preven tion Proper implementation of the recommendations conveyed in this report will not of itself be sufficient te prevent
73. ructural fill If existing utility lines remain in place we recommend that the condition of the backfill material be thoroughly evaluated by means of test pit excavations Unsuitable backfill materials encountered in the utility trenches should be undercut and replaced with properly compacted structural fill During site preparation activities the contractor should identify materials that will be used as fill and provide samples to the testing laboratory to evaluate the suitability for use as structural fill and to determine appropriate moisture density curves 7 2 MOISTURE SENSITIVE SOILS The silty clayey sand encountered in the borings exhibited low plasticity characteristics with significant silt fraction These types of materials are sensitive to slight increases in soil moisture contents The contractor should anticipate some difficulty during the earthwork phase of this project if moisture levels are moderate to high during construction Increased moisture levels will soften the subgrade soils and the soils will lose stability under the influence of repeat construction traffic loading 9 7 3 SUBGRADE PREPARATION AND EVALUATION After initial site preparation the proposed construction area should be carefully proofrolled with a heavy rubber tired vehicle prior to fill placement or building construction The proofrolling will help densify the near surface soils and identify unstable subgrade areas The project geotechnical engineer or
74. s plans and specifications Contractors can also misinterpret a geotechnical engineering report Reduce that risk by having your geotechnical engineer participate in prebid and preconstruction conferences and by providing construclion observation Do Net Redraw the Engineer s Logs Geotechnica engineers prepare final boring and testing jogs based upon their interpretation of field logs and laboratory data To prevent errors or omissions the logs included in a geotechnical engineering report should never be redrawn for inclusion in architectural or other design drawings Only photographic or electronic reproduction is acceptable but recognize that separating logs from the report can elevate risk i Give Contractors a Complete Report and Guidance Some owners and design professionals mistakenly believe they can make contractors liable for unanticipated subsurface conditions by limiting what they provide for bid preparation To heip prevent costly problems give con tractors the complete geotechnical engineering report but preface it with a clearly wrilfen letter of transmittal in that fetter advise contractors thal the report was not prepared for purposes of bid development and that the report s accuracy is limited encourage them to confer with the geotechnical engineer who prepared the report a madest fee may be required and or to conduct additional study to obtain the specific types of information they need or prefer A prebid con
75. seepage not be AL ak ee 8 encountered while drilling 5 berini and boring dry upon CETERE Dt completion ae SAMPLETYPE X Split Spoon Eee arrama ees N VALUE STANDARD PENETRATION RESISTANCE AASHTO T 206 REC RECOVERY MOISTURE PERCENT NATURAL MOISTURE CONTENT RQD ROCK QUALITY DESIGNATION AYA GROUNDWATER LEVEL IN THE BOREHOLE UD UNDISTURBED Qu UNCONFINED COMPRESSIVE STRENGTH ESTIMATE FROM POCKET PENETROMETER TEST y Birmingham Aim Huntsville ALm Auburn AL Columbus GAm Savannah GAW Raleigh NG Tulsa OK Springdale AR Shreveport LAs Louisville KY Niceville FL BUILDING amp EARTH SCIENCES INC BORING LOG DESCRIPTION Building amp Earth Sciences Inc Building amp Earth used the gINT software program to prepare the attached boring logs The gINT program provides the flexibility to custom design the boring logs to include the pertinent information from the subsurface exploration and results of our laboratory analysis The soil and laboratory information included on our logs is summarized below Depth The depth below the ground surface is shown Sample Type The method used to collect the sample is shown The typical sampling methods include Split Spoon Sampling Shelby Tube Sampling Grab Samples and Rock Core A key is provided at the bottom of the log showing the graphic symbol for each sample type Sample Number Each sample collected is numbered sequentially Blows per 6 REC RQD W
76. shall maintain the concrete temperature between 50 F and 70 F continuously throughout the curing period When necessary make arrangements before concrete placing for heating covering insulating or housing as required to maintain the specified temperature and moisture conditions continuously for the concrete curing period Do not use combustion the first 24 hours of curing without taking precautions to prevent exposure of the concrete to exhaust gases Provide cold weather protection complying with the requirements of ACI 306 Adopted 2 21 2013 2200 13 of 16 Construction Standards Concrete CONSTRUCTION STANDARDS 2200 CONCRETE 2 When the atmospheric temperature is 80 F and above or during other climatic conditions which will cause too rapid drying of the concrete the Contractor shall make arrangements before the start of concrete placing for the installation of wind breaks or shading and for fog spraying wet sprinkling or moisture retaining covering Protect the concrete continuously for the concrete curing period Provide hot weather protection complying with the requirements of ACI 305 Maintain temperature as uniformly as possible and protect from rapid atmospheric temperature changes Avoid temperature changes in concrete which exceed 5 degrees F in any one hour and 50 degrees F in any 24 hour period h Protection from mechanical injury 1 During the curing period protect concrete from damaging mechanical disturbances
77. shoring underneath and no construction load shall be supported upon nor any shoring removed from any part of the structure under construction until that portion of the structure has attained sufficient strength to support safely its weight and the loads placed thereon D Form facing material may be removed four 4 days after placement only if shores and other vertical supports have been arranged to permit removal of form facing material without loosening or disturbing shores and supports Re use of forms 1 The Contractor shall form lumber which is to be used a second time shall be free from bulge or warp and shall be thoroughly cleaned and repaired Split frayed delaminated or otherwise damaged form facing material will not be acceptable The Contractor shall apply new form coating compound material to concrete contact surfaces as specified for new form work 2 When forms are extended for successive concrete placement the Contractor shall thoroughly clean surfaces remove fins and latence and tighten forms to close all joints Align and secure joints to avoid offsets Do not use patched forms for exposed concrete surfaces except as acceptable to the Owner s Representative j Concrete surface repairs 1 Patching defective areas A The Contractor shall repair and patch all defective areas with cement mortar immediately after removal of forms but only when directed by the City of Stillwater B The Contractor shall cut out honeyco
78. sories in contact with the form work shall be galvanized steel or plastic e The placing and fastening of reinforcement in each section of the work shall be accepted by the City of Stillwater before any concrete is deposited in the section f Care shall be taken not to disturb the reinforcement after the concrete has taken its initial set g Reinforcing steel shall be overlapped to fully develop the reinforcing h Splicing bars shall be performed in accordance with ACI Code 318 for minimum lap Splice locations shall be at mid span on all top bars and at the supports for all bottom bars i The minimum coverages for reinforcement shall be maintained as stated in ACI Code 318 14 Anchors and inserts a Anchor bolts castings steel shapes conduit sleeves masonry anchorage and other materials that are to be embedded in the concrete shall be accurately positioned in the forms and securely anchored b Unless installed in pipe sleeves anchor bolts shall have sufficient threads to permit a nut to be installed on the concrete side of the form or template A second nut shall be installed on the other side of the form or template and the two nuts shall be adjusted so that the bolt will be held rigidly in proper position c Inserts shall be clean when installed After installation surfaces not in contact with concrete shall be cleaned of concrete spatter and other foreign substances d The Contractor shall coordinate the installation of all a
79. t 3 Installation A Concrete mixing 1 Experimental concrete mixes a The Contractor shall make experimental mixes prior to the placing of the concrete and at any time during the progress of the work when necessary to demonstrate that the concrete will meet these specifications Materials for making experimental mixes shall be furnished by the Contractor and these materials shall be identical with those intended for use in the work The cost of the materials as well as the costs of crushing test specimens made from the experimental mix shall be borne by the Contractor and shall be included in the price bid for concrete 2 On site mixing a General The Contractor shall mix concrete in a batch mixer conforming to requirements of the mixer manufacturer s Bureau of the Associated General Contractors of America Mixer shall bear the manufacturer s rating plate indicating rated capacity and recommended revolutions per minute operate mixer in accordance with these recommendations and use only mixers that are equipped with a suitable charging hopper water storage tank water measuring device and are capable of thoroughly mixing the concrete into a uniform mass within the specified mixing time and of discharging the mix without segregation b Admixtures After approved for use the Contractor shall dispense liquid admixtures by means of an automatic dispenser or similar metering device weigh or measure by volume powdered admixtures as recommended
80. te surfaces are exposed to view the Contractor shall not use form ties which when removed will leave a depression larger than one 1 inch in diameter The Contractor shall use water seal ties in concrete exposed to hydrostatic pressure which conform to ACI 301 and 347 a a Metal inserts shall be used for anchorages of materials or equipment to concrete construction not supplied by other trades and as required for the work Threaded inserts of malleable cast iron furnished complete with full depth bolts to the proper size shall be used unless otherwise noted b b Adjustable wedge inserts of malleable cast iron complete with bolts nuts and washers and bolt size shall be used C Screen chairs Metal or wood screen chairs shall not be used d Corner chamfer Chamfers shall be mill run white pine solid material or preformed PVC at all exposed corners of columns walls and beams H Concrete Curing Compounds TtT Absorptive cover Burlap cloth shall be made from jute or kenaf weighing approximately 9 oz per sq yd complying with AASHTO M 182 Class 3 2 2 Moisture retaining cover Moisture retaining covers shall be one of the following complying with ASTM C 171 a a Waterproof paper b b Polyethylene film c c Polyethylene coated burlap 3 3 Membrane forming curing compound Membrane forming curing compounds shall conform to ASTM C 309 Type with white fugitive dye unless other type acceptable to the City of Still
81. tes are not segregated Conveying concrete shall occur to prevent segregation of the aggregate Conveying shall be by belt conveyor tremmie chutes or pumps Vertical drops in excess 5 feet shall be conveyed using one of these techniques Chutes shall not be used if the slopes are greater than 3 1 c Deposit concrete in forms in horizontal layers not deeper than 24 inches and in a manner to avoid inclined construction joints Where placement consists of several layers place each layer while preceding layer is still plastic to avoid cold joints d Remove temporary spreaders in forms when concrete placing has reached the elevation of such spreaders e The concrete shall be deposited in continuous horizontal layers so that no concrete will be allowed to harden and cause the formation of seams or planes of weaknesses Concrete placement shall occur at a rate to keep the placed concrete integral with the new concrete Work shall be arranged in order that each part of the work shall be placed as a unit if this is possible Where necessary to stop placing concrete the work shall be brought up in level courses and against a vertical stop board f Consolidate concrete placed in forms by mechanical vibrating equipment supplemented by hand spading rodding or tamping so that the concrete is thoroughly worked around reinforcement and embedded item and into the corners of forms Consolidate each layer of concrete with previously placed layers in a manner that
82. tic surface Do not disturb the slab surfaces prior to beginning finishing operations 18 Cold weather placement a Concrete placed during cold weather shall conform to ACI Code 306 1 90 Standard Specification for Cold Weather Concreting 19 Hot weather placement a Concrete placed during hot weather shall conform to ACI Standard 305 1 06 Specification for Hot Weather Concreting The work shall be performed entirely at the Contractor s risk 20 Bonding a Roughen surface of set concrete at all joints except where bonding is obtained by use of a concrete bonding agent and clean surfaces of laitance coatings loose particles and foreign matter Roughen surfaces in a manner to expose boned aggregate uniformly and to not leave latence loose particles of aggregate or damaged concrete at the surface b Prepare for bonding of fresh concrete to new concrete that has set but is not fully cured as follows 1 At joints between footings and walls and between walls and beams or slabs they support and elsewhere unless otherwise specified herein dampen but do not saturate the Adopted 2 21 2013 2200 11 of 16 Construction Standards Concrete CONSTRUCTION STANDARDS 2200 CONCRETE roughened and cleaned surface of set concrete immediately before placing fresh concrete 2 At joints in exposed work at vertical joints in walls at joints in girders beams supported slabs and other structural members and at joints designed to contain liq
83. typically postpone grading operations during wet weather to wait for conditions that are more favorable Contractors can typically disk or aerate the upper soils to promote drying during intermittent periods of favorable weather When deadlines restrict postponement of grading operations additional measures such as undercutting and replacing saturated soils or stabilization can be utilized to facilitate placement of additional fill material 11 8 0 FOUNDATION RECOMMENDATIONS Structural loads were not provided however we assumed that the proposed building will be lightly loaded with maximum column loads and bearing wall loads in the range of 20 to 40 kips and 2 to 3 kips per linear foot klf respectively Based on the information provided and the results of our field exploration the subsurface conditions are suitable to support the proposed building on shallow footings Footings bearing in Interlayered sandstone and lean clay unit can be dimensioned for a maximum net allowable bearing pressure of 3 000 pounds per square foot psf Total settlement of footings designed and constructed as recommended above is estimated to be less than inch Differential settlement of footings designed and constructed as recommended above should be within the tolerable limits addressed above Differential settlement between the proposed building addition and the existing structures could approach inch Consideration should be given to the use of expansio
84. uids dampen but do not saturate the roughened and cleaned surface of set concrete and apply a liberal coating of neat cement grout 3 Use neat cement grout consisting of equal parts Portland cement and fine aggregate by weight and not more than 6 gallons of water per sack of cement Apply with a stiff broom or brush to a minimum thickness of 1 16 Deposit fresh concrete before cement grout has attained its initial set 4 In lieu of neat cement grout bonding grout may be commercial bonding agent Apply to cleaned concrete surfaces in accordance with the printed instructions of the bonding material manufacturer 21 Construction joints Construction joints shall be located as shown on the plans and at other points as may be necessary during construction provided that the location and nature of additional joints shall be accepted by the City of Stillwater In general joints shall be located at points of minimum shear shall be perpendicular to the principal lines of stress and shall have suitable keys having areas of approximately one third 1 3 of the area of the joints When placing against a construction joint the surface of the concrete previously placed shall be thoroughly cleaned of dirt scum laitance or other soft material and shall be roughened The surface shall then be thoroughly washed with clean water and covered with at lease 2 inches of cement mortar after which concreting may proceed Mortar shall be placed in a manner that will
85. uired Submittal packages for specific equipment proposed for THIS BUILDING as described in the List of Documents Required As Revised by Addendum No 2 dated May 31 2013 SUBMIT ONE ORIGINAL AND TWO COPIES OF ALL DOCUMENTS REQUIRED QOmmoom ARTICLE 8 DEFINED TERMS 8 01 The terms used in this Bid with initial capital letters have the meanings indicated in the Instructions to Bidders the General Conditions and the Supplementary Conditions ARTICLE 9 BID SUBMITTAL 9 01 This Bid is submitted by OAn Individual Name typed or printed By SEAL Individual s Signature doing business as Business address Telephone number FAX number SS or FED D Bid Form As Revised by Addendum No 2 dated May 31 2013 J 5 ATTACHMENT 1 Revised Per Addendum No 2 dated May 31 2013 City of Stillwater Equipment Storage Building at the WTP Project 13WG02 Exhaust Fans 3 Total minimum ii eae Iz ii li i lil li lii li I I I I I I I I I I i B Recepticles i RIR El Lights Lights Lights Lights we 3 5 8 2 5 O g Parts R 220 V Recepticles 2 2 220 V Recepticles R R 5 s R o cz Storage Gas and 2 Area Power to Elec Panel Site by il Owner Lights tights Lights Lights D IRIRI D Auto ON OFF i Auto ON OFF L s3 i Pees 2 H S3 53 ee E E x 3 Door with 4 Deep Awning H 3 Door 3 Door with 4 Deep Awning z i z 3 ae p I R A Roll up Door 14 W x 16 H i Roll up Door 1
86. water 4 4 Liquid curing sealing hardening compound The following list of materials is not intended to be a complete list of materials and work required but a guide to the type quality and finish required for various surfaces The list of products below is intended only to set a standard of quality Product Manufacturer Eucocure Euclid Chemical Co Masterseal Master Builders Polyclear Upco Chemical USM Corp Dress amp Seal L amp M Construction Chemicals Triple Seal Protex Industries Clear Bond Guardian Chemical Co Cure amp Seal Symons Corporation Kure N Seal Sonneborn Building Products Special notes e Curing compounds containing oil or wax shall not be used Adopted 2 21 2013 2200 4 of 16 Construction Standards Concrete CONSTRUCTION STANDARDS 2200 CONCRETE e Allow concrete to thoroughly dry following rain e Use form release agents which will not transfer to the concrete Water Stops Provide 3 1 4 polyvinyl chloride PVC water stops at construction joints and other joints of type shown on drawings J Preformed Expansion Joint Fillers Preformed expansion joint fillers shall conform ASTM D 1751 and be non extruding and resilient type K Radius Former Radius former shall be PVC L Flowable Fill 1 Specify strength limitations to allow for diggable flowable concrete 2 Flowable Fill admixture shall be provided with manufacturers instructions regarding installation requirements and strength limitations Par
87. water Surface defects as such include color and texture irregularities cracks spalls air bubbles honeycomb rock pockets and holes left by the rods and bolts fins and other projections on the surface and stain and other discoloration that cannot be removed by cleaning The Contractor shall repair concealed formed concrete surfaces where possible that contain defects that adversely affect the durability of the concrete If defects cannot be repaired remove and replace the concrete having defective surfaces Surface defects as such include cracks in excess of 0 01 inch wide cracks of any width and other surface deficiencies which penetrate to the reinforcement or completely through non reinforced sections honeycomb rock pockets holes left by tie rods and bolts and spalls except minor breakage at the corner 3 Repair of unformed surfaces A Adopted 2 21 2013 The Contractor shall test unformed surfaces such as monolithic slabs for smoothness and to verify surface plane to the tolerances specified for each surface and finish The Contractor shall correct low and high areas as herein specified Test unformed surfaces sloped to drain for trueness of slope in addition to smoothness using a template having the required slope Correct high and low areas as herein specified Repair finished unformed surfaces that contain defects which adversely affect the durability of the concrete Surface defects as such include cracking crac
88. y Ewo ZGOMEL efotd d M 341 e Buippng oGemg tuawdnbg aremmg jo 45 LNAWHOWVLEY PNAS fo ND amp q papiaosd unig ang ONIMVAA SIHL HOnNdONd OL adasn JONJAAAAA BUILDING amp EARTH Geotechnical Environmental and Materials Engineers LOG OF BORING Designation B 1 Sheet 1 of 1 Project Name Proposed Metal Building Water Treatment Plant Project Number OK13092 10828 E Newton St Suite 111 Tulsa OK 74116 Office 918 439 9005 Fax 918 439 9255 www BuildingAndEarth com Project Location Stillwater Oklahoma Date Drilled 5 20 13 Drilling Method Solid Stem Auger Weather Conditions Equipment Used Giddings Surface Elevation Hammer Type Automatic Drill Crew Data Testing Inc Boring Location East Hole Logged By Teja Maganti E LT Ze G N Vaiue O Ells a 10 20 30 40 EN l ziz amp A Quisi A g xm joe Fee 1 2 3 4 i x E z See 1 Atterberg Limits 4 SOIL DESCRIPTION lt REMARKS Alaz 2 20 40 60 80 T lt Z Moisture az 20 40 60 80 i 3 3 SILTY CLAYEY SAND SC SM q 9 gtay brown and orange pockets with 4 i sandstone fragments trace to low plasticity 15 15 18 e moist dense J INETERLAYERED SANDSTONE AND LEAN CLAY orange tan and brown low plasticity moist poorly cemented s2 2 26 18 43 sot orange brown and yellow with

Download Pdf Manuals

image

Related Search

Related Contents

NewAir AF-1000R Use and Care Manual    KitchenAid KFCK03IT User's Manual  fornos turbos elétricos  Controlador PID    Danby DMW099WDB User's Manual  Page 1 Page 2 ハイバックフロント子供のせ FBG  GDO600 - Leroy Merlin  LAVINA® 30G-S User Manual - Polished Concrete Solutions  

Copyright © All rights reserved.
Failed to retrieve file