Home
Bushnell 119415 Digital Camera User Manual
Contents
1. ON OFF SWITCH A cn REDTI THERMOPILE GAS VAIVE OPTIONAL WALL SWITCH THERMOSTAT OR REMOTE BLACK 51 Figure 24 Standing Pilot Ignition Wiring Diagram WIRING DIAGRAM NOTE IF ANY OF THE ORIGINAL WIRE VARIABLE SPEED CONTROL AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED IT MUST BE BLK REPLACED WITH TYPE 105 DEGREE C E JUNCTION BOX RATED WIRE LT BLK H BLOWER RECEPTACLE BLK TEMPERATURE SENSOR SWITCH BLOWER 110 120 VAC JUNCTION p TEMPERATURE A gt SENSOR SWITCH SPEED CONTROL a RHEOSTAT Figure 25 Fan Wiring Diagram For Direct Spark Ignition DSI Wiring Appliance Requirements This appliance requires that 110 120 VAC be wired to the factory installed junction box Maintain correct polarity when wiring the junction box Optional Accessories Optional fan and remote control kits require that 110 120 VAC be wired to the fireplace junction box Remote Wall Switch Position the remote wall switch in the desired position on a wall Run a maximum of 25 feet 7 8 m or less of 16 A W G minimum wire and connect it to the fireplace ON OFF switch pigtails NOTE Electrical wiring must be installed by a licensed electrician CAUTION LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION VERIFY
2. S842 216 mm Y 10 sa 11 5 8 i4 216 11 1416 7 38 5 718 295 281 mm 187 mm 149 mm C u 5 116 _ 858 165 mm 129 gt 220 mm 4 11 1516 8 5 8 303 220 mm DV 48D y 35 3 4 908 mm 8 3 4 222 mm NOTE PIPES OVERLAP 1 3 8 INCHES 34 93 mm AT EACH JOINT Figure 5 D Series Direct Vent Component Specifications 5 inch inner pipe 8 5 8 inch outer pipe HORIZONTAL VENTING H Kit No Max Run DVK 01D DVK 01TRD 24 610 mm 90 DEGREE ELBOWS Figure 6 Corner Installation Models 6000XLS 6000GDVFL are tested and approved to use 45 elbows in corner installations However 90 elbows will result in better performance VENTING WITH ONE 1 90 ELBOW V H 417 MIN 305 mm MAX 610 mm 2 MIN 610 mm 1 22 m 37 MIN 914 mm MAX 1 86 m 4 MIN 1 22 m MAX 2 48 m 407 MAX 12 4 m MAX 2 48 m Figure 7 Venting with One 90 Elbow VENTING WITH TWO 2 909 ELBOWS V 17 MIN 305 mm 2 MIN 610 mm 3 MIN 914 mm 4 MIN 1 22 m 20 MAX 6 2 m H 2 MAX 610 mm 4 MAX 1 22 m 6 MAX 1 86 m 8 MAX 2 48 m 8 MAX 2 48 m Figure 8 Venting with Two 90 Elbows H H 6 MAX 1 86 m 12 MAX 3 72 18 5 58 24
3. Figure 2 Fireplace Dimensions Locations and Space Requirements Clearance Requirements The top back and sides of the fireplace are defined by stand offs Minimum Clearances from the Fireplace to Combustible Materials Glass Back of Sides of Top of Front Floor Fireplace Fireplace Fireplace Ceiling 36 inches 0 1 2 inch 1 2 inch 3 1 2 inches 31 inches 914 mm 13 mm 13 mm 89 mm 787 mm The minimum clearance to a perpendicular wall extending past the face of the fireplace is one inch 25 mm For 6000 Series Models the back of the fireplace may be recessed 21 1 2 inches 546 mm into combustible construction Minimum Clearances from the Vent Pipe to For Horizontal Sections Sections Combustible Materials For Vertical At Wall Firestops 3 inches 75 mm 25 mm 25 mm Step 2 Framing the Fireplace CAUTION The framing headers may rest on the fireplace stand offs BASE FIREPLACE 2 1 2 inches 1 2 inch 63 7 mm 13 mm 05 mm For minimum clearances see the direct vent termination clearance diagrams on pages 19 and 21 in this section Fireplace framing can be built before or after the fireplace is set in place Framing should be positioned to accommodate wall coverings and fireplace facing material The diagram below shows framing reference dimensions MEASURE FIREPLACE DIMENSIONS AND VERIFY FRAMING METHODS AND WALL COVERING DETAILS BEFORE FRAMING CONSTRU
4. the burner Replace old ember material with new dime size and shape pieces of Golden Ember GE 93 and Glowing Ember 050 721 New ember material should be placed alternately on top of the burner a layer of Golden Ember a layer of Glowing Ember and so on Save the remaining ember material and repeat this procedure at your next servicing For more information see Placing Ember Material in the INSTALLERS GUIDE Brush or vacuum the control compartment fireplace logs and burner areas surrounding the logs Make a visual check of your fireplace s flame patterns Make sure the flames are steady not lifting or floating See the picture in Figure 31 The flame sensor DSI or thermopile thermocouple standing pilot tips should be covered with flame See the picture in Figure 32 Inspect the external vent cap on a regular basis to ensure that no debris is interfering with the flow of air Clean as necessary particularly after adding new ember flame colorant material Film deposits on the inside of the glass door should be cleaned off using a household glass cleaner NOTE DO NOT handle or attempt to clean the door when it is hot and DO NOT use abrasive cleaners 32 MAKE SURE THE FLAMES ARE STEADY NOT LIFTING OR FLOATING 3 8 10 mm DSI IGNITION TOO CLOSE TO THE CERAMIC INSULATORS CAN ___ IGNITOR CAUSE NUISANCE gt LOCKOUTS AND ELECTRODE FAILURE
5. 111 BU 4 X 1 2 13 mm Figure 22 Gas Controls Systems Step 6 The Gas Supply Line NOTE Have the gas supply line installed by a qualified service technician in accordance with all building codes NOTE Before the first firing of the fireplace the gas supply line should be purged of any trapped air NOTE Consult local building codes to properly size the gas supply line leading to the 1 2 inch 13 mm hook up at the unit This gas fireplace is designed to accept a 1 2 inch 13 mm gas supply line To install the gas supply line A listed 1 2 inch 13 mm manual shut off valve and a listed flexible gas connector are connected to the 1 2 inch 13 mm inlet of the control valve A 1 8 inch 3 mm plugged tapping accessible for test gauge connection should be provided for in the gas supply line leading to the unit s shut off valve Locate the gas line access hole in the outer casing of the fireplace Open the fireplace lower grille insert the gas supply line through the gas line hole and connect it to the shut off valve When attaching the pipe support the control so that the lines are not bent or torn After the gas line installation is complete use a soap solution to carefully check all gas connections for leaks WARNING DO NOT USE AN OPEN FLAME TO CHECK FOR GAS LEAKS The gas line should be installed by a qualified service technician Step 7 Gas
6. Drill a hole or drive a nail through this centerpoint Check the floor above for any obstructions such as wiring or plumbing runs Reposition the fireplace and vent system if neces sary to accommodate the ceiling joists and or obstructions Cut an 11 X 11 inch 280 mm X 280 mm hole through the ceiling using the centerpoint previously marked Frame the hole with framing lumber the same size as the ceiling joists EXISTING CEILING JOISTS p MEMBERS 7 CEILING Figure 15 11 x 11 Hole and New Framing Members If the area above the ceiling is NOT an attic position and secure the ceiling firestop on the ceiling side of the previously cut and framed hole Figure 16 Ceiling Firestop Ceiling Side 16 17 This shows attic installation 1 Keep insulation away from the vent pipe at least 1 inch 25 mm If the area above the ceiling IS an attic position and secure the firestop on top of the previously framed hole NAILS 4 REQUIRED CEILING FIRESTOP Figure 17 Attic Firestop C Vent Termination For Horizontal Terminations To attach and secure the termination to the last section of horizontal vent Rotate and interlock the ends as described at the beginning of the Installing Vent Components sec tion The termination kit should pass through the wall firestops from the exterior of the building Adjust the termination cap to its final exterior posi t
7. v 1 2 13mm INSULATOR 3 16 5 Figure 32 Pilot Ignitor Flame Patterns 33 parts listed in this INSTALLERS GUIDE may be ordered from an authorized dealer When requesting service or replacement parts for your fireplace please provide the model number and the serial number Standing Pilot Only PART PART DESCRIPTION PART NUMBER Valve LP SRV60 523 Valve NG SRV60 522 Parts and Accessories Thermopile SRV60 512 Thermocouple SRV446 511 Pilot Orifice LP 5 446 517 Pilot Orifice NG 5 446 505 Pilot Assembly LP SRV446 511A Pilot Assembly NG SRV446 510A Pilot Tube SRV446 301 SRV60 307 34 35 DSI Ignition Only PART PART DESCRIPTION PART NUMBER DSI Valve LP SRV77 501 DSI Valve NG SRV77 500 SRV60 599 DSI Module SRV420 592 SRV77 591 SRV422 302 Both Standing Pilot and DSI Ignition PART PART DESCRIPTION PART NUMBER High Temperature Limit Switch SRV92 531 6000GDVFL amp 6000XLS NG SRV446 176A 6000 GDVFL amp 6000XLS LP SRV446 175A Burner Orifice SRV414 800 On Off Rocker Switch 5 60 525 Glass Door Assembly 6000GDVFL GLA 6FL 6000XLS GLA 6XLS Glass Clip Assembly SRV60 135AX Wing Nut SRV60 872 Glass Spring Fastener SRV79 001A GLASS SPECIFICATIONS 6000GDVFL 20 X 34 TEMPERED 6000XLS 20 X 34 CERAMIC 37 Both Standing Pilot and DSI Ignit
8. 7 74 24 MAX 7 74 20 6 2 m CANADA 10 VENTING WITH THREE 3 90 ELBOWS V H H H 1 MIN 305mm 2 MAX 610 mm 5 MAX 1 52 mm 27 MIN 610 4 MAX 1 22 10 MAX 3 1 3 MIN 914 6 MAX 1 86 15 4 65 m 4 MIN 1 22 m 8 2 48 20 6 2 8 2 48 20 MAX 6 2 m NOTE V V MAX 40 12 4 VENTING WITH THREE 3 90 ELBOWS V H 1 MIN 305 mm 2 610 mm 5 MAX 1 52 mm 2 MIN 610 mm 47 MAX 1 22 m 10 MAX 3 1 m 3 MIN 914 mm 6 MAX 1 86 m 15 MAX 4 65 m 4 MIN 1 22 m 8 MAX 2 48 m 20 MAX 6 2 m 20 MAX 6 2 m 8 MAX 2 48 m 20 MAX 6 2 m P Figure 9 Venting with three 90 elbows Apply the stove ce ment Line up the internal beads and rotate the pipe sections clock wise until locked Lock the vent compo nents into place Check the seal on the rope gasket B Installing Vent Components 1 Attach the First Vent Component to the Starting Collars To attach the first vent component to the starting collars of the fireplace Apply a 3 8 inch 9 5 mm bead of stove cement around the 5 inch 127 mm fireplace starting collar Make sure that the fireplace rope gasket supplied with the fireplace seals between the first 8 5 8 inch 219 mm vent component and the outer fireplace wrap Lock the vent c
9. Lowest Discharge Opening Step 4 Positioning Leveling and Securing the Fireplace 1 Place the fireplace into position 2 Level the fireplace from side to side and from front to back 3 Shim the fireplace with non combus tible material such as sheet metal as necessary 4 Secure the fireplace to the framing by nailing or screwing Step 5 The Gas Control Systems The diagram below shows how to properly position level and secure the fireplace NAILING BOTH SIDES Figure 21 Proper Positioning Leveling and Securing of a Fireplace N WARNING THIS UNIT IS NOT FOR USE WITH SOLID FUEL Two types of gas control systems are used with these models Standing Pilot Ignition and Direct Spark Ignition DSI Model 6000XLS has Standing Pilot Ignition only Standing Pilot Ignition System This system includes millivolt control valve standing pilot thermopile thermocouple flame sensor and piezo ignitor WARNING 110 120 VAC MUST NEVER BE CONNECTED TO A CONTROL VALVE INAMILLIVOLT SYSTEM Direct Spark Ignition DSI System This system includes a 24V control valve electronic module transformer and spark ignitor flame sensor N WARNING 110 120 VAC MUST BE WIRED TO THE FIREPLACE JUNCTION BOX IN A DSI SYSTEM IN WARNING DIRECT VENT PROPANE MODELS WITH DSI CONTROL SYSTEMS CANNOT BE USED IN CANADA 25 23 STANDING PILOT DSI IGNITION IGNITOR
10. PROPER 26 OPERATION AFTER SERVICING 27 TRANSFORMER TU REMDTE ELECTRODE BLACK iji Ex BLACK De eH IGNITIUN MODULE HIGH TEMP PURPLE LIMIT SWITCH SOLENOID OPERATED GAS VALVE Bake PURPLE Figure 26 Direct Spark Ignition DSI Wiring Diagram Step 9 Finishing Only non combustible materials may be used to cover the black fireplace front The following diagram shows the minimum vertical and corresponding maximum horizontal dimensions of fireplace mantels or other combustible projections above the top front edge of the fireplace See Figures 2 and 3 for other fireplace clearances TOP FRONT EDGE OF FIREPLACE NOTE ALL DIMENSIONS SHOWN IN INCHES Figure 27 Minimum Vertical and Maximum Horizontal Dimensions of Combustibles above Fireplace WARNING WHEN FINISHING THE FIREPLACE NEVER OBSTRUCT OR MODIFY THE AIR INLET OUTLET GRILLES IN ANY MANNER CAUTION 1 Apply non combus tible facing material to the fireplace sur round Step 10 Installing Trim Logs and Ember Material IF JOINTS BETWEEN THE FINISHED WALLS AND THE FIREPLACE SURROUND TOP AND SIDES ARE SEALED A 300 MINIMUM SEALANT MATERIAL MUST BE USED THESE JOINTS ARE N
11. accessories devices such as a fan wall switch or remote control are desired If the fireplace is to be installed on carpeting or tile or on any combustible material other than wood flooring the fireplace should be installed on a metal or wood panel that extends the full width and depth of the fireplace 26 1 2 672mm 13 1 4 336mm e 21 1 2 546mm VENT f 5 E COLLARS 35 889 25 1 4 641 GAS LINE 31 2 89mm ELECTRICAL 37 3 4 sl ACCESS 1 ACCESS Y t g T e 2 7 8 73mm 4 Ya 36 914mm T le 41 1041mm gt 7 1 4 184mm 4l 7 178mm PERT SE RIGHT SIDE TOP STANDOFFS 2 STANDOFFS___ GLASS DOOR SWITCH GAS LINE 55 LOWER GRILLE ACCESS 4 RATING PLATE LABELS NS ELECTRICAL ACCESS GAS CONTROLS amp SWITCHES Figure 1 Diagram of the6000 Series Step 1 The diagram below shows space and clearance Locating the requirements for locating a fireplace within a room Fireplace 1 MIN 25 mm Y ER Installing the Fireplace MIN 13 mm MODEL A B 6000 42 22 371 8 52 1 2 74 1 4 ALLOWS 1 CLEARANCE TO VENT WITH TYPICAL CORNER FRAMING CONTRUCTION NOTE DIMENSIONS SHOWN IN INCHES
12. aftermarket permanently located manufactured mobile home where not prohibited by local codes This appliance is only for use with the type of gas indicated on the rating plate This appliance is not convertible for use with other gases unless a certified kit is used Printed in U S A Please contact your Heat N Glo Fireplace Copyright 1997 dealer for any questions or concerns For the f t Heat N Gl 1 Heat N Glo Fireplace Products Inc d d 6665 W H 3 please call 612 890 7 5 est ighway 1 gt Savage MN 55378 836 SAFETY AND WARNING INFORMATION gt P gt gt La READ and UNDERSTAND all instructions carefully before starting the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warranty Prior to the first firing of the fireplace READ the Using Your Fireplace section of the Owners Guide DO NOT USE this appliance if any part has been under water Immediately CALL a qualified service technician to inspect the unit and to replace any part of the control system and any gas control which has been underwater THIS UNIT IS NOT FOR USE WITH SOLID FUEL Installation and repair should be PERFORMED by a qualified service person The appliance and venting system should be INSPECTED before initial use and at least annually by a professional service person More frequent cleaning may be required due to e
13. in the United States it may be necessary to decrease the input rating by changing the existing burner orifice to a smaller size Input should be reduced four percent 4 for each 1 000 feet above sea level unless the heating value of the gas has been reduced in which case this general rule will not apply To identify the proper orifice size check with the local gas utility When installing this fireplace at an elevation between 2 000 and 4 500 feet in Canada the input rating must be reduced by ten percent 10 When installing this fireplace at an elevation above 4 500 feet in Canada check with local authorities Consult your local gas utility for assistance in determining the proper orifice for your location Introducing the Heat N Glo Gas Fireplaces Pre installation Preparation Heat N Glo direct vent gas fireplaces are designed to operate with all combustion air siphoned from outside of the building and all exhaust gases expelled to the outside The information contained in this Installers Guide unless noted otherwise applies to all models and gas control systems Gas fireplace diagrams including the dimensions are shown in this section This gas fireplace and its components are tested and safe when installed in accordance with this Installers Guide Report to your dealer any parts damaged in shipment particularly the condition of the glass Do not install any unit with damaged incomplete or substitute pa
14. CTION BEGINS 12 X 12 VENT FRAMING HOLE Framing should be constructed of 2 X 4 lumber or heavier Model 6000 Models 42 22 NOTE DIMENSIONS SHOWN IN INCHES Figure 3 Framing Dimensions Step 3 Installing the Vent System Vent system termination kits 22 7 DVK TVCD DVK 01D DVK 01TRD A Vent System Approvals These appliances are approved to use D series direct vent pipe components and terminations Approved vent system components are labeled for identification NO OTHER VENTING SYSTEMS OR COMPONENTS MAY BE USED Detailed installation instructions are included with each vent termination kit and should be used in conjunction with this Installers Guide The drawing below shows vent system components and terminations Identifying Vent Components The vent systems installed on this gas fireplace may include one two or three 90 elbow assemblies The relationships of vertical rise to horizontal run in vent configurations using 90 elbows MUST BE strictly adhered to The rise to run relationships are shown in the venting drawings and tables Refer to the diagrams on the next several pages Vent system components STORM COLLAR ROOF FLASHING HORIZONTAL CN HORIZONTAL PIPE 4 TERMINATION SUPPORT _ PIPE LENGTH Figure 4 Vent Components and Terminations DV 45D DV 90D v 6 5 32 164 156
15. HE ROOF TOP THESE MINIMUM HEIGHTS ARE NECESSARY IN THE INTEREST OF SAFETY SEE THE FOLLOWING DIAGRAM FOR MINIMUM HEIGHTS PROVIDED THE TERMINATION CAP IS AT LEAST TWO 2 FEET FROM A VERTICAL WALLAND 2 FEET BELOW A HORIZONTAL OVERHANG NOTE This also pertains to vertical vent systems installed on the outside of the building 20 1 Attach the flashing and apply sealant around the edges of the flashing base Attach the storm collar over the flashing joint and apply sealant between the storm collar and vertical pipe To seal the roof hole and to divert rain and snow from the vent system Attach a flashing to the roof using nails and use a non hardening mastic around the edges of the flashing base where it meets the roof Attach a storm collar over the flashing joint to form a water tight seal Place non hardening mastic around the joint between the storm collar and the vertical pipe Slide the termination cap over the end of the vent pipe and rotate the pipe clockwise 1 4 turn TERMINATION CAP Roof Pitch flat to 6 12 6 12 to 7 12 over 7 12 to 8 12 over 8 12 to 9 12 over 9 12 to 10 12 over 10 12 to 11 12 over 11 12 to 12 12 over 12 12 to 14 12 over 14 12 to 16 12 over 16 12 to 18 12 over 18 12 to 20 12 over 20 12 to 21 12 HORIZONTAL OVERHANG VERTICAL WALL V H MIN MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING H min ft Figure 20 Minimum Height from Roof to
16. Heat N Glo Fireplace Installers Guide Models U S Patents 4 793 322 4 875 464 5 000 162 and Patents Pending 6000 GDVFL Canadian Patent 1 297 746 6000 XLS A G A Design Certified CGA Certified and Underwriters Laboratories Listed See Approvals Tabel on Page 1 9 APPROVED 8 WARNING IF THE INFORMATION IN THESE INSTRUCTIONS IS NOT FOLLOWED EXACTLY A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE PERSONAL INJURY OR LOSS OF LIFE Do not store or use gasoline or other flam mable vapors and liquids in the vicinity of this or any other appliance What to do if you smell gas Do not try to light any appliance Do not touch any electrical switch Do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions f you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier READ THIS MANUAL BEFORE INSTALLING OR OPERATING THIS APPLIANCE THIS INSTALLERS GUIDE MUST BE LEFT WITH APPLIANCE FOR FUTURE REFERENCE WARNING IMPROPER INSTALLATION ADJUSTMENT ALTERATION SERVICE OR MAINTENANCE CAN CAUSE INJURY OR PROPERTY DAMAGE REFER TO THIS MANUAL FOR ASSISTANCE OR ADDITIONAL INFORMATION CONSULT A QUALIFIED INSTALLER SERVICE AGENGY OR THE GAS SUPPLIER 1 This appliance may be installed in an
17. OT REQUIRED TO BE SEALED ONLY NON COMBUSTIBLE MATERIAL USING 300 F MINIMUM ADHESIVE IF NEEDED CAN BE APPLIED AS FACING TO THE FIREPLACE SURROUND SEE THE DIAGRAM SHOWN BELOW sTUD 2X4 STANDOFF FINISHED 5 WALL 14 HIGH TEMPERATURE 300 149 MIN SEAL JOINT m a Figure 28 Sealant Material Hearth Extensions A hearth extension may be desirable for aesthetic reasons However ANSI or CAN CGA testing standards do not require hearth extensions for gas fireplace appliances Installing the Trim Combustible materials may be brought up to the specified clearances on the side and top front edges of the fireplace but MUST NEVER overlap onto the front face The joints between the finished wall and the fireplace top and sides can only be sealed with a 300 F 149 C minimum sealant WARNING WHEN FINISHING THE FIREPLACE NEVER OBSTRUCT OR MODIFY THE AIR INLET OUTLET GRILLES IN ANY MANNER Install optional marble and brass trim surround kits as desired Marble brass brick tile or other non combustible materials can be used to cover up the gap between the sheet rock and the fireplace Do not obstruct or modify the air inlet outlet grilles When overlapping on both sides leave enough space so that the bottom grille can be lowered and the trim 28 door removed 29 Positioning Logs If the gas logs have been factory installed they should not need to be posit
18. OUTSIDE WALL VENTING TERMINALS SHALL NOT BE RECESSED INTO A WALL OR SIDING SEE THE FOLLOWING DIAGRAM FOR VENT TERMINATION CLEARANCES 18 Vv VENT TERMINAL 27 zAREA WHERE TERMINAL IS NOT PERMITTED X AIR SUPPLY INLET 12 clearances above grade veranda porch deck or balcony 12 clearances to window door that may be opened 9 U S A clearance to permanently closed window 12 Canada 18 vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet 60 cm from the center line of the terminal clearance to unventilated soffit 9 clearance to outside corner 6 clearance to inside corner 3 ft Canada not to be installed above a gas meter regulator assembly within 3 feet 90 cm horizontally from the center line of the regulator 3 ft U S A clearance to service regulator vent outlet 6 ft Canada 9 0 5 clearance to non mechanical air supply inlet to building 12 Canada or the combustion air inlet to any other appliance 3 ft U S A clearance to a mechanical air supply inlet 6 ft Canada 7 ft clearance above paved sidewalk or a paved driveway located on public property clearance under veranda porch deck or balcony a vent shall not terminate directly above a sidewalk or paved driveway which is located between two sing
19. Pressure Requirements At the gas line access hole use insulation to re pack the space around the gas pipe insulation from the outside of the fireplace and pack the insulation tightly to totally seal be tween the pipe and the outer casing USE A WRENCH ON SHUT OFF VALVE WHEN TIGHTENING GAS LINE GAS LINE NP 2 ACCESS HOLE 0 A E GAS VALVE MANUAL FLEX SHUT OFF CONNECTOR VALVE Figure 23 Gas Supply Line Pressure requirements for Heat N Glo gas fireplaces are shown in the table below Minimum 5 0 inches 11 0 inches Inlet Pressure W C W C Maximum Inlet 14 0 inches 14 0 inches Gas Pressure W C W C Manifold 3 5 inches 10 0 inches Pressure W C W C A one eighth 1 8 inch 3 mm N P T plugged tapping is provided on the outlet side of the gas control for a test gauge connection to measure the manifold pressure To measure inlet pressure provisions must be made to attach a test gauge to a one eighth 1 8 inch 3 mm N P T plugged tapping immediately upstream of the gas supply connection to the fireplace The fireplace and its individual shut off valve must be disconnected from the gas supply piping system during any pressure testing of the system at test pressures in excess of one half 1 2 psig 3 5 kPa The fireplace must be isolated from the gas supply piping system by closing its individual shut off valve during any pressure testing of the gas supp
20. and Codes The Heat N Glo fireplace models discussed in this Installers Guide have been tested to certification standards and listed by the applicable laboratories CERTIFICATION MODEL LABORATORY TYPE STANDARD 6000GDVFL A G A CGA Direct Vent ANSI Z21 50 CGA2 22 and Decorative Approvals Underwriters and Codes Laboratories 6000XLS A GAJCGA Direct Vent ANSI Z21A44 IRZ4l CANI 2 19 and Wall Furnace Underwriters Laboratories Installation Codes The fireplace installation must conform to local codes Before installing the fireplace consult the local building code agency to ensure that you are in compliance with all applicable codes including permits and inspections In the absence of local codes the fireplace installation must conform to the National Fuel Gas Code ANSI Z223 1 in the United States or the CAN CGA B149 Installation Codes in Canada The appliance must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electric Code ANSI NFPA No 70 in the United States or to the CSA C22 1Canadian Electric Code in Canada These models may be installed in a bedroom or bed sitting room in the U S A and Canada High Altitude Installations A G A CGA Design Certified and U L Listed gas fireplaces are tested and approved for elevations from 0 to 2 000 feet in the U S A and from 0 to 4 500 feet in Canada When installing this fireplace at an elevation above 2 000 feet
21. configuration Ensure that each succeeding vent component is securely fitted and locked into the preceding com ponent in the vent system 90 elbows may be installed and rotated to any point around the preceding component s vertical axis If an elbow does not end up in a locked position with the preceding component attach with a minimum of two 2 sheet metal screws 7 11 1110 Figure 11 Adding Venting Components 3 Install Support Brackets For Horizontal Runs The vent system must be supported every five 5 feet of horizontal run by a horizontal pipe support To install support brackets for horizontal runs Place the pipe supports around the vent pipe Nail the pipe supports to the framing members Use wall brackets to support vertical runs every 8 feet 2 4 m above the fireplace flue outlet NOTE For Vertical Runs The vent system must be supported every eight 8 feet 2 4 m above the fireplace flue outlet by wall brackets To install support brackets for vertical runs Attach wall brackets to the vent pipe and secure the wall bracket to the framing members with nails or screws WALL BRACKET WALL STUD 8FT 2 4 m FLUE OUTLET 1INCHMIN 25 4 mm 1 Figure 12 Installing Support Brackets 4 Install Firestops For Horizontal Runs Firestops are REQUIRED on both sides o
22. f a combustible wall through which the vent passes Model DVK 01TRD does not need an exterior firestop on an exterior combustible wall To install firestops for horizontal runs that pass through either interior or exterior walls Cut a 12 inch by 12 inch 305 mm X 305 mm hole through the wall The center of the hole is one 1 inch 25 4 mm above the center of the horizontal vent pipe 14 Position the firestops on both sides of the hole previously cut and secure the firestops with nails or Screws The heat shields of the firestops MUST BE placed towards the top of the hole Continue the vent run through the firestops 1 Cut the 12 inch by 12 inch hole 305 Figure 13 12 x 12 Hole and Vent Pipe 2 Position the firestops TRIM HEAT HEAT SHIELD 3 Place the heat shield oe to the top SHIELD IF TOO 7 SHORT 4 Continue the vent run EXTERIOR FIRESTOP INTERIOR FIRESTOP Figure 14 Heat Shield Interior and Exterior Firestops For Vertical Runs One ceiling firestop is REQUIRED at the hole in each ceiling through which the vent passes To install firestops for vertical runs that pass through ceilings Position a plumb bob directly over the center of the vertical vent component Mark the ceiling to establish the centerpoint of the vent 15 1 Cut the 11 inch by 11 inch hole 2 Add the new framing members This shows a ceiling installation
23. ion Cont eser Log Set Assembly 6000GDVFL LOGS 6FL 6000XLS LOGS CAMP Accessories PART PARTDESCRIPTON DESCRIPTION PART NUMBER Fan Kit GFK 160A Remote Control RC STAT ree SMART STAT RC MLT apt Wall Switch Kit Off White WSK 21 White WSK 21 W
24. ion on the building WARNING THE TERMINATION CAP MUST BE POSITIONED SO THAT THE ARROW IS POINTING UP For roundcap termination kits Use the exterior pipelock hole provided on the round flange of the wall firestop to secure the vent pipe in place For trapezoidal cap termination kits Using screws secure the cap to the exterior wall through the flanges built into the cap Use a high temperature sealant or fiberglass rope gasket to seal between the 8 5 8 inch 219 mm pipe and exterior firestop For round cap termination 1 Secure the 8 5 8 inch ROUND CAP TERMINATION 219 mm pipe using the exterior pipelock PERFORATION CANNOT BE hole on the round INSIDE THE WALL flange of the wall firestop mm 7 1 2 191mm MINIMUM TRAPEZOID CAP TERMINATION For trapezoidal termination 1 Screw the cap to the exterior wall through the flanges in the cap 2 Seal the joint between the pipe and the exterior firestop 184mm Figure 18 Round and Trapezoid Termination Caps WARNING THE BOTTOM OF THE VENT TERMINATION CAP MUST BE A MINIMUM OF 12 INCHES 305 MM ABOVE GROUND LEVEL GRADE THE TOP OF THE CAP MUST BE A MINIMUM OF 18 INCHES 457 MM BELOW COMBUSTIBLE MATERIAL SUCH AS A DECK AND THE SIDE OF THE CAP MUST BE A MINIMUM OF 6 INCHES 152 MM AWAY FROM A PARALLEL
25. ioned If the logs have been packaged separately refer to the installation instructions that accompany the logs Save the log instructions with this manual If sooting occurs the logs might need to be repositioned slightly to avoid excessive flame impingement Placing the Ember Material Two separate bags of ember material are shipped with this gas fireplace The bag labeled Golden Ember GE 93 is flame colorant material The bag labeled Glowing Ember 050 721 is standard glowing ember material To place the ember material Remove the wing nuts and glass clips or tension springs around the glass door Remove the glass door from the unit Cover the top of the burner with a single layer of ember material Then sprinkle GE 93 on top of the burner Save the remaining ember materials for use during fireplace servicing Replace the glass door and a front trim door on the unit see Replacement Parts Section of the manual Replace the wing nut glass clips and tension springs Hand tighten the wing nuts 1 Lift the trim door and out of the unit TENSION W 2 Remove the wing 06 nuts glass clips the glass door from the unit LATCH BRACKET GLASS ASSEMBLY Figure 29 Glass Assembly CAUTION HAND TIGHTEN THE WING NUTS BUT BE CAREFUL NOT TO OVERTIGHTEN 1 Place the ember material onto the top of the burner Figure 30 Placement of the Embe
26. le family dwellings and serves both dwellings only permitted if veranda porch deck or balcony is fully open on a minimum of 2 sides beneath the floor NOTE Local Codes or Regulations may require different clearances Figure 19 Vent Termination Minimum Clearances CAUTION IF EXTERIOR WALLS ARE FINISHED WITH VINYL SIDING IT IS NECESSARY TO INSTALL THE VINYL PROTECTOR KIT VPK DV TO THE TOP OF THE EXTERIOR FIRESTOP FOR ALL ROUND TERMINATION CAPS 19 For Vertical Terminations locate the vent and install the vent sections Locate and mark the vent centerpoint on the under side of the roof and drive a nail through the centerpoint Make the outline of the roof hole around the centerpoint nail The size of the roof hole framing dimensions depend on the pitch of the roof There MUST BE a inch 25 4 mm clearance from the vertical vent pipe to combustible materials Mark the roof hole accordingly Cover the opening of the installed vent pipes Cut and frame the roof hole Use framing lumber the same size as the roof rafters and install the frame securely Flashing anchored to the frame must withstand heavy winds Continue to install concentric vent sections up through the roof hole for inside vent installations or up past the roof line until you reach the appropriate distance above the roof for outside terminations WARNING MAJOR U S BUILDING CODES SPECIFY MINIMUM CHIMNEY AND OR VENT HEIGHT ABOVE T
27. ling the Fireplace 5 Step 1 Locating the Fireplace 5 Step 2 Framing the 1 6 Step 3 Installing the Vent System 7 A Vent System Approvals 7 B Installing Vent Components 13 C Vent Termination 18 Step 4 Positioning Leveling and Securing the Fireplace 23 Step 5 Gas Control Systems 23 Step 6 Gas Supply Line 24 Step 7 Gas Pressure Requirements 25 Step 8 Wiring the Fireplace 26 Step 9 Finishing eene 28 Step 10 Installing Trim Logs and Ember Material esses 29 Installing the Trim eene 29 Positioning the Logs eee 30 Placing the Ember Material 30 Step 11 Before Lighting the Fireplace 32 Step 12 Lighting the Fireplace 32 After the Installation seen 32 Section 4 Maintenance and Servicing 33 Section 5 Replacement Parts and Accessories 35 Replacement 1 35 ade be tree ee Cree e Ca 38 Table of Contents ii Approval Listings Appliance Certification
28. low The glass door assembly MUST be in place and sealed and the trim door assembly MUST be in place on the fireplace before the unit can be placed into safe operation DO NOT OPERATE this appliance with the glass door removed cracked or broken Replacement of the glass door should be performed by a licensed or qualified service person DO NOT strike or slam the glass door The glass door assembly SHALL ONLY be replaced as a complete unit as supplied by the gas fireplace manufacturer NO SUBSTITUTE material may be used DO NOT USE abrasive cleaners on the glass door assembly DO NOT ATTEMPT to clean the glass door when it is hot Turn off the gas before servicing this appliance It is recommended that a qualified service technician perform an appliance check up at the beginning of each heating season Any safety screen or guard removed for servicing must be replaced before operating this appliance Safety and Warning Information i Section 1 Approvals and Codes 1 Approval Listings and 1 Appliance Certification 1 Installation 2 4 8 1 High Altitude Installations 1 Section 2 Getting Started 2 Introducing the Heat N Glo Gas Fireplaces 2 Pre installation Preparation 2 Section 3 Instal
29. ly piping system at test pressures equal to or less than one half 1 2 psig 3 5 kPa 24 Step 8 NOTE Electrical wiring must be installed by a Wiring the licensed electrician Fireplace Caution Disconnect remote controls if you are absent for extended time periods This will prevent accidental fireplace operation For Standing Pilot Ignition Wiring Appliance Requirements This appliance DOES NOT require 110 120 VAC to operate WARNING DO NOT CONNECT 110 120 VAC TO THE GAS CONTROL VALVE OR REMOTE WALLSWITCH OR THE APPLIANCE WILL MALFUNCTION AND THE VALVE WILLBE DESTROYED Optional Accessories Optional fan and remote control kits require that 110 120 VAC be wired to the factory installed junction box before the fireplace is permanently installed Remote Wall Switch Position the remote wall switch in the desired position on a wall Run a maximum of 25 feet 7 8 m or less length of 18 A W G minimum wire and connect it to the fireplace ON OFF switch pigtails WARNING DO NOT CONNECT 110 120 VAC TO THE REMOTE WALL SWITCH OR THE CONTROL VALVE WILL BE DESTROYED CAUTION LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION VERIFY PROPER OPERATION AFTER SERVICING BLACK L1 2 BLACK L2 2 HI TEMP LIMIT SWITCH 71 THERMOCOUPLE 5 BLACK 52 3116 PIGGYBACK CONNECTOR 7 REMOTE SWITCH PIGTAIL
30. omponents into place by sliding the concentric pipe sections with four 4 equally spaced interior beads into the fireplace collar or previously installed component end with four 4 equally spaced indented sections When the internal beads of each 8 5 8 inch 219 mm outer pipe line up rotate the pipe section clockwise about one quarter 1 4 turn The vent pipe is now locked together The first 90 elbow installed in the vent system of a rear venting fireplace MUST BE in a vertical posi tion STARTING COLLAR 4 BEAD 3 8 INCH 9 5 mm VENT COMPONENT vi l 1 INCH 25 4 mm Figure 10 Attaching the First Vent Component to the Starting Collars WARNING A 3 8 INCH 9 5 MM BEAD OF STOVE CEMENT MUST BE PLACED AROUND THE 5 INCH 127 MM FIREPLACE STARTING COLLAR BEFORE ATTACHING THE FIRST VENT COMPONENT FAILURE TO SEAL THIS JOINT MAY CAUSE THE FIREPLACE TO OPERATE IMPROPERLY SEE THE 12 DIAGRAM 13 Continue adding vent components locking each succeeding component into place WARNING ENSURE THAT THE FIBERGLASS ROPE GASKET SUPPLIED WITH THE FIREPLACE SEALS BETWEEN THE FIRST VENT COMPONENT AND THE OUTER FIREPLACE WRAP If the installation is for a termination cap attached directly to the fireplace skip to the sections Install Firestops and Vent Termination 2 Continue Adding Vent Components To continue adding vent components in accordance with the pre planned vent system
31. ou ve checked the fireplace for gas leaks you know the vent system is unobstructed and you ve checked for faulty components Now you re ready to light the fireplace IN WARNING PLEASE REFER TO THE USER S MANUAL FOR ALL CAUTIONS SAFETY AND WARNING INFORMATION PERTAINING TO THE LIGHTING AND OPERATION OF THE FIREPLACE LEAVE THIS INSTALLATION MANUAL WITH THE APPLIANCE FOR FUTURE REFERENCE Firepla ce Although the frequency of your fireplace servicing and Maintenance maintenance will depend on use and the type of installation you should have a qualified service technician perform an appliance check up at the beginning of each heating season See the table below for specific guidelines regarding each fireplace maintenance task IMPORTANT TURN OFF THE GAS BEFORE SERVICING YOUR FIREPLACE Maintaining Type of and Fireplace Fireplace Maintenance Task To ipi Maintenance Frequency Be Completed Servicing Your Replacing Once annually Qualified Brush away loose ember material near Fireplace Old Ember Material Cleaning Burner amp Controls Checking Flame Patterns Flame Height Checking Vent System Cleaning Glass Door during the annual check up Once annually Periodically Before initial use and at least annually thereafter more frequently if possible As necessary Service Technician Qualified Service Technician Qualified Service Technician Qualified Service Technician Owner Homeowne
32. r Material CAUTION IT IS STRONGLY RECOMMENDED THAT TRIM DOORS WITH OPTIIONAL MESH SCREENS BE INSTALLED ON PROPANE MODELS 30 31 Step 11 Before Lighting the Fireplace Step 12 Lighting the Fireplace After the Installation Before lighting the fireplace be sure to do the following Review safety warnings and cautions Read the Safety and Warning Information section at the beginning of this nstallers Guide Double check for gas leaks Before lighting the fireplace double check the unit for possible gas leaks Double check vent terminations and front grilles for obstructions Before lighting the fireplace double check the unit for possible obstructions that could be blocking the vent terminations or the front grilles Double check for faulty components Any component that is found to be faulty MUST BE replaced with an approved component Tampering with the fireplace components is DANGEROUS and voids all warranties A small amount of air will be in the gas supply lines When first lighting the fireplace it will take a few minutes for the lines to purge themselves of this air Once the purging is complete the fireplace will light and will operate normally Subsequent lightings of the fireplace will not require this purging of air from the gas supply lines unless the gas valve has been turned to the OFF position in which case the air would have to be purged You ve reviewed all safety warnings y
33. rts The vent system components and trim doors are shipped in separate packages The gas logs are factory installed Model 6000GDVFL and are packaged separately and must be field installed Model 6000XLS Read all of the instructions before starting the installation Follow these instructions carefully during the installation to ensure maximum safety and benefit Failure to follow these instructions will void the owner s warranty and may present a fire hazard The Heat N Glo Fireplace Products Inc Warranty will be voided by and Heat N Glo Fireplace Products Inc disclaims any responsibility for the following actions Installation of any damaged fireplace or vent system component Modification of the fireplace or direct vent system Installation other than as instructed by Heat N Glo Fireplace Products Inc Improper positioning of the gas logs or the glass door nstallation and or use of any component part not manufactured and approved by Heat N Glo Fire place Products Inc not withstanding any indepen dent testing laboratory or other party approval of such component part or accessory ANY SUCH ACTION MAY POSSIBLY CAUSE A FIRE HAZARD Getting Started When planning fireplace installation it s necessary to determine Where the unit is to be installed The vent system configuration to be used Gas supply piping Electrical wiring Framing and finishing details Whether optional
34. xcessive lint from carpeting bedding material etc It is IMPERATIVE that the unit s control compartment burners and circulating air passageways BE KEPT CLEAN to provide for adequate combustion and ventilation air Always KEEP the appliance clear and free from combustible materials gasoline and other flammable vapors and liquids NEVER OBSTRUCT the flow of combustion and ventilation air Keep the front of the appliance CLEAR of all obstacles and materials for sevicing and proper operations Due to the high temperature the appliance should be LOCATED out of traffic areas and away from furniture and draperies Clothing or flammable material SHOULD NOT BE PLACED or near the appliance Children and adults should be ALERTED to the hazards of high surface temperature and should STAY AWAY to avoid burns or clothing ignition Young children should be CAREFULLY SUPERVISED when they are in the same room as the appliance These units MUST use one of the vent systems described in the Installing the Fireplace section of the Installers Guide NO OTHER vent systems or components MAY USED This gas fireplace and vent assembly MUST be vented directly to the outside and MUST NEVER be attached to a chimney serving a separate solid fuel burning appliance Each gas appliance MUST USE a separate vent system Common vent systems are PROHIBITED INSPECT the external vent cap on a regular basis to make sure that no debris is interfering with the air f
Download Pdf Manuals
Related Search
Related Contents
here Laney Amplification LG12 User's Manual Mini Video Speaker User`s Manual König KN-DVBT-IN52 television antenna Harman Kardon HK6850 User's Manual DELL B1265dfw August 1980 Ficha Técnica PINTURA ACRILICA SUELOS Manual - B&B Electronics Copyright © All rights reserved.
Failed to retrieve file