Tripp Lite 220/230/240V AC / 12W Power Supply User Manual
Contents
1. Communications Includes an RS 232 DB9 female connector an AS 400 DB9 female connector a dry contact DB9 female connector and an accessory slot Connections Input Terminal Block 60A Output Terminal Block 60A Physical Specifications Power Module Dimensions H x W x D 56 5 x 28 x 63 cm 22 2 x 11 x 24 8 in Power Module Shipping Weight 46 kg 101 3 Ib Battery Module Dimensions H x W x D 44 5 x 13 3 x 57 2 cm 17 5 x 5 25 x 22 5 in Battery Module Shipping Weight 86 kg 189 6 Ib Backup times are expandable with additional Battery Modules model BP240V10RT3U sold separately The policy of Tripp Lite is one of continuous improvement Specifications are subject to change without notice TRIPP LITE 1111 W 35th Street Chicago IL 60609 USA 773 869 1234 USA 773 869 1212 International www tripplite com 2009XXXXX 93 2228 EN
2. 1 2 second BATTERY LOW BATT XXV XX UNDER Continuous Beep BATTERY UNDER SHUT DOWN Operation Normal Conditions TURNING THE UPS ON Make sure the UPS is properly installed see Installation section and the Manual Bypass Key is set to NORMAL Turn the AC Input and Bypass AC Input Circuit Breakers ON If your AC input is providing power normally within your selected range see Input Voltage Selection and Specifications your connected load will energize However the UPS s inverter is not yet on Press the front ON OFF switch ON to begin inverter operation If your AC input is not providing power normally you have the option of starting from battery Your battery must be at least partially charged for this operation to succeed Press and hold both the Battery Start switch and the ON OFF switch for three seconds to start your UPS in ON BATTERY mode Note that some electronic equipment may draw more amps during startup when starting from battery consider reducing the initial load on the UPS The UPS will perform a brief self test and show the results on the LCD Display See Self Test section for display sequence After a successful self test the UPS will provide AC power from the inverter to your load TURNING THE UPS OFF e Press the front ON OFF Switch OFF Your load will still be energized The inverter is now off but your UPS is not fully deactivated The LCD Display will show ON BYPASS e
3. BP240V10RT3U Model SU10K3 1X Includes Power Module Model SU10K3 1INTPM Series AGPS4984 e Battery Module Model BP240V10RT3U Series AGBP240V7RT3U Input Input Voltage 270 485V Y 304W Input Frequency 50 60 Hz 3 Hz selectable Input Current 15A Inrush Current lt 200A Power Factor Full Load gt 0 95 Efficiency Full Load On Line gt 90 Circuit Breakers 32A 3 pole AC Input Breaker 63A 1 pole Bypass AC Input Breaker Output VA 10000 Watts Power Factor 0 8 8000 Waveform On Line Sinewave Waveform On Battery Sinewave Output Voltage RMS 220 230 240V AC 102W Output Frequency 50 60 Hz 0 2 Hz on battery Voltage Regulation 2 Max Harmonic Distortion Non Linear Full Load lt 3 Overload Capabilities lt 102 continuous 102 125 1 min 125 150 30 sec gt 150 2 sec Short Circuit Capability 2160A Crest Factor 3 1 Battery Battery Type 12V 9 AH Battery Quantity 20 Protection 2x 30A 600V fuse Typical Backup Time Full Load 6 min Typical Backup Time Half Load 18 min Operation On Line Transfer Time Line to Battery Battery to Line 0 ms Audible Noise Full Load 1 meter lt 55 dBA Indicators Includes an LCD Display and LEDs AC Line In AC to DC DC to AC AC Output Battery Back Up Bypass
4. LCD and stops supplying output power to its load If power levels return to an acceptable level the UPS resumes supplying power to the load and its LCD reports that output voltage was too high or too low at one time but has returned to nominal Bypass Voltage Condition LCD Display Message gt 15 Higher than Nominal BYPASS HI NO O P gt 20 Lower than Nominal BYPASS LO NO O P Was Too High Now Nominal BYPASS WAS HI Was Too Low Now Nominal BYPASS WAS LO Operation Special Conditions Meme OPERATION ON OVERLOAD When the UPS detects an output overload it will commence a countdown the length of time depending on the severity of the overload If the UPS is still overloaded at the end of the countdown the UPS will automatically shut down and go into Bypass Mode Overload Condition LCD Display Message Countdown to Shutdown 102 125 OVERLOAD 102 1 minute LOAD XXX X XXKW 125 150 OVERLOAD 125 30 seconds LOAD XXX X XXKW gt 150 OVERLOAD 150 2 seconds LOAD XXX X XXKW BATTERY CHARGE WARNINGS Since your UPS can provide battery backup only for as long as the batteries remain charged these warnings should be acted on immediately Battery Charge Warning LCD Display Message Battery charge nearly depleted BATTERY LOW Low battery shutdown LOW BATTERY SHUT DOWN OPERATION UNDER SHUTDOWN Your UPS will shut down and the LCD will display a mess
5. MODE OPERATION ON BATTERY MODE OPERATION 4 ON INVERTER ON BATTERY LOAD XXX X XXKUW LOAD XXX X XXKU 4 PRESS SELECT KEY PRESS SELECT KEY ON INVERTER ON BATTERY IN R XXXV XX XHzZ IN R XXXV_XX XHz J PRESS SELECT KEY PRESS SELECT KEY ON INVERTER ON BATTERY IN S XXXV T XXXV IN S XXXV T XXXV 4 PRESS SELECT KEY l PRESS SELECT KEY ON INVERTER ON BATTERY OUT XXXV XX XHz OUT XXXV XX XHz g PRESS SELECT KEY PRESS SELECT KEY ON INVERTER ON BATTERY BATT XXXV XXX BATT XXXV XXX PRESS SELECT KEY PRESS SELECT KEY ECONOMY MODE OPERATION ON BYPASS MODE OPERATION ECONOMY MODE ON BYPASS LOAD XXX X XXKW LOAD XXX X XXKW PRESS SELECT KEY li PRESS SELECT KEY ECONOMY MODE ON BYPASS IN R XXXV XX XHz BYPS XXXV XX XHZz 4 PRESS SELECT KEY l PRESS SELECT KEY ECONOMY MODE ON BYPASS IN S XXXV T XXXV OUT XXXV XXX 1 PRESS SELECT KEY PRESS SELECT KEY ECONOMY MODE OUT XXXV XX XHz 4 PRESS SELECT KEY ECONOMY MODE BATT XXXV XXX PRESS SELECT KEY Operation Special Conditions OPERATION ON BYPASS VOLTAGE OUT OF RANGE While in Bypass Mode the UPS monitors the input voltage which on Bypass equals the output voltage If the output voltage passes out of an acceptable range between 15 higher and 20 lower than nominal the UPS displays the condition on its
6. not dispose of the batteries in a fire as this could cause the battery to explode Because the batteries present a risk of electrical shock and burn from high short circuit current batteries should be changed only by trained service personnel observing proper precautions Consult your battery module manual before proceeding Remove watches rings and other metal objects Use tools with insulated handles Wear rubber gloves and boots Do not lay tools or metal parts on top of the batteries Do not short or bridge the battery terminals with any object Disconnect the charging source prior to connecting or disconnecting battery terminals Determine if the batteries are inadvertently grounded If inadvertently grounded remove the source of the ground Contact with any part of a grounded battery can result in electrical shock The likelihood of such shock will be reduced if such grounds are removed during installation and maintenance Connect only Tripp Lite battery packs to your UPS s external battery connectors Do not operate your UPS without batteries Fuses should be replaced only by factory authorized personnel Blown fuses should be replaced only with fuses of the same number and type Potentially lethal voltages exist within this unit as long as the battery supply is connected Service and repair should be done only by trained personnel During any service work the UPS should be turned off or put into manual bypass During hot swap batter
7. your UPS to a workstation or server It uses RS 232 communications to report UPS and power conditions It is used with Tripp Lite software and the included RS 232 Cable to monitor and manage network power and to automatically save open files and shut down equipment during a blackout See Communications for details 8 Dry Contact Interface Port This female DB9 port sends contact closure signals to indicate line fail and low battery status See Communications for details 9 Accessory Slot Remove the small cover panel and use optional accessories to remotely control and monitor your UPS Contact Tripp Lite Customer Support for more information and a list of available SNMP network management and connectivity products Rear Panels continea 10 Battery Start Switch This momentary rocker switch allows you to cold start your UPS and use it as a stand alone power source when utility supplied AC power is not present The switch enables the UPS s DC AC Inverter Before cold starting your UPS make sure your power module and external battery module s are properly installed Press and hold the Battery Start Switch and then press the ON OFF switch to turn your UPS ON To turn it OFF after cold start press the ON OFF Switch 11 AC Input Breaker Controls input power to the UPS during normal operation 12 Bypass AC Input Breaker Controls input power to the UPS during BYPASS operation 13
8. Connect the battery module to the power module Consult the owner s man ual that came with your battery module Fully insert the connector on the end of the battery module s cable into the connector on the rear panel of the i power module Small sparks may occur this is normal NOTE the power module does not contain internal batteries and will not start until a battery module is connected The battery modules are fully charged prior to ship ping However before expecting full backup capability particularly if the battery module has been stored for an extended period after the UPS sys tem is connected to a utility power source allow the battery module to recharge for 12 hours Once the UPS system is in use it will charge the bat teries and maintain the charge level automatically If needed connect addi tional battery modules in a daisy chain with each module s cable inserted ig into the previous module s connector a Battery Module Power Module Rear Panel Rear Panel BATTERY CONDITION VERIFICATION When the UPS is operating from battery power the alarm and LCD Display will both alert you to the UPS battery s charge condition Battery Charge Condition Alarm LCD Display FULL Short Beep every 2 seconds ON BATTERY BATT XXV XX LOW Short Beep every
9. Owner s Manual SmartOnline 3 Phase 10kVA Intelligent True On Line UPS System Tower Input Voltage Phase 270 485V AC Y 304W Output Voltage Phase User Selectable 220 230 240V AC 102W For all UPS system modules power module and battery module sold either separately or combined Select UPS system modules may include separate instruction or warning sheets which should be used in conjunction with this manual Register on line for a chance to win a FREE Tripp Lite product www tripplite com warranty E C E C E E Operation Normal Conditions aaaaaalllulululul EE Co ene u ululu a Mspeciicatons aaa llululul Espa ol Fran ais Deutsche Pycckn 16 31 46 61 TRIPP LITE POWER PROTECTION 1111 W 35th Street Chicago IL 60609 USA 773 869 1234 www tripplite com Copyright 2004 Tripp Lite All rights reserved SmartOnline is a trademark of Tripp Lite Important Safety Warnings SAVE THESE INSTRUCTIONS This manual contains important instructions and warnings that should be followed during the installation and maintenance of all Tripp Lite SmartOnline 3 Phase UPS Systems and their batteries UPS Location Warnings e Install your UPS indoors away from heat direct sunlight dust and excess moisture or other conductive contaminants e Install your UPS in a structurally sound area Your UPS is extremely heavy take care when moving and lifting the unit Only operat
10. Remote Emergency Power OFF EPO Connector This modular jack allows remote emergency shutdown See Communications for details 14 Inverter Operation DIP Switches Behind this removable panel are four DIP Switches that should be set to match your input voltage and input frequency Your input voltage and frequency DIP switch settings MUST match your input Your UPS WILL NOT CONVERT the voltage or frequency 15 Grounding Terminal This terminal connects to a grounding electrode conductor IT Is NOT SAFE TO OPERATE YOUR UPS WITHOUT CONNECTING IT The recommended conductor size is 6 AWG based on the UL 1778 standard Follow all applicable local electrical wiring regulations 16 Stabilizers These supports extend to keep your UPS from rolling or tipping 17 Battery Module Input Connector Use this connector to daisy chain additional battery modules to the first Remove the cover panel for access Refer to the battery module s owner s manual for connection instructions and safety warnings 18 Battery Module Output Cable Use this cable to connect the battery module to the power module or to another battery module when using more than one The power module will not start without a connection to a charged battery module Refer to the battery module owner s manual for connection instructions and safety warnings 19 Tower Mounting For additional stability during tower mounting of BP240V10RT3U External Battery Module you can order Tripp L
11. Turn the AC Input and Bypass AC Input Circuit Breakers OFF Your load will no longer be energized and the LCD display will be dark Operation Normal Conditions continea SELF TESTING When you turn the UPS ON it will perform a brief about 25 second self test See figure below for display sequence Note If starting from battery the BATTERY LED will be lit and the I P and BYPASS LEDs will not The final LCD display in the diagram below appears when the UPS is operating normally under utility supplied AC input power SELECT FREQ OUT XXHz a e 3 Phase SELECT AC INPUT OK SmartOnline 3 Phase UPS System SELECT Smart 3 Phase SELECT BATTERY OK BATTERY FAILURE va T Smar 3 Phase SELECT SELECT CHARGER OK CHARGER FAILURE ri Phase 5 Smar Phase 3 Pha SELECT SELECT AC DC OK AC DC FAILURE s i Smar S 3 Phase 3 Phase SELECT WAIT TESTING INVERTER S e ase SELECT ON INVERTER LOAD XXX X XXKW s ase Operation Normal Conditions ontinueo LCD DISPLAY SELECT SWITCH Momentarily press the SELECT switch on the front panel to browse through different power readings on the LCD Display The LCD Display will show which one of four operational modes your UPS is currently in Normal Economy On Battery or Bypass Also as you press the SELECT switch the LCD Display will browse through load input bypass output and battery conditions NORMAL
12. age if it detects one of the following conditions Note For all conditions the Input Output and Bypass LEDs will be illuminated Condition LCD Display Message Extended Overload gt 150 OVERLOAD XX SHUT DOWN Output Short Circuit SHORT CIRCUIT SHUT DOWN Remote Shutdown Command REMOTE from DB9 interface SHUT DOWN Remote Shutdown Command EMERGENCY STOP from RJ11 interface SHUT DOWN Internal Faults INVERTER TOO LO SHUT DOWN INVERTER TOO HI SHUT DOWN DC BUS HIGH LOW SHUT DOWN OVER TEMPERATURE SHUT DOWN Operation Special Conditions meme OPERATION OF MANUAL BYPASS SWITCH Turn this switch to BYPASS before performing any maintenance on the UPS with the connected load supported Connected equipment will receive filtered AC mains power but will not receive battery power in the event of a blackout SWITCHING UPS TO BYPASS MODE e Turn the ON OFF Switch OFF LCD will read ON BYPASS Turn the Manual Bypass Switch clockwise from NORMAL to BYPASS e Turn the AC Input Circuit Breaker OFF SWITCHING UPS TO NORMAL MODE e Turn the AC Input Circuit Breaker ON e Turn the Manual Bypass Switch counterclockwise from BYPASS back to NORMAL Turn the ON OFF Switch ON Communications RS 232 INTERFACE This female DB9 port connects your UPS via an RS 232 cable to a workstation or server equipped with Tr
13. e your UPS at indoor temperatures between 32 F and 104 F between 0 C and 40 C For best results keep indoor temperatures between 62 F and 84 F between 17 C and 29 C e Leave adequate space around all sides of the UPS for proper ventilation 12 in 30 cm clearance at the rear 4 in 10 cm at sides and on top e Do not install the UPS near magnetic storage media as this may result in data corruption UPS Connection Warnings e The power supply for this unit must be three phase rated in accordance with the equipment nameplate It also must be suitably grounded according to all applicable local electrical wiring regulations Equipment Connection Warnings Do not use Tripp Lite UPS Systems in life support applications in which a malfunction or failure of a Tripp Lite UPS System could cause failure or significantly alter the performance of a life support device e Connect your UPS s Grounding Terminal to a grounding electrode conductor e The UPS system contains its own energy source battery The output terminals may be live even when the UPS is not connected to an AC supply Battery Warnings Your UPS does not require routine maintenance Do not open your UPS for any reason There are no user serviceable parts inside The batteries in your battery module are recyclable Refer to local codes for disposal requirements or if in the USA call 1 800 SAV LEAD 1 800 728 5323 for complete recycling information CAUTION Do
14. een light will illuminate constantly to indicate the UPS s AC DC converter is activated 6 DC AC Inverter LED This green light will illuminate constantly to indicate the UPS s DC AC inverter is activated 7 O P Output LED This green light will illuminate constantly to indicate your UPS is supplying AC power to connected equipment 8 BYPASS LED This green light will illuminate when the UPS is providing filtered mains power without engaging its converter or inverter Connected equipment will not receive battery power in the event of a blackout 9 BATTERY LED This red light will illuminate when the UPS is discharging the battery to provide connected equipment with AC power An alarm will sound which can be cancelled by pressing and holding the SELECT switch for 3 seconds The alarm will be can celled but the LED will remain illuminated Rear Panels OG OOOO Battery Module Rear Panel Power Module Rear Panel 1 Manual Bypass Switch This switch is used in one step of putting the UPS in MANUAL BYPASS mode which mus
15. ipp Lite software The port uses RS 232 communications to report UPS status and power conditions Using this port Tripp Lite software can monitor and manage network power and automatically save open files and shut down equipment during a blackout Contact Tripp Lite Customer Support at 773 869 1234 for information on available SNMP network management and connectivity software and products RS 232 signals and operations include load level battery status battery level operation mode AC input voltage AC output voltage AC input frequency temperature inside unit set shut down delay time enable disable alarm and remote shutdown Hardware Baud Rate 2400 BPS Data Length 8 bits Stop Bit 1 bit Parity NONE Pin assignment Pin2 TXD Transmit Data Pin 3 RXD Receive Data Pin 5 GND Signal Ground Communications continued AS 400 INTERFACE This female DB9 port connects your UPS to an IBM AS 400 computer via the included AS 400 cable The port uses AS 400 Low BATTERY ZZR communications to report UPS status It can be used to allow an AS 400 to automatically save open files and shut down its operat ing system during a blackout AS 400 protocol includes operation BATTERY on inverter operation on AC power supply operation on battery BACK UP and low battery alarm DIRECT MAINS Pin assignment SUPPLY Pin 5 Common Pin 6 Operation on AC power supply Pin 7 Low battery alarm Pin 8 Operation on inverter Pi
16. ite base stands model 2 9USTAND sold separately Installation Using a small tool set the four Inverter Operation DIP Switches located on the rear panel of your UPS to match your input voltage input frequency and desired operational mode Input Voltage Selection DIP Switches 1 amp 2 These DIP switches must be set to match your input voltage Your UPS WILL NOT CONVERT the voltage Input Voltage DIP Switch Position 220V 1 UP amp 2 DOWN 230V 1 DOWN amp 2 UP 240V 1 DOWN amp 2 DOWN Input Frequency Selection DIP Switch 3 Your Input Frequency setting MUST match your input frequency Your UPS WILL NOT CONVERT the frequency Input Frequency DIP Switch Position 50 Hz 3 UP 60 Hz 3 DOWN Installation continued Operational Mode Selection DIP Switch 4 The On Line Mode provides on line operation with zero transfer time The Economy Mode provides line interactive operation for increased efficiency when on line protection is unnecessary thus reducing operating costs without affecting your UPS s output reliability during a power outage Operational Mode DIP Switch Position On Line 4 UP HRA Economy 4 DOWN l UPS LOCATION Move your UPS over short distances u
17. n 9 Operation on battery INVERTER AS 400 INTERFACE TABLE Pin 6 5 Pin 7 5 Pin 8 5 Pin 9 5 Battery OFF x ON ON Low Battery OFF ON ON ON Direct Mains Supply ON OFF OFF OFF Inverter OFF ON 7 Inactive may be in either state DRY CONTACT INTERFACE This female DB9 contact closure port allows your UPS to Pin assignment min 23 3mA send contact closure signals to indicate that it is on battery os back up mode and if its batteries are running low The port LOW BATTERY ae THE REMOTE SHUTDOWN can also receive a remote shutdown signal Sno I SIGNAL FROM EXTERNAL COM NC TI COM NC gt S i DRY CONTACT INTERFACE TABLE N 4 ON UPS Operating Pin 8 3 Pin 1 3 THE SIGNAL ame j Mode FROM COMPUTER i o i Normal OPEN OPEN THE MAXIMUN CAPACITY OF DRY CONTACT AC 250V 3A Back Up CLOSE pone Low Battery CLOSE CLOSE Inactive may be in either state Communications continea REMOTE EMERGENCY POWER OFF EPO This optional feature is only for those applications which require connection to a facility s Emergency Power Off EPO circuit When the power module is connected to this circuit it enables emergency shutdown of the output Using the included cable connect the power mod ule s EPO port to a user supplied remote switch The pin assignments for the EPO port are shown in the following diagram Note if there is a short bet
18. sing its wheels Stabilize the UPS by releasing the stabilizers on each side of the unit NOTE Do not stack the UPS System power module or external battery modules INPUT AND OUTPUT CONNECTION WIRING SELECTION Choose appropriate cabling cabling should have a temperature rating of 70 C and 6 AWG size to connect your UPS to an AC power supply and your equipment to your UPS WIRING CONNECTIONS Connect your wiring to the input and output terminal blocks located on the lower rear panel of your UPS see figure below CAUTION Qualified personnel should follow all procedures prescribed by N E C and other local codes for hardwiring devices to a utility source Ensure that cables are fitted with cable sleeves and are secured by connector clamps Tighten connections with a torque of not less than 35 inch pounds Input Output fo LOWES jojojo ReRESR emEcsEcS R R S T N G N L bypass main main main 220V input R phase Sphase T phase 230V gt 240V NOTE when shipped from the factory bypass input and main R phase terminals GROUND are shorted together CONNECTION TO THE BUILDING CAUTION Observe the appropriate cable connection regulations e g BOUND National Electrical Code NEC in the U S at all times Using cables of L improper size may damage your equipment and cause fire hazards Ground the UPS and the load equipment as shown in the figure Installation continued EXTERNAL BATTERY MODULE CONNECTION required
19. t be done before performing any maintenance on the UPS with the connected load supported See Operation Special Conditions for step by step instruc tions for going into MANUAL BYPASS While this switch is on MANUAL BYPASS connected equipment will receive filtered AC mains power but will not receive battery power in the event of a blackout 2 Input Terminal Block Use these terminals to connect your UPS to the AC main power input Unscrew and remove terminal block plate for access 3 Output Terminal Block Use these terminals to connect your UPS to equipment A plate covering the terminal block must be unscrewed and removed for access 4 External Battery Connector Use this to connect a Tripp Lite battery module to the power module Remove the cover for access The power module will not start without a connection to a charged battery module Refer to the battery module owner s manual for connection instructions and safety warnings 5 Exhaust Fan This cools and ventilates the inside of the UPS 6 AS 400 Interface Port This female DB9 port connects your UPS to an IBM AS 400 computer interface via the AS 400 Cable includ ed It uses AS 400 communications to report UPS status and power conditions Using this port an IBM AS 400 computer can automati cally save open files and shut down its operating system during a blackout See Communications for details 7 Smart RS 232 Interface Port This female DB9 port connects
20. ween pins 2 and 3 2 and 5 4 and 5 or 3 and 4 the UPS system will power off Pin assignment 12V Service Your SmartOnline UPS is covered by the 2 year limited warranty period described below A variety of service contracts is also available from Tripp Lite including start up service contracts and 3 to 5 year SafeSure on site service contracts For more information call Tripp Lite Customer Service at 773 869 1234 Warranty 2 Year Limited Warranty TRIPP LITE warrants its products including batteries to be free from defects in materials and workmanship for a period of two years from the date of initial purchase After 90 days from the date of purchase TRIPP LITE s obligation under this warranty is limited to replacing parts on such defective products To obtain service under this warranty you must call TRIPP LITE or an authorized TRIPP LITE service center Products must be returned to TRIPP LITE or an authorized TRIPP LITE service center with transportation charges pre paid and must be accompanied by a brief description of the problem encountered and proof of date and place of purchase This warranty does not apply to equipment which has been damaged by accident negligence or misapplication or has been altered or modified in any way This warranty applies only to the original purchaser who must have properly registered the product within 10 da
21. y replacement when the UPS is on manual bypass and connected equipment is turned ON your UPS will be unable to provide battery backup in the event of a blackout Do not connect or disconnect the battery modules while the UPS is operating from the battery supply or when the unit is not in bypass mode Control Panel There are two separate UPS system modules a power module and a battery module Familiarize yourself with the location and function of the features on each module before installing and operating your UPS system The power module is the only module which includes front panel features BYPASS I P AC DC DC AC BATTERY SmartOnline 3 Phase UPS System O00 1 ON OFF Switch This momentary rocker switch turns the UPS System s inverter ON and OFF 2 SELECT Button This button performs two functions it allows you to browse through different power readings on the LCD Display by momentarily pressing the button it also allows you to silence the UPS alarm by pressing and holding the button for 3 seconds 3 LCD Display This backlit 16x2 character dot matrix display indicates a wide range of UPS operating conditions and diagnostic data It will illuminate after you have properly completed installation and start up and after the ON OFF Switch is turned ON 4 I P Input LED This green light will illuminate constantly to indicate an AC input supply is present 5 AC DC Converter LED This gr
22. ys of purchase The warranties of all TRIPP LITE surge suppressors are null and void if they have been connected to the output of any UPS system The warranties of all TRIPP LITE UPS Systems are null and void if a surge suppressor has been connected to its output receptacles EXCEPT AS PROVIDED HEREIN TRIPP LITE MAKES NO WARRANTIES EXPRESS OR IMPLIED INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE Some states do not permit limitation or exclusion of implied warranties therefore the aforesaid limitation s or exclusion s may not apply to the purchaser EXCEPT AS PROVIDED ABOVE IN NO EVENT WILL TRIPP LITE BE LIABLE FOR DIRECT INDIRECT SPECIAL INCIDENTAL OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE OF THIS PRODUCT EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE Specifically TRIPP LITE is not liable for any costs such as lost profits or revenue loss of equipment loss of use of equipment loss of software loss of data costs of substitutes claims by third parties or otherwise The policy of TRIPP LITE is one of continuous improvement Specifications are subject to change without notice Specifications The specifications listed below are for Tripp Lite model SU10K3 1X which includes two modules a power module and a battery mod ule The two modules are also sold separately with their own individual model numbers power module individual model SU10K3 1IINTPM and battery module individual model
Download Pdf Manuals
Related Search
Related Contents
Dokument 1 Silverstone ML03 Elevex - Benutzerhandbuch 「取扱説明書」 10B-6シリーズ (20070701-A007) Bosch GHG 600 CE La révolution de bienveillance AGE-DEFYING EYE WRINKLE CORRECTING LASER distante distante circle distante r aida hamlet murano opera Bushnell TRAILSCOUT Nov-00 User's Manual Caldaie murali convenzionali a gas Copyright © All rights reserved.